1 2 3 4 5 6 7 8

NAME PLATE CUBICLE NO. FACTORY NO.


A . A
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

OUTGOING 1 =J04 FO101


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

.
OUTGOING 2 =J05 FO102
.

.
OUTGOING 3 =J06 FO103
.
B . B
OUTGOING 4 =J08 FO104
.

.
OUTGOING 5 =J09 FO105
.
.
OUTGOING 6 =J10 FO106
.

C . C
OUTGOING 7 =J11 FO107
.

01 12/07/2017 WD As Manufactured
D D
00 10/03/2017 AF First Issued

Rev N° Date Name Modification

Project Name

GI KAYU AGUNG PROJECT


Owner PT PLN (Persero) Order N° C2030-4020126
E E
Customer PT. INDOKOMAS BUANA PERKASA Switchboard 24kV Switchgear

SCHNEIDER-ELECTRIC INDONESIA Panel =Outgoing


EJIP PLOT 4B1-4B2 CIKARANG SELATAN Title
COVER SHEET
BEKASI 17550-JAWA BARAT
Schematic Diagram
Tel : (62-21) 897 02 03 Outgoing
PT. SCHNEIDER INDONESIA Fax : (62-21) 897 02 09
Date Name Sign Drawing Nr. X4020126-302
F Drawn 10/03/2017 AF Customer Doc. Nr. A01 F

Checked 10/03/2017 BWP Document Type A Sheet 1

Approved 10/03/2017 DTA Format A3 Scale NTS 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

CONTROL AND MONITORING


FUNCTION LOCAL LOCAL CONTROL REMOTE CONTROL REMARKS

CONTROL -Q51 -Q51 -Q51


BB1

STATUS SIGNAL -Q51,-Q30

-Q51

METERING -P50 (M8650) (kWh,kVARh) M

-P11, (AM)
B B
PROTECTION -F50, MiCOM P142 (50/51,50N/51N,74,79,50BF)

P1
CONTROL AND MONITORING

-T51L1-3

P2
TECHNICAL SWITCH DATA
DESIGNATION MANUFACT. TYPE NOMINAL CURRENT BREAKING CURRENT REMARKS

C -Q51 SCHNEIDER HVX24-25-08E 800A 25kA C


-Q30 SCHNEIDER ES PIX24
-C1L1-3

-Q30 -H101

TECHNICAL TRANSFORMER DATA


D D
DESIGNATION MANUFACT. TYPE RATIO CORE DATA REMARKS

-T51L1 TRAFINDO CTB 24 300-600/5-5A Class 5P20, 15VA / 0.2SFS10,15VA For Protection & Measurement
-T51L2 TRAFINDO CTB 24 300-600/5-5A Class 5P20, 15VA / 0.2SFS10,15VA
-T51L3 TRAFINDO CTB 24 300-600/5-5A Class 5P20, 15VA / 0.2SFS10,15VA

E E

F F

Date 10/03/2017 Project Name Title Cover Sheet Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 A02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 2
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Revision N° Document Identification


Customer Document Number Drawing Number Sheet Description
Type Designation Sheet name
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

X4020126-302 00 01 =Outgoing A01 1 Cover Sheet Schematic Diagram Outgoing


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

X4020126-302 00 01 =Outgoing A02 2 Cover Sheet Schematic Diagram Outgoing


X4020126-302 00 01 =Outgoing B01 3 List Of Content Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing C01 4 Wiring Specification Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing D01 5 AC/DC Supply Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing G01 6 Digital Inputs Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing M01 7 Closing Circuit Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing M02 8 Tripping Circuit Schematic Diagram Outgoing

B X4020126-302 00 01 =Outgoing Q01 9 Local Control Indication Schematic Diagram Outgoing B


X4020126-302 00 01 =Outgoing Q02 10 Local Control Indication Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing Q03 11 Spare Contacts Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing Q04 12 Spare Contacts Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing Q05 13 Spare Contacts Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing Q06 14 Spare Contacts Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing Q07 15 To Scada Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing S01 16 Communication Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing T01 17 Current Circuit Schematic Diagram Outgoing
C C
X4020126-302 00 01 =Outgoing T02 18 Voltage Circuit Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V01 19 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V02 20 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V03 21 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V04 22 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V04.1 23 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V04.2 24 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V05 25 Terminal Plan Schematic Diagram Outgoing
D X4020126-302 00 01 =Outgoing V06 26 Terminal Plan Schematic Diagram Outgoing D

X4020126-302 00 01 =Outgoing V07 27 Terminal Plan Schematic Diagram Outgoing


X4020126-302 00 01 =Outgoing V08 28 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V09 29 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V10 30 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing V11 31 Terminal Plan Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing X01 32 LV Door Layout Schematic Diagram Outgoing
X4020126-302 00 01 =Outgoing X02 33 LV Box Layout Schematic Diagram Outgoing

E X4020126-302 00 01 =Outgoing Y01 34 Bill Of Materials Schematic Diagram Outgoing E


X4020126-302 00 01 =Outgoing Y02 35 Bill Of Materials Schematic Diagram Outgoing

F F

Date 10/03/2017 Project Name Title List Of Content Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 B01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 3
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 34 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SWITCHES CONTACTS AND COIL PASSIVE COMPONENTS FUSE PHASE POLARITY COLOUR CODE (MARKER)
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Description Symbol Description Symbol Description Symbol Description Symbol Circuit Wire Size Marker
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

VT L1 Red
CHANGE-OVER L2 Yellow
BREAK BEFORE Black 2.5 sqmm
THERMOSTAT OR RESISTOR FUSE L3 Black
MAKE CONTACT
N Blue

IEC S00264 IEC S00230 IEC S00555 IEC S00362 CT L1 Red


L2 Yellow
Black 4 sqmm
L3 Black
MV CIRCUIT BREAKER
In Rack Out Position NORMALLY OPEN RESISTOR FUSE ISOLATOR N Blue
For Position Switch Adjustable
AC 3-Phase L1 Red
IEC S00287 IEC S00259 IEC S00557 IEC S00369 L2 Yellow
Black 2.5 sqmm
B L3 Black B
1 N Blue
MINIATURE CIRCUIT
BREAKER NORMALLY CLOSE DIODE TRANSFORMER
For Position Switch AC 1-Phase L Red
2 (For Control) Black 1.5 sqmm
N Blue
IEC S00287 & S00191 IEC S00260 IEC S00641 Description Symbol
DC Positive Brown
REMOTE

(For Control) Black 1.5 sqmm


LOCAL

Negative White
P1 P2
LOCAL REMOTE DISCONNECTOR LED CURRENT Communication Cable Positive Green -
SWITCH WITH KEY Off Load Isolating Switch Light Emitting Diode TRANSFORMER (MODBUS / RS485) Negative White 0.33 sqmm -

S1

S2
IEC S00480 & S00179 IEC S00288 IEC S00642 IEC S01344 Ground Silver -

A N Grounding Green/Yellow 2.5 sqmm -


CLOSE
TRIP

C CB CONTROL SWITCH Wirring Specification C


Spring Return to Center DISCONNECTOR SPACE HEATER VOLTAGE
PE - Multistranded flexible copper conductor type : NYAF
On Load Isolating Switch TRANSFORMER
-PVC insulation
a n
-Rated voltage: 750 Volt
IEC S00249 IEC S00290 IEC S00566 IEC S00842
-Dielectric test voltage 50Hz, 1 sec = 1000 Volt

ASSIGNMENT ADDRESS
OFF

GROUNDING AND TERMINATION


2
3
4
5
1

MULTI STEP CONTACTOR CAPACITIVE


WITH OFF DIVIDER
C Location Designation
IEC S00272 IEC S00218 IEC S00566 Description Symbol
+S1.B LV Box Compartment
+S1.D Door Compartment
VPIS +S2 CB Compartment
EMERGENCY ON DELAY LED Voltage Indicator EARTH / GROUND
D STOP CONTACT +S4 Cable connection compartment D
IEC S00258 IEC S00243 IEC S00200
TERMINAL WIRING CODE

