crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=1
administrativeState 1
alarmSlogan MAINS FAILURE
normallyOpen false
perceivedSeverity 4
userLabel MAINS FAILURE
end
gs-
gs+
crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=2
administrativeState 1
alarmSlogan RECTIFIER FAILURE
normallyOpen false
perceivedSeverity 4
userLabel RECTIFIER FAILURE
end
gs-
gs+
crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=3
administrativeState 1
alarmSlogan BATTERY DISCHARGE
normallyOpen false
perceivedSeverity 4
userLabel BATTERY DISCHARGE
end
gs-
confb+
gs+
crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=4
administrativeState 1
alarmSlogan ENCLOSURE FAN ALARM
normallyOpen true
perceivedSeverity 4
userLabel ENCLOSURE FAN ALARM
end
crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=5
administrativeState 1
alarmSlogan ENCLOSURE DOOR OPEN
normallyOpen false
perceivedSeverity 4
userLabel ENCLOSURE DOOR OPEN
end
gs-
confb-
crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=5
administrativeState 1
alarmSlogan Generator not running
normallyOpen true
perceivedSeverity 4
userLabel
end
crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=4
administrativeState 1
alarmSlogan Generator Running
normallyOpen true
perceivedSeverity 4
userLabel
end
crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=3
administrativeState 1
alarmSlogan BTS Battery Low
normallyOpen true
perceivedSeverity 4
userLabel
end
crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=2
administrativeState 1
alarmSlogan Recrifier Module Failure
normallyOpen true
perceivedSeverity 4
userLabel
end
crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=1
administrativeState 1
alarmSlogan Rectifier System Failure
normallyOpen true
perceivedSeverity 4
userLabel
end
gs-
confb-
set Equipment=1,FieldReplaceableUnit=SUP-1,Ecport=1 ecBusRef Equipment=1,EcBus=1
set FieldReplaceableUnit=SUP-1,EcPort=1 hubPosition NA
cr Equipment=1,FieldReplaceableUnit=SAU-1
set FieldReplaceableUnit=SAU-1 positionRef Equipment=1,Cabinet=1
cr Equipment=1,FieldReplaceableUnit=SAU-1,Ecport=1
set Equipment=1,FieldReplaceableUnit=SAU-1,Ecport=1 ecBusRef Equipment=1,EcBus=1
set FieldReplaceableUnit=SAU-1,EcPort=1 hubPosition SAU
cr EquipmentSupportFunction=1,climate=1
set EquipmentSupportFunction=1,climate=1 controlDomainRef Equipment=1,Cabinet=1
set EquipmentSupportFunction=1,climate=1 climateControlMode 0
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=1
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=2
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=3
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=4
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=5
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=6
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=7
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=8
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=9
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=10
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=11
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=12
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=13
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=14
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=15
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=16
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=1$ alarmSlogan DOOR OPEN
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=1$ perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=1$ normallyOpen false
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=2 alarmSlogan MAINS FAIL
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=2 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=2 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=3 alarmSlogan DG ON
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=3 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=3 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=4 alarmSlogan DG FAIL TO START
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=4 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=4 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=5 alarmSlogan DG FAIL TO STOP
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=5 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=5 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=6 alarmSlogan DG FUEL LEVEL
LOW
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=6 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=6 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=7 alarmSlogan RECTIFIER FAIL
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=7 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=7 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=8 alarmSlogan SITE ON BATTARY
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=8 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=8 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=9 alarmSlogan BATTARY FUSE
FAIL
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=9 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=9 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=10 alarmSlogan LOAD FUSE FAIL
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=10 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=10 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=11 alarmSlogan HIGH TEMPRATURE
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=11 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=11 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=12 alarmSlogan FIRE and SMOKE
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=12 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=12 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=13 alarmSlogan LOW BATTARY
VOLTAGE
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=13 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=13 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=14 alarmSlogan AC FAIL
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=14 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=14 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=15 alarmSlogan BOTH AC FAULTY
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=15 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=15 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=16 alarmSlogan DG LLOP
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=16 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=16 normallyOpen true
cvms SAU_Supportsystemconfig
confb-
gs-
pmxet . rssihigh$ -- 3G RSSI
pmxet . InterferencePucchPwr$ -- 4G RSSI