0% found this document useful (0 votes)
60 views1 page

Attachments

The document is an inspection notice from Dubai Electricity and Water Authority regarding electrical installation work at an office project. It lists the project details and contractor information. It then provides 6 comments from the inspector noting issues that need to be addressed such as providing a 32A MCB for the ring circuit, proper light fittings, wire dressing, and labeling. The contractor is requested to complete the work and submit for reinspection to obtain final approval and electric supply connection.

Uploaded by

Fadi Alatrash
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views1 page

Attachments

The document is an inspection notice from Dubai Electricity and Water Authority regarding electrical installation work at an office project. It lists the project details and contractor information. It then provides 6 comments from the inspector noting issues that need to be addressed such as providing a 32A MCB for the ring circuit, proper light fittings, wire dressing, and labeling. The contractor is requested to complete the work and submit for reinspection to obtain final approval and electric supply connection.

Uploaded by

Fadi Alatrash
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Application No : F-043363

Date Of Inspection : 20.01.2019

Inspection Notice
(LV Installation)

Project Type : OFFICE-305


Plot No, Area : 878 , AL DAGHAYA
Owner : HASABI REAL ESTATE

Contractor Details :
Name : HITESH ELECTRICAL CONTRACTING LLC
PO Box, City : 27575 , 369-AL QUOZ IND. FOURTH
Email : info@hiteshelectricals.com
Fax : 043557542 Phone : 043552515

Following comments were noted by our Engineer during inspection of the Electrical Installation at the
above Project.
1 . Provide 32A MCB for the ring circuit in the consumer DB (B2/DB-305) as per the approval.
2 . Provide ceiling rose with heat resistant silicone rubber insulated with stranded copper conductor
for pendant type light fittings as per DEWA regulation.
3 . Provide proper pendant light fittings for the shops and submit the confirmation letter from the
tenant for the false ceiling works.
4 . Provide proper dressing for the DB wiring with neatly manner.
5 . Provide S & L ferrules for identification of supply and load wires at the kWh meters.
6 . Arrange Payment of Estimate.

You are requested to complete the installation/rectification and submit application for re-inspection
/ final inspection of your works.

Further, please coordinate with our Inspection Engineer to release electric supply to the project.

Contact Name : Mr. Raja Jagadeesan


Telephone No : 043229498

Yours faithfully,

For DUBAI ELECTRICITY AND WATER AUTHORITY