PUSH BUTTON OFF DELAY LAMP AND INDICATION TERMINAL BLOCK Terminal Designation
CONTACT
-X1 AC Supply For Internal Wiring
IEC S00254 IEC S00244 Description Symbol IEC S00017 -X2 DC Supply For Internal Wiring
1 -X3 Current Circuit Wiring
-X4 Voltage Circuit Wiring
CONTACTS AND COIL RELAY COIL LAMP INDICATION CONNECTING LINK
TERMINAL BLOCK -X5 Spare Contact & To External
2
Description Symbol IEC S00305 IEC S00965 IEC S00044 -X6 Output Contact to SCADA/PLC
E E
-X7 Aux. Contact For Internal Wiring
BUZZER
1 1 -X11 Interconnection Wiring For AC Control Circuit
IEC S00973
NORMALLY OPEN TIMER OFF DELAY OR ARRESTER -X21 Interconnection Wiring For DC Control Circuit
( NO ) CONTACT RELAY COIL HORN 2 2 -X31 Interconnection Wiring For Current Circuit
IEC S00227 IEC S00311 IEC S00969 Description Symbol
-X41 Interconnection Wiring For Voltage Circuit
-X51 Interconnection Wiring for Interpanel
NORMALLY CLOSE TIMER ON DELAY SEMAPHORE SURGE ARRESTER -X61 Communication Wiring
( NC ) CONTACT RELAY COIL INDICATOR
All devices shown in this diagram are in open position, drawn out (test),
IEC S00229 IEC S00312 IEC S00968 IEC S00373 with operating mechanism discharged and all power source off.
F F

Date 10/03/2017 Project Name Title Wiring Specification Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 C01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 4
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

HEATER LIGHTING MOTOR DRIVE TRIPPING CIRCUIT CONTROL CIRCUIT


All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

+S1.B +S1.B
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A -X11 1 220V AC SUPPLY (P) -X11 2 A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B
-X11 3 220V AC SUPPLY (N) -X11 4
PREVIOUS +S1.B +S1.B NEXT
CUBICLE -X21 1 110V DC SUPPLY (L+) -X21 2 CUBICLE
+S1.B +S1.B
-X21 3 110V DC SUPPLY (L-) -X21 4

B B

+S1.B 1 3 +S1.B 1 3 +S1.B 1 3 +S1.B 1 3


-Q921 -Q922 -Q923 -Q924
2 4 2 4 2 4 2 4
-Q921 -Q922 -Q923 -Q924
a 11-14 a 11-14 a 11-14 a 11-14
/Q01.B4 /Q01.B4 /Q01.B5 /Q01.B5
b 11-12 b 11-12 b 11-12 b 11-12
a 91-94 a 91-94 a 91-94 a 91-94
/Q06.D5 /Q06.D6 /Q06.D6 /Q06.D7
C b 91-92 b 91-92 b 91-92 b 91-92 C
AUX. CONTACT AUX. CONTACT AUX. CONTACT AUX. CONTACT

1 1
+S1.B
-B21 >ϑ -S34
c 2

D D

+S1.B
-X1 3

+S4
-X031 1F
1M

M+

M-
1 1

CS+
TR+

CS-
TR-
+S4 +S1.B
PE
-R11 -H17
E E
2 2
+S4
/M01.A1

/M01.E1

/G01.A1

/G01.E1

/M01.A1

/M01.E1
-X031 2M
2F

+S1.B +S1.B
-X1 5 -X1 6

F F

Date 10/03/2017 Project Name Title AC/DC Supply Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 D01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 5
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

AUTO RECLOSE CB OPEN CB CLOSE CB TEST CB SERVICE EARTHING SWITCH SWITCH POSITION
OFF/ON POSITION POSITION OPEN CLOSE LOCAL REMOTE SUPERVISORY
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

+S1.B
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A TR+ -X2 9 A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

TR+
/D01.E6 /M02.A1

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X5 5 -X5 38 -X5 42 -X5 32 -X5 34 -X5 68

+S4 +S4 +S4 +S4


-X051 3F -X051 7F -X041 5F -X041 7F
B 3M 7M 5M 7M B

X01:A12

SUPERVISORY
+S1.D

REMOTE
+S4 -S650

LOCAL
OFF

-Q51
ON

1 13 5 1 1 S1:5 S1:7/M01.F3
13 15 17
+S1.D /M01.E1 S11
+S4 +S4
-S679 -SS2 +S4 +S4
/G01.E2 14 6 -ST2 -Q30 -Q30
OFF 2 2 2 S1:6 S1:8 L 14 R 16 S 18
/T02.B1 /T02.C1
X01:A13

X01:A14

+S4 +S4 +S4 +S4


-X051 4M -X051 8M -X041 6M -X041 8M
4F 8F 6F 8F

C C

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X5 6 -X5 7 -X5 39 -X5 43 -X5 33 -X5 35 -X5 69

+ D8 + D10 + D2 + D4 + D12 + D14 + D16 + B2 + B4 + B6 + B8


D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D D
-F50 L4 -F50 L5 -F50 L1 -F50 L2 -F50 L6 -F50 L7 -F50 L8 -F50 L9 -F50 L10 -F50 L11 -F50 L12
/M02.E4 /M02.E4 /M02.E4 /M02.E4 /M02.E4 /M02.E4 /M02.E4 /M02.F4 /M02.F4 /M02.F4 /M02.F4

- D7 - D9 - D1 - D3 - D11 - D13 - D15 - B1 - B3 - B5 - B7

E E
TR- TR-
/D01.E6 /M02.E1
-S679
b 1-2 /G01.B1
a 3-4
b 5-6 /Q07.C6
a 7-8 /Q07.D6
b 9-10
a 11-12

F F

Date 10/03/2017 Project Name Title Digital Inputs Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 G01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 6
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPRING CHARGE CB CLOSE AUTO RECLOSE PERMISSIVE CLOSE DIGITAL


MOTOR LOCAL REMOTE SUPERVISORY ENERGY METER
+S1.B
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

CS+ -X2 15
/D01.E7 /Q01.A1
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

M+

SUPERVISORY
/D01.E5
+S1.D

REMOTE
-S650

LOCAL
/M01.E3 1 5 9

L 2 R 6 S 10
E7 E8
+S1.D
-F50 RL4
/M02.E2
+S1.B +S1.B +S1.B 74
-X5 1 -X5 60 -X5 70 E9
B B
+S1.B
-X1 1
-Xx xx -Xx xx 12 14
+S1.B
B9 -K79

=Supervisory
CLOSE
+S1.D E1 /M02.E7

OPEN
11
-F50 RL8 +S1.D

=Remote
+S1.D 3 /M02.E3
-S601 -F50 RL1
X01:A1

/M01.C2 /M02.E2
C 4 -Xx xx B10 -Xx xx
-S601 E2 22 24
+S1.B
+S4 a 1-2 /M02.B3
-Q51 U1 +S1.B +S1.B +S1.B -K81 + L/+
a 3-4 /M01.C2 -X5 2 -X5 61 -X5 71 /Q02.E3 21 +S1.D
/M01.E1 M1
-P50 G
C M +S1.B C
-X5 84
U2 - N/-
X01:A2

+S1.B

/T02.D2
-X2 11

+S1.B
-X1 2
X01:A5

+S4
D -Q51 D
/M01.E1 F2 C1

C2
X01:A6

PE

/T02.D1
M-
/D01.E5
+S1.B
CS- -X2 12
/D01.E7 /Q01.F1

E -Q51 -Q51 -S650 E


a A12-A14 a B13-B14 /Q04.C4 b 1-2 /M01.A2
/G01.B2
b A12-A13 b A10-A11 /Q04.C5 b 3-4 /M02.A3
a A15-B1 MICRO SWITCH BY PB a 5-6 /M01.B3
/Q06.C4
b A15-A16 a 7-8 /M02.B4
a B2-B4 -Q51 a 9-10 /M01.B3
/Q01.C1
b B2-B3 a A7-A9 a 11-12 /M02.B4
b B5-B6 /Q07.D2 b A7-A8 b 13-14 /G01.B6
a B7-B8 /M02.B2 a B15-B16 /Q04.C3 a 15-16 /G01.C6
b B9-B10 a D15-D16 /Q04.C4 a 17-18 /G01.C7
b C9-C10 /Q07.D2 MICRO S. FOR MOTOR CTRL
a C11-C12 /Q04.C3
F AUX. SWITCH POS. IND. F

Date 10/03/2017 Project Name Title Closing Circuit Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 M01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 7
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PROTECTION RELAY CB OPEN 81U 50/51,50N/51N 79 LOCKOUT 50/51,50N/51N 50BF


