GenSet Controls
PowerCommand
        Digital Generator Set Control
          with Paralleling & Power Transfer
                                                                                PowerCommand Operator Panel, including
                                                                                graphical display and analog AC metering.
Description                                                       Features
                                                                  The control offers a wide range of standard control and
The PowerCommand™ Control (3201) is a
                                                                  digital display features so custom control configurations
microprocessor-based generator set monitoring, metering,
                                                                  are not needed to meet application specifications.
and control system. The control provides an operator
                                                                  System reliability is not compromised by use of untested
interface to the genset, digital voltage regulation, digital
                                                                  special components.
governing, generator set protective functions, and
automatic power transfer functions. The integration of all
the functions into a single control system provides               Major Control Features Include:
enhanced reliability and performance compared to                  •    Digital Full Authority Electronic Engine Controls
conventional control systems.                                          for Cummins HPI-PT fuel system, including engine
                                                                       monitoring and protection, and governing. These
PowerCommand generator set controls are suitable for                   functions are integrated with voltage regulation, and
use on generator set ranging in size from roughly 20kW to              paralleling functions for optimum system
4000 kW. They will directly read AC voltages up to                     performance.
600VAC, and can be configured for any frequency,                  •    Digital Voltage Regulation
voltage, and power connection configuration from 120-             •    AmpSentry™ Protection for true alternator
13,800VAC.                                                             overcurrent protection.
                                                                  •    Digital Power Transfer Controls, including operation
The PowerCommand control is designed for mounting on                   in open transition, closed transition, or soft (ramping)
the generator set. The operator panel may also be                      transfer modes.
remote-mounted from the generator set, and connected              •    Analog and Digital AC Output Metering.
via an RS485 network connection.                                  •    Battery Monitoring System to sense and warn
                                                                       against a weak battery condition.
Control power for PowerCommand is usually derived from
                                                                  •    Digital Alarm and Status Message Display
the generator set starting batteries. The control functions
                                                                  •    Generator set Monitoring: Displays status of all
over a voltage range from 8VDC to 35VDC.
                                                                       critical engine and alternator generator set functions.
                                                                  •    Smart Starting Control System: Integrated fuel
                                                                       ramping to limit black smoke and frequency
                                                                       overshoot, in addition to optimized cold weather
                                                                       starting.
                                                                  •    Advanced Serviceability using InPower, a PC-based
                                                                       software service tool.
                                                                  •    PowerCommand Network (optional).
                                                                  •    Warranty. PowerCommand Controls are supported
                                                                       by a worldwide network of independent distributors
                                                                       who provide parts, certified service and warranty
                                                                       support.
© 2004-2005 Cummins Power Generation         Specifications Subject to Change                                      S-1444c (5/05)
                                                                       the operator to reset the fault condition. If the fault
Operator Panel                                                         condition is not corrected, the fault will reappear, but
                                                                       will not be logged as a separate event. Multiple
The operator panel provides the user with a complete                   faults can be logged and displayed at one time.
package of easy to view and use information. It includes              EMERGENCY STOP Control Switch
an enhanced graphical operator panel that allows the user             Operator Adjustments - The control includes
to view up to 9 lines of information, as well as graphical             provisions for many set up and adjustment functions
displays of system data. Connections to the operator                   via raise/lower switches on the operator panel.
panel are sealed locking plug interfaces, for reliable,                Functions that can be adjusted by the operator
vibration-resistant interconnection to the generator set               include:
wiring harness.                                                            Time delay start (0-300 seconds)
                                                                           Time delay stop (0-600 seconds)
Control Switches and Functions                                             Alternator voltage (plus or minus 5%)
                                                                           Alternator frequency (plus or minus 3 hertz).
                                                                       The operator panel can be configured to require an
                                                                       access code prior to adjusting these values. A
                                                                       second access code is used to protect the control
                                                                       from unauthorized service level adjustments.
                                                                       Voltage and frequency adjustments are disabled
                                                                       during operation in parallel with a system bus to
                                                                       prevent inadvertent misadjustment of the paralleling
                                                                       load sharing functions.
