1 2 3 4 5 6 7 8

NAME PLATE CUBICLE NO. FACTORY NO.


A . A
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

INCOMING =J07 FI101


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

B B

C C

01 12/07/2017 WD As Manufactured
D D
00 10/03/2017 AF First Issued

Rev N° Date Name Modification

Project Name

GI KAYU AGUNG PROJECT


Owner PT PLN (Persero) Order N° C2030-4020126
E E
Customer PT. INDOKOMAS BUANA PERKASA Switchboard 24kV Switchgear

SCHNEIDER-ELECTRIC INDONESIA Panel =Incoming


EJIP PLOT 4B1-4B2 CIKARANG SELATAN Title
COVER SHEET
BEKASI 17550-JAWA BARAT
Schematic Diagram
Tel : (62-21) 897 02 03 Incoming
PT. SCHNEIDER INDONESIA Fax : (62-21) 897 02 09
Date Name Sign Drawing Nr. X4020126-301
F Drawn 10/03/2017 AF Customer Doc. Nr. A01 F

Checked 10/03/2017 BWP Document Type A Sheet 1

Approved 10/03/2017 DTA Format A3 Scale NTS 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

CONTROL AND MONITORING


FUNCTION LOCAL LOCAL CONTROL REMOTE CONTROL REMARKS

CONTROL -Q51 -Q51 -Q51


BB1

STATUS SIGNAL -Q51,-Q30

-Q51
METERING -P50 (M8650) (kWh,kVARh) M
-P10, (VM)
B -P11, (AM) B
PROTECTION -F50, MiCOM P142 (50/51,50N/51N,27,74,50BF)

P2
CONTROL AND MONITORING

-T51L1-3

TECHNICAL SWITCH DATA


P1
DESIGNATION MANUFACT. TYPE NOMINAL CURRENT BREAKING CURRENT REMARKS

C -Q51 SCHNEIDER HVX24-25-20E 2000A 25kA C


-Q30 SCHNEIDER ES PIX24
-T61L1-3 HSW 1.4A -C1L1-3

-Y8
-Q30 -H101

-T61L1-3
-T61L1-3

TECHNICAL TRANSFORMER DATA


D D
DESIGNATION MANUFACT. TYPE RATIO CORE DATA REMARKS

-T51L1 TRAFINDO CTB 24-2 1000-2000/1-1-1A Class 0.2SFS10, 15VA / Class 5P20, 15VA / Class PX For Protection & Measurement
-T51L2 TRAFINDO CTB 24-2 1000-2000/1-1-1A Class 0.2SFS10, 15VA / Class 5P20, 15VA / Class PX
-T51L3 TRAFINDO CTB 24-2 1000-2000/1-1-1A Class 0.2SFS10, 15VA / Class 5P20, 15VA / Class PX

-T61L1 TRAFINDO VTB 24 20kV/R3 : 100V/R3 : 100V/R3 Class 0.2, 50VA / Class 3P, 30VA For Protection & Measurement
-T61L2 TRAFINDO VTB 24 20kV/R3 : 100V/R3 : 100V/R3 Class 0.2, 50VA / Class 3P, 30VA
-T61L3 TRAFINDO VTB 24 20kV/R3 : 100V/R3 : 100V/R3 Class 0.2, 50VA / Class 3P, 30VA

E E

F F

Date 10/03/2017 Project Name Title Cover Sheet Drawing Nr. =Incoming
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-301 A02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 2
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Revision N° Document Identification


Customer Document Number Drawing Number Sheet Description
Type Designation Sheet name
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

X4020126-301 00 01 =Incoming A01 1 Cover Sheet Schematic Diagram Incoming


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

X4020126-301 00 01 =Incoming A02 2 Cover Sheet Schematic Diagram Incoming


X4020126-301 00 01 =Incoming B01 3 List Of Content Schematic Diagram Incoming
X4020126-301 00 01 =Incoming C01 4 Wiring Specification Schematic Diagram Incoming
X4020126-301 00 01 =Incoming D01 5 AC/DC Supply Schematic Diagram Incoming
X4020126-301 00 01 =Incoming G01 6 Digital Inputs Schematic Diagram Incoming
X4020126-301 00 01 =Incoming M01 7 Closing Circuit Schematic Diagram Incoming
X4020126-301 00 01 =Incoming M02 8 Tripping Circuit Schematic Diagram Incoming

B X4020126-301 00 01 =Incoming Q01 9 Local Control Indication Schematic Diagram Incoming B


X4020126-301 00 01 =Incoming Q02 10 Spare Contacts Schematic Diagram Incoming
X4020126-301 00 01 =Incoming Q03 11 Spare Contacts Schematic Diagram Incoming
X4020126-301 00 01 =Incoming Q04 12 Spare Contacts Schematic Diagram Incoming
X4020126-301 00 01 =Incoming Q05 13 To Scada Schematic Diagram Incoming
X4020126-301 00 01 =Incoming S01 14 Communication Schematic Diagram Incoming
X4020126-301 00 01 =Incoming T01 15 Current Circuit Schematic Diagram Incoming
X4020126-301 00 01 =Incoming T02 16 Voltage Circuit Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V01 17 Terminal Plan Schematic Diagram Incoming
C C
X4020126-301 00 01 =Incoming V02 18 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V03 19 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V04 20 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V05 21 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V05.1 22 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V05.2 23 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V05.3 24 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V06 25 Terminal Plan Schematic Diagram Incoming
D X4020126-301 00 01 =Incoming V07 26 Terminal Plan Schematic Diagram Incoming D

X4020126-301 00 01 =Incoming V08 27 Terminal Plan Schematic Diagram Incoming


X4020126-301 00 01 =Incoming V09 28 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V10 29 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V11 30 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming V14 31 Terminal Plan Schematic Diagram Incoming
X4020126-301 00 01 =Incoming X01 32 LV Door Layout Schematic Diagram Incoming
X4020126-301 00 01 =Incoming X02 33 LV Box Layout Schematic Diagram Incoming

E X4020126-301 00 01 =Incoming Y01 34 Bill Of Materials Schematic Diagram Incoming E


X4020126-301 00 01 =Incoming Y02 35 Bill Of Materials Schematic Diagram Incoming

F F

Date 10/03/2017 Project Name Title List Of Content Drawing Nr. =Incoming
01 As Manufactured 12/07/2017 WD Drawn AF GI KAYU AGUNG PROJECT Schematic Diagram
X4020126-301 B01
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 3
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SWITCHES CONTACTS AND COIL PASSIVE COMPONENTS FUSE PHASE POLARITY COLOUR CODE (MARKER)
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A Description Symbol Description Symbol Description Symbol Description Symbol Circuit Wire Size Marker A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

VT L1 Red
CHANGE-OVER L2 Yellow
BREAK BEFORE Black 2.5 sqmm
THERMOSTAT OR RESISTOR FUSE L3 Black
MAKE CONTACT
N Blue

IEC S00264 IEC S00230 IEC S00555 IEC S00362 CT L1 Red


L2 Yellow
Black 4 sqmm
L3 Black
MV CIRCUIT BREAKER
In Rack Out Position NORMALLY OPEN RESISTOR FUSE ISOLATOR N Blue
For Position Switch Adjustable
AC 3-Phase L1 Red
B IEC S00287 IEC S00259 IEC S00557 IEC S00369 L2 Yellow B
Black 2.5 sqmm
L3 Black

1 N Blue
MINIATURE CIRCUIT
BREAKER NORMALLY CLOSE DIODE TRANSFORMER
For Position Switch AC 1-Phase L Red
2 (For Control) Black 1.5 sqmm
N Blue
IEC S00287 & S00191 IEC S00260 IEC S00641 Description Symbol
DC Positive Brown
REMOTE

(For Control) Black 1.5 sqmm


LOCAL

Negative White
P1 P2
LOCAL REMOTE DISCONNECTOR LED CURRENT Communication Cable Positive Green -
SWITCH WITH KEY Off Load Isolating Switch Light Emitting Diode TRANSFORMER (MODBUS / RS485) Negative White 0.33 sqmm -

S1

S2
IEC S00480 & S00179 IEC S00288 IEC S00642 IEC S01344 Ground Silver -

C A N Grounding Green/Yellow 2.5 sqmm - C


CLOSE
TRIP

CB CONTROL SWITCH Wirring Specification


Spring Return to Center DISCONNECTOR SPACE HEATER VOLTAGE
PE - Multistranded flexible copper conductor type : NYAF
On Load Isolating Switch TRANSFORMER
-PVC insulation
a n
-Rated voltage: 750 Volt
IEC S00249 IEC S00290 IEC S00566 IEC S00842
-Dielectric test voltage 50Hz, 1 sec = 1000 Volt

ASSIGNMENT ADDRESS
OFF

GROUNDING AND TERMINATION


2
3
4
5
1

MULTI STEP CONTACTOR CAPACITIVE


WITH OFF DIVIDER
C Location Designation
IEC S00272 IEC S00218 IEC S00566 Description Symbol
+S1.B LV Box Compartment
+S1.D Door Compartment
VPIS +S2 CB Compartment
D EMERGENCY ON DELAY LED Voltage Indicator EARTH / GROUND D
STOP CONTACT +S4 Cable connection compartment
IEC S00258 IEC S00243 IEC S00200
TERMINAL WIRING CODE

