1.
1 Procedure for Relay setting Calculation for MiCOM P442 Distance Relay
Data required
1. Positive sequence Line impedance = R1+jX1
2. Zero sequence Line impedance = R0+JX0
3. CT Ratio
4. PT Ratio
5. Protected Line Length in kms
6. Adjacent Shortest Line Length in kms
7. Adjacent Longest Line Length in kms
8. Voltage ratio of the transformer at the remote end if any
9. MVA of the transformer at the Remote end
10. % Impedance of the transformer at remote end
11. Maximum load on the feeder in Amperes
Calculation Procedure
The relay settings are in terms of impedance that is Z
Total Positive sequence impedance of protected line with reference to primary
ZPL = [ZPL (Ohms /km)*Protected Line Length (km)]
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT ratio/PT ratio)
Positive sequence impedance Angle = Tan-1(X1/R1)
Similarly the Impedance for Adjacent Shortest Line ZSL, Adjacent Remote Long
Line ZLL and second Adjacent Long Line Z2LL can be calculated.
Total Transformer Impedance ZT (At remote end)
If there is more than one Transformer, the resultant Impedance considering the Transformers are
in parallel is taken.
ZT = (%Transformer Impedance)*((KV) 2/ MVA)]
Zero sequence impedance Z0 = √R02+X02
Zero sequence impedance Angle Z0 = Tan-1(X0/R0)
Loadability:
The Limiting conditions for setting the distance relay reach to avoid encroachment into loads.
As per “Reliability Standard PRC-023”, The maximum impedance for the distance relay
characteristics along 30º on the impedance plane for 0.85 per unit rated voltage and the
maximum specified current for each condition.
2
The maximums Load w.r.t Secondary Zmax = 0.85*VL-L/ (√3*1.5*.IL)
Where IL corresponds to thermal limit of the conductor.
The Resistance reach corresponding to Zmax w.r.t Secondary
R = Zmax *COS (30)
The Reactance reach corresponding to Zmax w.r.t Secondary
X= Zmax *SIN (30)
The New impedance for Parallel line drawn parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts
The Resistance axis is Z new= X (at Zmax) /SIN (Line angle)
The New Resistance from Known Reactance Rnew = Znew* COS (Line angle)
Resistance reach of Relay Characteristics obtained from maximum Loadability condition
Resistive Reach R = (R correspond to Zmax – Rnew)
Zone Settings
Zone 1
Zone 1 = 80 % of Protection Line
Kz 1 Zero sequence compensation
Kz1 = (Z0-Z1/3*Z1)
Kz1 angle = angle of Kz1
As per manufacturer’s specification the maximum X/R ratio allowed is 10, hence considering
this limitation and the maximum loadability limit the minimum of the two is considered
Resistive reach
3
R1G= MIN of [(10 times of Zone1 Impedance) and 0.8*Resistive Reach at Max load)]
R1PH= MIN of [(10 times of Zone1 Impedance) and 0.6*Resistive Reach at Max load)]
Zone 2
Zone 2 = [MAX OF ((Protection line+ (0.5*Adjacent shortest line)) AND
(1.2*Protection line)]
tz2 = if [ZONE 2 > 80 % of Next shortest line then t=0.5sec else t=0.3 sec
Kz2 = (Z0-Z1/3*Z1)
Kz2 angle = angle of Kz2
R2G = Minimum [10 times of Zone 2 Impedance and 0.8*Resistive Reach at Max load]
R2PH = Minimum [10 times of Zone 2 Impedance and 0.6*Resistive Reach at Max load]
Zone 3
Zone3 = [MIN OF (1.2*Protection line + Adjacent Long line) & (Protection line + Adjacent
Long line +0.25* Adjacent Second Long Line) & (Protection line +Transformer
impedance))]
R3G-R4G = Minimum [(10 times of Zone 3 Reactance) and 0.8* Resistance at Maximum
load]
R3PH-R4PH = Minimum [(10 times of Zone 3 Reactance) and 0.6* Resistance at Maximum
load]
tz3 = 1 sec
Zone 4
Zone4 = 0.25 *Zone 1
tz4 = 1 sec
Power Swing:
Criteria 1:
∆f = 5Hz (As Per Manufacturer Specification)
∆R = 0.032*∆f*Maximum Loadability
= 0.032*5*Resistance at Maximum Load
∆X = 0.032*∆f*Maximum Loadability
= 0.032*5*Resistance at Maximum Load
4
Criteria 2:
∆R =∆X = 20% of Resistive reach of R3Ph
So a setting below the value can be retained of it.
5
Sample setting calculation for MiCOM P44X
Substation : 220kV GSS Ballabgargh
Line : Ballabgargh to Charki dadri
Relay Name : MiCOM P442
Data
Positive sequence Line impedance = 0.09705+j0.39314
Zero sequence Line impedance = 0.57146+j1.83241
CT Ratio = 1200A/1A
PT Ratio = 220kV/110V
Protected Line Length (Charki dadri) = 119.9 Km
Adjacent Shortest Line Length (two different conductor connected) (Bhiwani) = 26 (0.3) + 8.7
(0.4) Km
Adjacent Longest Line Length (Samayapur) = 116.10 (0.3) Km
Second Longest Line Length (Bhadshapur 1) = 24.10 (0.4) Km
Voltage ratio of the transformer = 220kV/132 kV
MVA of the transformer at the Remote end = 2*100 MVA
Impedance of the transformer = %12.344, 12.00
CT/PT ratio = 0.6
Calculation
Positive sequence impedance of Protected line ZPL = √R2+X2
= √0.097052+0.393412
ZPL = 0.4052 Ohms/Km
Total Positive sequence impedance of Protected line ZPL=
= [ZPL (Ohms /Km)*Protected Line Length (km)]
= [0.4049 * 119.9]
ZPL W.R.T Primary = 48.548 Ω
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT/PT ratio)
6
= 48.548*(1200/1) / (220kV/110V)
ZPL = 29.129 Ω
Total Positive sequence impedance of the Adjacent Shortest line = (ZS1 + ZS2) * (CT/PT ratio)
Positive sequence impedance of Adjacent Shortest line 1 ZS1 = √R2+X2
= √0.097052+0.393412
= 0.4052* Line length
= 0.4052* 26
ZS1= 10.5352
Positive sequence impedance of Adjacent Shortest line 2 ZS2 = √R2+X2
= √0.07412+0.3832
= 0.390* Line length
= 0.390* 8.7
ZS2 = 3.393
Total Positive sequence impedance of the Adjacent Shortest line = (ZS1 + ZS2) * (CT/PT
ratio)
= (10.5352 + 3.393)* 0.6
ZSL W.R.T Secondary = 8.356 Ω
Total Positive sequence impedance of Adjacent Longest line ZLL=
= [ZLL (Ohms /Km)*Longest Line Length (km)]
= [0.4052 * 116]
ZLL W.R.T Primary = 47.00 Ω
ZLL W.R.T Secondary = ZLL W.R.T Primary * (CT/PT ratio)
= 47.00 * (1200/1) / (220kV/110V)
ZLL W.R.T Secondary = 28.201 Ω
Total Positive sequence impedance of Adjacent Second Longest line Z2LL=
= [ZLL (Ohms /Km)*Longest Line Length (km)]
= [0.4052 * 24.1]
7
Z2LL W.R.T Primary = 9.765Ω
Z2LL W.R.T Secondary = Z2LL W.R.T Primary * (CT/PT ratio)
= 9.765 * (1200/1) / (220kV/110V)
Z2LL W.R.T Secondary = 5.726 Ω
Total Transformer Impedance ZT (Remote):
If there is more than one Transformer, the resultant Impedance considering the Transformers are
in parallel is taken.
Considering Transformers are connected in parallel
Total Transformer Impedance ZT (Remote) = (% Transformer Impedance) *((kV) 2/MVA)]
Transformer Impedance Z1 = 0.12*(2202/100)
= 58.08 Ω
Transformer Impedance Z2 = 0.12344* (2202/100)
= 59.74496 Ω
Transformer Impedance W.R.T primary ZT = (1/((1/Z1)+(1/Z2)))
= 1/((1/58.08)+(1/59.74496))
ZT= 29.450 Ω
Transformer Impedance W.R.T Secondary ZT = 29.450 * 0.6
= 17.670 Ω
Load impedance for (as Per the NERC loadability)
Positive sequence impedance Angle =Tan-1(X/R)
Z1= Tan-1(0.39341/0.09705)
Line Angle = 76.14 Degree
The maximums Load w.r.t Secondary ZMAX primary = 0.85*VL-L/(√3*1.5*.IL)
ZMAX = 0.85* 220 /(√3*1.5*525)
[525 A is the maximum capacity of ACSR Goat conductor]
ZMAX = 137.1 Ω
The Resistance reach corresponding to Zmax w.r.t. Secondary
R = ZMAX *COS (30)
8
= 137.1*0.8660
R = 118.733Ω
The Reactance reach corresponding to Zmax w.r.t Secondary
X = ZMAX *SIN (30)
= 137.1*0.5
X = 68.55 Ω
The New impedance for Parallel line Drawn Parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts the Resistance axis is
Znew = X (at Zmax) /SIN(76.14)
= 68.55/0.9708
Znew = 70.608 Ω
The New Resistance from Known Reactance Rnew = Znew* COS (76.14)
= 70.608 *0.239
R new = 16.922
Resistances reach of Relay Characteristics With respect to primary
= (R corresponds to Zmax – R new)
R = 118.733 – 16.922 ; R =101.811 Ω
With respect to secondary = 101.811*0.6
= 61.086 Ω
Zone Settings
Zone 1
Zone 1= 80 % of Protection Line
=0.8* 29.129
Zone 1 = 23.30 Ω
Kz1 = (Z0-Z1/3*Z1)
= (0.57146+j1.83241)-(0.09705+j0.39314) -/3(0.09705+j0.39314)
Zero sequence Line impedance = 1.247 ∟-4.378
Kz1 Magnitude = 1.247
9
Kz1 angle = - 4.378 degree
R1G = Minimum of [(10 times of Zone1 Impedance) and 0.8 *(Resistance at Max load)]
R1G = Min [(23.30) and (0.8*61.086)]
R1G =Min [233 and 48.869]
R1G = 48.869 Ω
R1PH = Minimum of [(10 times of Zone1 Impedance) and 0.6 *(Resistance at Max load)]
R1PH = Min [(10*23.30) and (0.6*61.086)]
R1PH =Min [233 and 36.65]
R1PH = 36.65 Ω
Zone 2
Zone 2 = Minimum of [[Maximum of ((Protection line+ (0.5*Adjacent shortest line))
AND (1.2*Protection line)] (Protection line+ (0.5*Transformer impedance)]
= Min of [[Max of [(29.129+ (0.5*8.356)) and (1.2*29.129] & (29.129+0.5*17.67)]
= Min of [[Max of 33.307 and 34.95] and 37.96]
Zone 2 = 34.95 Ω
tz2 = 0.35 sec
Kz1 = (Z0-Z1/3*Z1)
= (0.57146+j1.83241)-(0.09705+j0.39314) -/3(0.09705+j0.39314)
Zero sequence Line impedance = 1.247 ∟-4.378
Kz1 Magnitude = 1.247
Kz1 angle = - 4.378 degree
R2G = Min [10 times of Zone 2 Impedance and 0.8*Resistance at Max load]
= Min [10*34.95) and 0.8*61.086]
R2G = Min [349.5 and 48.869]
R2PH = Min [10 times of Zone 2 Impedance and 0.8*Resistance at Max load]
= Min [10*34.95) and 0.6*61.086]
R2PH = Min [349.5 and 36.65]
R2PH = 36.65 Ω
10
Zone 3
Zone3= [MIN OF (1.2(Protection line) +Adjacent Long line) & (Protection line Adjacent Long
line+25% Second Adjacent Long Line) & (Protection line+ Transformer impedance)]
= Min of (1.2*29.129+ 28.208) & (29.129+28.208+0.25*5.726) and (29.129+17.670)
= Min of (63.163 and 58.768 & 46.799)
Zone3 = 46.799 Ω
tz3 = 1 sec
Kz1 = (Z0-Z1/3*Z1)
= (0.57146+j1.83241)-(0.09705+j0.39314) -/3(0.09705+j0.39314)
Zero sequence Line impedance = 1.247 ∟-4.378
Kz1 Magnitude = 1.247
Kz1 angle = - 4.378 degree
R3G= Min [10 times of Zone 3 Impedance and 0.8*Resistance at Max load]
= Min [10*46.799 and 0.8*61.086]
= Min of [467.99 and 48.8688]
R3G = 48.869 Ω
R3PH= Min [10 times of Zone 3 Impedance and 0.6*Resistance at Max load]
= Min [10*46.799 and 0.6*61.086]
= Min of [467.99 and 36.65]
R3PH= 36.65 Ω
Zone 4
Zone4 = 0.25 *Zone1 ; Zone4 = 0.25* 23.30 Ω
Zone4 = 5.82 Ω
tz4 = 1 sec
11
Power Swing:
Criteria 1:
∆f = 5Hz (As Per Manufacturer Specification)
∆R = 0.032*∆f*Maximum Loadability
= 0.032*5*40.35
= 6.456 Ω
∆X = 0.032*∆f*Maximum Loadability
= 0.032*5*40.35
= 6.456 Ω
Criteria 2:
∆R =∆X = 20% of R3 Ph
= 0.2 * 36.69
= 7.33 Ω
So a setting below the value can be retained of it.