    OFF/MANUAL/AUTO Mode Control Switch - The
     NOT IN AUTO lamp will flash when the control is in
     the MANUAL or OFF mode. In the AUTO mode, the                   PowerCommand Analog AC Metering Display
     generator set can be started using the exercise push-
     button, or with a start signal from a remote device,
     such as automatic transfer switches.                        Analog AC Metering Panel
    MANUAL RUN/STOP Control Switch And
                                                                 The PowerCommand control is equipped with an analog
     Indicating LED - When the mode control switch is in
                                                                 AC metering panel that simultaneously displays 3-phase
     the MANUAL position and the MANUAL RUN /STOP
                                                                 line to line AC volts and current, kW, power factor, and
     switch is pressed, the Generator set will start,
                                                                 frequency.
     bypassing all time delay start. (Time delay idle can
     also be bypassed with another control action.) If the
                                                                 The meter panel is composed of a series of LED’s
     generator set is running in the MANUAL mode,
                                                                 configured in bar graphs for each function. The LED’s are
     pressing the RUN/STOP switch will cause the
                                                                 color coded, with green indicating normal range values,
     generator set to shut down. An LED (light emitting
                                                                 amber for warning levels, and red for shutdown
     diode) lamp adjacent to the switch will light to
                                                                 conditions. Scales for each function are in % of nominal
     indicate the generator set is in manual mode.
                                                                 rated values. Resolution is 1% for values close to
    EXERCISE Control Switch And Indicating LED -
                                                                 nominal, and increases at increasing values from nominal.
     When the mode control switch is in the AUTO mode
     the EXERCISE control switch is used to complete a
     pre-programmed exercise sequence. All exercise
     functions are disabled when an emergency start
     command is received by the control. An LED lamp
     adjacent to the switch will light to indicate the
     generator set is in exercise mode.
    PANEL LAMP/LAMP TEST Control Switch
    FAULT ACKNOWLEDGE/RESET Switch – The
     control includes a fault acknowledge function to allow
© 2004-2005 Cummins Power Generation         Specifications Subject to Change                                 S-1444c (5/05)
                                                                        operating hours on the generator set, and also on the
                                                                        loads on the generator set since reset.
                                                                       Generator Set Output Voltage - all phases, line to
                                                                        line and line to neutral, accuracy 1%.
                                                                       Generator Set Output Current - all phases,
                                                                        accuracy 1%.
                                                                       Generator Set Output Frequency
                                                                       Generator Set Power Output - PowerCommand
                                                                        displays generator set kW and kVA output (average
                                                                        and individual phase, and direction of flow), and
                                                                        power factor with leading/lagging indication.
                                                                        Accuracy 5%.
                                                                       Generator Set kWh Power Output - Displays total
                                                                        kilowatt-hours produced by the generator set, and
Graphical Display Panel                                                 total produced since last reset, with time stamp of
                                                                        time of last reset.
The PowerCommand control is provided with a graphical                  Digital Synchroscope - Panel displays bus voltage
display capable of displaying up to 9 lines of data with                and frequency, generator set bus voltage and
approximately 27 characters per line. The graphical                     frequency, the phase angle displacement, and
display is accompanied by a set of six tactile feel                     provides a signal when the generator is ready to
membrane switches that are used by the operator to                      close to the bus. A breaker control switch is included
navigate through control menus, and to make control                     on this panel for convenient operation of the
adjustments. Display is configurable for multiple                       equipment without switching between viewing
languages. It is configurable for units of measurement.                 screens.
The display incorporates three levels of operation and                 Basic Engine Data - Engine Starting Battery
adjustability. All data on the control can be viewed by                 Voltage, Engine Lube Oil Pressure, Engine Coolant
scrolling through screens with the navigation keys. The                 Temperature
top three lines of the display are allocated to mode and               Engine Service Data - Engine Coolant Pressure
status messages that continuously display the operating                 Engine Fuel Rail Temperature and Pressure, Engine
mode of the control system, as well as any faults or                    Fuel Input And Output Temperature, Intake Manifold
warning conditions that may be present on the controller.               Temperature And Pressure, Ambient Air Pressure,
If more than one fault or warning message is present the                Crankcase Blowby Flow, Aftercooler Inlet Coolant
messages will scroll to allow the operator to view all active           Temperature
messages in the system.                                                Engine Fuel Consumption - The fuel consumed by
                                                                        the engine is determined by algorithms based on
    Generator Set Hardware Data - Generator set                        parameters monitored by the fuel system. Accuracy
     rating in kVA, complete Generator set model number                 is + 5% for load levels over 30% of standby rating.
     and serial number, engine model and serial number,                 Data provided includes overall average fuel
     and alternator model and serial number. The control                consumed, consumption since reset. This information
     also displays the part number of the control and the               is read with InPower.
     software version present in the control.                          Engine Exhaust Temperature (optional)
•    Data Logs - Number of start attempts and number of                Utility (Mains) Source Data – Displays line to line
     start attempts since reset. Number of times                        and line to neutral voltage of utility (mains) source,
     generator set has run, and number of times since                   frequency, and estimated amps, kW, and kVA
     reset. Duration of generator set running time, and                 supplied by utility (mains) source.
     duration of running time since last reset. Generator              System Status Information – Provides graphical
     set kWh produced, and kWh produced since last                      system status display showing availability of sources
     reset.                                                             and positions of each contactor.