SUPPLY 74 LOCAL REMOTE SUPERVISORY 27 TRIP
+S1.B
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

TR+ -X2 10
/G01.A8
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

SUPERVISORY
+ D6 +S1.D

REMOTE
+S1.D -S650

LOCAL
-F50 L3 /M01.E3 3 7 11
/M02.E4

- D5
L 4 R 8 S 12

+S1.B
-X2 7 +S1.B +S1.B +S1.B
-X5 3 -X5 62 -X5 81
B B

X01:B7
-Xx xx -Xx xx

CLOSE
B11 E5 E3 E10 E11 E16 E17

OPEN

=Supervisory
+S4 +S1.D 1 +S1.D 12 14 +S1.D +S1.D +S1.D +S1.D
-Q51 -F50 +S1.B -F50 -F50 -F50 -F50
3 -S601 RL9 RL3 RL2 RL5 RL7

=Remote
/M01.F1 S12 /M02.E3 -K81 /M02.E2 /M02.E2 /M02.F2 /M02.F2
/M01.C2 /Q02.E3
O 2 11
4 B12 E6 E4 E12 E18
-Xx xx -Xx xx

+ F2

X01:B8
+S1.D +S1.B +S1.B +S1.B
-F50 PE
-X5 4 -X5 63 -X5 82

+S1.B
- F1 -X5 85
C +S1.B C
-X2 8
/T02.C2

+S1.B
-X2 6 24 4
X01:D11

X01:D12

X01:A3

+S4
-Q51 13 1
/M01.E1 S12 S11
D 14 2 D
C1 A1 A1 A1
+S1.B +S1.B +S1.B
F11 -K79 -K50 -K50BF
C2 /M02.E6 /M02.E7 /M02.E8
A2 A2 A2

X01:A4
+S1.B
-X2 5

TR-
/G01.E8
ASSIGNMENT -F50 ASSIGNMENT -F50 ASSIGNMENT -F50 ASSIGNMENT -F50 -K79 -K50 -K50BF
WD a F14-F13 /Q07.C5 RL8 a B10-B9 /M01.C3 L1 D2-D1 /G01.D3 LED1 a 11-14 a 11-14 a 11-14
/M01.B6 /Q06.D2
E WD b F12-F11 /Q04.C5 RL9 a B12-B11 /M02.B4 L2 D4-D3 /G01.D3 LED2 b 11-12 b 11-12 b 11-12 E
RL1 a E2-E1 /M01.C5 a B15-B14 L3 D6-D5 /M02.B2 LED3 a 21-24 a 21-24 a 21-24
RL10 /Q04.C6 /Q01.B6 /Q07.D5 /Q03.D4
RL2 a E4-E3 /M02.B7 b B15-B13 L4 D8-D7 /G01.D1 LED4 b 21-22 b 21-22 b 21-22
RL3 a E6-E5 /M02.B6 a B18-B17 L5 D10-D9 /G01.D2 LED5 a 31-34 a 31-34 a 31-34
RL11 /Q04.C6 /Q06.D7 /Q03.D5
a E9-E8 b B18-B16 L6 D12-D11 /G01.D4 LED6 b 31-32 b 31-32 b 31-32
RL4 /M01.B5
b E9-E7 DIGITAL OUTPUT L7 D14-D13 /G01.D5 LED7 a 41-44 a 41-44 a 41-44
/Q01.B5
a E12-E11 L8 D16-D15 /G01.D5 LED8 b 41-44 b 41-44 b 41-44
RL5 /M02.B7
b E12-E10 L9 B2-B1 /G01.D6 AUX. RELAY AUX. RELAY AUX. RELAY
a E15-E14 L10 B4-B3 /G01.D6
RL6 /Q01.B6
b E15-E13 L11 B6-B5 /G01.D7
a E18-E17 L12 B8-B7 /G01.D8
RL7 /M02.B8
b E18-E16 DIGITAL INPUT
F DIGITAL OUTPUT F

Date 10/03/2017 Project Name Title Tripping Circuit Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 M02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 8
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ES BLOCKING
CB OPEN CB CLOSE ES CLOSE MAGNET DC CONVERTER AC/DC FAIL 50/51/50N/51N A/R INPROGRESS A/R LOCKOUT SILENCE ACK RESET TEST

+S1.B +S1.B
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

CS+ -X2 16 -X2 17


/M01.A8
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

E13 E14
12 14 12 14 42 44 +S1.D 22 24
+S1.B +S1.B +S1.B -F50 +S1.B
-Q921 -Q923 -K50 RL6 -K79
/M02.F2
/D01.C3 11 /D01.C5 11 /M02.E7 41 /M02.E7 21
E15 13 13 13 13
B +S1.D +S1.D +S1.D +S1.D B
12 14 12 14 -S17 14 -S18 14 -S19 14 -S20 14
+S1.B +S1.B
-Q922 -Q924
/D01.C4 11 /D01.C6 11

+S1.B
-X5 30

+S1.B
-X2 22

+S1.B
-X2 18
+S4
-X041
X01:B2

C 3F C
+110VDC +24VDC +24VDC DI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI10 COM0 COM1
3M
INPUT
+S4
-Q51 9 1 +S1.B +S1.B
/M01.E1 S1:3 -H1002 -H1001

PE
S12
+S4
10 2 -Q30 S1:4
/T02.B1
X01:B3

X01:B4

+S4

/T02.C2
-X041 4M
4F -110VDC -24VDC -24VDC PE COM DO0 DO1 DO2 DO3 DO4 DO5 COM2 DO6

+S1.B +S1.B +S1.B +S1.B


D -X2 19 -X2 20 -X5 31 -X2 23 D

+S1.B +S1.B
L11/X2 L12/X2 L21/X2 L22/X2 -X51 1 -X51 2

/T02.D1
+S1.D PREVIOUS +S1.B +S1.B NEXT
-H100 L11 L12 L21 L22 CUBICLE -X51 3 -X51 4 CUBICLE

X1

A1 L11: AC/DC SUPPLY FAIL


+S1.B
-K30 L12: OCR & EF FAIL
/Q01.E3 L21: AUTO RECLOSE IN PROGRESS
A2
-K30 L22: AUTO RECLOSE LOCKOUT
E E
a 11-14
/Q06.D5
X1 X1 X1 b 11-12
+S1.D +S1.D +S1.D a 21-24
-H52 -H51 -H30 /Q07.D4
b 21-22
GREEN X2 RED X2 RED X2 a 31-34
b 31-32
a 41-44
b 41-44

+S1.B +S1.B AUX. RELAY


-X2 13 -X2 14
/M01.E8
F F

Date 10/03/2017 Project Name Title Local Control Indication Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 Q01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 9
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

UNDER FREQUENCY
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B
-X51 5 81U1+ -X51 6

+S1.B +S1.B
-X51 7 81U2+ -X51 8
PREVIOUS +S1.B +S1.B NEXT
CUBICLE -X51 9 81U3+ -X51 10 CUBICLE
+S1.B +S1.B
-X51 11 81U4+ -X51 12

B B

04(STEP 4)
01(STEP 1)
02(STEP 2)
03(STEP 3)
0 (OFF)
1 5 3 7
+S1.D
-S681
/Q02.C3 2 6 4 8

-S681
a 1-2
a 3-4
/Q02.C3
C a 5-6 C
a 7-8
a 9-10
a 11-12
a 13-14
a 15-16

D D

+S1.B A1
-K81
/Q02.E3
A2

+S1.B +S1.B
E PREVIOUS -X51 13 TR- -X51 14 NEXT E
CUBICLE CUBICLE
-K81
a 11-14
/M02.C5
b 11-12
a 21-24
/M01.C6
b 21-22
a 31-34
/Q06.D3
b 31-32
a 41-44
b 41-44
AUX. RELAY
F F

Date 10/03/2017 Project Name Title Local Control Indication Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 Q02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 10
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

50BF TRIP 50BF TRIP


TO INCOMING TO BUS SECTION
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B
-X51 15 50BF1 -X51 16
PREVIOUS +S1.B +S1.B NEXT
CUBICLE -X51 19 50BF2 -X51 20 CUBICLE

