Kirkschemebook
Kirkschemebook
D E
A-2 A-3
L-O-C L-O-C
A B
A2 A 3
C
L-O L-O
D E
A-2 A 3 A 5 A-4
A-3 A-5
A-2 A-4
L-C L-C
A B
A2 A 4
C
A 1 A 1
L-O L-O
www.kirkkey.com
Table Of Contents
Purpose of Interlocking
Scheme# Function
Switch and Breaker
Scheme #1 Prevents opening of switch when breaker is closed.
Scheme #2 Prevents operation of switch when breaker is closed. Permits re-closing the breaker for servicing when switch is locked open.
Scheme #3 Prevents operation of switch when breaker is closed. Circuit cannot be cleared until proper supervisory key is obtained.
Interrupter Switch
Scheme #25 Prevents opening fuse compartment door when the interrupter switch is closed. Prevents closing interrupter switch until fuse
compartment door is locked closed.
Scheme #26 Prevents operation (open or closed) of interrupter switch when breaker is closed. Permits the breaker to be serviced and operated
while the interrupter switch is locked open.
Table Of Contents
Purpose of Interlocking
Scheme# Function
Interrupter Switch
Scheme #27 Prevents operation (open or closed) of interrupter switch when breaker is closed. Prevents opening fuse compartment door when
interrupter switch is closed. Prevents closing interrupter switch until fuse compartment door is locked closed. Permits the breaker to
be serviced and operated while the interrupter switch is locked open.
Scheme #28 Prevents dropping load when shifting from one source to the other. Prevents opening both interrupter switches at the same time.
Permits both interrupter switches to be closed at the same time.
Scheme #29 Prevents paralleling two lines - requires dropping load when shifting from one source to the other. Prevents closing both interrupter
switches at the same time. Permits both interrupter switches to be opened at the same time.
Scheme #30 Prevents paralleling two lines - requires dropping load when shifting from one source to the other. Prevents closing both interrupter
switches at the same time. Permits both interrupter switches to be open at the same time. Prevents operation (open or closed) of
either interrupter switch when breaker is closed. Permits the breaker to be serviced and operated while both interrupter switches are
locked open.
Scheme #31 Prevents operation (closed, open or closed) of a three position interrupter switch when the breaker is closed. Permits the breaker to
be serviced and operated while the interrupter switch is locked open.
Scheme #32 Prevents operation (closed, open or closed) of a three position interrupter switch when the breaker is closed. Prevents opening fuse
compartment door when the interrupter switch is closed. Prevents closing interrupter switch until fuse compartment door is locked
closed. Permits the breaker to be serviced and operated while the interrupter switch is locked open.
Scheme #36 Prevents paralleling of two lines - two loads, fed from either source (one tie breaker). Allows switching loads to two generators.
Scheme #38 Prevents access to capacitor bank enclosure until capacitors have been grounded and discharged - utilizing a Time Delay Key Release
Unit (TDKRU).
Precipitator Access
Scheme #41 Prevents access to an electrostatic precipitator, scrubber, or baghouse until all power supplies have been de-energized and properly
grounded.
Scheme #42 Prevents access to an electrostatic precipitator, scrubber, or baghouse until all power supplies have been de-energized and properly
grounded.
Legend\Symbols
KIRK KIRK
Device normally open.
Detachable latch interlock,
Type D.
Device normally closed.
Interlock
Direction of key transfer. KIRK
Auxiliary switch 2 make,
Multi-cylinder 2 break. Type SS
A-1, A-2, A-3 Key interchange number. Detachable latch interlock,
Type D.
KIRK
KIRK
KIRK
KIRK
Interlock used to lock Transfer interlock, Type T.
device open. 3 cylinder
L-O (with key removed)
Auxiliary switch
KIRK Type K
Interlock used to lock
KIRK
device open.
L-O
(with key held) KIRK
KIRK
Interlock used to lock
device closed.
L-C (with key held) Solenoid key release unit. Key
Padlock released when solenoid is E,
KIRK KIRK
Type P KIRK energized.
Interlock used to lock device
open and closed.
L-O-C
E
KIRK
KIRK
A3 Key Interchange number
(showing key held). Two key
Multi-lock interlock. Solenoid key release unit. Key
released when solenoid is E,
KIRK
energized.
KIRK
Initiating key
KIRK
Interlock with master lock. Interlock Key released when
(Also called apartment lock.) Auxiliary switch 1 make, solenoid is energized.
1 break. Type S E
E E
Key Removable Positions
A-2 A- 1
The “E” or “W” next to the interlock symbol indicates the position of the interlock bolt when the key is removable, “E” =
L-C A3
W
Extended, “W” = Withdrawn.
L-O For more information regarding key removable positions please reference the technical paper “How an Individual Key
Interlock Operates” on our website (Click on the 'APPS/Schemes' button, then click on 'Technical Papers', then click on
“How an Individual Key Interlock Operates”). Refer also to the Available Options on Data Sheets 1.1, 1.2, 1.3, 1.4, 1.5,
1.13 and to columns 8 & 9 on the Interlock Ordering Guide.
APPLICATION SCHEMES - Introduction
In order to lay out complicated interlock schemes, it is necessary to understand the simplest applications. On this page, the basic concepts of
interlocking are outlined and discussed.
Interlocking a Single Unit in One Position Interlocking Two Units in Two Positions
If it is desired to secure a device in the open position, an interlock is The other method for locking in both the open and closed positions
used as in Fig. 1. The possession of the key indicates requires two interlocks as show in Fig. 4. Possession of key A-1 indicates
that the device is locked open possession of key A-2 indicates that
the device is locked closed. The device is shown normally open;
therefore, key A-1 is free and the L-O interlock bolt is extended into its
recess provided in the movable member while key A-2 is held and the
A1 A-1 E A1 A-1 E L-C interlock bolt is withdrawn. To close the device, insert key A-1 in the
L-O lock and turn to withdraw bolt of L-O interlock, which permits the
L-O L-C device to be operated. Now the device can be moved to the closed
Fig. 1 Fig. 2 position. Key A-2 can be turned to extend the bolt of the L-C interlock
into its recess, which locks the device in the closed position.
that the device is in the open position and is locked by the extension of
the interlock bolt. When the key is inserted in the lock and turned to
withdraw the interlock bolt, the device is free to operate to the closed
position and the key is held in the lock. E E
A 1 A-1 A2
L-O L-C
When a device is to be locked only in the closed position an interlock is
used as shown in Fig. 2. The possession of the key indicates that the Fig. 4.
device is locked in the closed position, as the interlock bolt has been This releases Key A-2 from the L-C interlock. Meanwhile, key A-1 is held
extended to remove the key. When the key is inserted in the lock and in the L-O interlock since its withdrawn locking bolt cannot be
turned to withdraw the interlock bolt, the device is free to operate to extended.
the open position and the key is held in the lock.
