SRK 2002
SRK 2002
1-2
1.1 GENERAL INFORMATION
1.1.1 Specific features
The “Mitsubishi Daiya” room air conditioner: SRK series are of split and wall mounted type and the unit consists of indoor unit
and outdoor unit with refrigerant precharged in factory. The indoor unit is composed of room air cooling or heating equipment with
operation control switch and the outdoor unit is composed of condensing unit with compressor.
(1) Remote control flap
The flap can be automatically controlled by operating wireless remote control.
¡ AUTO (Natural flow) : Flap operation is automatically control.
¡ Swing : This will swing the flap up and down.
¡ Memory flap : Once the flap position is set, the unit memorizes the position and continues to
operate at the same position from the next time.
(2) Automatic Operation
When the remote control switch is set on “auto”, it will either automatically decide operation mode such as cooling,
heating and thermal dry, or operate in the operation mode before it has been turned to automatic control.
(3) Self diagnosis Function
We are constantly trying to do better service to our customers by installing such judges that show abnormality of operation
as follows.
}
RUN lamp is flashing. t Abnormality of heat
(1 Times/ 8sec.) exchanger sensor.
No lamps will flashing
when the unit is operating.
TIMER lamp is RUN lamp is flashing. t Abnormality of room
light up. (2 Times/ 8sec.) temperature sensor.
CE marking model
Flare connecting
Applicable power source …… See the specifications
H-Heat pump type C-Cool only type
Series No.
Product capacity
Wall mounted type room air conditioner
Split type room air conditioner
1-3
1.2 SELECTION DATA
1.2.1 Specifications
Model SRK208HENF-L (Indoor unit)
SRC208HENF-L (Outdoor unit)
Model SRK208HENF-L SRC208HENF-L
Item
Cooling capacity(1) W 1800/1850
Heating capacity(1) W 2000/2050
Power source 1 Phase, 220/240V, 50Hz
Cooling input kW 0.690/0.775
Operation data(1)
–
Gas line: 0.35m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5m (3 cores with Earth)
Connection Size x Core number 1.5mm2 x 5 cores (Including earth cable)
wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC JIS C9612, ISO-T1
Heating 20ºC – 7ºC 6ºC JIS C9612, ISO-T1
(2) The operation data are applied to the 220V or 240V districts respectively
(3) Limitation of Voltage application Minimum: 198V Maximum: 264V
(4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer, (when it is less than 10 m, add 20g refrigerant per meter and when it is 10 to 15m, add 30g
refrigerant per meter.)
(5) Expressed in sound pressure level.
1-4
Model SRK288HENF-L (Indoor unit)
SRC288HENF-L (Outdoor unit)
–
Gas line: 0.35m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5m (3 cores with Earth)
Connection Size x Core number 1.5mm2 x 5 cores (Including earth cable)
wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
1-5
Model SRK328HENF-L2 (Indoor unit)
SRC328HENF-L2 (Outdoor unit)
Model SRK328HENF–L2 SRC328HENF–L2
Item
(1)
Cooling capacity W 3000/3000
Heating capacity(1) W 3800/3800
Power source 1 Phase, 220/240V, 50Hz
Cooling input kW 1.39/1.49
Operation data(1)
–
Gas line : 0.35m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5m (3 cores with Earth)
Connection Size x Core number 1.5mm2 x 5 cores (Including earth cable)
wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
1-7
Model SRK501HENF-L (Indoor unit)
SRC501HENF-L (Outdoor unit)
Model SRK501HENF–L SRC501HENF–L
Item
Cooling capacity(1) W 4500/4500
Heating capacity(1) W 5700/5800
Power source 1 Phase, 220/240V, 50Hz
Cooling input kW 1.78/1.88
Operation data(1)
–
Gas line: 0.35m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5m (3 cores with Earth)
Connection Size x Core number 1.5mm2 x 5 cores (With Earth)
wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
1-8
Model SRK561HENF-L (Indoor unit)
SRC561HENF-L (Outdoor unit)
Model SRK561HENF–L SRC561HENF–L
Item
Cooling capacity(1) W 5000/5000
Heating capacity(1) W 6200/6300
Power source 1 Phase, 220/240V, 50Hz
Cooling input kW 2.08/2.18
Operation data(1)
–
Gas line: 0.35m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5m (3 cores with Earth)
Connection Size x Core number 1.5mm2 x 5 cores (With Earth)
wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
1-9
Model SRK50A (Indoor unit)
SRC50HA (Outdoor unit)
Model SRK50A SRC50HA
Item
(1)
Cooling capacity W 4500
Heating capacity(1) W 5700
Power source 1 Phase, 220/230/240V, 50Hz
Cooling input kW 1.79
Running current (Cooling) A 8.4/8.0/7.7
Heating input kW 1.83
Operation data(1)
1-11
Model SRK208CENF-L (Indoor unit)
SRC208CENF-L (Outdoor unit)
Model SRK208CENF-L SRC208CENF-L
Item
Cooling capacity(1) W 1800/1850