12
1.2 Procedure for Relay setting Calculation for MiCOM P433 Distance relay
Data required
1. Positive sequence Line impedance = R1+jX1
2. Zero sequence Line impedance = R0+JX0
3. CT Ratio
4. PT Ratio
5. Protected Line Length in kms
6. Adjacent Shortest Line Length in kms
7. Adjacent Longest Line Length in kms
8. Adjacent Second Longest Line Length in kms
9. Voltage ratio of the transformer at the remote end if any.
10. MVA of the transformer at the Remote end
11. % Impedance of the transformer at remote end
12. Maximum load on the feeder in Amperes
Calculation Procedure
The relay settings are in terms of impedance that is R and X
Total Positive sequence impedance of protected line with reference to primary
ZPL = [ZPL (Ohms /km)*Protected Line Length (km)]
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT ratio/PT ratio)
Reactance of protected line = ZPL W.R.T Secondary *SIN(Line angle)
Resistance of protected line= ZPL W.R.T Secondary *COS (Line angle)
Positive sequence impedance Angle = Tan-1(X1/R1)
Similarly the Impedance for Adjacent Shortest Line ZSL, Adjacent Remote Long
Line ZLL and second Adjacent Long Line Z2LL can be calculated.
Total Transformer Impedance ZT(At Remote end) =
(% Transformer Impedance) *((KV) 2/MVA)]
Zero sequence impedance Z0 = √R0 +X02
2
Zero sequence impedance Angle Z0 = Tan-1(X0/R0)
Loadability:
The Limiting conditions for setting the distance relay reach to avoid encroachment into loads.
As per “Reliability Standard PRC-023”, the maximum impedance for the distance relay
characteristics along 30º on the impedance plane for 0.85 per unit rated voltage and the
maximum specified current for each condition.
The maximums Load w.r.t Secondary Zmax = 0.85*VL-L/ (√3*1.5*.IL)
Where IL corresponds to thermal limit of the conductor.
The Resistance reach corresponding to Zmax w.r.t Secondary
R = Zmax *COS (30)
The Reactance reach corresponding to Zmax w.r.t Secondary
X= Zmax *SIN (30)
13
The New impedance for Parallel line drawn parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts
the Resistance axis is Z new= X (at Zmax) /SIN (Line angle)
The New Resistance from Known Reactance Rnew = Znew* COS (Line angle)
Resistance reach of Relay Characteristics obtained from maximum loadability condition
Resistive Reach R = (R correspond to Zmax – Rnew)
Zone Settings
Zone 1
Zone 1 = 80 % of Protection Line
X1 = Z1 * SIN (Line Angle)
Kz 1 Zero sequence compensation
Kz1 = (Z0-Z1/3*Z1)
Kz1 angle = angle of Kz1
As per manufacturer’s specification the maximum X/R ratio allowed is 10, hence considering
this limitation and the maximum loadability limit the minimum of the two is considered
Resistive reach
R2= Zone2 impedance W.R.T Secondary *COS (Line angle)
R1 PH = Minimum of (8* Zone 1 Reactance and Resistance at maximum Load)
R1G = Minimum of (8* Zone 1 Reactance and Resistance at maximum Load)
Zone 2
Zone 2 = Min of [MAX OF ((Protection line+ (0.5*Adjacent shortest line)) and
(1.2*Protection line)] and (Protected line + 05* Transformer impedance)
X2 = Z2 * SIN (Line Angle)
tz2 = if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.3 sec
Kz2 = (Z0-Z1/3*Z1)
Kz2 angle = angle of Kz2
14
R2= Zone2 impedance W.R.T Secondary *COS (Line angle)
R2 PH = Minimum of (8* Zone 2 Reactance and Resistance at maximum Load)
R2 G = Minimum of (8* Zone 2 Reactance and Resistance at maximum Load)
Zone 3
Zone3 = [MIN OF (1.2*Protection line + Adjacent Long line) & (Protection line + Adjacent
Long line +0.25* Adjacent Second Long Line) & (Protection line +Transformer
impedance)]
R3= Zone3 impedance W.R.T Secondary *COS (Line angle)
R3 PH-R4PH = Minimum of (8* Zone 3 Reactance and Resistance at maximum Load)
R3 G-R4G =Minimum of (8* Zone 3 Reactance and Resistance at maximum Load)
tz3 = 1 sec
Zone 4
Zone4 = 0.25 *Zone 1
R4= Zone4 impedance W.R.T Secondary *COS (Line angle)
tz4 = 1 sec
Sample setting calculation for MiCOM P433
Substation : 220 kV Bhakra Power House
Line : 220 kV GSS Bhakra right to 220 kV GSS Mahilpur
Relay Name : Areva MiCOM P433
Data
Positive sequence Line impedance = 0.0797+j0.40651
15
Zero sequence Line impedance = 0.233+j1.329
CT Ratio = 1200A/1A
PT Ratio = 220kV/110V
Protected Line Length(Mahilpur) = 51.1 Km
Adjacent Shortest Line Length (Rehan) = 26.7 Km
Adjacent Longest Line Length (Bhakra Right) = 51.1 Km
Second Longest Line Length = 0 Km
Voltage ratio of the transformer = 220 kV/132 kV
Maximum load on the feeder = 795 A (for Zeebra)
CT/PT ratio = 0.6
Calculation
Positive sequence impedance of Protected line ZPL = √R2+X2
= √(0.07972+0.40652)
ZPL = 0.4142 Ohms/Km
Total Positive sequence impedance of Protected line ZPL=
= [ZPL (Ohms /Km)*Protected Line Length (km)]
= [0.4142 * 51.1]
ZPL W.R.T Primary = 21.167 Ω
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT/PT ratio)
= 21.167 * 0.6
ZPL = 12.70 Ω
Positive sequence impedance of Adjasent Shortest line ZSL = √R2+X2
= √(0.07972+0.40652)
ZSL = 0.4142 Ohms/Km
Total Positive sequence impedance Adjacent Shortest ZSL=
= [Z (Ohms /Km)*Protected Line Length (km)]
= [0.4142 * 26.7]
16
ZSL W.R.T Primary = 11.06 Ω
ZSL W.R.T Secondary = ZSL W.R.T Primary * (CT/PT ratio)
= 11.06 *0.6
ZSL = 6.635 Ω
ZSL W.R.T Secondary = 6.635 Ω
Positive sequence impedance of Adjasent Longest line ZLL = √R2+X2
= √(0.07972+0.40652)
ZLL = 0.4142 Ohms/Km
Total Positive sequence impedance Adjacent Shortest ZLL=
= [Z (Ohms /Km)*Protected Line Length (km)]
= [0.4142 * 51.1]
ZLL W.R.T Primary = 21.167 Ω
ZLL W.R.T Secondary = ZLL W.R.T Primary * (CT/PT ratio)
= 21.167 * 0.6
ZLL W.R.T Secondary = 12.70 Ω
Total Positive sequence impedance of Adjacent Second Longest line Z2LL=
= [Z2LL (Ohms /Km)*Longest Line Length (km)]
= [0.4142 * 0]
Z2LL W.R.T Primary = 0Ω
Z2LL W.R.T Secondary = Z2LL W.R.T Primary * (CT/PT ratio)
= 0 * 0.6
Z2LL W.R.T Secondary = 0 Ω
Positive sequence impedance Angle =Tan-1(X/R)
Line Angle = Tan-1(0.4065/0.0797)
Line Angle = 78.91 Degree
17
The maximums Load w.r.t Secondary ZMAX primary = 0.85*VL-L/(√3*1.5*.IL)
ZMAX = 0.85* 220 /(√3*1.5*795)
[795 A is the maximum capacity of ACSR Zebra conductor]
ZMAX = 90.53 Ω
Corresponding Zmax secondary = Zmax * CT/PT Ratio = 90.53 * 0.6
= 54.32 Ω
The Resistance reach corresponding to Zmax w.r.t Secondary
R = ZMAX *COS (30)
= 54.32*0.8660
R = 47.044 Ω
The Reactance reach corresponding to Zmax w.r.t Secondary
X = ZMAX *SIN (30)
= 54.32*0.5
X = 27.16 Ω
The New impedance for Parallel line Drawn Parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts the Resistance axis is
Znew = X (at Zmax) /SIN(78.91)
= 27.16/ SIN (78.91)
Znew = 27.67 Ω
The New Resistance from Known Reactance Rnew = Znew* COS (78.91)
= 27.67*cos 78.91
R new = 5.322
Resistances reach of Relay Characteristics with respect to secondary
= (R corresponds to Zmax – R new)
R = 47.044 -5.322
R = 41.722 Ω
Zone Settings
Zone 1
18
Zone 1= 80 % of Protection Line
= 0.8 * 12.70
Zone 1 = 10.16 Ω
R1= Zone1 impedance W.R.T Secondary *COS (Line angle)
R1 (PH-PH) = Minimum of (8* Zone 1 Reactance and Resistance at maximum Load)
R1 (PH-E) =Minimum of (8* Zone 1 Reactance and Resistance at maximum Load)
X1PP, X1PG = 10.16* SIN (78.91)
X1PP, X1PG = 9.97 Ω
R1PP = Minimum of (8 *10.16 and 41.722)
R1PP = 41.722 Ω
R1PG = Minimum of (8*10.16 and 41.722)
R1PG= 41.722 Ω
Zone 2
Zone 2 = MIN OF [(Protected Line + 0.5*Transformer impedance at remote end) AND (MAX
OF (Protected line + (0.5*Adjacent shortest line) AND (1.2*Protected line))]
Since Transformer not available in Remote end.
= Max of [(16.02) and (15.24)]
= 16.02 Ω
Zone 2 = 16.02 Ω
tz4 = 0.35 sec
R2= Zone1 impedance W.R.T Secondary *COS (Line angle)
R2 (PH-PH) = Minimum of (8* Zone 2 Reactance and Resistance at maximum Load)
R2 (PH-E) =Minimum of (8* Zone 2 Reactance and Resistance at maximum Load)
X2PP, X2PG =16.02 * SIN (78.91)
19
X2PP, X2PG = 15.72 Ω
R2PP = Minimum of (8* 16.02 and 41.722)
R2PP = 41.722 Ω
R2PG = Minimum of (8* 16.02 and 41.722)
R2PG= 41.722 Ω
Zone 3
Zone3= [MIN OF (1.2(Protected line) +Adjacent Long line) & (Protected line + Adjacent Long
line+25% Second Adjacent Long Line) & (Protected line +Transformer impedance at remote
end)]
Since Transformer not available in Remote end.
= Min of (15.24+ 12.7) & (12.70+12.70+0.25*0)
= Minimum of (27.94 and 25.40)
Zone3 = 25.40
tz3 = 1 sec
R3= Zone1 impedance W.R.T Secondary *COS (Line angle)
R3 (PH-PH) = Minimum of (8* Zone 3 Reactance and Resistance at maximum Load)
R3 (PH-E) =Minimum of (8* Zone 3 Reactance and Resistance at maximum Load)
X3PP, X3PG = 25.4 * SIN (78.91)
X3PP, X3PG = 24.925 Ω
R3PP = Minimum of (8*25.4 and 41.722)
R3PP = 41.722 Ω
R3PG = Minimum of (8*25.4 and 41.722)
R3PG= 41.722 Ω
Zone 4
20
Zone4 = 0.25 *Zone1 Impedance
Zone4 = 0.25*10.16 =2.54
X4 = 5.73 *SIN ( 78.91)
X4 = 2.49 Ω
tz4 = 1 sec
21
1.3Procedure for Relay Setting Calculation For REL670
Calculation
Protected line
Total Positive sequence Resistance of Protected line
R1 W.R.T Primary = [R1 (Ohms /Km)*Protected Line Length (km)]
Total Positive sequence Reactance of Protected line X1 =
X1 W.R.T Primary = [X1 (Ohms /Km)*Protected Line Length (km)]
Adjacent Shortest line
Total Positive sequence Resistance of Adjacent Short Line R =
R1 W.R.T Primary = [R1 (Ohms /Km)*Protected Line Length (km)]
Total Positive sequence Reactance of Adjacent Short LineX1 =
X1 W.R.T Primary= [X1 (Ohms /Km)*Protected Line Length (km)]
Adjacent Long Line
Positive sequence Resistance of Adjacent Longest Line Primary
R1 = [R1 (Ohms /Km)*Longest Line Length (km)]
Total Positive sequence Reactance of Adjacent Long LineX1 =
X1 W.R.T Primary = [X1 (Ohms /Km)* Adjacent Long Line Length (km)]
Transformer Impedance
Total Transformer Impedance ZT (At remote end)
If there is more than one Transformer, the resultant Impedance considering the Transformers are
in parallel is taken.