B B

C C

22 24 32 34
+S1.B +S1.B
-K50BF -K50BF
/M02.E8 21 /M02.E8 31

D D

+S1.B +S1.B
E -X51 21 50BF2 -X51 22 E
PREVIOUS +S1.B +S1.B NEXT
CUBICLE -X51 17 50BF1 -X51 18 CUBICLE

F F

Date 10/03/2017 Project Name Title Spare Contacts Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 Q03
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 11
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CIRCUIT BREAKER INSTANTANEOUS SPRING CHARGE CB PLUG PROT. RELAY


AUX. CONTACT AUX. CONTACT IN/OUT SPARE CONTACT
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X5 11 -X5 17 -X5 19 -X5 21 -X5 24 -X5 26 -X5 48 -X5 64 -X5 66
B B

X01:C1

X01:A10

X01:A7

X01:B15

X01:D15
X01:C11
C C

1 +S4
+S4 S41 +S4 F11 B13 B14 B16 B17
-Q51 13
-Q51 3 15 5 11 -Q51 +S1.D +S1.D
/M01.E2 S2 /M01.E2 +S1.D
S11 S12 2 S2 -F50 -F50
-F50 WD RL10 RL11
9 14 /M02.E2 /M02.E3 /M02.E3
4 16 S11 6 12

10 F12 B15 B18


X01:C12

X01:D16
X01:B16
X01:A11

X01:A8

X01:A9
X01:C2

D D

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X5 12 -X5 18 -X5 20 -X5 22 23 -X5 25 -X5 27 -X5 49 -X5 65 -X5 67

E E

Spare Terminal Block


+S1.B +S1.B +S1.B +S1.B +S1.B
-X1 4 -X2 1 -X5 77 -X5 86 -X5 91
-X2 2 -X5 78 -X5 87 -X5 92
-X2 3 -X5 79 -X5 88 -X5 93
-X2 21 -X5 80 -X5 89
-X2 25 -X5 83 -X5 90

F F

Date 10/03/2017 Project Name Title Spare Contacts Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 Q04
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 12
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB POSITION
TEST / SERVICE
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B +S1.B +S1.B


-X5 52 -X5 54 -X5 56 -X5 58
B B

+S4 1F +S4 3F +S4 5F +S4 7F


-X052 -X052 -X052 -X052
C 1M 3M 5M 7M C

1 1 1 1
+S4 +S4 +S4 +S4
-ST3 -ST4 -SS3 -SS4
2 2 2 2

+S4 +S4 +S4 +S4


-X052 2M -X052 4M -X052 6M -X052 8M

2F 4F 6F 8F

D D

+S1.B +S1.B +S1.B +S1.B


-X5 53 -X5 55 -X5 57 -X5 59

E E

F F

Date 10/03/2017 Project Name Title Spare Contacts Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 Q05
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 13
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

OCR & EF FAIL UNDER FREQUENCY CIRCUIT BREAKER EARTHING SWITCH AC/DC SUPPLY OCR & EF
TRIP INDICATION SPARE CONTACT OPEN CLOSE CLOSE FAIL FAIL
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

=HV Side 150 kV


-Xx -Xx -Xx -Xx

=RCP
xx xx xx xx

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X5 44 -X5 46 -X5 8 -X5 50 -X5 72 -X5 73
B B

C C

X01:A15
+S4
-Q51 15 7
12 14 32 34 /M01.E1 12 14 92 94 92 94 92 94 92 94 32 34
+S1.B +S1.B S11 +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-K50 -K81 -K30 -Q921 -Q922 -Q923 -Q924 -K50
/M02.E7 /Q02.F3 16 8 /Q01.E4 /D01.C3
11 31 11 91 /D01.C4 91 /D01.C5 91 /D01.C6 91 /M02.E7 31

X01:A16

X01:B1
D D

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X5 45 -X5 47 -X5 9 -X5 10 -X5 51 -X5 74 -X5 75

E E

-Xx -Xx -Xx -Xx -Xx -Xx


=HV Side 150 kV

xx xx xx xx xx xx
=RCP

F F

Date 10/03/2017 Project Name Title Spare Contacts Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 Q06
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 14
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CIRCUIT BREAKER EARTHING SWITCH OCR & EF PROTECTION AUTO RECLOSE STATUS
OPEN CLOSE TEST SERVICE OPEN CLOSE FAIL FAIL OFF ON
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

=Scada
-Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


B -X6 1 -X6 4 -X6 7 -X6 10 -X6 12 -X6 14 B

1 4 7 10 12 14

+S1.B +S1.B +S1.B +S1.B


13 -X5 15 -X5 36 -X5 40 -X5 28

C +S4 +S4 +S4 C


-X051 1F -X051 5F -X041 1F
1M 5M 1M
X01:C9
X01:B5

F13

OFF
ON
+S1.D +S1.D 5 7
+S4 1 1 S1:1 22 24 22 24
-F50 WD -S679
+S4 +S1.B +S1.B /M02.E2 /G01.E2
-Q51 11 5 +S4
/M01.F1 -SS1 +S4 -K30 -K50 OFF 6 ON 8
S12 S12 -ST1
2 2 -Q30 S1:2/Q01.E4 21 /M02.E7 21 F14
12 6 /T02.B1
X01:C10

+S4 +S4 +S4


X01:B6

-X051 2M -X051 6M -X041 2M


2F 6F 2F
D D

+S1.B +S1.B +S1.B +S1.B


14 -X5 16 -X5 37 -X5 41 -X5 29

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-X6 2 -X6 3 -X6 5 -X6 6 -X6 8 -X6 9 -X6 11 -X6 13 -X6 15 -X6 16

2 3 5 6 8 9 11 13 15 16

E E

-Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx
=Scada

F F

Date 10/03/2017 Project Name Title To Scada Drawing Nr. =Outgoing


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 Q07
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 15
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SERIAL LINK COMMUNICATION


DIGITAL ENERGY METER
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.D RS485
-P50

GND SH- SH+

B B
+S1.B +S1.B
-X61 1 COM+ COM+ -X61 2

+S1.B +S1.B
PREVIOUS -X61 3 COM- COM- -X61 4 NEXT
CUBICLE +S1.B +S1.B
CUBICLE
-X61 5 GND GND -X61 6

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Communication Drawing Nr. =Outgoing


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 S01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 16
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CURRENT TRANSFORMER
PROTECTION MEASUREMENT

L1 L2 L3
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

+S4 +S4 +S4 +S4 +S4 +S4


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A -T51L1 -T51L2 -T51L3 -T51L1 -T51L2 -T51L3 A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

P1 P2

P1 P2 TO VOLTAGE
CIRCUIT
P1 P2

1S1

1S1

1S1

2S1

2S1

2S1
1S2

1S3

1S2

1S3

1S2

1S3

2S2

2S3

2S2

2S3

2S2

2S3
B B

/T02.D1

/T02.C1
+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
1 -X3 2 -X3 3 -X3 4 5 6 7 8 9 10 -X3 11 -X3 12 -X3 13 -X3 14 15 16 17 18 19 20

C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 C
+S1.D +S1.D
-XA1 -XA2
2 4 6 8 2 4 6 8

CTT CTT

1 3 5 7 1 3 5 7

C1 C3 C4 C6 C7 C9 C10 C12 I11 I21 I31


+S1.D 5A 1A 5A 1A 5A 1A 5A 1A +S1.D
D -F50 -P50 D

C2 C5 C8 C11 I12 I22 I32


OFF

L1 L2 L3
R
Y
B

+S1.D
-S611

A1 A2
E E

1
+S1.D
-P11 A
2

F F

Date 10/03/2017 Project Name Title Current Circuit Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 T01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 17
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EARTHING SWITCH VOLTAGE INDICATOR


MEASUREMENT PROTECTION RELAY
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

