Roadstone: Thermal Liteblock System
Roadstone: Thermal Liteblock System
01. Introduction
09. How do U values & Thermal Bridging affect the Energy Performance of a building?
17. 3D Details
LOCATIONS
Cork Laois Locations
1. Ballygarvan Retail Outlet Locations
26. Ballyadams
2. Carrigtwohill
Limerick
3. Castlemore 12
27. Joseph Hogan’s
4. Classis
28. Gooig
5. Keim
6. Mallow Longford
7. Midleton 29. Moyne
Clare Mayo
8. Ballyquinn 30. Castlebar 13
11
9. Bunratty Meath
10. Ryans 31. Barley Hill
Donegal 32. Duleek
11. Ballintra 33. Mullaghcrone 36
12. Carndonagh 34. Slane 30 8
29 31
13. Laghey Offaly
38
Dublin 35. Tullamore
34
14. Belgard Central Roscommon
33
37 32
Dispatch / Belgard 36. Boyle
Weighbridge 37. Cam 5
18
15. Huntstown Finglas 6 15
38. Castlemine 19 35
16. Head Office, 4 14 16
Tallaght Tipperary 23
47
39. Ballyknockane 46 9
17. Swords, Feltrim 10 3
40. Killough
8
26
Galway Waterford
9
18. Two-Mile-Ditch 28
41. Cappagh 27
26 45
40 24
19. Kilchreest
Wexford
Kerry 42. Brownswood,
20 39 42
20. Ballyegan Enniscorthy. 43
21. Killarney 25
43. Kilmuckridge 6 7
22. Killorglin 44. Killinick 22 21
44
5 41
Kildare Wicklow 2
23. Allen, Naas 45. Arklow 3 4
2 7
1
1
Kilkenny 46. Dorans Pit
24. Bennettsbridge 47. Fassaroe, Bray
25. Kilmacow
Cork Kilkenny
1. Ballygarvan 7. Kilmacow
2. Classis
Mayo
Clare 8. Castlebar
3. Ryans
Wicklow
Dublin 9. Fassaroe, Bray
4. Belgard
5. Feltrim, Swords
Galway
2
6. Two-Mile-Ditch
1
INTRODUCTION
Thermal bridging is one of the key factors The following construction types have
been examined and thermally modelled:
which need to be addressed to improve energy
efficiency in the design and construction of ► Cavity wall - full fill insulation
new buildings. All thermal bridges must be (Table D1)
► Cavity Wall - partial fill insulation
minimised to reduce heat loss through cold
(Table D1)
bridging. All major junctions between building ► External Insulation on to masonry
elements (floors, walls, roofs, windows and walls (Table D2)
doors) must be built in compliance with the ► Internal insulation with twin-pot
cavity block (Table D6)
Acceptable Construction Details (ACDs).
The Roadstone Thermal Liteblock system combines the Roadstone
Thermal Liteblock with the Roadstone concrete block range, which
when used in accordance with the Acceptable Construction Details
(ACDs), achieves psi values equal to or better than the standards set
out in Technical Guidance Document (TGD) Part L 2019.
Fig. 1
Definition Of Nearly Zero Energy Buildings Directive 2010/31/EU Energy Performance Of Buildings:
“ ‘nearly zero energy building’ means a building that has a very high energy performance, as determined in accordance with Annex I. The nearly zero or very low
amount of energy required should be covered to a very significant extent by energy from renewable sources, including energy from renewable sources produces
on site or nearby’’
The NZEB standard as set out in TGD L 2017 Buildings other than dwellings applies to works from 1st January 2019 (subject to
transitional arrangements). For Public Sector bodies, NZEB applies from 31st December 2018.
Impacts of NZEB
TGD L 2019 Dwellings includes numerical indicators for NZEB which apply to works from 1st November 2019 (subject to
transitional arrangements). The numerical indicators provide Maximum Permitted Energy Performance Coefficient (MPEPC)
of 0.30 and Maximum Permitted Carbon Performance Coefficient ( MPCPC) of 0.35. Note: These indicators are relevant to
both Part L 2011 (with 2017 amendments) and Part L 2019.
The nearly zero or very low amount of energy must be covered to a very significant extent by energy from renewable sources
including energy from renewable sources produced on site or nearby.
