C6416 Man Banco de Carga 1000 KW
C6416 Man Banco de Carga 1000 KW
Loadbank Operating
Instructions
Crestchic Ltd.
2nd Avenue
Centrum 100
Burton upon Trent
Staffordshire
United Kingdom
DE14 2WF
www.crestchicloadbanks.com
sales@crestchic.co.uk
hires@crestchic.co.uk
service@crestchic.co.uk
warranty@crestchic.co.uk
Reproduction of this document, in part or whole, by any means, electrical, mechanical, optical, chemical,
manual or otherwise is prohibited without written permission from Crestchic Limited.
The information contained herein is believed to be accurate as of the date of publication, however, Crestchic
Limited will not be liable for any damages, including indirect or consequential, arising from use of the
hardware or software described within or reliance upon the accuracy of this documentation. The information
contained herein is subject to change without notice.
Revision: 1
Date: 23rd December 2020
1000kW RESISTIVE LOADBANK
CONTENTS
Controller KCS100H-M
PC Software N/A
1. Injury to the person operating or servicing this equipment is able to occur if any of
these SAFETY and/or WARNING statements are ignored.
2. The user must be fully conversant with this manual and in full understanding of it
before operating the loadbank.
3. Personal injury from electrical shock may occur if the power is not isolated before
any maintenance measures are undertaken.
5. The loadbank must only be operated with all of its covers in their correct positions
and secured.
Installation
7. For safety purposes upon receiving the loadbank an initial inspection is
recommended. In addition to this periodical preventative maintenance and safety
inspections are required to ensure the continued safe and reliable operation of the
unit.
8. The loadbank must be properly sited, stable and located in a well ventilated area.
9. Connect a ground (Earth) wire from the Loadbank Earth Stud Terminal to the power
supply under test. Size the Earth cable accordingly. The loadbank must not be
operated without an adequate Earth connection.
10. A minimum clearance of 1m / 40” (2m / 80” recommended) must be allowed from
the inlet grille.
11. A minimum clearance of 5m / 197” (7m / 275” recommended) is required from the
outlet grille. It is recommended that the operator cordon off this area prior to
operation of the unit, to prevent accidental contact with the exhaust grilles and the
hot exhaust gas whilst the loadbank is operating.
14. All safety devices within the loadbank have been proven reliable as part of the test
procedure.
15. Ensure that the load cables are of good condition and suitably rated for the current
they will be required to carry from the power source to the loadbank.
16. Route the load cables through the canvas pouch aperture to the connection
chamber and securely connect them to the correct loadbank terminals – Cam-Loks.
Do not route the cables through the connection chamber door, or leave the door
open during test.
17. Observe the correct 3-Phase & Neutral sequence (if Neutral is used) when
connecting the loadbank to the power source. Connecting a Phase to the Neutral
will damage the loadbank.
18. Do not operate the Loadbank over the rated voltage or frequency as this may cause
failure of the loadbank.
20. Air-flow switches are fitted to the fan(s) to detect the fan(s) are running. If an air-flow
switch as not activated upon start up, or should open during operation the load will
be dropped after a 10 second delay to prevent overheating.
21. Circuit Breakers and/or Fuses are fitted in the loadbank for short circuit and over
current protection.
22. Ensure that all covers, inlet/outlet grilles are fixed and all doors are closed before
applying power to the loadbank.
23. At the end of a test the load must be set to zero and the loadbank fan(s) left running
for a minimum of 5 minutes to cool the resistive elements.
24. Avoid contact with the outlet grille during test and a period of time afterwards as this
becomes very hot during operation and may result in serious burns.
25. Do not permit objects to enter or block the air inlet/outlet grilles of the Loadbank. A
blockage will cause the Loadbank to overheat. If an object enters the loadbank it will
cause damage to the fan(s) and/or resistor elements. If objects enter the loadbank
grilles then the unit must be switched off, removed from all sources of electrical
supply and then inspected physically and electrically to ensure no damage has
occurred.
The function of the loadbank is the dissipation of electrical energy which is transformed
into heat by the resistive elements. This unit will produce 1000kW of real power
dissipation at 480V full load.
The heat is removed from the loadbank by the fan(s) passing air over the resistive
elements. It is essential the inlet and outlet grilles are free from any obstruction otherwise
the loadbank will overheat.
Circuit Breakers and/or Fuses are fitted inside the loadbank for short circuit and over
current protection.
Do not operate the Loadbank over the rated voltage or frequency as this may cause
failure to the loadbank
Thermal switches are located within the control chamber of the loadbank to protect the
equipment from any overheating that may occur.
External Auxiliary Supply input 380/480V 50/60Hz. If this supply is connected select
‘External’ using the ‘Control Supply’ switch and also select the voltage range on the
‘Control Voltage’ switch of the connected supply. This will supply the cooling fans and the
control of the loadbank. A 32A 3-phase supply is required.
If no External Auxiliary Supply is connected, the ‘Control Supply’ switch must be in the
‘Internal’ position. If the control of the loadbank is derived from the test supply, should the
voltage fall below 340V while under load the cooling fan(s) will stop, resulting in the load
being dropped.
Note: It is recommended that the auxiliary supply is utilised when the voltage is
not at the nominal 480V 60Hz
The loadbank must be properly sited, stable and located in a well ventilated area.
A minimum clearance of 1m / 40” (2m / 80” recommended) must be allowed from the
inlet grille. Ensure that no loose material is in the vicinity of the inlet grille (e.g. Paper).
A minimum clearance of 5m / 197” (7m / 275” recommended) is required from the outlet
grille. It is recommended that the operator cordon off this area before operation of the
unit.
Do not position the loadbank where hot exhaust air is able to re-circulate back through
the inlet grille, as this will cause the unit to overheat.
When installing two or more loadbanks ensure they are sufficiently spaced from each
other, so the hot exhaust from one unit does not feed the air intake of another.
Failure to observe the above may result in overheating and subsequent activation of the
over temperature protection.
Connect a ground (Earth) wire from the Loadbank Earth Stud Terminal to the power
supply under test. Size the Earth cable accordingly. The loadbank must not be operated
without an adequate Earth connection.
Ensure that the load cables are of good condition and suitably rated for the current they
will be required to carry from the power source to the loadbank.
Route the load cables through the canvas pouch aperture to the connection chamber and
securely connect them to the correct loadbank terminals – Cam-Loks. Do not route the
cables through the connection chamber door or leave the door open during test.
If using slave units, connect the loadbank load cables in parallel with the master unit.
Connect the ‘External’ auxiliary supply if one is to be used. A 32A 3-phase supply is
required. This is the most suitable option to maintain the control / fan(s) supply if the test
supply should fail.
Do not leave the connection chamber door open during operation of the loadbank or test
supply.
All safety devices within the loadbank have been proven reliable as part of the test
procedure.
Circuit Breakers and/or Fuses are fitted in the loadbank for short circuit and over current
protection.
Ensure that all covers, inlet/outlet grilles are fixed and all doors are closed before applying
power to the loadbank.
Eg.2 For 208V test supply – 480V auxiliary supply, select the following:-
External
440V-480V – Control Supply
2. Connect the controller unit to the control-input socket mounted on the load module
facia of the master unit, this is marked ‘Control I/P’. In some cases this may be via
an extension reel. Ensure that the cables are in good condition. A damaged cable
or plug may lead to failure of the loadbank.
3. If slave units are to be used, connect their control cables in cascade i.e. from the
‘Control O/P’ socket on the master unit to the ‘Control I/P’ socket on the first slave
unit and so on until all slave units are connected.
4. If the unit is to be used ‘Stand Alone’, the ‘Control O/P’ socket is not used.
5. Check that the decade switches on the remote controller are all set to zero.
6. Ensure that all covers are fixed and all doors are closed.
7. This equipment has been fitted with an ‘Emergency Stop’, if pressed this will shed
all load and stop the movement of the fan(s). Ensure that the fault / hazard as been
cleared before resetting the Emergency Stop.
Warning: - The Emergency Stop does not isolate the Test or Auxiliary
Supplies; this must be done at source.
13. Select the kW required on the indexing switches and press the ‘Enter’ button to
apply the load. The next load step may be selected but will not be applied until the
‘Enter’ button is pressed again.
14. The load may be removed at any time by pressing the ‘Clear’ button.
15. Avoid contact with the outlet grille during test and a period of time afterwards as this
becomes very hot during operation and may result in serious burns. It is
recommended that the loadbank operator to cordon off the area for a minimum of
5m (7m recommended) to prevent accidental contact with the exhaust grilles and
the hot exhaust gas whilst the loadbank is operating.
16. Do not permit objects to enter or block the air inlet/outlet grilles of the Loadbank. A
blockage will cause the Loadbank to overheat. If an object enters the loadbank it will
cause damage to the fan(s) and/or resistor elements. If objects enter the loadbank
grilles then the unit must be switched off, removed from all sources of electrical
supply, allowed to cool fully, and then inspected both physically and electrically to
ensure no damage has occurred.
17. If a cooling fault condition occurs, by loss of the airflow due to the inlet grilles being
blocked or fan failure, which is detected by airflow switches AF1 – AF2, or if the
temperature sensors inside the load module exceed 90°C (194°F) the load will
automatically lock out. If the fault can be cleared without removing the supply from
the loadbank then to re-initialise the operating system press the ‘Reset’ button,
otherwise isolate Test / Auxiliary supplies to clear the fault.
18. At the end of a test the load must be set to zero and the loadbank fan(s) left running
for a minimum of 5 minutes to cool the resistive elements. At that point the Stop
button can be actuated.
19. The number of starts per hour of the fan(s) should be limited to ten to avoid
overheating.
General maintenance must be carried out with the test and auxiliary power isolated from
the loadbank.
Maintenance work should only be done by qualified personnel, fully aware of the danger
involved.
