The  document  describes  the  Firmware  and  Hardware
Provisions in ABT meter required standards 
 IS 14697  AC Static Watthour Meters Class 1 and 2 - Specification 
IS 15959  Indian DLMS standard  
CBIP-88 
Specification for AC Static Electrical Energy Meters 
CBIP  technical 
report No. 304. 
Specification  for  AC  Static  Electrical  Energy  Meters.  With  latest 
amendments 
IS 15707  Testing,  Evaluation,  Installation  and  Maintenance  of  AC  Electricity 
Meters- Code of Practice 
IS 12063   
IS 12346  Specification for testing equipments for ac energy Meters 
IS 9000  Basic Environmental Testing Procedures for Electronic & Electrical 
items. 
DIN 43859  Watthour  meters  for  instrument-transformer  connection;  main 
dimensions for three-phase meters 
IEC 61000-4-3  Electromagnetic  compatibility  (EMC)  -  Testing  and  measurement 
techniques  -Radiated,  radio-frequency,  electromagnetic  field 
immunity test   
IEC 61000-4-5  Electromagnetic  compatibility  (EMC)  -  Testing  and  measurement 
techniques  Surge immunity test 
IEC  62052-11  
Electricity metering equipment (AC)  
General requirements, tests, and test conditions 
IEC  62053-22  
Electricity metering equipment (AC)  
Static meters for active energy class 0.2 and 0.5) 
IEC  62053-23  
Electricity metering equipment (AC)  
Static meters for reactive energy class 2 and 3) 
IEC 60529  Degrees of protection provided 
by enclosures (IP Code)  
HW Provisions  
The PCB of the meter is designed to meet the below specifications.  
Basic requirements 
Meter standards  
The ABT meter fulfills the following meter standards:  
  IS14697 
  CBIP-304 
  IEC62052-11  General requirements for electricity meters 
  IEC62053-22  electricity meters for active energy (class 0.2s and 0.5s)   
Nominal voltages 
  63.5V  -40% +20% 
  110 -40%  -40% +20% 
.  
Nominal current 
The ABT meter offers the following current range: 
  1(2)A or 5(10)A 
Nominal frequency 
The ABT works with the following frequencies:  
  50 Hz, +/- 5%  
Measurement possibilities 
It measures the following quantities:  
  Active energy, kWh 
  Reactive energy, kVARh 
  Apparent energy, kVAh 
  Current,  voltage,  active  power,  reactive  power,  apparent  power,  power  factor,  power 
factor angle, Voltage angle on all Phases and system. 
  Phase to Phase Voltage 
  Frequency. 
  %THD for Voltage And Current            
LCD 
The LCD of the meter has the following features:  
  Number of digits for identifier      7 digits 
  The digit size for identifier                 Min.5x3 mm 
  Number of digits for energy data      8 digits 
  The digit size main digit          10x5 mm 
  Inter digit gap          1mm 
  Side gap            2mm  
LCD  will  be  having  backlit.  The  LCD  is  of  STN  type  construction  suitable  for  temperature  80 
Deg.C storage and 65 Deg.C operation. The LCD has a wide viewing angle of 45 deg to 60 deg 
cone, up to one meter distance. 
Life time:100k hours 
Temp range Operating: -30 to 80 deg C 
Temp range Storage:   -40 to 80 deg C  
Apart  from  Provision  for  display  of  Identifiers  and  main  digits,  the  LCD  also  has  provision  for 
display of the follows: 
1)  The quadrant of operation 
2)  The presence of phase Voltage 
3)  Indicator for Current reversal 
4)  Top cover opening indication. 
5)  Magnetic tamper indication   
Display Modes  
The meter has 3 display modes. 
1)  Normal 
2)  Alternate 
3)  High Resolution Mode  
Normal Mode: In the normal mode the display parameters will scroll. The display hold time will 
be programmable. There will be an indication to indicate the communication is on.  
Alternate Mode: The pressing of a button will start or stop this mode. The display will scroll the 
parameters  in  up  or  down  direction  based  on  the  pressing  of  a  button.  There  will  be  an 
indication to indicate the communication is on.  
High Resolution Mode: The pressing of a button will start or stop this mode. The display  will 
scroll the parameters in up or down direction based on the pressing of a button. There will be an 
indication  to  indicate  the  communication  is  on.  The  meter  will  display  the  energy  parameters 
with 2 integers and 4 decimals.        
