Alarms Masters Creation

The document describes alarm configurations for various field replaceable units (FRUs) including a mains failure FRU, rectifier failure FRU, and battery discharge FRU. It also defines 16 alarm ports for a SAU-1 FRU and configures the alarm type, severity, and normal state for each.

Uploaded by

Moketch Moketch
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
You are on page 1/ 4

gs+

crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=1
administrativeState 1
alarmSlogan MAINS FAILURE
normallyOpen false
perceivedSeverity 4
userLabel MAINS FAILURE
end
gs-

gs+
crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=2
administrativeState 1
alarmSlogan RECTIFIER FAILURE
normallyOpen false
perceivedSeverity 4
userLabel RECTIFIER FAILURE
end
gs-

gs+
crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=3
administrativeState 1
alarmSlogan BATTERY DISCHARGE
normallyOpen false
perceivedSeverity 4
userLabel BATTERY DISCHARGE
end
gs-

confb+
gs+

crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=4
administrativeState 1
alarmSlogan ENCLOSURE FAN ALARM
normallyOpen true
perceivedSeverity 4
userLabel ENCLOSURE FAN ALARM
end

crn Equipment=1,FieldReplaceableUnit=BB_GL-1,AlarmPort=5
administrativeState 1
alarmSlogan ENCLOSURE DOOR OPEN
normallyOpen false
perceivedSeverity 4
userLabel ENCLOSURE DOOR OPEN
end

gs-
confb-

crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=5
administrativeState 1
alarmSlogan Generator not running
normallyOpen true
perceivedSeverity 4
userLabel
end

crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=4
administrativeState 1
alarmSlogan Generator Running
normallyOpen true
perceivedSeverity 4
userLabel
end

crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=3
administrativeState 1
alarmSlogan BTS Battery Low
normallyOpen true
perceivedSeverity 4
userLabel
end

crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=2
administrativeState 1
alarmSlogan Recrifier Module Failure
normallyOpen true
perceivedSeverity 4
userLabel
end

crn Equipment=1,FieldReplaceableUnit=DU-1,AlarmPort=1
administrativeState 1
alarmSlogan Rectifier System Failure
normallyOpen true
perceivedSeverity 4
userLabel
end
gs-
confb-
set Equipment=1,FieldReplaceableUnit=SUP-1,Ecport=1 ecBusRef Equipment=1,EcBus=1
set FieldReplaceableUnit=SUP-1,EcPort=1 hubPosition NA

cr Equipment=1,FieldReplaceableUnit=SAU-1
set FieldReplaceableUnit=SAU-1 positionRef Equipment=1,Cabinet=1

cr Equipment=1,FieldReplaceableUnit=SAU-1,Ecport=1

set Equipment=1,FieldReplaceableUnit=SAU-1,Ecport=1 ecBusRef Equipment=1,EcBus=1


set FieldReplaceableUnit=SAU-1,EcPort=1 hubPosition SAU

cr EquipmentSupportFunction=1,climate=1
set EquipmentSupportFunction=1,climate=1 controlDomainRef Equipment=1,Cabinet=1
set EquipmentSupportFunction=1,climate=1 climateControlMode 0

cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=1
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=2
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=3
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=4
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=5
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=6
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=7
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=8
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=9
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=10
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=11
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=12
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=13
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=14
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=15
cr Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=16

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=1$ alarmSlogan DOOR OPEN


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=1$ perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=1$ normallyOpen false

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=2 alarmSlogan MAINS FAIL


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=2 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=2 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=3 alarmSlogan DG ON


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=3 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=3 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=4 alarmSlogan DG FAIL TO START


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=4 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=4 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=5 alarmSlogan DG FAIL TO STOP


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=5 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=5 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=6 alarmSlogan DG FUEL LEVEL


LOW
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=6 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=6 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=7 alarmSlogan RECTIFIER FAIL


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=7 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=7 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=8 alarmSlogan SITE ON BATTARY


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=8 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=8 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=9 alarmSlogan BATTARY FUSE


FAIL
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=9 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=9 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=10 alarmSlogan LOAD FUSE FAIL


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=10 perceivedSeverity 3
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=10 normallyOpen true
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=11 alarmSlogan HIGH TEMPRATURE
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=11 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=11 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=12 alarmSlogan FIRE and SMOKE


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=12 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=12 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=13 alarmSlogan LOW BATTARY


VOLTAGE
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=13 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=13 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=14 alarmSlogan AC FAIL


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=14 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=14 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=15 alarmSlogan BOTH AC FAULTY


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=15 perceivedSeverity 2
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=15 normallyOpen true

set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=16 alarmSlogan DG LLOP


set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=16 perceivedSeverity 4
set Equipment=1,FieldReplaceableUnit=SAU-1,AlarmPort=16 normallyOpen true

cvms SAU_Supportsystemconfig

confb-
gs-

pmxet . rssihigh$ -- 3G RSSI

pmxet . InterferencePucchPwr$ -- 4G RSSI