This method is used more often than the single two-position interlock
Interlocking a Single Unit in Two Positions shown in Fig. 3, due to its adaptability to sequence operations. Also,
the possession of key A-1 or A-2 indicates that the device is locked
Two methods are used in interlocking a device in both open and open or locked closed, respectively.
closed position. The first method requires only one interlock as shown in
Fig. 3. The interlock bolt is extended in both the open and closed Sequence Interlocking
positions. This is accomplished with two recesses in the device that is
being interlocked - each coinciding with the locking bolt in one With the fundamentals developed above, it is quite simple to extend
position. the application to the interlocking of two or more devices in a desired
sequence.
A B
A 1 A-1 E
A-1 E A-1 E
A 1
L-O-C L-O L-O
Fig. 3 Fig. 5
Two devices are shown in Fig. 5. In operation they are not closed at
The possession of the key indicates that the interlock bolt is extended
the same time. With the interlocks arranged as shown, only one key is
and that the device is locked either in the open or closed position.
required in the interlocking system. Both devices are shown open;
Furthermore, the device cannot be operated until the key is inserted
therefore, the key is free. To close any one device, the key is inserted
and turned in the lock to withdraw the locking bolt. The key cannot be
and turned in that particular lock to withdraw the interlock bolt. The key
removed from the lock in an intermediate position, but in the fully
is held in this lock until the device is again locked open. This simple
open or closed positions only. However, in this application, possession
interlocking sequence lends itself to a multitude of applications. The
of the key gives no indication as to whether the device is locked
procedure is the same for two devices, neither of which is to be
closed or open.
opened at the same time.
Scheme 1 Scheme 3
To prevent opening of switch A when breaker B is closed. To prevent operation of switch A when breaker B is closed. Circuit
cannot be cleared until proper supervisory key is obtained.
A
B
A
B
A-1 E A 1 E
L-C L-O
W A-2 A 2
SUPERVISORY
Switch A and breaker B are in closed position. Key A-1 is held in breaker A-1 E A 1 E KEY
B interlock.
L-O-C L-O
1. Open breaker.
2. Turn key A-1 in L-O interlock on breaker B to lock open. Key A-
1 is now free.
3. Insert key A-1 in L-C interlock on switch A and turn to unlock.
4. Open switch A. Key A-1 is now held. Breaker B and switch A shown closed. Key A-1 held in breaker interlock.
Key A-2 retained by supervisor.
Reverse sequence to restore service.
A-1 A 1
L-O-C L-O B
A 1 E A-1 E
Switch A and breaker B are in closed position. Key A-1 is held in breaker
L-O L-O
B interlock.
1. Open breaker.
2. Turn key A-1 in L-O interlock on breaker B to lock open. Key A- Main switch A shown closed and grounding switch B shown open. Key
1 is now free. A-1 is held in main switch interlock.
3. Insert key A-1 in L-O-C interlock on switch A and turn to
unlock. 1. Open main switch A.
4. Open switch A. Key A-1 is now held. 2. Turn key A-1 in L-O interlock on main switch A to lock open.
5. Turn key A-1 in L-O-C interlock on switch A to lock open. Key Key A-1 is now free.
A-1 is now free. 3. Insert Key A-1 in L-O interlock on grounding switch B and turn
6. Return Key A-1 to breaker interlock and unlock for operation to unlock. Key A-1 is now held.
during servicing period. 4. Close grounding switch B.
L-O
To open fuse compartment door:
L-O-C L-C L-O
1. Proceed from normal position with operations as in 1
through 4 above.
2. Turn key A-2 in L-O interlock on disconnect switch to lock
open. Key A-2 is now free.
3. Insert key A-2 in L-C interlock on fuse compartment door
and turn to unlock. Key A-2 is now held.
Breaker, fuse compartment door and disconnect switch are shown in 4. Open fuse compartment door.
closed positions. Key A-1 is held in breaker interlock and key A-2 is held
in disconnect interlock. Reverse sequence to restore service.
Scheme 6
To prevent operation of disconnect switch A when breakers B, C, D and Disconnect A and breakers B, C, D and E are shown in closed position.
E are closed. Breakers may be opened in any sequence. Key A-1 is held in transfer interlock. Keys A-2, A-3, A-4 and A-5 are held
in interlocks on breaker B, C, D and E.
NOTE: Electrical circuit is equivalent of Scheme 7.
1. Open breakers B, C, D and E.
W A-5
2. Turn key in L-O interlock on each breaker B, C, D and E to
A lock breakers open. Keys A-2, A-3, A-4 and A-5 are now free.
A-1
W A-4 3. Insert keys A-2, A-3, A-4 and A-5 in transfer interlock.
L-O-C
W A-3
4. Turn key A-1 in transfer interlock. Key A-1 is now free. Keys A-
2, A-3, A-4 and A-5 are now held.
W A-2 5. Insert key A-1 in L-O-C interlock on disconnect A and turn to
unlock. Key A-1 is now held.
A 1 E
6. Open disconnect A.
T
7. Turn key A-1 in L-O-C interlock on disconnect A to lock open.
Key A-1 is now free.
8. Insert key A-1 in transfer interlock and turn. Key A-1 is now
held, Keys A-2, A-3, A-4 and A-5 are now free.
B C D E 9. Return keys A-2, A-3, A-4 and A-5, as desired, to breaker
A2 A3 A4 A5 interlocks and unlock for operation during servicing.
L-O L-O L-O L-O
Reverse sequence to restore service.
Scheme 7 Scheme 8
To prevent operation of disconnect switch A when breakers B, C, D and To prevent operation of disconnects A and B when breaker C is
E are closed. Breakers must be opened in pre-arranged sequence. closed. To permit servicing of breaker when disconnects are locked
open.
A A B
A-1 A5
L-O-C
SUPERVISORY C
KEY
E E E E E
A2 A-1 A 1 A 1 A-2
B W C W D W E W
A-2 A-3 A-4 A-5 L-O L-C L-O L-O L-C
A 1 A2 A3 A4
L-O E L-O
E L-O
E L-O
E
Disconnect A and breakers B, C, D and E are shown in closed position. Breaker C and disconnects A and B are shown closed. One key A-1 is
Key A-1 is held in breaker B interlock, key A-2 is held in breaker C held in breaker L-O interlock and the other key A-1 is held in L-O
interlock, key A-3 is held in breaker D interlock and key A-4 is held in interlock on disconnect B. Key A-2 is held in L-O interlock
breaker E interlock. Key A-5 is held free in breaker E interlock or is on disconnect A.
retained by supervisor.
