PEMBANGUNAN STASIUN PENGUMPUL
LAPANGAN JATIASRI
               POWER CONSUMPTION                                    No. Dok.              : JAS-EPC-SIN-00-J7-BOM-001
                  CALCULATION                                       Rev.                  :A
       ICSS for Gathering Station Jatiasri                          Halaman               : Hal 1 dari 7
               (Common Safety)
                                                PT. PERTAMINA EP / REGIONAL 2 – FUNGSI
       NAMA PEMILIK PROYEK                 :
                                                PROJECT ZONA 7
       NAMA PROYEK                         :    PT. PERTAMINA EP / REGIONAL 2 – FUNGSI PROJECT ZONA 7
                                                PEMBANGUNAN STASIUN PENGUMPUL JATIASRI
       LOKASI                              :    SP JATIASRI
       NO. KONTRAK                         :    002/PEP.80000/SP3MP/2022-S0
 A     27 Jun 2022   Issued For Approval       AM          PUR                     TRI             AP/MS             AFF
REV.    TANGGAL         DESKRIPSI          DISIAPKAN   DIPERIKSA             DISETUJUI            DIPERIKSA       DISETUJUI
                                                                    KONSORSIUM
                                                       PT. WAHANAKARSA SWANDIRI – PT. ALDABERTA
                                                                     INDONESIA
                                                                                                           PERTAMINA EP
                                                           PT . SARANA INSTRUMENT
POWER CONSUMPTION CALCULATION                                               JAS-EPC-SIN-00-J7-BOM-001
PT. PERTAMINA EP / REGIONAL 2 – FUNGSI PROJECT ZONA 7                                        REV.A
PEMBANGUNAN STASIUN PENGUMPUL JATIASRI                                                  Hal 2 dari 7
                                                  TABEL REVISI
       REV.     BAB      HAL            DESKRIPSI                KOMENTAR     REVISI/TANGGAPAN
         A                        Issued For Approval
                                   POWER CONSUMPTION
                                      CALCULATION
           Company                            Project                              Document No.
      PT. Pertamina EP              ICSS for Gathering Station          ID-51057-000-000-PWR-10001
         Regional 2                  Jatiasri (Common Safety)
                                   PT. Sarana Instrument
  ICSS for Gathering Station Jatiasri (Common Safety)
                              Schneider Electric Ref: ID-51057
                                     Client Ref: CO-0020622
                       PT Schneider Electric Systems Indonesia
      Revision       00             01             02            03                04             05
      Purpose        IFA
      Date           27-Jun-2022
                                             Schneider Electric
      By             MHSI
      Checked        MHSI
      Approved       MDN
                                                   Customer
      Approved
SESI Project No: ID-51057                  PT. Sarana Instrument                        Cust Proj.No: CO-0020622
Revision: 00                 ICSS for Gathering Station Jatiasri (Common Safety)
Revision Date: 27-Jun-2022       PT Schneider Electric Systems Indonesia
SE Doc No: ID-51057-000-000-PWR-10001                                                                  Page 3 of 7
                                 POWER CONSUMPTION
                                    CALCULATION
REVISION HISTORY
   REVISION         DATE        DESCRIPTION
     Rev 0       27-Jun-22      Issued for Approval
SESI Project No: ID-51057                  PT. Sarana Instrument                   Cust Proj.No: CO-0020622
Revision: 00                 ICSS for Gathering Station Jatiasri (Common Safety)
Revision Date: 27-Jun-2022       PT Schneider Electric Systems Indonesia
SE Doc No: ID-51057-000-000-PWR-10001                                                           Page 4 of 7
                                                   POWER CONSUMPTION CALCULATION FOR
                                                       GA PANEL NETWORK CABINET
                                                                                            Power Consumption
                                                                    Power        Total                                     Remarks
 No.                           Description                                                     24VDC (Watts)
                                                                    Source       Qty.      Per Unit    Total         Total           Unit
24VDC                                                                                                                  -
   1  8 PORT DESKTOP DEVICE SERVER (MOXA N PORT 5650-               QUINT-PS       1        7.38        7.38           -             Watts
      8-DT)
                            Total                                                                       7.38           -             Watts
                                                                                                    Power             Power Consumption(Watts)
                                                                       Power       Total       Consumption(Watts)
 No.                             Description
                                                                       Source      Qty.
