1.
FIRE SUPPRESSION SYSTEMS
1.1. FIRE SUPPRESSION SYSTEM DESIGN REFERENCES
     1.1.1. Applicable Codes
        IBC International Building Code 2009 Edition
        IFC        International Fire Code 2009 Edition
        NFPA 101 Life Safety Code® 2009 Edition
     1.1.2. Applicable Standards
        NFPA 10    Standard for Portable Fire Extinguishers 2006 Edition
        NFPA 12   Standard on Carbon Dioxide Extinguishing Systems 2005 Edition
        NFPA 13   Standard for the Installation of Sprinkler Systems 2010 Edition
        NFPA 14   Standards for the Installation of Standpipe, Private Hydrant and
                 Hose Systems 2010 Edition
        NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection
                 2007 Edition
        NFPA 70 National Electrical Code 2006 Edition
        NFPA 72 National Fire Alarm Code® 2006 Edition
        NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2000 Edition
        ASTM       American Society for Testing of Materials
        UL        Underwriters Laboratories Inc.
        FM        Factory Mutual, Inc.
     1.1.3. Applicable Design Guidelines
        RC Engineering Manual
1.2. FIRE SUPPRESSION SYSTEM REQUIREMENTS
     1.2.1. Code Requirements:
      The different facilities included in this project and there occupancy classification as per
      International Building Code is as given below:
      Community Building : This Building is classified as Group B in IBC. Refer IBC 304.1.
      RC Staff Building : This Building is classified as Group B in IBC. Refer IBC 304.1.
      Sprinkler system Requirements are as follows:
      Community Building : Automatic sprinkler system is not required in this building as the
        building Height is less than 55ft. Refer IBC 903.2.11.3.
      RC Staff Building: Automatic sprinkler system is not required in this building as the
        building height is less than 55ft. Refer IBC 903.2.11.3.
      Standpipe Requirements are as follows:
      Standpipe is not required in any of the buildings as the floor level of highest storey above
         the lowest level of fire department access is less than 9.144m in all buildings. Refer IBC
         905.3.1. Hose stream allowance is required in Warehouse building as per NFPA 13 Table
         16.2.3.1.
        Fire extinguishers are required in the buildings as follows:
        Portable fire extinguishers are required in Group B, Group F, Group H , Group I and
         Group M occupancies. Refer IBC 906.1.
     1.2.2. Standards Requirements
      Fire extinguishers shall be in accordance to NFPA 10.
       Water demand for sprinkler system shall be in accordance with NFPA 13.
     1.2.3. End Users Requirements
        All the facilities in this project are required to have Automatic sprinkler system irrespective
         of the code requirements as per end user.
FIRE SUPPRESSION SYSTEM DESCRIPTION
     1.2.4. Systems Overall Description
         The Occupancy Classification, Code requirements and end-user requirements are
         summarized below for all the buildings:
                            BUILDING OCCUPANCY CLASSIFICATION
                                               OCCUPANCY
                    BUILDING                                                 SPRINKLER SYSTEM
                                             CLASSIFICATION
S.No                                                                CODE                    END USER
                        AREA   HEIGHT                  CODE                      CODE
             NAME                         GROUP                    REQUIR-                   REQUIR-
                        (m²)    (m)                  REFERENCE                 REFERENCE
                                                                   EMENT                     EMENT
         Community                                                                IBC
 1                      1694     4.4      Group B     IBC 304.1      No                         Yes
          Building                                                             903.2.11.3
                                                                                  IBC
 2       RC Building    1684     4.4      Group B     IBC 304.1      No                         Yes
                                                                               903.2.11.3
      Electrical and telecom rooms
         Electrical room and Telecom room in all buildings shall be provided with a carbon
          dioxide type UL rated (5B: C) Portable Fire Extinguisher.
     1.2.5. Systems Operational Philosophy & Controls Description
     General
     The wet fire suppression water sprinkler system includes an array of individual fire sprinklers
     which are supplied with water through a main conduit and various branch conduits.