1. Open breaker.
1. Obtain key A-5 from supervisor. 2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1
2. Open breaker E. is now free.
3. Insert key A-5 in L-O interlock on breaker E and turn key A-4 to 3. Insert key A-1 in L-C interlock on disconnect A and turn to
lock open. Key A-5 is now held. Key A-4 is now free. unlock. Key A-1 is now held.
4. Open breaker D. 4. Open disconnect A.
5. Insert key A-4 in L-O interlock on breaker D and turn key A-3 to 5. Turn key A-2 in L-O interlock on disconnect A to lock open.
lock open. key A-4 is now held. key A-3 is now free. Key A-2 is now free.
6. Open breaker C. 6. Insert key A-2 in L-C interlock on disconnect B and turn to
7. Insert key A-3 in L-O interlock on breaker C and turn key A-2 to unlock. Key A-2 is now held.
lock open. Key A-3 is now held. Key A-2 is now free. 7. Open disconnect B.
8. Open breaker B. 8. Turn key A-1 in L-O interlock on disconnect B to lock open.
9. Insert key A-2 in L-O interlock on breaker B and turn key A-1 to Key A-1 is now free.
lock open. Key A-2 is now held. Key A-1 is now free. 9. Insert key A-1 in breaker L-O interlock and turn to unlock for
10. Insert key A-1 in L-O-C interlock on disconnect A and turn to operation during servicing.
unlock. Key A-1 is now held.
11. Open disconnect A. Reverse sequence to restore service.
12. Turn key A-1 in L-O-C interlock on disconnect A to lock open.
Key A-1 is now free.
13. Insert key A-1 in L-O interlock on breaker B and turn to unlock.
Key A-1 is now held and key A-2 is now free.
14. Breaker B may now be operated for servicing.
15. Insert key A-2 in L-O interlock on breaker C and turn to unlock.
Key A-2 is now held and Key A-3 is now free.
16. Breaker C may now be operated for servicing.
17. Insert key A-3 in L-O interlock on breaker D and turn to unlock.
Key A-3 is now held and key A-4 is now free.
18. Breaker D may now be operated for servicing.
19. Insert key A-4 in L-O interlock on breaker E and turn to unlock.
Key A-4 is now held and supervisor Key A-5 is now free.
20. Breaker E may now be operated for servicing.
E 1. Open breaker.
A 1 2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1
is now free.
L-O 3. Insert key A-1 in L-C interlock on disconnect A and turn to
unlock. Key A-1 is now held.
A B 4. Open disconnect A.
5. Turn key A-2 in L-O interlock on disconnect A to lock open.
C Key A-2 is now free.
6. Insert key A-2 in L-C interlock on disconnect B and turn to
unlock. Key A-2 is now held.
7. Open disconnect B.
8. Turn keys A-1 and A-3 in L-O interlock on disconnect B to
E E E E
lock open. Keys A-1 and A-3 are now free.
A-1 A2 A-2 A 1 9. Insert key A-1 in breaker L-O interlock and turn to unlock for
E
E
operation during servicing.
A-3 10. Insert key A-3 in L-C interlock (type D) on compartment door
L-C L-O L-C A3
and turn to unlock. Key A-3 is now held.
L-C 11. Open compartment door to service breaker.
L-O
Scheme 10
To prevent operation of disconnects A and B and by-pass disconnect To transfer load from breaker and disconnects to by-pass switch:
C under load. Provides for closing of by-pass disconnect C before
breaker circuit is opened, or permits breaker circuit to be opened with 1. Obtain key A-3 which is free and insures that both
by-pass disconnect C remaining open. disconnects A and B are locked closed.
2. Insert key A-3 in L-C interlock on breaker D and turn to lock
Disconnects A and B and breaker D normally closed. By-pass closed. Key A-3 is held and key A-4 is now free.
disconnect C normally open. Keys A-1, A-2, and A-4 normally held in 3. Insert key A-4 in L-O-C interlock on by-pass disconnect C and
locks as indicated. Key A-3 normally free. turn to unlock. Key A-4 is now held.
4. Close by-pass disconnect C.
5. Turn key A-4 in L-O-C interlock on by-pass disconnect C to
lock closed. Key A-4 is now free.
E
A-4 6. Insert key A-4 in L-C interlock on breaker D and turn to unlock.
Key A-4 is held and key A-3 is now free.
L-O-C
7. Open breaker D.
8. Turn key A-1 in L-O interlock on breaker D to lock open. Key A-
C 1 is now free.
9. Insert keys A-1 and A-3 in L-C interlock on disconnect A and
turn to unlock. Keys A-1 and A-3 are now held.
10. Open disconnect A.
11. Turn key A-2 in L-O interlock on disconnect A to lock open.
A B Key A-2 is now free.
D 12. Insert key A-2 in L-C interlock on disconnect B and turn to
unlock. Key A-2 is now held.
13. Open disconnect B.
14. Turn key A-1 in L-O interlock on disconnect B to lock open.
Key A-1 is now free.
15. Insert key A-1 in L-O interlock on breaker D and turn to unlock
E E E W E E
A 3 A 1 A-2
to permit operation during servicing.
A 2 A1 A-3
E E
A 4
To open disconnects A and B and breaker D, leaving by-pass
L-O A-1 L-O L-O L-C
disconnect C open:
L-C L-C
1. Proceed from normal position with operations as in 7 to 15
above.
Scheme 10A Scheme 11
To prevent operation of disconnect A and B and by-pass disconnect C To prevent paralleling of lines A and B. Single load, fed from either
under load. Permits by-pass disconnect C to operate only when source.
regulator is in neutral position. Permits isolating regulator for servicing.
A-1 A 2
L-O L-C
C
A B
Disconnect C shown closed and disconnect D shown open. Key A-1 is
REGULATOR held in disconnect C interlock.
1. Open switch C.
2. Turn key A-1 in L-O interlock on switch C to lock open. Key A-1
is now free.
3. Insert key A-1 in L-O interlock on switch D and turn to unlock.
A-3 A1 A 1 A-2 A3 Key A-1 is now held.
4. Close switch D.
L-C L-O L-N L-C L-O
Reverse sequence to restore service through switch C.