    Adjustment History - Provides a record of                         System Control – Allows operator to view status of
     adjustment and setting changes made on the control,                system, and manually control operation of the
     and identifies whether adjustment was made via the                 system. Provides manual adjustment capability for
     operator panel or with a service tool. If a service tool           time delay start, stop, transfer, and retransfer, as well
     is used, the control provides a record of the serial               as time delays for program transition (when used)
     number of the tool used. This information is read                  and power transfer overlap time.
     with InPower.
    Fault History - Provides a record of the most recent
     fault conditions with time stamp, along with the
     number of times each fault has occurred. At least 20
     events are stored in the control memory.
    Load Profile Data - Provides data indicating the
     operating hours at percent of load, in 10%
     increments. The data is presented based on total
© 2004-2005 Cummins Power Generation          Specifications Subject to Change                                 S-1444c (5/05)
Internal Control Functions                                         Synchronizer - PowerCommand incorporates a digital
                                                                   synchronizing function to force the generator set to match
                                                                   the phase relationship and voltage of the generator set
General Functions                                                  output with the utility grid. The synchronizer includes
Emergency Start Mode - PowerCommand accepts a                      provisions to provide proper operation even with highly
ground signal from remote devices or a network signal to           distorted bus voltage waveforms. The synchronizer
automatically start the generator set and immediately              operates over a range of 60-110% of nominal voltage and
accelerate to rated speed and voltage.                             frequency, and includes adjustments for phase angle
                                                                   window (5-20 degrees) and time delay (0.5-5 seconds).
PowerCommand includes a Smart StartingTM system, that
is designed to quickly start the engine, minimize black            Load Govern Mode - When PowerCommand receives a
smoke, and minimize voltage and frequency overshoot                signal indicating that the generator set is paralleled with
and oscillations on starting. The control system does this         an infinite source, such as a utility (mains) service, the
by careful simultaneous control of the engine fuel system          generator set will operate in load govern mode. In this
and alternator excitation system.                                  mode, the generator set will synchronize and close to the
                                                                   bus, and ramp to a pre-programmed kW and kVar load
Non-Emergency Start Mode - The control is provided                 level, and then operate at that point. Control is adjustable
with a separate remote start input or a network signal to          for kW values from 0-100% of standby rating, and 0.7-1.0
start the generator set via the programmable idle control.         power factor (leading). Default setting is 80% of standby
Using the non-emergency mode, the generator set takes              and 1.0 power factor. The control includes inputs to allow
longer to start, but there is less wear on the engine. In          independent control of kW and kVar load sharing level by
this start mode, the generator set will start, operate at idle     a remote device while in the load govern mode. The rate
speed for a predefined time period or until the engine             of load increase and decrease is also adjustable in the
reaches operating temperature (whichever is time is                control.
shorter), and then ramp to rated speed and voltage. Time
delay is adjustable from 0-300 seconds, and default is 10          Engine Control
seconds. The control also monitors and records the                      Engine Starting - The control operates a factory-
source of start signals, when that information is available.             supplied fuel valve that enables engine starting.
The control automatically exits idle mode if an emergency               Cycle Cranking - Configurable for number of starting
remote start signal is received at the control.                          cycles (1 to 7) and duration of crank and rest periods.
Screen-Saver Mode - PowerCommand can be                                  Control includes starter protection algorithms to
programmed to automatically switch off the operator panel                prevent the operator from specifying a starting
displays to reduce battery voltage drain when the control                sequence that might be damaging. Default setting is
is not being used and the generator set is not running.                  for (3) start cycles composed of 15 seconds of
Depressing any button on the operator panel, new fault                   cranking, and 15 seconds of rest.
conditions or receipt of a remote signal at the control will            Programmable Idle Speed Control - In this mode
“wake up” the control.                                                   the generator set would start and run to idle speed.