The resistive elements are long life maintenance free items, if an element was to “blow”
or become damaged for any reason, obviously this would affect the loading of the
electrical supply under test. The element cannot be repaired and a replacement element
would have to be installed, this can be obtained from Crestchic Ltd. (please specify kW
rating and voltage engraved on the element).
Fan units are fitted with ‘sealed for life’ bearings lubricated with wide temperature range
grease and require no maintenance.
All panel/door seals must be inspected every 6-months to ensure they make a good seal
to prevent water or any foreign matter entering the enclosure.
Door hinges and fasteners must be lubricated every 6-months, and also castor mounted
units should have the castors lubricated.
Replacing Elements
Disconnect the cables or coppers connected to the faulty element termination points. The
elements are fitted with two glands at the termination ends which securely hold the
element in position, some Load Banks are fitted with element support hooks and others
fitted with `toast racks' to support the other end. Remove the nuts on the glands to free
the element. Remove one of the grilles in the element chamber (the nearest to the
element) and slide the element out.
With regard to insulation readings of the loadbank, the minimum recommended constant
safe level to use is 1Meg.
When taking insulation readings, should any instrumentation/transducers be included
with the loadbank (INS370 or VIP) then these should be isolated before an IR test, as
damage may be caused to the instruments.
Ensure the equipment to be tested and the work area is safe (the equipment is de-
energised and disconnected).
Crestchic Loadbanks are an outdoor piece of equipment and therefore depending on the
time of year and/or climatic conditions with regard to moisture over the exposed parts of
the loadbank, the insulation reading may be measured below the minimum
recommended.
The loadbank should be thoroughly inspected before use, checking resistance levels are
in the region of those stated on the electrical drawing. If resistance values are not in the
region of the stated values, then further investigation will be required to ascertain potential
failed elements.
If resistance values are satisfactory, then it is possible to use the loadbank on load for a
period of time to remove any moisture and apply heat to the equipment. It is then advised
before any further usage, the insulation reading is again checked to ensure the level is
above the recommended minimum acceptable value of 1Meg.
Should the level not be above the recommended minimum value after the period of
operation, then there is the possibility of an element that is leaking to earth and each
element bank will be required to be individually inspected to identify the section and then
removing the copper to identify the specific element.
Note:- The element insulation could potentially degrade over a period time, depending
on usage or extreme climatic conditions.
To ensure correct tightness of all electrical POWER connections, the following table of
torque settings must be used.
The below checklist is recommended to be carried out at least once a year or after
prolonged usage to assist in the safe / reliable running of the loadbank.
Any areas of concern must be acted upon, or risk failure or damage to the loadbank.
Check crimps and cables for signs of Test the Extend facility if applicable
heating
Check terminals for tightness and wear to Check Emergency Stop
terminal pins
Check Earth Stud Check the Fan Overloads
Check fan fixings for loose connections Check Phase Rotation Sensor(s)
Check the continuity and correct value Load Test and check for Balance
fuses are fitted Record (if possible)
Check positioning of reactor sensors in the
outer winding and rubber sleeve fitted
Check the reactor fan filters for blockages
Table 3 – Troubleshooting
For spare/replacement parts see parts list enclosed and quote the stock reference
number. (service@crestchic.co.uk)
www.crestchic.co.uk www.crestchic.com
sales@crestchic.co.uk info-me@crestchic.com
www.crestchic.de www.crestchic-usa.com
lager@crestchic.de www.Sales-USA@crestchic.com
www.crestchic.com www.crestchic.fr
info@crestchic-ap.com contact@crestchic.fr
Power Relationship
Power Calculations:-
Metric Conversions:-
ITEM CIRCUIT REF STOCK No. Unit DESCRIPTION MANUFACTURERS REF ORDER No.
52 BROUGHT FORWARD
53
54 FC0-FC1 CON872 2 CONTACTOR S0 35A 3 POLE (7.5kW) 230V 50/60Hz 3RT20251AL20
55 C0 - C5 CON870 6 CONTACTOR S0 35A 3 POLE (4kW) 230V 50/60Hz 3RT20231AL20
56 C6, C7 CON904 2 CONTACTOR S2 55A 3 POLE 230V 50/60Hz 3RT2035-1AL20
57 C8 CON990 1 CONTACTOR S3 110A 3 POLE 230V 50/60Hz 3RT2047-1AL20
58 C9 - C13 CON902 5 CONTACTOR S6 AC1 250A 3 POLE 230V 50/60Hz No Aux 3RT14566AP36
59
60 SCF/R, AC/MC CON924N1 2 *C/O CONT. S0 3 POLE, AC-3 18kW 38A 400V, 230V 50/60H3RA2328-8XB30-1AL2
61
62 RL0, RLT CON860 2 CONTACTOR RELAY 10A 230V 50/60Hz - 3 NO 1 NC 3RH2131-1AP00
63 RL0, RLT CON861 2 SURGE SUPPRESSOR - 127-240V 3RT2916-1CD00
64 SCF/R, AC/MC
65 C0 - C5, FC0-1 CON953 12 SUPPRESSOR CAPACITOR SIZE 202 - 127-240V 3RT2926-1BD00
66 C6 - C8 CON967 3 SUPPRESSOR CAPACITOR FOR SIZE S2 S3 CONTACTOR3RT2936-1CD00
67 C9 - C13 CON952 5 SUPPRESSOR CAPACITOR SIZE 105-107 - 127-240V 3RT1956-1CD00
68
69 C0 - C4 BUS101 1 3PH BUSBAR INFEED TERMINAL CONNECTION FROM AB 3RV2925-5AB
70 C0 - C4 BUS105 1 3PH BUSBAR FOR 5 S0 CONTACTORS (63A/690V) 3RV1915-1DB
71
72 FC0T CON970 1 TIME DELAY 0.5 - 100 SECONDS 3RA2813-1AW10
73
74 OL0 - OL1 OLR142 2 OVERLOAD RELAY 9.0-12.5A 3RU2126-1KB0
75
76 F1 - F6 FUH542 2 CLASS T 3 POLE FUSE BLOCK 60A 60608T
77 F1 - F6 FUH559 6 CLASS T FUSE LINK 50A 600V - UL/CSA A6T50
78 F7 - F9 FUH543 1 CLASS T 3 POLE FUSE BLOCK 100A 61033T
79 F7 - F9 FUH562 3 CLASS T FUSE LINK 100A 600V - UL/CSA A6T100
80 F10 - F24 FUH568 15 CLASS T FUSE LINK 250A 600V - UL/CSA A6T250
81
82 CB1 CCT441 1 MCB 3 POLE 32 AMP TYPE C - UL 5SJ4 332-7HG42
83 CB2 CCT440 1 MCB 3 POLE 25 AMP TYPE C - UL 5SJ4 325-7HG42
84
85 CB10, CB11 CCT437 2 MCB 3 POLE 32 AMP TYPE D - UL 5SJ4 332-8HG42
86 CB15, 16 CCT413 2 MCB 2 POLE 10 AMP TYPE D - UL 5SJ4 210-8HG42
87 CB17 CCT412 1 MCB 2 POLE 6 AMP TYPE D - UL 5SJ4 206-8HG42
88 CB12, CB13 CCT438 2 MCB 3 POLE 2 AMP TYPE C - UL 5SJ4 302-7HG42
89 CB18 CCT400 1 MCB 1 POLE 1 AMP TYPE C - UL 5SJ4 101-7HG42
90 CB14 CCT420 1 MCB 2 POLE 2 AMP TYPE C - UL 5SJ4 202-7HG42
91 CB19 CCT401 1 MCB 1 POLE 2 AMP TYPE C - UL 5SJ4 102-7HG42
92
93
94 SW1 SWT303 1 SWITCH 4 POLE 3 POSITION CENTRE OFF (20A) CA10-A213-620EF
95 SW2 SWT312 1 SWITCH 1 POLE 2 POSITION (20A) CA10-A220-600EF
96
97 L1, L2 IND122 2 PILOT LIGHT BODY 440-480V 60Hz ZB4-BV8
98 L1, L2 IND144 2 PILOT LIGHT LENS RED ZB4-BV04
99
100 L4 IND134 1 PILOT INDICATOR TYPE ND 16 240V AC RED ND16R240
101
102 PSF, PSR SEN171 2 PHASE ROTATION RELAY 500 VOLTS FEC178-871 / 3UG4513-1BR20
103
104 AF0 - AF2 SEN109 3 AIR FLOW PADDLE COMPLETE ASSEMBLY SEN103-106
105
106 S0, S1
107 TEMP. SEN. SEN153 2 BI-METAL THERMAL SWITCH 90 DEG N/C (75 Reset) RS 331-528 / Farnell 1006844
108
109 RT, LOT TIM243 2 MULTI-FUNCTION TIMER 3RP1505-1BP30
110 RT SET TO MODE B & 10 SECONDS
111 LOT SET TO MODE E & 10 SECONDS
112
113
ITEM CIRCUIT REF STOCK No. Unit DESCRIPTION MANUFACTURERS REF ORDER No.
