A.C. Static Watthour Meters, Class 1 and 2 - Specification: Indian Standard
A.C. Static Watthour Meters, Class 1 and 2 - Specification: Indian Standard
ICS 91.140.50
© BIS 2020
Equipment for Electrical Energy Measurement, Tariff and Load Control Sectional Committee, ETD 13
FOREWORD
This Indian standard (Second revision) has been adopted by the Bureau of Indian Standards, after the draft finalized
by the Equipment for Electrical Measurement, Tariff and Load Control Sectional Committee and approved by the
Electrotechnical Division Council.
This Indian Standard covers the general requirements and tests for various types of ac static watt-hour meters of
class 1 and 2. General requirements and test applicable to transformer operated meters of class 0.2 S, 0.5 S and
1.0 S with performance levels attainable in such meters have been covered in a separate Indian Standard, i.e.
IS 14697.
This standard was first published in 1993 and subsequently it was revised in 1999. Later on five amendments were
issued. This revision has been bought out to integrate all amendments and update some requirements.
The test levels as specified in this standard are regarded as minimum values to guarantee the proper function of
the meter under normal working conditions. For special applications other test levels might be necessary and have
to be fixed between the user and the manufacturer.
New tests have been added in respect of electromagnetic compatibility (EMC) for which relevant part and section
of IEC 61000/IS 14700 series may be referred. Some of the test requirements have been revised in line with
requirement given in IEC 62052-11 : 2003 and its amendment 1.
The reliability aspect is not covered in this standard as there are no short time test procedures available which
would fit in the type test to substantially check this requirement. Also influence of various harmonics and suitable
test procedures to determine such influence, require detailed consideration for specifying such requirement.
While preparing this standard assistance have been mainly derived from following publications:
IEC 62052-11 : 2003 Electricity metering equipment (a.c.) — General requirements, tests and test
conditions – Part 11 Metering equipment and its amendment 1.
IEC 62053-21 : 2003 Electricity metering equipment (a.c.) — Particular requirements — Part 21:
Static meters for active energy (classes 1 and 2) and its amendment 1.
This standard is for type testing and general requirements of electricity meters (normal meters), being used
indoors and outdoors in large quantities. It does not deal with special implementations (such as metering-part and
or displays in separate housings).
This standard distinguishes between meters intended to be used indoors and outdoors.
The composition of the Committee, responsible for the formulation of this standard is given at Annex J.
For purpose of deciding whether a particular requirement of this standard is complied with the final value,
observed or calculated, expressing the result of a test or analysis shall be rounded off in accordance with
IS 2 : 1960 ‘Rules for rounding off numerical values ( revised ). The number of significant places retained in the
rounded off value should be same as that of the specified value in this standard.
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
Indian Standard
a.c. STATIC WATTHOUR METERS,
CLASS 1 AND 2 — SPECIFICATION
( Second Revision )
1
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
IS 13779 : 2020
3.4.4 Reinforced Insulation carried out under identical conditions, arising out of
A single insulation system applied to live parts, which factors other than measurement uncertainties.
provides a degree of protection against electric shock It is generally measured by standard deviation of
equivalent to double insulation. sufficiently large number of test data. It may also be
NOTE — The term ‘insulation system’ does not imply that the measured by dispersion of such data under limited
insulation must be one homogenous piece. It may comprise condition when sufficiently large data is not available.
several layers which cannot be tested singly as supplementary
or basic insulation. 3.5.8 Starting Current
3.4.5 Insulating Encased Meter The lowest value of current at which the meter starts
and continues to register.
A meter with case of insulating material in which
protection against electric shock does not rely on 3.6 Terms Related to influence Quantities
basic insulation only, but in which additional safety
precautions, such as double insulation of reinforced 3.6.1 Influence Quantity or Influence Factor
insulation, are provided. There being no provision for Any quantity, generally external to the meter, which
protective earth or reliance upon installation conditions. may affect its working performance.