Power source 1 Phase, 220/240 V, 50 Hz
Cooling input kW 0.54/0.58
Operation
1-12
Model SRK258CENF-L (Indoor unit)
SRC258CENF-L (Outdoor unit)
Model SRK258CENF-L SRC258CENF-L
Item
(1)
Cooling capacity W 2200/2250
Power source 1 Phase. 220/240 V, 50 Hz
Cooling input kW 0.66/0.74
Operation
1-13
Model SRK288CENF-L (Indoor unit)
SRC288CENF-L (Outdoor unit)
Model SRK288CENF-L SRC288CENF-L
Item
(1)
Cooling capacity W 2500/2550
Power source 1 Phase, 220/240 V, 50 Hz
Cooling input kW 0.87/0.95
Operation
1-14
Model SRK328CENF-L (Indoor unit)
SRC328CENF-L (Outdoor unit)
Model SRK328CENF-L SRC328CENF-L
Item
(1)
Cooling capacity W 2750/2750
Power source 1 Phase, 220/240 V, 50 Hz
Cooling input kW 0.93/0.99
Operation
1-15
Model SRK408CENF-L (Indoor unit)
SRC408CENF-L (Outdoor unit)
Model SRK408CENF-L SRC408CENF-L
Item
(1)
Cooling capacity W 3500/3500
Power source 1 Phase, 220/240 V, 50 Hz
Cooling input kW 1.320/1.405
Operation
1-16
Model SRK501CENF-L (Indoor unit)
SRC501CENF-L (Outdoor unit)
Model SRK501CENF-L SRC501CENF-L
Item
Cooling capacity(1) W 4500/4500
Power source 1 Phase, 220/240V, 50 Hz
Cooling input kW 1.78/1.88
Operation
–
Gas line : 0.35m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Connection Size × Core number 1.5 mm2 × 3 cores (Including earth cable)
wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27°C 19°C 35°C 24°C JIS C9612, ISO-T1
(2) The operation data are applied to the 220 V or 240 V districts respectively.
(3) Limitation of Voltage application
Minimum: 198 V Maximum: 264 V
(4) The refrigerant quantity to be charged includes the refrigerant in 7.5 m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer, (when it is less than 10 m, add 10 g refrigerant per meter and when it is 10 to 15 m, add 30 g refrigerant per meter.)
(5) Expressed in sound pressure level.
1-17
Model SRK561CENF-L (Indoor unit)
SRC561CENF-L (Outdoor unit)
Model SRK561CENF-L SRC561CENF-L
Item
(1)
Cooling capacity W 5000/5000
Power source 1 Phase, 220/240V, 50 Hz
Cooling input kW 2.08/2.18
Operation
–
Gas line : 0.35m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Connection Size × Core number 1.5 mm2 × 3 cores (Including earth cable)
wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27°C 19°C 35°C 24°C JIS C9612, ISO-T1
(2) The operation data are applied to the 220 V or 240 V districts respectively.
(3) Limitation of Voltage application
Minimum: 198 V Maximum: 264 V
(4) The refrigerant quantity to be charged includes the refrigerant in 7.5 m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer, (when it is less than 10 m, add 10 g refrigerant per meter and when it is 10 to 15 m, add 30 g refrigerant per meter.)
(5) Expressed in sound pressure level.
1-18
Model SRK50A (Indoor unit)
SRC50CA (Outdoor unit)
–
Gas line : 0.43m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 3 m (3 cores with Earth)
Connection Size × Core number 1.5 mm2 × 3 cores (Including earth cable)
wiring Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
1-19
Model SRK56A (Indoor unit)
SRC56CA (Outdoor unit)
Model SRK56A SRC56CA
Item
(1)
Cooling capacity W 5000
Power source 1 Phase, 220/230/240V, 50 Hz
Cooling input kW 2.08
Operation data(1)
1-20
1.2 SELECTION DATA
1.2.1 Specifications
Model SRK25GZ-L1 (Indoor unit)
SRC25GZ-L1 (Outdoor unit)
Model SRK25GZ-L1 SRC25GZ-L1
Item
Cooling capacity(1) W 2500 [900~2900]
Heating capacity(1) W 3400 [900~4000]
Power source 1 Phase, 220/240V, 50Hz
Cooling input kW 0.96 [0.31~1.22]
Operation data(1)
–
Gas line : 0.35 m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC 19ºC 35ºC 24ºC JIS C9612, ISO-T1
Heating 20ºC – 7ºC 6ºC JIS C9612, ISO-T1
(2) The values for performance and power consumption shown in brackes [~] indicate the range from minimum to maximum.
(3) The operation data are applied to the 220/240V districts respectively.
(4) Limitation of Voltage application Minimum: 198V Maximum: 264V
(5) The refrigerant quantity to be charged includes the refrigerant in 5 m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer,
(When it is 5 to 15 m, add 20 g refrigerant per meter.)
1-21
Model SRK35GZ-L1 (Indoor unit)
SRC35GZ-L1 (Outdoor unit)
–
Gas line : 0.35 m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
(2) The values for performance and power consumption shown in brackets [~] indicate the range from minimum to maximum.
(3) The operation data are applied to the 220/240V districts respectively.
(4) Limitation of Voltage application Minimum: 198V Maximum: 264V
(5) The refrigerant quantity to be charged includes the refrigerant in 5 m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer,
(When it is 5 to 15 m, add 20 g refrigerant per meter.)
