MCGG Manual Relaypdf
MCGG Manual Relaypdf
                                                        2
Models available                            MCGG 53                                   MCGG 82
                                            Two phase overcurrent (with               Three phase overcurrent plus earth
MCGG 22                                     polyphase measurement) plus earth         fault with instantaneous elements.
Single phase overcurrent with               fault with instantaneous elements.
instantaneous element.                                                                Associated publications:
                                            MCGG 62
MCGG 42                                                                               Midos System R6001
                                            Three phase overcurrent with
Two phase overcurrent with                                                            Directional Relay R6003
                                            instantaneous elements.
instantaneous elements.
                                            MCGG 63
MCGG 52                                     Three phase overcurrent (with
Two phase overcurrent plus earth            polyphase measurement), with
fault with instantaneous elements.          instantaneous element.
                                                                 3
Each measuring board has a built-in           Switch position               Operating
‘power off’ memory feature for the           (0)          (1)               characteristic
time delayed and instantaneous LED                         ●
indicators.                                                ●                Trip test
                                                           ●
Power to each measuring board
                                              ●
may be tested whilst the relay is in                                                                       t=      0.14
                                              ●                             Standard inverse                                      sec SI
service, without affecting the current        ●                                                                 (I0.02 – 1)
measurement. A test mode is also                           ●
                                                                                                           t=      13.5
available to carry out a trip test on         ●                             Very inverse                                         sec VI
                                              ●                                                                   (I – 1)
the output relays. During this test,
current measurement is inhibited.             ●
                                                                                                                    80
                                                           ●                Extremely inverse              t=                     sec EI
When required, directional control            ●                                                                  (I2 – 1)
can be exercised over the relay by                         ●
connecting an output contact from                                                                                  120
                                                           ●                Long time earth fault t =                             sec LT
direction relay type METI to the              ●                                                                   (I – 1)
terminals provided.                           ●
                                              ●                             Definite time 2 seconds                                  D2
Separate output contacts, capable                          ●
of circuit breaker tripping, are                           ●
provided for time delayed phase               ●                             Definite time 4 seconds                                  D4
faults, instantaneous phase faults,                        ●
time delayed earth fault and                  ●
instantaneous earth fault operations.                      ●                Definite time 8 seconds                                  D8
                                                           ●
                                                             4
Current setting                                                        Trip test
                                                                       Current measurement is inhibited by
Time delayed element
                                                                       setting the curve selection switches
The current setting control is marked                                  to 111. This causes all three LEDs to
Is = Σ x In where Is is the current                                    flash once per second. If the reset
setting in amps, Σ is the sum of all                                   push button is then pressed for
the switch positions and In is the                                     approximately six seconds, both
relay rated current in amps.                                           output relays associated with that
                                                                       measuring board will operate.
Each measuring board provides a
setting range of 0.05 x In to 2.4 x                                    Power supply healthy test
In in steps of 0.05 x In.
                                                                       If, whilst the relay is in service, the
Instantaneous element                                                  reset button is pressed, all the LEDs
                                                                       are illuminated, indicating that there
The setting control of the
                                                                       is power to the measuring boards.
instantaneous element is marked
                                                                       The LEDs are reset on releasing the
Iinst = Σ x Is where Σ is the sum of
                                                                       push button. During this test, normal
the switch positions and Is is the
                                                                       current measurement is not
time delayed element setting.
                                                                       inhibited.
When all switches are set to the left
(at zero), or when the lowest switch
is set to infinity regardless of the
                                                                                                                                                                                       Figure 2: Type MCGG 22 nameplate
positions of the other five switches,
the instantaneous feature is
rendered inoperable. The range of
adjustment of finite settings is from
1x to 31x in unity steps.
