Low Voltage Alternator - 4 Pole: Installation and Maintenance
Low Voltage Alternator - 4 Pole: Installation and Maintenance
                                           LSA 44.3
                             Low Voltage Alternator - 4 pole
This manual concerns the alternator which you have just purchased.
We wish to draw your attention to the contents of this maintenance manual.
2
      Electric Power Generation                 Installation and maintenance                              5056 en - 2021.09 / k
                                                         LSA 44.3
                                    Low Voltage Alternator - 4 pole
                                                           CONTENTS
1 - RECEIPT.............................................................................................................................4
     1.1 - Standards and safety measures................................................................................ 4
     1.2 - Inspection.................................................................................................................. 4
     1.3 - Identification.............................................................................................................. 4
     1.4 - Storage...................................................................................................................... 4
     1.5 - Applications............................................................................................................... 4
     1.6 - Usage restrictions...................................................................................................... 4
2 - TECHNICAL CHARACTERISTICS....................................................................................5
     2.1 - Electrical characteristics............................................................................................ 5
     2.2 - Mechanical characteristics........................................................................................ 5
3 - INSTALLATION..................................................................................................................7
     3.1 - Assembly................................................................................................................... 7
     3.2 - Checks prior to first use............................................................................................. 8
     3.3 - Terminal connection diagrams................................................................................... 8
     3.4 - Commissioning.........................................................................................................11
     3.5 - Setting up.................................................................................................................11
4 - SERVICING - MAINTENANCE.........................................................................................12
     4.1 - Safety measures...................................................................................................... 12
     4.2 - Routine maintenance............................................................................................... 12
     4.3 - Bearings.................................................................................................................. 13
     4.4 - Mechanical defects.................................................................................................. 13
     4.5 - Electrical faults........................................................................................................ 14
     4.6 - Dismantling, reassembly......................................................................................... 16
     4.7 - Installation & maintenance of the PMG................................................................... 17
     4.8 - Table of characteristics............................................................................................ 18
5 - SPARE PARTS.................................................................................................................20
     5.1 - First maintenance parts........................................................................................... 20
     5.2 - Technical support service........................................................................................ 20
     5.3 - Accessories............................................................................................................. 20
     5.4 - Exploded views, parts list and tightening torque..................................................... 21
EC Declaration
                                                                                                                                        3
     Electric Power Generation                Installation and maintenance                                5056 en - 2021.09 / k
                                                      LSA 44.3
                               Low Voltage Alternator - 4 pole
1 - RECEIPT                                                           1.4 - Storage
1.1 - Standards and safety                                            Prior to commissioning, machines should
measures                                                              be stored:
                                                                      - away from humidity (< 90%); after a long
Our alternators comply with most                                      period of storage, check the machine
international standards.                                              insulation. To prevent the bearings from
See the EC Declaration of Incorporation on                            becoming marked, do not store in an
the last page.                                                        environment with significant vibration.
1.2 - Inspection                                                      1.5 - Application
On receipt of your alternator, check that it                          This alternator is mainly designed to
has not suffered any damage in transit. If                            produce electricity in the context of
there are obvious signs of knocks, contact                            applications involving the use of
the transporter (you may be able to claim                             generators.
on their insurance) and after a visual
check, turn the machine by hand to detect                             1.6 - Usage restrictions
any malfunction.                                                      Use of the machine is restricted to operating
                                                                      conditions (environment, speed, voltage,
1.3 - Identification                                                  power, etc) compatible with the characteri-
The alternator is identified by means of a                            stics indicated on the nameplate.
nameplate fixed on the machine (see
drawing).
Make sure that the nameplate on the
machine conforms to your order.
So that you can identify your alternator
quickly and accurately, we suggest you fill in
its specifications on the nameplate below.