Data Logging - The control maintains a record of manual                  It would operate at that speed for a programmed time
control operations, warning and shutdown conditions, and                 period, then ramp to rated speed. When the control
other events. It uses the control “ON” time as the time                  gets a signal to stop, it will ramp to idle, operate for
stamp means when a real time clock is not included with                  the programmed period at idle, and then shut down.
the control. The control also stores critical engine and                 During idle mode engine protective functions are
alternator data before and after a fault occurs, for use by              adjusted for the lower engine speed, and alternator
InPower and the technician in evaluating the root causes                 function is disabled.
for the fault condition.                                                Time Delay Start And Stop (cooldown) -
                                                                         Configurable for time delay of 0-300 seconds prior to
Fault Simulation Mode - PowerCommand, in conjunction                     starting after receiving a remote start signal, and for
with InPower software, will accept commands to allow a                   time delay of 0-600 seconds prior to ramp to idle or
technician to verify the proper operation of all protective              shut down after signal to stop in normal operation
functions of the control, by simulating failure modes or by              modes. The generator set control will monitor the
forcing the control to operate outside of its normal                     load during operation of the generator set, and if the
operating ranges. InPower also provides a complete list                  total load on the set is less than 10% of rated, it will
of faults and settings for the protective functions of the               reduce the operation time for the time delay stop to
specific generator set it is communicating with.                         prevent extended operation of the engine at very light
                                                                         load levels. Default for both time delay periods is 0
Built In Test - The control system automatically tests                   seconds.
itself, and all the sensors, actuators and harnesses in the
control system on a startup signal. The test can also be
initiated from InPower, and can be accomplished either
local to the generator set or remotely.
© 2004-2005 Cummins Power Generation           Specifications Subject to Change                                S-1444c (5/05)
Engine Governing                                                  On a shutdown condition, the control will light the
                                                                  shutdown LED on the control panel, display the fault
    Isochronous Governing - Controls engine speed
                                                                  name and code, and initiate shut down and lock out the
     within plus or minus 0.25% for any steady state load
                                                                  generator set. The shutdown sequence of the generator
     from no load to full load. Frequency drift will not
                                                                  set includes programmable cooldown at idle for fault
     exceed plus or minus 0.5% for a 60F (33C) change
                                                                  conditions that do not endanger the engine. The control
     in ambient temperature over an 8 hour period.
                                                                  maintains a data log of all fault conditions as they occur,
    Droop Governing - Control can be adjusted to droop
                                                                  and time stamps them with the controller run time and
     from 0 to 10% from no load to full load, using
                                                                  engine operating hours data. Adjustments to most set
     InPower.
                                                                  points are made using the InPowerTM service tool.
    Temperature Dynamics - Modifies the engine fuel
     system control parameters as a function of engine
                                                                  The control system includes a “fault bypass” mode that
     temperature. Allows engine to be more responsive
                                                                  forces the system to function regardless of the status of
     when warm, and more stable when operating at
                                                                  protective functions. In this mode the only protective
     lower temperature levels.
                                                                  functions that are operational are Overspeed, loss of both
    Isochronous Load Sharing Control – see General
                                                                  speed sensors, or moving the control switch to the off
     Functions.
                                                                  position, or pressing the EMERGENCY STOP switch.
    Droop Load Sharing Control– see General
                                                                  The control maintains a record of the time that the mode
     Functions.
                                                                  is enabled, and all warning or shutdown conditions that
    Idle Mode - Engine governing can be regulated at an
                                                                  have occurred while in the “fault bypass” mode.
     idle speed for a programmed period on start or stop
     of the engine. When the engine is operating at idle
                                                                  Many protective functions within the control system are
     speed, the alternator excitation is automatically
                                                                  configurable for warning, shutdown, or both (2 levels).
     switched off.
                                                                  Exceptions to this include functions such as overspeed
                                                                  conditions, and loss of speed sensing. In addition, some
Alternator Control                                                warning functions can incorporate control functions as a
    Digital Output Voltage Regulation -                          consequence of a fault.