114 BROUGHT FORWARD
115
116 TRX554U 1 TRANSFORMER 1000VA P-380,400,415,440,480V/SEC 220VBWS
117
118
119 AUX I/P TML381 5 TERMINAL 125A/115A UL 600V - M6 Studs ENTRELEC UK - 115.140.23
120
121
122
123
124
125 CONT I/P, O/P CNR640 2 CHASSIS MOUNTED SOCKET SIZE 14 19 WAY (KCS) AB0521001419SN00
126 CONT I/P, O/P CNR641 2 DUST COVER CHASSIS MTD SOCKET 19 WAY (KCS) AB05006514
127 CONT I/P CNR415 1 COVER RED 25 WAY D-TYPE FEC 470-053
128 CONT I/P CNR275 1 PLUG 25 WAY D-TYPE FEC 113-2407
129
130
131 FIX122 15 EMKA LATCH SHORT (GH=18mm) (H=28mm)
132
133 FIX134 9 4-HOLE HINGE C.P. RH 7/04132
134 FIX135 6 4-HOLE HINGE C.P. LH 7/04131
135
136
137 WAC477 8 RUBBER BUFFER A0967
138
139
140 TEST - L1 CNR975 4 CAM-LOK J-SERIES 600V 400A MALE RECEPTACLE 2 HOLE1016-1707BB
141 TEST - L2 CNR976 4 CAM-LOK J-SERIES 600V 400A MALE RECEPTACLE 2 HOLE1016-1703BB
142 TEST - L3 CNR977 4 CAM-LOK J-SERIES 600V 400A MALE RECEPTACLE 2 HOLE1016-1701BB
143
144 TEST - E CNR972 1 CAM-LOK J-SERIES 600V 400A MALE RECEPTACEL 2 HOLE1016-1704BB
145
146 FIX453 26 5/16 UNC X 1 BRASS HEX SET SCREW (SPECIAL FIXING F
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
EM
Y
392°F
STOP
ABB
000 0
000 0
M2M
4. NO OBSTRUCTION PERMITTED WITHIN 80" ON AIR INLET & 275" FAN START/STOP, RESET BUTTON
A OUTLET GRILLES.
LOADBANK CONTROL SUPPLY
INT
OFF/RESET
FAN START
EXT
RESET
CONTROL VOLTAGE
380V-440V 440V-480V
FAN STOP
AUXILIARY/TEST SUPPLY LIVE / COOLING FAULT A
5. 40" CLEARANCE REQUIRED FOR MAINTENANCE ON CONTROL SIDE. TEST
SUPPLY
COOLING
FAULT
AUXILIARY
SUPPLY
KCS INPUT / OUTPUT
CONTROL I/P CONTROL O/P
A A
B M B M
P N L P N L
C C
V K V K
R U R U
D D
S T J S T J
E E
F H F H
G G
ADCOCK
R
DRJAMES
WENTWORTH
TRENTSTRETTON15
ON
BURTON
Aux.
Serial No. Weight kg.
IMPORTANT
BEFORE COMPLETING TEST
RUN FANS FOR 5 MINUTES
WITH ZERO LOAD SELECTED
B B
L1 L2 L3
E
kW
ENTER CLEAR
0 0 0 0
C C
2540lbs 2540lbs
EMERGENCY STOP
GEN
ER C
EM
STOP
DANGER DANGER
LIVE PARTS LIVE PARTS
ADCOCK
R
DRJAMES
WENTWORTH
TRENTSTRETTON15
ON
BURTON
POWER PLANT PROVING ENGINEERS ACCESS TO THIS APPARATUS BY ACCESS TO THIS APPARATUS BY
2ND. AVENUE CENTRUM 100
BURTON ON TRENT AUTHORISED PERSONS ONLY AUTHORISED PERSONS ONLY
UNITED KINGDOM STAFFORDSHIRE DE14 2WF
TEL:-44(0)1283 531645 FAX:-44(0)1283 510103
ABB M2M
0 00 0
0 00 0 ADCOCK
R
DRJAMES
WENTWORTH
TRENTSTRETTON15
ON
BURTON
0 00 0
Aux.
Serial No. Weight kg.
DANGER
FAN START RESET FAN STOP
LIVE PARTS
ACCESS TO THIS APPARATUS BY
AUTHORISED PERSONS ONLY
A A
B M B M
P N L P N L
C C
V K V K
D R U D R U
S T J S T J
E E
F H F H
G G
DANGER
Electric
shock risk
D D
ADCOCK
R
DRJAMES
WENTWORTH
TRENTSTRETTON15
ON
BURTON
DANGER OF ELECTROCUTION
Aux.
EXPOSED ELECTRICAL
Serial No. Weight kg. CONDUCTORS WITHIN DANGER DANGER
ACCESS STRICTLY PROHIBITED
IMPORTANT WHILST SUPPLIES ARE Electric Electric
BEFORE COMPLETING TEST CONNECTED
RUN FANS FOR 5 MINUTES
WITH ZERO LOAD SELECTED
shock risk shock risk
32"
IMPORTANT
BEFORE COMPLETING TEST
RUN FANS FOR 5 MINUTES
WITH ZERO LOAD SELECTED
DANGER
LIVE PARTS
YB S
ACCESS
UTARAPTO
PATHIS
SIHTAPPARATUS
OT SSECCA BY
YLNAUTHORISED
O SNOSREP DPERSONS
ESIROHTUONLY
A
DANGER
LIVE PARTS
YB S
ACCESS
UTARAP TO
PATHIS
SIHTAPPARATUS
OT SSECCA BY
YLNAUTHORISED
O SNOSREP DPERSONS
ESIROHTUONLY
A
DANGER
Electric DANGER
shock risk Electric
shock risk
DANGER OF ELECTROCUTION
EXPOSED ELECTRICAL
CONDUCTORS WITHIN
ACCESS STRICTLY PROHIBITED
WHILST SUPPLIES ARE
CONNECTED
E E
ELEMENT
RAILS
FAN ELEMENT
CHAMBER
CONTROL
B CABLE ENTRY
CHAMBER
B
kW
ENTER CLEAR
0 0 0 0
C C
EMERGENCY STOP
G EN
ER
EM
CY
STOP
ABB M2M
00 0 0
PSR
00 0 0
PSF
LOT
RT
00 0 0
RL0 RLT MC AC SCF SCR
INT EXT
A A
B M B M
P N L P N L
C C
V K V K
R U R U
D D
S T J S T J
E E
F H F H
FCA FCB
G G
CB11
CB17
CB13
CB15
CB16
CB14
CB19
CB18
OLA OLB
ADCOCK
R
DRJAMES
WENTWORTH
TRENTSTRETTON15
ON
BURTON
Aux.
Serial No. Weight kg.
IMPORTANT
TX
BEFORE COMPLETING TEST
RUN FANS FOR 5 MINUTES
WITH ZERO LOAD SELECTED
D L1 L2L3 LNE
D
CAM-LOKS
CABLE POUCH
E E
A A
B B
REAR VIEW
DOOR OPEN
C C
D D
E E
A A
S1 S2
CB12
C0
C1
CB10
PSR
PSF
LOT
RT
RL0 RLT MC AC SCF SCR
C2
KCS PCB CB1
C3
6 5 4 3 2 1 20 12 13 14 15 16 17 18 19 11 10 9 8 7 6 5 4 3 2 1
TBC
CB2
TBB
+
C14
C4
B B
-
- D0 D1 D2 D3 D7 D8 D9 D13 D14 D15
IC12 IC13
FS1 C4
+
C13 P2
C7
HS REG
-
C12
+
S
S
-
C5
REF
1
IC6 IC5 C5
C6
C9 C10
I
C
1
RN5
I
C
2
RN6
I
C
3
RN7
I
C
4
RN8 C11
F1
RN1 RN2 RN3 RN4
CRESTCHIC LTD
CL7214/A TBA
TX1 PL1
C6
F2
110V 240V 110V SER No
1 2 3 4 5 6
F3
FCA FCB
CB17
CB15
CB16
CB14
CB19
CB18
F4
F5
C7
OLA OLB
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
F6
F7
TX F8
C8
F9
C C
CAM-LOKS
C9 C10
L1 L3 E F10
SIEMENS
L2 LN
L1 L2 L3 CAM-LOKS
F11
F12
F13
SIEMENS
F14
CT F15
C11 C12
F16
SIEMENS
F17
D F18
D
F19
SIEMENS
F20
F21
C13
F22
SIEMENS
F23
F24
E E
A A
EMERGENCY STOP
EMERGENCY STOP
ER
GEN
POWER METER
EM
CY
STOP
LOADBANK INSTRUMENTATION
0000
0000
0000
A A
B M B M
P N P N
C L C L
V V
R U K R U K
D D
S T J S T J
E E
F H F H
G G
ADCOCK
R
DRJAMES
WENTWORTH
TRENTSTRETTON15
ON
BURTON
Aux.
Serial No. Weight kg.
IMPORTANT
BEFORE COMPLETING TEST
RUN FANS FOR 5 MINUTES
WITH ZERO LOAD SELECTED
C C
D D
L1 L2 L3
E
E E
INLET VIEW
DRAWING APPROVED FOR
DOOR REMOVED ISSUE BY D.O.
Printed On: 23 Dec,2020
Printed By: TONY HIGGINSON
CUSTOMER DRAWN BY DATE
Crestchic Loadbanks
2nd Avenue, Centrum 100, Burton-on-Trent, HAWTHORNE POWER SYSTEMS 24/03/20
Staffordshire, DE14 2WF, United Kingdom.
F TEL. +44 (0)1283 531645 FAX. +44 (0)1283 510103 CHECKED DATE
F
www.crestchicloadbanks.com 1 23/12/20 TH CN6416-01 AS BUILT AND TESTED
TITLE 25/03/20 ISSUE
A Northbridge Industrial Services PLC Company DATE CHK'D CHANGE No. DESCRIPTION
GENERAL ARRANGEMENT 1000kW
This Drawing is the property of Crestchic Ltd and may not be copied, or used for any CONTRACT SCALE ISSUE DRG. No. SHEET No.
purpose other than that for which it is supplied. Contravention will be prosecuted 480V, 60Hz, 3-PHASE, 3/4-WIRE A
KCS100H-M TRANSPORTABLE LOADBANK C6416 DNS 1 CL21217 5 of 5
copyright © 2020 Crestchic Ltd. 3
1 2 3 4 5 6 7 8
11. DRAWINGS – WIRING DIAGRAMS
4 PER PHASE
CAM-LOCKS
L1
L1
L1
L1
1500:5A
A CT1 1206A A
(1)
L1
S2 S1
CT2 (2)
S2 S1 TO
CT3 (3) SHEET
L2
L2
L2
L2
S2 S1 2
(4)
L2 LN
TEST SUPPLY
B B
5
1
CB10
CB12
CONNECTION
32A
2A
480V 60Hz
L3
L3
L3
3-PHASE L3
6
4
2
6
4
(310)
(311)
(312)
(313)
L3
(206)
(207)
(205)
S2 S1 S2 S1 S2 S1
(205)
1 CAM-LOCK I1 I2 I3 CONTROL
2
OUT1
EARTH (206)
SUPPLY
TO
1
C C
E
(207)
SHEET
4
2
OUT2
E
1
COLOUR CODING:
3-PHASE (4)
N
L1 - BROWN INS421 (301)
L1
D L2 - ORANGE X1
D
R
L1
L3 - YELLOW TEST SUPPLY
(302)
LN - GREY
L2
LIVE LAMP
E - GREEN X2
(303)
L3
1-PHASE 220V CB18
24-240V (269) 2 1 (250)
L - BROWN AC-DC 1A
FROM
N - BLUE (5) SHEET
(5)
12V DC & 24V DC 4
E P - RED E
NOTE:-
N - BLACK WHERE ORANGE SLEEVING
48V DC IS REQUIRED - RED IS
USED (NON AVAIALBLE) DRAWING APPROVED FOR
P - WHITE ISSUE BY D.O.
