10 CVT-22

This document summarizes the specifications for an outdoor, oil immersed single phase medium voltage transformer. The transformer is rated for 22kV primary voltage and 0.11kV and 0.11kV secondary voltages. It has an insulation level of 50kV and impulse withstand of 125kV. The transformer is oil filled, has porcelain insulation, and aluminum terminals. Dimensions are provided.

Uploaded by

Thanh Duy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views8 pages

10 CVT-22

This document summarizes the specifications for an outdoor, oil immersed single phase medium voltage transformer. The transformer is rated for 22kV primary voltage and 0.11kV and 0.11kV secondary voltages. It has an insulation level of 50kV and impulse withstand of 125kV. The transformer is oil filled, has porcelain insulation, and aluminum terminals. Dimensions are provided.

Uploaded by

Thanh Duy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

TECHNICAL DOCUMENT

OUTDOOR, OIL IMMERSED TYPE, 1PHASE


MEDIUM VOLTAGE TRANSFORMER
TYPE: PT22-1ZHOD1P
22:√3/0.11:√3/0.11:3 kV; Burden 30/50VA Class 0.5/3P
TECHNICAL DATA SHEETS
Item No Description Tender requirement Offered
1 Manufacturer
GELEX ELECTRIC
2 Type Outdoor, single phase, Outdoor, single
oil immersion phase, oil immersion
3 Installation location The Low winding of the The Low winding of
transformers the transformers
220kV/110kV/24kV 220kV/110kV/24kV
4 Description Inductive voltage
transformer
5 Standards IEC 61869-5 IEC 61869-3;
IEC 60044-2
6 Rated frequency 50Hz 50Hz
7 Rated voltage 24kV 24kV
8 Rated primary voltage 22kV 22kV
9 Rated capacitance 4400-8800pF -
10 Insulation level A
10.1 Power frequency withstand 50kV rms Induced voltage
voltage, dry, 1 minute withstand test 50kV
10.2 Lightning impulse withstand 125kV peak 125kV peak
voltage (1.2/50µs)
10.3 Maximum Partial Discharge ≤ 10pC Comply
Level at 1.2 Un
11 Creepage distance, 25mm/kV > 600mm Comply
12 Rated voltage factor and
rated time
Continuous 1.2 Un 1.2 Un
08 hours 1.9 Un 1.9 Un
13 Rated voltage, rated output,
Brown porcelain
Accuracy Class
13.1 No. 1 22/√3 : 0.11/√3kV 22/√3 : 0.11/√3kV
30VA, cl 0.5 30VA, cl 0.5
13.2 No. 2 22/√3 : 0.11/3kV 22/√3 : 0.11/3kV
50VA, cl 03P 50VA, cl 03P
14 Operation condition
- Ambient temperature -5÷450C Comply
- Ambient humidity 95% Comply
15 Terminals

- Material Aluminium

TP106-20/220kV Trà Nóc/PT22-1ZHOD1P 11-2020 GELEX ELECTRIC 2/8


- Dimensions Indication See drawing
16 Outside of the insulator:
- Type: Cylindrical Cylindrical
- Materials: Porcelain Porcelain
- Colored porcelain: Brown Brown
17 Insulation oil required
17.1 - Type Indication EsTran
17.2 - Weight Kg 15
17.3 - Oil indicate Yes Yes
17.4 - Sample valve, drain valve Yes Yes

TP106-20/220kV Trà Nóc/PT22-1ZHOD1P 11-2020 GELEX ELECTRIC 3/8


LIST OF TECHNICAL DOCCUMENT
OUTDOOR, OIL IMMERSED TYPE, 1PHASE
MEDIUM VOLTAGE TRANSFORMER
TYPE: PT22-1ZHOD1P
22:√3/0.11:√3/0.11:3 kV; Burden 30/50VA Class 0.5/3P

1. Speccifications
2. Connection diagram
3. Dimension

TP106-20/220kV Trà Nóc/PT22-1ZHOD1P 11-2020 GELEX ELECTRIC 4/8


SPECIFICATIONS OF
OUTDOOR, OIL IMMERSED TYPE, 1PHASE
MEDIUM VOLTAGE TRANSFORMER
TYPE: PT22-1ZHOD1P
22:√3/0.11:√3/0.11:3 kV; Burden 30/50VA Class 0.5/3P

GENERAL
- Medium voltage transformers type PT * are instruments convert large AC voltages in the
primary circuit to an appropriate level for secondary circuit equipment at the medium
voltage line (up to 40.5kV).
- PT* serises are designed epoxy casting or insulating oil immersed type.
- PT* series have high performance and high reliability. They are manufactured and tested
by modern technology line and equipments, ensured quality according to ISO9001:2015.
They comply with accuracy class specifications of the international standard IEC 61869-3;
IEC 60044-2.
- There are medium voltage feeding transformer for supplying low voltage to CB reclose
and other equipments.
1. Description:
- The steel cores are made of the grain-oriented silicon steel with high permeability,
ensuring minimum power fluctuation.
- The wire of coils made of enamel wire with high quality, temperature up to 200°C.
- The whole cores and coils are encapsulated by insulating oil immersed with hight
insulation, impervious to moisture.
- The primary inputs are connected by parallel groove connector or other types with high
trustworthily .
- The secondary terminals are located in an integral terminal block of body with protecting
box, terminalcover made of aluminium and sealing screws.
- The connection diagram is marked on the Name-plate.
- The base with 4 holes is easy for installing PT.

TP106-20/220kV Trà Nóc/PT22-1ZHOD1P 11-2020 GELEX ELECTRIC 5/8


2. TECHNICAL DATA

 Rated primary voltage (Un) : 22:√3kV


 Rated secondary voltage : 0.11:√3 /0.11:3kV
 Rated frequency (fn) : 50Hz
 Induced voltage withstand test 50kV : OK
 Impluse withstand voltage (1,2/50µs) : 125kV
 Rated voltage factor : 1.9xUn (8h)
 Burden : 30/50VA
 Class : 0.5/3P
 Creepage distance : 25 mm/kV
 Dimension
- Hight : 975 mm
- Width : 315 mm
- Length : 420 mm
 Weight : 77 kg
: 15kg (~17litres)
 Oil Weight

3. Instruction and maintenance

- Avoid strong shaking and impacting during transportation.

- Maintain at dry place, avoid dust, chemical, burning and exploded material, heat emitting or

strong shaking and impacting places.

- See the technicality and connection diagram before install. Check the oil leakage of the
cover.

- Insulation resistance test.

- Before power on, it is necessary to check the neutral connector (N) of the potential
transformer. Ground one terminal of each secondary winding during operation.

- The base must be grounded.

- Please do not connect over rated burden.

TP106-20/220kV Trà Nóc/PT22-1ZHOD1P 11-2020 GELEX ELECTRIC 6/8


CONNECTION DIAGRAM
OUTDOOR, OIL IMMERSED TYPE, 1PHASE
MEDIUM VOLTAGE TRANSFORMER
TYPE: PT22-1ZHOD1P
22:√3/0.11:√3/0.11:3 kV; Burden 30/50VA Class 0.5/3P

TP106-20/220kV Trà Nóc/PT22-1ZHOD1P 11-2020 GELEX ELECTRIC 7/8


DIMENSIONS (mm)
OUTDOOR, OIL IMMERSED TYPE, 1PHASE
MEDIUM VOLTAGE TRANSFORMER
TYPE: PT22-1ZHOD1P
22:√3/0.11:√3/0.11:3 kV; Burden 30/50VA Class 0.5/3P

TP106-20/220kV Trà Nóc/PT22-1ZHOD1P 11-2020 GELEX ELECTRIC 8/8