0 ratings0% found this document useful (0 votes) 1K views81 pagesUntitled
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, 
claim it here.
Available Formats
Download as PDF or read online on Scribd
AVTRON MODEL K696/K696A.
RESISTIVE LOAD BANK
Part Number D16133/D16423
Serial Numbers 595 Through 649
© 1983 Avtron Manufacturing, Inc. April 13, 1983
Cleveland, Ohio Rev. Mar. 24, 1995
Rev. Apr. 6, 1995This document contains drawings and information that, due to design
changes or customer modifications, may not reflect the hardware in its
present state. Avtron Manufacturing, Inc. cannot assume responsibility for
damage to equipment, or personal injury resulting from the use of this
manual when installing, operating, or servicing the unit. Avtron has made
every attempt to provide documentation which reflects the original hardware
configuration.AVTRON MANUFACTURING, INC.
Cleveland, Ohio
AVTRON MODEL K696/K696A
RESISTIVE LOAD BANK
Part Number D16133/D16423
    
    
   
 
     
TABLE OF CONTENTS
Section
I SAFETY CONSIDERATIONS ...........
IL K696 DESCRIPTION ........ sees
III K696A DESCRIPTION ........0-.2eeeeeeeeeeeeee sees Bed
Iv INSTALLATION ..........++ sees 41
v OPERATION Gases ee
VI K696A AUXILIARY OPERATION ........--- 2 6-1
VII OPTIONS FOR MODEL K696/K696A ............ Te.
OPTION 17, AUTOMATIC LOAD SHED SYSTEM ... 7-1.
(Drawings for options are listed at the
end of the Table of Contents.)
VIII MAINTENANCE .....--200---+005 8-1
Ix K696 REPLACEMENT PARTS LIST . 9-1
bg K696A REPLACEMENT PARTS LIST .. 10-1
 
APPENDIX - Avtron Load Bank Troubleshooting Guide
DRAWINGS FOR K696
SB1360 Outline Drawing
D16146 = Schematic Diagram
D16136 = Wiring Diagram, Load Bank
D16152 Wiring Diagram, Control Panel
D17049 ©=«-« Schematic, PC Board
DRAWINGS FOR K696A
 
$B1360 Outline Drawing
D16464 Schematic Diagram
D16463 Wiring Diagram, Load Bank
16222 Wiring Diagram, Control Panel
LKG/cr
Rev. 7/6/88
Rev. 1/20/97‘Avion Mode! K6S6/K596A
Losd Bank
 
TABLE OF CONTENTS (Cont.)
OPTIONS - Refer to Section VII (OPTIONS FOR MODEL K696/K696A) of
this manual. The following drawings apply to the various
options. Only the appropriate drawings have been
included in this manual as required by options delivered.
Not all options can be installed in the same unit at the
same
Drawings
B16250
16723
16724
B19078
17604,
Sheet 3
B19575,
Sheets 2 & 3
18523
18701
20523,
Sheet 3
A21230
Sheet 3
23382
23974
BMPikv
2888
Rev. 1/8/98
time.
Installation of Option 6
Schematic, Remote Control Unit (option 7)
Wiring Diagram, Remote Control Unit (Option 7)
Schematic, Automatic Load Shed Control (Option 17)
Wiring Diagram, Test Jacks Kit (Option 19) -
K696 Only
Schematics, Fan Reversal Switch (Option 20)
Sheet 2 - K696 Sheet 3 - K696a
Installation Instructions, Control Transformer
(Option 22)
Schematic, Control Transformer (Option 23)
Wiring Diagram, 600/120V, 50/60 Hz Control
‘Transformer (Option 30)
Schematic, Control Transformer 500 VA, 220/110V,
50/60 Hz (Option 32)
Installation of Option 35 (for Load Banks S/N 743
and above)
Installation of Option 36AVTRON NODEL K696/K696A
RESISTIVE LOAD BANK
Part Number D16133/D16423
SECTION I
SAPETY CONSIDERATIONS
Throughout this manual, you will find WARNING and CAUTION statements.
Personal injury to an operator using or repairing the equipment
may occur if a WARNING statement is ignored. Damage to the
equipment and potentially hazardous conditions for personnel may
occur if a CAUTION statement is ignored.
Each Avtron unit is safety checked for opens and shorts, and the
insulation is high potential tested to insure safe operation.
All fuses, safety interlocks and related safety equipment have
been tested as part of the testing procedure of each unit.
As part of your safety program, an initial inspection after
receiving the unit(s) and periodic preventive maintenance and
safety inspections should be conducted to insure the reliability
and safety built into your Avtron equipment.
The Model K696/K696A Load Banks are industrial test units designed
to be used indoors safely. However, because of the nature of the
Load Bank function (the dissipation of electrical energy), there
is inherent danger to the operators and to the equipment. These
dangers shall be outlined in this section.
Electrical energy is transformed into heat by the resistors.
This heat must be removed from the Load Bank by the cooling
blower. If there is any restriction or stoppage of airflow, the
Load Bank may overheat and may even start a fire. The following
events must be conducted if safe operation of the Load Bank is to
take place.
1. Read the manual before operating Load Bank.
2. An approved ground conductor wire from the Load Bank
ground lug and the generator frame to a good earth
ground must be connected. (Refer to the following table.)
3. Do not bypass the airflow switch to prevent nuisance
tripping. The switch is designed to drop out the load
if sufficient air is not reaching the load elements.
LKG/er q-1
Rev. 7/1/87
Rev. 4/28/88Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
70-116 NATIONAL ELECTRICAL CODE
 
Table 250-95. Minimum Size Equipment Grounding Conductors for
Grounding Raceway and Equipment
 
 
 
 
 
 
  
 
 
 
 
 
 
 
 
Rating or Setting of Size
‘Automatic Overcurrent
Device in Circuit Ahoad ‘Aluminum or
of Equipment, Condi Copper-Clad
‘tc., Not E> Copper ‘Aluminum,
(amperes) Wire No. *
15 4 12
20 12 10
30 10 8
40 10 8
60 10 8
100 8 6
200 6 4
300 4 2
400 3 1
500 2 1/0
600 1 2/0
800 0 3/0
1000 2/0 4/0
1200 3/0 250 MCM
1600 40 350”
2000 250 MC 400”
2500 350” 600”
3000 400” 600”
4000 500” 300”
5000 700” 1200”
6000 800” 1200”
NOTE: This information is provided only for reference.
For complete information, refer to applicable
sections of the NEC.
* See installation restrictions in Section 250-92(a).
Taken from National Electrical Code ® 1987
MP/kv 1-2
4/28/8810.
Le
LKG/cr
Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
Do not bypass any fuses which have blown. Bypassing
fuses can result in damage to the equipment and potentially
hazardous conditions for the operator. If a fuse is
blown, determine the cause of the blown fuse and correct
the situation.
Replace any burned out bulbs on the Control Panel.
Each lamp is an indication that a system is active or
has failed and is important to the operation of the
Load Bank and safety of the operator.
Maintenance personnel must always exercise caution when
access panels are removed. Personal injury from electrical
shock or from the moving blower blade may result if all
sources of power are not disconnected before servicing.
This is especially important since the blower motor has
an automatic reset overload relay that can restart the
blower. Maintenance work must be conducted only by
qualified personnel.
The Load Bank should be operated in a cool, well ventilated
area as described in the INSTALLATION section of this
manual. Do not allow exhaust air to recirculate through
the Load Bank.
Venting the heated air from the Load Bank exhaust is a
potential hazard. The Load Bank should be used in a
cool, well ventilated area.
Allow cool air to pass into the unit to cool the elements.
Do not allow the unit to be placed where hot exhaust
air can recirculate back through the unit causing a
constant rise in cooling air temperature.
After running a load test, leave the cooling blower on
for two minutes to allow the air to remove accumulated
heat from exhaust surfaces.
The operator should avoid coming in contact with the
resistor elements or surrounding covers during and for
some time after operation. These portions of the Load
Bank become quite hot and may result in a serious burn,
should contact be made with them.
Rev. 7/1/87
Rev. 4/28/8812.
1.
14,
15.
16.
le
18.
LKG/cr
Avtron Model K696/K696A,
Resistive Load Bank
Part Number D16133/D16423
Do not allow objects to enter or block the air intake
or exhaust of the Load Bank. A blockage could cause
Load Bank overheating. If an object enters the screens,
it will cause damage to the resistor elements, possibly
shorting them and causing shock and fire hazards.
Operators must not operate the Load Bank with the
access panels or screens removed or doors open. To do
80 exposes the operator and other persons to possible
personal injury from electrical shock or from the
moving fan biade.
Always put a short or shunt across the current transformers
(C.T.) when working on metering. Powering up an unshunted
C.m, will destroy the C.T. with possible harm to personnel
and metering.
Emergency shutdown procedure:
A. In an emergency, shut down the MASTER LOAD Switch,
then the generator. The MASTER LOAD Switch will
allow disconnection of all load steps and still
allow fan motor to run, cooling any heated elements.
B. The power ON/OFF switch will disconnect both load
steps and fan motor. A customer-supplied Generator
Emergency OFF Switch should be located near the
Load Bank.
An approved electrical fire extinguisher should be on
hand at all times.
It is the responsibility of the customer to take diligent
care in installing the Load Bank. The National Electrical
Code (NEC), sound local electrical and safety codes,
and the Occupational Safety and Health Act (OSHA)
should be followed when installing the equipment to
reduce hazards to persons and property. (Refer to the
following tables for additional information.)
Read and heed all WARNING and CAUTION statements in the
manual.
Rev. 7/1/87
Rev. 4/28/88NOTE:
MP/kv
4/28/88
Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
ARTICLE 310 — CONDUCTORS FOR GENERAL WIRING _ 70-153
‘Table 310-16. _Ampacitios of Not More than Three Single Insulated
‘Conductors, Rated 0 through 2000 Veli, n Raceway in Free Air
‘and Ampacities of Gable Types AC, NM, NMG ond SE.
Based on Ambiont Air Tomperaturo of 30°C (86°F)
 