                                                                                  A
                            P2                   P1
                        A
                             S2            S1
                        B
                                                                        C                    B
                        C                                                   Phase rotation
                                                         Directional
                                                           control
                                                            PhA                                                                                                 Indicator
                                                                       24                                     TMS           Inst            Curve                 reset
                                                                                                             setting      setting          selection
                  (See Note 4)                                         23
                                                       (See Note 2)    27                                                                        Time delayed trip
                                                                                                                          µC
                                                                  IA                                           Is                                  Inst. trip
                                                                                                                          PhA                                                                RL1–1    7
                                                                       28
                                                                                                                                                                                                      6
                                                                                                 Input      Current                                                                                        Phase fault
                                                                                                 circuit    setting                 I>Is                                                              5
                                                                                                                                                                                                           time delayed
                                                                                                   Ph         Ph                                                                             RL1–2    2    trip output
                                                                                                                                                                                 RL1                       contacts
           Case earth                                                                                                                                                             2                   1
                                                                       13
           1       2                                            +VE                      Power                                                                              Output
                                                           Vx          14
                                                                                         supply
                                                                                                                                                                            circuits         RL2–1    8
                                                                –VE                                                                                                            Ph
           5       6                                                   26                circuits                                                                                                     10
           7       8                                                                                                                                                             RL2                  9    Phase fault
                                                                                                                                                                                  2                        instantaneous
           9      10                                                                                                                                                                                       trip output
                                                                                                                                                                                             RL2–2    16
                                                                               Case earth connection                                                                                                       contacts
           13     14              (See Note 3)                                                                                                                                                        15
           15     16
                                                                                                                             MCGG 22
           23     24                   Notes:
                  26                   1. (a)               CT shorting links make                         2. When directional control is required the contacts
           27     28                                        before (b) and (c) disconnect.                    of the directional relays should be connected as shown.
                                           (b)        Short terminals break before (c).                       Contacts must close to inhibit overcurrent relay.
                                           (c)        Long terminals                                       3. Earthing connections (CTs) are typical only.
     Module terminal block
       viewed from rear                                                                                    4. CT connections are typical only.
                    Figure 3: Application diagram (10 MCGG 22 02): static modular overcurent relay type MCGG 22.
                              Single phase with instantaneous element.
                                                                                                                    5
              A                         P2                         P1
                                   A
                                         S2                   S1
                                   B                                          Directional                                                                                                  Indicator
                                                                                                                                  TMS           Inst              Curve                      reset
                                                                                control                                          setting      setting            selection
                                   C                                             PhA
                                                                                               49
    C                 B
        Phase rotation (See Note 4)                                                            50
                                                                                                                                                                                                            RL1
                                                                           (See Note 2)        21                                                                      Time delayed trip                     2
                                                                                                                                              µC
                                                                                          IA                                       Is         PhA
                                                                                                                                                                         Inst. trip                    Output             RL1–1          35
                                                                                               22                                                                                                      circuits
                                                                                                                                                                                                          Ph                             33
                                                                                               23                    Input      Current                                                                                                       Phase fault
                                                                                                                     circuit    setting                 I> Is                                                                            34
                                                                                                                                                                                                             RL2                              time delayed
                                                                                                                       Ph         Ph                                                                                      RL1–2          29   trip output
                                                                                                                                                                                                              2
                                                                                               24                                                                                                                                             contacts
                                                                                 Directional                                                                                                                                             30
                                                                                   control
                                                                                    PhC                                           TMS           Inst              Curve
                                                                                               45                                setting      setting            selection
                                                                                                                                                                                                                          RL2–1          36
                                                                                               46                                                                                                                                        37
        Case earth                                                                                                                                                       Time                                                                 Phase fault
                                                                                               25                                                                        delayed trip                                                    38
                                                                                                                                               µC                                                                                             instantaneous
        1         2       29       30                                                     IC                                                                               Inst. trip                                     RL2–2          41   trip output
                                                                                                                                   Is         PhC
                                                                                                                                                                                                                                              contacts
        3         4                                                                            26
        5         6       33       34                                                                                                                                                                                                    42
                                                                                               27                    Input      Current
        7         8       35       36                                                                                circuit    setting                 I> Is
        9        10       37       38                                                                                  Ph         Ph
        11       12                                                                            28
                                                                                               13
        13       14       41       42                                                   +VE                      Power
        15       16                                                               Vx    –VE
                                                                                               14
                                                                                                                 supply
        17       18       45       46                                                          1                 circuits
        19       20       47       48
                                                                                                                                                 MCGG 42
        21       22       49       50                                                               Case earth connection
                                                  (See Note 3)
        23       24
                                                                        Notes:
        25       26
                                                                        1. (a)                CT shorting links make                2. When directional control is required the contacts
        27       28                                                                           before (b) and (c) disconnect.           of the directional relays should be connected as shown.
                                                                           (b)          Short terminals break before (c).              Contacts must close to inhibit overcurrent relay.
         Module terminal block                                             (c)          Long terminals                              3. Earthing connections are typical only.
           viewed from rear
    (with integral case earth strap)                                                                                                4. CT connections are typical only.
                      Figure 4: Application diagram (10 MCGG 42 03): static modular overcurent relay type MCGG 42.
                                Two phase with instantaneous element.