Energy efficient design begins with a Fabric First Approach, whereby the buildings shape,
orientation and thermal mass, with proper detailing, will save energy. This ensures that the
majority of the energy saving work is done by the building by having a high performance
fabric rather than relying completely on the addition of mechanical renewable energy systems.
The Roadstone Thermal Liteblock plays a key role in achieving good thermal efficiency in
the building fabric by providing a highly cost effective solution to achieve improved thermal
bridging performance, thus reducing cold bridging and allowing designers more flexibility
when generating a Part L compliant specification.
To demonstrate the benefits, we need to be clear on what thermal bridging is, and the difference
between U value, thermal conductivity (Lambda λ) value, psi (ᴪ) values and how psi (ᴪ) values
are used to calculate the overall (y) factor for a building. All of these parametres are used in the
Dwelling Energy Assessment Procedure (DEAP) in Ireland, to calculate the overall heat loss through
the building fabric.
Thermal bridging is a localised area of the building envelope where the heat flow is increased
in comparison with that of adjacent areas, due to junctions where insulation is not continuous.
Thermal bridges are weaknesses in the building envelope where thermal energy is transferred
at an increased rate compared to the surrounding area. Thermal Bridging is first measured by
calculating the psi(ᴪ) value of each junction (see below explanation for psi(ᴪ) value. The sum of
the psi(ᴪ) values are then multiplied by the lengths of the bridged junctions, these figures are then
used to calculate the overall Thermal Bridging Factor (y value) for any given building.
1. Repeating (e.g. timber studs with insulation 3. Non-repeating (e.g. Junctions between
between, at fixed distance centres): floors and walls, walls and roofs, window
Because this type of bridging is constant, jambs and heads). Cold bridging at these
the effects of a repeating thermal bridge can junctions occurs where the insulation
be accounted for in a U value calculation. layer is interrupted by non-insulating
materials, and heat loss in these areas
2. Random (e.g. one off cold bridge due to can lead to reduced surface temperatures
penetration of the insulation layer, such as a causing interstitial and surface condensation
balcony support bracket, metre box etc). to occur.
Fig. 2
REGULAR BLOCK
Fig 2 – Thermal Bridging
heat flow diagram
5
What is a Lambda (λ) value? What is an R Value?
THERMAL CONDUCTIVITY (W/mK) THERMAL RESISTANCE (m2 K/W)
A Lambda value (λ) is a measure of the rate of The R- Value is a measure of the resistance to
heat flow through a material (fig 3). It will vary heat flow of a given thickness of a material (fig 4)
with density, porosity, moisture content and or combination of materials, i.e. building plane
temperature of the material. The units of Thermal elements such as a wall, roof or floor.
Conductivity are expressed in watts per metre To calculate the Thermal Resistance (R) of a
of thickness per degree Kelvin of temperature material, divide the thickness (d) of material by its
difference from one side of the material to the lambda value (λ). d/ λ =R.
other. The lower the number, the less heat passes
through the material.
For example:
Standard Concrete block: λ = 1.33 (W/mk)
Roadstone Thermal Liteblock: λ = 0.33 (W/mk)
Fig. 3 Fig. 4
Fig. 5 Fig. 6
U value = Watts (W) of heat flow Psi = Heat flow (Watts) per metre
per m2 x temperature difference (K) (m) x Temperature Difference (K)
What is a (y) factor? 6
The DEAP calculation accounts for thermal bridging at junctions between elements and around
openings using a (y) factor. When linear thermal transmittance psiᴪ(ᴪ) values are available for
element junctions, the psi values can be multiplied by the lengths (l) of their respective junctions
(ᴪ
ᴪ X l), and the sum of all the (psi X l) figure is then divided by the total area of building envelope
containing thermal bridging, to calculate the (y). Roadstone can now provide details* and
corresponding psi values, in line with Paragraph 3 of Appendix K of the DEAP Manual below:
Fig. 7
Paragraph 1
y = 0.08 W/m2K: for new dwellings whose details conform with “Limiting Thermal Bridging
and Air Infiltration – Acceptable Construction Details” (www.environ.ie ) as referenced
in Building Regulations 2008 and 2011 TGD L. This requires that the relevant drawings be
signed off by the developer, builder, site engineer or architect. The BER Assessor must retain the
relevant drawings, such as those from the Acceptable Construction Details and associated sign
off in support of thermal bridging factor entered.