PUSH BUTTON OFF DELAY LAMP AND INDICATION TERMINAL BLOCK Terminal Designation
CONTACT
-X1 AC Supply For Internal Wiring
IEC S00254 IEC S00244 Description Symbol IEC S00017 -X2 DC Supply For Internal Wiring
1 -X3 Current Circuit Wiring
-X4 Voltage Circuit Wiring
CONTACTS AND COIL RELAY COIL LAMP INDICATION CONNECTING LINK
TERMINAL BLOCK -X5 Spare Contact & To External
E 2 E
Description Symbol IEC S00305 IEC S00965 IEC S00044 -X6 Output Contact to SCADA/PLC
-X7 Aux. Contact For Internal Wiring
BUZZER
1 1 -X11 Interconnection Wiring For AC Control Circuit
IEC S00973
NORMALLY OPEN TIMER OFF DELAY OR ARRESTER -X21 Interconnection Wiring For DC Control Circuit
( NO ) CONTACT RELAY COIL HORN 2 2 -X31 Interconnection Wiring For Current Circuit
IEC S00227 IEC S00311 IEC S00969 Description Symbol
-X41 Interconnection Wiring For Voltage Circuit
-X51 Interconnection Wiring for Interpanel
NORMALLY CLOSE TIMER ON DELAY SEMAPHORE SURGE ARRESTER -X61 Communication Wiring
( NC ) CONTACT RELAY COIL INDICATOR
All devices shown in this diagram are in open position, drawn out (test),
F IEC S00229 IEC S00312 IEC S00968 IEC S00373 with operating mechanism discharged and all power source off. F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Wiring Specification
X4020126-301 C01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 4
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

HEATER LIGHTING MOTOR DRIVE TRIPPING CIRCUIT CONTROL CIRCUIT


All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

+S1.B +S1.B
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A -X11 1 220V AC SUPPLY (P) -X11 2 A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B
-X11 3 220V AC SUPPLY (N) -X11 4
PREVIOUS +S1.B +S1.B NEXT
CUBICLE -X21 1 110V DC SUPPLY (L+) -X21 2 CUBICLE
+S1.B +S1.B
-X21 3 110V DC SUPPLY (L-) -X21 4

B B

+S1.B 1 3 +S1.B 1 3 +S1.B 1 3 +S1.B 1 3


-Q921 -Q922 -Q923 -Q924
2 4 2 4 2 4 2 4
-Q921 -Q922 -Q923 -Q924
a 11-14 a 11-14 a 11-14 a 11-14
/Q01.B4 /Q01.B4 /Q01.B5 /Q01.B5
b 11-12 b 11-12 b 11-12 b 11-12
a 91-94 a 91-94 a 91-94 a 91-94
/Q04.D6 /Q04.D7 /Q04.D7 /Q04.D7
C b 91-92 b 91-92 b 91-92 b 91-92 C
AUX. CONTACT AUX. CONTACT AUX. CONTACT AUX. CONTACT

1 1
+S1.B
-B21 >ϑ -S34
c 2

D D

+S1.B
-X1 3

+S4
-X031 1F
1M

1 1

CS+
TR+

CS-
TR-
M+

M-
+S4 +S1.B
PE
-R11 -H17
E E
2 2
+S4
/M01.A1

/M01.E1

/G01.A1

/G01.E1

/M01.A1

/M01.E1
-X031 2M
2F

+S1.B +S1.B
-X1 5 -X1 6

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT AC/DC Supply
X4020126-301 D01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 5
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB OPEN CB CLOSE CB TEST CB SERVICE EARTHING SWITCH EARTHING SWITCH SWITCH POSITION AUX. MCB VT SUPPLY DIGITAL INPUT
POSITION POSITION OPEN CLOSE LOCAL REMOTE SUPERVISORY (SPARE)
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

+S1.B
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A TR+ -X2 9 A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

/D01.E6 /M02.A1

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X5 5 -X5 38 -X5 42 -X5 48 -X5 50 -X5 68

+S4 +S4 +S4 +S4


-X051 3F -X051 7F -X042 5F -X042 7F
B 3M 7M 5M 7M B
X01:A12

SUPERVISORY
+S1.D

REMOTE
+S4 -S650

LOCAL
-Q51 13 5 13 15 17
/M01.E1 1 1 S1:13 S1:15 /M01.F3 12 14 12 14
S11 +S4 +S1.B +S1.B
+S4 +S4 +S4
-SS2 -Q941 -Q942
14 6 -ST2 -Q30 -Q30 /T02.D3 /T02.D6
2 2 S1:14 S1:16 L 14 R 16 S 18 11 11
/T02.B1 /T02.C1
X01:A13

X01:A14

+S4 +S4 +S4 +S4


-X051 4M -X051 8M -X042 6M -X042 8M
4F 8F 6F 8F

C C

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X5 6 -X5 7 -X5 39 -X5 43 -X5 49 -X5 51 -X5 69

+ D2 + D4 + D8 + D10 + D12 + D14 + D16 + B2 + B4 + B6 + B8


D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D +S1.D D
-F50 L1 -F50 L2 -F50 L4 -F50 L5 -F50 L6 -F50 L7 -F50 L8 L9 -F50 L10 -F50 L11 -F50 L12
/M02.E4 /M02.E4 /M02.E4 /M02.E4 /M02.E4 /M02.E4 /M02.E4 /M02.F4 /M02.F4 /M02.F4

- D1 - D3 - D7 - D9 - D11 - D13 - D15 - B1 - B3 - B5 - B7

E E
TR-
/D01.E6 /M02.E1

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Digital Inputs
X4020126-301 G01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 6
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPRING CHARGE CB CLOSE INTERLOCKING DIGITAL


MOTOR LOCAL REMOTE SUPERVISORY ENERGY METER
+S1.B
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

CS+ -X2 15 CS+


/D01.E7 /Q01.A1
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

M+

SUPERVISORY
/D01.E5
+S1.D +S1.B +S1.B

REMOTE
-S650 -X51 -X51

LOCAL
5 6
/M01.E3 1 5 9
E7 E8 (*)
+S1.D -Xx xx -X51 11
L 2 R 6 S 10 -F50 RL4 (*) Note :

=Incoming External
/M02.E2
Remove Jumper Wire If Used
74

=Bus Coupler
E9

+S1.B +S1.B +S1.B -Xx xx -X51 11


B -X5 1 -X5 60 -X5 70 B
+S1.B
-X1 1 +S1.B +S1.B
+S1.B
12 14 -X51 7 -X51 8
-K86 +S1.B
-Xx xx -Xx xx /M02.E7 11 -X5 72

CLOSE
B9

OPEN

=Supervisory
+S1.D 3 +S1.D
-S601 -F50 RL8 -Xx

=Remote
X01:A1

/M02.E3 xx
/M01.C2
C 4
-Xx B10 -Xx

=HV Side 150 kV


xx xx 12 14
+S1.B
+S4 -S601
-Q51 U1
-K861 + L/+
a 1-2 /M02.B3 /M02.E8 11 +S1.D
/M01.E1 M1 +S1.B +S1.B +S1.B
-P50 G
C M a 3-4 /M01.C2 -X5 2 -X5 61 -X5 71 -Xx xx C
U2 +S1.B
-X5 88 - N/-
+S1.B
-X5 73
X01:A2

+S1.B

/T02.D2
-X2 11

+S1.B
-X1 2
X01:A5

+S4
D -Q51 D
/M01.E1 F2 C1

C2
X01:A6

PE

/T02.D1
M-
/D01.E5
+S1.B
CS- -X2 12 CS-
/D01.E7 /Q01.F1

E -Q51 -Q51 -S650 E


a A12-A14 a B13-B14 /Q02.C3 b 1-2 /M01.A2
/G01.B2
b A12-A13 b A10-A11 /Q02.C4 b 3-4 /M02.A3
a A15-B1 MICRO SWITCH BY PB a 5-6 /M01.B3
/Q04.C5
b A15-A16 a 7-8 /M02.B3
a B2-B4 -Q51 a 9-10 /M01.B3
/Q01.C1
b B2-B3 a A7-A9 a 11-12 /M02.B4
b B5-B6 /Q04.C1 b A7-A8 b 13-14 /G01.B5
a B7-B8 /M02.B2 a B15-B16 /Q02.C2 a 15-16 /G01.C6
b B9-B10 a D15-D16 /Q02.C3 a 17-18 /G01.C6
b C9-C10 /Q02.C2 MICRO S. FOR MOTOR CTRL
a C11-C12 /Q04.C1
F AUX. SWITCH POS. IND. F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Closing Circuit
X4020126-301 M01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 7
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PROTECTION RELAY CB OPEN 50/51,50N/51N EXTERNAL 50BF 50/51,50N/51N EXTERNAL


SUPPLY 74 LOCAL REMOTE SUPERVISORY 27 TRIP TRIP & LOCK OUT TRIP
+S1.B
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

TR+ -X2 10
/G01.A8
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

SUPERVISORY
+ D6 +S1.D

REMOTE
+S1.D -S650

LOCAL
E3
-F50 L3 /M01.E3 3 7 11 +S1.D
/M02.E4
-F50 RL2
/M02.E2
- D5
L 4 R 8 S 12
E4

+S1.B
-X2 7 +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-X5 3 -X5 62 -X5 110 -X5 74 -X51 15 -X51 16 -X5 76
B B

X01:B7
-Xx xx -Xx xx -Xx xx -X51 15 16 -X51 15 16 -Xx xx

CLOSE
B11 E5

OPEN

=Supervisory
+S4 +S1.D 1 +S1.D +S1.D 22 24
-Q51 -F50 -F50 +S1.B

=Outgoing

=Outgoing
3 -S601 RL9 RL3

=Remote

=External

=External
/M01.F1 S12 /M02.E3 /M02.E2 -K861
/M01.C2 /M02.E8
O 2 21
4 B12 E6
-Xx xx -Xx xx -Xx xx -X51 17 18 -X51 17 18 -Xx xx

+ F2
X01:B8

+S1.D +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-F50 PE
-X5 4 -X5 63 -X5 111 -X5 75 -X51 17 -X51 18 -X5 77