3.5 Terms Related to Meter Quantities 3.6.2 Reference Conditions
3.5.1 Basic Current (Ib) The appropriate set of influence quantities and
performance characteristics, with reference values,
The value of current in accordance with which the their tolerances and reference ranges, with respect to
relevant performance of the meter is fixed. which the intrinsic error is specified.
3.5.2 Rated Maximum Current (Imax) 3.6.3 Variation of Error Due to an Influence Quantity
The highest value of current at which the meter purports The difference between the percentage errors of the
to meet the accuracy requirements of this standard, meter when only one influence quantity assumes
when this current flows continuously in the meter. successively two specified values, one of them being
3.5.3 Reference Voltage the reference value.
The value of voltage in accordance with which the 3.6.4 Distortion Factor
relevant performance of the meter is fixed. The ratio of the r.m.s. value of the harmonic content
3.5.4 Reference Frequency (obtained by subtracting from a non-sinusoidal
The value of frequency is accordance with which the alternating quantity, its fundamental component) to
relevant performance of the meter is fixed. the r.m.s. value of the non-sinusoidal quantity. The
distortion factor is usually expressed in percentage.
3.5.5 Class Index
3.6.5 Electromagnetic Disturbance
A number which gives the limits of the permissible
percentage error, for all values of current between Conducted or radiated electromagnetic effects which
0.1 Ib and Imax for unity power factor (and in the case may interfere functionally or metrologically with the
of polyphase meters with balanced loads) when the operation of the meter.
meter is tested under reference conditions (including 3.6.6 Reference Temperature
permitted tolerances on the reference values) as defined
in this standard. The ambient temperature specified for reference
conditions.
3.5.6 Percentage Error
3.6.6.1 Mean temperature coefficient
The percentage error is given by the following formula:
The ratio of the variation of the percentage error to
( Energy registered by the meter − true energy ) the change of the temperature which produces this
Percentage error × 100
True energy
variation.
NOTE — Since the true value cannot be determined, it is
approximated by a value with a stated uncertainty that can
3.6.7 Operating Conditions
be traced to IS 12346 or standards agreed upon between A set of specified measuring ranges for performance
manufacturer and user. characteristics and specified operating ranges for
3.5.7 Repeatability of Error influence quantities, within which the variations
in percentage errors of a meter are specified and
Repeatability of error is the degree of closeness of determined.
agreement between results of successive error for tests
3
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
4
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
5.4 Standard Frequency The material of which the terminal block is made
Standard value for reference frequency is 50 Hz. shall be capable of passing the tests given in
IS 13360 (Part 6/Sec 17) for a temperature of 135 °C
6 GENERAL AND CONSTRUCTIONAL and a pressure of 1.8 MPa (Method A).
REQUIREMENTS The holes in the insulating material which form an
extension of the terminal holes shall be of sufficient size
6.1 General to also accommodate the insulation of the conductors.
Meters shall be designed and constructed in such a way The manner of fixing the conductors to the terminals
as to avoid introducing any danger in normal use and shall ensure adequate and durable contact such that
under normal conditions, so as to ensure especially: there is no risk of loosening or undue heating. Screw
a) Personal safety against electric shock; connections transmitting contact force and screw
b) Personal safety against effects of excessive fixings which may be loosened and tightened several
temperature; times during the life of the meter shall screw into a
metal nut.
c) Safety against spread of fire; and
All parts of each terminal shall be such that the risk of
d) Protection against solid objects, dust and water.
corrosion resulting from contact with any other metal
All parts which are subject to corrosion under normal part is minimized.
conditions shall be effectively protected. Any protective
coating shall not be liable to damage by ordinary The current circuit connections can be terminated or
handling nor damage due to exposure to air, used under guided through the measuring element of meter. The
normal working conditions. cable/conductor in such a design shall be held firmly
in position by suitable guiding and fixing arrangement
NOTE — For meters for special use in corrosive atmosphere,
and that contact pressure is not transmitted through
additional requirements shall be fixed in the purchase contract
(for example, salt mist test).
insulating material. For current circuits, the voltage
is considered to be the same as for the related voltage
6.2 Meter Case circuit.
The meter shall have a reasonably dust/moisture-proof The voltage circuit connection can be directly
case, which shall be sealed by the manufacturer in such terminated on a suitable terminal arrangement or
a way that the internal parts of the meter are accessible tapped by suitable arrangement which shall not cause
only after breaking such distinctive seal(s). burnouts and corrosion due to outdoor usage.