ZT = (%Transformer Impedance)*((KV) 2/ MVA)]
22
Loadability
Load impedance for (as Per the NERC Loadability)
The maximums Load w.r.t Secondary ZMAX = 0.85*VL-L / (√3*1.5*.IL)
Where ILcorresponds to thermal limit of the conductor.
The Resistance reach corresponding to Zmax w.r.t Secondary
R = ZMAX *COS (30)
The Reactance reach corresponding to Zmax w.r.t Secondary
X=ZMAX *SIN (30)
The New impedance for Parallel line Drawn Parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts the Resistance axis is Znew=X (at Zmax)
/SIN(Line Angle)
The New Resistance from Known Reactance Rnew= Znew* COS (Line Angle)
Resistance reach of Relay Characteristics
= (R corresponds to Zmax – Rnew)
Zero sequence impedance Z0 = √R2+X2
Zero sequence impedance Angle Z0
= Tan-1(X/R)
Protected line
Total Zero sequence Resistance of Protected line R =
Primary = [R0 (Ohms /Km)*Protected Line Length (km)]
Total Zero sequence Reactance of Protected line X0
W.R.T Primary = [ZPL (Ohms /Km)*Protected Line Length (km)]
23
Adjacent Short line
Total Zero sequence Resistance of Adjacent Short line R =
W.R.T Primary = [R0 (Ohms /Km)*Protected Line Length (km)]
Total Zero sequence Reactance of Adjacent Short line X0 =
X0 W.R.T Primary = [ZPL (Ohms /Km)* Adjacent Short line Length (km)]
Adjacent Long Line
Total Zero sequence Resistance of Adjacent Long line R
(Primary) = [R0 (Ohms /Km)* Adjacent Long Line Length (km)]
Zero sequence Reactance of Adjacent Long line X0 =
Total Zero sequence Reactance of Adjacent Long line X0 =
(Primary) = [ZPL (Ohms /Km)* Adjacent Long line Length (km)]
Positive sequence impedance Angle =Tan-1(X/R)
Zone Settings
Zone 1
Phase –Phase
X 1 = 80 % of (Protected Line)
R1 =80 % of (Protected Line)
RFPP = min [(3 times of Zone1 Reach) and 1.6*Zload min*(CosΘ-R1/X1*SinΘ)]
RFPE= min [4.5time Zone1 and [0.8*Zmin*[cos30 – ((2*R1PP+ROPE)/
(2*X1PP+XOPE)*sin30)]
Ref catalogue ABB REL 670 application manual page no 197,198 for the above condition
and the load encroachment function to be enabled for the second condition to prevail.
XO =80 % of (Protected Line Zero Sequence Reactance)
24
RO=80 % of (Protected Line Zero Sequence Resistance)
Zone 2
Phase –Phase
X 1 =Min of ([MAX OF ((Protected Line+ (0.5*Adjacent shortest line)) AND (1.2*Protected
Line)]), Protected Line + 0.5*Transformer Impedance at remote end)
R1 = MAX of ((Protected Line+ (0.5*Adjacent shortest line)) AND (1.2*Protected Line)))
RFPP = min [(3 times of Zone1 Reach) and 1.6*Zload min*(CosΘ-R1/X1*SinΘ)]
RFPE= min [4.5time Zone1 and [0.8*Zmin* [cos30 – ((2*R1PP+ROPE)/(2*X1PP+XOPE)
*sin30)]
X0 = Min of ([MAX OF ((Protected Line+ (0.5*Adjacent shortest line)) AND (1.2*Protected
Line)]),Protected Line+ 0.5*Transformer Impedance at remote end)
RO = MAX of ((Protected Line+ (0.5*Adjacent shortest line)) AND (1.2*Protected Line))
T2pp = if Zone2 > 80 % of the Next Shortest Line then t =0.6 sec else t=0.3 sec
t2pp= 0.35 sec
Zone 3
Phase –Phase
X1= MIN OF [(1.2*Protected Line Adjacent Long line)) & Protected Line Adjacent Long
line+0.25*second Long line & Protected Line+Transformer impedance at remote end]
R1= MIN of [(1.2*Protected Line+Adjacent Long line)) & Protected Line+Adjacent Long
line+0.25*second Long line]
RFPP = min [(3 times of Zone1 Reach) and 1.6*Zload min*(CosΘ-R1/X1*SinΘ)]
RFPE=min [4.5time Zone1 and [0.8*Zmin*[cos30 – ((2*R1PP+ROPE)/
(2*X1PP+XOPE)*sin30)]
X0 = [MIN OF (1.2*Protected Line+Adjacent Long line)) & Protected Line+Adjacent Long
line+0.25*second Long line & Protected Line+ Transformer impedance at remote end]
R0 = [MIN OF (1.2*Protected Line+Adjacent Long line)) & Protected Line+Adjacent Long
line+0.25*second Long line]
tz3 = 1 sec
25
Zone 4
Phase –Phase
X1 =0.25 *Zone 1 reach
RFPP = min [(3 times of Zone1 Reach) and 1.6*Zload min*(CosΘ-R1/X1*SinΘ)]
RFPE= min [4.5time Zone1 and [0.8*Zmin*[cos30 – ((2*R1PP+ROPE)/
(2*X1PP+XOPE)*sin30)]
XO= 0.25* Zone 1 reach
t4=1 sec
Sample setting Calculation for ABB REL 670 Distance Relay
Substation : 220kV Ganguwal
Line : 220kV Ganguwal to Bhakra
Relay Name : REL670
Protected Line
Positive sequence Line impedance = 0.0797+j0.4065
Zero sequence Line impedance = 0.233+j1.329
Adjacent Short Long line
Positive sequence Line impedance = 0.0797+j0.4065
Zero sequence Line impedance = 0.233+j1.329
Adjacent Longest Long line
Positive sequence Line impedance = 0.0797+j0.4065
Zero sequence Line impedance = 0.233+j1.329
Second Adjacent Longest Long line
Positive sequence Line impedance = 0.0797+j0.4065
Zero sequence Line impedance = 0.233+j1.329
CT Ratio = 1200A/1A
PT Ratio = 220kV/110V
ProtectedLineLength = 22.3 Km
Adjacent Shortest LineLength = 22.3 Km
AdjacentLongestLineLength = 86.4 Km
26
Second AdjacentLongestLine = 86.4 Km
Voltage ratio of the transformer = nil
MVA of the transformer at the Remote end = NA
Maximum load on the feeder = 795 A
CT/PT ratio = 0.6
Calculation
Protected line
Positive sequence Impedance of Protected line ZPL = (0.0797+j0.4065)Ohms/Km
Total Positive sequence Impedance of Protected line R =
= [Z1 (Ohms /Km)*Protected Line Length (km)]
= [22.3* (0.0797+j0.4065)]
ZPL W.R.T Primary = 1.77731+j9.06495
R1p-p = 1.77731 Ω =R1p-e
X1p-p = 9.06495 Ω =X1p-e
Zero sequence Impedance of Protected line ZPL = 0.233+j1.329Ohms/Km
Total Zero sequence Impedance of Protected line R =
= [Z1 (Ohms /Km)*Protected Line Length (km)]
= [22.3*(0.233+j1.329)]
ZPL W.R.T Primary = 5.1959+j29.63
ROp-e =5.1959Ω
XOp-e =29.63Ω
Adjacent Shortest line
Positive sequence Impedance of Adjacent Short line ZSL
Total Positive sequence impedance of Adjacent Short Line =
27
Total Positive sequence Impedance of Protected line R =
= [Z1 (Ohms /Km)*Protected Line Length (km)]
= [22.3* (0.0797+j0.4065)]
ZPL W.R.T Primary = 1.77731+j9.06495
ZSLW.R.T Primary = [22.3* (0.0797+j0.4065)]
= 1.77731+j9.06495
R1 W.R.T Primary = 1.77731 Ω
X1 W.R.T Primary = 9.06495 Ω
50% of Positive sequence Impedance of Adjacent Short line
50% ZSL = 0.8886+j4.5324 Ohms/Km
Zero sequence Impedance of Adjacent Short line ZSL
= [22.3*(0.233+j1.329)]Ohms/Km
=5.1959+j29.63
50% of Zero sequence Impedance of Adjacent Short line
ZSL W.R.T Primary = 50% (5.1959+j29.63)
R1 W.R.T Primary = 2.59795Ω
X1 W.R.T Primary = 14.815Ω
Adjacent Long Line
Positive sequence Impedance of Adjacent Longest Line =0.0797+j0.4065Ohms /Km
Total Positive sequence Impedance of Adjacent Longest Line
Z1 = [Z1 (Ohms /Km)*Longest Line Length (km)]
= [0.0797+j0.4065] *86.4]
28
Z1 W.R.T Primary = 6.88+j35.12
R1 W.R.T Primary = 6.88 Ω
X1 W.R.T Primary = 35.12 Ω
Zero sequence Impedance of Adjacent Longest Line=0.233+j1.329Ohms /Km
Z0 = [Z0 (Ohms /Km)*Longest Line Length (km)]
= [0.233+j1.329] * 86.4]
Z0 W.R.T Primary = 20.1312+j114.8256
R0 W.R.T Primary = 20.1312 Ω
X0 W.R.T Primary = 114.8256 Ω
Adjacent Second Long Line
Positive sequence Impedance of Adjacent Longest Line = 0.0797+j0.4065Ohms /Km
25 % of Z2LL = 0.25* [Z1 (Ohms /Km)*Longest Line Length (km)]
=0.25*[0.0797+j0.4065]*86.4)]
=0.25*[6.88+j35.12]
25% of Z2LL Positive sequence W.R.T Primary = (01.72+j8.78)
R1 W.R.T Primary =1.72Ω
X1 W.R.T Primary = 8.78 Ω
Zero sequence Impedance of Adjacent Longest Line= 0.48787+j1.92051Ohms /Km
25 % of Z2LL = [Z0 (Ohms /Km)*Longest Line Length (km)]
Total length = 0.25*(0.233+j1.329)*86.4
25% Z2LL Zero sequence W.R.T Primary = (5.0328+j28.7064)
R1 W.R.T Primary = 5.0328 Ω
X1 W.R.T Primary = 28.7064 Ω
Loadability
29
Load impedance for (as Per the NERC Loadability)
The maximums Load w.r.t Primary ZMAX = 0.85*VL-L/ (√3*1.5*.IL)
ZMAX = 0.85* 220000/√3*1.5*795)
ZMAX= 90.536 Ω
The Resistance reach corresponding to Zmax w.r.t Primary
R = ZMAX *COS (30)
=90.536*0.8660
R = 78.41 Ω
The Reactance reach corresponding to Zmax w.r.t Primary
X=ZMAX *SIN (30)
X = 45. 25 Ω
The New impedance for Parallel line Drawn Parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts the Resistance axis is Znew=X (at Zmax)
/SIN(78.85)
= 45.25 /0.9811
Znew = 46.12 Ω
The New Resistance from Known Reactance Rnew= Znew* COS (78.9)
= 46.12*0.1925
Rnew = 8.879 Ω
Resistance reach of Relay Characteristics
= (R corresponds to Zmax – Rnew)
R = 78.41 – 8.879
R = 69.531 Ω
Resistance reach of Relay Characteristics w r t Primary = 69.531 Ω
30
Positive sequence impedance Angle =Tan-1(X/R)
= Tan-1(X/R)
= Tan-1(0.4065/ 0.0797)
Z1 angle = 78.9 Degree
Zero sequence impedance Angle Z0
= Tan-1(1.329/0.233)
Z0 angle = 80.05 Degree
Zone Settings
Zone 1
Total length =22.3km
Zone 1 Length = 0.8 * Total length
= 0.8*22.3
= 17.84km
Phase –Phase
Zone 1= 80 % of (Protected Line)
= [0.8*(1.77731+9.06495j)]
= 1.421+ j7.2519
X 1PP = 7.2519 Ω
R1PP= 1.421 Ω
RFPP = min [(3 times of Zone1 Reach) and 1.6*Zloadmin*{cosΘ-R1/X1*SinΘ)]
= min of (3*7.25) and 1.6*90.536*{cos30 -1.421/7.2519*sin 30}
RFPP =21.76Ω
Phase –Earth
X 1PP= X1PE= 7.2519 Ω
31
R1PP = R1PE= 1.421 Ω
Zone1 Zero sequence Impedance = 80 % of Protected line Zero sequence impedance
= [0.8*(5.1959+j29.63)]
= 4.15672+j23.704
ROPE = 4.15672 Ω
XOPE = 23.704 Ω
RFPE = min [(4.5 times of Zone1 Reach) and 0.8* Zload max (cos ¢-((2*R1PE + ROPE / 2*
X1PE + XOPE) * sin¢)])]
= min (4.5*7.25) and [0.8*Zload-cos¢-(2*R1PP+ROPE) / (2*X1PP+XOPE)*sin¢
= min (4.5*7.25) and [0.8*90.536*[cos30–2*1.421 +4.156)/(2*7.2519+23.704)*sin30)]
= 32.625
RFPE = 32.625 Ω
Zone 2
Phase –Phase
ZONE2 = [MAX OF ((Protected Line+ (0.5*Adjacent shortest line)), AND (1.2*Protected
Line)] and MIN OF [Protected Line +0.5*Transformer impedance at remote end]
1.2*Protected Line = 1.2*(1.77731+j9.06495)
= (2.132+j10.877)