+S1.B
- F1 -X5 89
C +S1.B C
-X2 8
/T02.C2

+S1.B
-X2 6 24 4
X01:D11

X01:D12

X01:A3

+S4
-Q51 13 1
/M01.E1 S12 S11
D 14 2 D
C1 A1 A1
+S1.B +S1.B
F11 -K86 -K861
C2 /M02.E7 /M02.E8
A2 A2

X01:A4

+S1.B
-X2 5
TR-
/G01.E8
ASSIGNMENT -F50 ASSIGNMENT -F50 ASSIGNMENT -F50 ASSIGNMENT -F50 -K86 -K861
WD a F14-F13 /Q05.C5 RL8 a B10-B9 /M01.C3 L1 D2-D1 /G01.D2 LED1 a 11-14 a 11-14
/M01.B5 /M01.C5
E WD b F12-F11 /Q02.C4 RL9 a B12-B11 /M02.B4 L2 D4-D3 /G01.D2 LED2 b 11-12 b 11-12 E
RL1 a E2-E1 /Q04.D3 a B15-B14 L3 D6-D5 /M02.B2 LED3 a 21-24 a 21-24
RL10 /Q02.C5 /Q01.B5 /M02.C5
RL2 a E4-E3 /M02.B7 b B15-B13 L4 D8-D7 /G01.D3 LED4 b 21-22 b 21-22
RL3 a E6-E5 /M02.B5 a B18-B17 L5 D10-D9 /G01.D3 LED5 a 31-34 a 31-34
RL11 /Q02.C5 /Q04.D8
a E9-E8 b B18-B16 L6 D12-D11 /G01.D4 LED6 b 31-32 b 31-32
RL4 /M01.B5
b E9-E7 DIGITAL OUTPUT L7 D14-D13 /G01.D5 LED7 a 41-44 a 41-44
/Q05.C5
a E12-E11 L8 D16-D15 /G01.D5 LED8 b 41-44 b 41-44
RL5 /Q01.B6
b E12-E10 L9 B2-B1 /G01.D6 AUX. RELAY AUX. RELAY
a E15-E14 L10 B4-B3 /G01.D6
RL6 /Q04.D2
b E15-E13 L11 B6-B5 /G01.D7
a E18-E17 L12 B8-B7 /G01.D8
RL7 /Q05.C6
b E18-E16 DIGITAL INPUT
F DIGITAL OUTPUT F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Tripping Circuit
X4020126-301 M02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 8
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ES BLOCKING
CB OPEN CB CLOSE ES CLOSE MAGNET DC CONVERTER AC/DC FAIL 50/51/50N/51N 50BF SPARE SILENCE ACK RESET TEST

+S1.B +S1.B
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

CS+ -X2 16 -X2 17


/M01.A8
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B
-X5 78 -X5 79

-Xx xx 12 14 12 14 22 24 E10 E11


+S1.B +S1.B +S1.B

=HV Side 150 kV


-Q921 -Q923 -K86 +S1.D
/D01.C3 11 /D01.C5 11 /M02.E7 -F50
21 /M02.F2 RL5
13 13 13 13
B E12 +S1.D +S1.D +S1.D +S1.D B
-Xx xx 12 14 12 14 -S17 14 -S18 14 -S19 14 -S20 14
+S1.B +S1.B
-Q922 -Q924 +S1.B
/D01.C4 11 /D01.C6 11 -X5 80

+S1.B +S1.B
-X5 30 -X5 28

+S1.B
-X2 22

+S1.B
-X2 18
+S4 +S4
-X041 -X041
X01:B2

C 3F 1F C
+110VDC +24VDC +24VDC DI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI10 COM0 COM1
3M 1M
INPUT
+S4
-Q51 9 1 +S1.B +S1.B
/M01.E1 S1:3 S1:1 -H1002 -H1001

PE
S12
+S4 +S4
10 2 -Q30 -Q30
S1:4 S1:2
/T02.B1 /T02.B1
X01:B3

X01:B4

+S4 +S4

/T02.C2
-X041 4M -X041 2M
4F 2F -110VDC -24VDC -24VDC PE COM DO0 DO1 DO2 DO3 DO4 DO5 COM2 DO6

+S1.B +S1.B +S1.B +S1.B +S1.B


D -X2 19 -X2 20 -X5 31 -X5 29 -X2 23 D

+S1.B +S1.B +S1.B


-X2 21 L11/X2 L12/X2 L21/X2 L22/X2 -X51 1 -X51 2

/T02.D1
+S1.D PREVIOUS +S1.B +S1.B NEXT
-H100 L11 L12 L21 L22 CUBICLE -X51 3 -X51 4 CUBICLE
+S4
-X07 1F
1M
X1

A1 A1 11 L11: AC/DC SUPPLY FAIL


+S1.B +S1.B
-K52 -K51 +S4 L12: OCR & EF FAIL 12 14
/Q01.E4 /Q01.E3 +S1.B
A2 A2 -S81 14 L21: BREAKER FAIL
-K401
-K51 -K52 L22: SPARE -K401 /Q01.E7 11
E E
a 11-14 a 11-14 a 11-14
/Q01.E7
X1 X1 X1 +S4 E1 b 11-12 b 11-12 b 11-12
+S1.D +S1.D +S1.D -Y8 a 21-24 a 21-24 a 21-24
-H52 -H51 -H30 /Q05.C2 /Q05.C2 1
E2 b 21-22 b 21-22 b 21-22 +S1.D +S1.B A1
GREEN X2 RED X2 RED X2 a 31-34 a 31-34 a 31-34 -H74 -K401
+S4
/Q04.D4 /Q04.D3 /Q01.E7
-X07 2M b 31-32 b 31-32 b 31-32 2 A2
2F
a 41-44 a 41-44 a 41-44
b 41-44 b 41-44 b 41-44

+S1.B +S1.B AUX. RELAY AUX. RELAY AUX. RELAY


CS- -X2 13 -X2 14
/M01.E8
F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Local Control Indication
X4020126-301 Q01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 9
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CIRCUIT BREAKER INSTANTANEOUS SPRING CHARGE CB PLUG PROT. RELAY AUX. MCB VT SUPPLY
AUX. CONTACT AUX. CONTACT IN/OUT SPARE CONTACT
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-X5 11 -X5 15 -X5 19 -X5 21 -X5 24 -X5 26 -X5 81 -X5 64 -X5 66 -X5 83
B B
X01:C1

X01:C9

X01:A10

X01:A7

X01:B15

X01:D15
C C

1 +S4
+S4 S41 +S4 F11 B13 B14 B16 B17
-Q51 13
-Q51 3 5 5 11 -Q51 +S1.D +S1.D
/M01.E2 S2 /M01.E2 +S1.D 92 94 92 94
S11 S12 2 S2 -F50 -F50 +S1.B +S1.B
-F50 WD RL10 RL11
9 14 /M02.E2 /M02.E3 /M02.E3 -Q941 -Q942
4 6 S11 6 12 /T02.D3 /T02.D6
91 91
10 F12 B15 B18
X01:C10

X01:D16
X01:B16
X01:A11

X01:A8

X01:A9
X01:C2

D D

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-X5 12 -X5 16 -X5 20 -X5 22 23 -X5 25 -X5 27 -X5 82 -X5 65 -X5 67 -X5 84

E E

Spare Terminal Block

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X1 4 -X2 1 -X5 98 -X5 104 -X5 112 -X5 118
-X2 2 -X5 99 -X5 105 -X5 113 -X5 119
-X2 3 -X5 100 -X5 106 -X5 114 -X5 120
-X2 25 -X5 101 -X5 107 -X5 115
-X5 102 -X5 108 -X5 116
-X5 103 -X5 109 -X5 117

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Spare Contacts
X4020126-301 Q02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 10
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB POSITION
TEST / SERVICE
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.B +S1.B +S1.B +S1.B


-X5 52 -X5 54 -X5 56 -X5 58
B B

+S4 1F +S4 3F +S4 5F +S4 7F


C -X052 -X052 -X052 -X052 C
1M 3M 5M 7M

1 1 1 1
+S4 +S4 +S4 +S4
-ST3 -ST4 -SS3 -SS4
2 2 2 2

+S4 +S4 +S4 +S4


-X052 2M -X052 4M -X052 6M -X052 8M

2F 4F 6F 8F

D D

+S1.B +S1.B +S1.B +S1.B


-X5 53 -X5 55 -X5 57 -X5 59

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Spare Contacts
X4020126-301 Q03
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 11
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB INTERLOCKING ES OPEN OCR & EF FAIL 50BF CB STATUS TO 150kV CIRCUIT BREAKER EARTHING SWITCH AC/DC SUPPLY OCR & EF
INTERLOCK TRIP INDICATION TRIP OPEN CLOSE OPEN CLOSE CLOSE FAIL FAIL
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

=Incoming (Future)

=HV Side 150 kV


=Bus Coupler
-Xx -X51 -Xx -Xx -Xx -Xx -Xx -Xx -Xx

=RCP
xx 6 xx xx xx xx xx xx xx

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-X51 9 -X51 11 -X5 44 -X5 90 -X5 92 -X5 85 -X5 8 -X5 46 -X5 94 -X5 95
B B

+S1.B +S1.B
-X5 13 -X5 17

+S4
C +S4 -X042 3F C
-X042 3M

X01:A15
X01:C11

1F
X01:B5

1M

+S4 E13 E14 E1 +S4


-Q51 11 15 -Q51 15 7
S1:9 +S1.D +S1.D 32 34 32 34 /M01.E1 S1:11 92 94 92 94 92 94 92 94 32 34
/M01.F1 S12 S12 +S1.B +S1.B S11 +S1.B +S1.B +S1.B +S1.B +S1.B
+S4
-F50 RL6 -F50 RL1 +S4
/M02.F2 /M02.E2 -K52 -K51 -Q921 -Q922 -Q923 -Q924 -K86
12 16 -Q30 /Q01.E4 16 8 -Q30
S1:10 31 /Q01.E4 31 S1:12 /D01.C3 91 /D01.C4 91 /D01.C5 91 /D01.C6 91 /M02.E7 31
/T02.B1 /T02.B1
E15 E2