Paragraph 3
Alternatively values of (Ψ) can be determined from the results of numerical modelling, or
they can be derived from measurement. If the junction detail is as recommended in Acceptable
Construction Details (ACDs), the Ψ-value associated with that junction can be taken from TGD
L 2011 Appendix D or from Introduction Document for Acceptable Construction Details or
other certified Ψ values.
7 What happens with
U values and Y values in DEAP? (Dwelling Energy Assessment Procedure)
When entering the dimensions of a building into DEAP the assessor measures and enters the
areas and U values for each plane element. DEAP calculates the total building fabric heat loss by
multiplying the area of each element by their U value, adding these all together to get the total
heat loss via plane elements.
The assessor then uses a (y) factor to account for the heat losses via thermal bridging. The (y)
factor is a fraction or percentage of the overall heat lost through the fabric, and takes into account
the total envelope area containing thermal bridges. See figure 8 showing areas for U values, and
lengths for psi values.
The total heat loss envelope area, heat loss through plane elements and cold bridging are all
combined to determine the total heat loss through the building fabric. The fabric heat loss figure,
along with all other parameters, are used to determine the overall energy efficiency of the building.
Fig. 8
Include all external walls, windows, doors and floors. (Rear walls and windows not shown above).
All measurements to be taken in accordance with SEAI BER Assessor Methods, using internal dimensions
to measure lengths and areas.
What is the
Energy Performance Coefficient (EPC)?
DEAP calculates the Energy Performance of a building and measures it against a notional
compliant version of the same building simultaneously. DEAP then calculates and compares the
dwelling’s Energy Performance Coefficient (EPC) and Carbon Performance Coefficient (CPC) to the
Maximum Permitted Energy Performance Coefficient (MPEPC) and Maximum Permitted Carbon
Performance Coefficient (MPCPC) for Building Regulations TGD L 2019, currently set at MPEPC of
0.3 and MPCPC of 0.35.
8
U wall
U floor
Y value calculation
D.E.A.P.
Dwelling Energy
Assessment Procedure
As outlined earlier, DEAP uses the areas of building elements (roofs, walls, floors) and their
corresponding U values to calculate how much heat will be lost through the fabric of a building.
The lower the U value, the less heat loss through that particular element.
The building heat loss through thermal bridging is then accounted for by entering
a factor for thermal bridging (y) into DEAP. A lower (y) factor will result in a better BER result.
It is important to note that the higher the thermal performance of the building’s plane elements,
the higher the risk of condensation occurring at cold bridged junctions. As U values are lowered
(improved), correct detailing becomes extremely critical to avoid surface condensation occurring.
By using Roadstone Thermal Liteblock Standard Details*, you can claim a default (y) factor of 0.08
as described in paragraph (3) of the DEAP manual extract . (See Page 6)
Fig. 10
The psi values associated with the Roadstone Roadstone recommend that to get the
Thermal Liteblock can be used to significantly full cost benefit saving to the overall build cost of
reduce the (y) factor of a building and improve a building type, a full detailed (y)
the BER results when an overall (y) calculation is value calculation is carried out. Roadstone can
carried out. provide this service through their nominated
thermal modelling technical support teams.
Roadstone has thermally modelled each critical junction detail, ACD’s as listed in TGD L 2019
appendix D1, D2, D4 and D6 and has calculated the psi value for each junction. This means we
can provide a validated (y) factor calculation to our customers when using the Roadstone Thermal
Liteblock system and the improved benefits of this will be evident in the improved BER results for
your building. By using the Roadstone Thermal Liteblock System you can comfortably comply with
TGD Part L 2019 thermal bridging requirements.
The Roadstone Thermal Liteblock System provides the following benefits:
10
Fig. 11
House details
Jamb length doors - 8.2 m
Ground floor external perimeter - 23 m
Intermediate floor - 23 m
Eaves - 14 m
Gable (insulation at ceiling level)-9m
External Corners - 10.20m
Party wall corners with external - 10.20m
Party wall junction with floor- 9m
Party wall junction with ceiling -9m 5.1m
Rising walls-9m
This sample house has an Air to Water Heat pump providing hot water and space heating, no solar,
no heat recovery ventilation, with a wood burning stove as the secondary heating, with 1
flue and passive vents.