One key A-1 is held in regulator L-N (locked neutral) interlock and the
second key A-1 is held in L-O interlock on disconnect A. Key A-2 is held
in L-C interlock on disconnect C. Key A-3 is held in L-O interlock on
disconnect B.
C 1. Open breaker C.
2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1
A2 A-1 A-1 A-2 is now free.
A 1 3. Insert key A-1 in L-O-C interlock on disconnect A and turn to
L-O L-O-C L-O-C L-O unlock. Key A-1 is now held.
L-O 4. Open disconnect A.
5. Turn key A-1 in L-O-C interlock and key A-2 in L-O interlock on
disconnect A to lock open. Keys A-1 and A-2 are now free.
6. Insert key A-1 in L-O-C interlock on disconnect B and turn to
unlock. Key A-1 is now held.
7. Insert key A-2 in L-O interlock on disconnect B and turn to
Breaker C and disconnect A are shown in closed position. Disconnect unlock. Key A-2 is now held.
B is shown in open position. Key A-1 is held in breaker C interlock. Key A- 8. Close disconnect B.
2 is held in L-O interlock on disconnect A. 9. Turn key A-1 in L-O-C interlock on disconnect B to lock
closed. Key A-1 is now free.
To service breaker: 10. Insert key A-1 in breaker interlock and turn to unlock. Key A-1
is now held.
1. Open breaker C. 11. Close breaker.
2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1
is now free. Reverse sequence to restore service through line A.
Scheme 13
To prevent paralleling of lines A and B. Two loads, fed from either source. Breaker A is closed to supply load M. Breaker B is closed to supply load
N. Tie-breaker C is open. Keys A-1 are held in interlocks on both
breakers A and B. Tie-breaker C cannot be closed unless either A or B
is locked open.
1. Open breaker B
2. Turn key A-1 in L-O interlock on breaker B to lock open. Key
A B A-1 is now free.
3. Insert key A-1 in L-O interlock on tie-breaker C and turn to
unlock. Key A-1 is now held.
C 4. Close tie-breaker C.
D E
A-2 A-3
A-3 A-5
L-C L-C
A B
A2 A 3
A B
C A2 A 4
C
L-O L-O A 1 A 1
M N L-O L-O
Breaker A is closed to supply load M. Breaker B is closed to supply load Reverse sequence to restore service (M and N through breakers A
N. Breaker C is closed to supply load P. Keys A-1, B-1, and C-1 are held and B).
in L-O interlocks of breakers A, B, and C. Tie-breakers D and E are Any of the loads M, N, or P can be transferred from its own supply to
locked open. any adjacent supply.
Scheme 17
To prevent paralleling lines A, B, C, and D. Four loads, fed from any To transfer load M from breaker A to breaker B:
source (three tie-breakers).
1. Open breaker A.
2. Turn key A-1 in L-O interlock on breaker A to lock open. Key A-1 is
now free.
A B C D 3. Insert key A-1 in L-O interlock on tie-breaker E and turn to unlock.
Key A-1 is now held.
4. Close tie-breaker E.
E E E E
A1 A B1 B C1 C D1 D
Reverse sequence to restore service through breaker A.
To prevent paralleling lines A, B, C, and D. To prevent opening All loads can be transferred as described in scheme 17.
rear access doors when breakers are energized.
To open rear access doors K-1, K-2, and K-3:
1. Open breaker A.
2. Turn key A-1 in L-O interlock on breaker A to lock
open. Key A-1 is now free.
ACCESS ACCESS ACCESS ACCESS ACCESS ACCESS ACCESS ACCESS ACCESS 3. Open breaker B.
DOOR DOOR DOOR DOOR DOOR DOOR DOOR DOOR DOOR
#1 #2 #3 #4 #5 #6 #7 #8 #9 4. Turn key B-1 in L-O interlock on breaker B to lock open.
E E E E E E E E E
Key B-1 is now free.
K-1 K-2 K-3 K-4 K-5 K-6 K-7 K-8 K-9 5. Insert key A-1 and B-1 in transfer interlock.
L-C L-C L-C L-C L-C L-C L-C L-C L-C 6. Turn key A-1 in transfer interlock. Keys K-1, K-2, and K-
3 are now free. Keys A-1 and B-1 are now held.
7. Insert keys K-1, K-2, and K-3 in their respective rear
access door interlocks and turn to unlock. Keys K-1,
K-2, and K-3 are now held.
K3 W K9
W K6 W
8. Open the rear access doors.
K2 W K5 W W K8
Reverse sequence to restore service.
K1 W K4 W K7 W
E B-1 E C-1 E D-1 To open rear access doors K-4, K-5 and K-6
A-1 E B-1 E C-1 E
1. Open breaker B.
T T T 2. Turn key B-1 in L-O interlock on breaker B to lock open.
Key B-1 is now free.
3. Open breaker C.
A B C D 4. Turn key C-1 in L-O interlock on breaker C to lock
E E E E
open. Key C-1 is now free.
A1 A B1 B C1 C D1 D 5. Insert key B-1 and C-1 in transfer interlock.
6. Turn key B-1 in transfer interlock. Keys K-4, K-5, and K-
6 are now free. Keys B-1 and C-1 are now held.
7. Insert keys K-4, K-5, and K-6 in their respective rear
E F G
access door interlocks and turn to unlock. Keys K-4,
K-5, and K-6 are now held.
E E E 8. Open the rear access doors.
A-1 B-1 C-1
B-1 C-1 D-1
L-O L-O L-O Reverse sequence to restore service.
A1 A B1 B C1 C D1 D
A1 A B1 B C1 C
B-1
C-1
L-O
D E
E F G
N
A-1 C-1
A-1 B-1 A-1
B-1 D-1
B-1 C-1 L-O
D-1
L-O
L-O L-O L-O
A-1 E H
C-1
L-O M N P R
A E B
Breaker A is closed to supply load M.
F Breaker B is closed to supply load N.
H F
Breaker C is closed to supply load P.
M P Breaker D is closed to supply load R. D C
G
Breaker A is closed to supply load M. Breaker B is closed to supply load Keys A-1, B-1, C-1, and D-1 are held in L-O interlocks of breakers A, B, C, and
N. Breaker C is closed to supply load P. Keys A-1, B-1, and C-1 are held D. Tie breakers E, F, G, and H are locked open. Breaker E interlock has a
master or apartment lock and can be unlocked with either key A-1 or B-1.
in L-O interlocks on breakers A, B and C. Tie-breakers D, E, and F are Breaker F interlock has a master or apartment lock and can be unlocked
locked open. Master or apartment lock interlocks are mounted on tie- with either key B-1 or C-1. Breaker G interlock has a master or apartment lock
breakers D, E, and F, and can be unlocked for operation with either and can be unlocked with either key C-1 or D-1. Breaker H interlock has a
keys A-1 or B-1, B-1 or C-1, and A-1 or C-1, respectively. master or apartment lock and can be unlocked with either key A-1 or D-1.