N - BLACK CURRENT VALUES SHOWN ARE CALCULATED AT 480V 60Hz PHASE-TO-PHASE Printed On: 23 Dec,2020
Printed By: TONY HIGGINSON
CUSTOMER DRAWN BY DATE
Crestchic Loadbanks
2nd Avenue, Centrum 100, Burton-on-Trent, HAWTHORNE POWER SYSTEMS 24/03/20
Staffordshire, DE14 2WF, United Kingdom.
F TEL. +44 (0)1283 531645 FAX. +44 (0)1283 510103 CHECKED DATE F
www.crestchicloadbanks.com 1 23/12/20 TH CN6416-01 AS BUILT AND TESTED
TITLE 25/03/20 ISSUE
A Northbridge Industrial Services PLC Company DATE CHK'D CHANGE No. DESCRIPTION
WIRING DIAGRAM 1000kW
This Drawing is the property of Crestchic Ltd and may not be copied, or used for any CONTRACT SCALE ISSUE DRG. No. SHEET No.
purpose other than that for which it is supplied. Contravention will be prosecuted 480V, 60Hz, 3-PHASE, 3/4-WIRE A
KCS100H-M TRANSPORTABLE LOADBANK C6416 DNS 1 CL21218 1 of 7
copyright © 2020 Crestchic Ltd. 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
250A
250A
250A
250A
250A
250A
250A
250A
250A
250A
250A
250A
250A
250A
250A
100A
100A
100A
F21
F11
F19
F9
F22
F23
F20
F16
F17
F18
F13
F15
F10
F12
F7
F8
F24
F14
B B
(56)
(57)
(58)
TO
SHEET
5
3
C11
C13
C12
C10
C9
C8
2
6
4
4
(44)
(45)
(46)
C C
70mm² 70mm² 70mm² 70mm² 70mm² 25mm²
4x5.55kW
4x5.55kW
4x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
10x5.55kW
(4)
D D
166.65kW 166.65kW 166.65kW 166.65kW 166.65kW 66.66kW
1.38Ω/LEG 1.38Ω/LEG 1.38Ω/LEG 1.38Ω/LEG 1.38Ω/LEG 3.46Ω/LEG
E E
(1) 20351 20351 20231 (1) 20231 20231 20231 20231 20231
(2) (2)
A A
(3) (3)
24.1A
5
50A
50A
50A
50A
50A
50A
CB1
CB2
25A
32A
F1
F5
F6
F2
F3
F4
6
4
4
10mm²
B B
(17)
(18)
(19)
FROM
SHEET
C 2 C
40.1A 40.1A 20.4A 12.0A 4.81A 3.61A 2.41A 1.20A
(53)
(54)
(55)
(50)
(51)
(52)
(47)
(48)
(49)
1
5
C1
C7
C6
C5
C3
C2
C0
C4
2
6
4
4
(41)
(42)
(43)
(38)
(39)
(40)
(35)
(36)
(37)
(32)
(33)
(34)
(29)
(26)
(27)
(28)
(23)
(24)
(25)
(22)
(30)
(20)
(31)
(21)
D D
10mm² 10mm² 4mm² 2.5mm² 2.5mm² 2.5mm² 2.5mm² 2.5mm²
2x5.55kW
2x5.55kW
2x5.55kW
2x5.55kW
2x5.55kW
2x5.55kW
1x5.55kW
1x5.55kW
1x5.55kW
1x3.33kW
1x3.33kW
1x3.33kW
1x1.33kW
1x1.33kW
1x1.33kW
1x1.00kW
1x1.00kW
1x1.00kW
1x0.66kW
1x0.66kW
1x0.66kW
1x0.33kW
1x0.33kW
1x0.33kW
(4) (4)
E E
33.33kW 33.33kW 16.66kW 10kW 4kW 3kW 2kW 1kW
6.91Ω/LEG 6.91Ω/LEG 13.83Ω/LEG 23.04Ω/LEG 57.6Ω/LEG 76.8Ω/LEG 115.2Ω/LEG 230.4Ω/LEG
MC
(205) 1 2 (211) (211)
CONTROL TO
SUPPLY (206) 3 4 (212) (212) SHEET 5
A FROM COOLING A
SHEET 1 (207) (213) (213)
5 6 FANS
5
CB13
CB11
2A
(201) 1 2
(208) 1 2
(211)
T1
(217) 2
(219) 6
(218) 4
(202) 3 4
(209) 3 4
(212)
T2
AUXILIARY SUPPLY
CONNECTIONS (203) 5 6
(210) 5 6
(213)
380-480V 50/60Hz T3
B 3-PHASE 3-WIRE
32A AC B
1
CB15
CB16
22 22
T4
10A
10A
24 21 24 21
(221) 2
(223) 2
(220) 4
4
E 12 12
PSF & PSR
(222) L1 L2 L3 L1 L2 L3
3
14 14
CB14
11 11 VOLTAGE - 450V
5C1 PSF PSR 5C2
2A
(262)
PSF PSR DELAY - 2.0s
2
4
(261)
(228)
(229)
OFF
OFF
OFF
C EXT C
EXT
EXT
INT
INT
INT
SW1
1 3 5 7 9 11
2 6 10
(225)
AUXILIARY SUPPLY
SW2 2
LIVE LAMP
VOLTAGE
(224)
X1
R
L2
1 3 (260)
(226)
(227)
X2
440V
415V
D (250) 24 23
(260) D
RL0
TX1 E-STOP START
1.0KVA CB19 STOP
(250) 2 1
(251) 2 1
(252) (253) 4 3
1 2
220V TO
2A
61
61
(230) (231) SHEETS
1 3
MC
AC
CB17 14 13 1 & 5
(263) 62
(264) 62
6A RL0
2 4
(254)
E E
(250)
X1
A1 L3 A1 A1
NOTE:- ALL CONTACTOR COILS HAVE A (250) TO G
RL0 MC AC
SUPPRESSION CAPACITOR WIRED IN PARALLEL SHEET 1 A2 A2 A2
X2 DRAWING APPROVED FOR
(5) (5) ISSUE BY D.O.
Printed On: 23 Dec,2020
Printed By: TONY HIGGINSON
CUSTOMER DRAWN BY DATE
Crestchic Loadbanks
2nd Avenue, Centrum 100, Burton-on-Trent, HAWTHORNE POWER SYSTEMS 24/03/20
Staffordshire, DE14 2WF, United Kingdom.
F TEL. +44 (0)1283 531645 FAX. +44 (0)1283 510103 CHECKED DATE
F
www.crestchicloadbanks.com 1 23/12/20 TH CN6416-01 AS BUILT AND TESTED
TITLE 25/03/20 ISSUE
A Northbridge Industrial Services PLC Company DATE CHK'D CHANGE No. DESCRIPTION
WIRING DIAGRAM 1000kW
This Drawing is the property of Crestchic Ltd and may not be copied, or used for any CONTRACT SCALE ISSUE DRG. No. SHEET No.
purpose other than that for which it is supplied. Contravention will be prosecuted 480V, 60Hz, 3-PHASE, 3/4-WIRE A
KCS100H-M TRANSPORTABLE LOADBANK C6416 DNS 1 CL21218 4 of 7
copyright © 2020 Crestchic Ltd. 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SCF
(211) 1 2 20251 (214) 20251
5
9.0-12.5A
9.0-12.5A
FC1
FC0
1 2
6
4
4
3 4
OL1
OL0
2
6
4
4
5 6
(600)
(601)
(602)
(603)
(604)
(605)
SCR
B B
4.8/5.76kW 4.8/5.76kW
FAN0 FLC 9.2/10.0A FAN1 FLC 9.2/10.0A
SC 56.9/55.0A SC 56.9/55.0A
(260) (260)
25
13
RT
RLT
BATTLE LINK TO BY-PASS
11
11
AF0
C
13
13
C
26
28
AIR FLOW SWITCHES
14
SCR
SCF
PSR
(291)
PSF
13
14
14
(285)
12
12
14
14
TEMP. SENSOR
FC0
(281)
1
RESET
S0
(270)
14
16
18
16
18
(280)
AF1
53 (292)
2
13
67
LOT
RT
(282)
FROM
FC0T
FC1
15
15
SHEET
FC1
14
68
D 4 D
(280)
(265)
(260)
(287)
(290)
(266)
TEMP. SENSOR
(271)
54
S1
(286)
95
95
61
61
(283)
SCR
OL1
SCF
OL0
(272) 96
(273) 96
(367)62
(368) 62
TIMER B1 A1 A1
X1
MODE B
MODE E
2 SEC. RT LOT R
L4
MAX. 2 1 (295)
A1 A1 A1 A1 A1 A2 (10 SECS) A2 (10 SECS) TO
X2
SCF SCR FC0 FC1 RLT SHEET
E A2 A2 A2 FC0T A2 A2 E
(5) (5) 6
FAN 0 FAN 1 RUN OFF LOCKOUT COOLING
CONTACTOR CONTACTOR DELAY TIMER PULSE TIMER FAULT
DRAWING APPROVED FOR
ISSUE BY D.O.