1-22
Model SRK502Z-L (Indoor unit)
SRC502Z-L (Outdoor unit)
–
Gas line : 0.35 m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Size × Core number 1.5 mm2 × 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
(2) The values for performance and power consumption shown in brackets [~] indicate the range from minimum to maximum.
(3) The operation data are applied to the 220/240V districts respectively.
(4) Limitation of Voltage application Minimum: 198V Maximum: 264V
(5) The refrigerant quantity to be charged includes the refrigerant in 7 m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer,
(When it is 7 to 25 m, add 20 g refrigerant per meter.)
1-23
1.2.2 Range of usage & limitations
(1) Inlet air temperature
(a) Cooling operation (b) Heating operating
Applicable temp.
range
Outdoor air temp. ºC D. B.
JIS-Cooling
(2) Total one way piping length and vertical height difference.
Models
All models
Item
Total one way piping length (m) 15
Vertical height Outdoor unit is higher 5
difference (m) Outdoor unit is lower 5
1-24
1.2.3 Exterior dimensions
(1) Indoor unit
Models SRK 208, 288, 328, 408 -HENF, -CENF, 258CENF Unit: mm
A
790 174 3
275
56
Terminal block
9
15 760 15 49
9
46
161.5
117
61
260
187.5
60 16 60 20.5
Remote controller
780
6
36
37
Drain hose 600 (Ø16)
1-25
Models SRK50A, 56A
(2) Outdoor unit
Model SRC208 H(C) ENF-L
Unit: mm
14
68
220
237
265
44
250
14
120 510 120 30
750 Terminal block
492
65 78
45˚
45˚
80
15
Unit: mm
50
55 Drain holes MAX 80
22
14
58
65 93
255
272
44
265
23
14
795
Terminal block
542
539
32 115
413
40
45˚
16x12 (Oval holes)
for unit fixing 45˚
2 places
65
58 44
15
Drain holes
142.5 510 142.5 33 Service Service
50
1-27
Models SRC501H(C)ENF, 561H(C)ENF
25
19
307
345
Oval (M10x4) holes
30
19
for Anchor bolt
850 30 290
70.5 100
475
55
25
17
1-28
Models SRC50C(H)A, 56C(H)A
286.4 Drain hole 50
12
12
43.5
290
314
328
49.6
14
476
203.1 510 136.9 Elogated hole
(2-12X16)
850
Terminal block
124 34.6
640
Ground
terminal
42.7
20˚
Ø12.7 (1/2'')
15
1-29
1.2.3 Exterior dimensions
(1) Indoor unit
Model SRK25GZ-L1 Unit: mm
A Room temp. 178 3
750 thermistor
56
250
9
49
75 615 75 Terminal
block
150 450 150
117
46
9
236.5
15
19
60 16
Remote controller
746.9
36
92 40
4.5
36
7.5 62 62 7.5
Piping for Gas (Ø9.52) 370
37
40
Room temp.
thermistor
Piping hole right (left)
275
56
Terminal block
9
15 760 15 49
117
61
260
187.5
60 16
Remote controller
6
36
51 780
Piping for Gas
(Ø12.7) 390 62 18
67
Piping for Liquid (Ø6.35) 440
Drain hose 600 (Ø16)
37
Remote controller
274.5
300
44
372.5
23
12
127.7 33.3
Service valve (Liquid)
Flare connecting Ø6.35 (1/4˝)
540
39.7
40˚ 40˚
100.3
1-31
Model SRC35GZ-L1
50
55 Unit : mm
Drain holes MAX.80
22
14
58
65 93
255
272
44
23
14
265
795
Terminal block
32 115
542
539
413
40 45°
16 12 (Oval holes) 45°
for unit fixing
2 places
65
58 44
15
Model SRC502Z-L
Unit: mm
1-32
1.2.4 Piping system
Model SRK328HENF-L2
Cooling cycle
Heating cycle
Indoor unit Outdoor unit
Piping (Gas)
Ø12.7 Check
Room joint Discharge
temperature
sensor Compressor Accumulator Heat exchanger
Heat exchanger Heat
exchanger 4way valve
sensor
Suction
Defrost
Piping (Liquid) thermostat
Ø6.35
Strainer
Flare connecting Service valve (Liquid) Capillary tube
Model SRK408HENF-L2
Cooling cycle
Indoor unit Outdoor unit Heating cycle
Piping (Gas)
Ø12.7 Check
Room joint Discharge
temperature
sensor Accumulator
Compressor
Heat Heat exchanger
Heat exchanger exchanger 4way valve
sensor
Suction
1-33
Models SRK501HENF-L, 561HENF-L
Cooling cycle
Indoor unit Outdoor unit Heating cycle
Piping (Gas)
Ø12.7 Check
