Cable Terminations Gis
Cable Terminations Gis
Catalog Python13
Company Profile
G&W Headquarters
To meet the growing demand for our products, G&W
recently relocated to a new 360,000 square foot facility in
Bolingbrook, IL, a suburb of Chicago. Our new facility is
a world-class operation allowing us to more than double
our manufacturing capability. It is here where the latest
in engineering and production modeling technology is
combined with automated manufacturing equipment to
assure that our products meet quality standards and
customer requirements.
G&W products are backed by extensive design G&W sales office (Delhi, India)
and production testing in accordance with industry
standards. Even more important is the proven G&W sales office (Singapore)
performance and assured reliability that only
comes over time. G&W products have been proving Manufacturer’s Brass and Aluminum Foundry
themselves in installations worldwide for many (Blue Island, IL, USA)
decades.
1952 – Introduction of 161kV terminations for high pressure fluid filled cables
1954 – Introduction of 230kV terminations for high pressure fluid filled cables
1958 – Introduction of 69kV stop joint for low and high pressure fluid filled cables
1959 – Introduction of 138kV terminations for high pressure gas filled cables
1963 – Introduction of joint for 138kV low and high pressure fluid filled cables
1966 – Introduced Slip-on® terminations with factory installed stress control and factory
filled dielectric fluid for 15-46kV applications
1969 – Research and development test lab built at Blue Island, Illinois, USA
1969 – 500kV terminations for high pressure fluid filled cables sent to Waltz Mill underground
transmission testing program
1969 – Extended the application range of Slip-on® design terminations to 161kV extruded
dielectric cables
1991 – First installation of 220kV terminations and joints for extruded dielectric cables
State Electricity Commission of Victoria, Australia project
1999 – Introduction of 138kV transition joints for low and high pressure fluid filled cables
2000 – Acquisition of CTM “Cable Transition Module” molded epoxy transition joint product
lines through 33kV applications
2002 – Introduced silicone rubber stress cones for transmission voltage (69kV-230kV)
terminations for extruded dielectric cables
2006 – Acquisition of PSC and Easy-On 2 distribution voltage (15kV-46kV) and (69kV)
spring loaded elastomeric terminations
2006 – Introduced dry type terminations for outdoor applications up to 138kV extruded
dielectric cables
2007 – Introduced Python® brand terminations and joints with mechanical shrink installation
method for 69kV-230kV extruded dielectric cables
2011 – First prequalification test per IEC 62067 completed on Python® 230kV rated products
for extruded dielectric cables
Standard Components
1. Conductor Connector
(Crimp type connectors supplied as standard)
2. Hood nut
3. Corona shield cap
4. Termination body
5. Stress Cone
6. Position and cushion ring
7. Slip ring 5
8. Cable entrance housing
9. Insulation and seal tapes 6
10. Mounting bracket 7 8
11. Heat shrink tube 9
12. Grounding plate 10
13. Wiping seal
12 11
Application 13
Corrugated aluminum sheath or corrugated copper sheath
or lead sheathed cables.
145 (138) kV
2 2
Copper 240mm - 1000mm (500 kcmil - 2000 kcmil) 59mm - 81mm (2.32 in. - 3.19 in.)
*Contact your G&W representative for additonal cable sizes.
PAT130C - C- -X
1 2 3 4
Conductor Size
1 Basic Termination 2 (See application range chart, Page 6)
Rated Rated
Voltage kV Voltage kV BIL (kV) Code Size mm2 Code kcmil Code
(IEC) (IEEE)
240 240M 500 500K
145 138 650 PAT130C 300 300M 750 750K
400 400M 1000 1000K
3 Conductor Material 500 500M 1250 1250K
630 630M 1500 1500K
Material Code 800 800M 1750 1750K
1000 1000M 2000 2000K
Copper C
4-Hole NEMA, Rotating 4H 240mm2 - 300mm2 (500 kcmil - 750 kcmil) 13mm
PAT130C 36 kg (80 lbs) 240mm2 - 1000mm2 (500 kcmil - 2000 kcmil) 14.5mm
Example:
PAT130C-630MC-2H-X
145kV termination for 630mm2 copper conductor with 2-hole, non-rotating aerial connection.
Standard Components 5
1. Aerial lug specified by user
2. Connector (Crimp type connectors supplied as standard)
3. Aluminum cap plate
6
4. Aluminum corona shield
5. Insulator
6. Dielectric fluid
7. Premolded rubber stress cone
8. Aluminum entrance housing with heat shrink seal, 7
standoff insulators (4) and galvanized steel mounting
plate.
9. Cable preparation kit.
Kit includes grease, 9
sandpaper, PVC tape,
heat shrink seal, solder,
flux, tinned copper 8
ground braid and
grounding lugs.