NOTE:- ALL CONTACTOR COILS HAVE A SUPPRESSION Printed On: 23 Dec,2020
CAPACITOR WIRED IN PARALLEL Printed By: TONY HIGGINSON
CUSTOMER DRAWN BY DATE
Crestchic Loadbanks
2nd Avenue, Centrum 100, Burton-on-Trent, HAWTHORNE POWER SYSTEMS 24/03/20
Staffordshire, DE14 2WF, United Kingdom.
F TEL. +44 (0)1283 531645 FAX. +44 (0)1283 510103 CHECKED DATE
F
www.crestchicloadbanks.com 1 23/12/20 TH CN6416-01 AS BUILT AND TESTED
TITLE 25/03/20 ISSUE
A Northbridge Industrial Services PLC Company DATE CHK'D CHANGE No. DESCRIPTION
WIRING DIAGRAM 1000kW
This Drawing is the property of Crestchic Ltd and may not be copied, or used for any CONTRACT SCALE ISSUE DRG. No. SHEET No.
purpose other than that for which it is supplied. Contravention will be prosecuted 480V, 60Hz, 3-PHASE, 3/4-WIRE A
KCS100H-M TRANSPORTABLE LOADBANK C6416 DNS 1 CL21218 5 of 7
copyright © 2020 Crestchic Ltd. 3
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
19-WAY 'MIL' (CONTROL OUTPUT-EXTEND)
S H G F E D C B A V U P N M L K J
(4000)
(8000)
(2000)
(1000)
(400)
(800)
(200)
(100)
(40)
(0v)
(80)
(20)
(10)
(4)
(8)
(2)
(1)
A A
GRN/RED
RED/BRN
YEL/BLU
YEL/RED
RED/BLK
WHT
GRY
BRN
GRN
TRQ
PNK
ORG
YEL
BLK
BLU
RED
VIO
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
I/P
7 6 5 4 3 2 1 0 15 14 13 12 11 10 9 8
COIL I/P COIL I/P
TBB
IN LINK ISOLATE PIN 10
0V ON IC1,IC2 FROM
TBA
B CONTROL INPUT 19-WAY 'MIL' SOCKET 12V 0V +12V B
P1
PCB CL7215/A
CONNECT PIN TO PIN AS SHOWN ON SHEET 7 NO RELAYS FITTED
12V OUT
240V IN
5V OUT
0V OUT
NEU. IN
EARTH
COIL I/P COIL I/P
TBC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6
D (295) D
FROM
SHEET (5)
(104)
(109)
(108)
(107)
(106)
(105)
(103)
(102)
(100)
(113)
(112)
(110)
(101)
(111)
A1 A1 A1 A1 A1 A1 A1
C12 C10 C8 C6 C4 C2 C0
A2 A2 A2 A2 A2 A2 A2
A1 A1 A1 A1 A1 A1 A1
E C13 C11 C9 C7 C5 C3 C1 E
A2 A2 A2 A2 A2 A2 A2
A 19-WAY 'MIL' A
CHASSIS SOCKET
& COVER ON
LOADBANK FACIA
B B
C C
D D
E E
Page 1
KCS EXTEND LEAD MIL-TYPE PL1224
2CSG445010D1001
2CSG299883R4052
M2M MODBUS
2CSG299893R4052
M2M ETHERNET
2CSG299903R4052
M2M PROFIBUS
2CSG299913R4052
M2M ALARM
2CSG299923R4052
M2M I/O
2CSG299933R4052
M2M LV
2CSG299943R4052
NETWORK ANALYSER
EN Assembly and use instructions
M2M
ABB
SUMMARY
ABB
1 GENERAL INFORMATION
1.1 Reference regulations and conformity....................................................5
1.2 Use and storage of the manual.................................................................6
1.2.1 Storing .....................................................................................................6
EN
1.2.2 Copyright..................................................................................................6
1.3 General safety warnings............................................................................7
2 PACKAGING CONTENTS
2.1 Removal of packaging...............................................................................8
2.2 Description of the contents.......................................................................9
3 TECHNICAL CHARACTERISTICS
3.1 Description of the device........................................................................10
3.2 Measuring functions................................................................................10
3.3 Models....................................................................................................... 11
3.4 Overall dimensions ................................................................................12
3.5 Technical data...........................................................................................13
4 INSTALLATION
4.1 Assembly..................................................................................................18
4.2 Disassembly.............................................................................................19
4.3 Wiring diagrams.......................................................................................20
4.3.1 Wiring diagrams......................................................................................22
4.3.2 Inputs and outputs connections..............................................................24
4.4 Configurations for first use.....................................................................26
5 OPERATING
5.1 Front panel................................................................................................27
5.2 Use of device............................................................................................29
5.2.1 Access to the page.................................................................................30
5.3 Configuration of the SETUP device........................................................31
5.3.1 Control keys............................................................................................32
5.3.1.1 Data entry......................................................................................................33
5.3.2 Password menu......................................................................................34
5.3.2.1 Password creation.........................................................................................34
5.3.2.2 Password modification...................................................................................35
5.3.2.3 Password entry..............................................................................................35
5.3.3 Reset menu............................................................................................37
5.3.4 Configuration menu................................................................................38
5.3.4.1 Type of entry..................................................................................................38
5.3.4.2 CT ratio..........................................................................................................40
5.3.4.3 VT ratio..........................................................................................................41
5.3.4.4 Average time.................................................................................................42
5.3.4.5 Current threshold for T2 hour counter........................................................... 42
5.3.4.7 Generation.....................................................................................................44
5.3.4.8 Euro/energy factor.........................................................................................45
5.3.4.9 CO2/energy factor.........................................................................................45
5.3.4.10 Back lighting..................................................................................................46
5.3.4.11 Energy saving................................................................................................46
M2M
3
Rev. 1.0 NETWORK ANALYSER
ABB SUMMARY
M2M
4
NETWORK ANALYSER Rev. 1.0
CHAPTER 1
GENERAL INFORMATION ABB
1 GENERAL INFORMATION
EN
2006/95/CEE
93/68/CEE (Low-Voltage Directive).
Electrical safety
IEC 61010-1
IEC 60688
IEC 61326-1
Measuring instruments IEC 62053-21
IEC 62053-23
IEC 62053-31
M2M
5
Rev. 1.0 NETWORK ANALYSER
CHAPTER 1
ABB GENERAL INFORMATION
This manual contains all of the safety information, the technical aspects and the
operating necessary to ensure the correct use of the device and maintain it in safe
conditions.
1.2.1 Storing
The manual must be stored close to the device; safe from liquids and anything else
which may compromise its leggibility.
The manual and the declaration of conformity are both an integral part of the device
until it is dismantled.
If the manual is lost or illegible please request a copy from the manufacturer.
1.2.2 Copyright
The copyright of this manual is the property of ABB S.p.A.
This manual contains texts, designs and illustrations of a technical nature which must
not be disclosed or transmitted to third parties, even partially, without the written
authorisation of ABB S.p.A.
M2M
6
NETWORK ANALYSER Rev. 1.0
CHAPTER 1
GENERAL INFORMATION ABB
1.3 General safety warnings
EN
injury or death.
•• Use the suitable personal protection devices and adhere to the current
regulations governing electrical safety.
•• This device must be installed exclusively by qualified personnel who have
read all of the information relative to the installation.
•• Check that the voltage supply and measurement are compatible with the range
permitted by the device.
•• Ensure that all current and voltage supplies are disconnected prior to carrying
out any controls, visual inspections and tests on the device.
•• Always assume that all circuits are under voltage until they are completely
disconnected, subjected to tests and labelled.
•• Disconnect all of the power supply prior to working on the device.
•• Always use a suitable voltage detection device to check that the supply is
interrupted.
•• Pay attention to any dangers and carefully check the work area ensuring that
no instruments or foreign objects have been left inside the compartment in
which the device is housed.
•• The correct use of this device depends on a correct manipulation, installation
and use.
•• Failure to adhere to the basic installation information can lead to injuries as well
as damage to the electric instruments or to any other product.
•• NEVER connect an external fuse in by-pass.
•• Disconnect all of the input and output wires before carrying out a dielectric
rigidity test or an insulation test on an instrument in which the device is installed.
•• The tests carried out at a high voltage can damage the device's electronic
components.
M2M
7
Rev. 1.0 NETWORK ANALYSER
CHAPTER 2
ABB PACKAGING CONTENTS
2 PACKAGING CONTENTS
M2M
8
NETWORK ANALYSER Rev. 1.0
CHAPTER 2
PACKAGING CONTENTS ABB
2.2 Description of the contents
The packaging includes:
1) network analyser
2) user manual
EN
3) calibration certificate
4) mini CD with technical documentation
5) assembly accessories
3
1 2
M2M
9
Rev. 1.0 NETWORK ANALYSER
CHAPTER 3
ABB TECHNICAL CHARACTERISTICS
3 TECHNICAL CHARACTERISTICS
The M2M network analyser is an instrument that measures of the main electric
quantities on 3-phase and monophase networks designed for the monitoring and
the local or remote analysis of:
•• electrical parameters of systems in low or medium voltage;
•• system energy consumption.
3.2 Measuring functions
All of the M2M series models are able to measure and process the quantities
shown below.