joint
4way valve
Heat Discharge Heat exchanger
Room exchanger Accumulator
temperature thermistor
Deicer
thermistor thermostat
Compressor
Muffler
Heat exchanger
Suction
Capillary tube
Piping (Liquid)
Ø6.35 Strainer
Piping (Gas)
Ø12.7 Check
joint
4way valve
Heat Discharge Heat exchanger
Room exchanger Accumulator
temperature thermistor
Deicer
thermistor thermostat
Compressor
Muffler
Heat exchanger
Suction Capillary tube
Piping (Liquid)
Ø6.35 Strainer
1-34
Models SRK501CENF-L, 561CENF-L
Compressor
Capillary tube
Piping (Liquid) ø6.35
Model SRK408HENF-L
Cooling cycle
Indoor unit Outdoor unit Heating cycle
Flare connecting
Piping (Gas)
Ø12.7 Check
Room joint Discharge
temperature
sensor Accumulator
Compressor
Heat Heat exchanger
Heat exchanger exchanger 4way valve
sensor
Suction
1-35
Model SRK408HENF-L3
Cooling cycle
Indoor unit Outdoor unit Heating cycle
Piping (Gas)
Ø12.7 Check
Room joint Discharge
temperature
sensor Accumulator
Compressor
Heat 4way valve Heat exchanger
Heat exchanger exchanger
sensor
Suction
Model SRK208HENF-L
Cooling cycle
Indoor unit Outdoor unit Heating cycle
Flare connecting
Piping (Gas)
Ø9.52
Check
Room joint Discharge
temperature
sensor Compressor Accumulator
Heat Heat exchanger
Heat exchanger exchanger 4way valve
sensor
Suction
Piping (Liquid)
Ø9.52 Strainer
Capillary tube
Flare connecting Service valve (Liquid)
1-36
Models SRK288HENF-L, 328HENF-L
Cooling cycle
Indoor unit Outdoor unit Heating cycle
Flare connecting
Piping (Gas)
Room
(28:Ø9.52
32:Ø12.7)
Check
joint Discharge
temperature
sensor Compressor Accumulator Heat exchanger
Heat exchanger Heat
exchanger 4way valve
sensor
Suction
Piping (Liquid)
Ø6.35
Strainer
Flare connecting Service valve (Liquid) Capillary tube
Piping (Gas)
ø12.7 Check joint
Room Muffler
temperature
thermistor Discharge
Accumulator
Heat Heat Heat
exchanger exchanger exchanger
thermistor Suction
Compressor
Capillary tube
Piping (Liquid) ø6.35
1-37
1.2.4 Piping system
Models SRK208CENF-L, 258CENF-L, 288CENF-L, 328CENF-L, 408CENF-L
Cooling cycle
Indoor unit Outdoor unit
Piping (Gas)
( 20, 25,
32, 40 : ø12.7 )
28 : ø9.52
Room
Heat exchanger
Heat exchanger
temperature Accumulator
sensor
Compressor
Heat Suction
exchanger
sensor
Capilary tube
ø6.35
Piping (Liquid)
Service valve (Liquid)
Flare connecting
1-38
1.2.4 Piping system
Model SRK25GZ-L1
Indoor unit Outdoor unit Cooling cycle
Heating cycle Outdoor air
Flare connecting Service valve temp. thermistor
(Gas)
Strainer
Flare connecting
Model SRK35GZ-L1
Cooling cycle
Indoor unit Outdoor unit Heating cycle
Flare connecting
Outdoor air
temp. thermistor
Piping (Gas)
Ø12.7
Check
Room joint Discharge
temp.
thermistor Compressor
Heat Accumulator
exchanger 4way valve Heat exchanger
Heat exchanger thermistor
Discharge temp.
thermistor
Suction
1-39
Model SRK502Z-L
1-40
1.3 ELECTRICAL DATA
1.3.1 Electrical wiring
Models SRK50CA, 56CA
Power source Indoor unit Outdoor unit
1 Phase 220/230/240V 50Hz
Y/GN
BL OR BL
BR 4 4
RD BL F (250V 100mA)
3 3
Y/GN WH WH
2 2
BK BK
1 1
RD
52C-4 G 52C-3 S 20S 23D
52C BK
52C
TH1
51C
PC
CNG
BL 52X1
5 52X1 TH2 BK
Y F WH
4
FMI
WH
BK
3 (250V
3.15A ) FM0
OR
2 CM
RD
1 WH
CNU OR
Wireless RD
CNH
R-Amp WH
ZNR CF0 Cc
Display
CNM WH
LM
Back up sw
CNE
OR WH
Printed circuit board WH
1-41
Models SRK501CENF-L, 561CENF-L
LB
BR
BL 1 2
Y F
2
WH 250V
I
BK
3 (
3.15A )
4
RD
5
H
Wireless
R-Amp
Display
Printed circuit board
1-42
Model SRK208CENF-L
Power source
1 Phase 220/240V 50Hz
Wireless
R-Amp
Display
Color symbol
BK Black
BL Blue
BR Brown
RD Red
OR Orange
WH White
Y/GN Yellow/Green
Meaning of marks
Symbol Parts name Symbol Parts name
CC Capacitor for CM LM Louver motor
CFI Capacitor for FMI Th1, 2 Thermistor
CFO Capacitor for FMO Tr Transformer
CM Compressor motor ZNR Varistor
F Fuse 51C Motor protector for CM
FMI Fan motor (Indoor unit) 52C Magnetic contactor for CM
FMO Fan motor (Outdoor unit)
1-43
Models SRK258CENF-L, 288CENF-L, 328CENF-L, 408CENF-L
Power source
1 Phase 220/240V 50Hz
Wireless
R-Amp
Display
Color symbol
BK Black
BL Blue
BR Brown
RD Red
OR Orange
WH White
Y/GN Yellow/Green
Meaning of marks
Symbol Parts name Symbol Parts name
CC Capacitor for CM LM Louver motor
CFI Capacitor for FMI Th1, 2 Thermistor
CFO Capacitor for FMO Tr Transformer
CM Compressor motor ZNR Varistor
F Fuse 51C Motor protector for CM
FMI Fan motor (Indoor unit) 52C Magnetic contactor for CM
FMO Fan motor (Outdoor unit)
1-44
Model SRK208HENF-L Indoor unit Outdoor unit
Power source
1Phase 220/240V 50Hz
Wireless
R-Amp
Display
Printed circuit board
Color symbol
BK Black
BL Blue
BR Brown
RD Red
OR Orange
WH White
Y/GN Yellow/Green
Meaning of marks
Operation
Relay Control Cooling Heating Defrost
symbol part
52X4 20S × ×
52X5 FMO ×
52C CM
1-45
Models SRK288HENF-L, 328HENF-L, 408HENF-L
Power source
1Phase 220/240V 50Hz
Wireless
R-Amp
Display
Printed circuit board
Color symbol
BK Black
BL Blue
BR Brown
RD Red
OR Orange
WH White
Y/GN Yellow/Green
Meaning of marks
Operation
Relay Control Cooling Heating Defrost
symbol part
52X4 20S × ×
52X5 FMO ×
52C CM
Notes (1) : denotes magentized relay × : denotes demagnetized relay
(2) Th1 is room temperature sensor. Th2 (the heat exchanger sensor) is the hot start, hot keep, and frost prevention sensor. (for details,
refer to pages 72, 74 )
1-46
Models SRK328HENF-L2, 408HENF-L2
Indoor unit Outdoor unit
Y/GN
Power source
1 Phase 220/240V 50Hz
T2 T1
Y/GN BK 1 1 BK
BK
BL WH 2 2
WH
BR Sh1 OR 3 3 BL
BK
RD 4 4 RD
BK 63H RD
Sh1
WH
BK
52C3 52C4 20S 23D
Tr 52X5
4 2
52C
2 52X6
OR
BK
BK
6 3
BK BK
CNC CNB PC BK 23DH 2 51C
BK
RD
F Th1
BK
250V 1
CNG
CNU
BL
3.15A 52X4 Th2 OR 7 C
BK
FMo 20S 52X5 CM
BR 1 CFI S R
RD
OR
WH 8
WH
5
BK
7
RD
RD 3 ZNR
CNE CND
WH
WH
WH
WH
WH
RD
Display
Printed circuit board
CNM
Sh2
LM 52C 52X4
Color symbol
BK Black
BL Blue
BR Brown
RD Red
OR Orange
WH White
Y/GN Yellow/Green
Meaning of marks
Symbol Parts name Symbol Parts name
Cc Capacitor for CM Th1,2 Thermistor
CFI Capacitor for FMI Tr Transformer
CFO Capacitor for FMo ZNR Varistor
CM Compressor motor 20S 4 way valve, coil
F Fuse 51C Motor protector for CM
FMI Fan motor (Indoor unit) 52C Magnetic conductor for CM
FMO Fan motor (Outdoor unit) 52X4,5,6 Auxiliary relay
LM Louver motor 63H High pressure switch
PC Photo coupler 23DH Defrost thermostat
1-47
Models SRK501HENF-L, 561HENF-L
Y/GN
LB OR RD
BR 4 4
RD BL
3 3
Y/GN WH WH
2 2
BK BK RD
1 1
RD 63H RD RD
52C-4 G 52C-3 S 20S 23D
52C
BK
52C
TH1 52XA BK
PC
OR
WH
CNG
52X1 2 23
BL 52X1 TH2 52XB DH
5
Y F 6
RD
4 BL
FMI
WH
3 (250V
) BK
BK
RD
BK
3.15A 51C
BK
BK
RD
2
RD OR
1 FM0 20S 52XA CM
CNU
OR
CNH
Wireless
RD
R-Amp
WH
OR
ZNR OR CF0 52XB Cc
CNE
WH
WH
LM CNM Display
BK
RD
BL
Printed circuit board
Color symbol
BK Black
BL Blue
BR Brown
RD Red
OR Orange
WH White
Y Yellow
LB Light blue
Y/GN Yellow/Green
Meaning of marks
Symbol Parts name Symbol Parts name
CC Capacitor for CM Th1, 2 Thermistor
CFO Capacitor for FMO ZNR Varistor
CM Compressor motor 20S 4 way valve. coil
F Fuse 51C Motor protector for CM
FMI Fan motor (Indoor unit) 52C Magnetic contactor for CM
FMO Fan motor (Outdoor unit) 52XA, B, 1 Auxiliary relay
LM Louver motor 63H High pressure switch
PC Photo coupler 23DH Thermostat (Defrost)