 
 
 
 
 
 
 
  
    
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
‘ls tea slay femited cess ys Cole jig rcavet
Tee ites ea ca hy acd sate ae
{er 2AWG tnd anges or 10 AWG santas stoner ci tee sf y
‘Spe, i fo" alent tempore ed ramer of codutan ve ew apad
‘Far ry ted damp leno oly. Ser 15°C couma for welicaieas
 
 
This information is provided only for reference.
For complete information, refer to applicable
sections of the NEC.
Taken from National Electrical Code® 1987
1-5Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
8. Ampacity Adjustment Factors.
(a) More than Three Conductors in a Raceway or Cable. Where the
number of conductors in a raceway or cable exceeds three, the ampacities
given in Tables 310-16, 310-18, 310-22, 310-26, 310-27, 310-28, 310-29, 310-30,
and 310-31 shall be reduced as shown in the following table:
70-168 NATIONAL ELECTRICAL CODE
 
Percent of Values in Tables
310-16, 310-18, 310-22, 310-26,
310-27, 310-28, 310-29, 310-30,
 
Number of and 310-31, as Adjusted for
Conductors Ambient Temperature if Necessary
4 thru 6 80
7 thru 9 70
10 thru 24* 10
25 thru 42* 60
43 and above* 50
 
* These factors include the effects of a load diversity of 50 percent.
NOTE: This information is provided only for reference.
Por complete information, refer to appli
sections of the NEC. ae
Taken from National Electrical Code (®) 1987
MP/kv a
4/28/88Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
SECTION II
K696 DESCRIPTION
The K696/D16133 is a portable, indoor, self-contained unit for
electrically loading and testing generators. ‘The Load Bank is
rated at 250 KW at 240/480 volts. The available load steps are
100 KW, 50 KW, 50 KW, 20 KW, 10 KW, 10 KW, 5 KW, 5 KW, 4 KW, 3 KW,
2 KW, and 1 KW. The first seven load steps are selected by
toggle switches. The last five load steps are selected by a
rotary selector switch. The Load Bank provides a balanced load
for three phase generators within the range listed above. Single
phase loads are 2/3 the normal three phase load.
The blower motor is a 2 HP, three phase motor which operates from
230/460 volts, 30, 60 Hz power. The blower motor obtains power
from either the power source under test or from a remote source,
depending upon the positioning of fanning strip (FS4) on terminal
board 1B4. When operating from the power source under test, the
motor circuit automatically connects the motor for high or low
voltage. The K696 will test 240/480 volt, 36, 60 Hz generators
without any wiring changes. It can be used to test 60, 50 Hz, or
400 Hz generators; however, the blower motor and control circuit
power must be separate 60 Hz sources. For separate 60 Hz blower
motor power connection, see Section IV. Control power is 115
VAC, 60 Hz. A line cord is provided for control power.
Blower failure protection is provided in two ways. A differential
pneumatic pressure air switch (S17) senses the airflow through
the Load Bank. An additional slave relay (K30) is activated only
if power is applied to the blower motor terminals. This slave
relay will disconnect control power to all load contactors should
the blower power be disconnected, the motor overload trip out, or
the air inlet/exhaust screens become blocked.
TESS IIIS SI IIS IIIS ECS OBI IGE IG
CAUTION
This Load Bank should never be used without
the Fan Blower Motor operating. Inadequate
cooling airflow will result in resistor
elements overheating and a definite fire
hazard.
TESS I SSIS I III III III AAI
LKG/er 2-1
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
General Construction (Refer to Outline Drawing $B1360.)
The Control Panel is mounted on the Load Bank, but is also sized
for mounting into a 19-inch rack enclosure. The control panel
contains all the switches required to operate the Load Bank.
Voltage and current measurements are displayed on separate 3-1/2
digit LCD meters with a character height of 0.8 inch. The K696
Load Bank is constructed of aluminized steel and fiberglass,
forming a rigid structure. Mounted within this structure is the
load element resistor assembly, the cooling blower, the load step
contactors, motor starter, motor overload relay, fuses and customer
connection terminals. ‘The cooling air is drawn in from both sides,
forced across the resistor elements and exhausted out the end.
The unit is mounted on five-inch casters with one set provided
with wheel locks. ‘The customer connection panel is located at
the rear of the unit. Ahandle located above the customer connection
panel is provided for cable storage.
The Load Bank can operate at either 480 or 240 volts. A switch
on the control panel (S2) will automatically switch the load from
the high voltage configuration to the low voltage configuration
The blower motor configuration also changes if powered from
generator under test. The blower motor has separate overload
Protection for high and low voltage operation. The voltage
protection circuit will select the high voltage mode if 480 volts
is applied to the bus and S2 is in the 240 volt position.
Lower voltages and different frequencies may be applied to the
load circuit of the Load Bank. Frequency change causes no derating
of the load, however, the applied KW with a lower voltage is
computed with the following formula:
 
KWapplied RWRated x (Voltage Applied)?
(Voltage Rated)2
TASES IHS O SSH E ES SE rir
CAUTION
Never exceed the rated voltage, because this
will cause the Load Bank to overheat. Do not
apply DC voltages, because the contactors do
not have arc blowout magnets.
JESS SSSI ISOS ISOS IIIS SESS IOI IIA II
LKG/cr 2-2
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
JESSIE IID III II TIE
CAUTION
External blower power is required if a voltage
different than 240/480 is being applied or a
frequency other than 60 Hz. (See Section IV
for further details.)
JHE HESS SSIS OT I III IIIS IO III
System Description - Option 17, Automatic Load Shed System
The Model K696 is offered with an optional Automatic Load Shed
Control. It is comprised of a Load Shed Controller Part Number
18495 and a Current Transformer Part Number 370390 interfacing
with the K696 Load Bank manual controls. Option 17 maintains a
minimum load on a power source. ‘The separately supplied multi-
tap current transformer provides the feedback signal required to
operate the system. This feedback signal drives two (2) field
adjustable current sensing relays which detect the load level. The
system limits the resolution of the K696 Load Bank to 10 KW while
the Load Shed Controller is operating the Load Bank, whereas
operating the Load Bank manually maintains the 1 KW resolution.
The Load Shed Controller can be expanded to accommodate a K696A
auxiliary Load Bank by adding a jumper wire on the automatic Load
Shed Controller Part Number C18495.
Automatic Load Shed Controller Description (Option 17)
The optional Avtron Automatic Load Shed Controller Part Number C18495
contains all of the control devices of the system. The controller
has field adjustable setpoints which sense single phase current
from a current transformer. The setpoints (high/low) are adjusted
for the required operation range of the generator. The setpoints
inform the controller to increment, hold, or delete load. The
phase current is detected through the current transformer Part
Number 370390, The current transformer is inserted on the generator
side of the actual load and the Load Bank. (See Figure 7-1.)
To start the controller, a customer-supplied contact (N.0.) must
be closed. (See Load Bank Schematic/Interconnection Diagram
B19078.) This contact activates a 5-second time delay and enables
the controller. Avtron recommends that the generator overload
LKG/er 2-3
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
protection circuit open the customer-supplied contacts to immediately
shut down the auto load system if an excessive overload is detected.
Once the customer contacts close, the Load Bank will remain idle
for five (5) seconds, allowing the system to stabilize. The
controller adds load steps in 0.8-second intervals and deletes load
steps at 0.2-second intervals.
If the system experiences many overshoot conditions during the
course of normal operation, there can be conditions where the
controller may repeat operations. A repeated operation would be
viewed as a delay while the controller steps up to its previous
status.
 