M2M
10
NETWORK ANALYSER Rev. 1.0
CHAPTER 3
TECHNICAL CHARACTERISTICS ABB
3.3 Models
Serial
Models Inputs and outputs communication
EN
protocol
M2M
11
Rev. 1.0 NETWORK ANALYSER
CHAPTER 3
ABB TECHNICAL CHARACTERISTICS
D
A
EN
E F
B C
A 96 mm D 77 mm
B 96 mm E 57 mm
C 92 mm F 20 mm
IEC 61554
X 92 -0+0,8 mm
Y 92 -0+0,8 mm Y
M2M
12
NETWORK ANALYSER Rev. 1.0
CHAPTER 3
TECHNICAL CHARACTERISTICS ABB
3.5 Technical data
Auxiliary power supply
from 24 to 240 a.c./d.c.
EN
Voltage range [V] from 48 to 240 a.c../d.c. M2M ETHERNET,
M2M PROFIBUS, M2M I/O
Frequency range [Hz] 45 ÷ 65
T 0,5 A from 24 V to 100 V
Protection fuse
T 0.25 A from 24 V to 100 V
Accuracy class
Voltage ±0,5% F.S. ±1 digit
Current ±0,5% F.S. ±1 digit
40.0 ÷ 99.9: ±0,2% ±0,1
Frequency [Hz]
100 ÷ 500: ±0,2% ±1
±1% ±1 digit
Power factor (from cosΦ= 0,3 Inductive
to cosΦ= 0,3 Capacitive)
±1% ±0,1% F.S
Active power (from cosΦ= 0,3 Inductive
to cosΦ= 0,3 Capacitive)
Active energy Class 1
Measurement range
from 10 to 500 approx. TRMS VL-N
Voltage [V]
Visualisation with 0 decimals
from 50 mA to 5 A TRMS
Current
Visualisation in A with 2 decimals
from 40 to 500
Visualisation:
Frequency [Hz]
with 1 decimal up to 99.9
with 0 decimals above 100
Power factor Visualisation with 2 decimals
M2M
13
Rev. 1.0 NETWORK ANALYSER
CHAPTER 3
ABB TECHNICAL CHARACTERISTICS
Installation
Low and medium voltage
Singlephase insertion
Distribution networks
3-phase with neutral
EN
Energy measurement
Single phase maximum value
10 GWh / Varh / VAh
counted
3-phase maximum value counted 30 GWh / Varh / VAh
Energy balance maximum value
10 GWh / GVarh / GVAh with sign
counted
Input pulses maximum energy value
40 GWh / Varh
counted
Terminal characteristics
Ammetric inputs Section 6 mm2 - Step 6,35 mm
Volumetric inputs Section 2.5 mm2 - Step 7.62 mm
Pulse outputs Section 2.5 mm2 - Step 5.08 mm
RS485 Serial port Section 2.5 mm2 - Step 5.08 mm
Relay outputs Section 2.5 mm2 - Step 5.08 mm
M2M
14
NETWORK ANALYSER Rev. 1.0
CHAPTER 3
TECHNICAL CHARACTERISTICS ABB
Overall dimensions
96 mm x 96 mm x 77 mm (Depth inside switchboard: 57 mm)
EN
Weight [Kg] 0.400 max
Standard normatives
Overall dimensions IEC 61554
Degree of protection IEC 60529
IEC 60688, IEC 61326-1, IEC 62053-21 ,
Accuracy class
IEC 62053-23, IEC 62053-31.
Electrical safety IEC 61010-1
User interface
Scrolling text in several languages user
Display
selectable.
Display type LCD with back light intensity user selectable
Display dimensions [mm] 72x57
Communication interface
RS485
Protocol Modbus RTU
Electric standard RS485 with optical isolation
Baud rate 4.8, 9.6, 19.2 kbps
Parity number Odd, Even, None
Stop bit 1, 2
Address 1-247
4 pole terminal (integrated 120 Ohm terminator on T
Connectors
terminal)
Profibus
Profibus with slave DP-V0 function in compliance with IEC
Protocol
61158 standard
Electric standard RS485 with optical isolation
Baud rate Automatic detection [9.6 - 12 Mbps]
Green for communication status and Red for communication
LED indicators
error
Address 1-126
DB 9 female connector (do not use connectors with 90°
Connectors
cable outlet)
M2M
15
Rev. 1.0 NETWORK ANALYSER
CHAPTER 3
ABB TECHNICAL CHARACTERISTICS
Ethernet
Protocol Modbus TCP/IP
Connectors RJ45
EN
Relay outputs
Nominal current [A] 16 AC1 - 3 AC15
Max. instant current [A] 30
Nominal voltage [V] 250 a.c.
Max instant voltage [V] 400 a.c.
Nominal load [VA] 4000 AC1 - 750 AC15
Analog output
Settable electric parameters Span [0 - 20 mA or 4 - 20 mA]
Load typical 250 Ohm, max 600 Ohm
Digital inputs
Nominal voltage [V] 24 d.c. (absorption = 13 mA)
Max. voltage [V] 32 d.c. (absorption = 22 mA)
Max. voltage for OFF state [V] 8 d.c.
Min. voltage for ON state [V] 18 d.c.
M2M
16
NETWORK ANALYSER Rev. 1.0
CHAPTER 3
TECHNICAL CHARACTERISTICS ABB
Hour counters
Count of the system operating time through
the activation of a programmable threshold
Count-down timer on total current. Upon expiry of the
EN
maintenance period set an icon will appear
on the display.
Count-up timer Life time of instrument
Climatic conditions
Storing [°C] from -10 to +60
Operation [°C] from -5 to +55
Relative humidity Max 93% (without condensation) at 40°C
Degree of protection
Frontal IP50
At terminals IP25
M2M
17
Rev. 1.0 NETWORK ANALYSER
CHAPTER 4
ABB INSTALLATION
4 INSTALLATION
4.1 Assembly
EN
IEC 61554
A
2
A
A
A x4
A A
M2M
18
NETWORK ANALYSER Rev. 1.0
CHAPTER 4
INSTALLATION ABB
4.2 Disassembly
EN
A
A A x4
A
A A 1
2
1
M2M
19
Rev. 1.0 NETWORK ANALYSER
CHAPTER 4
ABB INSTALLATION
M2M
20
NETWORK ANALYSER Rev. 1.0
CHAPTER 4
INSTALLATION ABB
EN
M2M MODBUS
M2M / M2M LV
S2 S2
I1 I1
S1 S1
B
S2 S2
S I2
I2
A
S1 S1
T
S2 S2
I3 I3
S1 S1
24-240V| Max 500 V OUT2 | OUT1 24-240V| Max 500 V OUT2 | OUT1
M2M PROFIBUS
S2 S2
P
I1 I1
S1 r S1
o
LAN S2 f S2
I2 I2
i
S1 b S1
S2 u S2
I3 I3
s
S1 S1
48-240V| Max 500 V OUT2 | OUT1 48-240V| Max 500 V OUT2 | OUT1
C NO NC | C NO NC + COM + COM + - + - + -
S2 S2
M2M I/O
I1 I1
S1 S1
B B
S2 S2
S I2 S
A I2
S1 A
T S1
T
S2 S2
I3 I3
S1 S1
24-240V| Max 500 V OUT2 | OUT1 48-240V| Max 500 V OUT2 | OUT1
M2M
21
Rev. 1.0 NETWORK ANALYSER
CHAPTER 4
ABB INSTALLATION
2 3-phase with 3 CT
 
A Fuse B Load
1
A A
2
A A
3
TV3 TV2 TV1
A
M2M
22
NETWORK ANALYSER Rev. 1.0
CHAPTER 4
INSTALLATION ABB
AARON 3-phase with 2 CT and 3
4 6 Balanced 3-phase with 1 CT
VT
5 Monophase with 1 CT
EN
 
Fuse
A B Load
4
A
TV3 TV1
5
A
A
A A
M2M
23
Rev. 1.0 NETWORK ANALYSER
CHAPTER 4
ABB INSTALLATION
7 8
A A
B C
D
E
 
A V aux 48 V a.c./d.c. 100 mA D Load 16A AC1 - 3A AC15
 
B External relay E V aux 250 V a.c. MAX

C Pulse acquisition
M2M
24
NETWORK ANALYSER Rev. 1.0
CHAPTER 4
INSTALLATION ABB
M2M I/O digital inputs (example in
10 11 M2M I/O analog outputs
NPN mode)
EN
10 11 + +
H H
G
 
F G.M.C. + ES card H Typical 250 Ohm load, max 600 Ohm

G V aux 24 V d.c. (32 V d.c. max)
M2M
25
Rev. 1.0 NETWORK ANALYSER
CHAPTER 4
ABB INSTALLATION
M2M
26
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5 OPERATING
EN
13
15
14
18
17 16
L12
19
L23 10
8
L31 11
7 Alarm Setup
12
9
1 2 3 4 5
M2M
27
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Description
1 Control key 1
2 Control key 2
EN
3 Control key 3
4 Control key 4
5 Control key 5
10 Alarm indicators
16 Measurement unit
M2M
28
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.2 Use of device
During normal operating or during the reading of the parameters, the device is set
in DATA READING mode.
During the configuration phase of one or more parameters the device will pass on
EN
to the SETUP mode (signalled on display by the 12 icon).
Based on the mode activate, the control keys 6 perform a specific function.
M2M
29
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
A B
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
x1 x1 x1
>2s
Setup
C D
M2M
30
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3 Configuration of the SETUP device
To access the SETUP device configuration menu press the 5 key for more than
2 seconds.
EN
The display order of the main page of the menu and the relative configurations are
illustrated in the following table:
Menu Function
Insertion, modification and disabling of device protection
Password
password.
Reset the peak/average, energy, hour counter values and
Reset
reset the factory setting.
Device configurations (electric network, back lighting,
Configurations
conversion factors, alarm thresholds, etc.)
M2M
31
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Repeatedly press the 1 key to reach the Exit page, regardless of navigation point.
Press the 5 key to confirm.
EN
To quickly return to the normal DATA READING navigation, keep the 5 key pressed
down for more than 2 seconds.