     PowerCommand will regulate output voltage to within          PowerCommand provides the following system protective
     0.5% for any loads between no load and full load.            functions:
     Voltage drift will not exceed plus or minus 0.5% for a
     60F (33C) change in temperature in an 8 hour                      Ground Fault Warning (option- 600VAC class
     period. On engine starting, or sudden load                         generator sets) - Ground (Earth) fault sensing is
     acceptance, voltage is controlled to a maximum of                  adjustable over a range of 100-1200 amps, with time
     5% overshoot over nominal level.                                   delays of 0-1 second. May be configured for
    Torque-Matched Volts/Hz Overload Control - The                     shutdown rather than alarm.
     voltage roll-off set point and rate of decay (i.e., the           Configurable Alarm And Status Inputs -
     slope of the volts/hertz curve) is adjustable in the               PowerCommand will accept up to four alarm or
     control. This function is automatically disabled when              status inputs (contact closed to ground) to indicate
     the control is in a synchronizing mode.                            customer-specified conditions. The control is
    Fault Current Regulation - PowerCommand will                       programmable for warning, shutdown or status
     regulate the output current on any phase to a                      indication, and for labeling the input (up to 24
     maximum of 3 times rated current under fault                       characters). Four additional faults can be input to the
     conditions for both single phase and three phase                   control via the network.
     faults. In conjunction with a permanent magnet                    Breaker Fail To Close And Breaker Auxiliary
     generator, it will provide 3 times rated current on all            Contact Warning Or Shutdown - When the
     phases for motor starting and short circuit                        paralleling control signals a circuit breaker to close, it
     coordination purposes.                                             will monitor the breaker auxiliary contacts and verify
    Isochronous (kVar) Load Sharing Control – see                      that the breaker has connected the generator set to
     General Functions.                                                 the system bus. If the control does not sense a
    Droop (kVar) Load Sharing Control – see General                    breaker closure within 1 second of the close signal,
     Functions.                                                         the control will monitor the phase relationship
                                                                        between the generator set and the bus. If this
Protective Functions                                                    indicates that the generator set is not closed to the
                                                                        bus, the Breaker Fail to Close alarm will be indicated,
On a warning condition the control will indicate a fault by
                                                                        the breaker will be opened, and the generator set
lighting the warning LED on the control panel, and
                                                                        shut down. If the phase relationship monitor
displaying the fault name and code on the operator
                                                                        indicates that the generator set is in parallel with the
display panel. The nature of the fault and time of
                                                                        bus, the Breaker Auxiliary Contact Failure will be
occurrence are logged in the control. The service manual
                                                                        indicated, and the generator set will continue to run
and InPower service tool provide service keys and
                                                                        in normal operation mode.
procedures based on the service codes provided.
© 2004-2005 Cummins Power Generation          Specifications Subject to Change                                 S-1444c (5/05)
     Breaker Fail To Open Warning - The control                        Over Current Shutdown (51) - Output current on
      system monitors the operation of breakers that have                any phase is more than 110%, less than 175% of
      been signaled to open. If the breaker does not open                rating, and approaching thermal damage point of
      within 1 second of initiation of signal, a Breaker Fail            alternator. Control includes algorithms to protect
      to Open warning is initiated. The control will logically           alternator from repeated over current conditions over
      allow the generator set to continue to run if shutdown             a short period of time.
      of the generator set with the breaker closed will                 Short Circuit Shutdown (51V) -Output current on
      cause potential damage or operating problems.                      any phase is more than 110%, more than 175% of
     Bus Or Generator Set PT Input Calibration Error -                  rating, and approaching thermal damage point of
      The control system monitors the sensed voltage from                alternator. Control includes algorithms to protect
      the bus and generator set output voltage potential                 alternator from repeated over current conditions over
      transformers, and will indicate a warning condition                a short period of time.
      when they read different values when the paralleling              High AC Voltage Shutdown (59) - Output voltage
      breaker is closed.                                                 on any phase exceeds preset values. Time to trip is
     Emergency Stop - Annunciated whenever the local                    inversely proportional to amount above threshold.
      or remote emergency stop signal is received. Alarm                 Values adjustable from 105-125% of nominal
      panel distinguishes between local or remote                        voltage, with time delay adjustable from 0.25-10
      operation.                                                         seconds. Default value is 110% for 10 seconds.
                                                                        Low AC Voltage Shutdown (27) - Voltage on any
                                                                         phase has dropped below a preset value. Adjustable
                                                                         over a range of 50-95% of reference voltage, time
                                                                         delay 2-10 seconds. Default value is 85% for 10
                                ALTERNATOR                               seconds. Function tracks reference voltage. Control
                                THERMAL                                  does not nuisance trip when voltage varies due to the
                                DAMAGE                                   control directing voltage to drop, such as during a
                                CURVE                                    voltage roll-off during synchronizing.
