Controlador Siemens Lae10 Lfe
Controlador Siemens Lae10 Lfe
             The LAE10 / LFE10 and this Data Sheet are intended for use by OEMs which
             integrate the flame safeguards in their products!
Use
LAE10        -   For the supervision of oil flames
             -   Flame supervision with silicon photocell detector RAR9...
LFE10        -   For supervision of gas flames and luminous or blue-burning oil flames
             -   Flame supervision with flame detector QRA... or ionization probe
General      Both types of flame safeguards are used primarily in conjunction with LEC1 control
             units on the following applications:
             -    Dual-supervision of burners / supervision of the main flame or of the ignition and
                  main flame by 2 identical or different types of detectors
             -    Supervision of forced draft oil / gas burners / supervision of the flame with
                  different types of detectors, depending on the operating mode
             -    Multiflame supervision / plants with several burners whose flames must be
                  supervised individually by one or several detectors, whose startup and supervision,
                  however, should or must be carried out centrally and simultaneously by only 1
                  burner control
             -    The flame safeguards can also be used in connection with other types of burner
                  controls provided the given combination and selected connection circuit do not
                  impair the burner control’s safety functions
             -    The flame safeguards are also used as flame indication units in combustion plant
                  with manual startup
CC1N7781en
                                                         Building Technologies Division
15.10.2012                                                Infrastructure & Cities Sector
Warning notes
                                 The avoid injury to persons, damage to property or the environment, the
                                 following warning notes must be observed!
                                    All activities (mounting, installation and service work, etc.) must be performed by
                                     qualified staff. If this is not observed, there is a risk of loss of safety functions or
                                     a risk of electric shock
                                    For safety reasons – self-test of flame supervision circuit, etc. – at least one
                                     controlled shutdown is required every 24 hours. If this is not observed, there is a
                                     risk of loss of safety functions
                                    Before making any wiring changes in the connection area, completely isolate the
                                     plant from mains supply (all-polar disconnection). Ensure that the plant cannot be
                                     inadvertently switched on again and that it is indeed dead. If not observed, there is
                                     a risk of electric shock hazard
                                    Ensure protection against electric shock hazard by providing adequate protection
                                     for the flame safeguard´s connection terminals. If this is not observed, there is a
                                     risk of electric shock
                                    Each time work has been carried out (mounting, installation, service work, etc.),
                                     check to ensure that wiring is in an orderly state. If this is not observed, there is a
                                     risk of loss of safety functions or a risk of electric shock
                                    Fall or shock can adversely affect the safety functions. Such units must not be put
                                     into operation, even if they do not exhibit any damage
                                    The ionization probe does not offer protection against electrical shock hazard. The
                                     mains-operated ionization probe must be protected against accidental contact. If
                                     this is not observed, there is a risk of electric shock
                                    An ignited UV tube is a source of UV radiation! In case of flame supervision by
                                     means of flame detectors, the detectors must be placed such that there is no
                                     direct visual contact between them. If this is not observed, there is a risk of
                                     loss of safety functions
Engineering notes
                                 Ensure that the drop out delay time of relay «d» does not exceed 50 ms (also refer to
                                 «Connection examples», 7781a02).
Mounting notes
                                    The relevant national safety regulations must be complied with
                                    The flame safeguards can be mounted in any position directly on the burner, in
                                     control panels, or on the front of a panel
                                    There are 2 types of plug-in bases available, designed for cable entry from the
                                     front, the side or below. 2 earth terminals provide looping facilities for the earth
                                     connections of other burner plant components such as ignition transformers (the
                                     flame safeguards themselves are double-insulated!)
Installation notes
                                    Always run the high-voltage ignition cables separately while observing the greatest
                                     possible distances to the unit and to other cables
                                    Do not mix up live and neutral conductors
2/13
                                                  With LEC1…
                   LAE10         x         x           x             x          x           ---              x             ---
                   LFE10         x         x           x             x         ---           x               x              x
Life cycle
                                     Flame safeguards has a designed lifetime* of 250,000 burner startup cycles which,
                                     under normal operating conditions in heating mode, correspond to approx. 10 years of
                                     usage (starting from the production date given on the type field). This lifetime is based
                                     on the endurance tests specified in standard EN230 / EN298 and the table containing
                                     the relevant test documentation as published by the European Association of
                                     Component Manufacturers (Afecor) (www.afecor.org).