                                        P2                         P1
                               A
                                             S2               S1             Directional                                                                                                   Indicator
             A                                                                 control
                               B                                                                                                                                                             reset
                                                                                PhA                                               TMS           Inst              Curve
                               C                                                               49                                setting      setting            selection
                                                                                               50                                                                                                                  RL1
C                     B                                                    (See Note 2)        21                                                                      Time delayed trip                            2
                               (See Note 4)                                                                                                                                                                               RL1–1          35
    Phase rotation                                                                                                                            µC
                                                                                         IA                                                                              Inst. trip
                                                                                                                                   Is         PhA                                                      Output                            33
                                                                                               22                                                                                                      circuits                               Phase fault
                                                                                                                     Input      Current                                                                   Ph                             34   time delayed
                                                                                               23                    circuit     setting                I >I s                                                     RL2                        trip output
                                                                                                                                                                                                                          RL1–2          29
                                                                                                                       Ph          Ph                                                                               2                         contacts
                                                                             Directional
                                                                               control         24                                                                                                                                        30
                                                                                PhC                                               TMS           Inst              Curve
                                                                                               45
                                                                                                                                 setting      setting            selection                                                RL2–1          36
                                                                                               46
                                                                                                                                                                                                                                         37
                                                                                               25                                                                      Time
                                                                                                                                                                       delayed trip                                                      38   Phase fault
                                                                                                                                               µC                                                                                             instantaneous
                                                                                          IC                                       Is         PhC
                                                                                                                                                                         Inst. trip
                                                                                                                                                                                                                          RL2–2          42   trip output
                                                                                               26                                                                                                                                             contacts
                                                                                                                     Input      Current                                                                                                  41
                                                                                                                     circuit    setting                 I >I s
        Case earth                                                                                                     Ph         Ph
                                                                             Directional                                                                                                                                  RL3–1          7
        1         2   29           30                                          control                                                                                                                                                   6
        3         4                                                              E/F                                              TMS           Inst              Curve                                                                       Earth fault
                                                                                               43                                                                                                                                        5
        5         6   33           34                                                                                            setting      setting            selection                                                                    time delayed
                                                                                               44                                                                                                                  RL3    RL3–2          2    trip output
        7         8   35           36
                                                                                               27                                                                                                                   2                         contacts
        9        10   37           38                                                                                                                                  Time delayed trip
                                                                                                                                               µC                                                                                        1
        11       12                                                                     E/F                                                                              Inst. trip                    Output
                                                                                                                                   Is                                                                  circuits
        13       14       41       42                                                          28                                                                                                                         RL4–1          8
        15       16   43           44                                                                                Input      Current
                                                                                               13                    circuit    setting                 I >I s                                                     RL4                   10
        17       18   45           46                                                  +VE            Power                                                                                                         2                         Earth fault
                                                                                  Vx           14                                                                                                                                        9
        19       20   47           48                                                  –VE            supply                                                                                                                                  instantaneous
        21       22   49           50                                                          17     circuits                                                                                                            RL4–2          16   trip output
                                                                                                                                                                                                                                              contacts
        23       24
                                                                                                                                                                                                                                         15
        25       26                                                                                 Case earth connection                                        MCGG 52
                                                   (See Note 3)
        27       28
                                                    Notes:
                                                    1. (a)                 CT shorting links make                  2. When directional control is required the contacts                      3. Earthing connections are typical only.
         Module terminal block                                             before (b) and (c) disconnect.             of the directional relays should be connected as shown.                4. CT connections are typical only.
           viewed from rear
    (with integral case earth strap)                    (b)         Short terminals break before (c).                 Contacts must close to inhibit overcurrent relay.
                                                        (c)         Long terminals
                      Figure 5: Application diagram (10 MCGG 52 03): static modular overcurent relay type MCGG 52.
                                Two phase plus earth fault with instantaneous elements.