                                                                                                       Grand Total    Grand Total
                                                                                            Per Unit
                                                                                                       (Max Load)    (Actual Load)     Unit
220 VAC
   1   DELL PowerEdge R540                                             220 VAC         2     750.00      1500.00           1500.00    Watts
   2   Cisco Smart Switch 24 Giga ports, 4 SFP (CBS220-24T-4G-EU)      220 VAC         2      18.00       36.00             36.00
                                    Total                                                                1536.00           1536.00     Watts
                                                   POWER CONSUMPTION CALCULATION FOR
                                                        SYSTEM INTERCONNECTION
                                                                                                    Power             Power Consumption(Watts)
                                                                       Power       Total       Consumption(Watts)
 No.                             Description
                                                                       Source      Qty.
                                                                                                       Grand Total    Grand Total
                                                                                            Per Unit
                                                                                                       (Max Load)    (Actual Load)     Unit
220 VAC
   1    DELL Optiplex 7090 Tower                                       220 VAC         2     300.00       600.00           600.00      Watts
   2    DELL 24” Monitor FHD Resolution 1920 x 1080                    220 VAC         2     14.50         29.00           29.00       Watts
   3    HP DeskJet Ink Advantage 3835 All-in-One                       220 VAC         2      10.00       20.00             20.00      Watts
                                    Total                                                                365.00             649.00     Watts
                            POWER CONSUMPTION CALCULATION GA PANEL MARSHALLING CABINET
                                                                        Power Consumption
                                                    Power      Total                                    Remarks
 No.                       Description                                     24VDC (Watts)
                                                    Source     Qty.
                                                                       Per Unit    Total         Total            Unit
24VDC                                                                                               -
   1    CPU M580 HSBY SIL3 - L2                     QUINT-PS     1      7.00        7.00            -             Watts
   2    COPROCESSOR M580 SIL3                       QUINT-PS     1      7.00        7.00            -             Watts
   3    M580 Ethernet Comm Module                   QUINT-PS     2      2.90        5.80            -             Watts
   4    MODICON X80 EIO DROP ADAPTER                QUINT-PS     2      5.90        11.80           -             Watts
   5    NON-ISULATED ANALOG INPT MODULE             QUINT-PS     3      1.10        3.30            -             Watts
   6    ANALOG OUTPT MODULE M340-8 OUTPUT           QUINT-PS     1      3.90        3.90            -
   7    DISCRETE INPUT MODULE X80-32 INPUT 24 VDC   QUINT-PS     3      3.90        11.70           -             Watts
   8    ANALOG INPUT MODULE X80-4 INPUTS-SAFETY     QUINT-PS     3      3.60        10.80           -             Watts
   9    DISCRETE INPUT MODULE 16 INPUTS 24 VDC      QUINT-PS     1      3.57        3.57            -             Watts
  10    DISCRATE OUTPUT MODULE 8 OUTPUTS SOLID      QUINT-PS     2      0.36        0.72            -             Watts
        STATE 24 VDC
 11     DISCRETE OUTPUT MODULE 4 OUTPUTS RELAY-     QUINT-PS     2      3.12        6.24            -             Watts
        SAFETY
 12     ANALOG INPUT MODULE X80-4 INPUTS SAFETY     QUINT-PS     5      2.76        13.80           -
 13     DISCRETE INPUT MODULE 16 INPUTS 24 VDC      QUINT-PS     1      2.40        2.40            -             Watts
 14     DISCRETE OUTPUT MODULE 8 OUTPUTS SOLID      QUINT-PS     1      0.36        0.36            -             Watts
        STATE 24 VDC
 15     REDUNDANCY MODULE 40 A FOR REGULATED SMPS   QUINT-PS     1        -           -             -             Watts
 16     SURGE ARRESTER                                  -        78       -           -             -             Watts
 17     TERMINAL BLOCK FUSE                             -       250       -           -             -             Watts
 18     TERMINAL BLOCK                                  -       250       -           -             -             Watts
                            Total                                                   88,39           -             Watts
                                                                        Power Consumption        Power Consumption(Watts)