Protected Line + (0.5*Adjacent shortest line) = (1.77731+j9.06495) + 0.5*(1.77731+j9.06495)
= (2.665965+ j13.597)
X 1PP = 13.597Ω
R1PP = 2.665965Ω
RFPP = min [3 times of X1PP and 1.6*Zloadmin*{cosΘ-R1/X1*SinΘ)]
= (3*13.597) and 1.6* 90.536*{cos30-2.66/13.597*sin30}
32
RFPP = 40.791 Ω
T2pp= if Zone2 > 80 % of the Next Shortest Line then t =0.6 sec else t=0.3 sec
t2pp= 0.350 sec
Phase –Earth
X 1PE = 13.597Ω
R1PE = 2.665965Ω
Zone 2
Zero Sequence = Min of [MAX OF ((Protected Line+ (0.5*Adjacent shortest line)) AND1.2
*Protected Line])
1.2*Protected Line = 1.2 * (5.1959+j29.63)
= 6.236+ j35.55
Protected Line+ (0.5*Adjacent shortest line) = (5.1959+j29.63)+ 0.5*(5.1959+j29.63)
= 7.795 + j44.445
XOPE = 44.445 Ω
ROPE = 7.795 Ω
RFPE = min (4.5*44.445) and [0.8*Zload-cos¢-(2*R1PP+ROPE)/ (2*X1PP+XOPE)*sin¢
= min (200) and 0.8* 90.536- cos(30)-(2*2.66+7.795)/ (2*13.597+44.445)*sin(30)
= 200 and 56.095
RFPE = 56.095 Ω
Zone 3
Phase –Phase
Zone 3= [MIN OF (1.2*Protected Line + Adjacent Long line)), Protected Line +Adjacent Long
line+0.25 second long line)]
1.2*Protected Line+ Adjacent Long line =1.2 *(1.77731+j9.06495) + (6.88+j35.12)
33
= 9.012772+ j45.99
Protected Line +Adjacent Long line+0.25 second long line
= (1.77731+j9.06495) + (6.88+j35.12) + 0.25* (6.88+j35.12)
= 10.377 +j52.964
Zone 3 impedance =9.012772+ j45.99
X1PP = 45.99Ω
R1PP= 9.012772Ω
RFPP= min [3 times of Zone Reach and 1.6*Zloadmin*{cosΘ-R1/X1*SinΘ}]
=min [3 * 45.90 and (1.6*90.536*0.753)]
= 109.077Ω
X1PE = 45.99Ω
R1PE= 9.012Ω
Phase –Earth
Zone 3= [MIN OF (1.2*Protected Line +Adjacent Long line)), Protected Line +Adjacent Long
line+0.25 second long line)]
1.2*Protected Line +Adjacent Long line = 1.2*(5.1959+j29.63)+ (20.1312+j114.8256)
= 26.366+j150.38
Protected Line +Adjacent Long line+0.25 second long line
= (5.1959+j29.63)+(20.1312+j114.8256)+0.25*(20.1312+j114.8256)
= 30.3599+j173.162
XOPE = 150.38Ω
ROPE = 26.366Ω
RFPE = min (4.5*150.38) and [0.8*Zload-cos¢-(2*R1PP+ROPE)/ (2*X1PP+XOPE)*sin¢
34
= min 676.71& (0.8*90.536 [cos(30)-(2*9.012+26.366)/(2*45.99+150.38)*sin(30)]
RFPE = 56.09Ω
tz3 =1 sec
Zone 4
Phase –Phase
Zone4 = 0.25 *Zone 1 impedance = 0.25*(1.421+ j7.2519)
X1PP= 1.812Ω
R1PP= 0.355 Ω
RFPP = min [3 times of Zone Reach and 1.6*Zloadmin*{cosΘ-R1/X1*SinΘ}]
= 3 *1.812and 1.6 *90.536*{cos30-0.355/1.812sin30}
RFPP = 5.436 Ω
Phase –Earth
X1PE= 1.812Ω
R1PE= 0.355Ω
RFPE = min [4.5 times of Zone Reach and [0.8*Zload-cos¢-(2*R1PP+ROPE)/
(2*X1PP+XOPE)*sin¢]
= 4.5*1.812 and 0.8*90.536*0.7744
RFPE = 8.154Ω
Zone4 Zero sequence = 0.25*zone 1 zero sequence= (5.1959+j29.63)*0.25
XOPE =7.4075Ω
ROPE = 1.298Ω
tz4=1 sec
Note: If Arc and Tower footing resistance are known then it is possible to set the correct value
of RFPP and RFPE by taking the consideration as;
35
Criteria 1= Arc resistance
Criteria 2=Arc resistance+Tower footing resistance
Then the equation can be modified as given below;
RFPP= Min(3 times of Zone Reach and 1.6*Zloadmin*{cosΘ-R1/X1*SinΘ}],2*criteria1)
RFPE=min [4.5 times of Zone Reach and [0.8*Zload-cos¢-(2*R1PP+ROPE)/
(2*X1PP+XOPE)*sin¢, 2*criteria 2]
1.4 Procedure for Relay setting Calculation for SIEMENS SIPROTECH 7SA52X/7SA61X
Data required
1. Positive sequence Line impedance = R1+jX1
2. Zero sequence Line impedance = R0+JX0
3. CT Ratio
4. PT Ratio
36
5. Protected Line Length in kms
6. Adjacent Shortest Line Length in kms
7. Adjacent Longest Line Length in kms
8. Adjacent Second Longest Line Length in kms
9. Voltage ratio of the transformer at the remote end if any.
10. MVA of the transformer at the Remote end
11. % Impedance of the transformer at remote end
12. Maximum load on the feeder in Amperes
Calculation Procedure
The relay settings are in terms of impedance that is R and X
Total Positive sequence impedance of protected line with reference to primary
ZPL = [ZPL (Ohms /km)*Protected Line Length (km)]
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT ratio/PT ratio)
Reactance of protected line = ZPL W.R.T Secondary *SIN(Line angle)
Resistance of protected line= ZPL W.R.T Secondary *COS (Line angle)
Positive sequence impedance Angle = Tan-1(X1/R1)
Similarly the Impedance for Adjacent Shortest Line ZSL, Adjacent Remote Long
Line ZLL and second Adjacent Long Line Z2LL can be calculated.
Total Transformer Impedance ZT (At remote end)
If there is more than one Transformer, the resultant Impedance considering the Transformers
are in parallel is taken.
ZT = (%Transformer Impedance)*((KV) 2/ MVA)]
Zero sequence impedance Z0 = √R02+X02
Zero sequence impedance Angle Z0 = Tan-1(X0/R0)
Loadability:
The Limiting conditions for setting the distance relay reach to avoid encroachment into
loads. As per “Reliability Standard PRC-023”, The maximum impedance for the distance
relay characteristics along 30º on the impedance plane for 0.85 per unit rated voltage and
the maximum specified current for each condition.
The maximums Load w.r.t Secondary Zmax = 0.85*VL-L/ (√3*1.5*.IL)
Where IL corresponds to thermal limit of the conductor.
The Resistance reach corresponding to Zmax w.r.t Secondary
R = Zmax *COS (30)
The Reactance reach corresponding to Zmax w.r.t Secondary
X= Zmax *SIN (30)
The New impedance for Parallel line drawn parallel to the Line impedance passing
through Zmax to the point at which the parallel line cuts
the Resistance axis is Z new= X (at Zmax) /SIN (Line angle)
The New Resistance from Known Reactance Rnew = Znew* COS (Line angle)
37
Resistance reach of Relay Characteristics obtained from maximum loadability condition
Resistive Reach R = (R correspond to Zmax – Rnew)
Zone Settings
Zone 1
Zone 1 = 80 % of Protection Line
R1= Zone1 impedance W.R.T Secondary *COS (Line angle)
Zone 2
Zone 2 = Min of [MAX OF ((Protection line+ (0.5*Adjacent shortest line)) AND
(1.2*Protection line)] & (Protection line+ 0.5*Transformer Impedance at remote end)
tz2 = if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.35 sec
R2= Zone2 impedance W.R.T Secondary *COS (Line angle)
R2 (PH-PH) = R2 + (Arc Resistance / 2)
R2 (PH-E) = R2 + Arc Resistance + Tower Footing Resistance
Zone 3
Zone3 = [MIN OF (1.2*Protection line + Adjacent Long line) & (Protection line +
Adjacent Long line +0.25* Adjacent Second Long Line) & (Protection line +Transformer
impedance))]
R3= Zone3 impedance W.R.T Secondary *COS (Line angle)
R3 (PH-PH) = R3 + (Arc Resistance / 2)
R3 (PH-E) = R3 + Arc Resistance + Tower Footing Resistance
tz3 = 1 sec
Zone 4
Zone4 = 0.25 *Zone 1
R4= Zone4 impedance W.R.T Secondary *COS (Line angle)
38
R4 (PH-PH) = R4 + (Arc Resistance / 2)
R4 (PH-E) = R4 + Arc Resistance + Tower Footing Resistance
tz4 = 1sec
Power Swing Blocking:
As per manufactures specification power swing zone has a minimum distance
Zdiff of 5 Ω (at inom = 1 A) or 1 Ω(at inom = 5 A)
39
Sample setting calculation for SIPROTECH 7SA522
Substation : Charkhi Dadri
Line : Charkhi dadri to Khethri I
Relay Name : SIEMENS SIPROTECH 7SA522
Data
Protected Line
Positive sequence Line impedance = 0.0797+j0.4065
Zero sequence Line impedance = 0.233+j1.329
Adjacent Short Long line
Positive sequence Line impedance = 0.0797+j0.4065
Zero sequence Line impedance = 0.233+j1.329
Adjacent Longest Long line
Positive sequence Line impedance = 0.0797+j0.4065
Zero sequence Line impedance = 0.233+j1.329
Second Adjacent Longest Long line
Positive sequence Line impedance = 0.0797+j0.4065
Zero sequence Line impedance = 0.233+j1.329
CT Ratio = 600A/1A
PT Ratio = 220kV/110V
Protected Line Length = 71.61 Km
Adjacent Shortest Line Length (Khethri) = 34.5 Km
Adjacent Longest Line Length (Heerapura) = 144 Km
Second Longest Line Length (Heerapura -Khethri) = 139 Km
Voltage ratio of the transformer = 220kV/132kV
MVA of the transformer at the Remote end = 3*100 MVA and 1*150 MVA
Impedance of the transformer = %12,08, % 10.35, %9.65, %10.98
Maximum load on the feeder = 795 A
CT/PT ratio = 0.3
Calculation
Positive sequence impedance of Protected line ZPL = √R2+X2
= √(0.07972+0.40652)
ZPL = 0.414 Ohms/Km
40
Total Positive sequence impedance of Protected line ZPL=
= [ZPL (Ohms /Km)*Protected Line Length (km)]
= [0.414 * 71.61]
ZPL W.R.T Primary = 29.66 Ω
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT/PT ratio)
= 29.66 *0.3
ZPL = 8.90 Ω
Positive sequence impedance of Adjacent Shortest line ZSL= √R2+X2
= √(0.07972+0.40652)
ZSL = 0.414 Ohms/Km
Total Positive sequence impedance Adjacent Shortest ZSL=
= [Z (Ohms /Km)*Adjacent short Line Length (km)]
= [0.414 * 34.5]
ZSL W.R.T Primary = 14.29 Ω
ZSL W.R.T Secondary = ZSL W.R.T Primary * (CT/PT ratio)
= 14.29 * 0.3
ZSL W.R.T Secondary = 4.29 Ω
Positive sequence impedance of Adjacent Longest line ZLL = √R2+X2
= √(0.07972+0.40652)
ZLL = 0.414 Ohms/Km
Total Positive sequence impedance of Adjacent Longest line ZLL=
= [ZLL (Ohms /Km)*Longest Line Length (km)]
= [0.414 * 144]
ZLL W.R.T Primary = 59.65 Ω
41
ZLL W.R.T Secondary = ZLL W.R.T Primary * (CT/PT ratio)
= 59.65 * 0.3
ZLL W.R.T Secondary = 17.90 Ω
Positive sequence impedance of Adjacent Second Longest line ZS = √R2+X2
= √(0.07972+0.40652)
Z2LL = 0.414 Ohms/Km
Total Positive sequence impedance of Adjacent Second Longest line Z2LL=
= [Z2LL (Ohms /Km)*Longest Line Length (km)]
= [0.414 * 144]
Z2LL W.R.T Primary = 57.58 Ω
Z2LL W.R.T Secondary = Z2LL W.R.T Primary * (CT/PT ratio)
= 57.58 * 0.3
Z2LL W.R.T Secondary = 17.27 Ω
Total Transformer Impedance ZT (Remote):
If there are more than one Transformer, the resultant Impedance considering the Transformers
are in parallel is taken.
