Outdoor Terminations
G&W’s Python® outdoor PAT style transmission terminations                                                        1
are designed for extruded dielectric cable systems from
                                                                                                                 2
72.5kV to 245kV IEC (69kV to 230kV IEEE).
                                                                                                                 3
Features
•	    Stress Cone: Factory molded and 100% tested                                                                4
•	    Available with mechanical shrink or slip on installation
      method
•	    69kV and 138kV are type tested per applicable
      requirements of IEEE 48 and IEC 60840
•	    230kV is prequalified and type tested per IEC 62067
•	    Suitable for XLPE and EPR insulated cables
Standard Components                                                                                              5
1.	 Aerial lug specified by user
2.	 Connector (Crimp type connectors supplied as standard)
3.	 Aluminum cap plate
                                                                                                                 6
4.	 Aluminum corona shield
5.	 Insulator
6.	 Dielectric fluid
7.	 Premolded rubber stress cone
8.	 Aluminum entrance housing with heat shrink seal,                                                             7
    standoff insulators (4) and galvanized steel mounting
    plate.
9.	 Cable preparation kit.
    Kit includes grease,        9
    sandpaper, 	 PVC tape,
    heat shrink seal, solder,
    flux, tinned copper                                                                                          8
    ground braid and
    grounding lugs.
Application Range
      Conductor
                                           Conductor Size                                   Insulation Diameter**
       Material
                                                        72.5 (69) kV
       Copper                240mm2 - 1600mm2 (500 kcmil - 3200 kcmil)
                                                                                     40.5mm - 93.2mm (1.59 in. - 3.67 in.)
      Aluminum              240mm2 - 1600mm2 * (500 kcmil - 3200 kcmil) *
                                               145 (138) kV and 170 (161) kV
       Copper                240mm - 1200mm2 (500 kcmil - 2500 kcmil)
                                    2
                                                                                      43mm - 96.5mm (1.69 in. - 3.80 in.)
      Aluminum              240mm2 - 1200mm2 * (500 kcmil - 2500 kcmil) *
                                                        245 (230) kV
                                     2          2
       Copper                400mm - 2500mm (750 kcmil - 5000 kcmil)
                                                                                     74mm - 123.9mm (2.91 in. - 4.88 in.)
      Aluminum              400mm2 - 1600mm2 * (750 kcmil - 3200 kcmil) *
 * Aluminum conductors larger than 1200mm2 (2500 kcmil) may require special conductor connection provisions.
 **Contact your G&W representative for additonal cable sizes.
G&W ELECTRIC            PAGE 8
Insulator Options                                                        Cable Suspension Grip Option
 • Gray porcelain (standard)                                             Supplied with:
                                                                         • Stainless steel cable grip
 • Brown porcelain (optional)                                            • Turnbuckles (2)
  - Blends with existing installations                                   • Eyebolts (2)
 • Silicone rubber, composite insulator (optional)                       Arcing Horns Option
  - Less than one third the weight of porcelain insulator
  - Will not break or fracture                                           • Prevents damage to insulator due to significant 	
  - Fire and UV resistant                                                  overvoltage conditions
                                                                         • Provides an alternate current path away from 		
 Note: Extra creepage available on all models.                              the insulator
                                                                         • Adjustable to system requirements
Aerial Lug Options
                                        Style 4 Clamp Type
                                                                                                              Style 8 NEMA 4-Hole Type
                            Aerial      Aerial Lug                                     3”
                          Conductor       Height                                    (76mm)
                                                                                                                   Description                 Code
                            Size        Dimension     Lug Material    Code
                                 AWG/                                                               3”
                          mm2          inches   mm                                                                 Bare Copper                    N
                 Height
                                 kcmil                                                           (76mm)
                                                                               8”
                                                      Bare Copper     C1                                      Tin Plated Copper                  NT
                                                                             (203mm)
                          35-    #2-                     Tinned       C1T                                   Silver Plated Copper                 NS
                                          7     178
                          240    500                  Silver Plated
         3.38”                                                        C1S
        (86mm)                                           Copper
                                                      Bare Copper     C2
                          300-   550-                    Tinned       C2T
                                          7     178
                          500    1000                 Silver Plated
                                                                      C2S
                                                         Copper
Dielectric Fluid Volume Compensating System
                                                                                                                          Schrader Valve for filling
 • Required for proper performance in horizontal or inverted termination	                         Pressure Gauge           internal Gas Bladder
    installations.
 • Compensates for dielectric fluid expansion and contradiction caused 	
    by temperature fluctuations.
 • Supplied with:
   - Dielectric fluid reservoir with internal gas bladder
   - Insulating hose                                                                                         1/2” Valve
   - Optional alarm device to signal accidental loss of dielectric fluid
                                                                                                                                      Dielectric fluid
 • Contact your G&W representative for additional information.