The cover shall not be removable without the use of a Terminals with different potentials which are grouped
tool. close together shall be protected against accidental
The case shall be so constructed and arranged that short-circuiting. Protection may be obtained by
any non-permanent deformation cannot prevent the insulating barriers. Terminals of one current circuit are
satisfactory operation of the meter. considered to be at the same potential.
Unless otherwise specified, the meters having a case The terminals, the conductor fixing screws, or the
wholly or partially made of metal, shall be provided external or internal conductors shall not be liable to
with a protective earth terminal. come in to contact with terminal covers (if made of
metals).
6.3 Window The protective earth terminal, if any:
If the cover is not transparent one or more windows shall a) Shall be electrically bonded to the accessible
be provided for reading the displays and observation of metal parts;
the operation indicator, if fitted. These windows shall
be covered by toughened transparent material which b) Should, if possible, form part of meter base;
cannot be removed undamaged without breaking the c) Should preferably be located adjacent to its
seal(s). terminal block;
d) Shall accommodate a conductor having a cross
6.4 Terminals, Terminals Block(s) and Protective
section at least equivalent to the main current
Earth Terminal
conductors but with a lower limit of 6 mm2 and
Terminals may be grouped in (a) terminal block(s) an upper limit of 16 mm2 (for copper conductors);
having adequate insulating properties and mechanical and
strength. In order to satisfy such requirements when e) Shall be clearly identified by the earthing symbol.
choosing insulating materials for the terminal block(s),
adequate testing of materials should be taken into After installation, it shall not be possible to loosen the
account. protective earth terminal without the use of a tool.
5
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
6
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
non-volatile memory shall have a minimum retention the cover, the number is to be marked also on the
time of 5 years. Manufacturer shall declare the retention meter base or displayed;
time. e) The reference voltage in one of the following
NOTE — Longer retention time of the non-voltaic memory forms:
should be the subject of purchase contract. The number of elements if more than one, and
In the case of multiple values presented by a single the voltage at the meter terminals of the voltage
display, it must be possible to display the contents of circuit(s).
all relevant memories. When displaying the memory, 1) The nominal voltage of the system or
identification of each tariff/parameter shall be available. the secondary voltage of the instrument
The current tariff shall be indicated. When the meter is transformer to which the meter is intended to
not energised; the electronic display need not be visible. be connected.
The principal unit for the measured values shall be kilo 2) Examples of voltage markings are shown in
watthour (kWh) or the mega watthour (MWh). Table 5.
The register shall be able to record and display starting f) Principal unit in which the meter reads, for
from zero, for a minimum of 1 500 h, the energy example, kWh.
corresponding to rated maximum current at reference g) The rated secondary current of the transformer(s)
voltage and unity power-factor. Register should not to which the meter should be connected, for
rollover in between this duration. example, –/5 A: the basic current and the rated
NOTE— Values higher than 1500 h should be the subject of maximum current of the meter may be included in
purchase contract. the type designation.
Examples of current markings are shown in Table 6.
6.11 Output Device
Table 5 Voltage Markings
The meter shall have a test output accessible from the
front and be capable of being monitored with suitable [ Clause 7.1 (e) ]
testing equipment. The operation indicator, if fitted, Type of Meter Method of Marking Example
must be visible from the front.