E
B
4. Close tie-breaker E.
To transfer load M from breaker A to breaker B: Reverse sequence to restore service through breaker A.
1. Open breaker A.
2. Turn key A-1 in L-O interlock on breaker A to lock open. Key A- To transfer load M and N from breaker A and B to breaker C:
1 is now free. 1. Close tie-breaker E as above.
3. Insert key A-1 in L-O interlock on tie-breaker D and turn to 2. Open breaker B.
3. Turn key B-1 in L-O interlock on breaker B to lock open. Key B-1 is
unlock. Key A-1 is now held. now free.
4. Close tie-breaker D. 4. Insert key B-1 in L-O interlock on tie-breaker F and turn to unlock.
Reverse sequence to restore service through breaker A. Key B-1 is now held.
5. Close tie-breaker F.
To transfer load M and N from breakers A and B to breaker C: Reverse sequence to restore service (M and N) through breakers A and B.
1. Close tie-breaker D as above.
2. Open breaker B. To transfer load R from breaker D to breaker C:
3. Turn key B-1 in L-O interlock on breaker B to lock open. Key B- 1. Open breaker D.
1 is now free. 2. Turn key D-1 in L-O interlock on breaker D to lock open. Key D-1 is
now free.
4. Insert key B-1 in L-O interlock on tie-breaker E and turn to
3. Insert key D-1 in L-O interlock on tie-breaker G and turn to unlock.
unlock. Key B-1 is now held. Key D-1 is now held.
5. Close tie-breaker E. 4. Close tie-breaker G.
Reverse sequence to restore service (loads M and N) through breakers Reverse sequence to restore service through breaker D.
A and B.
To transfer load M from breaker A to breaker D:
To transfer load P from breaker C to breaker A: 1. Open breaker A.
1. Open breaker C. 2. Turn key A-1 in L-O interlock on breaker A to lock open. Key A-1 is
2. Turn key C-1 in L-O interlock on breaker C to lock open. Key now free.
3. Insert key A-1 in L-O interlock on tie-breaker H and turn to unlock.
C-1 is now free. Key A-1 is now held.
3. Insert key C-1 in L-O interlock on tie breaker F and turn to 4. Close tie-breaker H.
unlock. Key C-1 is now held. Reverse sequence to restore service through breaker A.
4. Close tie-breaker F. Any of the loads M, N, P, or R can be transferred from its own supply to any
Reverse sequence to restore service through breaker C. adjacent supply.
Scheme 20
To prevent paralleling three power sources through a common tie bus not Breakers A, B, and C are normally closed. Breakers D, E, and F are normally
normally in service. To permit feeding any load bus from a second power open. Under normal conditions keys A-1 and A-5 are held in breaker A
source through the tie bus. To permit one power source to supply all three interlock, keys A-2 and A-5 are held in breaker B interlock, and keys A-3 and
load busses through the tie bus. A-5 are held in breaker C interlock.
To transfer load from line No. 1 to line No. 2 or line No. 3 through the tie
bus, proceed as follows:
Load Bus Load Bus Load Bus To transfer load from lines No. 1 and No. 2 to line No. 3 through tie bus,
proceed as follows:
Scheme 21
To prevent paralleling three power sources through a common tie bus not Breakers A, B, and C are normally closed. Breakers D, E, and F are normally
normally in service. To permit feeding any load bus from a second power open. Under normal conditions key A-1 is held in breaker A interlock, key A-2
source through the tie bus only when authorized by supervisor. To permit is held in breaker B interlock, and key A-3 is held in breaker C interlock. Key
one power source to supply all three load busses through the tie bus only A-5 is retained by supervisor.
when authorized by supervisor.
To transfer load from line No. 1 to line No. 2 or line No. 3 through tie bus,
proceed as follows:
1. Open breaker A.
2. Turn key A-1 in L-O interlock on breaker A to lock breaker open.
Line 1 Line 2 Line 3
Key A-1 is now free.
3. Insert key A-1 in L-O interlock on breaker D and turn to unlock.
Key A-1 is now held.
4. Close breaker D.
5. Insert supervisor's key A-5 (only one A-5 is available) in L-O
interlock on either breaker E or F and turn to unlock. Key A-5 is
A A1
B A2
C A3
now held.
6. Close breaker E or F (whichever is selected).
To transfer load from lines No. 1 and No. 2 to line No. 3 through tie bus,
proceed as follows:
A-1 A-2 A-3 1. Close breaker D as per steps 1 to 4 above.
D E F 2. Open breaker B.
A-5 A-5 A-5
3. Turn key A-2 in L-O interlock on breaker B to lock breaker open.
L-O L-O L-O Key A-2 is now free.
4. Insert key A-2 in L-O interlock on breaker E and turn to unlock. Key
A-2 is now held.
5. Close breaker E.
6. Insert supervisor's key A-5 in L-O interlock on breaker F and turn to
Tie Bus unlock. Key A-5 is now held.
A 5
7. Close breaker F.
SUPERVISORY
KEY
Reverse sequence to restore load to lines No. 1 and No. 2.
Scheme 22 Scheme 23 (Continued)
To prevent paralleling incoming primary sources, lines 1 and 2, through
primary tie bus disconnect. To prevent operation (open or closed) of the Line 1 Line 2
disconnects under load. Permits one power source to supply both loads
through tie bus.
Line 1 Line 2
D E
A2 A4 A4 A2
A2 A4 A4 A2
L-C A3 A-2 L-C
L-C L-O
T
T
A5 A C B A5
A1 A3
A B A3 A-5
L-O L-O
Load 1 Load 2
Load 1 Load 2
To transfer load No. 1 from line 1 to line 2 through the secondary tie breaker
C, proceed as follows:
1. Open breaker A.
Scheme 23 2. Turn key A-1 in L-O interlock on breaker A to lock open. Keys A-1
and A-5 are now removable.