                                                                                                 Insulating Hose
                                                                                                                                        reservoir
Drain Valve Option                               Ship Weight
                                                                                                Approximate Ship Weight
• Permits sampling of the dielectric 	                  Catalog Prefix
  fluid                                                                                     Porcelain                          Composite
• Located on base plate                                      PAT119                    150 kg (327 lbs)                     100 kg (217 lbs)
• Required if volume compensating 	                          PAT140                    270 kg (592 lbs)                     180 kg (394 lbs)
  system option is specified                                 PAT150                    290 kg (639 lbs)                     188 kg (415 lbs)
                                                             PAT160                 1068 kg (2337 lbs)                      780 kg (1710 lbs)
                                                                                                          G&W ELECTRIC                       PAGE 9
                            Outdoor Style PAT Terminations
Catalog Number Builder
Use the chart below to build your G&W catalog number. This number should be used for all inquiries and quote requests.
In addition, the following cable information is required to process your order:
1.	 Conductor size and O.D. of conductor (nominal and max)	
2.	 Insulation O.D. (min and max)					
3.	 Insulation shield O.D. (min and max)
4.	 Jacket O.D. (nominal and max)
5.	 Cable construction details with metallic screen type and fault current rating.
                                                -              -              -       -              -       -
                                     1              2              3     4        5       6     7        8       9
                                    1    Basic Termination
                                       Rated          Rated
                                     Voltage kV     Voltage kV         BIL (kV)               Code
                                       (IEC)          (IEEE)
                                         72.5             69             350              PAT119
                                         145              138            650              PAT140
                                         170              161            750              PAT150
                                         245              230           1050              PAT160
 2 Insulator- Material, Color, and Creepage
                    PAT 119                             Code                                  PAT 140                    Code
    Porcelain, gray, 1702mm standard creepage       1702G                Porcelain, gray, 3540mm standard creepage       3540G
   Porcelain, brown, 1702mm standard creepage       1702B               Porcelain, brown, 3540mm standard creepage       3540B
     Porcelain, gray, 2464mm extra creepage         2464G                    Porcelain, gray, 5050mm extra creepage      5050G
    Porcelain, brown, 2464mm extra creepage         2464B                 Porcelain, brown, 5050mm extra creepage        5050B
 Silicone rubber, gray, 1524mm standard creepage    1524G              Silicone rubber, gray, 3283mm standard creepage   3283G
   Silicone rubber, gray, 2194mm extra creepage     2194G               Silicone rubber, gray, 4863mm extra creepage     4863G
                    PAT 150                             Code                                  PAT 160                    Code
    Porcelain, gray, 4115mm standard creepage       4115G                Porcelain, gray, 5221mm standard creepage       5221G
   Porcelain, brown, 4115mm standard creepage           4115B           Porcelain, brown, 5221mm standard creepage       5221B
      Porcelain, gray, 5890mm extra creepage        5890G                    Porcelain, gray, 8006mm extra creepage      8006G
     Porcelain, brown, 5890mm extra creepage        5890B                 Porcelain, brown, 8006mm extra creepage        8006B
 Silicone rubber, gray, 3728mm standard creepage    3728G              Silicone rubber, gray, 5272mm standard creepage   5272G
   Silicone rubber, gray, 5410mm extra creepage     5410G               Silicone rubber, gray, 7693mm extra creepage     7693G
G&W ELECTRIC            PAGE 10
      Conductor Size
 3    (See application range chart, Page 8)
                                                             4    Conductor Material
                                                                                  Material                            Code
     Size mm2          Code                 kcmil   Code
                                                                                  Copper                                  C
       240             240M                 500     500K                       Aluminum                                   A
       300             300M                 750     750K
       400             400M                 1000    1000K
       500             500M                 1250    1250K   5
       630             630M                 1500    1500K
       800             800M                 1750    1750K                            Description                              Code
      1000            1000M                 2000    2000K                     Mounting plate with standoff
                                                             insulators (4), aluminum entrance housing and heat shrink          X
      1200            1200M                 2500    2500K                               seals
      1400            1400M                 3000    3000K       Wiping sleeve for lead sheath, corrugated aluminum, or
                                                                corrugated copper cable, Mounting plate with standoff          WS
      1600            1600M                 5000    5000K
                                                                                     insulators (4)
      1800            1800M
      2000            2000M
      2500            2500M                                  7
                                                                   Aerial Lug Finish
                                                                                       Finish                                 Code
 6     Aerial Lugs                                                                     None                                    X
                   Description                      Code                              Tinned                                   T
                  No aerial lug                      X                                 Silver                                  S
        Clamp, Copper, 240mm max   2
                                                    C1
                 Clamp, Copper,
                                                    C2
                300mm2 - 500mm2
                                                             9     Installation
             NEMA 4-hole, Copper                     N
                                                                                     Description                              Code
 8     Additional Components                                                      Mechanical shrink                            X
                                                             Slip on: Use for spares or long term storage. Installation
                   Description                      Code            tool is available and is ordered separately
                                                                                                                               S
        No additional components required            X
                   Arcing horns                     AH
                   Drain valve                      DV
         Stainless steel suspension grips           SG
E XAMPLE :
PAT140-3540G-630MC-X-C1T-X-X
145kV termination with gray porcelain insulator for 630mm2 copper conductor, mounting plate with standoff insulators,
aluminum entrance housing and heat shrink seals, with clamp style, tinned copper aerial lug for 240mm2 maximum
overhead conductor with standard, mechanical shrink installation.
                                                                                                G&W ELECTRIC              PAGE 11