                                                                                                                                        6
                                                      P2                              P1
                                           A
                                                           S2                   S1             Directional                                                                                                            Indicator
                   A                                                                             control
                                           B                                                                                                                                                                            reset
                                                                                                  PhA                                                      TMS           Inst              Curve
                                           C                                                                        49                                    setting      setting            selection
                                                                                                                    50                                                                                                                       RL1
    C                             B                                                          (See Note 2)           21                                                                           Time delayed trip                            2
                                           (See Note 4)                                                                                                                                                                                              RL1–1            35
          Phase rotation                                                                                                                                                  µC
                                                                                                          IA                                                                                       Inst. trip
                                                                                                                                                              Is          Ph                                                      Output                              33
                                                                                                                    22                                                                                                            circuits                                   Phase fault
                                                                                                                                                                                                                                     Ph                               34     time delayed
                                                                                                                    23                                   Current                 I >I s                                                      RL2
                                                                                                                                                          setting                                                                                    RL1–2            29     trip output
                                                                                                                                                            Ph                                                                                2                              contacts
                                                                                               Directional          24                                                                                                                                                30
                                                                                                 control
                                                                                                  PhC                                                                                                                                                RL2–1            36
                                                                                                                    45
                                                                                                                    46                                                                                                                                                37
                                                                                                                                                                                                                                                                      38     Phase fault
                                                                                                                    25
                                                                                                                                                                                                                                                                             instantaneous
                                                                                                           IC                                                                                                                                        RL2–2            41     trip output
                                                                                                                                                                                                                                                                             contacts
                                                                                                                    26
                                                                                                                                                                                                                                                                      42
           Case earth
                                                                                                                                            Input
                                                                                                                                            circuit
                                                                                               Directional                                    Ph                                                                                                     RL3–1            7
           1             2            29         30                                              control                                                                                                                                                              6
           3             4                                                                         E/F                                                     TMS           Inst              Curve                                                                             Earth fault
                                                                                                                    43                                                                                                                                                5
                                                                                                                                                          setting      setting            selection                                                                          time delayed
           5             6            33         34
                                                                                                                    44                                                                                                                       RL3     RL3–2            2      trip output
           7             8            35         36
                                                                                                                    27                                                                                                                        2                              contacts
           9            10            37         38                                                                                                                                              Time delayed trip
                                                                                                                                                                          µC                                                                                          1
           11           12                                                                                E/F                                                                                      Inst. trip                     Output
                                                                                                                                                              Is                                                                  circuits
           13           14            41         42                                                                 28                                                                                                                               RL4–1            8
           15           16            43         44                                                                 13                      Input       Current                  I >I s                                                      RL4
                                                                                                      +VE                     Power         circuit     setting                                                                                                       10
           17           18            45         46
                                                                                                 Vx                 14                                                                                                                        2                              Earth fault
           19           20            47         48                                                   –VE                     supply                                                                                                                                  9
                                                                                                                    17                                                                                                                                                       instantaneous
                                                                                                                              circuits                                                                                                               RL4–2            16     trip output
           21           22            49         50
                                                                                                                                                                                                                                                                             contacts
           23           24
                                                                                                                           Case earth connection                                                                                                                      15
           25           26                                        (See Note 3)
                                                                                                                                                                                          MCGG 53
           27           28                                         Notes:
                                                                   1. (a)                     CT shorting links make                      2. When directional control is required the contacts                          3. Earthing connections are typical only.
                                                                                              before (b) and (c) disconnect.                 of the directional relays should be connected as shown.                    4. CT connections are typical only.
            Module terminal block
               viewed from rear                                           (b)          Short terminals break before (c).                     Contacts must close to inhibit overcurrent relay.
        (with integral case earth strap                                   (c)          Long terminals
                             Figure 6: Application diagram (10 MCGG 53 02): static modular overcurent relay type MCGG 53.
                                       Two phase (with polyphase measurement), plus earth fault with instantaneous elements.
                                                 P2                              P1
                                      A
                                                      S2                   S1               Directional                                                                                                          Indicator
               A                                                                              control
                                      B                                                                                                                                                                            reset
                                                                                               PhA                                                      TMS           Inst            Curve
                                      C                                                                        49                                      setting      setting          selection
                                                                                                               50
                                                                                                               26
      13           14            41         42                                                                                           Input        Current
                                                                                                               13                        circuit      setting                 I>Is
                                                                                                   +VE                     Power           Ph           Ph
                              45            46                                                Vx               14
                                                                                                    –VE                    supply
                              47            48                                                                 1           circuits
      21           22         49            50
      23           24                                                                                                    Case earth connection
      25           26                                           (See Note 3)                                                                                                         MCGG 62
                                                                Notes:
      27           28
                                                                1. (a)                      CT shorting links make         2. When directional control is required the contacts                                      3. Earthing connections are typical only.
                                                                                            before (b) and (c) disconnect.    of the directional relays should be connected as shown.
         Module terminal block                                                                                                                                                                                       4. CT connections are typical only.
                                                                    (b)              Short terminals break before (c).        Contacts must close to inhibit overcurrent relay.
           viewed from rear
    (with integral case earth strap)                                (c)              Long terminals
                             Figure 7: Application diagram (10 MCGG 62 03): static modular overcurent relay type MCGG 62.
                                       Three phase with instantaneous element.