                                                                      MOTEURS LEROY-SOMER
                                                          2 BD MARCELLIN LEROY - 16000 ANGOULÊME - FRANCE
                                                                             www.leroy-somer.com                    Scan the code or go to
                                                                                                                         GEN.LS1.DO
                                                                          Made in Europe by Leroy-Somer             to check product data
4
    Electric Power Generation     Installation and maintenance                 5056 en - 2021.09 / k
                                        LSA 44.3
                            Low Voltage Alternator - 4 pole
2 - TECHNICAL                                            2.2 - Mechanical characteristics
CHARACTERISTICS                                          - Steel frame
                                                         - Cast iron end shields
2.1 - Electrical characteristics                         - Protected ball bearings, greased for life
This alternator is a machine without                     - Mounting arrangement: single bearing
sliprings or revolving armature brushes,                 with standard feet and SAE flanges/
wound as “2/3 pitch”, 4 or 12-wire, with                 coupling discs, two-bearing with SAE flange
class H insulation and a field excitation                and standard cylindrical shaft extension
system available in either SHUNT, AREP or                - Drip-proof machine, self-cooled
PMG version (see diagrams and AVR                        - Degree of protection: IP 23
manuals).
                                                         • Mechanical options
• Electrical options                                     - Air inlet filter
- Stator temperature detection sensors                   - IP 44 protection
- Space heaters
- R791 interference suppression
                                                                                    T1 T3
     EXCITER
                                              Varistor
Armature
                                                                                    T2      T4
       Field
                                                                                                           5
         Electric Power Generation        Installation and maintenance                 5056 en - 2021.09 / k
                                                     LSA 44.3
                                 Low Voltage Alternator - 4 pole
• SHUNT three-phase 12-wire
                                 MAIN FIELD                                    STATOR: 12-wire (marking T1 to T12)
                                                                               T1 T7         T2 T8         T3 T9
         EXCITER
                                               Varistor
         Armature
    5+              6-
                                                                               T4 T10        T5 T11            T6 T12
           Field
         Armature
    5+              6-
                                                                               T4 T10        T5 T11            T6 T12
           Field
                                                                               T1 T7         T2 T8         T3 T9
         EXCITER
                                              Varistor
PMG
         Armature
 5+                 6-
                                                                               T4 T10        T5 T11            T6 T12
           Field
6
    Electric Power Generation     Installation and maintenance          5056 en - 2021.09 / k
                                        LSA 44.3
                            Low Voltage Alternator - 4 pole
3 - INSTALLATION                                   • Single-bearing coupling
Personnel undertaking the various                  Before coupling, check the compatibility
operations indicated in this section must          between the alternator and the engine by
wear personal protective equipment                 performing:
appropriate for mechanical and electrical          - undertaking a torsional analysis of the
hazards.                                           transmission (alternators data are available
                                                   on request),
3.1 - Assembly                                     - checking the dimensions of the flywheel
                                                   and its housing, the flange, coupling discs
                                                   and offset.
                                                                  WARNING
All mechanical handling operations                 When coupling the alternator to the
must be undertaken using suitable                  prime mover, do not use the fan to turn
equipment and the machine must be                  the alternator or rotor.
horizontal. Check how much the machine             The holes of the coupling discs should
weighs before choosing the lifting tool.           be aligned with the flywheel holes by
During this operation, do not allow                cranking the engine.
anyone to stand under the load.                    Make sure the machine is securely
                                                   bedded in position during coupling.
• Handling                                         Check that there is lateral play on the
The generously-sized lifting eyes are for          crankshaft.
handling the alternator only. They must not        • Double-bearing coupling
be used to lift the genset. The choice of          - Semi-flexible coupling
lifting hooks or handles should be determined      Careful alignment of the machines is
by the shape of the lifting eyes. Choose a         recommended, checking that the lack of
lifting system which respects the integrity        concentricity and parallelism of both parts
and the environment of the machine.                of the coupling do not exceed 0.1 mm.
                                                   This alternator has been balanced with a
During this operation, do not allow                1/2 key.
anyone to stand under the load.                    • Location
                                                   The location where the alternator is placed
                                                   must be ventilated to ensure that the
                                                   ambient temperature cannot exceed the
                                                   data on the nameplate.
                                                                                                7
     Electric Power Generation     Installation and maintenance                             5056 en - 2021.09 / k
                                          LSA 44.3
                             Low Voltage Alternator - 4 pole
3.2 - Checks prior to first use                     3.3 - Terminal connection diagrams
• Electrical checks                                 To modify the connection, change the
                                                    position of the stator cables on the terminals.
                                                    The winding code is specified on the
                                                    nameplate.
                                                                         T2                            T4
                                                                                                            L
                 WARNING                                            0V        T3
                                                                                                       T1
                                                                                                            NDE
Ensure that the alternator has the degree
of protection matching the defined
environmental conditions.