(1) (2) (3)
Since the sequence of test output pulses may not 1- phase, 2-wire Voltage between line 240 V
be homogeneous, the manufacturer shall state the and neutral
minimum number of pulse counts necessary to ensure 3-phase, 3-wire 2 × Voltage between 2 × 110V
that the error contribution due to such non-homogeneity lines
does not exceed 1/10th of the specified error limits at 3-phase, 4-wire 3 × Voltage between 3 × 110/√3 V, 3 × 240
various points and consistent with desired resolution. line and neutral V or 3 × 63.5V
The resolution of the test output in the form of pulses Table 6 Current Markings
or high resolution register, whether accessible on the
[ Clause 7.1 (g) ]
meter through external display, shall be sufficient to
conduct satisfactorily accuracy test at the lowest load in Type of Meter Method of Example
less than 5 min and starting current test in less than 10 Marking
min. Additional high resolution register with minimum (1) (2) (3)
decimal of two digits shall also be available in the 1-phase , whole current, Basic current and 10-20 A
meter for testing purpose as mentioned in this standard. Ib 10 A, Imax 20 A rated maximum
current
7 MARKING OF METERS 1-phase, transformer operated, Basic current and –/1(1.2) A
Ib 1A, Imax 1.2 A rated maximum
current
7.1 Name Plate
3-phase, whole current, Basic current and 50 – 60 A
Every meter shall bear the following information: Ib 50 A, Imax 60 A rated maximum
current
a) Manufacturer’s name and/or trade mark and the
3-phase, transformer operated, Basic current and -/5 (6) A
place of manufacture; Ib –/5A, Imax 6 A rated maximum
b) Designation of type (see 3.1.4) and, if required, current
space for approval mark; h) The reference frequency in Hz;
c) The number of phases and the number of wires for j) The meter constant, for example in the form; X
which the meter is suitable (for example, single Wh/imp or X imp/kWh;
phase 2 wire, three phase 3 wire, three phase 4
k) The class index of the meter;
wire). These markings may be replaced by the
graphical symbols (as per IS 12032 series); m) The reference temperature if different from 27 °C;
d) The serial number and year of manufacture. If n) The sign of double square for insulating encased
the serial number is marked on a plate fixed to meters; and
7
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
8
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
9
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
10
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
Table 16 Percentage Error Limits (Polyphase Meters Carrying a Single Phase Load, But with Balanced
Polyphase Voltages Applied to Voltage Circuits)
( Clause 11.1 )
Value of Current Power Factor of Relevant Percentage Error Limits for
Element Meters of Class
For direct connected meters For transformer operated meters 1 2
(1) (2) (3) (4) (5)
0.1 Ib ≤ I ≤ Imax 0.05 Ib ≤ I ≤ Imax 1 ± 2.0 ± 3.0
0.2 Ib ≤ I ≤ Imax 0.1 Ib ≤ I ≤ Imax 0.5 lagging ± 2.0 ± 3.0
NOTES 4 The test conditions are given in Annex C. This test does not
1 For the voltage ranges from –20 percent to –10 percent and apply to transformer operated meters.
+10 percent to +20 percent, the limits of variation in percentage 5 The test conditions are specified in 12.11.
error are three times the values given in Table 17. 6 A magnetic induction of external origin of 0.5 mT produced
Below 0.8 Vref and upto 0.7 Vref, the said limits are five times by a current of the same frequency as that of the voltage applied
the value given in Table 17. to the meter and under the most unfavourable conditions of
Below 0.7 Vref the error of the meter may vary between phase and direction shall not cause a variation in the percentage
+10 percent and –100 percent. error of the meter exceeding the values shown in Table 17. The
test conditions are specified in 12.11.
2 The distortion factor of the voltage shall be less than
1 percent. The variation in percentage error shall be measured 7 The test conditions are specified in 12.9.3
under two conditions. The peak of third harmonic in the first 8 Such an accessory, enclosed in the meter case is energized
measurement in phase and in the second measurement in intermittently, for example, the electromagnet of a multi-rate
antiphase of the peaks of the fundamental current. register.
3 The polyphase meter shall measure and register within the 9 The test conditions are specified in 12.11. In the event of
variation in percentage error limits shown in Table 17 if one logging of abnormal magnetic induction with date and time,
or the two phases of the 3-phase network are interrupted, the positive variation may be beyond the limit of 4 percent but
provided the reference phase is available that is Y-phase for not exceeding a power value equivalent to the product of rated
3-phase 3-wire meters and neutral for 3-phase 4-wire meters. voltage and maximum current.
However, the operation of the meter shall not be affected by 10 The test conditions are specified in 12.9.4.
such removal of reference phase.
11
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
12
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
1.2 a.c. high voltage test 12.7.6.3 A R 6.3 Spring hammer test 12.3.3
13
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
14
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
12.7.2 Test of Influence of Supply Voltage their thermal time constants) carrying 1.15 times the
The test shall be carried out under the following reference voltage, the temperature rise of the external
conditions: surface shall not exceed by more than 20 °C, with the
ambient temperature between 25 °C to 45 °C.
a) Meter in operating condition,
During the test, the duration of which shall be 2h, the
b) Voltage and auxiliary circuits energised with meter shall be not exposed to draught or direct solar
reference voltage, radiation.
c) Without any current in the current circuits:
After the test, the meter shall show no damage and shall
1) Voltage interruptions of Vref = 100 percent comply with the dielectric tests of 12.7.6.4.
i) Interruption time: 1 s
12.7.6 Test of Insulation Properties
ii) Number of interruptions: 3
iii) Restoring time between interruptions: 50 12.7.6.1 General test conditions
ms (see also Annex D) The test shall be carried out only on a complete meter
2) Voltage interruption of Vref = 100 percent with its cover (except when indicated hereafter) and
i) Interruption time: 20 ms terminal cover, the terminal screws being screwed
down to maximum applicable conductor fitted in the
ii) Number of interruptions: 1 (see also terminals. Test procedure shall be in accordance with
Annex D) IS 2071 (Part 1).
3) Voltage dips of Vref = 50 percent
The impulse voltage tests shall be carried out first and
i) Dip time: 1 min the a.c. high voltage tests afterwards.
ii) Number of dips: 1 (see also Annex D) During type tests, the dielectric property tests are
For requirement, see 9.2.2 considered to be valid only for the terminal arrangement
of the meter which has undergone the tests. When the
12.7.3 Test of Influence of Short Time Over Currents terminal arrangements differ, all the dielectric property
The test circuit shall be practically non-inductive. tests shall be carried out for each arrangement.
After the application of the short-time over current For the purpose of these tests, the ‘earth’ has the
with the voltage maintained at the terminals, the meter following meaning:
shall be allowed to return to the initial temperature with a) When the meter case is made of metal, the earth is
the voltage circuit(s) energised (about one hour). For the case itself placed on a flat conducting surface.
requirement, see 9.2.3
b) When the meter case or only a part of it is made
12.7.4 Test of Influence of Self-Heating of insulating material, the earth is a conductive
foil wrapped around the meter, touching all
The test shall be carried out as follows:
accessible conductive parts and connected to the
After the voltage circuits have been energised at flat conducting surface on which the meter base
reference voltage for at least 2 h, meters without any is placed. Where the terminal cover makes it
current in the current circuits, the rated maximum current possible, the conductive foil shall approach the
shall be applied to the current circuits. The meter error terminals and holes for the conductors within a
shall be measured at unity power-factor immediately distance of not more than 2 cm.
after the current is applied and then at intervals short
During the impulse and the a.c. voltage tests, the circuits
enough to allow a correct drawing to be made of the
which are not under test are connected to the earth as
curve of error variation as a function of time. The test
indicated hereafter. A flashover (capacitance discharge)
shall be carried out for at least 1 h and in any event until
during impulse test is not necessarily a criterion of
the variation of error during 20 min does not exceed 0.1
failure as this may occur in a position that does not
percent or the measurement uncertainties whichever is
damage and the manufacturer shall decide, whether or
greater. Maximum test duration shall not be more than
not to eliminate the cause. The meter shall withstand
2 h. The same test shall be carried out at 0.5 (lagging)
a.c. voltage as per 12.7.6.3 and insulation resistance is
power factor. The variation of error, measured as
as per 12.7.6.4.
specified, shall not exceed the values given in Table 13.