Considering Transformers are connected in parallel
Total Transformer Impedance ZT (Remote) = (% Transformer Impedance) *((kV) 2/MVA)]
Transformer 1 Impedance Z1 = 0.0965*(2202/100)
= 46.706 Ω
Transformer 1 Impedance Z2 = 0.1208*(2202/100)
= 58.4672 Ω
Transformer 1 Impedance Z3 = 0.1035*(2202/100)
= 50.094 Ω
Transformer 1 Impedance Z4 = 0.1098*(2202/150)
42
= 35.4288 Ω
Total Transformer Impedance W.R.T primary ZT = 1/ ((1/Z1) + (1/Z2) + (1/Z3) + (1/Z4))
ZT = 1/ ((1/46.706)+(1/58.467)+(1/50.094)+(1/35.4288))
ZT = 11.5337 Ω
Load impedance for (as Per the NERC loadability)
Positive sequence impedance Angle =Tan-1(X/R)
Z1= Tan-1(0.415/.0741)
Line Angle = 78.91 Degree
The maximums Load w.r.t Secondary ZMAX primary = 0.85*VL-L/(√3*1.5*.IL)
ZMAX = 0.85* 220 / (√3*1.5*795)
[795 A is the maximum capacity of ACSR Zebra conductor]
ZMAX = 90.53 Ω
Corresponding Zmax secondary = Zmax * CT/PT Ratio = 90.53 * 0.3 = 27.159 Ω
The Resistance reach corresponding to Zmax w.r.t Secondary
R = ZMAX *COS (30)
= 27.159 *0.8660
R = 23.519 Ω
The Reactance reach corresponding to Zmax w.r.t Secondary
X = ZMAX *SIN (30)
= 27.159 *0.5
X = 13.579 Ω
The New impedance for Parallel line Drawn Parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts the Resistance axis is
Znew = X (at Zmax) /SIN(78.91)
= 13.579/ SIN(78.91)
Znew = 13.83 Ω
The New Resistance from Known Reactance Rnew = Znew* COS (78.91)
= 13.83*cos 78.91
43
R new = 2.66
Resistances reach of Relay Characteristics
= (R corresponds to Zmax – R new)
R = 23.519 -2.66
R = 20.86 Ω
Tower Footing Resistance assuming = 10 Ω in secondary
Arc Resistance(Ph-Ph) assuming = 10 Ω in secondary
Zone Settings
Zone 1
Zone 1= 80 % of Protection Line
= 0.8* 8.90
Zone 1 = 7.12 Ω
R1= Zone1 impedance W.R.T Secondary *COS (Line angle)
R1 (PH-PH) = R1 + (Arc Resistance / 2)
R1 (PH-E) = R1 + Arc Resistance + Tower Footing Resistance
R1 = 7.12* COS (78.91)
R1 = 1.37 Ω
R1(PH-PH) = 1.37 +(10/2)
R1(PH-PH) = 6.37Ω
R1(PH-PE) = 1.37+10+10
R1(PH-PE)= 21.37 Ω
Zone 2
44
Zone 2 = MIN OF [MAX OF (Protected line + (0.5*Adjacent shortest line) and (1.2*Protected
line)] and (Protected Line + 0.5*Transformer impedance at remote end)
= Min Of [Max of [(8.90+ (0.5*4.29) and (1.2*8.90)] and (8.90+0.5*3.46)
= Min Of [Max of [11.045 and 10.68] and 10.63
= 11.045 and 10.68
Zone 2 = 10.63 Ω
tz2 = 0.35 sec
R2= Zone 2 impedance W.R.T Secondary *COS(Line angle)
R2 (PH-PH) = R2 + (Arc Resistance / 2)
R2 (PH-E) = R2 + Arc Resistance + Tower Footing Resistance
R2 = 10.63 * COS (78.91)
R2 = 2.044 Ω
R2(PH-PH) = 2.044 +(10/2)
R2(PH-PH) = 7.05 Ω
R2(PH-PE) = +10+10
R2(PH-PE)= 22.05 Ω
Zone 3
Zone3= MIN OF [(1.2(Protected line) +Adjacent Long line) & (Protected line + Adjacent Long
line+25% Second Adjacent Long Line) & (Protected line +Transformer impedance)]
= Min of (1.2*8.90+ 17.90) & (8.90+17.90+0.25*17.27) and (8.90+3.46)
=Min of (28.58 and 31.117 & 12.36)
Zone3 = 12.36 Ω
tz3 = 1 sec
R3= Zone 3 impedance W.R.T Secondary *COS(Line angle)
R3 (PH-PH) = R3 + (Arc Resistance / 2)
R3 (PH-E) = R3 + Arc Resistance + Tower Footing Resistance
45
R3 = 12.36 * COS (78.91)
R3 = 2.377 Ω
R3(PH-PH) = 2.377 +(10/2)
R3(PH-PH) = 7.377 Ω
R3(PH-PE) = 2.377+10+10
R3(PH-PE)= 22.377 Ω
Zone 4
Zone4 = 0.25 *Zone1
Zone4 = 0.25*7.12
Zone4 = 1.78 Ω
tz4 = 1sec
R4= Zone 3 impedance W.R.T Secondary *COS(Line angle)
R4 (PH-PH) = R3 + (Arc Resistance / 2)
R4 (PH-E) = R3 + Arc Resistance + Tower Footing Resistance
R4 = 1.78 * COS (78.91)
R4 = 0.342 Ω
R4(PH-PH) = 0.342 +(10/2)
R4(PH-PH) = 5.342 Ω
R4(PH-PE) = 0.342+10+10
R4(PH-PE)= 20.342 Ω
1.5 Procedure for Relay setting Calculation for GE D60
Data required
1. Positive sequence Line impedance = R1+jX1
2. Zero sequence Line impedance = R0+JX0
3. CT Ratio
4. PT Ratio
5. Protected Line Length in kms
46
6. Adjacent Shortest Line Length in kms
7. Adjacent Longest Line Length in kms
8. Voltage ratio of the transformer at the remote end if any
9. MVA of the transformer at the Remote end
10. % Impedance of the transformer at remote end
11. Maximum load on the feeder in Amperes
Calculation Procedure
The relay settings are in terms of impedance that is Z
Total Positive sequence impedance of protected line with reference to primary
ZPL = [ZPL (Ohms /km)*Protected Line Length (km)]
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT ratio/PT ratio)
Positive sequence impedance Angle = Tan-1(X1/R1)
Similarly the Impedance for Adjacent Shortest Line ZSL, Adjacent Remote Long
Line ZLL and second Adjacent Long Line Z2LL can be calculated.
Total Transformer Impedance ZT (At remote end)
If there is more than one Transformer, the resultant Impedance considering the Transformers
are in parallel is taken.
ZT = (%Transformer Impedance)*((KV) 2/ MVA)]
Zero sequence impedance Z0 = √R02+X02
Zero sequence impedance Angle Z0 = Tan-1(X0/R0)
Loadability:
The Limiting conditions for setting the distance relay reach to avoid encroachment into loads.
As per “Reliability Standard PRC-023”, The maximum impedance for the distance relay
characteristics along 30º on the impedance plane for 0.85 per unit rated voltage and the
maximum specified current for each condition.
The maximums Load w.r.t Secondary Zmax = 0.85*VL-L/ (√3*1.5*.IL)
47
Where IL corresponds to thermal limit of the conductor.
The Resistance reach corresponding to Zmax w.r.t Secondary
R = Zmax *COS (30)
The Reactance reach corresponding to Zmax w.r.t Secondary
X= Zmax *SIN (30)
The New impedance for Parallel line drawn parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts
the Resistance axis is Z new= X (at Zmax) /SIN (Line angle)
The New Resistance from Known Reactance Rnew = Znew* COS (Line angle)
Resistance reach of Relay Characteristics obtained from maximum Loadability condition
Resistive Reach R = (R correspond to Zmax – Rnew)
Zone Settings
Zone 1
Zone 1 = 80 % of Protection Line
Zone 2
48
Zone 2 = Min of [MAX of ((Protection line+ (0.5*Adjacent shortest line)) and
(1.2*Protection line)] and (Protected line + 0.5* Transformer impedance at remote
end)
tz2 = if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.3 sec
Zone 3
Zone3 = [MIN OF (1.2*Protection line + Adjacent Long line) & (Protection line + Adjacent
Long line +0.25* Adjacent Second Long Line) & (Protection line + (Transformer
impedance))]
tz3 = 1 sec
Zone 4
Zone4 = 0.25 *Zone 1
tz4 = 1 sec
Power Swing:
Inner Forward Reach = Zone 3 Reach
Outer Forward Reach = 1.2* Inner Forward Reach
49
Sample setting calculation for GE D60 Distance Relay
Substation : 400kV GSS Bhiwani
Line : 400kV Bhiwani to 400kV Hissar
Relay Name : GE D60
DATA:
Protected Line
Positive sequence Line impedance = 0.026626+j0.330931
Zero sequence Line impedance = 0.261887+j1.03144
Adjacent Short Long line
Positive sequence Line impedance = 0.026626+j0.330931
Zero sequence Line impedance = 0.261887+j1.03144
Adjacent Longest Long line
Positive sequence Line impedance = 0.026626+j0.330931
Zero sequence Line impedance = 0.261887+j1.03144
CT Ratio = 1000A/1A
PT Ratio = 400kV/110V
Protected Line Length = 32.74 km
Adjacent Shortest Line Length = 65.4 km
Adjacent Longest Line Length = 212 km
Voltage ratio of the transformer = 400kV/220kV
MVA of the transformer at the Remote end = 3*315 MVA
Impedance of the transformer = 12.52%, 12.52% & 12.52%
Maximum load on the feeder = 900 A
50
CT/PT ratio = 0.275
Calculation
Protected line
Positive sequence impedance of Protected line ZPL = √R2+X2
= √0.0266262+ 0.3309312
ZPL = 0.332 Ohms/Km
Total Positive sequence impedance of Protected line ZPL=
= [ZPL (Ohms /Km)*Protected Line Length (km)]
= [0.332 * 32.74]
ZPL W.R.T Primary = 10.869 Ω
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT/PT ratio)
= 10.84 * 0.275
ZPL = 2.989 Ω
Positive sequence impedance of Adjacent Shortest line ZPL = √R2+X2
= √0.0266262+ 0.3309312
ZSL = 0.332 Ohms/Km
Total Positive sequence impedance Adjacent Shortest ZSL=
= [Z (Ohms /Km)*Protected Line Length (km)]
= [0.332 * 65.4]
ZSL W.R.T Primary = 21.71 Ω
ZSL W.R.T Secondary = ZSL W.R.T Primary * (CT/PT ratio)
= 21.71*0.275
ZSL W.R.T Secondary = 5.97 Ω
51
Total Positive sequence impedance of Adjacent Longest line ZLL=
= [ZLL (Ohms /Km)*Longest Line Length (km)]
= [0.332* 212]
ZLL W.R.T Primary = 70.384 Ω
ZLL W.R.T Secondary = ZLL W.R.T Primary * (CT/PT ratio)
= 70.384 * 0.275
ZLL W.R.T Secondary = 19.355 Ω
Total Transformer Impedance ZT (Remote):
If there are more than one Transformer, the resultant Impedance considering the Transformers
are in parallel is taken.