     Operation
     The individual fire sprinklers are provided with a fusible link that melts when the ambient
     temperature reaches a predetermined level indicative of a fire. In this way, the extent of water
     damage may be minimized.
     The melting of the member opens the fire sprinkler to spray water in order to suppress the fire.
     Alarm
    Fire suppression systems often times have one or more alarms that detects the flow of water
    through the main conduit and indicates that a fire has started. The alarm typically triggers an
    audible signal to warn occupants of the building that a fire has started and may also send an
    appropriate signal directly to a fire department.
    Flow of water, even from a single sprinkler is sufficient to move the member and trigger the
    alarm. Often times, such water flow indicator alarms are electronically connected to an audible
    alarm single generator as well as to light panels to indicate the area in which the fire has
    occurred.
    Community Water Supply System
    Fire suppression systems which include water sprinklers are oftentimes in fluid communication
    with the community water supply system or with whatever source of potable water is available
    in the vicinity. The water within the fire suppression system itself, however, can remain within
    the piping for a considerable period of time and is considered to be stagnant water.
    Note: Water supply lines to building are to be provided with back flow preventers. Refer to civil
    site drawings for fire and potable water drawing.
    Fire Department
    In addition, a pump provided by the fire department will be connected to an inlet in
    communication with the fire suppression system in order to provide additional water and/or
    pressure in the event of a fire.
    In case of fire, a fire alarm system sends an alarm, at which time the trained occupants shall
    use fire extinguishers to fight fire while the others execute the evacuation plan, until fire
    department officials arrive.
1.3. FIRE SUPPRESSION SYSTEMS DESIGN CALCULATIONS, METHODS & TOOLS
    1.3.1. Fire Water Building Total Demand
    Based on the occupancy classification and above mentioned codes & standards, the fire
    water demand and pressure demand for each building is summarized below which is based
    on hydraulic calculations.
                   BUILDING NAME                  DEMAND FLOW        DEMAND PRESSURE
                   RC Staff Building                260 gpm              3.35 bar
                  Community Building                235 gpm              3.63 bar
         Fire water demand for each building is provided by a common pump. Refer ME-2500
     for Pump details.
    1.3.2. Calculation to be prepared
    Hydraulic calculations are performed to estimate the total demand flow & demand pressure
    required for each facility in the project.
1) Fire Suppression System Design Criteria
    The calculations are performed for Automatic wet sprinkler system by Hydraulic
       calculations method as per NFPA13 - 11.2.3
     The building is Light Hazard. Refer NFPA13 - A.5.2.
     The water density for light hazard           =   0.1gpm/ft² and
     Design area of sprinkler operation           =   1500ft² (139m²). Refer NFPA13 11.2.3.1.1.
     Maximum sprinkler coverage area              =   20.9m², Refer NFPA13 - 8.6.2.2.1(a).
     Actual sprinkler coverage area               =    Design area / no. of sprinklers in design
             area
                                                   =   1500 / 14
                                                   =   107ft²
     The calculations shall be performed for the most remote sprinkler in the operation
             area.
     Sprinkler K factor = 5.65 and sprinkler orifice diameter = ½ in.
2) Fire Suppression System Demand (Flow & Pressure)
    Calculations are carried out for Demand Flow rate (Q) and Demand Residual
             Pressure (P).
        a)     Demand Flow Q = Sprinkler flow requirement (from Elite program) + Inside &
                                 Outside Hose allowance.
                        Thus Q = 260+ 0
                             Q = 260 gpm
        b) Demand Residual Pressure P = P1 + P2
           Where P1 = Pressure calculated at inflow node (by Elite program)
                        P2 = Additional pressure required at Most remote hose connection
                                 (To get the pressure of 4.5bar for 1 1/2 in. Hose connection.)
             Thus P1 = 48.56 PSI
                     P2 = 0 (Since the Standpipe is not required in the building. Refer IBC
      905.3.1.)
                     Therefore     P = 48.56 PSI = 3.34 BAR