X01:A16
X01:C12

X01:B1
+S4
X01:B6

-X042 2M +S4
2F
-X042 4M
4F
D D

+S1.B +S1.B
-X5 14 -X5 18

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-X51 10 -X51 12 -X5 45 -X5 91 -X5 93 -X5 86 -X5 87 -X5 9 -X5 10 -X5 47 -X5 96 -X5 97

E E
=Incoming (Future)

-Xx -X51 -Xx -Xx -Xx -Xx -Xx -Xx -Xx -Xx -Xx -Xx
=HV Side 150 kV

xx 8 xx xx xx xx xx xx xx xx xx xx
=Bus Coupler

=RCP

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Spare Contacts
X4020126-301 Q04
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 12
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CIRCUIT BREAKER EARTHING SWITCH OCR & EF PROTECTION UNDER


OPEN CLOSE TEST SERVICE OPEN CLOSE FAIL FAIL VOLTAGE
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

=Scada
-Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


B -X6 1 -X6 4 -X6 7 -X6 10 -X6 12 -X6 14 B

1 4 7 10 12 14

+S1.B +S1.B +S1.B +S1.B


-X5 36 -X5 40 -X5 32 -X5 34

+S4 +S4 +S4 +S4


C -X051 1F -X051 5F -X041 5F -X041 7F C
1M 5M 5M 7M

F13 E16 E17


22 24 22 24 1 1 S1:5 S1:7 42 44 +S1.D +S1.D
+S1.B +S1.B +S4 +S1.B -F50 -F50
+S4 +S4 +S4 WD RL7
-K52 -K51 -SS1 -K86 /M02.E2 /M02.F2
/Q01.E4 -ST1 -Q30 -Q30
21 /Q01.E4 21 2 2 S1:6 S1:8 /M02.E7 41
/T02.B1 /T02.B1
F14 E18

+S4 +S4
+S4 +S4 -X041 6M -X041 8M
6F 8F
-X051 2M -X051 6M
2F 6F

+S1.B +S1.B +S1.B +S1.B


D -X5 37 -X5 41 -X5 33 -X5 35 D

+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B


-X6 2 -X6 3 -X6 5 -X6 6 -X6 8 -X6 9 -X6 11 -X6 13 -X6 15

2 3 5 6 8 9 11 13 15

E E

-Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx -Xx xx


=Scada

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT To Scada
X4020126-301 Q05
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 13
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SERIAL LINK COMMUNICATION


DIGITAL ENERGY METER
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

+S1.D RS485
-P50

GND SH- SH+

B B
+S1.B +S1.B
-X61 1 COM+ COM+ -X61 2

+S1.B +S1.B
PREVIOUS -X61 3 COM- COM- -X61 4 NEXT
CUBICLE +S1.B +S1.B
CUBICLE
-X61 5 GND GND -X61 6

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Communication
X4020126-301 S01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 14
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CURRENT TRANSFORMER
DIFF. PROTECTION PROTECTION MEASUREMENT

L1 L2 L3
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

+S4 +S4 +S4 +S4 +S4 +S4 +S4 +S4 +S4


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A -T51L1 -T51L2 -T51L3 -T51L1 -T51L2 -T51L3 -T51L1 -T51L2 -T51L3 A


All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

P2 P1

P2 P1 TO VOLTAGE
CIRCUIT
P2 P1

3S1

3S1

3S1

2S1

2S1

2S1

1S1

1S1

1S1
3S3

3S2

3S3

3S2

3S3

3S2

2S3

2S2

2S3

2S2

2S3

2S2

1S3

1S2

1S3

1S2

1S3

1S2
B B

/T02.C1

/T02.D1

/T02.C1
+S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-X3 21 -X3 22 -X3 23 -X3 24 25 26 27 28 29 30 -X3 11 -X3 12 -X3 13 -X3 14 15 16 17 18 19 20 1 -X3 2 -X3 3 -X3 4 5 6 7 8 9 10

C 21 22 23 24 25 26 27 28 29 30 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 C
(*) (*) (*) +S1.D +S1.D
-XA2 -XA1
2 4 6 8 2 4 6 8

Note (*) :
Remove the jumper link if CTT CTT
Protection device is installed
1 3 5 7 1 3 5 7

C1 C3 C4 C6 C7 C9 C10 C12 I11 I21 I31


D +S1.D 5A D
1A 5A 1A 5A 1A 5A 1A +S1.D
-F50 -P50

C2 C5 C8 C11 I12 I22 I32

OFF
L1 L2 L3

R
Y
B
+S1.D
E -S611 E

A1 A2

1
+S1.D
-P11 A
2

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Current Circuit
X4020126-301 T01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 15
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EARTHING SWITCH VOLTAGE INDICATOR VOLTAGE TRANSFORMER


MEASUREMENT PROTECTION
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

FROM CURRENT
CIRCUIT

-F30L1 -F30L2 -F30L3


+S4 +S4
+S4 +S4
-Q30
-C1L1 -C1L2 -C1L3

-Q30 C C C +S4 +S4 +S4


b 1-2 /Q01.D3 A N A N A N
-T61L1 -T61L2 -T61L3
B a 3-4 /Q01.D2 B
PE PE PE
b 5-6 /Q05.D4
a 7-8 /Q05.D4 L1 L2 L3 a1 n1 a2 n2 a1 n1 a2 n2 a1 n1 a2 n2 +S4
b 9-10 /Q04.D2 -X022 7F
+S4 +S4 +S4 +S4
a 11-12 /Q04.D6 -H101 -X021 1F 4F -X021 2F 5F -X021 3F 6F 7M
b 13-14 /G01.C4 1M 4M 2M 5M 3M 6M /T02.C2
a 15-16 /G01.C5
PE +S4 +S4 +S4
AUX. CONTACT -X022 1F 4F -X022 2F 5F -X022 3F 6F
1M 4M 2M 5M 3M 6M
+S4
-PE 1
/M02.C2

/Q01.D4
/T01.C8

/T01.C3

/T02.B6

C C

+S1.B
-XPE 1 2 3 4 5 6 7 +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B +S1.B
-Q941 -X4 1 -X4 2 -X4 3 -X4 4 5 6 -Q942 -X4 7 -X4 8 -X4 9 -X4 10 11 12
a 11-14 a 11-14
/G01.C7 /G01.C8
b 11-12 b 11-12
+S4 +S1.B +S1.B
-PE 3 a 91-94 1 3 5 7 a 91-94 1 3 5 7
/Q02.C6 -Q941 /Q02.C7 -Q942
/T01.C6

/Q01.D5

/M01.E3

/M01.C8

/T02.D5

/T02.D8

b 91-92 b 91-92

/T02.D2

/T02.D2
AUX. CONTACT 2 4 6 8 AUX. CONTACT 2 4 6 8

+S1.D +S1.D
-XV1 -XV2
D 2 4 6 8 2 4 6 8 D

PTT PTT

1 3 5 7 1 3 5 7
+S1.B +S1.B +S1.B +S1.B
-X41 1 1UR -X41 2 -X41 9 2UR -X41 10

+S1.B +S1.B +S1.B +S1.B


-X41 3 1US -X41 4 -X41 11 2US -X41 12

+S1.B +S1.B +S1.B +S1.B


-X41 5 1UT -X41 6 -X41 13 2UT -X41 14

+S1.B +S1.B +S1.B +S1.B


E -X41 7 1UN -X41 8 -X41 15 2UN -X41 16 E
OFF
RN
RY

YN
YB

R S T N V1 V2 V3 Vref C19 C20 C21 C22


BR

BN

+S1.D +S1.D
+S1.D -P50
-S610 -F50

V1 V2

+S1.D
-P10
17 18
V
F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming S


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Voltage Circuit
X4020126-301 T02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 16
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 5 ]
Terminal UT 4. [ 6 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X1 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Incoming +S4 -Q51 :X01:A1 M+ 1 =Incoming +S1.B -Q922 :2 /M01.B2
=Incoming +S4 -Q51 :X01:A2 M- 2 =Incoming +S1.B -Q922 :4 /M01.D2
HEATER =Incoming +S4 -X031 :1F 01P 3 =Incoming +S1.B -B21 :c /D01.D3
B 4 /Q02.E4 B

=Incoming +S4 -X031 :2F 01N 5 /D01.F3


=Incoming +S1.B -Q921 :4 01N 6 =Incoming +S1.B -H17 :2 /D01.F4

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 17
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 24 ]
Terminal UT 4. [ 25 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X2 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
1 /Q02.E5
2 /Q02.F5
3 /Q02.F5
B =Incoming +S4 -Q51 :X01:A3 TR+ 4 =Incoming +S1.B -X51 :17 /M02.C2 B

