Exn series type nA explosion-proof connectors
Product Description
AVIC JONHON OPTRONIC TECHNOLOGY CO.,LTD
May,2016
Exn series type nA explosion-proof connectors
3、 Product name:
Exn series type nA explosion-proof connectors.
4、 description:
Exn series explosion-proof connectors feature environment
resistance and explosion-proof function. The products can be used in the
environment with flammable gases and vapors as Zone 2 with temperatures
classes T4, T3, T2 & T1. The products are widely used in fields of oil drilling, power transmission
and signal transmission.
●Applied in electrical connection of equipments and cables in severe environment like dampness
and drench.
●Protection degree: IP67
●Termination methods: crimping
●Both plug and receptacle can be mounted with removable pin or socket.
5、 Part number and basic insert arrangements
3.1 Ordering information
Basic series Exn □ □ □ □ □ □ □
Shell size 8、10、12、14、16、18
Shell Type
YT-plug
GZ- panel mount flange receptacle
YZ-portable receptacle
Current rating
10A、16A、25A、60A、100A、150A、200A、 250A、500A、1000A
etc
Number of contacts
1、3、4、5、10、14、20、30 etc
Contact type
Z-crimp pin ZL- 2 hole bus bar pin
K- crimp socket KL-2 hole bus bar socket
keys
Blank:N key、(X):X key、(Y):Y key、(JH):Y key
Mounting panel
Blank:no 、+FA:yes
3.1.1 Designation example
1、portable connectors:Exn8YT16A3Z _ Exn8YZ16A3K
Exn series 08# shell 3-wires connector part number: be made up of plug part number and portable receptacle part
number;
Plug part number, Exn8YT16A3Z:Exn series 08# shell 3-wires plug with pins, current rating 16A.
Portable receptacle part number,Exn8YZ16A3K:Exn series 08# shell 3-wires receptacle with sockets, current rating
16A,N key, without mounting panel.
2、Panel mount connectors:Exn8YT16A3Z _ Exn8GZ16A3K
Exn series 08# shell 3-wires connector part number: be made up of plug part number and panel mount receptacle
part number;
Plug part number, Exn8YT16A3Z:Exn series 08# shell 3-wires plug with pins, current rating 16A.
Panel mount receptacle part number,Exn8GZ16A3K:Exn series 08# shell 3-wires panel mounted receptacle with
sockets, current rating 16A, N key.
Note: the cable connector can only be used when the plug and socket
are integrated as a whole.
3.2 products layout
contact layout( views of insulator interface with pins)
Shell size contact layout( views of insulator interface with pins)
A A
C B B
N
C
3-φ2.4
1-φ7.5 4-φ2.4
8
Contact Wire size
Electrical ratings Matched cable diameter
Num. (mm2)
1 1×25 1 pin 100A/600V
3 3×2.5 1 phase 3 wires 16A/600V φ8~φ19.5
4 3×2.5+1×1.5 3 phase4 wires 16A/600V
N
A A C
B C
B
3-φ3
1-φ12 4-φ3
N 1 2 3
A P
4 5 6 7
8 9 10
B C
10
10-φ2.4
5-φ3
Contact
Wire size(mm2) Electrical ratings Matched cable diameter
Num.
1 1×95 1 pin 250A/600V
3 3×4 1 phase 3 wires 25A/600V
4 3×4+1×2.5 3 phase4 wires 25A/600V φ11~φ22.5
5 3×4+2×2.5 3 phase 5 wires 25A/600V
10 10×2.5 10 pins 16A/400V
N N
A A C A P
B C
B C
B
3-φ5
4-φ5 5-φ5
1 2 3 1 2
4 5 6 7 3 5
6 9
8 9 10
10 12
12 13 14
10-φ3 14-φ2.4
Contact
Wire size(mm2) Electrical ratings Matched cable diameter
Num.
3 3×10 1 phase 3 wires 60A/600V
4 3×10+1×6 3 phase 4 wires 60A/600V
5 3×10+2×6 3 phase5 wires 60A/600V φ15~φ27
10 10×4 10 pins 25A/600V
14 14×2.5 14 pins 10A/400V
N N
A C A P
14 B C
B
4-φ7.5 5-φ7.5
1-φ18
1 2
3 4 5 6 7
8 9 10 11
12 13 14 15 16
17 18 19 20
20-φ2.4
Contact Wire size
Electrical ratings Matched cable diameter
Num. (mm2)
1 1×185 1 pin 500A/600V φ23~φ35
4 3×25+1×16 3 phase 4 wires 100A/600V
φ27~φ39
5 3×25+2×16 3 phase 5 wires 100A/600V
20 20×2.5 20 pins 10A/400V φ23~φ35
N N
A C A P
B C
B
1-φ23 4-φ9.1 5-φ9.1
1 2 3
1 2 4 5 6 7
3 4 5 6 7 8 9 12
10 11
8 9 10 11 13 14 15 16 17 18
12 13 14 15 16 19 20 21 22 23
17 18 19 20 24 25 26 27
28 29 30
16
20-φ3
30-φ2.4
Contact
Wire size(mm2) Electrical ratings Matched cable diameter
Num.