Application Range
Conductor
Conductor Size Insulation Diameter**
Material
72.5 (69) kV
Copper 240mm2 - 1600mm2 (500 kcmil - 3200 kcmil)
40.5mm - 93.2mm (1.59 in. - 3.67 in.)
Aluminum 240mm2 - 1600mm2 * (500 kcmil - 3200 kcmil) *
145 (138) kV and 170 (161) kV
Copper 240mm - 1200mm2 (500 kcmil - 2500 kcmil)
2
kcmil (76mm)
8”
Bare Copper C1 Tin Plated Copper NT
(203mm)
35- #2- Tinned C1T Silver Plated Copper NS
7 178
240 500 Silver Plated
3.38” C1S
(86mm) Copper
Bare Copper C2
300- 550- Tinned C2T
7 178
500 1000 Silver Plated
C2S
Copper
• Located on base plate PAT119 150 kg (327 lbs) 100 kg (217 lbs)
• Required if volume compensating PAT140 270 kg (592 lbs) 180 kg (394 lbs)
system option is specified PAT150 290 kg (639 lbs) 188 kg (415 lbs)
PAT160 1068 kg (2337 lbs) 780 kg (1710 lbs)
- - - - - -
1 2 3 4 5 6 7 8 9
1 Basic Termination
Rated Rated
Voltage kV Voltage kV BIL (kV) Code
(IEC) (IEEE)
72.5 69 350 PAT119
145 138 650 PAT140
170 161 750 PAT150
245 230 1050 PAT160
Example:
PAT140-3540G-630MC-X-C1T-X-X
145kV termination with gray porcelain insulator for 630mm2 copper conductor, mounting plate with standoff insulators,
aluminum entrance housing and heat shrink seals, with clamp style, tinned copper aerial lug for 240mm2 maximum
overhead conductor with standard, mechanical shrink installation.
Features
• Pressure tight epoxy socket insulator p Contact Pad
• Prefabricated silicone rubber stress cone per IEC 62271-209
• Dry type design, no oil filling of the termination required
• Dimensions meet the requirements of IEC 62271-209 5
• Third party type tested per IEC 60840 6
• 230kV is type tested per IEC 62067
• Suitable for GIS applications through 230kV and
7
transformer (oil-immersed) applications through
170kV IEC (161kV IEEE)
• Application range is 240mm2 - 2500mm2 XLPE cable 8
p Corona Shield
Standard Components
1. Contact Pad 9
2. Quick connect assembly
3. Connector
4. Connector stopper
5. Stress cone stopper
6. Epoxy Insulator
7. Premolded rubber stress cone
8. Clamping ring
9. Stress cone compression kit 10
10. Entrance housing
11. Heat shrink tube 11
Application Range
145 (138) kV
2 2
Copper 240mm - 2000mm (500 kcmil - 4000 kcmil)
57.5mm - 101.5mm (2.26 in. - 3.99 in.)
2 2
Aluminum 240mm - 1200mm * (500 kcmil - 2500 kcmil) *
170 (161) kV
2 2
Copper 240mm - 2000mm (500 kcmil - 4000 kcmil)
2 2
57.5mm - 101.5mm (2.26 in. - 3.99 in.)
Aluminum 240mm - 1200mm * (500 kcmil - 2500 kcmil) *
245 (230) kV
2 2
Copper 400mm - 2500mm (750 kcmil - 5000 kcmil)
76.5mm - 116.5mm (3.01 in. - 4.59 in.)
Aluminum 400mm2 -1600mm2 * (750 kcmil - 3200 kcmil) *
* Aluminum conductors larger than 1200mm2 (2500 kcmil) may require special conductor connection provisions.
**Contact your G&W representative for additonal cable sizes.
- - -
1 2 3 4 5
Rated Rated
Voltage kV Voltage kV BIL (kV) Code Description Code
(IEC) (IEEE)
Conductor Size
3 Corona Shield Option 4 (See application range chart, Page 12)
Standard Components
1. Equipment connection:
5
• Contact pad style suitable for GIS or oil immersed
transformer applications
p Contact Pad
• Stem connector style suitable for oil immersed
6 per IEC 62271
transformer applications. Various styles of aerial lugs
are available for stem connector design.
2. Connector with double “O”-ring seal 7
3. Epoxy insulator with built-in cable shield break
4. Dielectric fluid
5. Premolded rubber stress cone 8
6. Aluminum clamping ring
7. Aluminum base plate
8. Aluminum entrance housing with heat shrink seal
Application Range
72.5 (69) kV
2 2
Copper 240mm - 1600mm (500 kcmil - 3200 kcmil)
40.5mm - 90mm (1.59 in. - 3.54 in.)
Aluminum 240mm2 - 1600mm2 * (500 kcmil - 3200 kcmil) *
145 (138) kV
Copper 240mm2 - 1200mm2 (500 kcmil - 2500 kcmil)
43mm - 96mm (1.69 in. - 3.78 in.)