=Incoming +S4 -Q51 :X01:A4 TR- 5 Connection is not unique. /M02.E2


=Incoming +S4 -Q51 :X01:D11 TR+ 6 /M02.C2
=Incoming +S1.D -F50 L3:D5 TR+ 7 =Incoming +S4 -Q51 :X01:B7 /M02.B2
=Incoming +S4 -Q51 :X01:B8 TR+ 8 =Incoming +S1.D -S601 O:2 /M02.C2
=Incoming +S1.D -S650 :13 TR+ 9 Connection is not unique. /G01.A6
Connection is not unique. TR+ 10 Connection is not unique. /M02.A7
TR+ =Incoming +S1.B -X51 :15 /M02.A7
C =Incoming +S4 -Q51 :X01:A5 CS+ 11 =Incoming +S1.B -X5 :73 /M01.D3 C
=Incoming +S4 -Q51 :X01:A6 CS- 12 =Incoming +S1.B -Q924 :4 /M01.E3
=Incoming +S1.D -H52 :X2 CS- 13 Connection is not unique. /Q01.F2
Connection is not unique. CS- 14 =Incoming +S1.B -H1002 :-110VDC /Q01.F3
Connection is not unique. CS- /Q01.F3
Connection is not unique. CS+ 15 =Incoming +S1.B -Q924 :2 /M01.A3
Connection is not unique. CS+ 16 =Incoming +S4 -Q51 :X01:B2 /Q01.A2
=Incoming +S1.B -H1002 :+110VDC CS+ 17 Connection is not unique. /Q01.A3
=Incoming +S1.B -H1001 :COM1 CS+ 18 Connection is not unique. /Q01.C8
D D
CS+ =Incoming +S1.B -H1001 :COM0 /Q01.C8
=Incoming +S4 -Q51 :X01:B3 CS+ 19 Connection is not unique. /Q01.D2
=Incoming +S4 -Q51 :X01:B4 CS+ 20 Connection is not unique. /Q01.D2
=Incoming +S4 -X07 :1F CS+ 21 =Incoming +S1.B -X5 :29 /Q01.D3
Connection is not unique. 24+ 22 =Incoming +S1.B -H1001 :+24VDC /Q01.C3
24+ =Incoming +S1.B -H1002 :+24VDC /Q01.C3
=Incoming +S1.B -H1001 :COM 24- 23 =Incoming +S1.B -H1001 :-24VDC /Q01.D5
24- =Incoming +S1.B -H1002 :-24VDC /Q01.D5
E E
=Incoming +S4 -Q51 :X01:D12 #10338 24 /M02.C2
25 /Q02.F5

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 18
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal URTK/S [ 1 - 30 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X3 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Incoming +S1.D -XA1 :2 CL1 1 =Incoming +S4 -T51L1 :1S1 /T01.C7
=Incoming +S1.D -XA1 :4 CL2 2 =Incoming +S4 -T51L2 :1S1 /T01.C7
=Incoming +S1.D -XA1 :6 CL3 3 =Incoming +S4 -T51L3 :1S1 /T01.C7
B =Incoming +S1.D -XA1 :8 4 =Incoming +S1.B -XPE :1 /T01.C8 B

CN 5 =Incoming +S4 -T51L1 :1S2 /T01.C8


CN 6 =Incoming +S4 -T51L1 :1S3 /T01.C8
CN 7 =Incoming +S4 -T51L2 :1S2 /T01.C8
CN 8 =Incoming +S4 -T51L2 :1S3 /T01.C8
CN 9 =Incoming +S4 -T51L3 :1S2 /T01.C8
CN 10 =Incoming +S4 -T51L3 :1S3 /T01.C8
=Incoming +S1.D -XA2 :2 CL1 11 =Incoming +S4 -T51L1 :2S1 /T01.C4
C =Incoming +S1.D -XA2 :4 CL2 12 =Incoming +S4 -T51L2 :2S1 /T01.C5 C
=Incoming +S1.D -XA2 :6 CL3 13 =Incoming +S4 -T51L3 :2S1 /T01.C5
=Incoming +S1.D -XA2 :8 14 =Incoming +S1.B -XPE :1 /T01.C6
CN 15 =Incoming +S4 -T51L1 :2S2 /T01.C6
CN 16 =Incoming +S4 -T51L1 :2S3 /T01.C6
CN 17 =Incoming +S4 -T51L2 :2S2 /T01.C6
CN 18 =Incoming +S4 -T51L2 :2S3 /T01.C6
CN 19 =Incoming +S4 -T51L3 :2S2 /T01.C6
CN 20 =Incoming +S4 -T51L3 :2S3 /T01.C6
D D
CL1 21 =Incoming +S4 -T51L1 :3S3 /T01.C2
CL2 22 =Incoming +S4 -T51L2 :3S3 /T01.C3
CL3 23 =Incoming +S4 -T51L3 :3S3 /T01.C3
PE 24 =Incoming +S1.B -XPE :2 /T01.C3
CN 25 =Incoming +S4 -T51L1 :3S2 /T01.C4
CN 26 =Incoming +S4 -T51L1 :3S1 /T01.C4
CN 27 =Incoming +S4 -T51L2 :3S2 /T01.C4
CN 28 =Incoming +S4 -T51L2 :3S1 /T01.C4
E E
CN 29 =Incoming +S4 -T51L3 :3S2 /T01.C4
CN 30 =Incoming +S4 -T51L3 :3S1 /T01.C4

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V03
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 19
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 11 ]
Terminal UT 4. [ 12 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X4 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Incoming +S4 -X021 :1M 1UR 1 =Incoming +S1.B -Q941 :1 /T02.C4
=Incoming +S4 -X021 :2M 1US 2 =Incoming +S1.B -Q941 :3 /T02.C4
=Incoming +S4 -X021 :3M 1UT 3 =Incoming +S1.B -Q941 :5 /T02.C5
B =Incoming +S4 -X021 :4M 1UN 4 /T02.C5 B

=Incoming +S4 -X021 :5M 1UN 5 =Incoming +S1.B -Q941 :7 /T02.C5


=Incoming +S4 -X021 :6M 6 =Incoming +S1.B -XPE :5 /T02.C5
=Incoming +S4 -X022 :1M 2UR 7 =Incoming +S1.B -Q942 :1 /T02.C6
=Incoming +S4 -X022 :2M 2US 8 =Incoming +S1.B -Q942 :3 /T02.C7
=Incoming +S4 -X022 :3M 2UT 9 =Incoming +S1.B -Q942 :5 /T02.C7
=Incoming +S4 -X022 :4M 2UN 10 /T02.C8
=Incoming +S4 -X022 :5M 2UN 11 =Incoming +S1.B -Q942 :7 /T02.C8
C =Incoming +S4 -X022 :6M 12 =Incoming +S1.B -XPE :6 /T02.C8 C

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V04
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 20
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 32 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X5 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Incoming +S1.D -S650 :6 CS+ 1 =Incoming +S1.B -X5 :60 /M01.B3
=Remote -Xx :xx CS+ /M01.B3
=Remote -Xx :xx CS+ 2 =Incoming +S1.B -X5 :61 /M01.C3
B CS+ =Incoming +S1.B -X5 :88 /M01.C3 B

=Incoming +S1.D -S650 :8 TR+ 3 =Incoming +S1.B -X5 :62 /M02.B3


=Remote -Xx :xx TR+ /M02.B3
=Remote -Xx :xx TR+ 4 =Incoming +S1.B -X5 :63 /M02.C3
TR+ =Incoming +S1.B -X5 :89 /M02.C3
=Incoming +S4 -Q51 :X01:A12 TR+ 5 Connection is not unique. /G01.B2
=Incoming +S4 -Q51 :X01:A13 TR+ 6 =Incoming +S1.D -F50 L1:D2 /G01.C2
=Incoming +S4 -Q51 :X01:A14 TR+ 7 =Incoming +S1.D -F50 L2:D4 /G01.C2
C =RCP -Xx :xx CS+ 8 =Incoming +S4 -Q51 :X01:A15 /Q04.B5 C
=Incoming +S4 -Q51 :X01:A16 CS+ 9 =RCP -Xx :xx /Q04.E5
=Incoming +S4 -Q51 :X01:B1 CS+ 10 =RCP -Xx :xx /Q04.E5
=Incoming +S4 -Q51 :X01:C1 CS+ 11 /Q02.B2
=Incoming +S4 -Q51 :X01:C2 CS+ 12 /Q02.E2
=Incoming +S4 -Q51 :X01:B5 CS+ 13 =Incoming +S1.B -X51 :9 /Q04.B1
=Incoming +S4 -Q51 :X01:B6 CS+ 14 =Incoming +S1.B -X51 :10 /Q04.D1
=Incoming +S4 -Q51 :X01:C9 CS+ 15 /Q02.B2
=Incoming +S4 -Q51 :X01:C10 CS+ 16 /Q02.E2
D D
=Incoming +S4 -Q51 :X01:C11 CS+ 17 =Incoming +S1.B -X51 :11 /Q04.B2
=Incoming +S4 -Q51 :X01:C12 CS+ 18 =Incoming +S1.B -X51 :12 /Q04.D2
=Incoming +S4 -Q51 :X01:A10 CS+ 19 /Q02.B2
=Incoming +S4 -Q51 :X01:A11 CS+ 20 /Q02.E2
=Incoming +S4 -Q51 :X01:A7 CS+ 21 /Q02.B3
=Incoming +S4 -Q51 :X01:A8 CS+ 22 /Q02.E3
=Incoming +S4 -Q51 :X01:A9 CS+ 23 /Q02.E3
=Incoming +S4 -Q51 :X01:B15 CS+ 24 /Q02.B3
E E
=Incoming +S4 -Q51 :X01:B16 CS+ 25 /Q02.E3
=Incoming +S4 -Q51 :X01:D15 CS+ 26 /Q02.B4
=Incoming +S4 -Q51 :X01:D16 CS+ 27 /Q02.E4
=HV Side 150 kV -Xx :xx CS+ 28 =Incoming +S4 -X041 :1F /Q01.B3
=Incoming +S4 -X041 :2F CS+ 29 =Incoming +S1.B -X2 :21 /Q01.D3
=Incoming +S4 -X041 :3F CS+ 30 Connection is not unique. /Q01.B2
=Incoming +S4 -X041 :4F CS+ 31 =Incoming +S1.D -H30 :X1 /Q01.D2
=Incoming +S4 -X041 :5F CS+ 32 =Incoming +S1.B -X6 :7 /Q05.C4
F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V05
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 21
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 32 - 64 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X5 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
CS+ =Incoming +S1.B -X5 :34 /Q05.C4
=Incoming +S4 -X041 :6F CS+ 33 =Incoming +S1.B -X6 :8 /Q05.D4
=Incoming +S4 -X041 :7F CS+ 34 =Incoming +S1.B -X5 :32 /Q05.C4
B =Incoming +S4 -X041 :8F CS+ 35 =Incoming +S1.B -X6 :9 /Q05.D4 B