For test requirement see 9.3. In this sub-clause, the expression all the terminals
means the whole set of the terminals of the current
12.7.5 Test of Influence of Heating circuits, voltage circuits and, if any, auxiliary circuits
With each current circuit of the meter carrying rated having a reference voltage over 40 V.
maximum current and with each voltage circuits These shall be made in normal conditions of use.
(and with those auxiliary, voltage circuits which During the test, the quality of the insulation shall not be
are energised for periods of longer duration than impaired by dust or abnormal humidity.
15
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
Unless otherwise specified, the normal conditions for and appropriately insulated (for example, each circuit
insulation test are: connected to measuring transformer) the test shall be
a) Ambient temperature: 20 °C to 35 °C; made separately on each circuit.
b) Relative humidity: 45 percent to 95 percent; and During the test of a current circuit, the terminals of
the other circuits shall be connected to earth and the
c) Atmospheric pressure: 86 to 106 kPa (860 mbar to
impulse voltage shall be applied between one of the
1060 mbar).
terminals of the current circuit and earth. During the
12.7.6.2 Impulse voltage test test of a voltage circuit, the terminals of the other
circuits and one of the terminals of the voltage circuit
The impulse of 6 kV is applied ten times with one
under test shall be connected to earth and the impulse
polarity and then repeated with the other polarity.
voltage shall be applied between the other terminal of
The minimum time between the impulses shall be 3 s.
the voltage circuit and earth.
The waveform and the generator characteristics shall
be in accordance with IS 2071 (Part 1) with source The auxiliary circuits intended to be connected either
impedance 500 ohm ± 50 ohm and source energy directly to the mains or to the same voltage transformers
0.5 J ± 0.05 J as the meter circuits and with a reference voltage over
40 V shall be subjected to the impulse voltage test in
a) Impulse voltage tests for circuits and between the
the same conditions as those already given for voltage
circuits
circuits. The other auxiliary circuits shall not be tested.
The test shall be made independently on each circuit
(or assembly of circuits) which are insulated from the b) Impulse voltage test of electric circuits relative to
other circuits of the meter in normal use. The terminals earth
of the circuits which are not subjected to impulse All the terminals of the electric circuits of the meter,
voltage shall be connected to earth. including those of the auxiliary circuits with a reference
voltage over 40 V, shall be connected together.
Thus, when in normal use the voltage and the current
circuits of measuring elements are connected together, The auxiliary circuits with a reference voltage below or
the test shall be made on the whole. The other end equal to 40 V shall be connected to earth.
of the voltage circuit shall be connected to earth and The impulse voltage shall be applied between all the
impulse voltage shall be applied between the terminal electric circuits and earth.
of the current circuit and earth. When several voltage
circuits of a meter have a common point, this point 12.7.6.3 a.c. voltage test
shall be connected to earth and the impulse voltage The a.c. voltage test shall be carried out in accordance
successively applied between each of the free ends of with Table 21 for type test and acceptance test of new
the connections (or the current circuit connected to it) meters. For any subsequent test, the voltage applied
and earth. shall be 80 percent of the test voltage indicated in the
When in normal use, the voltage and the current Table 21.
circuits of the same measuring element are separated
16
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
The test voltage shall be substantially sinusoidal, The meter shall be in operating condition:
having a frequency between 45 Hz and 55 Hz, and a) Voltage circuits and auxiliary power supply
applied for one minute for type test and acceptance test. circuits energized with reference voltages; and
The test duration for routine test shall be minimum 5 s.