                                                    Power      Total            (Watts)
 No.                       Description
                                                    Source     Qty.              Grand Total    Grand Total
                                                                       Per Unit
                                                                                 (Max Load)    (Actual Load)      Unit
220 VAC
   1  REDUNDANT HP AC POWER SUPPLY SIL3             220 VAC      6      40.00      240.00        240.00           Watts
   2  REDUNDANT HP AC POWER SUPPLY                  220 VAC      2      40.00       80.00         80.00           Watts
   3   REGULATED SWITCH POWER SUPPLY                220 vac      1     480.00      480.00      480.00             Watts
       1/2P,240V,24V,20 A
   4   CUBICLE LAMP                                 220 VAC      1      11.00       11.00        11.00            Watts
                          Total                                                    811.00        811.00           Watts
                          POWER CONSUMPTION CALCULATION GA PANEL SYSTEM CABINET
                                                                              Power
                                                     Power      Total     Consumption                  Remarks
 No.                       Description
                                                     Source     Qty.      24VDC (Watts)
                                                                         Per      Total        Total             Unit
                                                                         Unit
24VDC                                                                                             -
   1    CPU M580 HSBY SIL3 - L2                      QUINT-PS     1      7.00      7.00           -              Watts
   2    COPROCESSOR M580 SIL3                        QUINT-PS     1      7.00      7.00           -              Watts
   3    M580 Ethernet Comm Module                    QUINT-PS     2      2.90      5.80           -              Watts
   4    MODICON X80 EIO DROP ADAPTER                 QUINT-PS     5      5.90     29.50           -              Watts
   5    NON-ISULATED ANALOG INPUT MODULE             QUINT-PS     6      1.10      6.60           -              Watts
   6    ANALOG OUTPT MODULE M340-8 OUTPUT            QUINT-PS     2      3.90      7.80           -
   7    DISCRETE INPUT MODULE X80-32 INPUT 24 VDC    QUINT-PS     4      3.90     15.60           -              Watts
   8    ANALOG INPUT MODULE X80-4 INPUTS-SAFETY      QUINT-PS     5      3.60     18.00           -              Watts
   9    DISCRETE INPUT MODULE 16 INPUTS 24 VDC       QUINT-PS     1      3.57      3.57           -              Watts
  10    DISCRETE OUTPUT MODULE 4 OUTPUTS RELAY-      QUINT-PS     3      3.12      9.36           -              Watts
        SAFETY
 11     ANALOG INPUT MODULE X80-4 INPUTS SAFETY      QUINT-PS     5      2.76     13.80           -
 12     DISCRETE INPUT MODULE 16 INPUTS 24 VDC       QUINT-PS     1      2.40      2.40           -              Watts
 13     DISCRETE OUTPUT MODULE 8 OUPUT SOLID STATE   QUINT-PS     4      0.36      1.44
        24 VDC (BMXSD00802)
 14     CONNEXIUM BASIC MANAGED SWITCH 8 PORTS       QUINT-PS     1      6.00      6.00
 15     REDUNDANCY MODULE 40 A FOR REGULATED         QUINT-PS     1        -         -            -              Watts
        SMPS
 16     SURGE ARRESTER                                  -        60       -         -             -              Watts
 17     TERMINAL BLOCK FUSE                             -        250      -         -             -              Watts
 18     TERMINAL BLOCK                                  -        250      -         -             -              Watts
                            Total                                                 133.87          -              Watts
                                                                        Power Consumption      Power Consumption(Watts)
                                                     Power      Total         (Watts)
 No.                       Description
                                                     Source     Qty.           Grand Total   Grand Total
                                                                         Per
                                                                               (Max Load)      (Actual           Unit
                                                                        Unit                    Load)
220 VAC
  1   REDUNDANT HP AC POWER SUPPLY SIL3              220 VAC      8      40.00    240.00      240.00             Watts
  2   REDUNDANT HP AC POWER SUPPLY                   220 VAC      4      40.00    80.00        80.00             Watts
  3   REGULATED SWITCH POWER SUPPLY                  220 vac      1     480.00    480.00     480.00              Watts
      1/2P,240V,24V,20 A
  4   CUBICLE LAMP                                   220 VAC      1     11.00     11.00       11.00              Watts
  5   ETHERNET GATEWAY-2 ETHERNET PORT-24VDC         220 VAC      1     40.00     40.00       40.00
      AND POE
                         Total                                                    851.00      851.00             Watts