If an overload is detected, the controller
will only attempt to remove load steps for
1.0 second or four load steps. Once the 1.0
second is reached, the unit will drop out all
remaining energized load steps.
Enclosure
‘The optional Automatic Load Shed Controller is enclosed within a
20 inch x 20 inch x 6 inch deep NEMA 12 wall-mount enclosure.
JES ESSE SSIS SISSIES ISIS ISHII TIT IE
WARNING
Disconnect all power from the Load Bank and
the Load Shed Controller before servicing.
JHE USS S EIS E SSSI S SEIT IIIT
The enclosure protects the internal electronics from direct dust,
dirt, oil, and water. The enclosure access door must remain
closed. The operating temperature for the controller is from 00°C
to 450C with a non-condensing humidity from 5% to 95%.
LKG/cr 2-4
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
SECTION ITI
K696A DESCRIPTION
‘The K696A is a variant of the K696.
It has the versatility of a self-contained Load Bank, or it may
be used as a companion to the K696. The K696A has three load
steps of 50 KW, 100 KW and 100 KW for a total of 250 KW. The K696
has the capability to control two K696A's and itself for a total
energy-absorbing capacity of 750 KW, To use the K696A as an
auxiliary companion Load Bank to the K696, see Section VI.
The blower motor is a 2 HP, three phase motor which operates from
240/480 volts, 30, 60 Hz power. The blower motor obtains power
from either the power source under test or from a remote source
depending upon the positioning of fanning strip (PS4) on terminal
board (1B4). When operating from the power source under test,
the motor circuit automatically connects the motor for high or
low voltage. The K696A will test 240/480 volt, 30, 60 Hz generators
without any wiring changes. It can be used to test 60, 50 Hz, or
400 Hz generators; however, the blower motor and control circuit
power must be separate 60 Hz sources. For separate 60 Hz blower
motor power connection, see Section IV. Control power is 115 VAC,
60Hz. A line cord is provided for control power.
Blower failure protection is provided in two ways. A differential
pneumatic pressure air switch (S17) senses the airflow through
the Load Bank. An additional slave relay (K30) is activated only
if power is applied to the blower motor terminals. This slave
relay will disconnect control power to all load contactors should
blower power be disconnected, the motor overload trip out of the
air intake or exhaust screens become blocked.
JHE ESHEETS III III III Ir
CAUTION
This Load Bank should never be used without
the Fan Blower Motor operating. Inadequate
cooling airflow will result in resistor
elements overheating and a definite fire
hazard.
JESSIE SE TEES III III IIE
LKG/cr 3-1
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
General Construction (Refer to Outline Drawing SB1360.)
The control panel is mounted on the Load Bank, but is also sized
for mounting into a 19-inch rack enclosure. ‘The control panel
contains all the switches required to operate the Load Bank.
‘The K696A Load Bank is constructed of aluminized steel and fiberglass,
forming a rigid structure. Mounted within this structure is the
load element resistor assembly, the cooling blower, the load step
contactors, motor starter, motor overload relay, fuses, and
customer connection terminals. The cooling air is drawn in from
both sides, forced across the resistor elements, and exhausted
out the end.
The unit is mounted on five-inch casters with one set provided
with wheel locks. The customer connection panel is located at
the rear of the unit. A handle located above the customer connection
panel is provided for cable storage.
The Load Bank can operate at either 480 volts or 240 volts. A
switch on the control panel (S2) will automatically switch the
load from the high voltage configuration to the low voltage
configuration. The blower motor configuration also changes if
powered from generator under test. The blower motor has separate
overload protection for high and low voltage operation. The voltage
protection circuit will select the high voltage mode if 480 volts
is applied to the bus and S2 is in the 240 volt position.
Lower voltages and different frequencies may be applied to the
load circuit of the Load Bank. Frequency change causes no derating
of the load, however, the applied KW with a lower voltage is
computed with the following formula:
2
KW oied = KM 5
Applied ae (Voltage Rated) 2
FEES IU III II III III I III ITI III
CAUTION
Never exceed the rated voltage because this
will cause the Load Bank to overheat. Do not
apply DC voltages because the contactors do
not have arc blowout magnets.
JESSE IORI IIE TI III III III III AE
LKG/cr 3-2
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
JOSHI OE EE EE IIE IESE
CAUTION
External blower power is required if a voltage
different than 240/480 is being applied or a
frequency other than 60 Hz. (See Section Iv,
INSTALLATION, for further details.)
TEES S SSSI IIS SEIS OEE IIS ISIE
System Description ~ Option 17, Automatic Load Shed System
See Section II.
LKG/cr 3-3
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
SECTION IV
INSTALLATION
Before Installation
Inspect the Load Bank for obvious damage such as broken wires,
broken or dented panels, cracked ceramic insulators, or any other
component breakage that may have occurred in shipment.
Location
The K696 & K696A Load Banks are designed for indoor use. ‘The
Load Bank must be used in a cool, well ventilated area. It must
be installed where cool air is continually available and where hot
exhaust air will not be recirculated through the Load Bank. If
the Load Bank is operated in a closed space, ventilation of
6,000 CFM or greater is required.
A minimum of eight feet of clearance from the inlet and exhaust
is required for proper airflow.
JHE ESSE ESSE SSIES IE ISIE
WARNING
The exhaust air may be in excess of 2500P
under full load conditions. ‘The unit must
not be installed near any equipment, wiring
or plumbing which may be damaged by high air
temperatures or which may constitute a fire
hazard. Care should also be taken so as not
to set off a sprinkler system by exposing it
to hot exhaust air.
TEE HEISEI ES III EIS S IOI III I III
Airflow Considerations
Even with an ample supply of cooling air, the Load Bank may
overheat, if it is not properly installed. ‘There are two types
of airflow problems that should be avoided:
LKG/cr 4-1
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
RECIRCULATING AIRFLOW ~ If the hot, exhausted air is permitted
to recirculate through the Load Bank, it will reach such a
high temperature and low density that it will no longer cool
the resistance elements. A Load Bank should not be installed
so close to any surface which may reflect the exhausted air
back to the air intake. When two or more Load Banks are
being used, care must be taken in positioning the Load Banks
so that the exhausted air of one unit does not feed the air
intake of another.
RESTRICTION OF COOLING AIR - Any obstruction located within
eight (8) feet of the inlet or exhaust screens will restrict
the Load Bank's airflow. Airflow is also restricted when
two or more Load Banks have air inlets positioned close to
each other. This competition for cooling air causes a low
pressure area, restricting adequate airflow to either unit.
JESSE ESSE IIS EES II IEE II IIE II
WARNING
It is vitally important to install the Load
Bank properly. Installation errors may
result in a catastrophic failure. The Airflow
Switch, a protective device in the Load Bank,
will guard against some of these problems.
If protective circuitry prevents application
of the load, determine the source of the
problem. DO NOT DISABLE the AIRFLOW SWITCH.
‘This will cause a safety hazard and will void
our warranty. The following installation
instructions are critical to the safe operation
of the Load Bank. (Refer to Section I,
SAFETY CONSIDERATIONS, of this manual.)
FEES S SESH SESS O SSUES IOC Un OEE Ee
Power Requirements
The Load Bank requires a 115V, 10, 60 Hz, 10 amp source of power
for operation of the control circuit. A power cord for control
power is provided with the Load Bank. Connect unit to a grounded
115 volt source.
LKG/cr 4-2
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
An optional control transformer may be installed in the K696/D16133
and K696A/D16423 Load Banks. This option (Option 6 in the
Replacement Parts List) enables the operator to use the generator
output for control power. When the operator applies either 240 V
or 480 V to the primary, the control transformer automatically
supplies 120 VAC for control power. As an assurance that proper
voltage and frequency are applied to the transformer, Option 6 is
connected in parallel with the blower motor. An external power
source must be provided (as described in section B of Blower Motor
Connections) if internal power for motor and control power is not
desired.
During startup, be sure the load switch on the generator under test
is not "ON" until the prime mover has the generator up to speed.
This avoids blowout of fuses Fil and F12. Also, be sure the load
switch is OFF before generator shutdown procedures are started.
JESSE SIS ISI SSH SISIISIS SII I IEE
CAUTION
When the Load Bank includes this option, never
connect a control power line cord to TB4 (12)
and TB4 (13). This would permanently damage
the control transformer.
JESSE IIIS SIS SIISSIII IO
Blower Motor Connections
The blower circuit consists of fuses, motor starters, contactors,
overload relays, and the blower motor.
A. INTERNAL BLOWER POWER OPERATION: The blower is connected on
FS4 which is between terminals 1-5 on TB4. When operating the
blower motor from the generator source, an additional load of
2400 watts will be applied. This additional load will be
reflected in the meter readings and should be noted on load
readings to prevent errors.
 
REMOTE FAN POWER OPERATION: When testing single phase system
or systems or a frequency other than 60 Hz, the fan motor must
be run from a separate source. To do this, locate TB4 on the
customer connection panel at the front of the Load Bank.
 
LKG/or
Rev. 7/1/87
Rev. 3/24/95 4-3Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
Remove fanning strip FS4 from terminals 1 through 5 on TB4 and
reconnect it to terminals 6 through 10. Next, connect the
jumper wire from terminal 11 to either terminal 10 (for 480V
fan power), or to terminal 9 (for 240V fan power). Connect
the external fan power source to terminals 6 through & of
1B4, Be sure the fan rotates in the proper direction before
operating the Load Bank. If the blower rotation is reversed,
interchange any two leads supplying power to the motor.
NON-STANDARD BLOWER MOTOR FREQUENCY: Blower motor will
operate between 208 and 250 volts and between 416 and 500
volts at 3-phase, 60 Hz.
Connection at 50 Hz is the same as 60 Hz, shown on the following
page, with motor voltage range of 180 to 220 volts and 360 to 440
volts.
JESSE SISSIES CSS ISOS IIS III I IE
WARNING
When operating at 50 Hz, the motor speed (RPM)
is reduced, which also reduces cooling of Load
Bank. Do not exceed 400 volts in the 480 mode
or 200 volts in the 240 mode, to input bus
when running the fan at 50 Hz.
TEESE HUIS ISIS IIIS IIIT IIIS II III
CAUTION
Do not attempt to operate any blower motor at
400 Hz. When loading unit with power other
than 50/60 Hz, the blower motor must be wired
to external power source supplying any of the
above proper voltages and frequencies.
JESS OSI ISIS SAI IIIT IIIS
LKG/er
Rev.
Rev.
7/1/87
3/24/95 4-4Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Connection when
the Load Source
is used to run
the fan motor
230V or 460V.
LKG/cr
Rev. 7/1/87
 
 
 
 
 
 
Connections when
the fan motor is
run on a 460V
external power
source.
 
