Control Valves Data Sheet
Document No: SIWP-Z0-DAS-8004
Revision: 00
Date of Issue: 21/06/2016
XXXXX Data Sheet Page 1 of 9
DOCUMENT NUMBER: SIWP-Z0-DAS-8004
Control Valves
Revision 00
Data Sheet
Isuued 21/06/2016 Page 2 of 9
NOTE: This document and all its contents is the property of Sohar SWRO Construction Company LLC. It is confidential and is given to you
for a limited purpose and must be returned on request. Neither this document nor any information concerning it may be copied, exhibited or
furnished to others without the consent of Sohar SWRO Construction Company LLC
00 21/06/2016 Issued for quotation JMHA VMV DCB
AA 17/06/2016 Isued for comments JMHA VMV DCB
ENGINEERING
REV DATE DESCRIPTION AUTHOR REVIEW (OWNER) REVIEW
MANAGER
XXXX Data Sheet Page 2 of 9
DATA SHEET : SIWP-Z0-DAS-8004
Control Valve Data Sheet
GENERAL DATA Unit
Tag 4 FV-BTMB1P01-01 / FV-BTMB1P02-02 / FV-BTMB1P02-03 / FV-BTMB1P03-02
Service Intake Back-up Pressure
Line Nº DN1400-B1-RW-G01F-0101 / DN1400-B1-RW-G01F-0104 / DN1400-B1-RW-G01F-0104 / DN1400-B1-
RW-G01F-0103
Line Size DN 1400
Schedule SN 2500 - PN 6
Pipe Material GRP
PID Nº SIWP-B1-PID-0001
Zone Intake
Specification G01F
Hook up Not Apply
Unit
Fluid Name Seawater
Fluid Phase Liquid
Operating Conditions (Min/Norm/Max/Other)
Flow m3/h 6945 9260 11574 6945
Pressure (Upstream) barg 1,37 1,58 1,73 0,97
Temperature ºC 35 35 20 35
Pressure drop m.W.C 3 2 1 7
Density kg/m3 1020 1020 1025 1020
Viscosity cP 0,83 0,83 1,08 0,83
Calculated Noise dB (A) 72 74 70 110
Calculated Cv - 18310 24413 43259 10614
Velocity m/s 1.27 1.69 2.11 1.27
%Opening % (*) (*) (*) (*)
Vapor Pressure bar a 0,055 0,055 0,043 0,055
Liquid Pressure Recovery Factor (FL) (Note 3) 0,55 (*) 0,55 (*) 0,55 (*) 0,55 (*)
Cavitation Coefficient Kc ( Note 3) 0,15 (*) 0,15 (*) 0,15 (*) 0,15 (*)
Critical Pressure bar a 221
Cv Required / Cv Selected - 55000 (*)
Max. Shutoff Diff. Pressure bar 2,7
Corrossive Agent / Toxic Agents - Yes No
Design Pressure barg 0 3,5
Design Temperature ºC 0 55
PURCHASE DATA
Manufacturer *
Model Number *
Mtr. Requisition *
Purchase Order Number *
VALVE BODY Unit
Valve Type Butterfly (Note 1)
Body / Bonnet Material Flanged Type
Material detail Carbon Steel with HALAR coating (Note 2)
Body Size DN 1400 - Vendor to Advice
Port Size N/A
Connect Rating 150#
Facing RF
Packing Material PTFE
Packing construction Rings
Guiding N/A
Bonnet Type N/A
End connection Flanged
TRIM DATA Unit
Trim Type Double Excentric
Trim Size (*)
Plug / Disc / Valve Material Carbon Steel with HALAR coating (Note 2)
Seat Material Soft Seat
Stem / Shaft Material Superduplex (Note 2)
Flow Tends to Open
Trim Characteristic Lineal
Leakage Class Class IV
ACTUATOR
Manufacturer / Model (*)
Actuator Type Electric Motor
Size (*)
Valve Action on Failure Close
Handwheel Yes
Maximum Actuator Force Forward/Reverse (*)
Power Supply (Electrical) V 415
Air Supply Range bar g N/A
Spring Range N/A
POSITIONER
Positioner Type Smart Type with Motor. Local Mounting
Manufacturer / Model Number (*)
HART / BUS Profibus DP
Input Signal / Output Signal Set-Point / Feedback Travel / Alarm signals
Position tansmitter Yes
Positioner Action / Characteristic (*)
IP Rating IP 68
Electrical / Pneumatical Connection 1/2" NPT for Profibus DP / For Power TBD
Local Display Yes
LIMIT SWITCHES
Tag No. Not Apply
Manufacturer / Model number
IP Rating
Electrical connection
Type
ACCESSORIES AND OPTIONS
Booster Relay Not Apply
Locking Device Not Apply
Set Pressure to Locker Not Apply
Air Filter regulator Not Apply
Pressure gauge Not Apply
Air connection Not Apply
Tubing Not Apply
Cableglands Yes. Brass-Nickel for Armoured cable
REQUIREMENTS AND TEST
Material Certificate Yes
Test Requirements (2*)
PIPING INTERFACE
Process Connection Flanged
Material GRP
Size / Rating / Facing Inlet DN1400 / 150# / FF
Size / Rating / Facing Outlet DN1400 / 150# / FF
Others
REMARKS:
Note 1: Other Bodies and types are admisible.