                                                                        Under Frequency Shutdown (81u) - Generator set
                                                                         output frequency cannot be maintained. Settings are
                                       AMPSENTRY                         adjustable from 0-10 hertz below nominal governor
           10                          OVERCURRENT                       set point, for a 0-20 second time delay. Default: 6Hz,
                                       PROTECTION                        10 seconds. Under frequency protection is disabled
    Second                             CURVE                             when excitation is switched off (such as when engine
    s                                                                    is operating in idle speed mode or the synchronizer is
              1                                                          enabled).
                                                                        Over Frequency Shutdown/Warning (81o) -
                                                                         Generator set is operating at a potentially damaging
                                                                         frequency level. Defaults: Disabled.
                                                                        Over Load (kW) Warning - Provides a warning
                                                                         indication when engine is operating at a load level
                                                                         over a set point. Adjustment range: 80-140% of
       0.03                                                              rated kW, 0-120 second delay. Defaults: 105%, 60
                                                                         seconds.
                                                                        Reverse Power Shutdown (32) - Adjustment range:
                                                                         5-20% of standby kW rating, delay 1-15 seconds.
                    1             10       Amps ( x rated)               Defaults: 10%, 3 seconds.
                                                                        Sync Check (25) - Verifies that the generator set is
                                                                         operating in synchronism with the system bus prior to
AmpSentryTM                                                              allowing the paralleling breaker to close. Includes
AmpSentry is a comprehensive monitoring and control                      dead bus sensing capability.
system integral to the PowerCommand control that guards                 Fail To Synchronize Warning Or Shutdown -
the electrical integrity of the alternator and power system              Indicates that the generator set could not be brought
by providing protection against a wide array of fault                    to synchronization with the system bus. Configurable
conditions in the generator set or in the load. It also                  for warning or shutdown, and adjustable for time
provides single and 3-phase fault current regulation, so                 delay of 10-120 seconds. Default is 120 seconds.
that downstream protective devices have the maximum                     Phase Sequence Sensing Shutdown - Verifies that
current available to quickly clear fault conditions, without             the generator set phase sequence matches the bus
subjecting the alternator to potentially catastrophic failure            prior to allowing the paralleling breaker to close. The
conditions. Functions included:                                          generator set will shutdown if the generator set and
    Over Current Warning - Output current on any                        bus phase sequence does not match.
     phase at more than 110% of rating for more than 60                 Reverse Var Shutdown - Shutdown level is
     seconds.                                                            adjustable: 15-50% of rated Var output, delay 10-60
                                                                         seconds. Defaults: 20%, 10 seconds.
© 2004-2005 Cummins Power Generation           Specifications Subject to Change                               S-1444c (5/05)
    High Alternator Temperature (Option)                        •    3-phase (line to neutral) close differential under
                                                                      voltage sensing for utility (mains) service. Sensing for
Engine Protection                                                     pickup in an adjustable range from 85-100% of
                                                                      nominal, with default at 95% of dropout setting.
    Overspeed Shutdown - Default setting is 115% of
                                                                      Dropout is configurable 75-98% of pickup, with default
     nominal.
                                                                      at 85%.
    Low Lube Oil Pressure Shutdown - Level is preset
     to match the capabilities of each engine. Control           •    3-phase over voltage sensing for normal utility service
     includes time delays to prevent nuisance shutdown                adjustable for pickup at 95-105% of dropout, and
     signals.                                                         dropout configurable for 105-135% of nominal. Time
    Low Lube Oil Pressure Warning - Level is preset to               delay is adjustable in a range of 0.5-120 seconds.
     match the capabilities of each engine. Control                   Default is disabled, and is enabled using InPower.
     includes time delays to prevent nuisance shutdown
                                                                 •    Under frequency sensing for normal utility service.
     signals.
                                                                      Adjustment range is 80-95% of nominal. Default is
    High Coolant Temperature Shutdown
                                                                      disabled, and is enabled using InPower.
    High Coolant Temperature Warning
    Low Coolant Pressure Warning/Shutdown                       •    Configurable sequence of operation with or without
    Low Coolant Level Warning/Shutdown                               adjustable program-transition capability. Adjustment
    Low Coolant Temperature Warning. Indicates that                  range is 0-60 seconds.
     engine temperature may not be high enough for a 10
                                                                 •    Remote Exercise feature. Accepts a remote signal to
     second start or proper load pickup.