When we calculate the (y) factor for this house using the Roadstone Thermal Liteblock System’s
thermal bridging psi values, the (y) factor improves to 0.0266 W/m2K. This results in a BER of A2 @
49.99 kwh/m2/yr. This lower thermal bridging factor has a very significant effect on the BER. This (y)
factor calculation and BER result is based on traditional build cavity wall details using Roadstone
Thermal Liteblock psi values in lieu of defaults from Table D1 of TGD L 2019. Roadstone modelled
psi values are also available for twin-pot cavity blocks, solid masonry block with external insulation
and frame construction types.
See table 1 for summary specification and BER results.
11 The effects of Thermal Bridging
(y) factors on the BER of a large detached house:
To examine the effects of improved (y) factors further, we have carried out the same exercise
on a larger detached house. See table 1 for summary specification and BER results,
which demonstrates clearly the benefit of using the Roadstone Thermal Liteblock in key
locations, achieving lower (y) factors, resulting in reduced energy values, lower heating bills
and better BER results.
Fig. 12
This larger sample house also has an Air to Water Heat Pump providing all Domestic Hot Water,
passive ventilation, a wood burning stove as the secondary heating system with 1 flue and no
solar thermal panels.
By implementing the Roadstone Thermal Liteblock and using the psi values from the Roadstone
Thermal Modelling research, the (y) factor is calculated to be .05 W/m2K, and the BER result is an A2
Rating at 46.84 kWh/m2/yr.
Primary Heating System Air to Water Heat Pump Air to Water Heat Pump
449% Efficient 449% Efficient
Secondary Heating System Wood burning Stove with flue Wood burning Stove with flue
Heating Distribution Fully zoned with time and Fully zoned with time and
temperature controls temperature controls
Domestic Hot Water From Heat Pump, into 200ltr From Heat Pump, into 200ltr
insulated cylinder. insulated cylinder.
U Values
BER Results
The improved y values that the Roadstone Thermal Liteblock system provides, offers reduced
thermal bridging and limits the risk of surface condensation and mould growth.
Surface condensation can occur on the surfaces of walls, windows, ceilings and floors and
may result in mould and mildew. Condensation in buildings occurs whenever warm moist air
meets surfaces that are at or below the dew point of that air. The key factor used in assessing the
risk of mould growth or surface condensation in the vicinity of thermal bridges is the temperature
factor (fRsi).
where:
Tsi = minimum internal surface temperature,
Te = external temperature, and
Ti = internal temperature.
For dwellings, the value of fRsi should be greater than or equal to 0.75, so as to avoid
the risk of mould growth and surface condensation. Full checks should be performed on the
likelihood of surface and interstitial condensation of a construction detail in accordance with I.S. EN
ISO 13788 and the 2019 Building Regulations. The Roadstone Thermal Liteblock System provides
improved psi(Ψ) values equal to or better than the standards set out in TGD Part L,2019 and lower
subsequent y values that limit the risk of surface condensation. The risk of surface condensation
and subsequent mould growth is significantly reduced for junctions with lower linear thermal
transmittance (psi(Ψ) values).
FREEZE/THAW RESISTANCE
The Roadstone 13N Thermal Liteblock has been tested for freeze/thaw resistance using
an in-house method based on I.S. EN 772-22 ‘Determination of freeze/thaw resistance
of clay masonry units’. Clay masonry units are typically unrendered and exposed to the
elements and therefore require a higher level of freeze/thaw resistance. The test takes
12 days to complete and subjects a saturated masonry panel to 100 cycles of freezing to
-15°C and thawing to +10°C, while spraying with water at regular intervals throughout.
This is a severe and robust test method and far exceeds the typical freeze/thaw durability
requirements of masonry units in Ireland. The Roadstone 13N Thermal Liteblock proved
to be exceptionally durable to freeze/thaw attack. Based on the criteria outlined in I.S. EN
772-22 the Roadstone 13N Thermal Liteblock can be classified as Freeze/Thaw Resistance
Category F2 (suitable for use in severe exposure conditions) and therefore satisfies the
freeze/thaw durability requirements of S.R. 325 Table 14(A).