The power source shall be capable of supplying at least b) Without any current in the current circuits and the
500 VA. current terminals shall be open circuit.
IS 13779 : 2020
c) Basic current Ib and Cos θ = 1 h) Number of tests: 5 positive and 5 negative; and
During the test, the behaviour of the equipment shall not j) Repetition rate: maximum 1/min.
be perturbed and the variation of error shall be within the The application of test shall not produce change in
limits as specified in Table 17. Frequency at which the register of more than 0.01 kWh and the test output shall
meter is affected shall be reported. not produce a signal equivalent to more than 0.01 kWh.
These values are based on the rated current of 5A and
12.9.4 Fast Transient Burst Test
100 V of the meter. For other voltage and current ratings,
The test shall be carried out according to the value 0.01 kWh has to be converted accordingly.
IS 14700 (Part 4/Sec 4) under the following conditions:
During the test, a temporary degradation or loss of
a) Tested as table top equipment; function or performance is acceptable.
b) Meter in operating condition:
12.9.6 Radio Interference Measurement
1) Voltage and auxiliary circuits energized with
reference voltage, or The test for radio interference shall be carried out as per
IS 6873 (Part 2/Sec 1). The input to be applied to meter
2) With basic current in current circuit, PF is unity.
during test is reference voltage, load current between
c) Cable length between coupling device and EUT: 0.1 Ib to Ib at UPF.
1m
a) Test for conducted emission for the frequency range
d) Test voltage shall be applied in common mode (line 0.15 Mhz to 30 Mhz.
to earth) to:
The test shall be carried out on mains part as per
1) The voltage circuits; clause 4.3.3 of IS 6873 (Part 2/Sec 1). For mains
2) The current circuits, if separated from the parts, the limit specify in column 2 and 3 of Table 5
voltage circuits in normal operation; or of IS 6873 (Part 2/Sec 1) apply.
3) The auxiliary circuit; if separated from the b) Test for radiated emission for frequency range
voltage circuits in normal operation. 30 Mhz to 300 Mhz.
e) Test voltage on current and voltage circuit: 4 kV The test shall be carried out as per clause 5.3.3 or 5.3.4
f) Test voltage on auxiliary circuits with a reference of IS 6873 (Part 2/Sec 1). The limits specified in column
voltage above 40 V: 2 kV 2 and 3 of Table 7 or of Table 9 respectively, of IS 6873
g) Duration of test: 60 s at each polarity (Part 2/Sec 1) apply.
NOTE — Accuracy may be determined by the registration 12.10 Test of Accuracy Requirements
method or other suitable means.
12.10.1 General Test Conditions
During the test, temporary degradation or loss of function
or performance is acceptable, nevertheless the variation Determination of meter errors for the purpose of
of the error shall be within the limits as specified in verification of accuracy requirement (see 11) and
Table 17. verification of such errors for the purpose of other
requirements shall be carried out in a meter testing station
12.9.5 Surge Immunity Test having meter testing equipment of relevant accuracy
The test shall be carried out according to class as laid down in IS 12346.
IS 14700 (Part 4/Sec 5) under the following conditions The following test conditions shall be maintained:
with meter in operating condition:
a) The meter shall be tested in its case with cover in
a) Voltage and auxiliary circuits energized with position, all parts intended to be earthed shall be
reference voltage; earthed;
b) Without any current in the current circuits and the b) Before any tests are made, the circuits shall have
current terminals shall be open circuit; been energised for a time to reach thermal stability;
c) Cable length between surge generator and meter: c) In addition, for polyphase meters:
1m
1) The phase sequence shall be as marked on the
d) Tested in differential mode (line to line); diagram of connections, or
e) Phase angle: pulses to be applied at 60° and 240° 2) The voltages and currents shall be substantially
relative to zero crossing of a.c. supply; balanced (see Table 23 and 24).
f) Test voltage on the current and voltage circuits d) The minimum test period at any test point shall
(main lines): 4 kV, generator source impedance: contain sufficient number of power cycles
2 ohm (not less than 20 seconds) to take care
g) Test voltages on auxiliary circuits with a reference instantaneous power Variation within a cycle.