FROM CURRENT
CIRCUIT

+S4 +S4
+S4 +S4
-Q30
-C1L1 -C1L2 -C1L3

C C C

B B

-Q30 L1 L2 L3
b 1-2 /Q07.D4
+S4
a 3-4 /Q01.D2 -H101
b 5-6 /G01.C5
a 7-8 /G01.C5
PE
AUX. CONTACT

+S4
-PE 1
/M02.C2

/Q01.D4
/T01.C6

C C

+S1.B
-XPE 1 2 3 4 5 6 7

+S4
-PE 3
/T01.C3

/Q01.D5

/M01.E3

/M01.C7

D D
+S1.B +S1.B +S1.B +S1.B
-X41 1 1UR -X41 2 -X41 9 2UR -X41 10

+S1.B +S1.B +S1.B +S1.B


-X41 3 1US -X41 4 -X41 11 2US -X41 12
PREVIOUS +S1.B +S1.B NEXT PREVIOUS +S1.B +S1.B NEXT
CUBICLE -X41 5 1UT -X41 6 CUBICLE CUBICLE -X41 13 2UT -X41 14 CUBICLE
+S1.B +S1.B +S1.B +S1.B
-X41 7 1UN -X41 8 -X41 15 2UN -X41 16

E E

V1 V2 V3 Vref C19 C20 C21 C22

+S1.D +S1.D
-P50 -F50

F F

Date 10/03/2017 Project Name Title Voltage Circuit Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 T02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 18
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 5 ]
Terminal UT 4. [ 6 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X1 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Outgoing +S4 -Q51 :X01:A1 M+ 1 =Outgoing +S1.B -Q922 :2 /M01.B2
=Outgoing +S4 -Q51 :X01:A2 M- 2 =Outgoing +S1.B -Q922 :4 /M01.D2
=Outgoing +S4 -X031 :1F 01P 3 =Outgoing +S1.B -B21 :c /D01.D3
B 4 /Q04.E4 B

=Outgoing +S4 -X031 :2F 01N 5 /D01.F3


=Outgoing +S1.B -Q921 :4 01N 6 =Outgoing +S1.B -H17 :2 /D01.F4

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 19
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 24 ]
Terminal UT 4. [ 25 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X2 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
1 /Q04.E5
2 /Q04.E5
3 /Q04.F5
B =Outgoing +S1.D -F50 RL3:E6 TR+ 4 =Outgoing +S4 -Q51 :X01:A3 /M02.C3 B

=Outgoing +S4 -Q51 :X01:A4 TR- 5 Connection is not unique. /M02.E3


=Outgoing +S4 -Q51 :X01:D11 TR+ 6 /M02.C2
=Outgoing +S1.D -F50 L3:D5 TR+ 7 =Outgoing +S4 -Q51 :X01:B7 /M02.B3
=Outgoing +S4 -Q51 :X01:B8 TR+ 8 =Outgoing +S1.D -S601 O:2 /M02.C3
Connection is not unique. TR+ 9 =Outgoing +S1.D -S650 :13 /G01.A6
Connection is not unique. TR+ 10 =Outgoing +S1.D -F50 RL3:E5 /M02.A6
Connection is not unique. TR+ /M02.A6
C =Outgoing +S4 -Q51 :X01:A5 CS+ 11 =Outgoing +S1.B -K81 :21 /M01.D3 C
=Outgoing +S4 -Q51 :X01:A6 CS- 12 =Outgoing +S1.B -Q924 :4 /M01.E3
=Outgoing +S1.D -H52 :X2 CS- 13 Connection is not unique. /Q01.F2
Connection is not unique. CS- 14 =Outgoing +S1.B -H1002 :-110VDC /Q01.F3
=Outgoing +S1.D -H100 :X1 CS- /Q01.F3
Connection is not unique. CS+ 15 =Outgoing +S1.B -Q924 :2 /M01.A3
Connection is not unique. CS+ 16 =Outgoing +S4 -Q51 :X01:B2 /Q01.A2
=Outgoing +S1.B -H1002 :+110VDC CS+ 17 Connection is not unique. /Q01.A3
=Outgoing +S1.B -H1001 :COM1 CS+ 18 =Outgoing +S1.B -H1001 :COM0 /Q01.C8
D D
=Outgoing +S4 -Q51 :X01:B3 CS+ 19 =Outgoing +S1.D -H52 :X1 /Q01.D2
=Outgoing +S4 -Q51 :X01:B4 CS+ 20 =Outgoing +S1.D -H51 :X1 /Q01.D2
21 /Q04.F5
=Outgoing +S1.B -H1002 :+24VDC 24+ 22 Connection is not unique. /Q01.C3
24+ =Outgoing +S1.B -H1001 :+24VDC /Q01.C3
=Outgoing +S1.B -H1001 :COM 24- 23 =Outgoing +S1.B -H1001 :-24VDC /Q01.D5
24- =Outgoing +S1.B -H1002 :-24VDC /Q01.D5
=Outgoing +S4 -Q51 :X01:D12 #10597 24 /M02.C2
E E
25 /Q04.F5

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 20
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal URTK/S [ 1 - 20 ]
Terminal UT 6. [ 21 - 23 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal UT 6. [ 24 ]
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X3 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Outgoing +S1.D -XA1 :2 CL1 1 =Outgoing +S4 -T51L1 :1S1 /T01.C2
=Outgoing +S1.D -XA1 :4 CL2 2 =Outgoing +S4 -T51L2 :1S1 /T01.C3
=Outgoing +S1.D -XA1 :6 CL3 3 =Outgoing +S4 -T51L3 :1S1 /T01.C3
B =Outgoing +S1.D -XA1 :8 4 =Outgoing +S1.B -XPE :1 /T01.C3 B

CN 5 =Outgoing +S4 -T51L1 :1S2 /T01.C4


CN 6 =Outgoing +S4 -T51L1 :1S3 /T01.C4
CN 7 =Outgoing +S4 -T51L2 :1S2 /T01.C4
CN 8 =Outgoing +S4 -T51L2 :1S3 /T01.C4
CN 9 =Outgoing +S4 -T51L3 :1S2 /T01.C4
CN 10 =Outgoing +S4 -T51L3 :1S3 /T01.C4
=Outgoing +S1.D -XA2 :2 CL1 11 =Outgoing +S4 -T51L1 :2S1 /T01.C4
C =Outgoing +S1.D -XA2 :4 CL2 12 =Outgoing +S4 -T51L2 :2S1 /T01.C5 C
=Outgoing +S1.D -XA2 :6 CL3 13 =Outgoing +S4 -T51L3 :2S1 /T01.C5
=Outgoing +S1.D -XA2 :8 14 =Outgoing +S1.B -XPE :2 /T01.C6
CN 15 =Outgoing +S4 -T51L1 :2S2 /T01.C6
CN 16 =Outgoing +S4 -T51L1 :2S3 /T01.C6
CN 17 =Outgoing +S4 -T51L2 :2S2 /T01.C6
CN 18 =Outgoing +S4 -T51L2 :2S3 /T01.C6
CN 19 =Outgoing +S4 -T51L3 :2S2 /T01.C6
CN 20 =Outgoing +S4 -T51L3 :2S3 /T01.C6
D D
21
22
23
24

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V03
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 21
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 30 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X5 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Outgoing +S1.D -S650 :6 CS+ 1 =Outgoing +S1.B -X5 :60 /M01.B3
=Remote -Xx :xx CS+ /M01.B3
=Remote -Xx :xx CS+ 2 =Outgoing +S1.B -X5 :61 /M01.C3
B CS+ =Outgoing +S1.B -X5 :84 /M01.C3 B