=Incoming +S4 -X051 :1F CS+ 36 =Incoming +S1.B -X6 :4 /Q05.C3


CS+ =Incoming +S1.B -X5 :40 /Q05.C3
=Incoming +S4 -X051 :2F CS+ 37 =Incoming +S1.B -X6 :5 /Q05.D3
=Incoming +S4 -X051 :3F TR+ 38 Connection is not unique. /G01.B3
=Incoming +S4 -X051 :4F TR+ 39 =Incoming +S1.D -F50 L4:D8 /G01.C3
=Incoming +S4 -X051 :5F CS+ 40 =Incoming +S1.B -X5 :36 /Q05.C3
=Incoming +S4 -X051 :6F CS+ 41 =Incoming +S1.B -X6 :6 /Q05.D3
C =Incoming +S4 -X051 :7F TR+ 42 Connection is not unique. /G01.B4 C
=Incoming +S4 -X051 :8F TR+ 43 =Incoming +S1.D -F50 L5:D10 /G01.C4
=HV Side 150 kV -Xx :xx CS+ 44 =Incoming +S4 -X042 :1F /Q04.B2
=Incoming +S4 -X042 :2F CS+ 45 =HV Side 150 kV -Xx :xx /Q04.E2
=RCP -Xx :xx CS+ 46 =Incoming +S4 -X042 :3F /Q04.B6
=Incoming +S4 -X042 :4F CS+ 47 =RCP -Xx :xx /Q04.E6
=Incoming +S4 -X042 :5F TR+ 48 Connection is not unique. /G01.B4
=Incoming +S4 -X042 :6F TR+ 49 =Incoming +S1.D -F50 L6:D12 /G01.C4
=Incoming +S4 -X042 :7F TR+ 50 Connection is not unique. /G01.B5
D D
=Incoming +S4 -X042 :8F TR+ 51 =Incoming +S1.D -F50 L7:D14 /G01.C5
=Incoming +S4 -X052 :1F CS+ 52 /Q03.B4
=Incoming +S4 -X052 :2F CS+ 53 /Q03.E4
=Incoming +S4 -X052 :3F CS+ 54 /Q03.B4
=Incoming +S4 -X052 :4F CS+ 55 /Q03.E4
=Incoming +S4 -X052 :5F CS+ 56 /Q03.B5
=Incoming +S4 -X052 :6F CS+ 57 /Q03.E5
=Incoming +S4 -X052 :7F CS+ 58 /Q03.B5
E E
=Incoming +S4 -X052 :8F CS+ 59 /Q03.E5
=Incoming +S1.D -F50 RL8:B9 CS+ 60 =Incoming +S1.B -X5 :1 /M01.B4
=Incoming +S1.D -F50 RL8:B10 CS+ 61 =Incoming +S1.B -X5 :2 /M01.C4
CS+ =Incoming +S1.B -X5 :71 /M01.C4
=Incoming +S1.D -F50 RL9:B11 TR+ 62 =Incoming +S1.B -X5 :3 /M02.B4
=Incoming +S1.D -F50 RL9:B12 TR+ 63 =Incoming +S1.B -X5 :4 /M02.C4
TR+ =Incoming +S1.B -X5 :111 /M02.C4
=Incoming +S1.D -F50 RL10:B14 CS+ 64 /Q02.B5
F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V05.1
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 22
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 65 - 96 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X5 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Incoming +S1.D -F50 RL10:B15 CS+ 65 /Q02.E5
=Incoming +S1.D -F50 RL11:B17 CS+ 66 /Q02.B6
=Incoming +S1.D -F50 RL11:B18 CS+ 67 /Q02.E6
B TR+ 68 Connection is not unique. /G01.B8 B

=Incoming +S1.D -F50 L12:B8 TR+ 69 /G01.C8


=Incoming +S1.D -S650 :10 CS+ 70 =Supervisory -Xx :xx /M01.B4
=Supervisory -Xx :xx CS+ 71 =Incoming +S1.B -X5 :61 /M01.C4
=HV Side 150 kV -Xx :xx CS+ 72 =Incoming +S1.B -X51 :7 /M01.B6
=HV Side 150 kV -Xx :xx CS+ 73 =Incoming +S1.B -X2 :11 /M01.C6
=External -Xx :xx TR+ 74 =Incoming +S1.B -K861 :24 /M02.B6
TR+ =Incoming +S1.B -X51 :15 /M02.B6
C =External -Xx :xx TR+ 75 =Incoming +S1.B -X51 :17 /M02.C6 C
TR+ =Incoming +S1.B -K861 :21 /M02.C6
=External -Xx :xx TR+ 76 Connection is not unique. /M02.B8
=External -Xx :xx TR+ 77 =Incoming +S1.B -K861 :A1 /M02.C8
=HV Side 150 kV -Xx :xx CS+ 78 Connection is not unique. /Q01.B3
Connection is not unique. 24+ 79 /Q01.B6
24+ 80 =Incoming +S1.B -H1001 :DI3 /Q01.B6
=Incoming +S1.D -F50 WD:F11 CS+ 81 /Q02.B5
=Incoming +S1.D -F50 WD:F12 CS+ 82 /Q02.E5
D D
CS+ 83 Connection is not unique. /Q02.B6
CS+ 84 Connection is not unique. /Q02.E6
=HV Side 150 kV -Xx :xx CS+ 85 Connection is not unique. /Q04.B4
=HV Side 150 kV -Xx :xx CS+ 86 =Incoming +S1.B -K52 :31 /Q04.E4
=HV Side 150 kV -Xx :xx CS+ 87 =Incoming +S1.B -K51 :31 /Q04.E4
=Incoming +S1.D -S601 C:4 CS+ 88 =Incoming +S1.B -X5 :2 /M01.C3
=Incoming +S1.D -F50 RL4:E7 CS+ /M01.C3
=Incoming +S1.D -F50 RL3:E6 TR+ 89 =Incoming +S1.B -X5 :4 /M02.C3
E E
=Incoming +S1.D -S601 O:2 TR+ /M02.C3
=HV Side 150 kV -Xx :xx CS+ 90 =Incoming +S1.D -F50 RL6:E14 /Q04.B3
=Incoming +S1.D -F50 RL6:E15 CS+ 91 =HV Side 150 kV -Xx :xx /Q04.E3
=HV Side 150 kV -Xx :xx CS+ 92 =Incoming +S1.D -F50 RL1:E1 /Q04.B3
=Incoming +S1.D -F50 RL1:E2 CS+ 93 =HV Side 150 kV -Xx :xx /Q04.E3
=RCP -Xx :xx CS+ 94 Connection is not unique. /Q04.B6
CS+ 95 =Incoming +S1.B -K86 :34 /Q04.B8
=RCP -Xx :xx CS+ 96 Connection is not unique. /Q04.E6
F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V05.2
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 23
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 97 - 110 , 120 ]
Terminal UT 4. [ 111 - 119 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X5 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=RCP -Xx :xx CS+ 97 =Incoming +S1.B -K86 :31 /Q04.E8
98 /Q02.E5
99 /Q02.F5
B 100 /Q02.F5 B

101 /Q02.F5
102 /Q02.F5
103 /Q02.F5
104 /Q02.E5
105 /Q02.F5
106 /Q02.F5
107 /Q02.F5
C 108 /Q02.F5 C
109 /Q02.F5
=Incoming +S1.D -S650 :12 TR+ 110 =Supervisory -Xx :xx /M02.B4
=Supervisory -Xx :xx TR+ 111 =Incoming +S1.B -X5 :63 /M02.C4
112 /Q02.E5
113 /Q02.F5
114 /Q02.F5
115 /Q02.F5
116 /Q02.F5
D D
117 /Q02.F5
118 /Q02.E6
119 /Q02.F6
120 /Q02.F6

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V05.3
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 24
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal MTK-P/P [ 1 - 15 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X6 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Scada -Xx :xx CS+ 1 Connection is not unique. /Q05.B2
=Scada -Xx :xx CS+ 2 =Incoming +S1.B -K52 :21 /Q05.E2
=Scada -Xx :xx CS+ 3 =Incoming +S1.B -K51 :21 /Q05.E2
B =Scada -Xx :xx CS+ 4 =Incoming +S1.B -X5 :36 /Q05.B3 B

=Scada -Xx :xx CS+ 5 =Incoming +S1.B -X5 :37 /Q05.E3


=Scada -Xx :xx CS+ 6 =Incoming +S1.B -X5 :41 /Q05.E3
=Scada -Xx :xx CS+ 7 =Incoming +S1.B -X5 :32 /Q05.B4
=Scada -Xx :xx CS+ 8 =Incoming +S1.B -X5 :33 /Q05.E4
=Scada -Xx :xx CS+ 9 =Incoming +S1.B -X5 :35 /Q05.E4
=Scada -Xx :xx CS+ 10 =Incoming +S1.B -K86 :44 /Q05.B5
=Scada -Xx :xx CS+ 11 =Incoming +S1.B -K86 :41 /Q05.E5
C =Scada -Xx :xx CS+ 12 =Incoming +S1.D -F50 WD:F13 /Q05.B5 C
=Incoming +S1.D -F50 WD:F14 CS+ 13 =Scada -Xx :xx /Q05.E5
=Scada -Xx :xx CS+ 14 =Incoming +S1.D -F50 RL7:E17 /Q05.B6
=Incoming +S1.D -F50 RL7:E18 CS+ 15 =Scada -Xx :xx /Q05.E6