Key Function
M2M
32
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.1.1 Data entry
Some of the pages require the entry of alphanumerical characters (A-Z, 0-9) in the
SETUP mode.
EN
In these cases the page will have a series of fields where the active field will be
identified by a flashing cursor.
M2M
33
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Password menu
Enter?
EN
x1 x1 x1
>2s
Setup
The entry, convalidation, modification and disabling of the device protection password
operations can be carried out in this menu.
Password creatio
Password:
x1 x1 x1 x1 x1
>2s
Setup
M2M
34
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.2.2 Password modification
Password modifica
EN
Password:
x1 x1 x1 x1
>2s
Setup
Password entry
Password: ----
x1 x1 x1 x1
>2s
Setup
M2M
35
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
At the password entry request, go to the Password entry page in the Password entry
menu and continue as follows:
Enter password
Password:
Setup
Password incorre
Password:
Setup
and the device will automatically return to the advanced menu level.
M2M
36
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.3 Reset menu
Reset menu
Enter?
EN
x1 x2 x1
>2s
Setup
Confirm reset
<-esc OK-conf.
Setup
3) Press the 5 key to confirm the selection or the 1 key to cancel and return
to the advanced menu level.
M2M
37
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Configuration men
Enter?
EN
x1 x3 x1
>2s
Setup
In this menu the settings of the parameters relative to the entry of the electric
network device, the T2 hour counter, the generation functions, the back lighting and
the conversion factors used to calculate the values in euro and CO2 can be made.
Type of entry
GENERIC
x1 x3 x1 x1
>2s
Setup
M2M
38
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
Types of entry Description / Effect Note
EN
in the navigation menu the voltage
The self-diagnosis carries
3-PHASE out controls on the correct
insertion[1]
The value of the I1 current
is assumed to be valid for
BALANCED Use channel I1 to insert the
the two remaining phases
3-PHASE current
(allows you not to connect
I2 and I3)
The self-diagnosis does not
GENERIC carry out controls on the
correct insertion
See paragraph “5.3.10 Self-diagnosis menu” for more information on the tests
[1]
carried out.
M2M
39
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
5.3.4.2 CT ratio
Set CT ratio
5/5
EN
x1 x3 x1 x1 x1
A B
>2s
Setup
1) Insert a value between 1 A and 10000 A for the primary value in A (see
paragraph “5.3.1.1 Data entry”).
2) Move the cursor to the figure relative to the secondary current B and select
1 A or 5 A.
3) Press the 5 key to confirm.
If the CT is replaced varying the value of the transformation ratio, before proceeding
we recommend:
1) Noting the value of the energy counts accumulated with the previous ratio.
2) Resetting the energy counts.
3) Insert a new value of the transformation ratio.
M2M
40
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.4.3 VT ratio
Set ratio
VT 100/100
EN
x1 x3 x1 x2 x1
A B
>2s
Setup
1) Insert a value between 60 A and 60000 A for the primary value in A (see
paragraph “5.3.1.1 Data entry”).
2) Move the cursor to the figure relative to the voltage of the secondary B and
insert a value between 60 V and 190 V (see paragraph “5.3.1.1 Data entry”).
3) Press the 5 key to confirm.
M2M
41
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Average time
time(min) 15
EN
x1 x3 x1 x3 x1
>2s
Setup
In this page the time intervals used by the device to carry out the calculation of the
average values is set.
1) Insert a value between 1 and 60 minutes (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
Current threshol
ThrI(A) 0.00
x1 x3 x1 x4 x1
>2s
Setup
The current threshold for the T2 hour counter represents the minimum current value
at which the counter begins the countdown.
1) Insert a value of between 0 and the nominal value of the current transformer
used, KA*5 (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
M2M
42
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.4.6 Hour counter count-down
Hour counter
EN
T2(h) 8760h
x1 x3 x1 x5 x1
>2s
Setup
When the count down hour counter completes the countdown the 11 symbol will
appear on the display.
1) Insert a value between 1 and 26280 hour (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
M2M
43
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
5.3.4.7 Generation
Generation
EN
Enabled
x1 x3 x1 x6 x1
>2s
Setup
By activating the GENERATION option, the energy counts will be carried out on 4
quadrants separating energy and absorbed power, shown with the “+” sign, from that
generated shown with the “-” sign.
It is important that the insertion of the CT is carried out correctly adhereing to
the absorption direction of the current.
1) Press the 2 or the 3 key to enable or disable the acquisition mode of the
data in the 4 quadrants.
2) Press the 5 key to confirm.
If the Generation option is not active the instrument will carry out the automatic
inversion of the current direction meaning that the powers active will always be
positive and the energy count will occur on two quadrants. With each switching on
or as soon as the current is different from 0, the analyser will automatically and in an
independent manner for each phase, read the displacement of the current in respect
to the corresponding phase voltage for some periods. If it finds that the current is out
of phase it inverts the direction of the current concerned.
M2M
44
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.4.8 Euro/energy factor
Euro/energy fact
EN
€/KWh 0.18
x1 x3 x1 x7 x1
>2s
c Setup
The active 3-phase energy, both absorbed and generated, is multiplied by the
conversion factor so that the equivalent can be displayed in euro.
1) Insert a value between 0.01 and 9.99 (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
The active 3-phase energy, both absorbed and generated, is multiplied by the
CO2/energy facto
Kg/KWh 0.05
x1 x3 x1 x8 x1
>2s
c Setup
1) Insert a value between 0.01 and 9.99 (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
M2M
45
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Back lighting
EN
interme
x1 x3 x1 x9 x1
>2s
Setup
Energy saving
Enabled
x1 x3 x1 x10 x1
>2s
Setup
The energy saving foresees the automatic switching off of the back lighting (if not set
at “off”) if the control keys 6 remain inactive for approx. 3 minutes.
The back lighting can be reactivated by pressing any of the 6 control keys.
1) Press the 2 key or the 3 key to enable or to disable the ‘Energy saving’
mode.
2) Press the 5 key to confirm.
M2M
46
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.5 Digital output menu
Digital output m
Enter?
EN
x1 x4 x1
>2s
c Setup
In this menu the parameters associated with the pulses or the alarms of the digital
output available on all models, OUT1 and OUT2 can be set.
Select “pulses” to use OUT1 and OUT2 as pulse output channels associated
respectively with the 3-phase active energy and the 3-phase reactive energy.
Select “Alarms” to use OUT1 and OUT2 as alarm output channels.
Output mode
Alarms
x1 x4 x1 x1
>2s
Setup
1) Press the 2 key or the 3 key to select one of the two options available (‘Alarms’
or ‘Pulses’).
2) Press the 5 key to confirm.
M2M
47
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Energy value
EN
Wh/imp. 10
x1 x4 x1 x1 x1
>2s
Setup
1) Press the 2 key or the 3 key to select one of the following values expressed
in Wh/imp for OUT1 and VArh/imp for OUT2:
•• 10
•• 100
•• 1000
•• 10000
2) Press the 5 key to confirm.
M2M
48
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.5.3 Alarm1 or alarm2(*) parameter
Alarm parameter
EN
None
x2
x1 x4 x1 x1
x3(*)
>2s Setup
1) Press the 2 key or the 3 key to navigate between the parameters given in
paragraph “5.3.7.6 Output associated parameter table”.
M2M
49
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Alarm threshold
EN
th2 1.00
x1 x4 x1 x4 x1
>2s
Setup
1) Insert the values required (see paragraph “5.3.1.1 Data entry”), checking the
parameters and the setting intervals (see paragraph “5.3.7.6 Output associated
parameter table”).
2) Press the 5 key to confirm.
Activation at
over threshold
x1 x4 x1 x5 x1
>2s
Setup
1) Press the 2 key or the 3 key to select one of the two options available (‘over
threshold’ or ‘below threshold’).
2) Press the 5 key to confirm.
M2M
50
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.5.6 Alarms 1 or 2 activation delay
Activ. delay
EN
Dly2(s) 10
x1 x4 x1 x6 x1
>2s
Setup
1) Insert a value between 1 and 900 seconds (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
1) Insert a value between 0 and 40% (see paragraph “5.3.1.1 Data entry”).
Alarm hysteresis
Hyst2(%) 0
x1 x4 x1 x7 x1
>2s
Setup
M2M
51
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Enter?
x1 x5 x1
>2s
c Setup
Alarm parameter
None
x1
x1 x5 x2(*) x1
>2s Setup
1) Press the 2 key or the 3 key to navigate between the parameters given in
paragraph “5.3.7.6 Output associated parameter table”.
M2M
52
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.6.2 Alarm 3 or 4 threshold
Alarm threshold
EN
th3 1.00
x1 x5 x1 x1 x1
>2s
Setup
Insert the values required (see paragraph “5.3.1.1 Data entry”), checking the
parameters and the setting intervals (see paragraph “5.3.7.6 Output associated
parameter table”).
1) Press the 5 key to confirm.
Activation at
over threshold
x1 x5 x1 x2 x1
>2s
Setup
1) Press the 2 key or the 3 key to select one of the two options available
(‘over threshold’ or ‘below threshold’).
2) Press the 5 key to confirm.
M2M
53
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Activ. delay
EN
Dly3(s) 10
x1 x5 x1 x3 x1
>2s
Setup
1) Insert a value between 1 and 900 seconds (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
Alarm hysteresis
Hyst3(%) 0
x1 x4 x1 x4 x1
>2s
Setup
1) Insert a value between 0 and 40% (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
M2M
54
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.7 I/O card menu
EN
Enter?
x1 x5 x1
>2s
c Setup
From the I/O card menu it is possible to set the parameters associated with the
analog outputs 4-20mA (“AN-O1” and “AN-O2”) and the pulse reading inputs(“IN1”,
“IN2” and “SYNCH”).
Outputs span
0-20mA
x1 x5 x1 x1
>2s
Setup
Selecting “0-20mA”, the output current will assume the values from 0 to 20mA
proportional to the parameter associated therewith; when selecting “4-20mA” the
values assumed by the output currents will be between 4 and 20 mA. Values lower
than 4mA indicate a failure along the current loop.