• Mechanical checks
Before starting the machine for the first time,
check that:
- all fixing bolts are tight,
- the length of bolt and the tightening torque
are correct,
- the cooling air is drawn in freely,
- the protective grille and housing are cor-
rectly in place,
- the standard direction of rotation is clock-
wise as seen from the drive end (phase
rotation in order 1 - 2 - 3).
For anti-clockwise rotation, swap 2 and 3.
- the winding connection corresponds to the
site operating voltage (see section 3.3).
8
          Electric Power Generation                                               Installation and maintenance                    5056 en - 2021.09 / k
                                                                                            LSA 44.3
                                                                     Low Voltage Alternator - 4 pole
• SHUNT, AREP or PMG three-phase 12-wire
                        Connection codes                                                 Voltage / Detection                    Factory connection
 A        3PH                          L1(U)
                                                                                  Winding       50 Hz          60 Hz                      T12
                                                                                                                          T6       T11
 D        3PH                     T1
                                            L1(U)                                 Winding       50 Hz             60 Hz            T11
                                                                                                                                          T12
 F        1PH                                                                     Winding       50 Hz          60 Hz
           or                                L1(U)
          3PH                     T12          T1                                    6        220 - 240      220 - 240
                                                                                                                          T6       T3
                             T9                        T4
                                                                                     7        250 - 260            -      T9       T11
                                                                                                                                                   L      L3(W)
                        T6                              T7
                                                                                     8           200         220 - 240    T5
                                                                                                                                                   L
                                                                                                                          T8      T10                     L2(V)
                   T3                                          T10
                                                                                      R250 :                              T4       T2
  L3(W)                                                              L2(V)
                        T11            T8      T5         T2                          0 => (T8) / 110 V => (T11)
          L                                                               L                                               T7      T12                     L1(U)
                                            M                                         D350 :
 Voltage LM = 1/2 voltage LL                                                          U => T1 / V => T2 / W => T3                  T1
                                                                                                                                                              NDE
                                                                                  Winding       50 Hz          60 Hz
 FF                                                                                                                       T4       T11
              1PH
                                                                                                                          T7
                                                                                     6        220 - 240      220 - 240
                   T2         T6                  T8         T12                                                                   T3
                                                                                     7        250 - 260            -      T9                              L
                                       T3
          T5                             T11                         T9              8            200        220 - 240            T10
               T1                 T4            T7                                                                        T8       T6
                                                                T10
 L                                                                            L       R250 :
                                            M                                                                             T12      T2
                                                                                      0 => (T1) / 110 V => (T4)
                                                                                                                                   T5                     L
                                                                                      D350 :
 Voltage LM = 1/2 voltage LL                                                                                                                                  NDE
                                                                                      V => T1 / W => T10                           T1
                                                                                                                                                                  9
         Electric Power Generation                           Installation and maintenance                              5056 en - 2021.09 / k
                                                                        LSA 44.3
                                                    Low Voltage Alternator - 4 pole
• SHUNT, AREP or PMG three-phase 12-wire
                     Connection codes                                   Voltage / Detection                          Factory connection
                                                                                            ST
                                                                                Voltage adjustment
                                                                                via remote potentiometer
                                                                                      103                                        130 °C
                                                                                                                     Ph1         Blue wire
                     101                                                                                                         150 °C
                                                                                                                     Ph2         Black wire
                     102
                                                                                                                                 180 °C
                                                                                                                     Ph3         Red/white wire
                                                                                      104
10
     Electric Power Generation     Installation and maintenance          5056 en - 2021.09 / k
                                         LSA 44.3
                             Low Voltage Alternator - 4 pole
• Connection checks                                 3.4 - Commissioning
                                                                                                 11
     Electric Power Generation    Installation and maintenance             5056 en - 2021.09 / k
                                         LSA 44.3
                             Low Voltage Alternator - 4 pole
4 - SERVICING - MAINTENANCE                                        WARNING
4.1 - Safety measures                              Do not use: trichlorethylene, perchlo-
Servicing or troubleshooting must be
                                                   rethylene, trichloroethane or any alkaline
carried out strictly in accordance with
                                                   products.
instructions so as to avoid the risk of
accidents and to maintain the machine in
its original state.