 
 
 
 
 
fw] | | Fanning rs | 7 ol w
[=| Strip
= wa} S22 a o m D
5 =| { tion = 3 = =
= 5 sp,asov (To = 2 S
60" 39,2304 Fanning
~ I= | Line ({“ S 60H | |~ "| | strip
= fe 2 a tine | [> =| \eonnee-
e = Fanning ion
© |) strip 7 7
z S a S| | conse = =
a = = ‘ion Jumpet 7 =
= = Jumper, = opp
a a 2 a]
 
Connections when
the fan motor is
run on a 230V
external power
source.Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
NOTE
The fanning strip is prewired in the factory
and is designed to be easily connected to and
disconnected from TB4 when the blower motor
power source changes.
Load Connection
Connect a 240/480 volt, three phase source to the three fused
bars labeled A, B and C, located on the customer connection
panel. Cables to the Load Bank should be sized to handle the
maximum rated load according to the National Electric Code. ‘The
current can be determined by the following formula:
KW_x 577
VOLTAGE (LINE TO LINE)
 
Line Current
696 TYPICAL LOAD WIRING
 
10 39 ond capactty
GENER 00s
7018 oN capacity
GeweravoR oot
FEES SSSI SEUSS SE IS EEI IOSD
WARNING
"B" Bus and any attached wiring are electrically
hot when operating Load Bank in single phase.
JEU OSE ESSE ISIS ISSO ISITE IS IIE
LKG/cr 4-6
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
Grounding
A permanent ground should be connected to the Load Bank enclosure
either by a grounded conduit or with a separate ground wire to
prevent a potential above ground on the enclosure. No internal
ground connections are made to any terminal on the Load Bank.
The ground conductor should be run with the load power conductors
to provide the lowest impedance fault path. The ground stud must
be connected to both the generator frame and a good earth ground.
The ground conductor should be sized for National Electric Code
section 250-95 if not superseded by local codes.
JOSIE SISOS I IO III I IIT I I III
WARNING
Do not operate the Load Bank with any panel
or screen removed. This may expose the operator
to dangerous high voltage and the rotating
fan blade, as well as disrupting the airflow.
TEE ESS III IIIS III III III I I III
Optional Load Capacity
Optional auxiliary load capacity may be added to the K696 by
purchasing a K696A. (See Section VI, K696A AUXILIARY OPERATION
of this manual.)
Storage
The Load Bank should be covered to protect against moisture, and
the accumulation of dust and dirt. ‘The unit should be stored in
a dry, enclosed area. An optional waterproof vinyl cover (option
1) is available for the Load Bank; however, even with this cover,
the Load Bank should not be stored outdoors.
Install £ Option 17 ; a a
Option 17, Automatic Load Shed Controller, has two (2) parts: the
Load Shed Controller Part Number C18495 and the separately supplied
Current Transformer Part Number 370390.
LKG/cr 47
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
The current transformer must be installed at the main
power bus of the power source to be loaded. The current
transformer must be installed before any branching to
other loads so that the controller monitors total
generator load. (See Figure 7-1.)
 
The Load Shed Controller is contained within the 20 x
20 x 6-inch deep NEMA 12 enclosure. The controller
should be located between the Load Bank and the source
or at the Load Bank itself. All current transformer
interconnecting wire lengths should be minimized.
 
Control Co: ions for Option 17
All interconnections from the Load Bank to the optional controller
are shown on the Schematic/Interconnection Diagram Part Number
B19078. The controller derives 120 VAC control power from the
K696 control power although the Load Shed Controller power can
also be derived from any 120 VAC, 60 Hz source
Select the next higher C.T. ratio than the full current output of
the power source.
Amp(Line) =
 
The current transformer taps are defined below:
 
REQUIRED
C.T. RATIO TAP
300:5 XB-K4
500 X4-K5
800 X3-K5
1001 x1-x2
1201 X2-K3
1501 X2-K4
2001 X2-K5
2201 X1-K3
2501 x1-K4
3001 x1-K5
LKG/cr 4-8
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
FEES SII IOI III II III IIIT I ITI I III
WARNING
Disconnect all sources of power before
interconnecting the controller.
The control power circuit is protected by
fuses Fl, F2, F3, and F10. Use only the
fuses listed in the spare parts list. Do not
bypass the fuses if they blow. Bypassing the
fuses can result in damage to the equipment
and potentially hazardous conditions for the
operator.
TOES IESE III III II III IE
Disconnect power from the Load Shed Controller unit when the unit
is not in use. Never allow the secondary of the current transformer
to remain disconnected when primary current is passing through
the transformer. If the Load Shed Controller unit must be
disconnected, put a short or shunt across the current transformer.
 
A_Au:
An additional jumper is required when the Automatic Load Shed
Controller interconnects with a K696 and a K696A Load Bank. A
jumper is required in Controller C18495 from TB11 (25) to TB11 (26).
The incremental steps of the Load Shed Controller are based on
the K696 Load Bank. The K696A Load Bank must be preset to 250 KW
bulk load when interconnected or the system will not increment
correctly.
JX HE EIS S OI SISSOSISIOSE SO ETS IAT IA
CAUTION
When drilling or tapping holes in the enclosure,
do not allow metal shavings to enter any
device within the Load Shed Controller.
Take care in connecting the Load Bank and
controller. The controller could be permanently
damaged if incorrectly connected.
JEU UES ESSE HGS ISS IST II
LKG/cr 4-9
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
The Auto Load Shed Controller (P/N C18495) can be a free-standing
or wall-mount unit. Control power and interconnections are made
by punching a hole into the enclosure. If the unit is wall
mounted, conduit can be used to carry wiring. Always protect
wiring from sharp edges created by the hole punch.
NOTE
Before placing the system into automatic,
place all K696 load step switches to the OFF
position, and, if required, verify that the
auxiliary jumper is placed correctly.
LKG/er 4-10
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
SECTION V
OPERATION
Purpose And Use of Controls
1, VOLTS 240/480 Select Switch. ‘This switch selects the 240 or
480 volt mode for the Load Bank.
 
POWER ON/OFF Switch. This switch turns on both the control
circuit and the blower circuit. Digital meters will
illuminate. (K696A - Power ON lamp will light.)
3. BLOWER FAIL Lamp. This lamp should momentarily light when
power switch is turned on. This shows the air safety circuit
is working. This lamp’s purpose is to warn the operator of an
air failure or improper cooling of load elements.
 
 
 
4. VOLTS AB/BC/CA Phase Select Switch. The function of each
switch position is as follows: (NOTE: 696 only)
Function
cA Measures Phase C to Phase A voltage
Be Measures Phase B to Phase C voltage
AB Measures Phase A to Phase B voltage
5. AMPS A/B/C Current Phase Select Switch. The function of each
switch position is as follows: (NOTE: 696 only)
Function
A Measures Phase A Current
B Measures Phase B Current
c Measures Phase C Current
6. METER READ/HOLD Switch. This switch holds all readings on the
digital meters at the same time. To update the information on
the meters, place the switch back to the read position.
(NOTE: K696 only)
7. MASTER LOAD ON/OFF Switch. This switch connects power to all
load steps, thus allowing all set load steps to be actuated at
the same time. It is also a master load disconnect.
LKG/cr,
Rev. 7/1/87
Rev. 8/29/90 5-1Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
 