                                                                      initiate with or without load testing; or testing can be
    Low and High Battery Voltage Warning - Indicates
                                                                      initiated by the operator. Test sequence may include
     battery charging system failure by continuously
                                                                      a programmed idle period prior to acceleration to
     monitoring battery voltage and indicating a problem
                                                                      rated voltage and frequency and after cooldown. Test
     when voltage is outside a preset acceptance band.
                                                                      may be configured to be performed with load or
    Discharged Battery Protection. When DC voltage
                                                                      without load.
     is below a preset threshold the control will shut down
     to avoid completely discharging the battery.                •    Time delays: time delay start and stop as described in
    Weak Battery Warning - The control system will test              this document; time delay transfer adjustable in a
     the battery bank each time the generator set is                  range of 0-120 seconds, and retransfer in a range of
     signaled to start, and indicate a warning if the                 0-1800 seconds; all in 1-second increments.
     generator set battery indicates impending failure.
                                                                 •    Fail to disconnect timer. The control includes a fail to
    Fail to Start (Overcrank) Shutdown
                                                                      disconnect timer that is adjustable in a range of 0.1 to
    Fail to Crank Shutdown - Control has signaled
                                                                      120 seconds.
     starter to crank engine but engine does not rotate.
    Redundant Starter Disconnect
    Redundant Speed Sensors - Loss of one sensor                Control Interface
     results in a Mag Pickup sensor warning. Loss of
     both sensors results in Mag Pickup Failure.                 Input signals to the PowerCommand control include:
    Low Fuel-Day Tank and Low Fuel-Main Tank                        Remote Start signal. May be connected via either
     warning.                                                         discrete signal or Lon network, or both for premium
    Cranking Lockout. The control will not allow the                 reliability. Discrete signal is normally open contact to
     starter to attempt to engage or to crank the engine              ground, or normally closed contact that opens to
     when the engine is rotating.                                     indicate start signal. Separate signal inputs available
    Sensor Failure Indication. All analog sensors are                for emergency start and non-emergency start.
     provided with sensor failure logic to indicate if the           Remote Emergency Stop
     sensor or interconnecting wiring has failed. Separate           Configurable Customer Inputs. Control includes
     indication is provided for fail high or low.                     provisions for (4) input signals from customer
    High Crankcase Blowby Level Warning                              discrete devices.
    High Fuel Temperature Warning                                   Low Main or Daytank Fuel Level warning.
    High Intake Manifold Temperature/Pressure                       Remote Alarm Reset.
    Aftercooler Cooler Inlet Over Temperature                       Load Demand Stop.
                                                                     Utility Parallel (Load Govern) Mode command.
Power Transfer Control
                                                                 Output signals from the control include:
The Power Transfer Control feature allows                           Generator Set Running signal. Fused normally
PowerCommand to provide integrated automatic power                   open contact rated 5A @ 30VDC/180VAC, closes to
transfer functions including source availability sensing and         indicate generator set is running.
transfer device monitoring and control. The control is              Generator Set Common Shutdown signal. Self-
configurable for open transition, fast (100 mS) transfer, or         protected relay driver.
soft (ramping) sequences of operation. Standard                     Load Shed signal. Self-protected relay driver.
functions include:                                                   Operation is configurable for under frequency or over
                                                                     kW load, or both. Adjustment range is 80-140% of
© 2004-2005 Cummins Power Generation         Specifications Subject to Change                                S-1444c (5/05)
     standby rating, with time delay of 0-120 seconds.           moisture, oil, and exhaust fumes. The panel uses sealed
     Default settings are: overload: 105%, 60 sec; under         membrane or oil-tight switches to provide long reliable
     frequency: 3 Hz below governor reference for 3              service life in harsh environments.
     seconds.
    Ready to Load signal. Self-protected relay driver.          The control system is specifically designed for resistance
     Operates when the generators sets has reached               to RFI/EMI, and to resist the effects of vibration to provide
     90% of rated speed and voltage and latches until            a long reliable life when mounted on a generator set. The
     generator set is switched to off or idle mode.              control includes transient voltage surge suppression to
    Modem Control signal. Self-protected relay driver.          provide compliance to referenced standards.
    Paralleling Breaker Interface. Fused normally open
     relay contact (5A, 30Vdc/180Vac) for parallel breaker       Software
     close signal, and normally open contact for parallel
     breaker open signal.
                                                                 InPower
Control power for auxiliary devices is available from the        InPower is a PC-based software service tool that is
controller.                                                      designed to directly communicate to PowerCommand
                                                                 generator sets and transfer switches to facilitate service
Network connections include:                                     and monitoring of these products.