                                     The designed lifetime is based on use of the flame safeguards according to the
                                     manufacturer’s Data Sheet. After reaching the designed lifetime in terms of the number
                                     of burner startup cycles, or the respective time of usage, the flame safeguards is to be
                                     replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
                                     The flame safeguards contain electrical and electronic components and must not be
                                     disposed of together with household waste.
                                     Local and currently valid legislation must be observed.
3/13
                                 The electrical circuit is intrinsically safe in connection with LEC1 control unit – is tested
                                 in respect of proper functioning each time the burner is started up. The plug-in bases –
                                 like the housing – are made of impact-proof and heat-resistant plastic. For illustrations
                                 of the plug-in bases and other notes, refer to «Dimensions».
Special features LAE10           Automatic light simulation test by increasing the sensitivity of the amplifier during the
                                 burner off and the purging times of the LEC1 control unit control.
Special features LFE10           Automatic testing of the flame detector by increasing the operating voltage of the UV
                                 tube during the burner off and the purging times of the LEC1 control unit.
Ionization probe                 Flame supervision by making use of the electrical conductivity of the flame in
                                 conjunction with the rectifying effect is only possible with gas and blue-flame burners.
                                 Since the flame signal amplifier responds only to the DC component of the flame signal
                                 (ionization current), a short-circuit between flame detector and functional earth cannot
                                 simulate a flame signal.
4/13
                                 Flame safeguard
                                 - For the supervision of gas / oil flames with flame detector QRA... or ionization probe
                                 - AC 220…240 V                                                                       LFE10
                                 - AC 110 V                                                                    LFE10-110V
Ordering
                                 When ordering, please give complete type reference.
                                 Flame safeguard is delivered without plug-in base; order these separately (refer to
                                 «Accessories»).
Accessories
                                 Silicon photocell detectors RAR9...                           refer to Data Sheet N7713
5/13
                                                                              LAE10                        LFE10
                                 Flame supervision with...                  ...RAR9...      ...Ionization probe       ...QRA...
                                 Required detector current
                                 - At AC 100 V / AC 220 V                   Min. 8 µA           Min. 8 µA          Min. 150 µA
                                 - At AC 110 V / AC 240 V                   Min. 8 µA           Min. 9 µA          Min. 200 µA
                                 Possible detector current
                                 - At AC 100...110 V / AC 220...240 V      Max. 38 µA          Max. 100 µA         Max. 650 µA
                                  Caution!
                                  Condensation, formation of ice and ingress of water are not permitted!
6/13
                                  Caution!
                                  Ignition may affect the ionization current!
                                  Remedy: Exchange the connections on the primary side of the ignition
                                  transformer.
Function
                                 Basic mode of operation of the flame safeguards in connection with the LEC1 control
                                 unit:
                                 When used with the LEC1, the flame safeguard feeds the flame signal into the burner
                                 control’s control program the same way as if the flame safeguard was a component of
                                 the burner control (same as with an oil or gas burner control). In the event of non-
                                 ignition, loss of flame during burner operation or faulty flame signal during burner off or
                                 purging times, the burner will always be shut down and the burner control will initiate
                                 lockout. The switching functions needed to feed the flame signal into the burner
                                 control’s control circuit are provided by flame relay «FR» of the flame safeguard and
                                 the 2 auxiliary relays «HR1» and «HR2» of the LEC1 control unit. The LEC1 control
                                 unit also delivers the sequence control for the flame simulation test in connection with
                                 the LAE10 flame safeguard, and the flame detector test with the LFE10. The test is
                                 controlled via the connecting line between terminal 15 of the burner control and
                                 terminal 6 of the respective flame safeguard.
                                 Both tests
                                  start about 7 seconds after a controlled shutdown
                                  are continued during burner off times
                                  Are continued during the ensuing prepurge time
                                  end 3 seconds before start of the safety time
                                 Following flame signals during this test time lead to lockout with interlocking of the
                                 LEC1 control unit:
                                 -    Extraneous light
                                 -    Ageing flame detectors
                                 -    Other defects of the flame supervision equipment
                                 In the flame safeguard, the switching functions required are performed by auxiliary
                                 relay «HR3».