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V06
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 25
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 3 ]
Terminal UT 4. [ 4 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X11 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
220V AC SUPPLY (P) P 1 /D01.A2
220V AC SUPPLY (P) P 2 Connection is not unique. /D01.A7
220V AC SUPPLY (N) N 3 /D01.A2
B 220V AC SUPPLY (N) N 4 Connection is not unique. /D01.A7 B

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V07
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 26
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 3 ]
Terminal UT 4. [ 4 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X21 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
110V DC SUPPLY (L+) 110V(+) 1 /D01.A2
110V DC SUPPLY (L+) 110V(+) 2 Connection is not unique. /D01.A7
110V DC SUPPLY (L-) 110V(-) 3 /D01.B2
B 110V DC SUPPLY (L-) 110V(-) 4 Connection is not unique. /D01.B7 B

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V08
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 27
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 15 ]
Terminal UT 4. [ 16 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X41 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
1UR 1 /T02.E1
Connection is not unique. 1UR 2 /T02.E5
1US 3 /T02.E1
B Connection is not unique. 1US 4 /T02.E5 B

1UT 5 /T02.E1
Connection is not unique. 1UT 6 /T02.E5
1UN 7 /T02.E1
Connection is not unique. 1UN 8 /T02.E5
2UR 9 /T02.E6
Connection is not unique. 2UR 10 /T02.E8
2US 11 /T02.E6
C Connection is not unique. 2US 12 /T02.E8 C
2UT 13 /T02.E6
Connection is not unique. 2UT 14 /T02.E8
2UN 15 /T02.E6
Connection is not unique. 2UN 16 /T02.E8

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V09
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 28
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 17 ]
Terminal UT 4. [ 18 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X51 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
CS+ 1 /Q01.D7
CS+ 2 Connection is not unique. /Q01.D8
CS+ 3 /Q01.D7
B CS+ 4 Connection is not unique. /Q01.D8 B

=Incoming External -Xx :xx CS+ 5 =Incoming +S1.B -K861 :11 /M01.A6
=Bus Coupler -X51 :11 CS+ 6 /M01.A6
=Incoming External -Xx :xx CS+ 7 =Incoming +S1.B -X5 :72 /M01.B6
=Bus Coupler -X51 :11 CS+ 8 /M01.B6
=Incoming (Future) -Xx :xx CS+ 9 =Incoming +S1.B -X5 :13 /Q04.B1
=Incoming (Future) -Xx :xx CS+ 10 =Incoming +S1.B -X5 :14 /Q04.E1
=Bus Coupler -X51 :6 CS+ 11 =Incoming +S1.B -X5 :17 /Q04.B2
C =Bus Coupler -X51 :8 CS+ 12 =Incoming +S1.B -X5 :18 /Q04.E2 C
=Outgoing -X51 :16 TR+ 15 =Incoming +S1.B -X2 :10 /M02.B7
TR+ =Incoming +S1.B -X5 :74 /M02.B7
=Outgoing -X51 :15 TR+ 16 /M02.B7
=Outgoing -X51 :18 TR+ 17 =Incoming +S1.B -X2 :4 /M02.C7
TR+ =Incoming +S1.B -X5 :75 /M02.C7
=Outgoing -X51 :17 TR+ 18 /M02.C7

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V10
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 29
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal UT 4. [ 1 - 11 ]
Terminal UT 4. [ 12 ]
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-X61 Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Incoming +S1.D -P50 :SH+ COM+ 1 /S01.B2
=Incoming +S1.D -P50 :SH+ COM+ 2 /S01.B7
=Incoming +S1.D -P50 :SH- COM- 3 /S01.B2
B =Incoming +S1.D -P50 :SH- COM- 4 /S01.B7 B

=Incoming +S1.D -P50 :GND GND 5 /S01.B2


=Incoming +S1.D -P50 :GND GND 6 /S01.B7
7
8
9
10
11
C 12 C

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V11
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 30
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Terminal type
TERMINAL PLAN Terminal USLKG 5 [ 1 - 7 ]
Terminal
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

Terminal
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

Terminal
-XPE Terminal

Vinyl Wire Wire Wire Wire Wire Wire Vinyl


Function Connection Target Signal Number Connection Target Reference
Colour Colour Size Type Type Size Colour Colour
=Incoming +S1.B -X3 :4 PE 1 =Incoming +S1.B -X3 :14 /T02.C1
=Incoming +S1.B -X3 :24 PE 2 =Incoming +S1.B -H1001 :PE /T02.C1
=Incoming +S4 -Q51 :PE PE 3 /T02.C1
B =Incoming +S1.D -P50 :G PE 4 =Incoming +S4 -X022 :7M /T02.C2 B

=Incoming +S4 -PE :3 PE 7 /T02.C2


=Incoming +S1.D -F50 :PE PE 5 =Incoming +S1.B -X4 :6 /T02.C2
=Incoming +S1.B -H1002 :PE PE 6 =Incoming +S1.B -X4 :12 /T02.C2

C C

D D

E E

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Terminal Plan
X4020126-301 +S1.B V14
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 31
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NOTE :
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
DEVICE
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

EQUIPMENT DESCRIPTION ENGRAVING


CODE
-F50 FEEDER MANAGE RELAY, MiCOM P142 -F50, FEEDER MANAGE RELAY
-H74 HORN, KACON -H74, HORN
-H100 ANNUNCIATOR, IDEC -H100, ANNUNCIATOR
-P10 ANALOG VOLT METER, CROMPTON -P10, VOLTMETER
B B
-H74
-P11 -P10 -P11 ANALOG AMPER METER, CROMPTON -P11, AMMETER

2 1
-P50 -P50 DIGITAL ENERGI METER, M8650 -P50, DIGITAL ENERGY METER
G

L/+

N/-
-H51 LAMP INDICATION FOR CB CLOSE/RED, SCHNEIDER -H51, CB CLOSE INDICATION
I32 I22 I12 V3 V1

-F50
Vref I31 I21 I11 V2
-H52 LAMP INDICATION FOR CB OPEN/GREEN, SCHNEIDER -H52, CB OPEN INDICATION
-H100

MiCOM P14X -H30 LAMP INDICATION FOR ES CLOSE/RED, SCHNEIDER -H30, ES CLOSE INDICATION

C
TRIP

ALARM
-S17 SILENCE/HORN STOP PUSH BUTTON -S17, SILENCE C
OUT OF SERVICE
-S17 -S18 -S19 -S20
O I
HEALTHY

C = CLEAR

= READ
= ENTER
-S18 ACKNOWLEDGE PUSH BUTTON BLACK -S18, ACKNOWLEDGE
C
-H52
-H30 -H51
-S19 RESET PUSH BUTTON BLACK -S19, RESET
-S20 TEST LAMP PUSH BUTTON BLACK -S20, TEST LAMP
-S611 -S650 -S601 -S610
-XA1 -XA2
1 5 3 7 11 9
-XV1 -XV2
-S601 SELECTOR SWITCH FOR CB OPEN/CLOSE K&N -S601, CB OPEN/CLOSE
2 6 4 8 12 5 6 7 8
10
13 17 15 19 23 21

-S610 VOLT SELECTOR SWITCH, K&N -S610, VOLT SELECTOR SWITCH


14 18 16 20 24 22

CTT CTT 25 29 27 31 35 33 PTT PTT


26 30 28 32 36 34
37 38 39 40 41 42

D -S611 AMPERE SELECTOR SWITCH, K&N -S611, AMPERE SELECTOR SWITCH D

-S650 LOCAL/REMOTE/SUPERVISORY SELECTOR SWITCH, K&N -S650, LOCAL/REMOTE/SUPERVISORY


-XA1 CURRENT TEST BLOCK, YONGSUNG -XA1, CTB FOR MEASUREMENT
PIX LV DOOR
-XA2 CURRENT TEST BLOCK, YONGSUNG -XA2, CTB FOR PROTECTION
Height : 710mm
Width : 960mm -XV1 VOLTAGE TEST BLOCK, YONGSUNG -XV1, VTB FOR MEASUREMENT
-XV2 VOLTAGE TEST BLOCK, YONGSUNG -XV2, VTB FOR PROTECTION
E E

F F

Date 10/03/2017 Project Name Title LV Door Layout Drawing Nr. =Incoming
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-301 +S1.B X01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 32
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

1
-S34
DUCT 65x65 2
-H17 2

-X6

1
-X11 -X21 -X41 -X51 -X61 -X1 -X6

2
-X6

3
-X6

4
-X6

5
-X6

6
-X6

7
-X6

8
-X6

15 14 13 12 11 10 9

9
-MO17 -X6

15 14 13 12 11 10
-X6
1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
-X6
-X6
4 4 16 18 12 6 -X6
-X6

B B
DUCT 45x65

-H1001 -H1002 -K51 -K86 -K861


COMDI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI10

-X2 PE +24VDC -24VDC


44 34 24 14

42 32 22 12
44 34 24 14

42 32 22 12
44 34 24 14

42 32 22 12
44 34 24 14

42 32 22 12
44 34 24 14

42 32 22 12

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
A1 A2 A1 A2 A1 A2 A1 A2 A1 A2