1-48
Models SRK50HA, 56HA
Power source Indoor unit Outdoor unit
1 Phase 220/230/240V 50Hz
Y/GN
BL OR RD
BR 4 4
RD BL
3 3
Y/GN WH WH
2 2
BK BK RD
1 1
RD 63H RD RD
52C-4 G 52C-3 S 20S 23D
52C
BK
52C
TH1 52XA BK
PC
OR
WH
CNG
52X1 23
BK
BL 52X1 TH2 52XB DH
5
Y F
RD
4 BL
( 250V
)
BK BK
WH
FMI 3 BK
BK
3.15A 51C
BK
BK
RD
2
RD OR
1 FM0 20S 52XA CM
CNU Wireless
OR
CNH
RD
WH WH
R-Amp
ZNR CF0 52XB Cc
Display
CNE
OR
WH
WH
LM CNM
BK
RD
BL
Back up sw
Printed circuit board
Meaning of marks
Symbol Parts name Symbol Parts name
CC Capacitor for CM Th1, 2 Thermistor
CFO Capacitor for FMO ZNR Varistor
CM Compressor motor 20S 4 way valve. coil
F Fuse 51C Motor protector for CM
FMI Fan motor (Indoor unit) 52C Magnetic contactor for CM
FMO Fan motor (Outdoor unit) 52XA, B, 1 Auxiliary relay
LM Louver motor 63H High pressure switch
PC Photo coupler 23DH Thermostat (Defrost)
Y/GN
Power source
1 Phase 220/240V 50Hz
T2 T1
Y/GN BK 1 1 BK
BK
BL WH 2 2
WH
BR Sh1 OR 3 3 BL
BK
RD 4 4 RD
BK 63H RD
Sh1
WH
BK
52C3 52C4 20S 23D
Tr 52X5
4 2
52C
2 52X6
OR
BK
BK
6 3
BK BK
CNC CNB PC BK 23DH 2 51C
BK
RD
F Th1
BK
1
CNG
250V
CNU
BL
3.15A 52X4 Th2 OR 7 C
BK
FMo 20S 52X5 CM
BR 1 CFI S R
RD
OR
WH 8
WH
5
BK
7
RD
RD 3 ZNR
CNE CND
WH
WH
WH
WH
WH
RD
Display
Printed circuit board
CNM
Sh2
LM 52C 52X4
Color symbol
BK Black
BL Blue
BR Brown
RD Red
OR Orange
WH White
Y/GN Yellow/Green
Meaning of marks
Symbol Parts name Symbol Parts name
Cc Capacitor for CM Th1,2 Thermistor
CFI Capacitor for FMI Tr Transformer
CFO Capacitor for FMo ZNR Varistor
CM Compressor motor 20S 4 way valve, coil
F Fuse 51C Motor protector for CM
FMI Fan motor (Indoor unit) 52C Magnetic conductor for CM
FMO Fan motor (Outdoor unit) 52X4,5,6 Auxiliary relay
LM Louver motor 63H High pressure switch
PC Photo coupler 23DH Defrost thermostat
1-50
Indoor unit Outdoor unit
Power source
1 phase 220/240V 50Hz
NK
Y/GN Y/GN RD RD
3 3
NF
LB WH WH WH
2 2 2 4
BR BK GY BK
1 1 1 3
(Power source F2(15A)
Signal line) BK
Tr 52C4 52C3 WH
Model SRK25GZ-L1
J
52C
Y/GN RE
DS
CNC CNB N
BR
F1
(250V 3.15A) V
CNC V WH
FM0
CNW
WH
CFI DS
FMI Y
RE C
WH CNB
20S
RD ZNR RD
CNU
52C
Th5
NK
CNE CNG U RD
Th6 CND
Color symbol Power V WH
Back up
BK Black transistor W BK
switch
Th7
BL Blue Printed circuit board
BR Brown Display
Wireless
LB Light blue R-Amp CM
Y Yellow Th1 Th2
RD Red
GY Gray
WH White
V Violet
Y/GN Yellow/Green
1-51
Indoor unit Outdoor unit
1-52
Power source
1 phase 220/240V 50Hz
NK
Y/GN Y/GN RD RD
3 3
NF
LB WH WH WH
2 2 2 4
BR BK GY BK
1 1 1 3
(Power source F2(20A)
Signal line) BK
Tr 52C4 52C3 WH
Model SRK35GZ-L1
J
52C
Y/GN RE
DS
CNC CNB N
BR
F1
(250V3.15A) V
CNC V WH
FM0
CNW
WH
CFI DS
FMI Y
RE C
WH CNB
20S
RD ZNR RD
CNU
52C
Th5
NK
CNE CND CNG U RD
Th6 CND
Color symbol Power V WH
Back up
BK Black transistor W BK
switch
Th7
BL Blue Printed circuit board
BR Brown Wireless
Display
R-Amp CM
LB Light blue
Y Yellow Th1 Th2
RD Red
GY Gray
WH White
V Violet
Y/GN Yellow/Green
Indoor unit Outdoor unit
Model
Y/GN RD 3 3 RD
Power source LB WH WH
1 phase 220/240V 50Hz 2 2
BR BK BK
1 1
SRK502Z-L
ZNR WH
CNA OR RE
SM FMo
CNM
IC2
CNE CNH CNF CNG
Printed circuit
board RL
Colorsymbol
BK Black Wireless Th5
BL Blue R-Amp RD U P N
Back up
WH V Th6
BR Brown switch CM BK W
Display Th3 Th2 Th1
Y Yellow
Th7
RD Red
Power transistor
LB Light blue
WH White
Y/GN Yellow/Green
1-53
1.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
1.4.1 Table for operation control
Refering page
Functions Content
High efficiency, low input rotary –
compressor Low input rotary compressor with high efficiency is equipped.