Considering Transformers are connected in parallel
Total Transformer Impedance ZT (Remote) = (% Transformer Impedance) *((kV) 2/MVA)]
Transformer Impedance of Z1 = [0.1252*(4002/315)]
= 63.59 Ω
Transformer Impedance of Z2 = [0.1252*(4002/315)]
= 63.59 Ω
Transformer Impedance of Z3 = [0.1252*(4002/315)]
= 63.59 Ω
Total Transformer Impedance ZT (Remote) = 1/((1/Z1)+ (1/Z2) + (1/Z3))
ZT (Remote) = 1/((1/63.59)+(1/3.59)+(1/63.59))
Transformer Impedance W.R.T primary ZT = 21.197 Ω
Total Transformer Impedance ZT (Remote) Secondary = ZT (Remote) *(CT/PT ratio)
= 21.197 * 0.275
Transformer Impedance W.R.T Secondary ZT = 5.829 Ω
52
Loadability
Positive sequence impedance Angle =Tan-1(X/R)
Z1= Tan-1(0.33/0.0266)
Line Angle = 85.40 Degree
The maximums Load w.r.t Secondary ZMAX primary = 0.85*VL-L/(√3*1.5*.IL)
ZMAX = 0.85* 400 / (√3*1.5*900)
[900 A is the maximum capacity of ACSR Markulla and Moose conductor]
ZMAX = 145.41 Ω
Corresponding Zmax secondary = Zmax * CT/PT Ratio = 145.41 * 0.275 = 40.01 Ω
The Resistance reach corresponding to Zmax w.r.t Secondary
R = ZMAX *COS (30)
= 40.01*0.8660
R = 34.648 Ω
The Reactance reach corresponding to Zmax w.r.t Secondary
X = ZMAX *SIN (30)
= 40.01 * 0.5
X = 20.00 Ω
The New impedance for Parallel line Drawn Parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts the Resistance axis is
Znew = X (at Zmax) /SIN(85.4)
= 20.00 / 0.9967
Znew = 20.066 Ω
The New Resistance from Known Reactance Rnew = Znew* COS (85.4)
= 20.066 *0.080
R new = 1.609
Resistances reach of Relay Characteristics
= (R corresponds to Zmax – R new)
53
R = 34.648 -1.609
R = 33.0219 Ω
Zero sequence impedance Z0 = √R02+X02
= √0.2618872+1.031442
Z0 = 1.064 Ω
Zero sequence impedance Angle Z0 = Tan-1(X0/R0)
= Tan-1(1.03144 / 0.26188)
Z0 = 75.75 Degree
Positive sequence impedance Angle = Tan-1(X/R)
Z1= Tan-1(0.330931/0.026626)
Z1= 85.40 Degree
Zone Settings
Zone 1
Zone 1= 80 % of Protection Line
=0.8* 2.989
Zone 1 = 2.391 Ω
Zone 2
Zone 2 = MIN of [[MAX OF ((Protection line+ (0.5*Adjacent shortest line)) AND
(1.2*Protection line)]( Protection line+ (0.5*Transformer impedance at remote end)]
= Min of [[Max of [(2.989+ (0.5*5.97)) and (1.2*2.989) and (2.989 + 0.5*5.829)]
= Min of [[Max of 5.974 and 3.586] 5.90]
Zone 2 = 5.90 Ω
tz2 = if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.35 sec
tz2 = 0.35 sec
54
Zone 3
Zone3= [MIN OF (1.2(Protection line) +Adjacent Long line) & (Protection line+Adjacent Long
line+25% Second Adjacent Long Line) & (Protection line +Transformer impedance)]
= Min of (1.2*2.989+ 19.355) & (2.989+19.355+0.25*0) and (2.989+5.829)
=Min of (22.941 & 22.344 and 8.818)
Zone3 = 8.818 Ω
tz3 = 1.0 sec
Zone 4
Zone4 = 0.25 *Zone1
= 0.25* 2.3912
Zone4 = 0.5978 Ω
tz4 = 1 sec
Power Swing:
Inner Forward Reach = Zone 3 Reach
= 8.818 Ω
Outer Forward Reach = 1.2* Inner Forward Reach
= 1.2* 8.818
= 10.58 Ω
55
1.6 Procedure for Relay setting Calculation for EPAC 3000
Data required
1. Positive sequence Line impedance = R1+jX1
2. Zero sequence Line impedance = R0+JX0
3. CT Ratio
4. PT Ratio
5. Protected Line Length in kms
6. Adjacent Shortest Line Length in kms
7. Adjacent Longest Line Length in kms
8. Voltage ratio of the transformer at the remote end if any
9. MVA of the transformer at the Remote end
10. % Impedance of the transformer at remote end
11. Maximum load on the feeder in Amperes
Calculation Procedure
The relay settings are in terms of impedance that is Z
Total Positive sequence impedance of protected line with reference to primary
ZPL = [ZPL (Ohms /km)*Protected Line Length (km)]
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT ratio/PT ratio)
Positive sequence impedance Angle = Tan-1(X1/R1)
Similarly the Impedance for Adjacent Shortest Line ZSL, Adjacent Remote Long
Line ZLL and second Adjacent Long Line Z2LL can be calculated.
Total Transformer Impedance ZT (At remote end)
If there is more than one Transformer, the resultant Impedance considering the Transformers
are in parallel is taken.
ZT = (%Transformer Impedance)*((KV) 2/ MVA)]
Zero sequence impedance Z0 = √R02+X02
Zero sequence impedance Angle Z0 = Tan-1(X0/R0)
Zone Settings
Zone 1
Zone 1 = 80 % of Protection Line
Kz 1 Zero sequence compensation
Kz1 = (Z0-Z1/3*Z1)
56
Kz1 angle = angle of Kz1
As per manufacturer’s specification the maximum X/R ratio allowed is 10, hence considering
this limitation and the maximum loadability limit the minimum of the two is considered
Resistive reach
R1G= Minimum of [(10 times of Zone1 Reactance) and 0.8 *Resistive Reach (loadability)]
R1PH= Minimum of [(10 times of Zone1 Reactance) and 0.6 *Resistive Reach (loadability)]
Zone 2
Zone 2 = Min of [MAX OF ((Protection line+ (0.5*Adjacent shortest line)) AND
(1.2*Protection line)] and (Protected line + Transformer impedance at remote end)
tz2 = if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.3 t0 0.35 sec
Kz2 = (Z0-Z1/3*Z1)
Kz2 angle = angle of Kz2
R2G= Minimum of [(10 times of Zone1 Reactance) and 0.8 *Resistive Reach (loadability)]
R2PH= Minimum of [(10 times of Zone1 Reactance) and 0.6 *Resistive Reach (loadability)]
Zone 3
Zone3 = [MIN OF (1.2*Protection line + Adjacent Long line) & (Protection line + Adjacent
Long line +0.25* Adjacent Second Long Line) & (Protection line + (Transformer impedance at
remote end))]
R3G= Minimum of [(10 times of Zone1 Reactance) and 0.8 *Resistive Reach (loadability)]
R3PH= Minimum of [(10 times of Zone1 Reactance) and 0.6 *Resistive Reach (loadability)]
tz3 = 1 sec
Zone 4
Zone4 = 0.25 *Zone 1
tz4 = 1 sec
57
Sample setting calculation for EPAC 3000 Distance Relay
DATA:
Substation name: 220kV GSS Kurukshethra
Protected feeder: 220kV Kurukshetra to 220kV Jagadhri
Protected Line Length : 48.29 km
Adjacent Shortest Line Length : 158 km ( 220 kV Gangual )
Adjacent Longest Line Length : 158 km ( 220 kV Gangual )
Second Adjacent Longest Line : 110 km (Dhulkote)
Protected Line
Positive sequence Line impedance = 0.07411+j0.40988
Zero sequence Line impedance = 0.29524+j1.260416
Adjacent Short Long line
Positive sequence Line impedance = 0.07505+j0.415
Zero sequence Line impedance = 0.2989+j1.2804
Adjacent Longest Long line
Positive sequence Line impedance = 0.07505+j0.415
Zero sequence Line impedance = 0.2989+j1.2804
Adjacent Second Longest Long line
Positive sequence Line impedance = 0.09944+j0.4004
Zero sequence Line impedance = 0.5746+j1.9712
Nomber of Remote end Transformers : 3
Voltage Ratio of Transformer on Remote Bus: 220/132 kV
Remote end Transformer MVA: 60 MVA
% Impedance of the Remote end Transformer: 9.76 %, 10.1%, 11.1%
CT Ratio : 1200/1
58
PT Ratio : 220 kV/110 V
CT/PT Ratio: 1200/2000 = 0.6
Positive Sequence Impedance of Protected Line = √ ( R12 +X12)
=√( 0.074112+0.409882)
ZPL = 0.416 Ω/km
Total Positive Sequence of Protected Line w.r.t. Primary = ZPL * Line Length
= 0.416*48.29
=20.11Ω
Total Positive Sequence Impedance w.r.t. Secondary = 18.99 * CT/PT Ratio
= 20.11*0.6
ZPL Secondary =12.068 Ω
Positive Sequence Impedance of Shortest Line ZSL = √ ( R12 +X12)
=√( 0.075052+ 0.4152)
ZSL = 0.421 Ω/km
Total Positive Sequence of Protected Line w.r.t. Primary = ZSL * Line Length
= 0.421*158
= 66.633 Ω
Total Positive Sequence Impedance w.r.t. Secondary = ZSL * CT/PT Ratio
= 66.633 * 0.6
ZSL Secondary = 39.98 Ω
Positive Sequence Impedance of Longest Line ZLL = √ ( R12 +X12)
=√( 0.075052+ 0.4152)
ZLL = 0.421 Ω/km
Total Positive Sequence of Protected Line w.r.t. Primary = ZLL * Line Length
= 0.421*158
= 66.633 Ω
Total Positive Sequence Impedance w.r.t. Secondary = ZLL * CT/PT Ratio
59
= 66.633 * 0.6
ZLL Secondary = 39.98 Ω
Positive Sequence Impedance of Second Longest Line Z2LL = √ ( R12 +X12)
=√( 0.099442+ 0.40042)
Z2LL = 0.412 Ω/km
Total Positive Sequence of Protected Line w.r.t. Primary = Z2LL * Line Length
= 0.412*110
= 45.38 Ω
Total Positive Sequence Impedance w.r.t. Secondary = Z2LL * CT/PT Ratio
= 66.633 * 0.6
Z2LL Secondary = 27.229 Ω
Total Transformer Impedance ZT (Remote):
If there are more than one Transformer, the resultant Impedance considering the Transformers
are in parallel is taken.