Note 2: Other materials compatible with process fluid could be admisible
* data to be filled by the manufacturer
XXXXX Data Sheet Page 3 of 9
DATA SHEET : SIWP-Z0-DAS-8004
Control Valve Data Sheet
GENERAL DATA Unit
Tag FV-BTMD2G01-01 / FV-BTMD2G02-01 / FV-BTMD2G03-01 / FV-BTMD2G04-01 / FV-BTMD2G05-01 /
FV-BTMD2G06-01 / FV-BTMD2G07-01 / FV-BTMD2G08-01 / FV-BTMD2G09-01 / FV-BTMD2G10-01 /
22 FV-BTMD2G10-01 / FV-BTMD2G11-01 / FV-BTMD2G12-01 / FV-BTMD2G13-01 / FV-BTMD2G14-01 /
FV-BTMD2G15-01 / FV-BTMD2G16-01 / FV-BTMD2G17-01 / FV-BTMD2G18-01 / FV-BTMD2G19-01 /
FV-BTMD2G20-01 / FV-BTMD2G21-01 / FV-BTMD2G22-01
Service Filtered water
Line Nº
DN500-D2-FW-G01F-0101 / DN500-D2-FW-G01F-0201 / DN500-D2-FW-G01F-0301 / DN500-D2-FW-
G01F-0401 / DN500-D2-FW-G01F-0501 / DN500-D2-FW-G01F-0601 / DN500-D2-FW-G01F-0701 /
DN500-D2-FW-G01F-0801 / DN500-D2-FW-G01F-0801 / DN500-D2-FW-G01F-0801 / DN500-D2-FW-
G01F-0901 / DN500-D2-FW-G01F-1001 / DN500-D2-FW-G01F-1101 / DN500-D2-FW-G01F-1201 /
DN500-D2-FW-G01F-1301 / DN500-D2-FW-G01F-1401 / DN500-D2-FW-G01F-1501 / DN500-D2-FW-
G01F-1601 / DN500-D2-FW-G01F-1701 / DN500-D2-FW-G01F-1801 / DN500-D2-FW-G01F-1901 /
DN500-D2-FW-G01F-2001 / DN500-D2-FW-G01F-2101 / DN500-D2-FW-G01F-2201
Line Size DN 500
Schedule SN2500 - PN 6
Pipe Material GRP
PID Nº
SIWP-D2-PID-0001 / SIWP-D2-PID-0002 / SIWP-D2-PID-0003 / SIWP-D2-PID-0004 / SIWP-D2-PID-
0005 / SIWP-D2-PID-0006 / SIWP-D2-PID-0007 / SIWP-D2-PID-0008 / SIWP-D2-PID-0009 / SIWP-D2-
PID-0010 / SIWP-D2-PID-0011 / SIWP-D2-PID-0012 / SIWP-D2-PID-0013 / SIWP-D2-PID-0014 / SIWP-
D2-PID-0015 / SIWP-D2-PID-0016 / SIWP-D2-PID-0017 / SIWP-D2-PID-0018 / SIWP-D2-PID-0019 /
SIWP-D2-PID-0020 / SIWP-D2-PID-0021 / SIWP-D2-PID-0022
Zone Gravity filters
Specification G01F
Hook up Not Apply
Unit
Fluid Name Seawater
Fluid Phase Liquid
Operating Conditions (Min/Norm/Max/Other)
Flow m3/h
771 771 1286 1286
Pressure (Upstream) mm.W.C 2526 1250 2526 1250
Temperature ºC 20 35 35 20
Pressure (downstream) mm.W.C 250 250 250 250
Density kg/m3 1020 1020 1020 1026
Viscosity cP 0,83 0,83 0,83 1,04
Calculated Noise dB (A) 98 98 101 97
Calculated Cv - 1922 1917 3232 5005
Velocity m/s 1,11 1,11 1,76 1,76
%Opening % 38 45 59 62
Vapor Pressure bar a 0,043 0,056 0,056 0,043
Liquid Pressure Recovery Factor (FL) (Note 3) 0,81 0,78 0,73 0,73
Cavitation Coefficient Kc ( Note 3) 0,328 0,304 0,266 0,266
Critical Pressure bar a 221
Cv Required / Cv Selected - 6300 (*)
Max. Shutoff Diff. Pressure bar 1.5
Corrossive Agent / Toxic Agents - Yes No
Design Pressure barg 0 3.5
Design Temperature ºC 0 55
PURCHASE DATA
Manufacturer *
Model Number *
Mtr. Requisition *
Purchase Order Number *
VALVE BODY Unit
Valve Type Butterfly (Note 1)
Body / Bonnet Material Flanged Type
Material detail Carbon Steel with HALAR coating (Note 2)
Body Size 18" (*)
Port Size N/A
Connect Rating 150#
Facing RF
Packing Material PTFE
Packing construction Rings
Guiding N/A
Bonnet Type N/A
End connection Flanged
TRIM DATA Unit