                                                   These operations must be performed at
                                                   a cleaning station, equipped with a
                                                   vacuum system that collects and flushes
All such operations performed on the
                                                   out the products used.
alternator should be undertaken by
                                                   The insulating components and the
personnel trained in the commissioning,
servicing and maintenance of electrical            impregnation system are not at risk of
and mechanical components, who must                damage from solvents. Avoid letting the
wear personal protective equipment                 cleaning product run into the slots.
appropriate for mechanical and electrical          Apply the product with a brush, sponging
hazards.                                           frequently to avoid accumulation in the
Before any intervention on the machine,            housing. Dry the winding with a dry cloth. Let
ensure that it cannot be started by a manual       any traces evaporate before reassembling
or automatic system and that you have              the machine.
understood the operating principles of the         • Mechanical servicing
system.
                                                                   WARNING
                                                   Cleaning the machine using water or a
                                                   highpressure washer is strictly prohi-
Warning : During and after running, the
                                                   bited. Any problems arising from such
alternator will reach temperatures hot
enough to cause injury, such as burns.             treatment are not covered by our
                                                   warranty.
                                                   Degreasing: Use a brush and detergent
4.2 - Routine maintenance                          (suitable for paintwork).
                                                   Dusting: Use an air gun.
• Checks after start-up
                                                   If the machine is fitted with air inlet and outlet
After approximately 20 hours of operation,
check that all fixing bolts on the machine are     filters, the maintenance personnel should
still tight, plus the general state of the         clean them routinely at regular intervals. In
machine and the various electrical                 the case of dry dust, the filter can be cleaned
connections in the installation.                   using compressed air and/or replaced if it is
                                                   clogged.
• Electrical servicing                             After cleaning the alternator, it is essential to
Commercially-available volatile degreasing         check the winding insulation (see sections
agents can be used.                                3.2 and 4.5).
12
    Electric Power Generation         Installation and maintenance                    5056 en - 2021.09 / k
                                               LSA 44.3
                            Low Voltage Alternator - 4 pole
4.3 - Bearings
The bearings are permanently greased           Approximate life of the grease (depending on use) =
                                               20,000 hours or 3 years.
                                                - System short-circuit
                                                - Misparalleling
             Alternator damaged by a            Possible consequences
Abnormal                                        - Broken or damaged coupling
             significant impact, followed by
noise                                           - Broken or bent shaft end
             humming and vibration
                                                - Shifting and short-circuit of main field
                                                - Fan fractured or coming loose on shaft
                                                - Irreparable damage to rotating diodes/AVR, surge suppressor
                                                                                                                  13
       Electric Power Generation                   Installation and maintenance                                5056 en - 2021.09 / k
                                                             LSA 44.3
                                      Low Voltage Alternator - 4 pole
4.5 - Electrical faults
     Fault                Action                            Effect                                       Check/Cause
                                             The alternator builds up and
                                             its voltage is still correct - Lack of residual magnetism
                                             when the battery is removed
              Connect a new
              battery of 4 to 12             The alternator builds up but           - Check the connection of the voltage reference
No voltage volts to terminals                its voltage does not reach               to the AVR
at no load on E- and E+,                     the rated value when the               - Faulty diodes
start-up      respecting the                 battery is removed                     - Armature short-circuit
              polarity, for 2 to 3
                                             The alternator builds up but -- Faulty
              seconds                                                               AVR
                                             its voltage disappears when - Field   windings open circuit (check winding)
                                                                             Revolving field coil open circuit (check the
                                             the battery is removed          resistance)
                                                                                    Check the AVR connections (AVR may be
                                                                                    faulty)
                                                                                    - Field windings short-circuited
                                             Correct speed                          - Rotating diodes burnt out
Voltage too       Check the drive                                                   - Revolving field coil short-circuited (check the
low               speed                                                               resistance)
                                                                                    Increase the drive speed (do not touch the AVR
                                             Speed too low                          voltage pot. (P2) before running at the correct
                                                                                    speed)
Voltage too       Adjust AVR voltage Adjustment ineffective                         - Faulty AVR
high              potentiometer
                                                                              - Check the speed: possibility of cyclic
                                                                                irregularity
                  Adjust the
Voltage                                      If no effect: try normal or fast - Loose connections
                  AVR stability
oscillations                                 stability modes (ST2)            - Faulty AVR
                  potentiometer                                               - Speed too low when on load (or AVR LAM set
                                                                                too high)
                                 Voltage between E+ and E-
                                 (DC)
Voltage       Run at no load and SHUNT < 20V - AREP / PMG - Check the speed (or AVR LAM set too high)
correct at no check the voltage < 10V
load and too between E+ and
                                 Voltage between E+ and E- -- Faulty
low when on E- on the AVR                                            rotating diodes
                                 SHUNT > 30V - AREP / PMG Short-circuit
load (*)                                                                    in the revolving field coil (check
                                                              the resistance)
                                 > 15V                      - Faulty exciter armature (check the resistance)
                  Check the AVR, the                                                - Exciter winding open circuit
Voltage           surge suppressor,                                                 - Faulty exciter armature
disappears        the rotating diodes, The voltage does not return                  - Faulty AVR
during            and replace any      to the rated value                           - Revolving field coil open circuit or short-
operation         defective                                                           circuited
                  components
(*) During single-phase operation, check that the sensing wires from the AVR are connected to the correct output terminals.
