Enclosed ATS: Enclosed Automatic Transfer Switch
Enclosed ATS: Enclosed Automatic Transfer Switch
Auto
Mode
L&T Electrical & Automation, India's leading switchgear company, is dedicated to promoting excellence
in among the fraternity of electrical practitioners. Beginning with a single Switchgear Training Centre
(STC) in Pune in 1986, the initiative has grown to cover 6 state-of the-art facilities at strategic locations
across the country.
The STCs offer a wide range of courses with hands-on training for students, electricians, electrical
engineers, panel builders and consultants. A cutting-edge curriculum, refreshed regularly, helps
enhance on-site electrical safety, system reliability and cost efficiency.
Introduction 01
Technical Parameters 09
Overall Dimensions 13
INTRODUCTION
Rapid industrialization and urbanization are leading to ever-rising demand for reliable
electricity.
Technological advancement and changing lifestyles have given rise to many applications
which demand 24 X7 uninterruptible power supply. In some industries, power outages
for even short duration may lead to considerable commercial losses.
L&T’s Enclosed Automatic Transfer Switch(ATS) constantly monitors the incoming power
sources and seamlessly switches the load to the ‘back-up’ supply when it senses
variation or abnormality in the main supply. Once main supply is restored, the load is
automatically shifted to the main supply.
Option of priority source selection and swapping gives additional flexibility to suit
different site requirements.
These switches are very convenient to use as one does not have to manually operate the
switch.
The typical applications are in critical processes in various industries and also in growing
residential, commercial & infrastructure segments.
1
Enclosed Automatic
Transfer Switch
Range:
125A to 630A,
415V AC
Flexibility
• Priority Source Selection
• Adjustable Time Delay (0.1 sec to 3 hours)
• Suitable for 3-Phase as well as 1-Phase Sources
Performance
• Double-Break Contact System offering High
Short-time withstand (ICW)
• High Mechanical & Electrical Life: Double than
requirement of IS/IEC Standard
• Suitable for Aluminium Termination
Safety
• Protections : UV/OV, Phase Sequence, Single
Phasing, Frequency
• Authorized Access Control through Password
Protection
• Inbuilt Terminal Shrouds, Phase Barriers &
Source Separator
Convenience
• Ample Space for Cable Termination,
No need of Separate Cable Gland Box
• Ease of Generator Control
(ON-OFF Cooling Cycle, Self-Test)
• Cyclic Event Logger : Logs 100 Events
2
Motorised Changeover
Product Features
3
Clear Manual override Manual and Auto
termination Manual operation of motorised
changeover switch is also
mode selection
access feasible through the manual
The selector switch enables/disables
Motorised kit (EOM) fits well the control supply to motorised
override feature. As a safety
within the body of the manual changeover switch. Electrical
feature, the control supply of
changeover switch, enabling operation is possible only in auto
motorised kit (EOM) is
clear access to the terminals mode while manual mode allows
automatically cut off during the
even after mounting the the user to operate the motorised
insertion of handle
motorised kit changeover switch manually using
the handle safely by cut-off of
control supply to motorised
changeover switch
4
AuXC-2000 Controller
tic
a
m er
to sf
Au ran
T
5
AuXC-2000 Controller
Intuitive user interface Password access to prevent any unauthorized
• 5 keys navigation keypad for parameters setting access
• 128x80 pixel, Backlit LCD screen with 4 Grey levels • The password is used to enable or disable the access
to setting menu and to commands menu
Status at a glance
• 4 LEDs for plant synoptic (source line and ATS status) Generator setup
• 2 LEDs for alarm presence and AUTO mode active • Management of generator set start-stop & cooling cycle
• Management of automatic test for generators with
Flexibility to suit site conditions emergency and rotation
• Suitable for switching between Utility-Utility or
Utility-Gensetor Genset-Genset Failure simulation
• Selection between auto and manual mode of switching • Test the changeover setup without connecting actual load
• Enabling and disabling of priority supply
• Settable transition time for allevents Event Logger
• Storage of last 100 events
Programmable digital inputs, outputs &
alarms to control changeover device
• 6 programmable digital inputs
• 6 +1digital outputs:
- 6 relay swith NO contact (8A, 250V AC)
- 1 relay swith changeover contact (8A, 250V AC)
• 18 alarms (4 user programmable alarms)
6
AuXC-2000 Controller
Selects the
OFF operating
mode
▲ and ▼ keys - Used to scroll through the display pages or to select the list of options
in a menu. Simultaneously pressing ▼ + ▲ calls up the Main menu with rotating icons
Front LED
Line 1 voltage status Line 2 voltage status
LED (green) - LED (green) -
indicates that the line indicates that the line
voltage source 1 is within voltage source 2 is within
the programmed limits the programmed limits.
Modes of Operation:
OFF Mode:
In this mode, the automatic control is disabled and the controller does not take any action. All views of the measures and the status
of the LEDs remain active.
To access the programming/settings menu, it is mandatory to operate in OFF mode.
Pressing the OFF-RESET button resets the retentive alarms, provided the conditions that generated the alarm have been removed.
7
Manual Mode:
In this mode, the ATS can be manually controlled by the pressing the MAN key.
Closing/opening operation can be done by:
- Selecting the switch position
- Pressing the up and down buttons to confirm the closing or opening operation
The generators can also be controlled manually by moving on the page start/stop groups.