                                                                                                                                                              7
                                                        P2                       P1
                                           A
                                                             S2             S1               Directional                                                                                                   Indicator
                   A                                                                           control
                                           B                                                                                                                                                                 reset
                                                                                                PhA                                               TMS            Inst             Curve
                                           C                                                                 49                                  setting       setting           selection
                                                                                                             50                                                                                                                    RL1
 C                                B                                                        (See Note 2)      21                                                                        Time delayed trip                            2
                                           (See Note 4)                                                                                                                                                                                   RL1–1          35
      Phase rotation                                                                                                                                           µC
                                                                                                       IA                                                                                Inst. trip
                                                                                                                                                    Is         Ph                                                      Output                            33
                                                                                                             22                                                                                                        circuits                               Phase fault
                                                                                                                                                                                                                          Ph                             34   time delayed
                                                                                             Directional                                        Current                  I> Is                                                     RL2
                                                                                                                                                 setting                                                                                  RL1–2               trip output
                                                                                               control                                                                                                                                                   29
                                                                                                                                                                                                                                                              contacts
                                                                                                PhB                                                Ph                                                                               2
                                                                                                             47
                                                                                                                                                                                                                                                         30
                                                                                                             48
                                                                                                             23                                                                                                                           RL2–1          36
                                                                                                        IB                                                                                                                                               37
                                                                                                                                                                                                                                                         38   Phase fault
                                                                                                             24                                                                                                                                               instantaneous
                                                                                             Directional                                                                                                                                  RL2–2          41   trip output
                                                                                               control                                                                                                                                                        contacts
                                                                                                PhC                                                                                                                                                      42
                                                                                                             45
        Case earth
                                                                                                             46
          1              2            29           30                                                        25
          3              4                                                                              IC
          5              6            33           34
                                                                                                             26
          7              8            35           36                                                                            Input
                                                                                                             27
          9             10            37           38                                                                            circuit
          11            12
          13            14            41           42                                                        28
          15            16                                                                                   13
                                                                                                      +VE           Power
          17            18            45           46                                          Vx            14
                                                                                                      –VE           supply
          19            20            47           48                                                        1      circuits
          21            22            49           50
          23            24                                                                                        Case earth connection
          25            26                                        (See Note 3)                                                                                                   MCGG 63
          27            28                                        Notes:
                                                                  1. (a)                     CT shorting links make            2. When directional control is required the contacts                          3. Earthing connections are typical only.
                                                                                             before (b) and (c) disconnect.       of the directional relays should be connected as shown.                    4. CT connections are typical only.
          Module terminal block
            viewed from rear                                          (b)             Short terminals break before (c).           Contacts must close to inhibit overcurrent relay.
     (with integral case earth strap)                                 (c)             Long terminals
                             Figure 8: Application diagram (10 MCGG 63 02): static modular overcurent relay type MCGG 63.
                                       Three phase (with polyphase measurement) with instantaneous element.
               A                                        P2                       P1
                                            A                                                 Directional
                                                         S2           S1                        control                                                                                                    Indicator
                                               B                                                                                                                                                             reset
                                                                                                 PhA
                                            C                                                                49                                    TMS           Inst             Curve
                                                                                                                                                  setting      setting           selection
C                            B              N                                                                50                                                                                                                    RL1
    Phase rotation                                                                          (See Note 2) 21                                                                                                                         2
                                                                                                                                                                                       Time delayed trip
                                  (See Note 4)                                                                                                                 µC                                                                         RL1–1          35
                                                                                                       IA                                                                                    Inst. trip
                                                                                                                                                    Is         PhA                                                     Output
                                                                                                                                                                                                                                                         33
                                                                                                             22                                                                                                        circuits
                                                                                                                               Input circuit Current setting                                                              Ph                                  Phase fault
                                                                                                                                                                         I>Is                                                                            34   time delayed
                                                                                                                                   Ph             Ph                                                                               RL2