All operation modes can be operated from distance place by the wire-
less remote control. And also liquid crystal is used to show all kinds to 68
Wireless remote control operation or, off, air flow switch, operation switch, timer switch, timer
set, temperature set, flap control.
Dry Defumidifies while keeping room temperature to the thermostat setting 73
level by M.C. thermostat.
ON TIMER ON timer setting for anytime during 24 (32, 40: 12) hours can be performed. 70
OFF timer setting for favourite time can be performed. Comfortable
Cooling and Dry operation to prevent catching cold in sleep and eco-
nomical operation can be performed, while raising room temperature
setting during 1 hour period in steps.
OFF TIMER While COOL & DRY: When the timer is set to OFF the temperature is 70
increased by 0.5ºC simultaneously, by 0.5ºC additionally every 30
minutes and by 1.5ºC in one hour.
While HEAT: When the timer is set to OFF the temperature is de-
creased by 1ºC simultaneously by 1ºC additionally every 30 minutes
Comfortability, Economical efficiency, Operational simplicity
stop to set value in accordance with the temperature of the indoor air
heating operation)
1-54
(1) Remote controller
ACL
ON TIMER button
This button sets the ON timer times. OFF TIMER button
This button sets the OFF timer Times.
1-55
(4) Operation control function by remote control switch
Remote control switch
S Models SRK 208, 258, 288, 328, 408 models
TIMER button
This button changes the selection of
SET TIMER button ON timer/OFF timer operation and
normal operation.
This button sets the ON timer and OFF
timer times.
RESET switch
Switch for resetting microcomputer.
1-56
(3) Back-up Switch
When the remote controller batteries become weak, or if the remote controller is lost or malfunctioning, this switch may be used to
turn the unit on and off.
(a) Operation
Push the switch once to place the unit in the automatic mode. Push it once more to turn the unit off.
(b) Details of operation
The unit will go into the automatic mode in which it automatically determines, from room temperature (as detected by
sensor), whether to go into the cooling, thermal dry or heating modes.
Function Room temperature
Fan speed Flap Timer switch
Operation mode setting
Cooling About 26ºC
Thermal dry About 25ºC Auto Natural flow Continuous
Heating About 25ºC
On operating in automatic operation mode by back-up switch, functions show in the above table are not altered, white, the other micro-
computer control functions remain effective.
• 40 model • 50, 56 models
ON/OFF
ON/OFF
Back-up switch
Back-up switch
(4) AUTOMATIC operation
(a) Determination of operation mode
S50, 56 models
The blow operation of the indoor fan is carried out at the 1st speed for 20 seconds and the room temperature is checked to
determine the operation mode automatically. (When the unit is operated by the turn-on timer, the blow operation is not
carried out.)
Room temperature Room temp.<21˚C 21˚C <
= Room temp.<26˚C 26˚C <
= Room temp.
S40 model
When starting operation after more than 1 hour since operation stops
(Operation stop button ON or ON-Timer), this system operates indoor fan with Lo for 20 seconds checks room temperature
and allowing decision of operating mode automatically.
(b) The temperature is checked once every 30 minutes after operation start. When the judgment is different
from the previous operation mode, the operation mode is transferred. (50, 56 models only)
1-57
(c) When switching to automatic operation during “Heating” “Cooling” “Dry” or when restarting with in 30 minutes (40 : 1
hour) after stopping with automatic operation mode, the former operating mode is selected. (In this case, 20 seconds Lo
operation of indoor fan is not performed). When the previous mode is in “FAN”, operation mode is to be set by the above
mentioned chart.
(d) Established temperature (operate by the established temperature button on remote controller).
Wireless remote control signal (Indication)
-6 -5 -4 -3 -2 -1 ±0 +1 +2 +3 +4 +5 +6
Temperature
Cooling 20 21 22 23 24 25 26 27 28 29 30 31 32
setting
Thermal dry 19 20 21 22 23 24 25 26 27 28 29 30 31
Heating 19 20 21 22 23 24 25 26 27 28 29 30 31
1-58
1.2.5 Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be
obtained in the following way.
Net capacity = Capacity shown on specification ✕ Correction factors as follows.
(1) Coefficient of cooling and heating capacity in relation to temperatures
1.3
1.2
Coefficient of cooling &
relation to temperature
Cooling
Heating capacity in
1.1
1.0
Heating
0.9
0.8
0.7
0.6
Applicable range
Cooling operation
43
Outdoor air D.B.
temperature
40
°C D.B.
35
30
25
20 24
15
14 16 18 20 22
27
°C D.B.
25
20 20
15
10
-10 -5 0 5 10 15
Outdoor air W.B. temperature °C W.B. ISO-T1 Standard Condition
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor
units.
Piping length [m] 7 10 15
Cooling 1.0 0.99 0.975
Heating 1.0 1.0 1.0
Adjustment coefficient 0.95 0.94 0.93 0.91 0.88 0.86 0.87 0.92 1.00
1-59
Additional refrigerant charge
When refrigerant piping exceeds 7(40 : 7.5) m conduct additional refrigerant charge after refrigerant sweeping.