Trim Type Conventional
Trim Size (*)
Plug / Disc / Valve Material Carbon Steel with HALAR coating (Note 2)
Seat Material Soft Seat
St
Stem / Shaft
Sh ft Material
M t i l S
Superduplex
d l (N (Note
t 2)
Flow Tends to Open
Trim Characteristic Equal Percentage
Leakage Class Class IV
ACTUATOR
Manufacturer / Model (*)
Actuator Type Electric Motor
Size (*)
Valve Action on Failure Close
Handwheel Yes
Maximum Actuator Force Forward/Reverse (*)
Power Supply (Electrical) V 415
Air Supply Range bar g N/A
Spring Range N/A
POSITIONER
Positioner Type Smart Type with Motor. Remote Mounting
Manufacturer / Model Number (*)
HART / BUS Profibus DP
Input Signal / Output Signal Set-Point / Feedback Travel / Alarm signals
Position tansmitter Yes
Positioner Action / Characteristic (*)
IP Rating IP 68
Electrical / Pneumatical Connection 1/2" NPT for Profibus DP / For Power TBD
Local Display Yes
LIMIT SWITCHES
Tag No. Not Apply
Manufacturer / Model number
IP Rating
Electrical connection
Type
ACCESSORIES AND OPTIONS
Booster Relay Not Apply
Locking Device Not Apply
Set Pressure to Locker Not Apply
Air Filter regulator Not Apply
Pressure gauge Not Apply
Air connection Not Apply
Tubing Not Apply
Cableglands Yes. Brass-Nickel for Armoured cable
REQUIREMENTS AND TEST
Material Certificate Yes
Test Requirements (2*)
PIPING INTERFACE
Process Connection Flanged
Material GRP
Size / Rating / Facing Inlet 16" / 150# / RF
Size / Rating / Facing Outlet 16" / 150# / RF
Others
REMARKS:
Note 1: Other Bodies and types are admisible.
Note 2: Other materials compatible with process fluid could be admisible
* data to be filled by the manufacturer
Coupling Page 4 of 9
DATA SHEET : SIWP-Z0-DAS-8004
Control Valve Data Sheet
GENERAL DATA Unit
Tag
FV-BTMD2G01-02 / FV-BTMD2G02-02 / FV-BTMD2G03-02 / FV-BTMD2G04-02 / FV-BTMD2G05-02 /
FV-BTMD2G06-02 / FV-BTMD2G06-02 / FV-BTMD2G07-02 / FV-BTMD2G08-02 / FV-BTMD2G09-02 /
22 FV-BTMD2G10-02 / FV-BTMD2G11-02 / FV-BTMD2G12-02 / FV-BTMD2G13-02 / FV-BTMD2G14-02 /
FV-BTMD2G15-02 / FV-BTMD2G16-02 / FV-BTMD2G17-02 / FV-BTMD2G18-02 / FV-BTMD2G19-02 /
FV-BTMD2G20-02 / FV-BTMD2G21-02 / FV-BTMD2G22-02
Service Maduration Gravity Filters
Line Nº
DN300-D2-BH-P01F-0103 / DN300-D2-BH-P01F-0203 / DN300-D2-BH-P01F-0303 / DN300-D2-BH-
P01F-0403 / DN300-D2-BH-P01F-0503 / DN300-D2-BH-P01F-0603 / DN300-D2-BH-P01F-0703 /
DN300-D2-BH-P01F-0803 / DN300-D2-BH-P01F-0903 / DN300-D2-BH-P01F-1003 / DN300-D2-BH-
P01F-1103 / DN300-D2-BH-P01F-1203 / DN300-D2-BH-P01F-1303 / DN300-D2-BH-P01F-1403 /
DN300-D2-BH-P01F-1503 / DN300-D2-BH-P01F-1603 / DN300-D2-BH-P01F-1703 / DN300-D2-BH-
P01F-1803 / DN300-D2-BH-P01F-1903 / DN300-D2-BH-P01F-2003 / DN300-D2-BH-P01F-2103 /
DN300-D2-BH-P01F-2203
Line Size DN 300
Schedule PN 10
Pipe Material PP
PID Nº
SIWP-D2-PID-0001 / SIWP-D2-PID-0002 / SIWP-D2-PID-0003 / SIWP-D2-PID-0004 / SIWP-D2-PID-
0005 / SIWP-D2-PID-0006 / SIWP-D2-PID-0007 / SIWP-D2-PID-0008 / SIWP-D2-PID-0009 / SIWP-D2-
PID-0010 / SIWP-D2-PID-0011 / SIWP-D2-PID-0012 / SIWP-D2-PID-0013 / SIWP-D2-PID-0014 / SIWP-
D2-PID-0015 / SIWP-D2-PID-0016 / SIWP-D2-PID-0017 / SIWP-D2-PID-0018 / SIWP-D2-PID-0019 /
SIWP-D2-PID-0020 / SIWP-D2-PID-0021 / SIWP-D2-PID-0022
Zone Gravity filters
Specification P01F
Hook up Not Apply
Unit
Fluid Name Seawater
Fluid Phase Liquid
Operating Conditions (Min/Norm/Max/Other)
Flow m3/h 1060 1060 1153 1153
Pressure (Upstream) mm.W.C 2526 2526 2526 2526
Temperature ºC 35 20 35 20
Pressure (downstream) mm.W.C 250 250 250 250
Density kg/m3 1020 1026 1020 1026
Viscosity cP 0,83 1,04 0,83 1,04
Calculated Noise dB (A) 56 56 56 56
Calculated Cv - 2628 2620 2850 2858
Velocity m/s 4,07 4,07 4,43 4,43
%Opening % 55 55 58 58
Vapor Pressure bar a 0,056 0,043 0,056 0,043
Liquid Pressure Recovery Factor (FL) (Note 3) 0,8 0,8 0,74 0,74
Cavitation Coefficient Kc ( Note 3) 0,32 0,32 0,274 0,274
Critical Pressure bar a 221
Cv Required / Cv Selected - 3750 (*)
Max. Shutoff Diff. Pressure bar 3
Corrossive Agent / Toxic Agents - Yes No
Design Pressure barg 0 3.5
Design Temperature ºC 0 55
PURCHASE DATA
Manufacturer *
Model Number *
Mtr. Requisition *
Purchase Order Number *
VALVE BODY Unit
Valve Type Butterfly (Note 1)
Body / Bonnet Material Flanged Type
Material detail Carbon Steel with HALAR coating (Note 2)
Body Size 12" (*)
Port Size N/A
Connect Rating 150#
Facing RF
Packing Material PTFE
Packing construction Rings
Guiding N/A
Bonnet Type N/A
End connection Flanged
TRIM DATA Unit
Trim Type Conventional
Trim Size (*)
Plug / Disc / Valve Material Carbon Steel with HALAR coating (Note 2)
Seat Material Soft Seat
Stem / Shaft Material Superduplex (Note 2)
Flow Tends to Open
Trim Characteristic Equal Percentage
Leakage Class Class IV
ACTUATOR
Manufacturer / Model (*)
Actuator Type Electric Motor
Size (*)
Valve Action on Failure Close
Handwheel Yes
Maximum Actuator Force Forward/Reverse (*)
Power Supply (Electrical) V 415
Air Supply Range bar g N/A
Spring Range N/A
POSITIONER
Positioner Type Smart Type with Motor. Remote Mounting
Manufacturer / Model Number (*)
HART / BUS Profibus DP
Input Signal / Output Signal Set-Point / Feedback Travel / Alarm signals
Position tansmitter Yes
Positioner Action / Characteristic (*)
IP Rating IP 68
Electrical / Pneumatical Connection 1/2" NPT for Profibus DP / For Power TBD
Local Display Yes
LIMIT SWITCHES
Tag No. Not Apply
Manufacturer / Model number
IP Rating
Electrical connection
Type
ACCESSORIES AND OPTIONS
Booster Relay Not Apply
Locking Device Not Apply
Set Pressure to Locker Not Apply
Air Filter regulator Not Apply
Pressure gauge Not Apply
Air connection Not Apply
Tubing Not Apply
Cableglands Yes. Brass-Nickel for Armoured cable
REQUIREMENTS AND TEST
Material Certificate Yes
Test Requirements (2*)
PIPING INTERFACE
Process Connection Flanged
Material GRP
Size / Rating / Facing Inlet 12" / 150# / RF
Size / Rating / Facing Outlet 12" / 150# / RF
Others
REMARKS:
Note 1: Other Bodies and types are admisible.
Note 2: Other materials compatible with process fluid could be admisible
* data to be filled by the manufacturer
XXXXX Data Sheet Page 5 of 9
DATA SHEET : SIWP-Z0-DAS-8004
Control Valve Data Sheet
GENERAL DATA Unit
Tag 2 FV-BTME1L16-01 / FV-BTME1L66-01
Service By-pass Output cartridge filters
Line Nº DN400-E1-DW-G01F-0117 / DN400-E1-DW-G01F-0269
Line Size DN400
Schedule SN2500 - PN10
Pipe Material GRP
PID Nº SIWP-E1-PID-0001 / SIWP-E1-PID-0002
Zone Cartridge Filters
Specification G01F
Hook up Not Apply
Unit
Fluid Name Seawater
Fluid Phase Liquid
Operating Conditions (Min/Norm/Max/Other)
Flow m3/h 1060 1270 2500 2500
Pressure (Upstream) barg 3 3 3,8 3,8
Temperature ºC 35 35 35 20
Pressure drop bar 2,88 2,87 3,51 3,51
Density kg/m3 1020 1020 1020 1026
Viscosity cP 0,83 0,83 0,83 1,04
Calculated Noise dB (A) 136 137 152 142
Calculated Cv - 769 923 1735 1740
Velocity m/s 2,4 2,8 5,35 5,35
%Opening % 32 35 48 48
Vapor Pressure bar a 0,056 0,056 0,056 0,043
Liquid Pressure Recovery Factor (FL) (Note 3) 0,81 (*) 0,81(*) 0,78(*) 0,78(*)
Cavitation Coefficient Kc ( Note 3) 0,328(*) 0,328(*) 0,304(*) 0,304(*)
Critical Pressure bar a 221
Cv Required / Cv Selected - 2262 (*)
Max. Shutoff Diff. Pressure bar 5
Corrossive Agent / Toxic Agents - Yes No
Design Pressure barg 0 3.5
Design Temperature ºC 0 55
PURCHASE DATA
Manufacturer *
Model Number *
Mtr. Requisition *
Purchase Order Number *
VALVE BODY Unit
Valve Type Butterfly
Body / Bonnet Material Flanged Type
Material detail Superduplex (Note 2)
Body Size 14" (*)
Port Size N/A
Connect Rating 150#
Facing RF
Packing Material PTFE
Packing construction Rings
Guiding N/A
Bonnet Type N/A
End connection Flanged
TRIM DATA Unit
Trim Type Bi-excentric
Trim Size (*)
Plug / Disc / Valve Material Superduplex (Note 2)
Seat Material Soft Seat
Stem / Shaft Material Superduplex (Note 2)
Flow Tends to Open
Trim Characteristic Equal Percentage
Leakage Class Class IV
ACTUATOR
Manufacturer / Model ((*))
Actuator Type Electric Motor
Size (*)
Valve Action on Failure Locked
Handwheel Yes
Maximum Actuator Force Forward/Reverse (*)
Power Supply (Electrical) V 415
Air Supply Range bar g N/A
Spring Range N/A
POSITIONER
Positioner Type Smart Type with Motor. Remote Mounting
Manufacturer / Model Number (*)
HART / BUS Profibus DP
Input Signal / Output Signal Set-Point / Feedback Travel / Alarm signals
Position tansmitter Yes
Positioner Action / Characteristic (*)
IP Rating IP 68
Electrical / Pneumatical Connection 1/2" NPT for Profibus DP / For Power TBD
Local Display Yes
LIMIT SWITCHES
Tag No. Not Apply
Manufacturer / Model number
IP Rating
Electrical connection
Type
ACCESSORIES AND OPTIONS
Booster Relay Not Apply
Locking Device Not Apply
Set Pressure to Locker Not Apply
Air Filter regulator Not Apply
Pressure gauge Not Apply
Air connection Not Apply
Tubing Not Apply
Cableglands Yes. Brass-Nickel for Armoured cable
REQUIREMENTS AND TEST
Material Certificate Yes
Test Requirements (2*)
PIPING INTERFACE
Process Connection Flanged
Material GRP
Size / Rating / Facing Inlet 14" / 150# / RF
Size / Rating / Facing Outlet 14" / 150# / RF
Others
REMARKS:
Cavitation and Chocked Flow occurs. Max dP admisible according to engineering calculations: dP=2.6 bar case Min and Norm; dP=2.88 for Max and Other.