To prevent paralleling incoming primary sources, lines 1 and 2, through the 3. Insert key A-5 in L-O interlock on tie breaker C and turn to unlock.
primary tie bus disconnect or the secondary tie bus breaker. To prevent Key A-5 is now held.
operation (open or closed) of the disconnects under load. Permits one 4. Close tie breaker C.
power source to supply both loads through either the primary or secondary Reverse procedure to restore service on line 1. Load No. 2 can be supplied
tie bus. from line No. 1 through the secondary tie breaker C in a similar manner.
Scheme 24
To prevent paralleling incoming primary sources, lines 1 and 2. To To transfer load No. 1 from line 1 to line 2 through bus tie disconnect T,
prevent operation (open or closed) of the disconnects under load. proceed as follows:
(Permits transformer primary disconnects K & L to open and close the
transformer magnetizing current.*) Permits isolating breakers for 1. Open breaker A.
servicing. Permits one power source to supply both loads through tie 2. Turn key A-2 in L-O interlock on breaker A to lock open. Key
bus. A-2 is now free.
3. Open breaker C.
4. Turn key A-4 in L-O interlock breaker C to lock open. Keys A-1
and A-4 are now free.
Line 1 Line 2 5. Insert key A-2 from L-O interlock on breaker A and key A-1
from L-O interlock on breaker C in L-C interlock on
disconnect F and turn to unlock. Keys A-1 and A-2 are now
held.
E G 6. Open disconnect F.
A-3 A2 B2 B-3
7. Turn key A-3 in L-O interlock on disconnect F to lock open.
Keys A-3 and T-1 are now free.
L-C L-O L-O L-C 8. Insert key T-1 in L-O interlock on bus tie disconnect T and turn
to unlock. Key T-1 is now held.
9. Close bus tie disconnect T.
A B 10. Turn key B-1 in L-C interlock on bus tie disconnect T to lock
A2 B2 closed. Keys A-1 and B-1 are now free.
11. Insert key A-1 in L-O interlock on breaker C and turn to
L-O L-O unlock. Keys A-1 and A-4 are now held.
12. Close breaker C.
F H Reverse sequence to restore load No. 1 to line 1. To transfer load No.
T1 A-1 A1 B-1 T1
2 from line 2 to line 1, proceed in a similar manner.
A3 A-2 B1 T-1 B-2 B3
To isolate breaker A for servicing, proceed as follows:
L-O L-C L-C L-O L-C L-O
1. Proceed from normal position with operations as in 1
through 7 above.
2. Insert key A-3 in L-C interlock on disconnect E and turn to
T unlock. Key A-3 is now held.
3. Open disconnect E.
K L 4. Turn key A-2 in L-O interlock on disconnect E to lock open.
A-4 B-4
Key A-2 is now free.
5. Return key A-2 to breaker A and unlock for operation during
L-O-C L-O-C servicing.
A
E E
A 1 A-1
L-O L-C E E E E
A 1 A-1 A 2 A-2
Fuse compartment door and interrupter are shown in closed position. L-O L-O-C L-O L-C
Key A-1 is held in interrupter interlock.
1. Open interrupter.
2. Turn key A-1 in L-O interlock on interrupter switch to lock open.
Key A-1 is now free.
3. Insert key A-1 in L-C interlock on fuse compartment door and A
turn to unlock. Key A-1 is now held.
4. Open fuse compartment door.
1. Open breaker.
E E
2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1
A 1 A-1 is now free.
3. Insert key A-1 in L-O-C interlock on interrupter and turn to
L-O L-O-C unlock. Key A-1 is now held.
4. Open interrupter.
5. Turn key A-1 in L-O-C interlock on interrupter to lock open. Key
Interrupter and breaker are shown in closed position. Key A-1 is held in
A-1 is now free.
breaker interlock.
6. Return key A-1 to breaker interlock and unlock for operation
of breaker during servicing.
1. Open breaker.
2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1
Reverse sequence to restore service.
is now free.
3. Insert key A-1 in L-O-C interlock on interrupter and turn to
To open fuse compartment door, proceed as follows:
unlock. Key A-1 is now held.
4. Open interrupter.
1. Proceed from normal position with operations as in 1 through
5. Turn key A-1 in L-O-C interlock on interrupter to lock open. Key
4 above.
A-1 is now free.
2. Turn key A-2 in L-O interlock on interrupter switch to lock open.
6. Return key A-1 to breaker interlock and unlock for operation
Key A-2 is now free.
of breaker during servicing.
3. Insert key A-2 in L-C interlock on fuse compartment door and
turn to unlock. Key A-2 is now held.
Reverse sequence to restore service.
4. Open fuse compartment door.
1. Close interrupter B.
2. Turn key A-1 in L-C interlock on interrupter B to lock closed.
Key A-1 is now free.
A B 3. Insert key A-1 in L-C interlock on interrupter A and turn to
E E
A-1
unlock. Key A-1 is now held.
A 1
4. Open interrupter A.
L-C L-C
Scheme 29
To prevent paralleling lines A and B requires dropping load when Interrupter switch A is shown closed and interrupter switch B is shown
shifting from one source to the other. To prevent closing both interrupter open. Key A-1 is held in interrupter switch A interlock.
switches A and B at the same time. Permits both interrupter switches to
be opened at the same time. 1. Open interrupter A.
2. Turn key A-1 in L-O interlock on interrupter A to lock open. Key
A-1 is now free.
3. Insert key A-1 in L-O interlock on interrupter B and turn to
A unlock. Key A-1 is now held.
B 4. Close interrupter B.
E E
A 1 A-1
Reverse sequence to restore service through interrupter A.
L-O L-O
Scheme 30
To prevent paralleling lines A and B requires dropping load when To service breaker, proceed as follows:
shifting from one source to the other. To prevent closing both interrupter
switches A and B at the same time. Permits both interrupter switches to 1. Open breaker.
be opened at the same time. To prevent operation (open or closed) of 2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1
either interrupter switch when breaker is closed. Permits breaker to be is now free.
serviced and operated while both interrupter switches are locked 3. Insert key A-1 in L-O-C interlock on interrupter A and turn to
open. unlock. Key A-1 is now held.
4. Open interrupter A.
5. Turn key A-1 in L-O-C interlock on interrupter A to lock open.
Key A-1 is now free.
A B 6. Return key A-1 to breaker interlock and unlock for operation
E E E E of breaker during servicing.
A 2 A-1 A-2 A-1 Reverse sequence to restore service.
L-O L-O-C L-O L-O-C To transfer load from interrupter A to interrupter B:
E E
A2 A-1
E
L-O L-C-O-C
A-1
E
L-C-O-C
A-2
L-C
E
A 1
L-O
E
1. Open breaker. Breaker, fuse compartment door, and interrupter are shown in closed
2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1 position, connected to line B. Key A-1 is held in breaker interlock and
is now free. key A-2 is held in interrupter interlock.