Considering Transformers are connected in parallel
Total Transformer Impedance ZT (Remote) = (% Transformer Impedance) *((kV) 2/MVA)]
Transformer Impedance of Z1 = [0.0976*(2202/60)]
= 78.7307 Ω
Transformer Impedance of Z2 = [0.101*(2202/60)]
= 81.4733 Ω
Transformer Impedance of Z3 = [0.111*(2202/60)]
= 89.54 Ω
Total Transformer Impedance ZT (Remote) = 1/((1/Z1)+ (1/Z2) + (1/Z3))
ZT (Remote) = 1/((1/78.7307)+(1/81.4733)+(1/89.54))
Transformer Impedance W.R.T primary ZT = 27.6674 Ω
60
Total Transformer Impedance ZT (Remote) Secondary = ZT (Remote) *(CT/PT ratio)
= 27.6674 * 0.6
Transformer Impedance W.R.T Secondary ZT = 16.60 Ω
Loadability
Positive sequence impedance Angle =Tan-1(X/R)
Line Angle = Tan-1(0.40988/0.07411)
Line Angle =79.75 Degree
The maximums Load w.r.t Secondary ZMAX primary = 0.85*VL-L/(√3*1.5*.IL)
ZMAX = 0.85*220 / (√3*1.5*795)
[900 A is the maximum capacity of ACSR Markulla and Moose conductor]
ZMAX = 90.54 Ω
Corresponding Zmax secondary = Zmax * CT/PT Ratio = 90.54 * 00.6 = 54.32 Ω
The Resistance reach corresponding to Zmax w.r.t Secondary
R = ZMAX *COS (30)
= 54.32*0.8660
R = 47.05 Ω
The Reactance reach corresponding to Zmax w.r.t Secondary
X = ZMAX *SIN (30)
= 54.32 * 0.5
X = 27.16 Ω
The New impedance for Parallel line Drawn Parallel to the Line impedance passing through
Zmax to the point at which the parallel line cuts the Resistance axis is
Znew = X (at Zmax) /SIN(79.75)
= 27.16 / 0.9967
Znew = 27.60 Ω
The New Resistance from Known Reactance Rnew = Znew* COS (79.75)
= 27.60*0.01779
R new = 4.911
61
Resistances reach of Relay Characteristics
= (R corresponds to Zmax – R new)
R = 47.05 - 4.911
R = 42.13 Ω
Zone Settings
Zone 1
Zone 1= 80 % of Protection Line
= 0.8* 12.068
Zone 1 = 9.654 Ω
Kz 1 Zero sequence compensation
Kz1 = (Z0-Z1/3*Z1)
= (0.29524+j1.260416)-(0.07411+j0.40988) / 3(0.07411+j0.40988)
Zero sequence Line impedance = 0.703 ∟-4.33
Kz1 angle = angle of Kz1
Resistive reach
R1G= MIN of [(10 times of Zone1 Impedance) and 0.8*Resistive Reach at Max load)]
R1G = Min of (10* 9.654 and 0.8* 42.13)
R1G = 33.71 Ω
R1PH= MIN of [(10 times of Zone1 Impedance) and 0.6*Resistive Reach at Max load)]
R1PH = Min of (10* 9.654 and 0.8* 42.13)
R1PH= 25.28 Ω
Zone 2
Zone 2 = Min of [[MAX OF ((Protection line+ (0.5*Adjacent shortest line)) AND
(1.2*Protection line)]( Protection line+ (0.5*Transformer impedance at remote end)]
= Min of[[Max of [(12.068+ (0.5*39.98)) and (1.2*12.068)](12.068 +0.5*16.60)]
= Min of [Max of 32.058 and 14.48 ] and 20.368
Zone 2 = 20.368 Ω
62
tz2 = 0.35 sec
Kz 1 Zero sequence compensation
Kz1 = (Z0-Z1/3*Z1)
= (0.29524+j1.260416)-(0.07411+j0.40988) / 3(0.07411+j0.40988)
Zero sequence Line impedance = 0.703 ∟-4.33
Kz1 angle = angle of Kz1
Resistive reach
R2G= MIN of [(10 times of Zone1 Impedance) and 0.8*Resistive Reach at Max load)]
R2G = Min of (10* 20.368 and 0.8* 42.13)
R2G = 33.71 Ω
R2PH= MIN of [(10 times of Zone1 Impedance) and 0.6*Resistive Reach at Max load)]
R2PH = Min of (10* 20.368 and 0.8* 42.13)
R2PH= 25.28 Ω
Zone 3
Zone3= [MIN OF (1.2(Protection line) +Adjacent Long line) & (Protection line+Adjacent Long
line+25% Second Adjacent Long Line) & (Protection line +0.8Transformer impedance)]
= Min of (1.2*12.068 + 39.98) & (12.068 +39.98 +0.25*27.229) and (12.068+ 16.60)
=Min of (54.46 and 58.855 & 28.668)
Zone3 = 28.668 Ω
tz3 = 1 sec
Resistive reach
R3G= MIN of [(10 times of Zone1 Impedance) and 0.8*Resistive Reach at Max load)]
R3G = Min of (10* 28.668 and 0.8* 42.13)
R3G = 33.71 Ω
R3PH= MIN of [(10 times of Zone1 Impedance) and 0.6*Resistive Reach at Max load)]
R3PH = Min of (10* 28.668 and 0.8* 42.13)
R3PH= 25.28 Ω
63
Zone 4
Zone4 = 0.25 *Zone1
Zone4 = 0.25*9.654 Ω
Zone4 = 2.413 Ω
tz4 = 1 sec
64
1.7 Procedure for Relay setting Calculation for Quadramho Relay
Total Positive sequence impedance of Protected line ZPL=
= [ZPL (Ohms /Km)*Protected Line Length (km)]
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT/PT ratio)
Similarly the Impedance for Adjacent Shortest Line ZSL and Adjacent Remote Long Line ZPL
can be calculated like above.
Total Transformer Impedance ZT (At remote end)
If there is more than one Transformer, the resultant Impedance considering the Transformers
are in parallel is taken.
ZT = (%Transformer Impedance)*((KV) 2/ MVA)]
Zero sequence impedance Z0 = √R02+X02
Zero sequence impedance Angle Z0 = Tan-1(X0/R0)
Positive sequence impedance Angle = Tan-1(X1/R1)
The setting below are calculated on the basis of 1A Relay ie.In = 1.
Zone Settings
Zone 1
Zone 1= 80% of Protection Line
Phase Fault Reach
Phase reach should not exceed the Zone 1 Reach
Zph = (K1+K2)/In
Existing Setting of Zone 1 = (K11+k12+K13)*K14*Zph
K1 =1 (0 to 4 in steps of 1)
K2 = 0.8 (0 to 0.8 in steps of 0.2
K11 = 1 (1 to 9 in steps of 1)
k12 = 0 (0 to 0.9 in steps of 0.1)
k13 = 0.04 (0 to 0.08 in steps of 0.02)
K14 = 1 (1,5)
65
Zone 2
Zone 2 =Minimum of [ [MAX OF ((Protection line+ (0.5*Adjacent shortest line)) AND
(1.2*Protection line)] and ( Protected Line + 0.5 *Transformer Impedance)]
Existing setting of Zone 2 =K24*(K21+K22)*Zph
K21=1 ( 1 to 9 in steps of 1)
K22=0.6 ( 0 to 0.9 in steps of 0.1)
K24=1
tz2= if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.3 sec]
Zone 3(forward)
Zone3= [MIN OF (1.2*Protection line +Adjacent Long line)), Protection line +Adjacent Long
line+0.25*Second Long Line & Protection line + (Transformer impedance)]
Existing Setting of Zone 3 = (K31+K32)*K33*Zph
K31= ( 1 to 9 in steps of 1)
K32= ( 0 to 0.9 in steps of 0.1)
K33= (1,5)
tz3 = 0.8 sec
Zone 3 ( Offset)
Zone 4 = 0.25 *Zone 1 reach
The Existing setting of Zone 4 = (K35*K36)K33*K37*Zph
K33 = (1, 5)
K35 = (1 to 9 in steps of 1)
K36 = (0 to 0.9 in steps of 0.1)
K37 = ( 0, 0.25, 0.5, 1.0)
tz3 = 0.8 sec
Earth Fault Compensation Zn=Z0-Z1/3Z1
Zn = (K4+K5+K6) =Zph
K4 = (0 to 5 in steps of 1)
66
K5 = (0 to 0.9 in steps of 0.1
K6 = (0 to 0.08 in steps of 0.02)
Relay Characteristics angle
Relay Characteristics angle ӨPhase= Tan-1 X/R
ӨEarth = Angle Zn
Sample setting Calculation for Quadra mho relay
Substation : 400 kV GSS Bhiwani
Line : Bhiwani to Bapora 1
Relay Name : Quadramho Relay
DATA:
Protected Line Length : 6.8 km
Adjacent Shortest Line Length : 6.8 km ( 220 kV Bapora 2 )
Adjacent Longest Line Length : 6.8 km ( 220 kV Bapora 2 )
Protected Line
Positive sequence Line impedance = 0.0797 + j0.4065
Zero sequence Line impedance = 0.233 +j1.329
Adjacent Short Long line
Positive sequence Line impedance = 0.0797 + j0.4065
Zero sequence Line impedance = 0.233 +j1.329
Adjacent Longest Long line
Positive sequence Line impedance = 0.0797 + j0.4065
Zero sequence Line impedance = 0.233 +j1.329
Nomber of Remote end Transformers: 3
CT Ratio = 1200A/1A
PT Ratio = 220kV/110V
67
Protected Line Length = 6.8 Km
Adjacent Shortest Line Length = 6.8 Km
Adjacent Longest Line Length = 6.8 Km
Voltage ratio of the transformer = 220kV/132V
MVA of the transformer at the Remote end = 3*100 MVA,
Impedance of the transformer = 10.302 %, 11.87 %, 12.34%
CT/PT ratio = 0.6
Calculation
Positive sequence impedance of Protected line ZPL = √R2+X2
= √0.07972+0.40652
ZPL = 0.414 Ohms/Km
Total Positive sequence impedance of Protected line ZPL=
= [ZPL (Ohms /Km)*Protected Line Length (km)]
= [0.414 * 6.8]
ZPL W.R.T Primary = 2.8168 Ω
Total Positive Sequence Impedance of Protected Line w.r.t. Secondary
= 2.8168 *0.6
ZPL W.R.T. Secondary = 1.69 Ω
Positive sequence impedance of Shortest line ZSL = √R2+X2
= √0.07972+0.40652
ZSL = 0.414 Ohms/Km
Total Positive sequence impedance Adjacent Shortest ZSL=
= [ZSL (Ohms /Km)*Protected Line Length (km)]
= 0.414* 6.8
ZSL W.R.T. primary = 2.8168 Ω
Total Positive Sequence Impedance of the Adjacent Shortest Line w.r.t. Secondary
68
= 2.8168 * 0.6
ZSL W.R.T. Secondary = 1.69 Ω
Positive sequence impedance of Longest line ZLL = √R2+X2
= √0.07972+0.40652
ZLL = 0.414 Ohms/Km
Total Positive sequence impedance Adjacent Longest ZLL=
= [ZLL (Ohms /Km)*Protected Line Length (km)]
= 0.414* 6.8
ZLL W.R.T. primary = 2.8168 Ω
Total Positive Sequence Impedance of the Adjacent Shortest Line w.r.t. Secondary
= 2.8168 * 0.6
ZLL W.R.T. Secondary = 1.69 Ω
Total Transformer Impedance ZT (Remote):
If there is more than one Transformer, the resultant Impedance considering the Transformers are
in parallel is taken.