Normal Display Resolution:  
1.  Voltage    = 0.01V 
2.  Current    = 0.001A 
3.  PF      = 0.01 
4.  Active Energy  = 0.001kWh 
5.  Apparent Energy  = 0.001kVAh 
6.  Reactive Energy  = 0.001kVARh 
7.  Demand    = 0.001kVA/kW   
Enclosure 
The ABT meter offers the following features: 
  Unbreakable,  high  grade,  flame  retardant  polycarbonate  with  thickness  more  than 
2.0 mm, and of good dielectric and mechanical strength. The material of meter base 
& terminal block shall be glass reinforced 
The detachable terminal block shall be moulded type made of non-hygroscopic, flame retardant 
material  having  good  dielectric  and  mechanical  strength.  The  molded  terminal  block  shall  be 
made from 10- 20% glass filled polycarbonate material conforming to FH-1 of IS 11731 (Part-I) 
having adequate insulating properties and mechanical strength with brass inserts for connecting 
terminals. The terminal block satisfy  all the conditions specified in IEC-62052 & IS-14697. The 
Terminal  block  shall  form  an  extension  of  the  meter  case  and  shall  have  terminal  holes  and 
shall be of sufficient size to accommodate the insulated conductors & meeting the requirement 
of IS 13779 :1993/CBIP technical report- 88.   
The polycarbonate parts  fulfill the requirement of following tests: 
Sr.No.  Test  10%  Glass  filled 
non-transparent 
material  for  meter 
base  &  terminal 
block 
Transparent 
material  for  meter 
cover  &  terminal 
cover 
1  UV  ageing  for  200  Hrs.  as  per 
ASTM:G53 (Cl. No. 9.3) 
4  Hours  UV  at  60C, 
4  Hours 
condensation at 50C 
4  Hours  UV  at  60C, 
4  Hours 
condensation at 50C 
2  Boiling water test (10 Min)   No  softening  & 
whitening  &  No 
change  in  colour, 
shape,  size  & 
dimensions 
No  softening  & 
whitening  &  No 
change  in  colour, 
shape,  size  & 
dimensions 
3  Ball  pressure  test  as  per  IEC-60695-
10-2 
125 C +/- 2C  125 C +/- 2C 
4  Flammability Test 
(a)  As per UL 94 or 
(b)  As per IS 11731 (Part-2) 1986 
VO 
FVO 
VO 
FVO 
5  Glow wire test 
IS:11000(part 2/ SEC-1) 1984 OR IEC 
60695-2-12 
960 C  850 C 
6  Heat deflection Temp.(HDT) 
HDT/Ae, 1.8MPa edge(100mm) As per 
ISO 75/Ae 
132 C  125 C  
  Terminal cover 
  Extended Terminal Block Cover 
  Short Terminal Block Cover 
  The  fixing  screw(s)  used  on  the  ETBC  for  fixing  and  sealing  of  extended  terminal 
cover shall be held captive on the terminal cover. 
  Extended terminal block cover shall be provided to ensure that the internal parts are 
not  accessible  for  tampering  etc.  without  breaking  the  seals.  The  ETBC  shall  be 
extended by  about 30 mm 5 mm below the terminal block. A firm connection shall 
be established with in the meter case to energies the voltage circuit. 
  To facilitate sealing, a raised support arrangement with minimum 2 mm hole nearby 
sealing screws, which shall constitute an integral part of the terminal cover or a slot 
type arrangement underneath/alongside the sealing screw shall be provided. 
  The meter shall have minimum three fixing holes, one at the top and other two inside 
the terminal block. The top hole shall be key-hole type on the back of the meter base 
so  that  the  hanging-screw  is  not  accessible  after fixing  of the meter  and it  shall  not 
be  possible  to  remove  the  meter  from  the  hanging-screw  without  removing  the 
terminal cover and screw(s) from the terminal block.  The lower fixing holes shall be 
provided under the extended terminal cover.  
  Top cover assembly- transparent. 
  Support of top cover removal detection  
  Push button  
  Optical interface 
  Optical Port seal 
  The main cover  be ultrasonically welded to the base 
  Protection class:  IP 54 
  Communication in form of RS232 /RS485 on main PCB,  
  Ethernet port  
  USB  
  Internal GSM/GPRS Modem                                 
Name plate and Marking 
The  meter  shall  have  a  nameplate  clearly  visible,  effectively  secured  against  removal  and 
indelible.  It    be  distinctly  marked  with  all  essential  details  as  per  IS14697/IEC  62052-11-2003 
standard.  The  meter  Serial  No.  shall  be  Bar  Coded  along  with  Numeric  No.  The  nameplate 
marking  not fade or otherwise be adversely affected by UV exposure with lapse of time. 
Top cover removal detection 
The  Top  cover  Opening  is  detected  and  logged  as  an  event.  It  operates  without  obstruction 
while opening or closing the Enclosure.            
Magnetic field Test 
The meter withstands all the tests for external AC/DC magnetic field as per CBIP-88. Moreover, 
the  magnetic  influence  test  for  permanent  magnet  of  0.5  Tesla  for  a  minimum  period  of  15 
minutes on the meter body. If the accuracy of the meter gets affected during the test, then the 
same shall be recorded as magnetic tamper event with date and time stamping and the meter 
shall  record  energy  considering  maximum  value  current  (Imax)  and  reference  voltage  at  unity 
power factor. After removal of the magnet the meter  behave normally and meet the accuracy as 
per IS14697.  