3. Insert key A-1 in L-C-O-C interlock on interrupter and turn to
unlock. Key A-1 is now held. To service breaker, proceed as follows:
4. Open interrupter.
5. Turn key A-1 in L-C-O-C interlock on interrupter to lock open. 1. Open breaker.
Key A-1 is now free. 2. Turn key A-1 in L-O interlock on breaker to lock open. Key A-1
6. Return key A-1 to breaker interlock and unlock for operation is now free.
of breaker during servicing. 3. Insert key A-1 in L-C-O-C interlock on interrupter and turn to
unlock. Key A-1 is now held.
Reverse sequence to restore service through either line A or line B. 4. Open interrupter.
5. Turn key A-1 in L-C-O-C interlock on interrupter to lock open.
To transfer interrupter from line B to line A: Key A-1 is now free.
6. Return key A-1 to breaker interlock and unlock for operation of
1. Proceed from normal position with operations as in steps 1 breaker during servicing.
through 3 above. Reverse sequence to restore service through either line A or line B.
2. Open interrupter switch from line B and connect to line A.
3. Turn key A-1 in L-C-O-C interlock on interrupter to lock closed. To open fuse compartment door:
Key A-1 is now free.
4. Insert key A-1 in L-O interlock on breaker and turn to unlock. 1. Proceed from normal position with operations 1 through 4
Key A-1 is now held. above.
5. Close breaker. 2. Turn key A-2 in L-O interlock on interrupter to lock open. Key A-
2 is now free.
Reverse sequence to restore service through line B. 3. Insert key A-2 in L-C interlock on fuse compartment door and
turn to unlock. Key A-2 is now held.
4. Open fuse compartment door.
Reverse sequence to restore service.
Scheme 34
To prevent opening of guard B for a pre-determined time after TIME DELAY KEY RELEASE UNIT
removal of power.
SIGNAL LIGHT
Starting switch normally closed. Key A-1 is held in starting switch A 2 A-1
interlock. Guard B (or door) is locked closed by means of type D
(detachable) interlock.
To prevent paralleling of any sources while allowing switching of the To prevent paralleling of any sources while allowing switching of the
loads to alternate sources. loads to alternate sources.
GENERATOR A B GENERATOR
A B GENERATOR
A-1
B-1
A-1
H L-O
B-1 A-1 A1 A B B1 G B-1
L-O
A1 A B B1 G B-1
C M N
To prevent closing ground switch B under load and to enable To gain access to capacitor bank enclosure, proceed as
access to the capacitor bank enclosure only after the follows:
capacitor bank has been grounded and discharged.
1. Open breaker A.
CAPACITOR BANK 2. Turn key A-1 in L-O interlock on breaker A to lock
ENCLOSURE
open. Key A-1 is now free.
3. Insert key A-1 in L-O interlock on ground switch B and
turn to unlock. Close ground switch B. Key A-1 is now
ACCESS
#2
A E held.
A-3
4. Turn key A-2 in L-C interlock on ground switch B to
ACCESS L-C lock closed. Key A-2 is now free.
#1
5. Insert key A-2 in L-C interlock (Type M2D) on capacitor
E E E
B bank enclosure access door #1 and turn to unlock.
A1 A-1 A2 W
A3 Key A-2 is now held and key A-3 is now free.
L-O L-O L-C
A-2
E 6. Open access door #1 to enter capacitor bank
L-C
enclosure.
7. Insert key A-3 in L-C interlock (Type D) on access door
#2 and turn to unlock. Key A-3 is now held.
Capacitor bank scheme without time delay. 8. Open access door #2 to enter capacitor bank
enclosure.
Breaker A is closed. Ground switch B is locked open. All
capacitor bank enclosure doors are locked closed. Key A-1 is Reverse sequence to restore service.
held in L-O interlock on breaker A. Key A-2 is held in L-C
interlock on ground switch B. Key A-3 is held in L-C interlock
(Type M2D) on access door #1.
Scheme 38
To prevent closing ground switch B under load and to enable To gain access to capacitor bank enclosure, proceed as follows:
access to the capacitor bank enclosure only after the capacitor
bank has been grounded and discharged.
1. Open breaker A.
CAPACITOR BANK
2. Turn key A-1 in L-O interlock on breaker A to lock open.
ENCLOSURE Key A-1 is now free.
3. Insert Key A-1 in initiating lock on TDKRU. Turn key to start
ACCESS
A E
A-4 4. Signal light energized and key A-2 can be removed
after the prescribed time period. Key A-1 is now held.
L-C
E E E
B ACCESS
#1 5. Insert key A-2 in L-O interlock on ground switch B and turn
A1 A-2 A3
to unlock. Close ground switch B. Key A-2 is now held.
L-O L-O L-C A4
W 6. Turn key A-3 in L-C interlock on ground switch B to lock
E
closed. Key A-3 is now free.
A-3 7. Insert key A-3 in L-C interlock (Type M2D) on capacitor
SIGNAL LIGHT L-C
bank enclosure access door #1 and turn to unlock. Key
A 2 A-1
A-3 is now held and key A-4 is now free.
TIME DELAY KEY RELEASE UNIT 8. Open access door #1 to enter capacitor bank
enclosure.
9. Insert key A-4 in L-C interlock (Type D) on access door #2
Capacitor bank scheme with time delay. and turn to unlock. Key A-4 is now held.
10. Open access door #2 to enter capacitor bank
Breaker A is closed. Ground switch B is locked open. All capacitor enclosure.
bank enclosure doors are locked closed. Key A-1 is held in L-O
interlock on breaker A. Key A-2 is held in Time Delay Key Release Reverse sequence to restore service.
Unit (TDKRU). Key A-3 is held in L-C interlock on ground switch B.
Key A-4 is held in L-C interlock (Type M2D) on access door #1.
Scheme 39 Scheme 40
To prevent improper maintenance bypass of Uninterruptible To prevent improper maintenance bypass of Uninterruptible
Power Supply. Power Supply.