Note 1: Other Bodies and types are admisible.
Note 2: Other materials compatible with process fluid could be admisible
* data to be filled by the manufacturer
Coupling Page 6 of 9
DATA SHEET : SIWP-Z0-DAS-8004
Control Valve Data Sheet
GENERAL DATA Unit
Tag
FV-ROME1S01-12 / FV-ROME1S02-12 / FV-ROME1S03-12 / FV-ROME1S04-12 / FV-ROME1S05-12/
11 FV-ROME1S06-12 / FV-ROME1S07-12 / FV-ROME1S08-12 / FV-ROME1S09-12 / FV-ROME1S10-12 /
FV-ROME1S11-12
Service Discharge Brine flow control valve
Line Nº DN450-E2-BW-G01F-0110 / DN450-E2-BW-G01F-0210 / DN450-E2-BW-G01F-0310 / DN450-E2-BW-
G01F-0410 / DN450-E2-BW-G01F-0510 / DN450-E2-BW-G01F-0610 / DN450-E2-BW-G01F-0710 /
DN450-E2-BW-G01F-0810 / DN450-E2-BW-G01F-0910 / DN450-E2-BW-G01F-1010 / DN450-E2-BW-
G01F-1110
Line Size DN450
Schedule SN2500 - PN10
Pipe Material GRP
PID Nº SIWP-E2-PID-0001 / SIWP-E2-PID-0002 / SIWP-E2-PID-0003 / SIWP-E2-PID-0004 / SIWP-E2-PID-
0005 / SIWP-E2-PID-0006 / SIWP-E2-PID-0007 / SIWP-E2-PID-0008 / SIWP-E2-PID-0009 / SIWP-
E2-PID-0010 / SIWP-E2-PID-0011
Zone RO SKIDS
Specification G01F
Hook up Not Apply
Unit
Fluid Name BRINE
Fluid Phase Liquid
Operating Conditions (Min/Norm/Max/Other)
Flow m3/h 1170 1270 1370 1170
Pressure (Upstream) barg 1,4 1,4 1,4 1,4
Temperature ºC 35 35 35 20
Pressure drop bar 0,3 0,3 0,3 0,3
Density kg/m3 1023 1023 1023 1030
Viscosity cP 0,83 0,83 0,83 1,02
Calculated Noise dB (A) 62 62 63 62
Calculated Cv - 3070 3332 3595 3170
Velocity m/s 2,59 2,81 3.03 2,59
%Opening % 67,7 71,5 75,5 65
Vapor Pressure bar a 0,056 0,056 0,056 0,043
Liquid Pressure Recovery Factor (FL) (Note 3) 0,83 (*) 0,82 (*) 0,82 (*) 0,82 (*)
Cavitation Coefficient Kc ( Note 3) 0,344 (*) 0,336(*) 0,366(*) 0,344 (*)
Critical Pressure bar a 221
Cv Required / Cv Selected - 3081 (*)
Max. Shutoff Diff. Pressure bar 6
Corrossive Agent / Toxic Agents - Yes No
Design Pressure barg 0 10
Design Temperature ºC 0 55
PURCHASE DATA
Manufacturer *
Model Number *
Mtr. Requisition *
Purchase Order Number *
VALVE BODY Unit
Valve Type Rotative
Body / Bonnet Material Flanged Type
Material detail Superduplex
Body Size 16"
Port Size N/A
Connect Rating 150#
Facing RF
Packing Material PTFE
Packing construction Rings
Guiding (*)
Bonnet Type Standard Manufacturer
End connection Flanged
TRIM DATA Unit
Trim Type Rotative
Trim Size (*)
Plug / Disc / Valve Material Superduplex
Seat Material Duplex
Stem / Shaft Material Superduplex
Flow Tends to Open
Trim Characteristic Natural
Leakage Class Class IV
ACTUATOR
Manufacturer / Model (*)
Actuator Type Electric Motor
Size (*)
Valve Action on Failure Locked
Handwheel Yes
Maximum Actuator Force Forward/Reverse (*)
Power Supply (Electrical) V 415
Air Supply Range bar g N/A
Spring Range N/A
POSITIONER
Positioner Type Smart Type with Motor. Remote Mounting
Manufacturer / Model Number (*)
HART / BUS Profibus DP
Input Signal / Output Signal Set-Point / Feedback Travel / Alarm signals
Position tansmitter Yes
Positioner Action / Characteristic (*)
IP Rating IP 68
Electrical / Pneumatical Connection 1/2" NPT for Profibus DP / For Power TBD
Local Display Yes
LIMIT SWITCHES
Tag No. Not Apply
Manufacturer / Model number
IP Rating
Electrical connection
Type
ACCESSORIES AND OPTIONS
Booster Relay Not Apply
Locking Device Not Apply
Set Pressure to Locker Not Apply
Air Filter regulator Not Apply
Pressure gauge Not Apply
Air connection Not Apply
Tubing Not Apply
Cableglands Yes. Brass-Nickel for Armoured cable
REQUIREMENTS AND TEST
Material Certificate Yes
Test Requirements (2*)
PIPING INTERFACE
Process Connection Flanged
Material GRP
Size / Rating / Facing Inlet 16" / 150# / RF
Size / Rating / Facing Outlet 16" / 150# / RF
Others
REMARKS:
Note 1: Other Bodies and types are admisible.