=Outgoing +S1.D -S650 :8 TR+ 3 =Outgoing +S1.B -X5 :62 /M02.B4


=Remote -Xx :xx TR+ /M02.B4
=Remote -Xx :xx TR+ 4 =Outgoing +S1.B -X5 :63 /M02.C4
TR+ =Outgoing +S1.B -X5 :85 /M02.C4
Connection is not unique. TR+ 5 =Outgoing +S4 -Q51 :X01:A12 /G01.B2
=Outgoing +S4 -Q51 :X01:A13 TR+ 6 =Outgoing +S1.D -F50 L5:D10 /G01.C2
=Outgoing +S4 -Q51 :X01:A14 TR+ 7 =Outgoing +S1.D -F50 L1:D2 /G01.C3
C =RCP -Xx :xx CS+ 8 =Outgoing +S4 -Q51 :X01:A15 /Q06.B4 C
=Outgoing +S4 -Q51 :X01:A16 CS+ 9 =RCP -Xx :xx /Q06.E4
=Outgoing +S4 -Q51 :X01:B1 CS+ 10 =RCP -Xx :xx /Q06.E4
=Outgoing +S4 -Q51 :X01:C1 CS+ 11 /Q04.B3
=Outgoing +S4 -Q51 :X01:C2 CS+ 12 /Q04.E3
=Outgoing +S4 -Q51 :X01:B5 CS+ 13 =Outgoing +S1.B -X6 :1 /Q07.C2
CS+ =Outgoing +S1.B -X5 :15 /Q07.C2
=Outgoing +S4 -Q51 :X01:B6 CS+ 14 =Outgoing +S1.B -X6 :2 /Q07.D2
=Outgoing +S4 -Q51 :X01:C9 CS+ 15 =Outgoing +S1.B -X5 :13 /Q07.C2
D D
=Outgoing +S4 -Q51 :X01:C10 CS+ 16 =Outgoing +S1.B -X6 :3 /Q07.D2
=Outgoing +S4 -Q51 :X01:C11 CS+ 17 /Q04.B3
=Outgoing +S4 -Q51 :X01:C12 CS+ 18 /Q04.E3
=Outgoing +S4 -Q51 :X01:A10 CS+ 19 /Q04.B3
=Outgoing +S4 -Q51 :X01:A11 CS+ 20 /Q04.E3
=Outgoing +S4 -Q51 :X01:A7 CS+ 21 /Q04.B4
=Outgoing +S4 -Q51 :X01:A8 CS+ 22 /Q04.E4
=Outgoing +S4 -Q51 :X01:A9 CS+ 23 /Q04.E4
E E
=Outgoing +S4 -Q51 :X01:B15 CS+ 24 /Q04.B4
=Outgoing +S4 -Q51 :X01:B16 CS+ 25 /Q04.E4
=Outgoing +S4 -Q51 :X01:D15 CS+ 26 /Q04.B5
=Outgoing +S4 -Q51 :X01:D16 CS+ 27 /Q04.E5
=Outgoing +S4 -X041 :1F CS+ 28 =Outgoing +S1.B -X6 :7 /Q07.C4
CS+ =Outgoing +S1.B -K30 :24 /Q07.C4
=Outgoing +S4 -X041 :2F CS+ 29 =Outgoing +S1.B -X6 :8 /Q07.D4
=Outgoing +S4 -X041 :3F CS+ 30 Connection is not unique. /Q01.B2
F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V04
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 22
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 31 - 63 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X5 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Outgoing +S4 -X041 :4F CS+ 31 Connection is not unique. /Q01.D2
Connection is not unique. TR+ 32 =Outgoing +S4 -X041 :5F /G01.B5
=Outgoing +S4 -X041 :6F TR+ 33 =Outgoing +S1.D -F50 L7:D14 /G01.C5
B Connection is not unique. TR+ 34 =Outgoing +S4 -X041 :7F /G01.B5 B

=Outgoing +S4 -X041 :8F TR+ 35 =Outgoing +S1.D -F50 L8:D16 /G01.C5
=Outgoing +S4 -X051 :1F CS+ 36 =Outgoing +S1.B -X6 :4 /Q07.C3
CS+ =Outgoing +S1.B -X5 :40 /Q07.C3
=Outgoing +S4 -X051 :2F CS+ 37 =Outgoing +S1.B -X6 :5 /Q07.D3
Connection is not unique. TR+ 38 =Outgoing +S4 -X051 :3F /G01.B3
=Outgoing +S4 -X051 :4F TR+ 39 =Outgoing +S1.D -F50 L2:D4 /G01.C3
=Outgoing +S4 -X051 :5F CS+ 40 =Outgoing +S1.B -X5 :36 /Q07.C3
C =Outgoing +S4 -X051 :6F CS+ 41 =Outgoing +S1.B -X6 :6 /Q07.D3 C
Connection is not unique. TR+ 42 =Outgoing +S4 -X051 :7F /G01.B4
=Outgoing +S4 -X051 :8F TR+ 43 =Outgoing +S1.D -F50 L6:D12 /G01.C4
=HV Side 150 kV -Xx :xx CS+ 44 =Outgoing +S1.B -K50 :14 /Q06.B2
=HV Side 150 kV -Xx :xx CS+ 45 =Outgoing +S1.B -K50 :11 /Q06.E2
CS+ 46 =Outgoing +S1.B -K81 :34 /Q06.B3
CS+ 47 =Outgoing +S1.B -K81 :31 /Q06.E3
=Outgoing +S1.D -F50 WD:F11 CS+ 48 /Q04.B6
=Outgoing +S1.D -F50 WD:F12 CS+ 49 /Q04.E6
D D
=RCP -Xx :xx CS+ 50 =Outgoing +S1.B -K30 :14 /Q06.B5
=RCP -Xx :xx CS+ 51 =Outgoing +S1.B -K30 :11 /Q06.E5
=Outgoing +S4 -X052 :1F CS+ 52 /Q05.B4
=Outgoing +S4 -X052 :2F CS+ 53 /Q05.E4
=Outgoing +S4 -X052 :3F CS+ 54 /Q05.B4
=Outgoing +S4 -X052 :4F CS+ 55 /Q05.E4
=Outgoing +S4 -X052 :5F CS+ 56 /Q05.B5
=Outgoing +S4 -X052 :6F CS+ 57 /Q05.E5
E E
=Outgoing +S4 -X052 :7F CS+ 58 /Q05.B5
=Outgoing +S4 -X052 :8F CS+ 59 /Q05.E5
=Outgoing +S1.D -F50 RL8:B9 CS+ 60 =Outgoing +S1.B -X5 :1 /M01.B4
=Outgoing +S1.D -F50 RL8:B10 CS+ 61 =Outgoing +S1.B -X5 :2 /M01.C4
CS+ =Outgoing +S1.B -X5 :71 /M01.C4
=Outgoing +S1.D -F50 RL9:B11 TR+ 62 =Outgoing +S1.B -X5 :3 /M02.B4
=Outgoing +S1.D -F50 RL9:B12 TR+ 63 =Outgoing +S1.B -X5 :4 /M02.C4
TR+ =Outgoing +S1.B -X5 :82 /M02.C4
F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V04.1
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 23
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 64 - 84 ]
Terminal UT 4. [ 85 - 93 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X5 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Outgoing +S1.D -F50 RL10:B14 CS+ 64 /Q04.B6
=Outgoing +S1.D -F50 RL10:B15 CS+ 65 /Q04.E6
=Outgoing +S1.D -F50 RL11:B17 CS+ 66 /Q04.B7
B =Outgoing +S1.D -F50 RL11:B18 CS+ 67 /Q04.E7 B

TR+ 68 Connection is not unique. /G01.B8


=Outgoing +S1.D -F50 L12:B8 TR+ 69 /G01.C8
=Outgoing +S1.D -S650 :10 CS+ 70 =Supervisory -Xx :xx /M01.B4
=Supervisory -Xx :xx CS+ 71 =Outgoing +S1.B -X5 :61 /M01.C4
=RCP -Xx :xx CS+ 72 Connection is not unique. /Q06.B5
CS+ 73 =Outgoing +S1.B -K50 :34 /Q06.B7
=RCP -Xx :xx CS+ 74 Connection is not unique. /Q06.E5
C =RCP -Xx :xx CS+ 75 =Outgoing +S1.B -K50 :31 /Q06.E7 C
76
77 /Q04.E5
78 /Q04.E5
79 /Q04.F5
80 /Q04.F5
=Outgoing +S1.D -S650 :12 TR+ 81 =Supervisory -Xx :xx /M02.B5
=Supervisory -Xx :xx TR+ 82 =Outgoing +S1.B -X5 :63 /M02.C5
83 /Q04.F5
D D
Connection is not unique. CS+ 84 =Outgoing +S1.B -X5 :2 /M01.C3
=Outgoing +S1.D -S601 O:2 TR+ 85 =Outgoing +S1.B -X5 :4 /M02.C4
TR+ =Outgoing +S1.B -K81 :11 /M02.C4
86 /Q04.E5
87 /Q04.E5
88 /Q04.F5
89 /Q04.F5
90 /Q04.F5
E E
91 /Q04.E5
92 /Q04.E5
93 /Q04.F5

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V04.2
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 24
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal MTK-P/P [ 1 - 16 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X6 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Scada -Xx :xx CS+ 1 =Outgoing +S1.B -X5 :13 /Q07.B2
=Scada -Xx :xx CS+ 2 =Outgoing +S1.B -X5 :14 /Q07.E2
=Scada -Xx :xx CS+ 3 =Outgoing +S1.B -X5 :16 /Q07.E2
B =Scada -Xx :xx CS+ 4 =Outgoing +S1.B -X5 :36 /Q07.B3 B