14
    Electric Power Generation                   Installation and maintenance                             5056 en - 2021.09 / k
                                                      LSA 44.3
                            Low Voltage Alternator - 4 pole
• Checking the winding                                           Assembly A: Connect a 12 V battery in
You can check the winding insulation by                          series with a rheostat of approximately
performing a high voltage test. In this case,                    50 ohms - 300 W and a diode on both exciter
you must disconnect all AVR wires.                               field wires (5+) and (6-).
                                                                   ASSEMBLY A
                                                                             6 - Field                               5+
                     WARNING
                                                                                                   1A diode      Rh. 50 -300W
Damage caused to the AVR in such
conditions is not covered by our
warranty.                                                                                               +
                                                                       -
• Checking the diode bridge
A diode in good working order should allow                                                        12V battery
the current to flow only in the anode-to-
cathode direction.                                               Assembly B: Connect a “Variac” variable
             Anode
                     +          -
                                        Cathode
                                                                 power supply and a diode bridge on both
    +    -
                                                                 exciter field wires (5+) and (6-).
                                    +       -
                                                                 Both these systems should have
                                                                 characteristics which are compatible with
    A    C
                                    A       C                    the field excitation power of the machine
                                                                 (see the nameplate).
                                                                 3) Run the unit at its rated speed.
                                                                 4) Gradually increase the exciter field
                                                                 current by adjusting the rheostat or the
                                                                 variac and measure the output voltages on
                                                                 L1 - L2 - L3, checking the excitation voltage
                                                                 and current at no load (see the machine
                                                                 nameplate or ask for the factory test report).
                                                                 When the output voltage is at its rated value
                                                                 and balanced within 1% for the rated
                                                                 excitation level, the machine is in good
                                                                 working order. The fault therefore comes
                                                                 from the AVR or its associated wiring (ie.
• Checking the windings and rotating                             sensing, auxiliary windings).
diodes using separate excitation
                                                                     ASSEMBLY B
                                                                                                            6 - Field              5+
                                                                            40
                                                                                 50   60                                +
                                                                      30
70
                                                                                                                                 1A diode
During this procedure, make sure that
                                                                      20
80
90
0 100
                                                                                                                                        15
     Electric Power Generation     Installation and maintenance           5056 en - 2021.09 / k
                                         LSA 44.3
                             Low Voltage Alternator - 4 pole
4.6 - Dismantling, reassembly                       - Check all modules using an ohmmeter or a
                                                    battery lamp.
                 WARNING                            - Refit the modules.
                                                    - Refit the air intake grille (51).
During the warranty period, this
operation should only be carried out in             • Access to connections and the
an approved workshop or in our factory,             regulation system
otherwise the warranty may be
invalidated.                                        The terminals are accessed directly by
Whilst being handled, the machine                   removing the terminal box lid (48).
should remain horizontal (rotor not
locked in position). Check how much the             • Replacing the NDE bearing on single
machine weighs before choosing the                  bearing machines
lifting method.                                     Dismantling
                                                    - Remove the terminal box lid (48).
                                                    - Unscrew the fixing clamps on the power
                                                    output cables, remove the connector from
                                                    the exciter.
                                                    - Remove the nuts on the tie rods.
                                                    - Remove the NDE shield (36) using a puller:
                                                    eg. U.32 - 350 (Facom).