Note 2: Other materials compatible with process fluid could be admisible
* data to be filled by the manufacturer
XXXXX Data Sheet Page 7 of 9
DATA SHEET : SIWP-Z0-DAS-8004
Control Valve Data Sheet
GENERAL DATA Unit
Tag
2 FV-BTCE7T01-11 / FV-BTCE7T01-31
Service Fill flushing tanks
Line Nº
DN300-E7-PM-P01F-0101 / DN300-E7-PM-P01F-0102
Line Size DN300
Schedule PN 10
Pipe Material PP
PID Nº
SIWP-E7-PID-0001
Zone Flushing and CIP Tanks
Specification P01F
Hook up Not Apply
Unit
Fluid Name Water
Fluid Phase Liquid
Operating Conditions (Min/Norm/Max/Other)
Flow m3/h 530 1060 1060 530
Pressure (Upstream) barg 2 1 2 1
Temperature ºC 20 35 35 35
Pressure drop bar 1,9 1,3 1,9 0,3
Density kg/m3 998 994 994 994
Viscosity cP 1.02 0,719 0,719 0,719
Calculated Noise dB (A) 89 94 77 54
Calculated Cv - 456 1158 3627 1126
Velocity m/s 2.01 4,03 4.03 2,01
%Opening % 33 50 75 48
Vapor Pressure bar a 0.056 0.056 0.056 0.056
Liquid Pressure Recovery Factor (FL) (Note 3) 0.82 0.82 0.84 0,84
Cavitation Coefficient Kc ( Note 3) 0.336 0.336 0.353 0,353
Critical Pressure bar a 221
Cv Required / Cv Selected - 4500 (*)
Max. Shutoff Diff. Pressure bar 5
Corrossive Agent / Toxic Agents - Yes No
Design Pressure barg 0 10
Design Temperature ºC 0 55
PURCHASE DATA
Manufacturer *
Model Number *
Mtr. Requisition *
Purchase Order Number *
VALVE BODY Unit
Valve Type Butterfly
Body / Bonnet Material Flanged Type
Material detail AISI 316
Body Size 10"
Port Size N/A
Connect Rating 150#
Facing RF
Packing Material PTFE
Packing construction Rings
Guiding (*)
Bonnet Type Standard Manufacturer
End connection Flanged
TRIM DATA Unit
Trim Type Conventional (*)
Trim Size (*)
Plug / Disc / Valve Material AISI 316
Seat Material AISI 316
Stem / Shaft Material 17-4 PH
Flow Tends to Open
Trim Characteristic Lineal
Leakage Class Class IV
ACTUATOR
Manufacturer / Model (*)
Actuator Type Double Piston
Size (*)
Valve Action on Failure Closed
Handwheel Yes
Maximum Actuator Force Forward/Reverse (*)
Power Supply (Electrical) V Not Apply
Air Supply Range bar g 4.5 - 8
Spring Range Not Apply
POSITIONER
Positioner Type Electropneumatic
Manufacturer / Model Number (*)
HART / BUS HART
Input Signal / Output Signal 4 - 20 mA / 4 - 20 mA
Position tansmitter Yes
Positioner Action / Characteristic (*)
IP Rating IP 65
Electrical / Pneumatical Connection 1/2" NPT / 1/4" NPT
Local Display Yes
LIMIT SWITCHES
Tag No. Not Apply
Manufacturer / Model number
IP Rating
Electrical connection
Type
ACCESSORIES AND OPTIONS
Booster Relay Not Apply
Locking Device Not Apply
Set Pressure to Locker Not Apply
Air Filter regulator Yes
Pressure gauge Yes. Inlet and outlet
Air connection 1/4" NPT
Tubing Nylon 11 or Nylon 12
Cableglands Yes. Brass-Nickel for Armoured cable
REQUIREMENTS AND TEST
Material Certificate Yes
Test Requirements (2*)
PIPING INTERFACE
Process Connection Flanged
Material GRP
Size / Rating / Facing Inlet 10" / 150# / RF
Size / Rating / Facing Outlet 10" / 150# / RF
Others
REMARKS:
Note 1: Other Bodies and types are admisible.