voltage over 40 V: 1 kV; Generator source The maximum test period is however determined
impedance: 42 ohm; by homogeneity and resolution of test output
(see 6.11); and
18
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
19
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
20
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX A
( Clause 2 )
LIST OF REFERRED INDIAN STANDARDS
21
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX B
( Clause 8.2 )
RELATIONSHIP BETWEEN AMBIENT AIR TEMPERATURE AND RELATIVE HUMIDITY
22
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX C
( Table 17 Note 4 )
NOTES
1 The balancing impedance shall be equal to the equipment under test (EUT) to ensure the measurement accuracy.
2 It is recommended to use a meter of same type as the EUT in place of balancing impedance.
3 The rectifier diodes shall be of the same type.
4 To improve the balancing condition an additional resistor or RB can be introduced in both paths. Its value should be approximately
10 times the value of the EUT.
5 The influence of the d.c. components and even harmonics in the a.c. current shall be checked at 0.5 Ib, 0.5 Imax and any current between
0.5 Ib and 0.5 Imax. Current in the standard meter is 2/√2 times the current in meter under test [for example, for 0.5 Ib in meter under test,
current in standard meter will be (2/√2) 0.5 Ib].
6 With above connections, the EUT will measure half of the energy measured by standard meter.
23
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
24
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX D
( Clause 12.7.2 )
VOLTAGE WAVE FROM THE TESTS OF INFLUENCE OF SUPPLY VOLTAGE
25
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX E
( Clauses 9.6 and 12.8 )
TEST CIRCUIT DIAGRAM FOR THE TEST OF IMMUNITY TO EARTH FAULT
26
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX F
( Clause 12.11 )
ELECTROMAGNET FOR TESTING THE INFLUENCE OF
EXTERNALLY PRODUCED MAGNETIC FIELDS
All dimensions in mm
27
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX G
( Clause 12.2.2.1 )
RECOMMENDED SAMPLING PLAN
28
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX H
( Clause 7.2 )
STANDARD CONNECTION DIAGRAMS
The standard connection diagrams are given below. phase of a single phase supply is generally marked
The phase supply terminals ate generally marked ‘M’. It should be noted that each individual metered
as ‘R’, ‘Y’ and ‘I’ though other conventions are also connection for independent load should be given an
acceptable if suitably marked on the terminal block independent set of phase and neutral connections direct
cover. The neutral terminal marked as ‘N’ and the from the supply side.
29
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
Fig. H-3 Three Phase Three Wire Meter for Direct Connection
Fig. H-4 Three Phase Three Wire Meter for Current Transformers
Fig. H-5 Three Phase Four Wire Single Tariff Meter for Direct Connection
30
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
Fig. H-6 Three Phase Four Wire Meter with Current Transformers
Fig. H-7 Three Phase Four Wire Meter for Direct Connection
(Meters with no terminals for current circuits, i.e, load current carrying conductors are not terminated at the
meter and are passed through current measuring sensors)
31
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
ANNEX J
( Foreword )
COMMITTEE COMPOSITION
Equipment for Electrical Energy Measurement, tariff and Load Control Sectional Committee, ETD 13
32
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
IS 13779 : 2020
Member Secretary
Ms Meghna Mudgal
Scientist ‘B’ (ETD), BIS
33
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
Free Standard provided by BIS via BSB Edge Private Limited to Kartikeya sharma -
gandhinagar(kartikeya.sharma@gmail.com) 61.2.224.16 [for non-commercial use only].
BIS is a statutory institution established under the Bureau of Indian Standards Act, 2016 to promote harmonious
development of the activities of standardization, marking and quality certification of goods and attending to
connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form without
the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the
standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to
copyright be addressed to the Director (Publications), BIS.
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards: Monthly Additions’.
This Indian Standard has been developed from Doc No.: ETD 13 (11300).