                                                    - Remove the antifriction bearing (70) using
                                                    a screw puller.
• Tools required
To fully dismantle the machine, we
recommend using the tools listed below:             Reassembly
- 1 ratchet spanner + extension                     - Heat the inner slipring of a new bearing by
- 1 torque wrench                                   induction or in a drying oven at 80°C (do not
- 1 set of flat spanners: 7, 8, 10, 12 mm           use an oil-bath) and fit it to the machine.
- 1 socket set: 8, 10, 13, 16, 18, 21, 22,          - Place the preloading wavy washer (79) in
24 mm                                               the shield and fit a new “O” ring seal (349).
- 1 Allen key: size 5 (eg. Facom: ET5), size 6      Refit the NDE shield and pass the bundle of
(ET6), size 10 (ET10, size 14 (ET14)                wires between the top bars of the shield.
- 1 socket TORX bit T20 and T30                     - Refit the fixing clamps on the cables and
- 1 puller (U35)/(U32/350)                          the exciter connector.
• Screw tightening torque                           - Replace the terminal box lid (48) and also
                                                    the earth continuity screw (29).
See section 5.4.
• Access to diodes
- Remove the air intake grille (51).
16
    Electric Power Generation       Installation and maintenance             5056 en - 2021.09 / k
                                          LSA 44.3
                            Low Voltage Alternator - 4 pole
                                                     • Accessing the main field and stator
                                                                                                     17
      Electric Power Generation            Installation and maintenance              5056 en - 2021.09 / k
                                                 LSA 44.3
                              Low Voltage Alternator - 4 pole
4.8 - Table of characteristics                              • Three-phase: 4-pole, AREP excitation
Table of average values:                                    Resistances at 20 °C (Ω)
Alternator - 4 pole - 50 Hz - Standard winding
                                                                          Stator       Exciter Exciter
No. 6 (12-wire) and M or M1 (4-wire)                            Type             Rotor
                                                                           L/N          field armature
connected in dedicated single-phase (400 V
for the excitation values).                                    S2/S3      0.0503   2.354     7.262           0.790
The voltage and current values are given for                   S4/S5      0.0390   2.642     8.068           0.920
no-load operation and operation at rated                        M6        0.0335   2.893     8.068           0.920
load with separate field excitation.                            M8        0.0287   3.145     8.068           0.920
All values are given to within ± 10% and may                    L10       0.0236   3.433     8.068           0.920
be changed without prior notification (for
                                                                L12       0.0236   3.433     8.068           0.920
exact values, consult the test report).
                                                             VL13/VL14    0.0188   4.044     5.307           1.149
For 60 Hz machines, the “i exc” values are
approximately 5 to 10 % lower.
                                                            Resistance of auxiliary windings at
                                                            20 °C (Ω)
• Three-phase: 4-pole, SHUNT excitation
                                                               Type           X1, X2                 Z1, Z2
Resistances at 20 °C (Ω)
                                                               S2/S3          0.341                  0.627
               Stator       Exciter Exciter                    S4/S5          0.305                  0.571
     Type             Rotor
                L/N          field armature                     M6            0.289                  0.575
  S2/S3        0.0503   2.354     11.647     0.790              M8            0.271                  0.559
  S4/S5        0.0390   2.642     12.942     0.920              L10           0.247                  0.525
   M6          0.0335   2.893     12.942     0.920              L12           0.247                  0.525
   M8          0.0287   3.145     12.942     0.920           VL13/VL14        0.238                  0.547
   L10         0.0236   3.433     12.942     0.920
   L12         0.0236   3.433     12.942     0.920          Field excitation current i exc (A)
VL13/VL14      0.0188   4.044      5.307     1.149          400V - 50 Hz
                                                            “i exc”: excitation current of the exciter field
Field excitation current i exc (A)                             Type        No load             At rated load
400V - 50 Hz                                                    S2          0.97                    2.67
“i exc”: excitation current of the exciter field
                                                                S3          0.97                      3
     Type         No load          At rated load                S4          0.94                    2.71
      S2           0.75                 2.07                    S5          0.94                    2.98
      S3           0.75                 2.33                    M6          0.85                    3.18
      S4           0.73                 2.11                    M8          0.81                    3.05
      S5           0.73                 2.31                    L10         0.86                    3.15
      M6           0.66                 2.47                    L12         0.86                    3.49
      M8           0.62                 2.37                   VL13         0.78                    3.17
      L10          0.67                 2.45                   VL14         0.78                    3.53
      L12          0.67                 2.71
     VL13          0.78                 3.17
     VL14          0.78                 3.53
18
     Electric Power Generation         Installation and maintenance              5056 en - 2021.09 / k
                                              LSA 44.3
                              Low Voltage Alternator - 4 pole
• Dedicated single-phase M: 4-pole,                     • Table of weights
SHUNT excitation - 50 Hz                                (values given for information only)
                                                                                                             19
     Electric Power Generation     Installation and maintenance            5056 en - 2021.09 / k
                                           LSA 44.3
                             Low Voltage Alternator - 4 pole
5 - SPARE PARTS                                     In the event of failure to comply with this
                                                    advice, the manufacturer cannot be held
5.1 - First maintenance parts                       responsible for any damage.