   Serial Interface. This communication port is to allow
    the control to communicate with a personal computer          PowerCommand for Windows
    running InPower service and maintenance software.
   Echelon LonWorks Interface (Option).                         PowerCommand for Windows is a software tool that is
    PowerCommand generator sets incorporating this               used to remotely monitor and control generator sets,
    option are LonMarkTM compliant.                              transfer switches, and other on-site power system
                                                                 devices.
Certifications
PowerCommand meets or exceeds the requirements of
the following codes and standards:
    NFPA110 for level 1 systems.
    UL508 Listed, Category NIWT7 for US and Canada.
    CSA C282-M1999 Compliance
    CSA 22.2 No. 14 M91 Industrial Controls.
    ISO 8528-4: 1993 Compliance, Controls and
     Switchgear
    NFPA99: Standard for Health Care Facilities
    CE Marking
    EN 50081-1 Residential, commercial, light industrial
    EN 50081-2 Industrial
    EN 50082-1 Residential, commercial, light industrial
    EN 50082-2 Industrial
    ISO 7637, pulses #2b, 4; DC supply surge voltage
     test.
    Mil Std 202C, Method 101 Salt Fog test
    ANSI C62.41 Surge Withstand
    Mil Std 461
    IEC 801.2, 3, 4, 5
    IEEE 587
PowerCommand control systems and generator sets are
designed and manufactured in ISO9001 certified facilities.
Environment
The control is designed for proper operation without
recalibration in ambient temperatures from –40C to +70C,
and for storage from –40C to +80C. Control will operate
with humidity up to 95%, non-condensing, and at altitudes
up to 13,000 feet (5000 meters).
The operator control panel is a NEMA 3R/IP53 enclosure.
The operator control panel has a single membrane
surface, which is impervious to the effects of dust,
© 2004-2005 Cummins Power Generation         Specifications Subject to Change                               S-1444c (5/05)
Options and Accessories                                                     Closed Transition (Ramping) Power Transfer
                                                                                Control. Control will operate two circuit breakers to
 Key-type Mode Select Switch.                                                  provide power transfer between a normal source and
 Ground Fault Alarm Module.                                                    generator in a “make before break” sequence
 Utility Protective Relaying. Gensets can be                                   between live sources, and “break before make” from a
    provided with power switching mechanisms and utility                        failed source. Overlap time between sources is
    grade protective relaying to meet local grid protection                     configurable, and control ramps load from source to
    requirements.                                                               source to minimize disturbances on transfer.
   Isolated Bus Paralleling. Provides all automatic and                       Exhaust Temperature Monitoring
    manual paralleling functions for systems that operate                      Alternator Temperature Monitoring
    isolated from the utility service.                                         Digital Remote Annunciator
   Full Function Paralleling. Provides all paralleling                        Digital Output Relay Module
    functions, including automatic and manual operation,
                                                                               ILSI (Isochronous Load Sharing Interface). Allows
    protection, and other features described in this
                                                                                PowerCommand to share real load with other load
    document.
                                                                                sharing systems that incorporate analog load sharing
   Open Transition Power Transfer Control. Control                             lines.
    will operate two circuit breakers to provide power
    transfer between a normal source and a generator in
    a “break before make” sequence.                                        Warranty
   Fast Closed Transition Power Transfer Control.                         PowerCommand control systems are a part of complete
    Control will operate two circuit breakers to provide                   power systems provided by Cummins Onan, and are
    power transfer between a normal source and                             covered by a one-year limited warranty as a standard
    generator in a “make before break” sequence                            feature.
    between live sources, and “break before make” from a
    failed source. Overlap between sources is 100mS or                     Extended warranty options are available for coverage up
    less.                                                                  to 10 years.
See your distributor for more information
Cummins Power Generation
1400 73rd Avenue N.E.
Minneapolis, MN 55432
763.574.5000
Fax: 763.574.5298
Cummins Power Generation is a subsidiary of Cummins Inc.
PowerCommand is a registered trademark of Cummins Inc.
AmpSentry is a trademark of Cummins Inc.
Windows is a registered trademark of Microsoft.
LONWORKS AND LONMARK are registered trademarks of Echelon
Warning: Backfeed to a utility system can cause electrocution and/or property damage. Do not connect to any building's electrical system
except through an approved device or after building main switch is open.
© 2004-2005 Cummins Power Generation                  Specifications Subject to Change                                        S-1444c (5/05)