=Scada -Xx :xx CS+ 5 =Outgoing +S1.B -X5 :37 /Q07.E3


=Scada -Xx :xx CS+ 6 =Outgoing +S1.B -X5 :41 /Q07.E3
=Scada -Xx :xx CS+ 7 =Outgoing +S1.B -X5 :28 /Q07.B4
=Scada -Xx :xx CS+ 8 =Outgoing +S1.B -X5 :29 /Q07.E4
=Scada -Xx :xx CS+ 9 =Outgoing +S1.B -K30 :21 /Q07.E4
=Scada -Xx :xx CS+ 10 =Outgoing +S1.B -K50 :24 /Q07.B5
=Scada -Xx :xx CS+ 11 =Outgoing +S1.B -K50 :21 /Q07.E5
C =Scada -Xx :xx CS+ 12 =Outgoing +S1.D -F50 WD:F13 /Q07.B5 C
=Outgoing +S1.D -F50 WD:F14 CS+ 13 =Scada -Xx :xx /Q07.E5
=Scada -Xx :xx CS+ 14 Connection is not unique. /Q07.B6
=Outgoing +S1.D -S679 M:6 CS+ 15 =Scada -Xx :xx /Q07.E6
=Outgoing +S1.D -S679 A:8 CS+ 16 =Scada -Xx :xx /Q07.E6

D D

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V05
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 25
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 3 ]
Terminal UT 4. [ 4 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X11 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
220V AC SUPPLY (P) P 1 /D01.A2
220V AC SUPPLY (P) P 2 Connection is not unique. /D01.A7
220V AC SUPPLY (N) N 3 /D01.A2
B 220V AC SUPPLY (N) N 4 Connection is not unique. /D01.A7 B

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V06
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 26
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 3 ]
Terminal UT 4. [ 4 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X21 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
110V DC SUPPLY (L+) 110V(+) 1 /D01.A2
110V DC SUPPLY (L+) 110V(+) 2 Connection is not unique. /D01.A7
110V DC SUPPLY (L-) 110V(-) 3 /D01.B2
B 110V DC SUPPLY (L-) 110V(-) 4 Connection is not unique. /D01.B7 B

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V07
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 27
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 15 ]
Terminal UT 4. [ 16 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X41 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
1UR 1 /T02.D3
Connection is not unique. 1UR 2 /T02.D5
1US 3 /T02.D3
B Connection is not unique. 1US 4 /T02.D5 B

1UT 5 /T02.D3
Connection is not unique. 1UT 6 /T02.D5
1UN 7 /T02.E3
Connection is not unique. 1UN 8 /T02.E5
2UR 9 /T02.D6
Connection is not unique. 2UR 10 /T02.D8
2US 11 /T02.D6
C Connection is not unique. 2US 12 /T02.D8 C
2UT 13 /T02.D6
Connection is not unique. 2UT 14 /T02.D8
2UN 15 /T02.E6
Connection is not unique. 2UN 16 /T02.E8

D D

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V08
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 28
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 21 ]
Terminal UT 4. [ 22 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X51 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
CS+ 1 /Q01.D7
CS+ 2 Connection is not unique. /Q01.D8
CS+ 3 /Q01.D7
B CS+ 4 Connection is not unique. /Q01.D8 B

81U1+ 5 /Q02.A2
Connection is not unique. 81U1+ 6 /Q02.A8
81U2+ 7 /Q02.A2
Connection is not unique. 81U2+ 8 /Q02.A8
81U3+ 9 /Q02.B2
Connection is not unique. 81U3+ 10 /Q02.B8
81U4+ 11 /Q02.B2
C Connection is not unique. 81U4+ 12 /Q02.B8 C
TR- 13 /Q02.E2
TR- 14 Connection is not unique. /Q02.E8
50BF1 15 /Q03.B2
50BF1 16 Connection is not unique. /Q03.B8
50BF1 17 /Q03.E2
50BF1 18 Connection is not unique. /Q03.E8
50BF2 19 /Q03.B2
50BF2 20 Connection is not unique. /Q03.B8
D D
50BF2 21 /Q03.E2
50BF2 22 Connection is not unique. /Q03.E8

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V09
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 29
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 11 ]
Terminal UT 4. [ 12 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X61 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Outgoing +S1.D -P50 :SH+ COM+ 1 /S01.B2
=Outgoing +S1.D -P50 :SH+ COM+ 2 /S01.B7
=Outgoing +S1.D -P50 :SH- COM- 3 /S01.B2
B =Outgoing +S1.D -P50 :SH- COM- 4 /S01.B7 B

=Outgoing +S1.D -P50 :GND GND 5 /S01.B2


=Outgoing +S1.D -P50 :GND GND 6 /S01.B7
7
8
9
10
11
C 12 C

D D

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V10
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 30
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal USLKG 5 [ 1 - 7 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-XPE Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
PE 1 =Outgoing +S1.B -X3 :4 /T02.C1
=Outgoing +S1.B -X3 :14 PE 2 =Outgoing +S1.B -H1001 :PE /T02.C1
=Outgoing +S4 -Q51 :PE PE 3 /T02.C1
B PE 4 /T02.C2 B

=Outgoing +S4 -PE :3 PE 7 /T02.C2


=Outgoing +S1.D -F50 :PE PE 5 /T02.C2
=Outgoing +S1.D -P50 :G PE 6 =Outgoing +S1.B -H1002 :PE /T02.C2

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Terminal Plan Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B V11
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 31
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

NOTE :
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

DEVICE
EQUIPMENT DESCRIPTION ENGRAVING
CODE
-F50 FEEDER MANAGE RELAY, MiCOM P142 -F50, FEEDER MANAGE RELAY
-H100 ANNUNCIATOR, IDEC -H100, ANNUNCIATOR
-P11 ANALOG AMPER METER, CROMPTON -P11, AMMETER
B -P50 DIGITAL ENERGI METER, ION8650 -P50, DIGITAL ENERGY METER B
-P11

-H51 LAMP INDICATION FOR CB CLOSE/RED, SCHNEIDER -H51, CB CLOSE INDICATION


-P50
-H52 LAMP INDICATION FOR CB OPEN/GREEN, SCHNEIDER -H52, CB OPEN INDICATION
-H30 LAMP INDICATION FOR ES CLOSE/RED, SCHNEIDER -H30, ES CLOSE INDICATION
-H100
-F50
-S17 SILENCE/HORN STOP PUSH BUTTON -S17, SILENCE
MiCOM P14X

-S18 ACKNOWLEDGE PUSH BUTTON BLACK -S18, ACKNOWLEDGE


TRIP

-S17 -S18 -S19 -S20


C ALARM
C
OUT OF SERVICE

HEALTHY
O I
-S19 RESET PUSH BUTTON BLACK -S19, RESET
C = CLEAR

-S20 TEST LAMP PUSH BUTTON BLACK -S20, TEST LAMP


= READ
= ENTER

C -H30 -H52 -H51

-S601 SELECTOR SWITCH FOR CB OPEN/CLOSE K&N -S601, CB OPEN/CLOSE


-S611 LOCAL/REMOTE SELECTOR SWITCH, K&N -S611, SEL. SWITCH
-XA1 -XA2 -S650 -S601 -S681 -S679 -S611

13

14
1

2
5

17

18
3

15

16
7

19

20
11

12

23

24
9

10

21
5 6 7 8 1

2
3

4
5

6
7

8
9

10
11

12
6

12
5

11
4

10
3

9
2

8
1

7
-S650 LOCAL/REMOTE/SUPERVISORY SELECTOR SWITCH, K&N -S650, LOCAL/REMOTE/SUPERVISORY
CTT CTT 22
25 29 27 31 35 33 13 15
26 30 28 32 36 34

-S679 AUTO RECLOSE SELECTOR SWITCH, K&N -S679, AUTO RECLOSE


37 38 39 40 41 14 16
42

D D
-S681 UNDER FREQUENCY SELECTOR SWITCH, K&N -S681, UNDER FREQUENCY
-XA1 CURRENT TEST BLOCK, YONGSUNG -XA1, CTB FOR PROTECTION
-XA2 CURRENT TEST BLOCK, YONGSUNG -XA2, CTB FOR MEASUREMENT
PIX LV DOOR 1