                                 Since in the case of flame supervision with an ionization probe, it is not necessary to
                                 carry out a test, the connecting line between terminal 15 of the burner control and
                                 terminal 6 of the flame safeguard is not required here.
                                  Information!
                                  Instead, terminal 6 must be connected to the live wire.
                                  Example: By making a connection to terminal 1, 5 or 7.
                                 Any flame signal – be it a normal flame signal during operation or a faulty signal – is
                                 indicated by the indication lamp at housing of flame safeguard.
7/13
                                 3 4            1 6
                                                      8
                                         FR                RAR9...
                                                      9              +
                                                      10
              Z   OV1 OV2                  L1
                                 7 5            2 LAE10
8/13
                                 Note!
                                Ensure that the drop out delay time of relay «d» does not exceed 50 ms (also refer to
                                 «Connection examples», 7781a02).
                                 Caution!
                                 An ignited UV tube is a source of UV radiation! In case of flame supervision by
                                 means of flame detectors, the detectors must be placed such that there is no direct
                                 visual contact between them. If this is not observed, there is a risk of loss of safety
                                 functions
9/13
                 0 I                                 L1
                                                                10 QRA...               only – after the burner control has been reset –
                           Z
                 BS                          7 5          2 LFE10
                                                                                        when the faulty burner has been shut down.
                               GV1 GV2                                                  In that case, the operating switch must not only
                                                                                        bridge the control contacts of the respective
                                                                                        flame safeguards, thus closing the control chain
                                             3 4          1 6
                                                                8                       again, but must also break the phase wire
                                                     FR                      ION
                                                                9       +               connection to the ignition transformer and the
                                                                10 QRA...
                 0 I   Z                             L1                                 fuel valves.
                 BS                          7 5          2 LFE10                       Likewise, after rectification of the fault, the
                               GV1 GV2                                                  burner can only be restarted in connection with
                                                                                        the other burners, that is, only after all burners
 P(R) N(Mp)                7781a03/0903
                                                                                        have previously been shut down.
                                                                                                  Caution!
                                                                                                  Terminal 10 must be connected to
                                                                                                  earth also when using the flame
                                                                                                  detector QRA...!
10/13
P(R)
H 15 LEC1
7 5 1 6
                     FR
                                                            HR3
                                                                      8
                                                                                    QRA...
    hr3                                                               9                      +
                                                                      10
                L1
      3 4                          2                            7781a05/0199
                                           N(Mp)
      13 14 LEC1
                 Caution!
                 Terminal 10 must be connected to earth!
P(R)
7 5 1 6
FR HR3
                                                                               8
                                                                                         ION
     hr3                                                                       9
                                                                               10
                L1
      3     4                          2                              7781a06/0903
                                                   N(Mp)
      13 14 LEC1
                                                            15 LEC1
                                                                                                     FR        Flame relay
                           H
                                                                                                     H         Main switch
       7    5                                  1                6                                    HR3       Auxiliary relay for UV detector or
                                                                                                               flame simulation test
                     FR                                                                              ION       Ionization probe for ionization
                                                                HR3
                                                                                                               supervision
                                                                          8                          L1        Built-in signal lamp
                                                                                    RAR9...
    hr3                                                                    9                     +              Indication of flame
                     L1                                                   10                         QRA...    Flame detector
                                                                                                     RAR9...   Silicon photocell detector
      3     4                          2
                                                                    7781a04/0908
                                               N(Mp)
      13 14 LEC1
                                                                                                                                                11/13
Base versions
13
                                                                      4,6
                                    1 2 3 4 5      6 7 8 9 10                    31
                                                                  4
                                    1 2 3 4 5      6 7 8 9 10
                                                                       13
                                                                            16
                                                                                 31
90 4
                                              22    22                  16,2
                                           25       25                                       7781m02/1198
                                          30         30
                                       42,5           42,5
12/13
Base versions
13
                                                                                     4,5
                                                                                                        31,5
                                      1   2   3 4   5   6    7        8   9 10
                                                                                 4
                                          N
                                                        11       12
                                                                                      13
                                                                                            16
                                                                                                 23,5
                                                                                                        34
                                                  16 10,5                                                                     110            4
                                                22      22                            4,5
                                               25           25
                                               30            30                                                7781m01/1198
                                          45                          45