Line 2 selected
Breaker 1 selected
Selectable function
Function selectable Page scroll locked with MAN
Page scroll locked with MAN
Auto Mode:
The AUT mode is indicated by the green LED for AUT. In automatic mode, the controller automatically gives command for opening
& closing of the ATS. When the priority line voltage is out of bounds for a time longer than that specified (line presence green LED
turns off), the unit disconnects the load from the priority line and connects it to secondary line considering start-up of generator
(if programmed) and interlock time delay. When the priority line returns within the programmed limits, the controller will switch
back the load on it.
The cycles of automatic operation vary according to the type of application (utility-utility, utility-generator, generator generator).
8
Enclosed Automatic Transfer Switch
Rating(A) Unit
Reference Standards
Type Designation
No. of Poles
Rated Operational Voltage(Ue) (power circuit)
Rated Impulse Withstand Volatge(Uimp) ( power circuit) (V)
Rated Operational Voltage(Ue) (control circuit) (kV)
Rated Impulse Withstand Volatge(Uimp) ( control circuit) (kV)
Rated Frequency (Hz)
Pollution Degree
Conventional enclosed thermal current at 40O(Ithe) (A)
Rated Operational Current(I the) according to IS/IEC: 60947-3
415Vac, AC-21A / AC-22A / AC-23A (A)
Rated Operational Current(I the) according to IS/IEC: 60947-6
415Vac, AC-31B (A)
415Vac, AC-31A (A)
415Vac, AC-32B (A)
Rated breaking capacity for AC-23A (A)
Rated making capacity for AC-23A (A)
1 sec (kA rms)
Short time withstand, lcw (kA rms)
0.2 sec
Short-circuit making capacity, lcm (kA peak)
Endurance (category AC 23A) Mechanical (O-I-O-II-O cycle)
Endurance (category AC 23 A) Electrical (O-I-O-II-O cycle)
Rated fused short-circuit current at 415V, 50/60 Hz DIN/Cylin (kA rms)
Operating torque (N-m)
Weight (kg)
Rated Control Voltage (V)
Control Voltage Range (%)
Max. Current at 240V ac (A)
O-I / I-O (sec)
Operating time
I-II / II-I (sec)
Black out time (sec)
Termination
Maximum Al. cable with lug ( sq. mm)
Maximum link width (mm)
Maximum link thickness (mm)
Termination tightening torque (N-m)
9
Frame 2 Frame 3 Frame 4
125A 160A 200A 250A 315A 400A 630A
IS / IEC 60947-3, EN 60947-3, IS / IEC 60947-6-1, EN 60947-6-1
ATS-125 ATS-160 ATS-200 ATS-250 ATS-315 ATS-400 ATS-630
4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole 4 Pole
415 415 415 415 415 415 415
12 12 12 12 12 12 12
4 4 4 4 4 4 4
50/60 50/60 50/60 50/60 50/60 50/60 50/60
3 3 3 3 3 3 3
125 160 200 250 315 400 630
10
Wiring Diagrams & Control Logic
SOURCE 1 SOURCE 2
K2 K1
K1 K2
K1
K2
K1
K2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
L1 L2 L3 N L1 L2 L3 N A1 A2
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
11
Pre-programmed Parameters Time Delay Setting
Preprogrammed Available
Parameter Code
Programing Connection Code Setting (Description) Setting
Terminal Line 1 to Line 2 interlock time M05>>P05.03 0.1 0.1....1800Sec
15(INP1) M10>> P10.01.01 Line 1 closed (Feedback 1)
Inputs Line 2 to Line 1 interlock time M05>>P05.04 0.1 0.1....1800Sec
16(INP2) M10>> P10.02.01 Line 2 closed(Feedback 2)
Presence delay 1
25(OUT4) M11>> P11.04.01 Close line 1 (When Line 2 source not available) M06>>P06.07 1....6000Sec
Outputs 27(OUT5) M11>> P11.05.01 Open line 1 / line 2 Presence delay M06>>P06.08 1 1....6000Sec
(When Line 2 source available)
30(OUT7) M11>> P11.07.01 Close line 2
Presence delay 1....6000Sec
Others - M05>> P05.07 Changeover Pulse (When Line 1 source not available) M07>>P07.07 1
Presence delay
(When Line 2 source available) M07>>P07.08 1 1....6000Sec
Note : Refer AuXC2000- Automatic Transfer Controller Manual for further details and complete settings/programming parameters
Ordering Information
Description CAT No.
Enclosed ATS, Frame 2, 125A CK90161BSOO
Enclosed ATS, Frame 2, 160A CK90162BSOO
Enclosed ATS, Frame 2, 200A CK90163BSOO
Enclosed ATS, Frame 3, 250A CK90164BSOO
Enclosed ATS, Frame 3, 315A CK90165BSOO
Enclosed ATS, Frame 4, 400A CK90166BSOO
Enclosed ATS, Frame 4, 630A CK90167BSOO
12
Enclosed ATS
Overall Dimensions
E C D
B
213
Mounting Holes
B
A 213
RATING(A) A B C D
13
Enclosed ATS
Handle Clamp & IP Cover Mounting
Clamp Mounting for Handle
- Remove the screws and fix clamp to the enclosure as shown.
- Keep the handle inside the clamp when not in use.
IP Cover Mounting
Insert the IP cover as shown
Click
14
Notes:
Notes:
SP 51009 R0