1 646MCM 1 pin 1000A/1000V
4 3×35+1×16 3 phase 4 wires 150A/600V
5 3×35+2×16 3 phase 5 wires 150A/600V φ31~φ44.5
20 20×4 20 pins 25A/600V
30 30×2.5 30 pins 10A/400V
N N
A C A P
B C
B
18
4-φ10 5-φ10
Contact Wire size
Electrical ratings Matched cable diameter
Num. (mm2)
4 3×50+1×25 3 phase 4 wires 200A/600V
φ36~φ48.5
5 3×50+2×25 3 phase 5 wires 200A/600V
In practice, the holding-down nuts should be screwed until the cable is fixed completely.
3.3 contact sizes:
contact size Withdraw tool
Φ23 None
Φ18 None
Φ10/Φ12 QX-Exn-10
Φ9.1 QX-Exn-9.1
Φ7.5 QX-Exn-7.5
Φ5 QX-Exn-5
Φ3 QX-Exn-3
Φ2.4 QX-Exn-2.4
4 、 Mechanical performance and environment conditions in normal
operation.
——Shell:aluminium alloy
——Insulator:thermoplastic material
——cable sealing ring:anti-flame rubber
——Contact:copper alloy, silver plating
——Viberation:frequency 10Hz-2000Hz, acceleration 147 m/s2
——Shock:acceleration 490 m/s2
——Endurance:500 cycles
——Operation Temp:-55℃~+60℃
——ambient pressure: 80~110KPa
——Protect degree:IP67
——Application: The products can be used in the environment with flammable gases and vapors as
Zone 2 with temperatures classes T4, T3, T2 & T1.
——the cable entry seal ring should be timely replaced with another one of the same size and material
when it become aged and transformed.
5、Manufacture company:
AVIC JONHON Optronicl Technology Co, Ltd.
6、structure features
6.1 outlines
[Plug]
Shell D1 L1
8 φ46.8 140
10 φ58 148
D1
12 φ63.5 160
14 φ75.5 168
16 φ82.3 190
( L 1)
18 φ87.5 210
[Portable Receptacle]
4 × d1
Shell d1 P Q L2 L3
8 φ4.5 42.5 34 45 134
10 φ4.5 51 42 47 143
Q
P
12 φ4.5 56 47.5 47 154
14 φ5.5 70 60 47 162
( L2 ) Q 16 φ5.5 75 64 54 190
( L3 ) P
18 φ5.5 80 70 54 212
[Portable Receptacle Mounting Dimensions]:
E ± 0.1 Shell d2 D3 E
8 φ4.5 φ39 34
10 φ4.5 φ51 42
E± 0 . 1
+0 .3 12 φ4.5 φ58 47.5
D3 0
4× d2 14 φ5.5 φ71 60
16 φ5.5 φ76 64
18 φ5.5 φ82 70
[Panel Mount Receptacle]
4×d 1 Shell d1 P Q D2 L4 L5
8 φ4.5 42.5 34 φ33 10 54
10 φ4.5 51 42 φ42 14 61
D2
Q
P
12 φ4.5 56 47.5 φ48 14 63
14 φ5.5 70 60 φ61 14 69
L4
Q
(L5) 16 φ5.5 75 64 φ64.5 15 79
P
18 φ5.5 80 70 φ71 23 84
[Panel Mount Receptacle Mounting Dimensions ]:
Shell d2 D3 E
8 φ4.5 φ34 34
10 φ4.5 φ42.5 42
12 φ4.5 φ48.5 47.5
E ± 0. 1 14 φ5.5 φ61.5 60
16 φ5.5 φ65.5 64
φ71.5
E± 0. 1
+0 .3
D3 0
4× d2 18 φ5.5 70
6.2 Connectors Use
6.2.1 The cable connector can only be used when the plug and socket are integrated as a whole.
6.2.2 Make sure of complete assembly and connection of the product before it is powered on; and
make sure that power is cut off before separating the plug and socket.
6.2.3 Warning:
DO NOT SEPARATE WHEN ENERGIZED!
DO NOT CHARGE WHEN SEPARATED!
DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT!