01
Protection Relays
MiCOM P54x
Differential Protection
                                    With comprehensive distance and aided
                                    DEF protection.
                                    Design evolution K
                                    Schneider Electric announces a major
                                    evolution, with the P54x line differential
                                    protection now incorporating the proven
                                    technology of the sub-cycle distance
                                    MiCOM P443, merged as one single Intelligent
                                    Electronic Device (IED).
  Customer Benefits
                                    The new P54x evolution combines current
                                    differential, five zone sub-cycle distance
  •	Reduced spares holding
                                    protection and a phase segregated aided
  •	Harmonized scheme drawings
                                    directional earth fault protection, providing the
   and panels wiring
                                    complete solution for any type of fault on the
  •	Minimum training requirements
                                    power system.
  •	Reduced time to commission
                                    This relay becomes the standard in all HV, EHV
                                    and UHV line protection applications, duplicated
                                    where dual redundant main protection is
                                    demanded.
                                    The enhanced functionality and versatility of
     The P54x is the ideal          working in either a two or three ended scheme,
     cost-benefit choice to         combined with the ease of adaptation as the
     protect HV, EHV and            power and communication systems expand and
                                    change in complexity, make the P54x a truly
     UHV lines or cables.
                                    future-proof relay.
                                                                                                                                                                                                  02
 Protection Relays MiCOM P54x
New features                                                                        •	 GPS synchronizing caters for differences between
                                                                                         the transmit and receive path message routing,
•	 The evolution of P54x relays provides an excellent
                                                                                         as typically found in SONET (synchronous digital
     cost-effective solution for line protection. The optional
                                                                                         hierarchy) multiplexed applications. The proven“ping-
     five zones of sub-cycle distance protection can work
                                                                                         pong” time alignment method, and optional GPS
     as independent parallel protection to the differential.
                                                                                         synchronism using the P594 for the common time
     Alternatively, each zone can be set to work as
                                                                                         base, are carried forward into all new P543-P546
     backup in case of communication failure.
                                                                                         models.
•	 Phase segregated aided directional earth fault DEF
                                                                                    •	 The new P54x relays deliver a comprehensive
     (67N) can also be configured as main protection to
                                                                                         implementation of IEC61850, the international
     provide high resistance ground fault detection.
                                                                                         standard for Ethernet-based communication in
     The innovative “Virtual Current Polarizing” feature
                                                                                         substations. IEC61850 enables integration of all
     even ensures correct operation when the fault
                                                                                         protection, control, measurement and monitoring
     generates negligible zero or negative sequence
                                                                                         functions within a substation.
     voltages.
                                                                                         The IEC61850 implementation in MiCOM relays
•	 The relay provides two independent tele-protection                                    allows interoperability with other vendors’ IEDs
     schemes each using a separate communication                                         and systems, and easy integration with the PACiS
     channel. The distance and DEF functions are                                         substation control systems.
     therefore flexible in configuration, to operate in
                                                                                    •	 P543 and P545 now facilitate in-zone transformer
     shared channel logic or in discrete modes.
                                                                                         feeder applications
     If differential protection is not used, ON-OFF
                                                                                    •	 All models support ABC and ACB phase rotation
     teleprotection can be enhanced by using
                                                                                    •	 A new easy to use Human Machine Interface (HMI)
     InterMiCOM64 digital signaling.
                                                                                         includes ten Programmable User Function Keys
•	 Differential current transformer supervision provides                                 with associated Tri-Color LEDs. Typical control,
     stability of the differential protection in case of failure                         maintenance, and commissioning options are
     on any CT wire in the differential zone. The relay                                  initiated from simple key presses, rather than the
     will detect which one of the local or remote current                                need to navigate a menu.
     transformers has failed, making it easy for the user to
     identify the affected CT circuit.
                                                                                                                                                               Zone 3
                                                                                                                                                    Zone P (fwd)
                                                                                                                                                 Zone 2
                                      Ia                    Ib                                                                                  Zone 1
Differential
current
| I diff |                                                                                                                                                                      Directional
                                                       Ic                                                                                                                       (forward)
                                                                                                                          Zone P
                                                                                                                          (Reverse)
                        Trip
                                                                                                                        Zone 4
                                                                          Percentage
                                                                           bias k2                                                         Offset Reverse Z3
                      Percentage
                       bias k1
                                                                         Restrain                       Quadrilateral characteristics
     I S1
                                                        I S2                      Bias current
                                                                                    | I bias |
                      | I diff | = | I a + I b + I c |                                                                                 Zone 3
                                                                                                                                       (without offset)
                      | I bias | = 0.5 ( |I a| + | I b| + | I c |)                                                                     Zone 2
                                                                                                                                                             Zone 3
                                                                                                                                       Zone P                (reverse offset)
                      The relay operates when                                                             Directional
                                                                                                          (reverse)                    Zone 1
                                 I bias < I S2
                                                                                                                                                                                                        © 2010 Schneider Electric - All rights reserved
                      (1) For
                                  I diff > k1 I bias + I S1
                                                                                                                                                           Directional
                      (2) For    I bias > I S2                                                                                                             (forward)
                                  I diff > k2 I bias    – (k2 – k1) I S2 + I S1
                                                                                                                           Zone P
                                                                                                                           (reverse)
Biased current differential protection
                                                                                                                                             Zone 4
                                                                                                         MiCOM characteristics
Schneider Electric 35 rue Joseph Monier CS30323 92506 Rueil-Malmaison Cedex, France Tel: +33 (0) 1 41 29 70 00 Fax: +33 (0) 1 46 99 71 00 www.schneider-electric.com
EnergyAutomation-DS-P54D-1317-EN                                                                                                                                                              10-2010