KW LOAD Step Switches. The load in kilowatts is marked above
each actuating switch. A load step may be turned on or off
before or during a test, but will load the unit only when the
MASTER LOAD Switch is ON. A six-position rotary KW LOADS
Switch is also provided to enable loading resolution down to
1 KW.
9. Aux Load Switch. Used to control a load outside of the K696.
(NOTE: K696 only)
Operating Instructions
1. Connect the Load Bank to a 120 volt, 60 Hz source for control
power. Line cord provided.
2. Connect the unit to be tested as described in Section Iv,
INSTALLATION, under Power Requirements. Use all three
terminals on the input terminal board for 3-phase generators,
or connect the power cables to the Phase A and Phase C
terminals for single phase generators. (See Section IV,
INSTALLATION, for details.)
JESS SEES SSS IES IS III
CAUTION
The cooling blower motor is rated at 240/480
volts, 3-phase, 60 Hz, with corresponding
overload heaters for protection. The motor
must be connected to a separate power source
if:
1. Using the unit to test a single phase
unit.
2. Operating at any frequencies other than
50/60 Hz.
3. Operating at any voltage other than
240/480 volts + 10 @ 60 Hz and 240/480
volts @ 50 Hz.
(Refer to Non-Standard Blower Motor Frequency
in Section Iv.)
Urtttrercrceterccetteccccetercrttlttretcrrrrrrrssy
LKG/cr
Rev. 7/1/87 5-23.
4.
Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
Place all switches on the control panel in the OFF position
Place the VOLTS Select Switch to the correct voltage to test
the generator.
JESUS SISOS HHS III ISITE IIE I IIE
CAUTION
DO_NOT operate the Load Bank over the rated
voltage as this will cause catastrophic
failure in the Load Bank.
DQ make sure that the VOLTS Select Switch is
in the proper position before applying load.
EEE OO EEE OEE EEE SOE EERE EE REE EEEEE
Place the POWER Switch to the ON position. Digital meters
will illuminate. Blower will turn on.
Upon energizing the unit, the red BLOWER FAIL lamp will light
momentarily until the air switch detects sufficient cooling
air, at which time it will go out, applying power load
switches. If at any time, there is insufficient cooling air
to the elements, this safety switch will drop out the load
and the red BLOWER FAIL lamp will light.
TESS ESD SS EOI SS ESSE EIU DIG RAE EERE EER
CAUTION
The operation of the blower is vital to the
safe operation of this Load Bank. When the
POWER Switch is turned ON, the BLOWER FAIL
light will come on momentarily until the
blower accelerates up to its operating speed,
at which time the light will go out. If the
air switch prevents the load from being
applied, do not bypass this switch. If the
BLOWER FAILURE light stays on for more than a
few seconds, shut down the Load Bank and do
not operate the unit until the problem is
corrected. (Refer to Section I, SAFETY CON-
SIDERATIONS, of this manual.)
JESUS SEIU IIE SESS ISSO SETI ISIE
LKG/cr 5-3
Rev.
7/1/8710.
1.
12.
Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
With the MASTER LOAD Switch in the OFF position, start the
generator to be tested. Verify that the voltage displayed
by the voltmeter matches the position of the VOLTS Select Switch.
The resistive loading is selected by toggle switches, using
any one or combination of toggle switches to make up a given
load.
By placing the MASTER LOAD Switch to the ON position, the
preselected load will be applied to the power source.
Any KW LOAD switch can be added or removed as required with
the NASTER LOAD Switch closed (ON).
Monitor the unit under test using the digital volts and
current display.
To remove load, move MASTER LOAD Switch to OFF position.
Shutdown: Reverse steps 1 through 11. It is good procedure
to allow the fan blower motor to operate for about 2 minutes
after the load is removed. This will exhaust any accumulated
heat and allow exhaust surfaces to cool.
 
TEESE ISSO SS III IIS ISTO II
WARNING
DO NOT touch the exhaust screen during operation.
The screen will become hot from the exhaust
heat and may cause a serious burn. (Refer to
Section I, SAFETY CONSIDERATIONS, of this manual.)
DO NOT allow objects to enter or block screens.
JESSIE SSSI III III II II III III IIIS
LKG/er 5-4
Rev.
1/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
NOTE
Lower voltages and different frequencies may
be applied to the load circuit of the Load
Bank. Frequency change causes no derating of
the load. The Applied KW with a lower voltage
is computed using the following formula:
KWapplied = KWRated x (Voltage Applied}:
(Voltage Rated)
 
peettetttttttttrtrtrttrtrrttcrrtetterer ttt crrrresy
CAUTION
Never exceed the rated voltage. This will
cause the Load Bank to overheat.
Do not apply DC voltages, because the contactors
do not have arc blowout magnets.
JE SESS EES SHEE IIS SSSI ESS IIEE IS EE
LKG/cr 5-5
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
SECTION VI
K696A AUXILIARY OPERATION
The K696 Load Bank has the capability of using one or two K696A
Load Banks for a total of 500 KW or 750 KW. ‘The K696A, when
interconnected, can be operated from the main K696 control panel.
Installation
ie
Location of Load Bank should meet all conditions set forth
in the INSTALLATION section of this manual.
2. load Connections: (See Figure 6-1, Wiring for K696A Auxiliary
Operation.)
3. Control Power: Each Load Bank requires its own 120V, 60 Hz
control power source. (See the Power Requirements paragraph
of Section IV, INSTALLATION, of this manual.)
4, Blower: Each Load Bank requires 240 or 480 VAC, 3, 60 Hz for
the blower motor.
See the Blower Motor Connections paragraph of Section Iv,
INSTALLATION, of this manual.
5. Control Interface: The K696 can be interconnected to the
K696A as follows: On the K696A, connect TB4 (15)-TB4(20) to
its counterpart on the K696. Wire point to point.
POSSIBLE KW STEPS TOTAL MAX.
MODEL (S) AT_240/480 VOLTAGE KW_CAPACITY
K696 1 KW thru 250 KW 250 KW
K696 PLUS 1 KW thru 250 KW 500 KW
K696A PLUS up to 250 KW (AUX)
K696 PLUS 1 KW thru 250 KW 750 KW
2xK696A. PLUS up to 500 KW (AUX:
Even with this arrangement, the K696A can be used as a
self-contained Load Bank with its own control panel. (See
Section III, K696A DESCRIPTION, of this manual.)
LKG/cr 6-1
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
Operation
The K696A Load Bank operating instructions are almost identical
to that of the K696. If operating a K696A Load Bank independent
of a K696, refer to Section V, OPERATION. If more than one Load
Bank is interconnected, follow the instructions below; then refer
to Section V, OPERATION.
 
Connect the Load Bank to a 120 volt, 60 Hz source for control
power. Line cord provided.
2. Place the VOLTS Select Switch to the correct voltage to test
the generator.
3. Place the POWER Switch to the ON position. Blower motor will
turn ON.
 
Be sure the MASTER LOAD Switch is in the OFF position. Select
desired load. The AUX Switch on the K696 can be used to
apply and remove the K696A load. Refer to Section V.
Option 17
Preset the K696A Load Bank to 250 KW. ‘The incremental steps are
based on a 250 KW auxiliary load.
Operation Using the Remote Control Panel
A Remote Control Panel (OPTION 7, Part Number C16721) allows
remote operation of the load step toggle switches. The switches
are mounted in a small enclosure which can be connected to the
Load Bank with the 90 feet of cable provided. The part number of
the Remote Control Unit is D16983.
JESSIE IOS IIIT SIITI ETII TIIIE
WARNING
DISCONNECT ALL POWER FROM THE Load Bank
BEFORE INSTALLING THIS OPTION.
JAE HE I IS SI E I SSIS IIIS E IIIT I EIIII III
LKG/cr 6-2
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
Installation of this option is accomplished by connecting the
fanning strips at the end of the cable to the terminal blocks
(TB5 and TB6) located on the customer connection panel. Wiring
Diagrams and Schematics have been included at the back of this
manual.
Operation of the Load Bank is the same with the Remote Control
Panel as it is using the toggle switches on the Load Bank Control
Panel.
NOTE
When using the Remote Control Panel, make
sure all load step switches on the Load Bank
Control Panel are OFF. These switches will
add load if turned ON.
Before using the Remote Control Panel switches, set up the Load Bank
Control Panel switches as described in this manual with the
exception of the load step toggle switches. The indicator light
on the Remote Control Panel will illuminate when the MASTER LOAD
switch on the Remote Control Panel is turned ON and the Load Bank
controls are ON and properly set.
LKG/cr 6-3
Rev. 7/1/87Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
 
 
   
    
    
   
 
  
K696A/D16423
LOAD BANK
TB4
15 | 16 | 17] 18}19 | 20
K696/D16133
LOAD BANK
       
    
A
GENERATOR
    
         
   
 
    
as [16 | 17
  
18,
TB4
  
igl20
K696A/D16123,
LOAD BANK
FIGURE 6-1. WIRING FOR K696A AUXILIARY OPERATION
LKG/er 6-4
Rev. 7/1/87‘Aviron Mods! K696IKE96A
{oe Bank
 
SECTION VII
AVTRON MODEL K696/K696A OPTION LIST
These options are available on the Model K696/K696A Load Banks.
Not all options can be installed in the same unit
Part Number
15941,
B16110
B16111
B16112
B16113
B16250
16721,
16722
15583
A14702
B16791,
B16792
B16793
A16560
16667
BMPav
$2888, Rev. 313197
Option
a
2
10
a
12
13
14
Description
Storage cover
LED Digital Watt Meter (S/N 84 and Below]
45-99 Hz LED Digital Frequency Meter
(S/N 84 and Below!
45-450 Hz LCD Digital Frequency Meter
(S/N 84 and Below)
Air Fail Warning Horn
Dual Voltage Control Transformer
Control Unit, Remote (with cable)
(For K696D16133 Load Bank)
Control Unit, Remote (with cable)
(For K696D16158 Load Bank:
Silkscreen for Load Steps Derated per
208 VAC
10 Feet of Load Cables
Lep Digital Watt Meter (S/N 85 to
S/N 742)
45-65 Hz LCD Frequency Meter
(S/N 85 to S/N 742)
45-450 Hz LCD Digital Frequency Meter
(S/N 85 to S/N 742)
Elapsed Time Meter
Single Overhead Lift Point
7-1‘K696/K696A Option List
‘Avon Model KS96/K5964
Loe Bank
 
Part Number
16770
17543
17603
A17604
B19575
18100
18523
A18647
19135
i972
19173
19174
19175
19176
420523
B22436
21083
21230
BMPrkv
028/88, Rev. 25183,
Option
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Description
Weather Resistance Kit (Cannot be used
with option 18)
Auto Load Shed Controller with Current
Transformer (for K696D16133 Load Bank
Lift Support with Two Handles
(Cannot be used with option 16)
Instrument Test Jacks Kit with Shorting
Links
Installation of Fan Reversal Switch
Paint Exterior of Load Bank Ford Blue
Installation of a 380/120V, 50 Hz, 2 KVA
Control Transformer
Installation of Universal Control
Transformer wired for 380/110V,
400/115V, 208/110V, or 415/120V,
50/60 Hz per customer requirements
200/400V Derated Silkscreen
200/400V Derated Silkscreen
190/380V Derated Silkscreen
190/380V Derated Silkscreen
208/415V Derated Silkscreen
208/415V Derated Silkscreen
Installation of 500 VA, 600/120V,
50/60 Hz Control Transformer
Installation of Overtemperature
Protection
Installation of Tie Down Rings
Installation of 500 VA, 220/110Vv,
50/60 Hz Control TransformerK696/K696A Option List ‘Aviron Model K696/K696A
 
‘Load Bank
Part. er = Option Description
A21735 34 10 ft. power cable, 4 conductor,
terminated with 200A Crouse-Hinds
connector (for 480V operation only)
A23382 35 Installation of Option 35 (replaces
original meter with meter P/N A22821 on
Load Banks S/N 743 and above)
23974 36 Installation of option 36
rik 7-3
11783, Rev. 11898Avtron Model K696/K696A
Load Bank
REPLACEMENT PARTS LIST
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
OPTIONS
‘SCHEMATIC MANUFACTURER | AVTRON | OTY/
REFERENCE DESCRIPTION and PART NO. Py | UNIT
OPTION 2: LED Digital watt B16110
Meter (S/N 84 and Below:
ma -Display ais217 | 1
-Bezel RMF Products | 358954 | 1
Model 140-2
MT3 -Watt Transducer Scientific 372513 | 4
Columbus
CTS 10A2
RA -Resistor, 806 Ohm, 1/2 W, 18 123108 | 2
OPTION 3: 45-99 Hz LED B16111
Digital Frequency Meter
(S/N 84 and Below,
ma Meter Non-Linear 337828 | 1
systems
FM-37B
Bezel Assembly RMF Products | 358954 | 1
Model 140-2
73 - Transformer B16025 | 1
+ Transformer Square "D" co. | 370894 | 1
9070-E0-17
.+Kit, Fuseblock Square "D" co. | 324964 | 1
9070-AP-3
-+Fuse, ¥A, 250V Bussmann 324005 | 2
AGC
|
OPTION 4: 45-450 Hz LeD B16112
Digital Frequency Meter
(S/N 84 and Below]
ma -Meter a15225 | 1
:Bezel Assembly RMF Products | 358954 | 1
Model 140-2
13 - Transformer Bie025 | 1
: + Transformer Square "D" co. | 370894 | 1
9070-E0
.+Kit, Fuseblock Square "D" co. | 324964 | 1
9070-AP-3
.+Fuse, ¥A, 250V Bussmann 324005 a
AGC-&,
BMP/kv 7-4
4/28/88, Rev. 11/3/93Avtron Model K696/K696A
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
options Load Bank
SCHEMATIC MANUFACTURER | AVIRON | QTY/
REFERENCE DESCRIPTION and PART NO. eae | UNIT
OPTION 5: Air Fail Warning B16133,
Horn
Audible Warning Device P. R. Mallory | 303006 | 1
H4-1
Code #37942
OPTION 6: Dual Voltage B16250| 1
Control Transformer
w/Schematic
4 - Transformer, 500 VA Acme Elect. 370654 | 2
TA-2-81215
K101 -Relay, Volt Sense Magnecraft 350740 | 1
W236ACK~2
T40 - Transformer Square D 370528 | 1
F440 -Fuse, 0.5 Amp, 250V 324005 | 2
XF440 -Fuseblock Square D 324964 | 1
9070-AP-3
XK101 - Socket, Potter & Brum. | 358215 | 1
27121
100 Switch, P.B. Black Switchcraft 360017 | 1
913
s101 Switch, P.B. Red Switchcraft 360019 | 1
903
K100,K240 | .Relay B14795 | 2
K480 :Relay Bie143 | 1
cBL :Circuit Breaker Asea Brown 310330 | 1
Boveri
$272-K10 w/
S500-MEL
s102 -Switch Cutler Hammer | 360785 | 1
7991K10
TBS -Terminal Board cinch 364054 | 1
6-141
- Insulator cinch 450098 | 1
MS-6-141
FS5 -Fanning strip cinch 365076 | 1
6-161L,
BMP/kv 1-5
4/28/88, Rev. 7/23/96Avtron Model K696/K696A
 
 
 
 
 
 
 
 
 
 
 
 
 
options Load Bank
SCHEMATIC MANUFACTURER | AVIRON | OTY/
REFERENCE DESCRIPTION and PART NO. p/w | UNIT
| OPTION 7: Remote Control unit 16721
| TBS -Terminal Board Kulka 364103 1
| 601-20
BG -Terminal Board Kulka 364063 | 1
601-8
-Control Unit, Remote pi6983 | 1
$10 ++Switch, Rotary 620288 | 1
S81 ++Switch, Toggle Arrow-Hart 360677 | 1
82612
$2-S9 -.Switch, Toggle Westinghouse | 361599 | 8
PB1AAHAB
psi ..Indicator, Light Dialight 329137 | 1
502-3228-0112-
302
XDS1 - «Lamp General Elec. | 333011 | 1
686-125V
TB1 .-Terminal Board Kulka 364063 | 1
601-8
TB2 ..Terminal Board Kulka 364103 | 1
601-20
FS6 -/Fanning strip Cinch 365073 | a
5-161R
FSS +/Fanning strip Cinch 365095 | 2
20-161R
+-Wiring Diagram 16724 | REF
+ +Schematic 16723 | REF
OPTION 8: Remote Control 16722
Unit (K696D16158 only,
-Control Unit, Remote pissaa | 1
si +.Switch, Toggle Arrow-Hart, 360677 | 1.
82612
s2-S19 + .Switch, Toggle Westinghouse | 361599 | 18
PB1AAHAB
psi -.Indicator Light Dialight 329137 | 1
502-3228-0112-
302
XDS1 - «Lamp General Elec. | 333011 | 1
686-125V
TBL .-Terminal Board Cinch 364103 | 1
20-141
FS4 ++Fanning strip Cinch 365095 | 1
20-161R
+ Wiring Diagram c16726 | 2
+ «Schematic 16725 | REF
TB4 :Terminal Board Cinch 364103 | 2
20-141
BMP/kv 1-6
4/28/88, Rev. 11/3/93Avtron Model K696/K696A
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
options Load Bank
‘SCHEMATIC MANUFACTURER | AVIRON | QTY/
REFERENCE DESCRIPTION and PART NO. py | UNIT
OPTION 11: LCD Digital B16792
Wattmeter
-Watt Transducer Scientific 372513 | 1
Columbus
CTS 10A2
Cable Assembly Augat 390849 | 2
7P14-3912-2
-Display A15327 | 2
QPTION 12: LCD Digital B16792
Frequency Meter, 45-65 Hz
«Integrated Circuit U3 Motorola Semi. | 376868 | 1
MC14536BCPDS
-Standoff, .38 LG H. H. Smith aii6s4 | 2
2101
Standoff, .25 LG H. H. Smith 411700 | 2
2100
Cable Assembly Augat, 390849 | 1
7P14~3712-2
-Meter Datel-Intersil | 337762 | 1
DM-LX3
Display #
SD991M400 COFG
OPTION 13: LCD Digital B16793
Frequency Meter, 45-450 Hz
-Integrated Circuit U3 Motorola 376868 | 1
MC14536BCPDS
Cable Assembly Augat, 390847 | 1
7P14-3736-1
-Standoff, .25 LG H. H. Smith 411700 | 1
2100
Connector Datel-Intersil | 314049 | 1
58-2073083
-Meter ais328 | 1
:-Meter, Frequency Datel-Intersil | 337830 | 1
DM-4105,
Display #
SD458M400 COFC|
OPTION 14: Elapsed Time Metei 16560
Meter, Elapsed Time Engler Instmt. | 369222 | 1
200-10N-L7
BMP/kv 1-7
4/28/88,
Rev. 11/3/93Avtron Model K696/K696A
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
options Load Bank
SCHEMATIC MANUFACTURER | AVTRON | OT¥/
REFERENCE DESCRIPTION and PART NO. pyu | UNrr
OPTION 17: Auto Load Shed 17543
Controller
Insulator, Term. Block Cinch Mfg. 450136 | 2
MS-18-140
-Insulator, Term. Block Cinch Mfg. 450092 | 1
MS-6-140
| vais -Terminal Block Cinch Mfg. 364130 | 1
18-140
‘B17 -Terminal Block Kulka 364180 | 2
600-6
| -Schematic/Interconnection B19078 | REF
Diagram
T10 -Transformer, Current Instrument 370390 | 2
Transformers
135-302
AL -Load Shed Controller cisao5 | 2
:-Retainer Relay Rundel-IDEC 467522 | 18
1492-N2
-.Socket, Relay Rundel-IDEC 358215 | 9
SL711
. Relay syrelec 351590 | 2
DIRT-110 V
. Relay Potter & Brum. | 351060 | 9
KUP14A15
.+Fuseblock, 2 Pole Littelfuse 324521 | 2
357002
-+Fuse, 6 A Littelfuse 324086 | 1
314006
-+Fuse, 0.5 A Littelfuse 324005 | 3
312.500
- .Schematic/Interconnection B19078 | REF
Diagram
++Terminal Block Assembly ai7572 | 1
++sMarker Strip Weidmuller 364410 | 2
4687.6 (1-50)
+++Terminal Block Weidmuller 364408 | 30
2796.6
. Programmable Controller ai7s70 | 1
eeI.C. Programmer 680184 | 1
++ .Controller General Elec. | 395011 | 1
1€609SIR100
OPTION 19: Instrument Test 17604
Jacks Kit w/Shorting Links
+Link, Shorting H. H. Smith 410002 | 2
1828
Connector, Fem., Red H. H. Smith 366852 | 3
(Bind’g Post) 257-102
«Connector, Fem., Yel. He H. Smith 366870 | 4
(Bind’g Post) 257-107
BMP/kv 7-8
4/28/88, Rev. 11/3/93Avtron Model K696/K696A
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
options Load Bank
SCHEMATIC MANUFACTURER | AVIRON | gTY/
REFERENCE DESCRIPTION and PART NO. pya | UNIT
~ OPTION 20: Installation of
Fan Reversal Switch
K35,36 -Relay B14795 | 2
$100 :Switch, Toggle, 2 PDT Cutler-Hammer | 360747 | 1
7992K10
OPTION 22: Installation of 18523
380/120 V, 50 Hz, 2 KVA
Control Transformer
v4 . Transformer General Elec. | 370943 | 2
9951B172
Ful -Fuse Bussmann 324106 | 2
‘Tron FNQ
XFLL -Fuseholder Bussmann 32aeaa | 2
4515
B10 .Terminal Board cinch 364033 | 1
2-140
OPTION 23: Installation of 18647
380/115 V, 50 Hz Control
Transformer
120 . Transformer Acme Electric | 370709| 1
TA-1-54524
B20 Terminal Board cinch 364121 | 2
4-140
Fa. -Fuse Bussmann 324101 | 2
KTK-10
F20,22 -Fuse Bussmann 3eaii9 | 2
KTK-6
-Fuseblock Bussmann 32aeis | 2
2809
OPTION 30: 500 VA, 600/120 Vv) 420523,
50/60 Hz Control Transformer
120 . Transformer Acme Elec. 371032 | 2
TA-2-81005
1TB20 .Terminal Board Cinch 364033 | 1
12-140
-Marker Strip Cinch 450042 | 1
MS-12-140
F21,22 «Fuse, 8 A, 600 V Bussmann 32aiso | 2
FNO-8
F19,20 -Fuse, 2.5 A, 600 V Bussmann 324203 | 2
FNQ-R-2%
-Fuseblock Bussmann 324615 | 2
BM6033SQ
BMP/kv 7-9
4/28/88, Rev. 11/3/93Avtron Model K696/K696A
 
 
 
 
 
 
 
 
 
options Load Bank
‘SCHEMATIC manuracturer | AaVERON | gTY/
REFERENCE DESCRIPTION and PART NO. p/w | unrT
OPTION 31: Installation of B22436
Overtemperature Protection
$100 -Thermoswitch Selco agi012| 2
0-300:
 
OPTION 33: Installation of 21230
220/110 V, 50 Hz Control
Transformer
720 - Transformer Hevi Duty 370242| 1
E550
TB20 Terminal Board Cinch 364033 1
2-140
«Marker Strip cinch 450042 | 1
MS-2-140
P46,47 «Fuse, 5A, 600V Bussmann 324475 | 2
FNQ-R-5
F48,49 Fuse, 7.5A, 600V Littelfuse 324493 | 2
KLDR-7.5
.Fuseblock Littelfuse 324615] 2
LM60030-38
OPTION 34: 10 ft. Power 21735
 
Cable, 4 Conductor, with
200A Crouse-Hinds Connector
(480 V operation only)
 
 
 
 
 
 
 
=Connector crouse-Hinds | 313212] 1
AP20468
OPTION 35: Installation of
Option #35
ma sMeter aaze2i| 2
|
BCM/kv 7-10
6/16/92, Rev. 11/2/96Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
SECTION VII (Cont.)
OPTION 17, AUTOMATIC LOAD YSTEM
THEORY OF OPERATION AND ADJUSTMENTS
Option 17 - Theory of Operation
The Load Shed Controller parallels the normal K696 Load Bank manual
controls. Thus the Load Bank manual controls can override the
automatic control. (Reference Section V, OPERATION, of this
instruction manual.)
JHE SUSE SHEE SIS SSSI ISIS III ISS Ie
CAUTION
Always put a short or shunt across the current
transformer when servicing the Load Shed
Controller. Primary current flowing through
an unshunted current transformer will destroy
the transformer with possible harm to
personnel.
JE EEUU ISIS ISOS IIIS III II I IIe
A. Automatic Operation of optional Load Shedder
1. Place all K696 KW LOADS step switches on the
control panel to the OFF position. Place the 1 to
5 KW rotary KW LOADS switch to the 0 position.
2. Start the Load Bank. (Reference the K696 and K696A
OPERATION section.)
3. Place the K696 MASTER LOAD Switch to the oN
position.
4. Close the customer-supplied transfer control
contacts. (Refer to Automatic Load Shed Controller
Description on page 2-3 of this manual.)
LKG/cr
Rev. 7/1/87
Rev. 12/2/93 7-11Avtron Model K696/K696A.
Resistive Load Bank
Part Number D16133/D16423
NOTE
Load step power is derived from the K696 Load
Bank. The Load Bank blower must be energized
to energize the Load Shed Controller.
The Transfer Control contacts should energize if
automatic control is necessary and the generator is
prepared to accept loading.
5. Operation with K696A as auxiliary:
A. Place all K696A KW LOAD step switches to the
ON position.
B, Start the Load Bank.
C. Open the K696A MASTER LOAD Switch.
6. Shutdown. Open the MASTER LOAD Switch, thus
allowing the blower to operate to exhaust any
accumulated heat.
B. Controller Operation of Optional Load Shed system
JESSE SISSIES SSSI III I IIIA
CAUTION
Keep the enclosure access door closed at all
times.
JE EEE SSIES SISO IIS SII IIIS III ITI
To operate the Automatic Load Control system, first
follow the Load Bank operation instructions to start the
Load Bank. Verify that all load step switches are open
(in the OFF position).
Automatic control is engaged by closing the Transfer
Control Contacts. The load step power is energized by
closing the MASTER LOAD Switch. Once engaged, the
controller will automatically maintain a load on the
generator.
LKG/cr
Rev. 7/1/87
Rev. 12/2/93 7-12LKG/or
Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
An example of the operation of the unit is illustrated in
Figure 7-2, The generator load is shown from zero load
and zero time. The curve shows the typical operation of
the load controller during normal operation and during
small overload conditions.
The Load Shed Controller increments load every 0.8 second
and will decrement load every 0.2 second. If the system
decrements four consecutive load steps, the unit will
drop out all additional load steps that are active.
NOTE
The system is protected from a low current
control relay fault. If setpoint 1 fails
(remains closed) and setpoint 2 energizes
(closes), the controller will recognize this
situation as a fault condition. While in this
condition, the controller will completely shut
down in 1.0 second.
The low current relay fault condition can be detected by
opening the NEMA enclosure and observing indicator 27 on
the face of the programmable controller.
If indicator 27 is lit, then the low setpoint has failed
to operate. To reset the system, the 120 V, 60 Hz
control power must be momentarily interrupted.
The programmable controller requires a lithium battery to
maintain the controller operation status. The lithium
battery is behind a snap-in, rectangular cover plate
(located on the left side of the programmable
controller). The operation program is stored within PROM
memory; thus the program cannot be lost, although the
controller requires the lithium battery for internal
operation. Therefore, the lithium battery status
indicator must be routinely checked. The status
indicator (when lit) indicates low battery voltage.
Rev. 7/1/87
Rev. 12/2/93 7-13Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
 
LOAD
 
 
 
 
 
 
 
 
 
avrowrte
OAD SHED
conraoutr Log} oxy
curs69
 
 
 
 
 
FIGURE 7-1.
a8
 
      
 
  
Lop
KW)
oun Loan
fou oo i
TIME (SEC)
FIGURE 7-2.
LKG/or
Rev. 7/1/87
Rev. 6/22/92
Rev: 12/2/93
7-14Avtron Model K696/K696A,
Resistive Load Bank
Part Number D16133/D16423
Option 17 Setpoint Adjustments
Before the setpoint relays can be adjusted, the operator must
determine the maximum load the controller should maintain
(generally 60% to 70% of the total generator KVA). The maximum
value is the high setpoint (K11), and the minimum is the low
setpoint (K10). The difference between the high and low setpoints
is the operation window. To determine the "operation window," two
points must be understood. (See Figure 7-2.)
A. There is a 5% hysteresis of the total current transformer
ratio; thus the operation window must be greater than 5%
of the current transformer ratio.
   
Example: C.T. Tap = 2,000 to 5
Minimum operation window =
2,000 X 0.05 = 100 Amps
B. The minimum operation window must be at least two times
greater than the minimum resolution of the Load Bank.
 
Example: Load Bank minimum resolution
 
10 KW
Minimum system resolution =
2X 10 KW = 20 Kw
Once the high and low setpoints are determined, calculate the line
current.
LINE CURRENT CALCULATION:
y = amp (Li
= Amp (Line)
Volts (,1)
SECONDARY CURRENT CALCULATION:
2) Choose the next higher appropriate current tap on
the current transformer. Calculate the SECONDARY
transformer current.
LKG/cr
Rev. 7/1/87
Rev. 12/2/93 7-15Avtron Model K696/K696A,
Resistive Load Bank
Part Number D16133/D16423
‘The current transformer taps available are defined
below:
REQUIRED
¢.T. RATIO TAP
300:5 x3-K4
500:5 X4-X5
800:5 X3-X5
1000:5 x1-x2
1200:5 X2-x3
1500:5 x2-K4
2000:5 X2-X5
2200:5 x1-x3
2500:5 x1-x4
3000:5 X1-X5
Amps (Secondary) = (AMPS X 5)/C.T. (Tap:
‘The setpoint relays are now ready to be set.
Example 1: Calculate high and low setpoint.
1) Generator Rating: 800 KVA @ 480 VAC, 962 Amps
2) ¢.T. Ratio = 1,000 to 5
3) “Operating Window" = 2 Min. Load steps (20 KW}
4) Setpoint Values (upper approx. 70% of F.L.)
a) High setpoint = 800 x 0.7 = 560 KW
560 KW @ 480 V = 673 Amps
b) Low Setpoint = High Setpoint - operating Window
Low setpoint = 560 - 20
540 KW
  
current at low setpoint = 540 x 577/480
= 649 Amps (Line)
LKG/cr
Rev. 7/1/87
Rev. 12/2/93 7-16Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
Check for a 5% space between the upper and
lower setpoints.
Hysteresis = 1,000 X 0.05
50 Amps (Line)
= High Setpoint current
= Low Setpoint current
  
Operating Window = 673 - 649
= 24 Amps
(The operating window must be larger than
the hysteresis.)
24 < 50
The operating window is less than the 5%
hysteresis. A wider window must be selected.
“operating window" = 60 KW
Recalculate the low setpoint.
Low Setpoint = 560 - 60 = 500 KW
current at Low Setpoint = 500 x 577/480
= 601 Amps (Line)
Check for the 5% space.
 
“Operating window" = 673 - 601
72 Amps
72 > 50
The “operating window" is indeed greater than
the 5% hysteresis. The operating window is
also greater than the 2X minimum resolution
(20 KW).
There are three methods of field adjusting the trip point of the
current sensing relays (K10 and K11) Part Number 351590:
Method 1 - Using generator load power
Method 2 - Using a separate (0-5 Amp) current source without
the current transformer
Method 3 - Rough adjustment
LKG/cr
Rev. 7/1/87
Rev. 12/2/93Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
A. METHOD 1. Using the Actual Generator Load Power
‘This method uses the load current to set the setpoint relays.
1. Apply 120 VAC, 60 Hz control power to terminals TB11(22)
(high line), TB11(23) (neutral), and TB11(24) (ground).
JESSIE EHS SSE SSS ISIS III III
WARNING
There is lethal high voltage present within
the controller enclosure; care must be taken
when proceeding from this point.
 
JESSE SESS SSSI ISS SEI ISTE ISS IIIS
2. Turn the low setpoint sensing relay (K10) adjustment
knob, labeled THRESHOLD, down to 0.01%.
3. Energize the system while on line. Refer to the
OPERATION instructions in Section Vv.
NOTE
Always monitor the generator load with
external metering so as not to overload the
generator.
4, Adjust the generator load until the load equals the
desired lower setpoint. The K696 Load Bank can be used
manually to achieve the desired load current.
NOTE
If the Load Bank is used as part of the load,
it may be necessary to disconnect TB17 (4, 5,
and 6) to disable the controller output power.
LKG/er
Rev. 7/1/87
Rev. 12/2/93 7-18Avtron Model K696/K696A,
Resistive Load Bank
Part Number D16133/D16423
NOTE
On each setpoint relay, there is an LED
indicator. When lit, the relay is energized.
Turn the low setpoint relay (K10) knob, labeled
THRESHOLD, past the trip point (completely clockwise; LED
is off); ‘then turn slowly counterclockwise until the
relay trips on (LED is on).
5. Adjust the generator load until the load equals the
desired high setpoint. Turn the high setpoint relay
(K11) knob, labeled THRESHOLD, past the trip point
(completely clockwise; LED ‘is off); then turn
counterclockwise until the relay trips on (LED is on).
B. METHOD 2. Using a Separate (0-5 Amp) Current Source Without
the Current Transformer
1. Disconnect all sources of power to the Control Unit Part
Number ¢18495.
TEE ODES ISIS ISI ISIS ISI IIIS IAAI
WARNING
When disconnecting the current transformer,
the secondary terminals must be shorted. The
secondary of an unshorted current transformer
can penetrate several thousand volts.
JOISTS IIIT IIIT TAI ITI I II IIA
2. Set relays.
a. Apply 120 VAC, 60 Hz control power to terminals
TB11(22) (high line), 1B11(23) (neutral), and
1B11(24) (ground).
LKG/cr
Rev. 7/1/87
Rev. 12/2/93 7-19Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
JESSE ESS SSSI SISSIES IOC IIIT II II IAI III
WARNING
There is lethal high voltage within the
control enclosure.
JESS SESE SSE ISSO ISIS ISSO III ISI A I
b. Using a controlled current source, apply the lower
setpoint current (from secondary —_ current
calculation) to controller terminals 29 and 30.
©. Turn the relay knob labeled THRESHOLD past the trip
point; then decrease until the relay trips on.
a. Repeat steps b. and c. above for the high setpoint
relay Kil.
From Example 1:
1) Generator Rating: 800 KVA @ 480 VAC, 962 Amps
2) ¢.T. Ratio Selected = 1,000 to 5
 
3) peration Window" = 60 KW
4) Setpoint Values (upper approx. 70% of F.L.)
a) High Setpoint = 673 Amps (Line)
b) Low Setpoint = 601 Amps (Line)
c) Calculate the current transformer
secondary current:
 
Isec. HIGH = 673 X 5/1,000
= 3.37 Amps (Secondary)
Isec. LOW = 601 X 5/1,000
= 3.00 Amps (Secondary)
a) Inject the controlled current as
described above in 2-b, c, and d.
LKG/cr
Rev. 7/1/87
Rev. 12/2/93 7-20c. METHOD 3
 
Avtron Model K696/K696A
Resistive Load Bank
Part Number D16133/D16423
Rough Adjustment.
Use the following formula to calculate the percentage c.T. Tap
chosen to operate the relays:
% Dial Setting = Setpoint/c.T. Tap
From Example 1.
1)
2)
3)
4)
5)
6)
LKG/er
Rev. 7/1/87
Rev. 12/2/93
Generator Rating: 800 KVA @ 480 VAC, 962 Amps
©... Ratio Selected = 1,000 to 5
"operation Window’
 
60 KW
Setpoint Values
 
a. High setpoint = 560 KW
560 KW @ 480 V = 673 Amps
b. Low setpoint = 560 - 60 = 500 KW
500 KW @ 480 V = 601 Amps
Calculate % of full load.
a. High setpoint = 673/1,000 = .67
b. Low setpoint = 601/1,000 = .60
Set relays.
a. Set relay K10 to .67 setting.
b. Set relay K11 to .60 setting.1]
ESD PRECAUTIONARY GUIDELINES
CAUTION
Certain circuit card assemblies and their
components, typically integrated circuits, may
be damaged by seemingly undetectable
electrostatic discharge (ESD). Care must be
exercised during handling/repair of these
items Use electrostatic discharge
precautionary procedures.
The following guidelines are not necessarily all inclusive but
rather serve as reminders for good shop practices for the handling/
repair of ESD sensitive circuit card assemblies and devices.
Store ESD sensitive items in their original containers.
These items are often marked with the symbol shown at the
top of this page.
Put on a grounded wrist strap before handling any ESD
sensitive item.
Clear work area of Styrofoam, plastic, and vinyl items
such as coffee cups.
Handle ESD items by the body, never the open edge
connectors.
 
Never slide ESD sensitive items over any surface.
Transport ESD sensitive items in a static shielding
container to a static-free work station.
If a static-free work station is not available, ground
the transport container before removing or inserting an
ESD item.
Electric tools used during repair should be grounded.
For example, use only anti-static type solder suckers and
grounded tip soldering irons. Discharge non-electric
tools before use
Pack ESD items in static shielding containers before
shipping them to Avtron for repair.
“styrofoam is a registered trademark of Dow Chemical.