                                                                                              Directional                                                                                                                                                     trip output
                                                                                                control                                                                                                                             2     RL1–2          29
                                                                                                                                                                                                                                                              contacts
                                                                                                 PhB
    Case earth                                                                                               47                                    TMS           Inst             Curve                                                                  30
                                                                                                                                                  setting      setting           selection
                                                                                                             48
    1               2            29         30
                                                                                                                                                                                                                                          RL2–1          36
    3               4                                                                                        23                                                                        Time delayed trip
                                                                                                                                                               µC                                                                                        37
    5               6            33         34                                                          IB                                                                                   Inst. trip
                                                                                                                                                    Is         PhB                                                                                            Phase fault
    7               8                                                                                                                                                                                                                                    38
                                 35         36                                                               24                                                                                                                                               instantaneous
    9              10            37         38                                                                                 Input circuit Current setting                                                                              RL2–2          41   trip output
                                                                                                                                   Ph             Ph                     I>Is                                                                                 contacts
    11             12                                                                         Directional
     13            14            41         42
                                                                                                control                                                                                                                                                  42
                                                                                              phase PhC
    15             16            43         44                                                               45                                    TMS           Inst             Curve
                                                                                                                                                  setting      setting           selection                                                RL3–1          7
    17             18            45         46                                                               46
                                                                                                                                                                                                                                                         6
    19             20            47         48                                                               25                                                                        Time delayed trip                                                      Earth fault
    21             22            49         50                                                                                                                  µC                                                                                       5
                                                                                                                                                                                                                                                              time delayed
                                                                                                       IC                                                                                    Inst. trip
                                                                                                                                                    Is         PhC
                                                                                                                                                                                                                                          RL3–2          2    trip output
    23             24                                                                                        26
                                                                                                                               Input circuit Current setting
                                                                                                                                                                                                                                                              contacts
    25             26                                                                                                              Ph             Ph                     I>Is                                                                            1
    27             28                                                                        Directional
                                                                                             control E/F                                                                                                                                  RL4–1          8
                                                                                                             43                                    TMS           Inst             Curve                                            RL3
      Module terminal block                                                                                                                       setting      setting           selection                                                               10
                                                                                                             44                                                                                                                     2
        viewed from rear                                                                                                                                                                                                                                      Earth fault
 (with integral case earth strap)                                                                                                                                                                                                                        9
                                                                                                             27                                                                        Time delayed trip                Output                                instantaneous
                                                                                                                                                                µC                                                      circuits          RL4–2          16   trip output
                                                                                                                                                                                             Inst. trip
                                                                                                                                                    Is          E/F                                                       E/F                                 contacts
Notes:                                                                                                       28                                                                                                                    RL4
                                                                                                                               Input circuit Current setting                                                                                             15
1. (a)                           CT shorting links make                                                      13                    E/F            E/F                    I>Is                                                       2
                                 before (b) and (c) disconnect.                                       +VE           Power                                                             MCGG 82
                                                                                                Vx           14
     (b)                 Short terminals break before (c).                                                          supply
                                                                                                      –VE
     (c)                 Long terminals.                                                                     17     circuits
2. When directional control is required the contacts                                   (See Note 3)
   of the directional relays should be connected as shown.                                                        Case earth connection
   Contacts must close to inhibit overcurrent relay.
3. Earthing connections are typical only.
4. CT connections are typical only.
                             Figure 9: Application diagram (10 MCGG 82 03): static modular overcurent relay type MCGG 82.
                                       Three phase plus earth fault with instantaneous elements (4 wire system).
                                                                                                                                                      8
Technical Data
Ratings
AC current (In)                            1A or 5A
Frequency                                  50/60Hz
DC supply (Vx)                             24/54V, 48/125V or 110/250V
Burdens
AC Burden                                  Less than 0.25 VA for 1A relays and
                                           less than 0.5VA for 5A relays, at
                                           unity power factor and at rated
                                           current on any setting.
                                           The impedance of the relays over
                                           the whole of the setting range (5%
                                           to 240% rated current) is less than
                                           0.25Ω for 1A relays and less than
                                           0.02Ω for 5A relays and is
                                           independent of current.
DC burden          Relay         Relay type
                   rating
                                 MCGG          MCGG        MCGG         MCGG
                                 22, 63        42, 53      52, 62       82
                   24/54         1.5W          2.5W        3.0W         4.0W
                   48/125        2.0W          3.0W        3.5W         4.5W
                   110/250       2.5W          3.5W        4.0W         5.0W
                   The figures above are maxima under quiescent conditions.
                   With output elements operated they are increased by up to
                   2.5W per element.
                   9
Setting ranges                    Time delayed settings (Is), phase/
                                  earth fault measuring range: 5% to
                                  240% of In in 5% steps.
