Model T7900

The document describes an electro-pneumatic transducer called the Model T7900 that controls output air pressure proportionally to an electrical input signal. It has features like adjustable PID tuning, alarm indicators, and RFI protection. The transducer uses solenoid valves and a pressure sensor in a closed loop system to regulate pressure based on the difference between the setpoint and measured output. Specifications include an accuracy of less than 0.5%, frequency response of 1 Hz, and materials of aluminum, plastic, and steel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
194 views4 pages

Model T7900

The document describes an electro-pneumatic transducer called the Model T7900 that controls output air pressure proportionally to an electrical input signal. It has features like adjustable PID tuning, alarm indicators, and RFI protection. The transducer uses solenoid valves and a pressure sensor in a closed loop system to regulate pressure based on the difference between the setpoint and measured output. Specifications include an accuracy of less than 0.5%, frequency response of 1 Hz, and materials of aluminum, plastic, and steel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

CROSS SECTION

Figure 1. Model T7900 Detail Drawing

GENERAL INFORMATION

The Model T7900 I/P, E/P Electro-Pneumatic Trans- The Model T7900 has the following options:
ducer controls an output pressure in proportion to an
analog electrical control signal. An internal feedback • Electronic Feedback Output closes the loop.
sensor monitors output pressure to achieve high accu-
racy. Model T7900 applications include machine tool • External Pneumatic Feedback port is available.
automation and robotics.
The Model T7900 has the following features:
• RFI/EMI protection eliminates electromagnetic and
radio interference. OPERATING PRINCIPLES
• Output pressure displays in psig, BAR, or kPa.
• Reverse acting capability for input and feedback The Model T7900 has a closed loop, integrated electronic
output signals control system that regulates outlet pressure in proportion
• Select Current or Voltage input signals using the to an electrical control signal.
keypad.
• Select Current or Voltage feedback output signal The Feed and Bleed Solenoid Valves control pressure in the
using the keypad. Signal Chamber of the Booster Section. Apressure sensor
• Independently adjustable PID tuning coefficients. measures the outlet pressure of the transducer and pro-
• Set operation parameters with the keypad. vides a feedback signal to the Electronics Section. Any
• Liquid Crystal display screen. variation in pressure between the setpoint and the outlet
• High and Low Alarm indicator lights. pressure activates the Feed or Bleed Solenoid Valve to
• Backlit Liquid Crystal display screen. correct the output.

2 Model T7900
OUTLINE DIMENSIONS
4 1/4 3 7/16
108.0 87.4
Display 2 1/32 7/16 3 1/8
51.6 11.3 79.2
37/64
14.6 Cable
7 13/16 Connectors 2 INPUT

198.3 1
25.4
Mounting FEEDBACK/
Bracket ALARM

6 3/8
162.1 Keypad Remote 6 1/32
Pressure 153.2
Sensing
1/8 NPT 1/4-20
4 21/32 (optional) Screw (2)
118.2 (included with
Inlet/ mounting kit)
Supply Outlet
Filter GAUGE Port OUT 3 9/32
(typical) 83.2
3 1/4
82.4
Gauge 1 57/64
1 31/32 48 EXH
49.9 Port
1/4 NPT

13/16 55/64
20.5 Tapped 22.0 9/16
45/64 14.1
1 1/2 17.86 Exhaust
38.1
3
Port 1 1/2
76.2
(typical) 38.1
2 33/64
63.8 3
5 76.2
127.0
Figure 2. Outline Dimensions shown with Mounting Kit EA-19634-1 (Included with unit)