Aluminum 240mm2 - 1200mm2 * (500 kcmil - 2500 kcmil) *
245 (230) kV
2 2
Copper 400mm - 2500mm (750 kcmil - 5000 kcmil)
74mm - 124.9mm (2.91 in. - 4.92 in.)
Aluminum 400mm2 - 1600mm2 * (750 kcmil - 3200 kcmil) *
* Aluminum conductors larger than 800mm2 (1600 kcmil) may require special conductor connection provisions.
**Contact your G&W representative for additonal cable sizes.
G&W ELECTRIC PAGE 14
Aerial Lug Options- Used only with Stem Connector Style
kcmil (76mm)
8”
Bare Copper C1 Tin Plated Copper NT
(203mm)
35- #2- Tinned C1T Silver Plated Copper NS
7 178
240 500 Silver Plated
3.38” C1S
(86mm) Copper
Bare Copper C2
300- 550- Tinned C2T
7 178
500 1000 Silver Plated
C2S
Copper
• Kit can be used to fill multiple Contact Pad SG PATR140 90 kg (200 lbs)
per IEC 62271-209
terminations. G&W recommends
ordering one oil filling kit per six • Crimp type connectors supplied PATR160 177 kg (390 lbs)
terminations ordered. as standard
• Shear bolt connectors available
• Supplied with:
- Pump
- Valves and fittings
- Hose (2 meters)
- Sight glass
- - - - - -
1 2 3 4 5 6 7 8 9
Conductor Size
4 (See application range chart, Page 14)
5 Conductor Material 6 Entrance Configuration
Material Code
Size mm2 Code kcmil Code Description Code
Copper C
Aluminum A Aluminum entrance housing
240 240M 500 500K
and heat shrink seal X
7 Aerial Lugs
300 300M 750 750K (Use only with stem connector) Wiping Sleeve for lead
sheath, corrugated aluminum,
400 400M 1000 1000K Description Code or corrugated copper cable, WS
No aerial lug X Mounting plate with standoff
500 500M 1250 1250K insulators (4)
Clamp, Copper, 240mm2 max C1
G&W’s Python® premolded rubber joints (PMJ) are p PMJ shown installed on cable with copper housing outer
available for 145kV and 245kV IEC (138kV and 230kV protection.
IEEE) extruded dielectric cable systems.
Features Options
• Factory premolded joint • Available with mechanical shrink or slip-on installation
• 100% routine tested method.
• 138kV are type tested per applicable requirements of • Shield break or Non shield break configurations.
IEEE 48, IEC 60840 • Available with the following options for outer protection:
• 230kV is prequalification and type tested per IEC62067 – Heat shrink tubing
– Copper housing
Applications – Fiberglass housing
– Copper and fiberglass housing
• Extruded dielectric cable systems, XLPE and EPR insulated
• Shear bolt connectors available.
– Cable ground shield: copper wires / tapes, corrugated
aluminum or copper sheath, lead sheath.
– Direct burial, submersed or vault.
Application Range
Insulation
Conductor Material Conductor Size
Diameter**
145 (138) kV
2 2
Copper 400mm - 1200mm (750 kcmil - 2500 kcmil)
2 2
60mm - 94mm (2.36 in. - 3.70 in.)
Aluminum 400mm - 1200mm * (750 kcmil - 2500 kcmil) *
245 (230) kV
Copper 400mm2 - 2500mm2 (750 kcmil - 5000 kcmil)
82mm - 117mm (3.23 in. - 4.61 in.)
Aluminum 400mm2 -2500mm2 * (750 kcmil - 5000 kcmil) *
* Aluminum conductors larger than 500mm2 (1000 kcmil) may require special conductor connection provisions.
**Contact your G&W representative for additonal cable sizes.
- - - -
1 2 3 4 5 6
Rated Rated
BIL
Voltage Voltage Code Description Code Size mm2 Code kcmil Code
(kV)
kV (IEC) kV (IEEE)
145 138 650 PMJ140 With Shield Break B 400 400M 750 750M
245 230 1050 PMJ160 Without Shield Break N
500 500M 1000 1000K
4 Conductor Material 5 Additional Housing Protection
630 630M 1250 1250K
Material Code Description Code
800 800M 1500 1500K
Copper C
1000 1000M 1750 1750K
Aluminum A None X
1200 1200M 2000 2000K
6 Installation Method Copper Housing with 1400 1400M 2500 2500K
C
Compound
Description Code
1600 1600M 3000 3000K
Fiberglass Housing
Mechanical Shrink X with Compound
F
1800 1800M 5000 5000K
Slip On- Use for
spares or long term 2000 2000M
Copper Housing and
storage. Installation S
Fiberglass Enclosure CF
tool is available and is
with Compound 2500 2500M
ordered separately
Ship Weight
Catalog Prefix Approximate Ship Weight