                                  Instantaneous setting (Iinst)
                                  1 x –31 x   Is in 1 x 1s steps
Operating time
Time delayed element              Shown in Figure 10
Operating characteristics
selectable to give:               Standard inverse IDMT
                                  Very inverse IDMT
                                  Extremely inverse IDMT
                                  Long time earth fault IDMT
                                  Definite time 2s, 4s, 8s
Time multiplier setting           0.05 to 1.0 in 0.025 steps
                                  (applicable to all time
                                  characteristics)
Instantaneous elements            Shown in Figure 11
                                  For settings of 5 x Is and above:
                                  <35ms at 2x instantaneous setting
                       10
                                                                                                                    100
                                                                                                                     10
                                                                                                                                                                                        Definite 8 seconds
                                                                                                                                                                                            Very inverse
                                                                                                                                                                                                13.5
                                                                                                                                                                                            t=
                                                                                                                                                                                                I–1
240
220
200
180
160
                                140
          Operating time (ms)
120
                                100
                                                                                       Iinst = 1Is
                                 80
                                 60                                              2Is
                                                                           3Is
                                 40                       5-31Is    4Is
20
                                  0
                                                   1                                                                                     10                                                                        100
                                                                                  Current (multiple of instantaneous setting)
                                                                                                                              11
Accuracy – influencing quantities
Time multiplier                     On settings 0.05 to 1.0 ±2% or
                                    ±30ms whichever is the greater
Ambient temperature
operative range                     –25°C to +55°C
Variations over this range
Setting current                     ±5%
Time characteristic                 Time variation
Standard inverse
Very inverse                        ±5%
Long time inverse
Extremely inverse                   ±7.5%
Definite time                       ±3%
Frequency
Setting current                     ±1% over the range 47 – 62Hz
Operating time                      ±2% or ±30ms whichever is the
                                    greater, over the range 47–52Hz or
                                    57–62Hz.
DC auxiliary voltage                Vx dc(V)          Operative range (V)
                                    24/54             19 – 60
                                    48/125            37.5 – 150
                                    110/250           87.5 – 300
Variations over these ranges
Setting current                     ±1%
Operating time                      ±2% or ±30ms whichever is greater
Accuracy – general
Current setting
Time delayed element                1.0 x   Is to 1.1 x Is
Instantaneous elements              Iinst = 1 x Is 1.0 x Iinst to 1.1 x Iinst
All other settings                  Iinst ±5%
Operating time
Time characteristic                 Accuracy
Standard inverse
Very inverse                        ±5%
Long time inverse
Extremely inverse                   ±7.5% ±30ms whichever is greater
Definite time                       ±3%
Repeatability
(within basic accuracy claim)
Pick-up current                     Better than ±1%
Operating time                      Better than ±2% or ±30ms
                                    whichever is greater.
Overshoot time                      Less than 30ms (when the input
                                    current is reduced from any value
                                    within the operative range to zero).
                      12
Resetting current                         Time delayed and instantaneous
                                          elements: not less than 95% of time
                                          delayed current setting.
Resetting and disengaging times           Less than 70ms (when the input
                                          current is reduced from any value
                                          within the operative range to zero).
Transient overreach                       System time constant up to 30ms:
                                          5%
(instantaneous elements)                  System time constant up to 100ms:
                                          12%
Thermal withstand
Continuous withstand                      2 x Is or 2.6 x In whichever is
                                          lower, with a minimum of 1 x In
Short time withstand                      For 1s: 100 x   In with 400A
                                          maximum
                                          For 3s: 57 x   In with 230A
                                          maximum
Operation indicators
                                          Each measuring board is fitted with
                                          two red LED indicators, one showing
                                          time delayed operation and the
                                          other showing instantaneus
                                          operation. The reset button provided
                                          on the frontplate resets all the
                                          operation indicators.
                                          The green timer start indicator
                                          illuminates when the input current
                                          exceeds the setting current Is to
                                          facilitate testing of the module.
                                          This indicator is self resetting.
                                          LED covers are available to
                                          eliminate any undesired LED
                                          indication.
Contacts
                                                               Changeover Make
MCGG 52, 53, 82            Phase fault time delayed element        1        1
                           Phase fault instantaneous element       1        1
                           Earth fault time delayed element        1        1
                           Earth fault instantaneous element       1        1
MCGG 22, 42, 62, 63 Time delayed element                           1        1
                           Instantaneous element                   1        1
                    13
Contact ratings
Make and carry for 0.2s                    7500VA subject to maxima of 30A
and 300V ac or dc
Carry continuously                         5A ac or dc
Break                                      ac – 1250VA             subject to
                                           dc – 50W resistive      maxima of
                                           25W, L/R = 0.04s        5A and 300V
Durability
Loaded contact                             10,000 operations minimum
Unloaded contact                           100,000 operations minimum
Directional control
                                           Directional control can be exercised
                                           over each pole individually by
                                           connecting the output contact of a
                                           relay type METI across appropriate
                                           case terminals.