SPECIFICATIONS
FUNCTIONAL SPECIFICATIONS PERFORMANCE SPECIFICATIONS
Pneumatic psig 0-30 0-75 0-150 Deadband
Outputs [BAR] [0-2] [0-5] [0-10] (ISA S51.1) Adjustable from 0 to 7% of Full Scale
(kPa) (0-200) (0-500) (0-1000)
Input Signal 4-20 mA, 0-10 VDC Unit Accuracy Less than 0.50% Output Span
1 (ISA S51.1)
Supply Pressure 200 psig, [14 BAR], (1400 kPa) Max.
Frequency -3 db @ 1 Hz per ISA S26.4.3.1
Minimum psig 12 30 60 Response load configuration A.
Span [BAR] [0.8] [2.0] [4.0]
(kPa) (80) (200) (400)
Supply No Measurable Effect
Electrical Supply 24 VDC + 10% Pressure Effect

Power Consump. Less than 5 watts Vibration Less than 1% of Span under the following
Effect conditions: 5-15 Hz @ 0.8 inches constant
Analog Input 4-20 mA/500 ohms maximum, displacement 15-500 Hz @ 10 g's.
Signal/Impedance 0-10 VDC/400 ohms minimum
RFI/EMI Less than 0.5% EMC Directive 89/336/EEC
Air Consump. 0 @ steady state output Effect European Norms EN 50081-2 & EN 50082-2.
(SCFM)
Materials of Body and Housing . . . . . . . . .Chromate
Flow Rate 100 (17.0 m3/HR) @ 100 psig, Construction Treated Aluminum
(SCFM) [7 BAR], (700 kPa) supply @ 20 psig Cover and Pintle . . . . . . . Acetal Plastic
[1.5 BAR], (150 kPa) setpoint. Trim . . . . . . . . . . . . . . . . . . Plated Steel
Exhaust Flow 50 (85 m3/HR)@ 60 psig, [4 BAR], Elastomers . . . .Fluorocarbon & Silicone
(SCFM) (350 kPa) downstream pressure @ Finish . . . . . . . . . . . . . . . . . . . . .Epoxy
1
5 psig, [.35 BAR], (350 kPa) above setpt. Supply pressure must be no less than 5 psig,
[0.35 BAR], (35 kPa), above maximum output.
2
Temp. Range 00 F to +1600 F (-180 C to +710 C) Connecting cables sold separately.

Model T7900 3
TYPICAL APPLICATION ORDERING INFORMATION
Catalog Number T7900 -
Input
0-10 VDC (0)
4-20 mA (4)

Output
Select appropriate psig, [BAR], or (kPa) range.
0-30 psig (04)
0-75 psig (05)
0-150 psig (07)

[0-2.0 BAR] (14)


[0-5.0 BAR] (15)
[0-10.0 BAR] (17)

(0-200 kPa) (24)


(0-500 kPa) (25)
(0-1000 kPa) (27)

Pipe Size
1/4" (02)
3/8 " (03)
1/2" (04)

Pipe Thread Type


NPT Thread (O)
Figure 4. Model T7900 Application (U)
BSPT Thread
BSPP Thread (H)

TYPICAL APPLICATION Feedback Type


0-10 VDC Feedback Output (0)
4-20 mA Feedback Output (4)
The Model T7900 transducer provides blanket air
pressure to control the flow of powder (or liquid) in a Option
Hopper. The T7900 output pressure in the Hopper External Pneumatic Feedback (P)
maintains a constant flow rate into the containers as
they fill. Load Cells continuously monitor the powder T7900 Cables and Connectors (Sold Separately)
level in the Hopper and send a feedback signal to the Part number Description
T7900. The T7900 adjusts the pneumatic output to 055-IPI-089-M Male connector (Feedback)
maintain a constant flow rate into the containers. 055-IPI-089-F Female connector (Input)
032-IPI-009-3M Male cable w/one connector (3 meter)
032-IPI-009-3F Female cable w/one connector (3 meter)

OPERATION INSTALLATION
For operating instructions, see the Model T7900 Electro-Pneu- For installation instructions, see the Model T7900 Electro-
matic I/P, E/P Transducer (Feedback Output) Operation and Pneumatic I/P, E/P Transducer Installation Instructions,
Maintenance Instructions, OM-5T7900FO. II-500T7900.

CS-500T7900
Litho in USA
Rev. F 2/03

You might also like