25 +24VDC
-24VDC
PE COM0
DO0DO1DO2DO3COM1
DO4DO5COM2
DO6
-110VDC +110VDC
41 31 21 11 41 31 21 11 41 31 21 11 41 31 21 11 41 31 21 11

-K52 -K401

C C
DUCT 65x65

-Q921 -Q922 -Q923 -Q924 -Q941 -Q942


-XPE

-X3

DUCT 65x65
DUCT 65x65

94 94 94 94 94 94
92 1 3 92 1 3 92 1 3 92 1 3 92 1 3 5 7 92 1 3 5 7

-X4
-XPE
-XPE
-XPE
-XPE
-XPE
-XPE

91 91 91 91 91 91
1 2 3 4 5 6 7 8 9 10 11 12 24 25 26 27 28 29 30

1 2 3 4 7 5 6

-MO19
1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

12 11
12 2 4
11
12 2 4
11
12 2 4
11
12 2 4
11
12 2 4 6 8
11
12 2 4 6 8
14 14 14 14 14 14

Cymax ®
-B21
60 5
70 0

40
80

1
30
90
THERMOSTAT

20
0 10

D D
DUCT 65x65
1

PIX LV BOX
Height : 730mm
Width : 1000mm
E -X5 E

-MO18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120

120

F F

Date 10/03/2017 Project Name Title LV Box Layout Drawing Nr. =Incoming
01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT X4020126-301 +S1.B X02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 33
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BILL OF MATERIALS

Device Designation Description Technical Data Type / Ref. Number Manufacturer References Location Panel Remarks
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-B21 Thermostat 0 to 90 C Deg. Max 250VAC Cymax CYIT-90 Gumsung Controls - +S1.B =Incoming -
disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-H17 Panel Lighting 220V AC, 9 Watt E27 GE - +S1.B =Incoming -

-H1001 CPU PLC Module FC4A-C16R2C (9Input/7Output) FC4A-C16R2C IDEC - +S1.B =Incoming -

-H1002 DC-DC Converter PSSR-SC24, 85 - 264VAC / 100 - 370 DC PSSR-SC24 IDEC - +S1.B =Incoming -

-K51 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Incoming -

-K52 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Incoming -

-K86 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Incoming -

B -K401 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Incoming - B

-K861 Auxiliary Relay RXM4 Series, 4 COS RXM4AB2FD + RXZE2M114M Schneider Electric - +S1.B =Incoming -

-Q921 Miniature Circuit Breaker iC60N , 2P , 6A , DIN Rail Mounting A9F74206 Schneider Electric - +S1.B =Incoming -

-Q921 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Incoming -

-Q922 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Incoming -

-Q922 Miniature Circuit Breaker iC60N , 2P , 6A , DIN Rail Mounting A9F74206 Schneider Electric - +S1.B =Incoming -

-Q923 Miniature Circuit Breaker iC60N , 2P , 6A , DIN Rail Mounting A9F74206 Schneider Electric - +S1.B =Incoming -

C -Q923 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Incoming - C

-Q924 Miniature Circuit Breaker iC60N , 2P , 6A , DIN Rail Mounting A9F74206 Schneider Electric - +S1.B =Incoming -

-Q924 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Incoming -

-Q941 Miniature Circuit Breaker iC60N , 4P , 2A , DIN Rail Mounting A9F74402 Schneider Electric - +S1.B =Incoming -

-Q941 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Incoming -

-Q942 Miniature Circuit Breaker iC60N , 4P , 2A , DIN Rail Mounting A9F74402 Schneider Electric - +S1.B =Incoming -

-Q942 MCB Auxiliary Contact iOF + SD/OF A9A26929 Schneider Electric - +S1.B =Incoming -

D -S34 Microswitch 1 COS, Imax 15A, 250VAC Z15G-1307 TEND - +S1.B =Incoming - D
-F50 Protection Relay Micom P142 P142316B6M0468J Schneider Electric - +S1.D =Incoming -

-H30 Indication Lamp Red, 24-132VAC/DC 50/60HZ ZB5 AVBG4+ZB5 AV043 Schneider Electric - +S1.D =Incoming -

-H51 Indication Lamp Red, 24-132VAC/DC 50/60HZ ZB5 AVBG4+ZB5 AV043 Schneider Electric - +S1.D =Incoming -

-H52 Indication Lamp Green, 24-132VAC/DC 50/60HZ ZB5 AVBG3+ZB5 AV033 Schneider Electric - +S1.D =Incoming -

-H74 Horn KMB Series KMB-N80 KACON - +S1.D =Incoming -

-H100 Annunciator Lamp SLC30N-0104, 4 Windows SLC30N-0104 IDEC - +S1.D =Incoming -

-P10 Voltmeter 96 x 96mm E244-02VG CROMPTON - +S1.D =Incoming -


E E
-P11 Amperemeter 96 x 96mm E244-02AG CROMPTON - +S1.D =Incoming -

-P50 Energy Meter ION 8650, 3P4W M8650B4C0H5C7B1A Schneider Electric - +S1.D =Incoming -

-S17 Push Button 1N/O, Color Black XB5-AA21 Schneider Electric - +S1.D =Incoming -

-S18 Push Button 1N/O, Color Black XB5-AA21 Schneider Electric - +S1.D =Incoming -

-S19 Push Button 1N/O, Color Black XB5-AA21 Schneider Electric - +S1.D =Incoming -

-S20 Push Button 1N/O, Color Black XB5-AA21 Schneider Electric - +S1.D =Incoming -

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Bill Of Materials
X4020126-301 +S1.B Y01
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 34
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BILL OF MATERIALS

Device Designation Description Technical Data Type / Ref. Number Manufacturer References Location Panel Remarks
All technical information contained in this document is the exclusive property of PT. SCHNEIDER INDONESIA may neither be used nor

-S601 CB Control Switch S0 CA10 Series S0-CA10-A714-600 K&N - +S1.D =Incoming -


disclosed without its prior written consent. Only those drawings and diagrams remitted after order booking are binding for execution.

A A
All devices shown in this diagram are in open position, drawn out, with operating mechanism discharged and all power source off.

-S610 Volt Selector Switch S0 CA10 Series S0-CA10-A007 K&N - +S1.D =Incoming -

-S611 Ampere Selector Switch S0 CA10 Series S0-CA10-A058 K&N - +S1.D =Incoming -

-S650 Local/Remote/Supervisory Switch S0 CA10 Series S0-CA10-RIF280-FT2 K&N - +S1.D =Incoming -

-XA1 Current Test Block 4P, 10A, 250VAC YS CTT-04C / X0140500004 YongSung Electric - +S1.D =Incoming -

-XA2 Current Test Block 4P, 10A, 250VAC YS CTT-04C / X0140500004 YongSung Electric - +S1.D =Incoming -

-XV1 Voltage Test Block 4P, 10A, 250VAC YS PTT-04C / X0140500002 YongSung Electric - +S1.D =Incoming -

B -XV2 Voltage Test Block 4P, 10A, 250VAC YS PTT-04C / X0140500002 YongSung Electric - +S1.D =Incoming - B

-C1L1 Capacitive Divider Refer to Component List AMT000155-03 Refer to Component List - +S4 =Incoming -

-C1L2 Capacitive Divider Refer to Component List AMT000155-03 Refer to Component List - +S4 =Incoming -

-C1L3 Capacitive Divider Refer to Component List AMT000155-03 Refer to Component List - +S4 =Incoming -

-H101 Voltage Indicator 3 Phase L1, L2, L3 - Schneider Electric - +S4 =Incoming -

-Q30 Earthing Switch Auxiliary Contact EX-7.11M, 4NO + 4NC ES-PIX-24 Schneider Electric - +S4 =Incoming -

-Q51 Vacuum Circuit Breaker - - Schneider Electric - +S4 =Incoming -

C -R11 Heating Resistor Blizzard - DBK - +S4 =Incoming - C

-S81 Micro Switch V-156-1A5, 1COS V-156-1A5 OMRON - +S4 =Incoming -

-SS1 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX - +S4 =Incoming -

-SS2 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX - +S4 =Incoming -

-SS3 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX - +S4 =Incoming -

-SS4 Service Position Micro Switch EX1.20YR2 (Yellow), 1NO - ELMEX - +S4 =Incoming -

-ST1 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX - +S4 =Incoming -

D -ST2 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX - +S4 =Incoming - D
-ST3 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX - +S4 =Incoming -

-ST4 Test Position Micro Switch EX1.20BR2 (Blue), 1NC - ELMEX - +S4 =Incoming -

-T51L1 3 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 - +S4 =Incoming -

-T51L2 3 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 - +S4 =Incoming -

-T51L3 3 Cores Current Transformer Refer to sheet A02 CT Refer to sheet A02 - +S4 =Incoming -

-T61L1 2 Winding Voltage Transformer Refer to sheet A02 VT Refer to sheet A02 - +S4 =Incoming -

-T61L2 2 Winding Voltage Transformer Refer to sheet A02 VT Refer to sheet A02 - +S4 =Incoming -
E E
-T61L3 2 Winding Voltage Transformer Refer to sheet A02 VT Refer to sheet A02 - +S4 =Incoming -

-Y8 Blocking Magnet 110VDC ST436-101-048 Schneider Electric - +S4 =Incoming -

F F

Date 10/03/2017 Project Name Title Drawing Nr. =Incoming


01 As Manufactured 12/07/2017 WD Drawn AF
GI KAYU AGUNG PROJECT Bill Of Materials
X4020126-301 +S1.B Y02
Schematic Diagram
00 First Issued 10/03/2017 AF Checked BWP Incoming Customer Doc. Nr. Sheet 35
Rev N° Modification Date Name Approved DTA Order N° C2030-4020126 Switchboard 24kV Switchgear PT. SCHNEIDER INDONESIA 35 Sh.