Note 2: Other materials compatible with process fluid could be admisible
Cavitation a occurs according to engineering calculations
* data to be filled by the manufacturer
Coupling Page 8 of 9
DATA SHEET : SIWP-Z0-DAS-8004
Control Valve Data Sheet
GENERAL DATA Unit
Tag
2 FV-BTCL2T03-11 / FV-BTCL2T04-11
Service Lime Saturator
Line Nº
DN150-LM2-LM-P01F-0221 / DN150-LM2-LM-P01F-0222
Line Size DN150
Schedule PN 10
Pipe Material PP
PID Nº SIWP-L2-PID-0002
Zone Lime Saturator
Specification P01F
Hook up Not Apply
Unit
Fluid Name Water
Fluid Phase Liquid
Operating Conditions (Min/Norm/Max/Other)
Flow m3/h 46,8 117 117 117
Pressure (Upstream) barg 2 2 1 1
Temperature ºC 20 35 35 35
Pressure (downstream) mm.W.C 100 2800 2800 100
Density kg/m3 998 994 994 994
Viscosity cP 1.02 0,719 0,719 0,719
Calculated Noise dB (A) 67 69 57 65
Calculated Cv - 38 97 138 163
Velocity m/s 0,85 2,13 2.13 2.13
%Opening % 43 65 72 78
Vapor Pressure bar a 0.023 0.056 0.056 0.056
Liquid Pressure Recovery Factor (FL) (Note 3) 0,82 0,82 0,82 0,82
Cavitation Coefficient Kc ( Note 3) 1 1 1 1
Critical Pressure bar a 221
Cv Required / Cv Selected - 192 (*)
Max. Shutoff Diff. Pressure bar 5
Corrossive Agent / Toxic Agents - No No
Design Pressure barg 0 10
Design Temperature ºC 0 55
PURCHASE DATA
Manufacturer *
Model Number *
Mtr. Requisition *
Purchase Order Number *
VALVE BODY Unit
Valve Type Globe valve Stem guided
Body / Bonnet Material Flanged Type
Material detail AISI 316
Body Size 4"
Port Size N/A
Connect Rating 150#
Facing RF
Packing Material PTFE
Packing construction Rings
Guiding Stem Guide
Bonnet Type Standard Manufacturer
End connection Flanged
TRIM DATA Unit
Trim Type Conventional (*)
Trim Size (*)
Plug / Disc / Valve Material AISI 316
Seat Material AISI 316
Stem / Shaft Material 17-4 PH
Flow Tends to Open
Trim Characteristic Equal Percentage
Leakage Class Class IV
ACTUATOR
Manufacturer / Model ((*))
Actuator Type Spring Diaphragm
Size (*)
Valve Action on Failure Locked
Handwheel Yes
Maximum Actuator Force Forward/Reverse (*)
Power Supply (Electrical) V Not Apply
Air Supply Range bar g 4.5 - 8
Spring Range (*)
POSITIONER
Positioner Type Electropneumatic
Manufacturer / Model Number (*)
HART / BUS HART
Input Signal / Output Signal 4 - 20 mA / 4 - 20 mA
Position tansmitter Yes
Positioner Action / Characteristic (*)
IP Rating IP 65
Electrical / Pneumatical Connection 1/2" NPT / 1/4" NPT
Local Display Yes
LIMIT SWITCHES
Tag No. Not Apply
Manufacturer / Model number
IP Rating
Electrical connection
Type
ACCESSORIES AND OPTIONS
Booster Relay Not Apply
Locking Device Not Apply
Set Pressure to Locker Not Apply
Air Filter regulator Yes
Pressure gauge Yes. Inlet and outlet
Air connection 1/4" NPT
Tubing Nylon 11 or Nylon 12
Cableglands Yes. Brass-Nickel for Armoured cable
REQUIREMENTS AND TEST
Material Certificate Yes
Test Requirements (2*)
PIPING INTERFACE
Process Connection Flanged
Material Polypropylene
Size / Rating / Facing Inlet 4" / 150# / RF
Size / Rating / Facing Outlet 4" / 150# / RF
Others
REMARKS:
Note 1: Other Bodies and types are admisible.
Note 2: Other materials compatible with process fluid could be admisible
* data to be filled by the manufacturer
XXXXX Data Sheet Page 9 of 9