S 50, 56 models
7m over 15m : Additional charge amount per meter = 20g/m
S 40 model
Max. 10m : Additional charge amount per meter = 20g/m
10m over 15m : Additional charge amount per meter = 30g/m
[Example : 50 model]
How much amount of additional charge for 15m piping?
(15 – 7)m × 20g/m = 160g 160g for additional charge
1-60
(7) Standard operation data
(a) Heat pump type (220/240V)
(220V/240V)
(220/240V)
1-61
(220/230/240V)
Remote control
available in this area.
1-62
(220/240V)
installation.
ss
Remote control
available in this area.
1-63
1.6 MAINTENANCE DATA
1.6.1 Trouble shooting
(1) Trouble shooting to be performed prior to exchanging PCB, (Printed circuit board) [Common to all models]
All the models described in this chapter are controlled by a microcomputer. When providing maintenance service to customers it
is necessary to understand the function controlled by a micro computer thoroughly, so as not to mistakenly identify correct opera-
tions as mis-operations. It is also necessary to perform the following simple checks before conducting detailed checks or exchang-
ing printed circuit board.
Ascertain the nature of the claim. Unit did not cool, etc.
YES
Carry out checks according to detailed
check process (See later page)
1-64
(2) Indication of Self Diagnosis (Indoor unit)
TIMER lamp
is lights
RUN lamp is flashing. Abnormality of room ¡ Disconnection of room temperature
(2 Time flash.) temperature thermistor. thermistor.
continuously.
Note (1) When an abnormality is indicated on the outdoor unit for the cooling only model, check the fuse on the outdoor unit. If the fuse is burnt out,
replace it with new one.
(3) Troubleshooting
Abnormality of outdoor unit [Compressor malfunction of insufficient gas (refrigerant)]
No No
Does compressor operate? Is protective device normal? Replace protective device.
Yes
Yes
Is refrigerant circulation
volume normal?
No
Yes Is capacitor normal? Replace capacitor.
Yes
Yes
Abnormality of indoor fan motor (Fan motor defective, printed circuit board defective)
Yes
Yes
1-65
Anormality of thermistor Disconnection of thermistor and defective connection of connector
Resistance value
Is thermistor resistance No
Replace thermistor.
value normal?
Yes
(kΩ)
Replace PCB.
(Short circuit)
Temperature (°C)
(4) Trouble Diagnostic Procedures
Remove receptacle.
Unit malfunctions or Runaway of micro- Insert it after 3 min. No change. Replace PCB.
does not stop. computer and operate.
Replace PCB.
(1)
1-66
(5) Trouble shooting chart for the room temperature thermistor (Th1), heat exchanger thermistor (Th2) and defrost thermostat (23DH)
Function
Unit Thermistor Operation
Short circuit Broken connection
Continuous Cooling operation Cooling will not operate
¡ Cannot be turned ON/OFF by thermostat ¡ FMI : continuous operation
Cooling
Room temperature ¡ When FMI is on. “AUTO” is continuously ¡ CM,FMo: stopped
thermistor (1) (Th1) Hi
except for “continuous” Heating will not operate Continuous heating operation.
thermal setting. (CM, FMo, FMI all stopped) ¡ Cannot be turned ON/OFF by thermostat
Heating ¡ When FMI is on. “AUTO” is continuously Hi
Indoor unit
Defrost thermostat
(23DH) Heating will not operate normally Heating will operate.
(The defrosting will operate normally, but ¡ Unable to defros(2)
Heating 23DH reset is not possible. De frosts for 10 ¡ Will not operate for very long when outside air
minutes) temperature is low
Notes
(1) When the room temperature thermistor (Th1) will not operate normally. Cooling or heating operation may be run continuously by putting the thermostat setting on
“CONTINUOUS”
(2) When switching to the defrost cycle, 23DH opens (broken connection), the machanism resets to heating, and defrosting will not operate.
(6) How to make sure of remote controller Note (1) How to check the remote controller
(1)
Is remote NO Remote controller S40 model
controller
normal? defects
(a) Press the reset switch of remote controller.
(b) If the salmost normal if entire display of remote control-
YES
ler is shown after indication.
Again pushing
operating switch
NO
S50,56 models
Does operating
(a) Press the reset switch of remote controller.
backup switch
(b) If the salmost normal if entire display of remote
controller is shown after indication.
NO
Replace the
display
NO
Remote
controller defects
1-67
1.6.3 Power supply remote operation
When the remote part on indoor unit PCB is modified, the air conditioner is turned ON-OFF by power supply ON-OFF operation
without using remote control switch.
After the power supply remote operation, the operation contents can be modified by the remote controller.
(1) Operation contents
(a) Heat pump type
Operation change AUTO
Air conditioner
COOL: 26˚C
Start operation
3-minute timer
STOP
HEAT: 25˚C
Air capacity change AUTO
Flap AUTO
Timer Continuous
Air conditioner
Start operation
3-minute timer
COOL: 26˚C
Set temperature
operation
DRY: 25˚C
STOP
Air capacity change AUTO
Flap AUTO
Timer Continuous
1-68