ADVANTAGES
For more information on the Roadstone Thermal Liteblock, including a full range of Part L
compliant thermally modelled technical drawings and AutoCAD details, see
www.roadstone.ie
BLOCK RANGE
100mm SOLID
7.5 N/mm2 and
13 N/mm2
140mm SOLID
CAVITY CLOSER
EAVES
JAMB
BELOW SLAB
SEPERATING WALL A
SEPERATING WALL B
SEPERATING WALL C
GABLE
16
19
Sample Thermal Bridging Details
Download the full range of Technical Drawings from
www.roadstone.ie/thermal-liteblock.
440 x 215 x 100 Roadstone Floor U Value varies, must be within Ranges set
Standard Blocks out in Table D1 of Appendix D of TGD part L
350
440 x 215 x 100 Roadstone 2011 for Psi values to be applicable.
Thermal Liteblock 150
DPC See configuration options A and B below,
DPM / Radon Barrier depending on y value requirements.
Roadstone Custom Psi values
Cavity Wall U-Values vary,
see appendix D of TGD part L 2011.
Floor insulation to tightly abut blockwork wall U Value Part L Roadstone TLB
Range (Ψ) Psi (Ψ) Value
Install perimeter insulation with min. R value of
2.27m2k/W or greater (W/m2K) Option Option
All Blocks (Including Thermal A B
(example 50mm of PIR λ 0.022 = R2.27)
Liteblocks) to be minimum
7.5N in accordance with
section 1.1.3.5 TGD Part A 0.18 0.080 0.036 0.042
FFL
2012)
0.15 0.042 0.033 0.040
225mm min.
215
TO BE READ IN CONJUNCTION
SCALE: NTS JUNCTION: FULL FILL CAVITY WALL/ INSULATION ABOVE SLAB
WITH Y-VALUE CALCULATION
Copyright © ROADSTONE This information is supplied in good faith and no liability can be accepted for any loss or damage resulting from use.
20
440 x 215 x 100 Roadstone See TGD B for fire cavity barrier
Standard Blocks requirements. (Fire cavity barrier not
440 x 215 x 100 Roadstone included in Psi-Value Calculation)
Thermal Liteblock
DPC
Partial fill Cavity Wall Roadstone Custom Psi values
U-Values vary, see appendix D of Continue cavity wall insulation across
TGD part L 2011. U Value Roadstone TLB
wall abutment zone Part L
Range (Ψ) Psi (Ψ) Value
(W/m2K)
440
Partial fill insulation to be secured
firmly against the innerleaf of the
cavity wall
Roadstone Thermal Liteblock first
block in party wall, block on flat.
215
TO BE READ IN CONJUNCTION
SCALE: NTS JUNCTION: PARTIAL FILL CAVITY WALL/ PARTY WALL PLAN DETAIL
WITH Y-VALUE CALCULATION
Copyright © ROADSTONE This information is supplied in good faith and no liability can be accepted for any loss or damage resulting from use.
350
440 x 215 x 100 Roadstone 150 Roadstone Standard Block
Standard Blocks
Roadstone Custom Psi values
Ensure that full depth of U Value Part L
440 x 215 x 100 Roadstone Roadstone TLB
insulation between and over
Thermal Liteblock
joists extends to the inner edge Range (Ψ) Psi (Ψ) Value
Continue cavity wall insulation to of the wall (W/m2K)
top of gable
OR
270mm above bottom of ceiling
tie and insert cavity tray 0.18 0.272 0.173
Roof buildup:
0.15 0.152 0.129
Varies, to achieve U values within the
As modelled by NSAI registered Thermal
wall 0.21 or 0.15 Range (refer to
Modellers:
Appendix D of TGD part L 2011)
*Note:
JUNCTION: PARTIAL FILL GABLE CAVITY WALL/ VENTILATED ROOF - INSULATED AT ATTIC TO BE READ IN CONJUNCTION
SCALE: NTS
FLOOR LEVEL WITH Y-VALUE CALCULATION
Copyright © ROADSTONE This information is supplied in good faith and no liability can be accepted for any loss or damage resulting from use.