Relay type                                 Direction control terminals
MCGG 22                                    23,24
MCGG 42                                    45, 46, 49, 50
MCGG 52, 53                                43 to 46, 49, 50
MCGG 62, 63                                45 to 50
MCGG 82                                    43 to 50
Note: The directional control circuits are isolated from all other circuits but
      are electrically connected to the relay case. These circuits must not,
      therefore, be insulation or impulse tested to the case.
                     14
Electrical environment
High frequency disturbance
IEC 60255-22-1: 1988 Class III   2.5kV peak between independent
                                 circuits and case earth.
                                 1kV peak across terminals of the
                                 same circuit.
                                 Note: The directional control
                                 terminals comply with class II and
                                 will withstand 1kV peak between all
                                 independent circuits, and 500V
                                 peak across the directional control
                                 terminals.
DC supply interruption
IEC 60255-11: 1979               The unit will withstand a 10ms
                                 interruption in the auxiliary supply,
                                 under normal operating conditions,
                                 without de-energising.
AC ripple on dc supply
IEC 60255-11: 1979               The unit will witstand 12% ac ripple
                                 on the dc supply.
Fast transient disturbance
IEC 60255-22-4: 1992 Class IV    4kV, 2.5kHz applied directly to
                                 auxiliary supply.
                                 4kV, 2.5kHz applied directly to
                                 all inputs.
Electrostatic discharge
IEC 60255-22-2: 1996 Class II    4kV discharge in air with cover
                                 in place
                                 4kV contact discharge with cover
                                 removed.
Surge immunity
IEC 61000-4-5: 1995 Level 4      4kV peak, 1.2/50µs between all
                                 groups and case earth.
                                 2kV peak, 1.2/50µs between
                                 terminals of each group.
EMC compliance
89/336/EEC                       Compliance with the European
                                 Commission Directive on EMC is
                                 claimed via the Technical
                                 Construction File route.
EN50081-2: 1994                  Generic Standards were used to
EN50082-2: 1995                  establish conformity.
Product safety
73/23/EEC                        Compliance with the European
                                 Commission Low Voltage Directive.
EN 61010-1: 1993/A2: 1995        Compliance is demonstrated by
EN 60950: 1992/A11: 1997         reference to generic safety
                                 standards.
                  15
Atmospheric environment
Temperature
IEC 60255-6: 1988         Storage and transit
                          –25°C to +70°C
                          Operating –25°C to +55°C
IEC 60068-2-1: 1990       Cold
IEC 60068-2-2: 1974       Dry heat
Humidity
IEC 60068-2-3: 1969       56 days at 93% RH and 40°C
Enclosure protection
IEC 60529: 1989           IP50 (dust protected)
Mechanical environment
Vibration
IEC 60255-21-1: 1988      Response Class 1
                          Endurance Class 1
                  16
Cases
                                                                                               52
MCGG 22 Size 4
                                    97                              4 holes Ø4.4
                                                                                                          23.5
MCGG 42 Size 6
MCGG 62 Size 6
                                                All dimensions in mm.
MCGG 63 Size 6
                                                                              168                            159
MCGG 52 Size 8
MCGG 53 Size 8
                                                 Push button
MCGG 82 Size 8                                   projection 10 max.                            99
                                   103                                                                       11
                                                              Flush mounting.
                                                                                           103.6
                                  149                            4 holes Ø4.4
                                                                                                            23.5
                                               Push button
                                                                                            151
                                               projection 10 max.
                                                                                   Panel cut-out:
                                                                                   Flush mounting fixing details.
                                                                      32                 212
                                                                                                                    25 min.
                                  155
                                                                      Flush mounting.                               11
                                          17
                                                                    155.4
                  200                 4 holes Ø4.4
                                                                                        24
168 159
                                 Push button
                                                                    203
                                 projection 10 max.
                                                              Panel cut-out:
                                                              Flush mounting fixing details.
                                                  32                 212
                                                                                               25 min.
                   206                                                                         11
                                                  Flush mounting.
       All dimensions in mm.
Information Required
with Order
Relay type (see models available).
Rated current and frequency.
DC auxiliary voltage range.
Requirement for LED cover part
GJ0280 001.
(These self adhesive LED covers can
be supplied to cover the
instantaneous LED when used in
auto-reclose applications as the
LEDs remain on during normal use).
                         18
19
                          ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England
             Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: pcs.enquiries@tde.alstom.com Internet: www.alstom.com
                                                                        ©1999 ALSTOM T&D Protection & Control Ltd
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
    only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
                       ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.