M2M
55
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Outputs paramete
V1
EN
x1 x5 x1 x1 x1
>2s
Setup
1) Press the 2 key or the 3 key to navigate between the parameter given in
paragraph “5.3.7.6 Output associated parameter table”.
2) Press the 5 key to confirm.
Outputs size
l1
x1 x5 x1 x2 x1
>2s
Setup
1) Press the 2 key or the 3 key to navigate between the parameter given in
paragraph “5.3.7.6 Output associated parameter table”.
2) Press the 5 key to confirm.
M2M
56
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.7.4 Input pulses factors
EN
x1 x4 x1 x3 x1
>2s
Setup
1) Insert the value required between 1 and 10000 Wh/pulses (see paragraph
“5.3.1.1 Data entry”); in case of interface with analysers MTME and DMTME
the same value must be set as in the setup of these instruments.
2) Press the 5 key to confirm.
Time synchronism
Disabled
x1 x4 x1 x4 x1
>2s
Setup
For the M2M I/O model the enabling of this parameter, in correspondence with the
arrival of an external synchronism pulse, synchronises the calculation of all of the
average values; any synchronism commands from protocol will not be accepted.
1) Press the 2 key or the 3 key to enable or disable the external synchronism
of the average time.
2) Press the 5 key to confirm.
M2M
57
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
The following table shows the parameters associated to alarm ouput and/or analog
output in current.
EN
M2M
58
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.8 Communication menu
Communication me
Enter?
EN
x1 x4 x1
>2s
Setup
Nod address
Addr 126
x1 x4 x1 x1
>2s
Setup
1) Enter the PROFIBUS node between 1 and 126 (see paragraph “5.3.1.1 Data
entry”) to be associated with the instrument.
2) Press the 5 key to confirm.
This is the only page available in this menu for the M2M
PROFIBUS model.
M2M
59
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Serial protocol
Prot MODBUS
EN
x1 x4 x1 x1
>2s
Setup
1) Press the 2 key or the 3 key to select one of the two options available
(‘MODBUS’ or ‘ASCII’).
2) Press the 5 key to confirm.
5.3.8.3 Address
Address
Addr 31
x1 x4 x1 x1 x1
>2s
Setup
1) Insert a value between 1 and 247 (see paragraph “5.3.1.1 Data entry”).
2) Press the 5 key to confirm.
M2M
60
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.8.4 Baud rate
Baud rate
BR(bps) 9600
EN
x1 x4 x1 x2 x1
>2s
Setup
1) Press the 2 key or the 3 key to select one of the following values available:
•• 4800
•• 9600 (default)
•• 19200
2) Press the 5 key to confirm.
Parity type
Pty None
x1 x4 x1 x3 x1
>2s
Setup
•• EVEN
•• ODD
2) Press the 5 key to confirm.
M2M
61
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
N. of bit of sto
Sb 1
EN
x1 x4 x1 x4 x1
>2s
Setup
1) Press the 2 key or the 3 key to select one of the two options available (‘1’ or ‘2’).
2) Press the 5 key to confirm.
M2M
62
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.9 Language menu
Language menu
Enter?
EN
x1 x3 x1
>2s
Setup
Active language
ITALIAN
Setup
M2M
63
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Self diagnosis m
Enter?
EN
x1 x2 x1
>2s
Setup
M2M
64
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.3.11 Info menu
Info menu
Enter?
EN
x1 x1 x1
>2s
Setup
In this menu the identifying data of the device can be displayed, such as:
•• Type of configuration
•• Series number
•• Firmware version
Press the 2 key or the 3 key to navigate between the pages and display the
information required.
M2M
65
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
M2M
66
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
Parameter Settable values Default
Input pulses factors (Wh/imp) [1÷10000] 10
Hour counter T2 (h) [1÷26280] 8760 (= 1 year)
Energy saving (automatic switching off
EN
ENABLED/DISABLED ENABLED
of display backlight)
OFF, INTERMEDIATE,
Display back lighting level MAXIMUM
MAXIMUM
MONOPHASE,
Configurations 3-PHASE, BALANCED 3-PHASE
3-PHASE, GENERIC
Generation mode ENABLED/DISABLED DISABLED
Energy cost factor (€/KWh) [0÷9.99] 0.18
Conversion factor in CO2 (KgCO2/KWh) [0÷9.99] 0.05
Password 4 digit alphanumericals 0000 = disabled
ENGLISH, ITALIAN,
FRENCH, SPANISH,
Language ENGLISH
GERMAN,
PORTUGUESE
Threshold in current for T2 timer (A) [0 - KA*5] 0A
Digital output mode Pulses or alarms Pulses
External synchronism for average values Enabled or disabled Disabled
M2M
67
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
Each key has a series of pages grouped according to the logic reported in the
following table:
Energies
Press the key corresponding to the data reading which you wish to carry out to
display the start page.
Each subsequent pressing of the same key cause the scrolling (cyclic) of the pages
available up to the return to the start page.
When you move from one key to another the first page to be
displayed is always the start page.
The display duration of a page is a maximum of 3 minutes after which the device will
return to the default page.
M2M
68
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.4.2 Voltages, Currents and 3-phase powers
EN
3-phase value Phase-neutral vo
PF 3F CAP0.99 Frq 50.0Hz
,3,9,8 V L1
,2,3,0 V
x1
,2.9,3 A x2
L2
,2,3,1 V
,1.9,9KW L3
,2,2,8 V
Concatenated voltages Currents
M2M
69
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
5.4.3 Energies
M2M
70
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
Equivalent active euro energy Equivalent active CO2 energy
EN
Equivalent euro Equivalent C02
€ 199.8 KgC02 55.4
x9 x10
Equivalent active euro energy generated Equivalent active CO2 energy generated
x11 x12
c c
M2M
71
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
M2M
72
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.4.5 THDF, Alarms, Timer and input pulses
Total voltage harmonic distortion factor (%) Total voltage harmonic distortion factor
EN
Distortion facto Distortion facto
THDFV% THDFV
L1
, , ,1 L1
,1.0,1
x1
L2
, , ,0 x2
L2
,1.0,0
L3
, , ,1 L3
,1.0,1
Total current harmonic distortion factor (%) Total current harmonic distortion factor
M2M
73
Rev. 1.0 NETWORK ANALYSER
CHAPTER 5
ABB OPERATING
M2M
74
NETWORK ANALYSER Rev. 1.0
CHAPTER 5
OPERATING ABB
5.4.6 Maximums
EN
Maximum values Maximum voltages
,4,0,0 V x1 L1
,2,3,3 V
x1
,2.9,9 A L2
,2,3,3 V
,2.1,0KW L3
,2,3,2 V
x1
Maximum concatenated voltages Maximum current
Maximum power
3F 2.40KVA
x1 L1
,8,8,5 VA
L2
,4,6,5 VA
L3
,1.1,3KVA
x6
M2M
75
Rev. 1.0 NETWORK ANALYSER
15. EC DECLARATION OF CONFORMITY
Form Issue Date Authorised Sheet No. 2nd Avenue, Centrum 100, Burton-on-Trent, Staffs. U.K.
CF091 11 18.02.14 M.W.B 1 of 1 Tel. +44 (0) 1283 531645 Fax. +44 (0) 1283 510103
E.C. DECLARATION OF CONFORMITY
Herewith we declare that the load proving equipment designated below, on the
basis of its design and construction, in the form brought on to the market by us,
is in accordance with the relevant safety and health requirements of the EC
Council Directive on electrical equipment. If modifications are made to the
equipment without prior consultations with us, this declaration becomes invalid.
Form Issue Date Authorised Sheet No. 2nd Avenue, Centrum 100, Burton-on-Trent, Staffs. U.K.
CF092 10 18.02.14 M.W.B 1 of 1 Tel. +44 (0) 1283 531645 Fax. +44 (0) 1283 510103
16. END OF LIFE PRODUCT RECYCLING AND DISPOSAL
With proper maintenance Crestchic Loadbanks can be used reliably for many years. We
offer a service department who can provide spare parts, maintenance and upgrades for
all our loadbanks.
If you require to dispose of the loadbank locally all the components can be unbolted from
the enclosure and separated for recycling.
It is the responsibility of the loadbank owner to ensure that disposal is carried out in
accordance with local regulations. For environmentally friendly recycling and disposal of
your electronic waste, please contact a local company certified for the disposal of
electronic waste.
Form Issue Date Authorised Sheet No. 2nd Avenue, Centrum 100, Burton-on-Trent, Staffs. U.K.
CF091 11 18.02.14 M.W.B 1 of 1 Tel. +44 (0) 1283 531645 Fax. +44 (0) 1283 510103
E.C. DECLARATION OF CONFORMITY
Herewith we declare that the load proving equipment designated below, on the
basis of its design and construction, in the form brought on to the market by us,
is in accordance with the relevant safety and health requirements of the EC
Council Directive on electrical equipment. If modifications are made to the
equipment without prior consultations with us, this declaration becomes invalid.
Form Issue Date Authorised Sheet No. 2nd Avenue, Centrum 100, Burton-on-Trent, Staffs. U.K.
CF092 10 18.02.14 M.W.B 1 of 1 Tel. +44 (0) 1283 531645 Fax. +44 (0) 1283 510103
16. END OF LIFE PRODUCT RECYCLING AND DISPOSAL
With proper maintenance Crestchic Loadbanks can be used reliably for many years. We
offer a service department who can provide spare parts, maintenance and upgrades for
all our loadbanks.
If you require to dispose of the loadbank locally all the components can be unbolted from
the enclosure and separated for recycling.
It is the responsibility of the loadbank owner to ensure that disposal is carried out in
accordance with local regulations. For environmentally friendly recycling and disposal of
your electronic waste, please contact a local company certified for the disposal of
electronic waste.