Considering Transformers are connected in parallel
Total Transformer Impedance ZT (Remote) = (% Transformer Impedance) *((kV) 2/MVA)]
Transformer Impedance of Z1 = [0.1032*(2202/100)]
= 49.9488 Ω
Transformer Impedance of Z2 = [0.1187*(2202/100)]
= 57.45Ω
Transformer Impedance of Z3 = [0.1234*(2202/100)]
= 59.74496 Ω
Total Transformer Impedance ZT (Remote) = 1/((1/Z1)+ (1/Z2) + (1/Z3))
ZT (Remote) = 1/((1/49.9488)+(1/57.45)+(1/59.74496))
69
Transformer Impedance W.R.T primary ZT = 18.4503 Ω
Total Transformer Impedance ZT (Remote) Secondary = ZT (Remote) *(CT/PT ratio)
= 18.4503 * 0.6
Transformer Impedance W.R.T Secondary ZT = 11.0702 Ω
Zone Settings
Zone 1
Zone 1 = 80% of Protection Line
= 0.8*1.69
Zone 1 = 1.352 Ω
Phase Fault Reach
Phase reach should not exceed the Zone 1 Reach
Zph = (K1+K2)/In
K1+K2 = 1+0.2
Zph = 1.2
Existing Setting of Zone 1 = (K11+k12+K13)*K14*Zph
= (K11+k12+K13)*K14*1.2
= (1+0+0.08) * 1.0 *1.2 =1.296 Ω
Zone 2
Zone 2 = Min of [MAX of ((Protected line+ (0.5*Adjacent shortest line)) AND (1.2*Protected
line)] and (Protected Line + 0.5 * Transformer Impedance at remote end)
= Min of (Max Of ((1.69 + (0.5*1.69)) and (1.2*1.69)) and (1.69 + 0.5 *11.0702)
= Min of (Max of 2.535 and 2.028) and 7.2251
Zone 2 = 2.535 Ω
Existing Zone 2 setting = K24*(K21+K22)*Zph
= 1*(2+0)*1.2
= 2.4 Ω
K21=5 (1 to 9 in steps of 1)
K22=0.2 (0 to 0.9 in steps of 0.1)
70
K24=1
tz2= if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.3 sec]
tz2= 0.350 sec
Zone 3(forward)
Zone3= MIN OF [(1.2*Protected line + Adjacent Long line)), (Protected line + Adjacent Long
line+0.25* Second Adjacent Long line) & (Protected line + Transformer impedance at remote
end)]
= Min of [(1.2*1.69+1.69) and (1.69+1.69+0) and (1.69+11.0702)]
= Min of [3.718 and 3.38 and 12.7602]
= 3.38 Ω
Zone 3 = 3.38 Ω
Existing Zone 3 setting = (K31+K32)*K33*Zph
=(K31+K32)*K33*1.2
= (8+0.7)*1*1.2
= 10.44 Ω
K31 = 2 (1 to 9 in steps of 1)
K32 = 0.5 (0 to 0.9 in steps of 0.1)
K33 = 5 (1, 5)
tz3 = 1 sec
Zone 4(Reverse)
Zone 4 = 0.25 *Zone 1
Zone 4 = 0.25*1.352
Zone 4 =0.338 Ω
Existing Zone 4 ( Reverse ) = (K35+K36)K33*K37*Zph
= (1+0.1)*1*0.25*1.2 =0.33 Ω
K33=5 (1, 5)
K35=1 (1 to 9 in steps of 1)
K36=0 (0 to 0.9 in steps of 0.1)
K37=0.25 (0, 0.25, 0.5, 1.0)
71
tz3 = 1 sec
Relay Characteristics angle
Relay Characteristics angle ӨPhase= Tan-1 X/R
= Tan-1 (0.4065/0.0797)
ӨPhase = 78.90 degree
ӨEarth = Angle Positive Sequence impedance +Angle Of Kn
=78.9 + (-5)
= 74.9 Degree
72
1.8 Procedure for Relay setting Calculation for Micro Mho Relay
Total Positive sequence impedance of Protected line ZPL=
= [ZPL (Ohms /Km)*Protected Line Length (km)]
ZPL W.R.T Secondary = ZPL W.R.T Primary *(CT/PT ratio)
Similarly the Impedance for Adjacent Shortest Line ZSL and Adjacent Remote Long Line ZPL
can be calculated like above.
Total Transformer Impedance ZT (At remote end)
If there is more than one Transformer, the resultant Impedance considering the Transformers
are in parallel is taken.
ZT = (%Transformer Impedance)*((KV) 2/ MVA)]
Zero sequence impedance Z0 = √R02+X02
Zero sequence impedance Angle Z0 = Tan-1(X0/R0)
Positive sequence impedance Angle = Tan-1(X1/R1)
The setting below are calculated on the basis of 1A Relay ie.In = 1.
Zone Settings
Zone 1
Zone 1= 80% of Protection Line
Phase Fault Reach
Phase reach should not exceed the Zone 1 Reach
Zph = (K1+K2)/In
Existing Setting of Zone 1 = (K11+k12+K13)*K14*Zph
K1 =1 (0 to 4 in steps of 1)
K2 = 0.8 (0 to 0.8 in steps of 0.2
K11 = 1 (1 to 9 in steps of 1)
k12 = 0 (0 to 0.9 in steps of 0.1)
k13 = 0.04 (0 to 0.08 in steps of 0.02)
K14 = 1 (1,5)
73
Zone 2
Zone 2 =Min of [[MAX OF ((Protection line+ (0.5*Adjacent shortest line)) AND
(1.2*Protection line)] and (Protected Line + 0.5 *Transformer Impedance at remote end)]
Existing setting of Zone 2 =K24*(K21+K22)*Zph
K21=1 (1 to 9 in steps of 1)
K22=0.6 (0 to 0.9 in steps of 0.1)
K24=1
tz2= if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.3 sec]
Zone 3(forward)
Zone3= [MIN OF (1.2*Protection line +Adjacent Long line)), Protection line +Adjacent Long
line+0.25*Second Long Line & (Protection line + Transformer impedance at remote end)]
Existing Setting of Zone 3 = (K31+K32)*K33*Zph
K31= ( 1 to 9 in steps of 1)
K32= ( 0 to 0.9 in steps of 0.1)
K33= (1,5)
tz3 = 0.8 sec
Zone 3 ( Offset)
Zone 4 = 0.25 *Zone 1 reach
The Existing setting of Zone 4 = (K35*K36)K33*K37*Zph
K33 = (1, 5)
K35 = (1 to 9 in steps of 1)
K36 = (0 to 0.9 in steps of 0.1)
K37 = ( 0, 0.25, 0.5, 1.0)
tz3 = 0.8 sec
Earth Fault Compensation Zn=Z0-Z1/3Z1
74
Zn = (K4+K5+K6) =Zph
K4 = (0 to 5 in steps of 1)
K5 = (0 to 0.9 in steps of 0.1
K6 = (0 to 0.08 in steps of 0.02)
Relay Characteristics angle
Relay Characteristics angle ӨPhase= Tan-1 X/R
ӨEarth = Angle Zn
75
Sample setting Calculation for Micro mho relay
Substation : 400 kV GSS Bhiwani
Line : Bhiwani to Charkhi Dhadri
Relay Name : Micro Mho Relay
Protected line 1
Positive sequence Line impedance = 0.0797+j0.405
Zero sequence Line impedance = 0.233+j1.329
Protected line 2
Positive sequence Line impedance = 0.097105+j0.39314
Zero sequence Line impedance = 0.57146+j1.83241
Adjacent Shortest line 1
Positive sequence Line impedance = 0.0797+j0.405
Zero sequence Line impedance = 0.233+j1.329
Adjacent Shortest line 2
Positive sequence Line impedance = 0.097105+j0.39314
Zero sequence Line impedance = 0.57146+j1.83241
Adjacent Longest line
Positive sequence Line impedance = 0.097105+j0.39314
Zero sequence Line impedance = 0.57146+j1.83241
Second Adjacent longest line
Positive sequence Line impedance = 0.0741+j0.389
Zero sequence Line impedance = 0.48787+j1.92051
CT Ratio = 1200A/1A
PT Ratio = 220kV/110V
Protected Line Length = 8.7 Km (0.0797+j0.405)
Protected Line Length = 26 Km (0.097105+j0.39314)
Adjacent Shortest Line Length = 8.7 Km (0.0797+j0.405)
76
Adjacent Shortest Line Length = 26 Km (0.097105+j0.39314)
Adjacent Longest Line Length = 119.89 Km (0.097105+j0.39314)
Adjacent Second Longest Line Length = 24.73 Km (0.0741+j0.389)
Voltage ratio of the transformer at remote end = 220kV/132V
MVA of the transformer at the Remote end = 2*100 MVA
Impedance of the transformer = 12.344 %, 12.00%
CT/PT ratio = 0.6
Calculation
Total Positive sequence impedance of Protected line ZPL = √R2+X2
= (√0.07972+0.4052)*8.7+ (√0.0971052+0.393142)*26
ZPL = 14.129 Ohms/Km
Total Positive Sequence Impedance of the Protected Line w.r.t. secondary
ZPL W.R.T. Secondary = 14.129 * 0.6
= 8.4774 Ω
Total Positive sequence impedance of Shortest line ZSL = √R2+X2
= (√0.07972+0.4052)*8.7+ (√0.0971052+0.393142)*26
ZSL = 14.129 Ohms/Km
Total Positive Sequence Impedance of the Protected Line w.r.t. secondary
ZSL W.R.T. Secondary = 14.129 * 0.6
= 8.4774 Ω
Total Positive sequence impedance of Adjacent Longest line ZLL=
= [ZLL (Ohms /Km)*Longest Line Length (km)]
= √ (0.0971052+0. 393142)*119.89
ZLL W.R.T Primary = 48.55 Ω
77
Total Positive Sequence Impedance of the Adjacent Longest Line w.r.t. Secondary
ZLL W.R.T. Secondary = 48.55 * 0.6
= 29.13 Ω
Total Positive sequence impedance of Second Adjasent Longest line Z2LL=
= [Z2LL (Ohms /Km)*Longest Line Length (km)]
= √ (0.07412+0. 3892)*24.73
Z2LL W.R.T Primary = 9.7929 Ω
Total Positive Sequence Impedance of the Adjacent Longest Line w.r.t. Secondary
Z2LL W.R.T. Secondary = 9.7929 * 0.6
= 5.8757 Ω
Total Transformer Impedance ZT (Remote):
If there is more than one Transformer, the resultant Impedance considering the Transformers are
in parallel is taken.
Considering Transformers are connected in parallel
Total Transformer Impedance ZT (Remote) = (% Transformer Impedance) *((kV) 2/MVA)
Transformer Impedance Z1 = 0.12 * 2202/ 100
= 58.08 Ω
Transformer Impedance Z2 = 0.1234 * 2202/100
= 59.744 Ω
Total Transformer impedance: Zt = Z1*Z2/ (Z1 + Z2)
Zt = 58.08 * 59.744/ (58.08+ 59.744)
Zt w.r.t. primary = 29.45 Ω
Transformer Impedance w.r.t. Secondary = 29.45 * (CT/PT Ratio )
= 29.45 * 0.6
= 17.67 Ω
78
Zone Settings
Zone 1
Zone 1 = 80% of Protection Line
= 0.8*8.477
Zone 1 = 6.782 Ω
Phase Fault Reach
Phase reach should not exceed the Zone 1 Reach
Zph = (K1+K2)/In
K1+K2 = 4+0.8
Zph = 4.8
Existing Setting of Zone 1 = (K11+k12+K13)*K14*Zph
= (K11+k12+K13)*K14*4.8
= (1+0.5+0.02) * 1.0 *1.2 =7.296 Ω
Zone 2
Zone 2 = Min of [MAX of ((Protected line+ (0.5*Adjacent shortest line)) and (1.2*Protected
line)] and (Protected Line + 0.5 * Transformer Impedance)
= Min of (Max Of ((8.477 + (0.5*8.477)) and (1.2*8.477) and (8.477 + 0.5 *17.67)
= Min of (Max of 12.71 and 10.172) and 17.312
Zone 2 = 12.71 Ω
Existing Zone 2 setting =K24*(K21+K22)*Zph
K24*(K21+K22)*4.8= 12.96 Ω
K21=5 ( 1 to 9 in steps of 1)
K22=0.2 ( 0 to 0.9 in steps of 0.1)
K24=1
tz2= if [ZONE 2 > 80 % of Next shortest line then t=0.6sec else t=0.3 sec]
tz2= 0.350 sec
79
Zone 3(forward)
Zone3= Min of (1.2*Protected line + Adjacent Long line)), Protected line + Adjacent Long
line+0.25* Second Adjacent Long line) & (Protected line + Transformer impedance at remote
end)]
= Min of [(1.2*8.477+29.13)] and [8.477+29.13+0.25*5.8757] and [8.477+17.67]
= Min of [39.30 and 39.076 and 26.1477]
= 26.1477 Ω
Zone 3 = 26.1477 Ω
Existing Zone 3 setting = (K31+K32)*K33*Zph
=(K31+K32)*K33*4.8
=(9+0.4)*1*4.8= 45.12 Ω
K31 = 9 ( 1 to 9 in steps of 1)
K32 = 0.4 ( 0 to 0.9 in steps of 0.1)
K33 = 1 (1,5)
tz3 = 1 sec
Zone 4(Reverse)
Zone 4 = 0.25 *Zone 1
Zone 4 = 0.25*6.782
Zone 4 =1.695 Ω
Existing Zone 4 ( Reverse ) = (K33+K34)*Zph
(K33+K34)*4.8 = (1+0.5)*4.8 = 2.4 Ω
K33=1 (1, 5)
K34=1 (0 to 0.9 in steps of 0.1)
tz3 (Reverse) = 1 sec
80
Power Swing Blocking:
Existing setting =K50= (K51+K52)*K53*ZPH
= (6+0)*1*4.8
=28.8 Ω
Setting should be equal to the reach value of zone3 according to manufacturer’s
recommendation for detecting the Power Swing.
Earth fault compensation = (Z0-Z1)/3*Z0 *Zph
= (Total Zero Sequence Impedance - Total Positive Sequence Impedance)/
(3*Total Zero Sequence Impedance) *Zph
= (((0.57146+j1.83241)-(0.097105+j0.39314))/(3*(0.097105+j0.39314)))*4.8
= 2.312 Ω
81