Emergency repair kits are available as an
option.
They contain the following items:
Emergency kit SHUNT              4891855
 AVR R250                           -               After operational testing, it is essential
 Diode bridge assembly              -               to replace all access panels or covers.
 Surge suppressor                   -
Emergency kit AREP/PMG           5155834            5.3 - Accessories
 AVR D350                           -               • Space heater for use when stopped
 Diode bridge assembly              -               The space heater must run as soon as the
 Surge suppressor                   -               alternator stops. It is installed at the rear of
                                                    the machine. Its standard power is 100W
Single-bearing kit               4879454            with 220V or 100W with 110V on request.
 Non drive end bearing              -
 «O» ring                           -
 Preloading (wavy) washer           -
Double-bearing kit               4877030            Warning: the power supply is present
 Non drive end bearing              -               when the machine has stopped.
 Drive end bearing                  -
 «O» ring                           -               • Temperature sensors with thermistors
 Preloading (wavy) washer           -               (PTC)
                                                    These are thermistor triplets with a positive
                                                    temperature coefficient installed in the
5.2 - Technical support service                     stator winding (1 per phase). There can be a
Our technical support service will be               maximum of 2 triplets in the winding (at 2
pleased to provide any additional                   levels: warning and trip) and 1 or 2
information you may require.                        thermistors in the shields.
                                                    These sensors must be linked to adapted
For all spare parts orders or technical             sensing relays (supplied optionally).
support requests, send your request to              Cold resistance of cold thermistor sensors:
service.epg@leroy-somer.com or your                 100 to 250 Ω per sensor.
nearest contact, whom you will find at
www.lrsm.co/support indicating the comp-
lete type of machine, its number and the
information indicated on the nameplate.
20
    Electric Power Generation    Installation and maintenance   5056 en - 2021.09 / k
                                       LSA 44.3
                            Low Voltage Alternator - 4 pole
5.4 - Exploded views, parts list and tightening torque
• Single bearing
                                                                                        21
     Electric Power Generation    Installation and maintenance   5056 en - 2021.09 / k
                                        LSA 44.3
                             Low Voltage Alternator - 4 pole
• Two-bearing
22
      Electric Power Generation       Installation and maintenance               5056 en - 2021.09 / k
                                             LSA 44.3
                                 Low Voltage Alternator - 4 pole
                                      Screw Torque                                          Screw Torque
Ref. Qty           Description                     Ref. Qty          Description
                                        Ø    N.m                                              Ø    N.m
                                                               Exciter armature
 28     1    Earth terminal            M6*    10**   100   1                                    -         -
                                                               (rotor)
                                                                                                              23
     Electric Power Generation     Installation and maintenance           5056 en - 2021.09 / k
                                         LSA 44.3
                             Low Voltage Alternator - 4 pole
Disposal and recycling instructions                 All materials listed above need special
We are committed to limiting the                    treatment to separate waste from
environmental impact of our activity. We            reclaimable materials and should be
continuously monitor our production                 entrusted to specialist recycling companies.
processes, material sourcing and product
design to improve recyclability and minimise        The oil and grease from the lubrication
our environmental footprint.                        system should be treated as hazardous
These instructions are for information              waste and must be treated in accordance
purposes only. It is the user’s responsibility      with local legislation.
to comply with local legislation regarding
product disposal and recycling.                     Our alternators have a specified lifetime of
                                                    20 years. After this period, the operation of
Recyclable materials                                the product should be stopped, regardless
Our alternators are mainly constructed from         of its condition. Any further operation after
iron, steel and copper materials, which can         this period will be under the sole responsi-
be reclaimed for recycling purposes.                bility of the user.