The  meter  accuracy  shall  not  be  affected  by  AC/DC magnetic  field  of  0.2T  on  all  the  sides  of 
meter i.e. front, sides, top and bottom of the meter as per CBIP-88 Technical Report. Moreover 
meter working shall not be affected by permanent magnet of 0.5 T of minimum size 70 x70 x 50 
mm. 
There  is  a  provision  to  select  whether  the  meter  add  the  Imax  Energy  to  the  billing  kWh 
readings or store in a separate. Imax recording   
RTC backup 
The time keeping during a power outage is realized with an internal battery. 
Optional HW requirements  
The ABT hardware also optionally offer the following features:  
  Relay card 2 /4 / 6/ relays   
  LPR (Low Power Radio)  
Firmware Provisions  
The Firmware provisions are:  
  Active  energy  measurement  in  both  Import  and  Export  direction  (kWh  Import,  kWh 
Export).  Active  energy  recording  on  fundamental  frequency  as  well  as  total 
(Fundamental +Harmonics) 
  Reactive  energy  measurement  in  all  four  quadrants  (kVARhQ1,  kVARhQ2, 
kVARhQ3 and kVARhQ4) 
  Apparent energy measurement (kVAh Import, kVAh Export)  
  TOU application 
  8 tariffs,  
  It  be possible to switch the rates at predefined time during the day. 
    Upto 4 seasons 
  Up to 12 historical data  
  The historical data  get logged at a predefined date and a predefined time 
  120 days of midnight 8 energy + 5 ABT parameters or 8 energy + 8 ABT parameters. 
  Demand measurement for any 4 parameters to be programmable from the below: 
  kW Import 
  kW Export 
  kVA Import 
  kVA Export 
  kVAR Import 
  kVAR Export 
  kVAR Q1 
  kVAR Q2 
  kVAR Q3 
  kVAR Q4 
  Support of optical port 
  Support of remote port 
  500 No of events 
  Events to be stored in buckets 
  All Voltage events 
  All Current events  
  Event Type 
  R phase Low phase current (Creep) 
  Y phase Low phase current (Creep) 
  B phase Low phase current (Creep) 
  Any phase High Voltage 
  R phase Low Voltage  
  Y phase Low Voltage 
  B phase Low Voltage 
  R phase Current Reversal 
  Y phase Current Reversal 
  B phase Current Reversal 
  Current Unbalance 
  Voltage Unbalance 
  Power outage & power up 
  Optical MD Reset 
  Warm start  
  Communication Protocol : 
  IEC 62056-21 Mode C 
  DLMS as per ICS 
  It shall be possible to communicate on the Optical and Remote port using 
IEC 62056-21 Mode C or DLMS protocol. 
  It    be  possible  to  program  the  Remote  port  to  send  a  preprogrammed 
parameter data on the Remote port at a regular interval of 1 seconds. 
  Modbus 
  It  be possible to program the remote port for Modbus protocol  
  Load  profile  data  of  energy/demand  of  every  15  minutes  interval  8  energy  for  120 
days ABT. 
  Per  phase  Voltage  and  Current  profile  data  of  averaged  over  every  15  minutes 
interval of 120 days  be stored in the meter memory 
  Average Frequency profile of every 15 minute interval of 120 days  be stored in the 
meter memory. 
  The energy/demand profile channels  be selectable from : 
  kWh Import 
  kWh Export 
  kVARh Import 
  kVARh Export 
  kVARh Q1 
  kVARh Q2 
  kVARh Q3 
  kVARh Q4 
  kVAh Import 
  kVAh Export 
  Net kWh 
  Net kVARh Hi 
  Net kVARh Low.          
The reactive energy shall be recorded for each metering interval in four different 
registers as kVARh Q1, kVARh Q2, kVARh Q3, kVARh Q4. 
Two separate registers shall be provided to record kVARH when system voltage 
is >103% and when system voltage is < 97%. 
The  meter  shall  compute  the  net  kWh  and  kVARh  during  each  successive  15-minute 
block metering interval along with a plus/minus sign. These values will be displayed and 
stored in the load profile.      
Additional Points:  
Immunity to 35 KV with logging 
10 KV impulse with 12 Ohm resistance 
Provisition  for  flush  mounting  with  automatic  CT  Shorting  facility,  auxillary  power  supply 
(AC/DC)  
Reading during power off mode : Internal or external battery with induction coupling. For display 
as well as data downloading. 
CT/PT compensation in ABT meter  
ABT time sync facility. 
Demand reset count for manual as well as auto reset count separetly. 
Phase sequence on display. 
Energy units programmable wh,kwh anf Mwh.