SKRU
SKRU
KIRK
KIRK A1
A1 E
B-1
UPS SYSTEM MAINTENANCE UPS SYSTEM MAINTENANCE
OUTPUT
E BYPASS OUTPUT BYPASS
BREAKER BREAKER BREAKER BREAKER
(NC) (NO) (NC) A A1 A-1 B (NO)
A B1 A-1 B B-1 B1
W W
Solenoid Key Release Unit (SKRU) shown with A-1 Key held Solenoid Key Release Unit (SKRU) shown with A-1 Key held
captive. UPS output breaker A is closed supplying the critical captive. UPS output breaker A is closed supplying the critical
load through the UPS. Key B-1 is held captive in the L-O load through the UPS. A second key A-1 is held captive in the
interlock on breaker A. Maintenance bypass breaker B cannot L-O interlock on breaker A. Key B-1 is held captive in L-O
be closed until the UPS is placed in bypass mode, sending a interlock on maintenance bypass breaker B. Maintenance
signal to the SKRU allowing release of key A-1. The SKRU has an bypass breaker B cannot be closed until the UPS is placed in
apartment lock that will accept either key A-1 or B-1. bypass mode, sending a signal to the SKRU allowing release of
SKRU key A-1.
To supply critical load through the maintenance bypass
breaker, proceed as follows: To supply critical load through the maintenance bypass
1. Place the UPS in bypass mode. breaker, proceed as follows:
2. Upon receipt of the proper signal, key A-1 in SKRU can 1. Place the UPS in bypass mode.
be turned changing status of SKRU internal contacts 2. Upon receipt of the proper signal, key A-1 in SKRU can
and releasing key A-1. be turned changing status of SKRU internal contacts
3. Insert key A-1 in L-O interlock on maintenance bypass and releasing key A-1.
breaker B and turn to unlock. 3. Insert key A-1 in L-O interlock on maintenance bypass
4. Close maintenance bypass breaker B. Key A-1 is now breaker B and turn to unlock.
held. 4. Close maintenance bypass breaker B. Key A-1 is now
5. Open UPS output breaker A. held. Key B-1 is now free.
6. Turn key B-1 in interlock on UPS output breaker A to 5. Open UPS output breaker A.
lock open. Key B-1 is now free. 6. Insert key B-1 in interlock on UPS output breaker A and
7. Insert key B-1 in SKRU and turn to return the SKRU turn to lock open. Key B-1 is now held. Key A-1 is now
internal contacts to the original position. Key B-1 is free.
now held in the SKRU. 7. Insert key A-1 in SKRU and turn returning the SKRU
internal contacts to the original position. Key A-1 is
Reverse sequence to restore equipment to original condition. now held in the SKRU.
Note: Refer to UPS manufacturer's operation and maintenance Reverse sequence to restore equipment to original condition.
manual for instructions regarding transferring the load to the
UPS maintenance bypass source. Persons not familiar with the Note: Refer to UPS manufacturer's operation and maintenance
operation of the UPS system should not attempt to change the manual for instructions regarding transferring the load to the
position the above devices. UPS maintenance bypass source. Persons not familiar with the
operation of the UPS system should not attempt to change the
position the above devices.
Scheme 41
To prevent opening any access doors of a precipitator until all power supplies are de-energized and properly grounded.
E E
A1 A2 A2
SINGLE SINGLE
G-1 G-2 G-3 G-4 INSERTION OF
T/R SWITCH T/R SWITCH
ALL GROUND
SWITCH KEYS
G-6 G-7 G-8 G-9 REQUIRED
E E TO RELEASE
HV A-1 HV A-2 ANY ACCESS
POSITION POSITION D1 D1 D1 DOOR KEYS.
L-C L-O
TR TR D1 D1 D1 D1
E
GROUND E
GROUND
G1 A1
POSITION POSITION D1 D1 D 1 ACCESS DOOR
E E
D-1 D-1 D-1 ACCESS DOOR KEYS ARE
RETAINED WHEN DOOR/HATCH
L-C L-C L-C IS IN THE OPEN POSITION.
ACCESS DOORS
The scheme above represents basic guidelines regarding the proper interlock sequence for an Electro-Static Precipitator. The equipment that
comprises an E.S.P., Scrubber, or Baghouse can vary depending upon the manufacturer and age of the equipment. Let us know your specific needs
and we will be glad to provide a free proposal without obligation.
Scheme 42
To prevent opening any access doors of a precipitator until all power supplies are de-energized and properly grounded.
E E
A1 A2 A3
E E
A1 A2 A3
L-O L-O L-C
TO
REENERGIZE
ONE SIDE
DUAL OUTPUT ONLY DUAL OUTPUT
T/R SWITCH T/R SWITCH TRANSFER PANEL
E E E
HV A-1 A-1 HV HV A-2 G-1 G-1 G-2 G-2
POSITION INSERTION OF
W POSITION POSITION
L-C A1 L-C L-O
ALL GROUND
G-6 G-6 G-7
SWITCH KEYS
TR G-1
E
TR TR
G-7
REQUIRED
TO RELEASE
ANY ACCESS
GROUND E TRANSFER E
GROUND GROUND E
D1 D1 D1 DOOR KEYS.
G1 G1 A1
POSITION POSITION POSITION
L-C L-C L-O
D1 D1 D1 D1
ACCESS DOOR
D1 D1 D 1 KEYS NORMALLY
HELD IN
TRANSFER PANEL.
D1 D1
E E
D-1 D-1 D-1
The scheme above represents basic guidelines regarding the proper interlock sequence for an Electro-Static Precipitator. The equipment that
comprises an E.S.P., Scrubber, or Baghouse can vary depending upon the manufacturer and age of the equipment. Let us know your specific needs
and we will be glad to provide a free proposal without obligation.
When appropriately applied, Kirk Key Interlock systems ensure that a pre-determined sequence of
operation is followed. Kirk Key Interlock systems can prevent expensive machinery and electrical
equipment from being damaged due to operator error. On high-voltage switchgear, the proper use
of Kirk Key interlocks could ultimately save someone’s life.
Most manufacturers provide key interlock provisions on their equipment. With Kirk Key's wide range of
components, it is possible to quickly design and supply an interlock system that is custom designed
for your specific physical requirements. If you need one key, one lock, or a whole interlock system -
Kirk Key is ready to help.
Interlocking is accepted by safety, insurance, and standards authorities throughout the world as the
most reliable and cost effective way of guarding against operator error. If you are concerned about
preserving safety in your sequential operations, let Kirk Key Interlock Company fulfill your needs with a
customized interlocking system for your particular project or operation.
For more information concerning any schemes in this book, or for help in configuring a custom interlock system, please feel free
to contact any one of our Product Coordinators. Kirk Key’s wide range of components makes it possible to quickly design and
supply an interlock system that is custom designed to your specific physical requirements.
1-800-438-2442
www.kirkkey.com