These materials can be reclaimed through a
combination of manual dismantling,
mechanical separation and melting
processes. Our technical support depart-
ment can provide detailed directions on how
to dismantle products on request.
24
     Electric Power Generation                     Installation and maintenance                                            5056 en - 2021.09 / k
                                                              LSA 44.3
                                    Low Voltage Alternator - 4 pole
                                                                                                       Moteurs Leroy-Somer
                                                                                                       Boulevard Marcellin Leroy - CS 10015
                                                                                                       16915 Angoulême cedex 9 - France
                                                               EC Declaration
             Moteurs Leroy-Somer declares hereby that the electric generators of the types:
              LSA 40 – LSA 42.3 – LSA 44.3 – LSA 46.3 – LSA 47.2 – LSA 47.3 – LSA 49.1 – LSA 49.3 – LSA 50.1 –
              LSA 50.2 – LSA 51.2 – LSA 52.2 – LSA 52.3 – LSA 53 – LSA 53.1 – LSA 53.2 – LSA 54 – LSA 54.2 – TAL
              040 – TAL 042 – TAL 044 – TAL 046 – TAL 047 – TAL 0473 – TAL 049 – LSAH 42.3 – LSAH 44.3
             as well as their derivatives, manufactured by Leroy-Somer or on Leroy-Somer's behalf:
             Declaration of compliance:
                - Low Voltage Directive Nr 2014/35/EU dated 26th February 2014.
                - EN and IEC 60034-1, 60034-5 and 60034-22.
                - ISO 8528-3 “Reciprocating internal combustion engine driven alternating current generating sets. Part
                    3. Alternating current generators for generating sets”.
             These generators also comply with the ROHS Directive Nr 2011/65/EU dated 8th June 2011 and its Annex II
             Nr 2015/863 dated 31st March 2015, as well as the EMC Directive Nr 2014/30/EU dated 26th February 2014.
             Declaration of incorporation:
             These generators are designed to meet the essential "Partly completed machinery" requirements of Machinery
             Directive Nr 2006/42/EC, as well as Annex VII, part B of this directive and the aforementioned standards.
             As a result, these "Partly completed machinery" are designed to be incorporated into Electrical Gen-Sets
             complying with the Machinery Directive Nr 2006/42/EC dated 17th May 2006.
             WARNING:
             The here mentioned generators should not be commissioned until the corresponding Gen-Sets have been
             declared in compliance with the Directives Nr 2006/42/EC, 2014/30/EU, 2011/65/EU and 2015/863, as well as
             with other relevant Directives.
             Moteurs Leroy-Somer undertakes to transmit, in response to a reasoned request by the national authorities,
             relevant information on the generator.
                                                              Technical Managers
                                                       J.P. CHARPENTIER – Y. MESSIN
                Moteurs Leroy-Somer
                Siege social : Boulevard Marcellin Leroy CS 10015 - 16915 Angoulême cedex 9 - France
                                                                                                                         4152 en - 2021.07 / u
                SAS au capital de 38 679 664 € - RCS Angoulême 338 567 258
The contractual EC Declaration of compliance and incorporation can be obtained from your contact on
request.
                                                                                                                                                   25
     Electric Power Generation    Installation and maintenance   5056 en - 2021.09 / k
                                        LSA 44.3
                             Low Voltage Alternator - 4 pole
26
                 Service & Support
            Life Extension
          •Reconditioning                                      Start-up
          •System upgrade
                                                           •Commissioning
                                                           •Training
                 Optimisation
                 •Monitoring                  Operation
                 •System audit                •Genuine spare parts
                                              •Repair services
Contact us:
Americas: +1 (507) 625 4011
Europe & rest of the world: +33 238 609 908
Asia Pacific: +65 6250 8488
China: +86 591 88373036
India: +91 806 726 4867
                                                                     Scan the code or go to:
    service.epg@leroy-somer.com                                    www.lrsm.co/support
                                   www.emersonindustrial.com
                                   www.leroy-somer.com/epg
Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
5056 en - 2021.09 / k