Height : 710mm
Width : 760mm

E E

F F

Date 10/03/2017 Project Name Title LV Door Layout Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B X01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 32
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

1
-S34
DUCT 65x65 2
-H17 2

-X11 -X21 -X41 -X51 -X61 -X1 -X6

1
-X6

2
-X6

3
-X6

4
-X6

5
-X6

6
-X6

7
-X6

8
-MO27 -X6

16 15 14 13 12 11 10 9

9
-X6

16 15 14 13 12 11 10
1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
-X6
-X6

4 4 16 22 12 6 -X6
-X6
-X6
-X6

B B
DUCT 45x65

-H1001 -H1002 -K30 -K50BF -K81


COMDI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI10

-X2 PE +24VDC -24VDC


44 34 24 14

42 32 22 12
44 34 24 14

42 32 22 12
44 34 24 14

42 32 22 12
44 34 24 14

42 32 22 12
44 34 24 14

42 32 22 12

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A1 A2 A1 A2 A1 A2 A1 A2 A1 A2

25 +24VDC
-24VDC
PE COM0
DO0DO1DO2DO3COM1
DO4DO5COM2
DO6
-110VDC +110VDC
41 31 21 11 41 31 21 11 41 31 21 11 41 31 21 11 41 31 21 11

-K50 -K79

C C
DUCT 65x65

-Q921 -Q922 -Q923 -Q924


-XPE

DUCT 65x65
DUCT 65x65

-X3 94
92 1 3
94
92 1 3
94
92 1 3
94
92 1 3
-XPE
-XPE
-XPE
-XPE
-XPE
-XPE
91 91 91 91
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Cymax
0

-B21
10

0
30 2
1 2 3 4 7 5 6

-MO29

90
THERMOSTAT

40

80
21 22 23 24 50
60 70

®
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

24 11
12 2 4
11
12 2 4
11
12 2 4
11
12 2 4
14 14 14 14

D D
DUCT 65x65
1

PIX LV BOX
Height : 730mm
Width : 800mm

E E
-X5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93

93

F F

Date 10/03/2017 Project Name Title LV Box Layout Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B X02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 33
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BILL OF MATERIALS

Device Designation Description Technical Data Type / Ref. Number Manufacturer References Location Panel Remarks
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-B21 Thermostat 0 to 90 C Deg. Max 250VAC Cymax CYIT-90 Gumsung Controls - +S1.B =Outgoing -
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-H17 Panel Lighting 220V AC, 9 Watt E27 GE - +S1.B =Outgoing -

-H1001 CPU PLC Module FC4A-C16R2C (9Input/7Output) FC4A-C16R2C IDEC - +S1.B =Outgoing -

-H1002 DC-DC Converter PSSR-SC24, 85 - 264VAC / 100 - 370 DC PSSR-SC24 IDEC - +S1.B =Outgoing -

-K30 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Outgoing -

-K50 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Outgoing -

-K50BF Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Outgoing -

B -K79 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Outgoing - B

-K81 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Outgoing -

-Q921 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Outgoing -

-Q921 Miniature Circuit Breaker iC60N , 2P , 6A , DIN Rail Mounting A9F74206 Schneider Electric - +S1.B =Outgoing -

-Q922 Miniature Circuit Breaker iC60N , 2P , 6A , DIN Rail Mounting A9F74206 Schneider Electric - +S1.B =Outgoing -

-Q922 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Outgoing -

-Q923 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Outgoing -

C -Q923 Miniature Circuit Breaker iC60N , 2P , 6A , DIN Rail Mounting A9F74206 Schneider Electric - +S1.B =Outgoing - C

-Q924 Miniature Circuit Breaker iC60N , 2P , 6A , DIN Rail Mounting A9F74206 Schneider Electric - +S1.B =Outgoing -

-Q924 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Outgoing -

-S34 Microswitch 1 COS, Imax 15A, 250VAC Z15G-1307 TEND - +S1.B =Outgoing -

-F50 Protection Relay Micom P142 P142316B6M0468J Schneider Electric - +S1.D =Outgoing -

-H30 Indication Lamp Red, 24-132VAC/DC 50/60HZ ZB5 AVBG4+ZB5 AV043 Schneider Electric - +S1.D =Outgoing -

-H51 Indication Lamp Red, 24-132VAC/DC 50/60HZ ZB5 AVBG4+ZB5 AV043 Schneider Electric - +S1.D =Outgoing -

D -H52 Indication Lamp Green, 24-132VAC/DC 50/60HZ ZB5 AVBG3+ZB5 AV033 Schneider Electric - +S1.D =Outgoing - D
-H100 Annunciator Lamp SLC30N-0104, 4 Windows SLC30N-0104 IDEC - +S1.D =Outgoing -

-P11 Amperemeter 96 x 96mm E244-02AG CROMPTON - +S1.D =Outgoing -

-P50 Energy Meter ION 8600, 3P4W M8650B4C0H5C7B1A Schneider Electric - +S1.D =Outgoing -

-S17 Push Button 1N/O, Color Black XB5-AA21 Schneider Electric - +S1.D =Outgoing -

-S18 Push Button 1N/O, Color Black XB5-AA21 Schneider Electric - +S1.D =Outgoing -

-S19 Push Button 1N/O, Color Black XB5-AA21 Schneider Electric - +S1.D =Outgoing -

-S20 Push Button 1N/O, Color Black XB5-AA21 Schneider Electric - +S1.D =Outgoing -
E E
-S601 CB Control Switch S0 CA10 Series S0-CA10-A714-600 K&N - +S1.D =Outgoing -

-S611 Ampere Selector Switch S0 CA10 Series S0-CA10-A058 K&N - +S1.D =Outgoing -

-S650 Local/Remote/Supervisory Switch S0 CA10 Series S0-CA10-RIF280-FT2 K&N - +S1.D =Outgoing -

-S679 Auto Reclose Switch S0 CA10 Series S0-CA10-A721-600 K&N - +S1.D =Outgoing -

-S681 Under Frequency Switch S0 CA10 Series S0-CA10-A262-620 K&N - +S1.D =Outgoing -

-XA1 Current Test Block 4P, 10A, 250VAC YS CTT-04C / X0140500004 YongSung Electric - +S1.D =Outgoing -

F -XA2 Current Test Block 4P, 10A, 250VAC YS CTT-04C / X0140500004 YongSung Electric - +S1.D =Outgoing - F

Date 10/03/2017 Project Name Title Bill Of Materials Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B Y01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 34
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BILL OF MATERIALS

Device Designation Description Technical Data Type / Ref. Number Manufacturer References Location Panel Remarks
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-C1L1 Capacitive Divider Refer to Component List AMT000155-03 Refer to Component List - +S4 =Outgoing -
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-C1L2 Capacitive Divider Refer to Component List AMT000155-03 Refer to Component List - +S4 =Outgoing -

-C1L3 Capacitive Divider Refer to Component List AMT000155-03 Refer to Component List - +S4 =Outgoing -

-H101 Voltage Indicator 3 Phase L1, L2, L3 - Schneider Electric - +S4 =Outgoing -

-Q30 Earthing Switch Auxiliary Contact EX-7.7M, 2NO + 2NC AMT000157-14 Schneider Electric - +S4 =Outgoing -

-Q51 Vacuum Circuit Breaker - - Schneider Electric - +S4 =Outgoing -

-R11 Heating Resistor Blizzard - DBK - +S4 =Outgoing -

B -SS1 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX - +S4 =Outgoing - B

-SS2 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX - +S4 =Outgoing -

-SS3 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX - +S4 =Outgoing -

-SS4 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX - +S4 =Outgoing -

-ST1 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX - +S4 =Outgoing -

-ST2 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX - +S4 =Outgoing -

-ST3 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX - +S4 =Outgoing -

C -ST4 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX - +S4 =Outgoing - C

-T51L1 2 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 - +S4 =Outgoing -

-T51L2 2 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 - +S4 =Outgoing -

-T51L3 2 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 - +S4 =Outgoing -

D D

E E

F F

Date 10/03/2017 Project Name Title Bill Of Materials Drawing Nr. =Outgoing
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-302 +S1.B Y02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Outgoing Customer Doc. Nr. Sheet 35
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.