Model: HFW-200 T5

This document provides specifications for an HIMOINSA HFW-200 T5 industrial generator set. Key details include: - It is a 200kVA/160kW open skid generator set powered by a FPT_IVECO 6.7L diesel engine. - The generator has a 400/230V, 50Hz output and meets EC and emissions standards. - Additional information provided includes engine specifications, fuel consumption rates, cooling systems, and generator details. - HIMOINSA is an industrial generator manufacturer headquartered in Spain with manufacturing and sales worldwide.

Uploaded by

Zaw Htet Aung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
431 views13 pages

Model: HFW-200 T5

This document provides specifications for an HIMOINSA HFW-200 T5 industrial generator set. Key details include: - It is a 200kVA/160kW open skid generator set powered by a FPT_IVECO 6.7L diesel engine. - The generator has a 400/230V, 50Hz output and meets EC and emissions standards. - Additional information provided includes engine specifications, fuel consumption rates, cooling systems, and generator details. - HIMOINSA is an industrial generator manufacturer headquartered in Spain with manufacturing and sales worldwide.

Uploaded by

Zaw Htet Aung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Model: HFW-200 T5

INDUSTRIAL RANGE
Open Skid
Powered by FPT_IVECO

K6

WATER-COOLED

THREE PHASE

50 HZ

STG.2 (FLEXIBLE SCHEME)

DIESEL

Generating Rates
SERVICE PRP STANDBY
Power kVA 200 220
Power kW 160 176
Rated Speed r.p.m. 1.500
Standard Voltage V 400
Available Voltages V 400/230 - 230/132 - 230 V
Rated at power factor Cos Phi 0,8

HIMOINSA Company with quality certification ISO 9001


HIMOINSA gensets are compliant with EC mark which includes the following directives:

• EN ISO 13857:2008 Machinery safety.


• 2006/95/EC Low voltage.
• 89/336/EEC Electromagnetic compatibility.
• 2000/14/EC Sound Power level. Noise emissions outdoor equipment. (amended by 2005/88/EC)
• 97/68/EC Emissions of gaseous and particulate pollutants. (amended by 2002/88/EC & 2004/26/EC)

Ambient conditions of reference: 1000 mbar, 25ºC, 30% relative humidity. Power according to ISO 3046 normative.
P.R.P. Prime Power - ISO 8528 : prime power is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per year,
between stated maintenance intervals. The permissible average power output during a 24 hours period shall not exceed 80% of the prime power. 10% overload available for
governing purposes only.

Standby Power (ISO 3046 Fuel Stop power): power available for use at variable loads for limited annual time (500h), within the following limits of maximum operating time: 100% load
25h per year – 90% load 200h per year. No overload available. Applicable in case of failure of the main in areas of reliable electrical network.

HIMOINSA HEADQUARTERS:
Fábrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 info@himoinsa.com www.himoinsa.com

Manufacture facilities:
SPAIN • FRANCE • INDIA • CHINA • USA
Subsidiaries:
ITALY | PORTUGAL | POLAND | GERMANY I SINGAPORE | UAE | MEXICO | PANAMÁ I ARGENTINA

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Powered by FPT_IVECO

Engine Specifications 1.500 r.p.m.


ENGINE PRP STANDBY
Rated Output Kw 175 193
Manufacturer FPT_IVECO
Model NEF67 TE 2A
Engine Type Diesel 4 strockes-cycle
Injection Type Direct. Common rail
Aspiration Type Turbocharged and aftercooled
Ciylinders Arrangement 6-L
Bore and Stroke mm 104x132
Displacement L 6,7
Cooling System Liquid (water + 50% Paraflu11)
Engine Specifications ACEA E3 - E5
Compression Ratio 17,5 : 1
Fuel Comsumption Stand By l/h 48
Fuel Comsumption 100% PRP l/h 44
Fuel Comsumption 80 % PRP l/h 35,7
Fuel Comsumption 50 % PRP l/h 25,6
Lube Oil comsumption full load 0,5 % of fuel consumption
Total Oil Capacity L 15
Total Coolant Capacity L 43,5
Governor Type Electrical
Air Filter Type Dry
Inner diameter exhaust pipe mm 70

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Powered by FPT_IVECO

Generator

Generator
Poles Num 4
Winding Conections (standard) Star-serie
Frame Mounting S-3 11"1/2
Insulation Class H class
Enclosure (according IEC-34-5) IP23
Exciter System self-excited, brushless
Voltage Regulator A.V.R. (Electronic)
Steady Voltage Precision ± 1,5%
Bearing Single bearing
Coupling Flexible disc
Coating type Standar (Vacuum impregnation)

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Control Panel Models Powered by FPT_IVECO

CEM7 CEC7 CEA7

FUNCIONALITY PANEL MODEL CONTROLLER MODE


Auto-start M5 CEM7
Automatic Control Panel Without Mains Control AS5 CEM7**
Automatic Control Panel With Mains Control AS5 CEA7
(customer change over contactors)
Automatic Control Panel With Mains Control AS5XCC2 CEM7+CEC7
(Himoinsa change over contactor with display)
Automatic Mains Failure (wall mounted panel) AC5 CEA7

(**) Pre-heating resistance in the Genset and


Battery charger in the control panel included.

Option available: Auto-start control panel


without circuit breaker

General Description

CEM 7 CEC 7 CEA 7


The CEM7 controller unit is The CEC7 controller unit is a net sings CEA7 controller is a supervision
a device able to control de supervision equipment, and control and supply equipment for mains signal and also
operation, monitoring and supplier through generating set. The controller a supervision and electrical supply
protection of a generating set. unit consists of 2 through the genset. This controller is
The controller unit consists of 2 different modules: composed by 2 different modules:
different modules: 1. The VISUALIZATION module 1. VISUALIZATION module
1. The VISUALIZATION module 2. The MEASUREMENTS module 2.MEASUREMENTS module
2. The MEASUREMENTS module VISUALIZATION MODULE VISUALIZATION MODULE
VISUALIZATION MODULE The visualization module provides information The visualization module provides
Provides information about the about the status of the device and, at the same information about the status of the
status of the device and, at the time, allows the user to interact with it. With device
same time, allows the user to this visualization module the user is able to and, at the same time, allows the user
interact with it. It consists on a control, program and configure the functions of to interact with it. With this visualization
backlit display and various LEDs the unit. It consists on a backlight display and module the user is able to control,
for monitoring the status of the various LEDs for monitoring the status of the program
controller and buttons that allow controller and buttons that allow the user to and configure the functions of the unit.
the user to control, program and control, program and configure the functions of MEASUREMENTS MODULE
configure the functions of the unit. the unit. The measurements module controls and
MEASUREMENTS MODULE MEASUREMENTS MODULE monitors the control board. It is located
Controls and monitors the control The measurements module controls and inthe rear part of the panel, in order to
board. It is located in the rear part monitors the control board. It is located in the reduce
of the panel, in order to reduce the rear part of the panel, in order to reduce the the wiring and to avoid electromagnetic
wiring and to avoid electromagnetic wiring and to avoid electromagnetic disturbances. Every signal, sensor and
disturbances. Every signal, sensor disturbances. actuator is connected to this module.
and actuator is connected to this Every signal, sensor and actuator is connected Connection between the measure
module. to this module module
The connexion between the The connection between the measure module and visualization mode is made by
visualization module and the and visualization mode is made by means of a means
measurements module is made CAN BUS (Communication Bus). This produces of a CAN BUS (Communication Bus). This
with a CAN communication bus. This an interconnection produces an interconnection between
feature allows the intercommunion between additional modules which additional
of other modules to the main guarantees the proper working of modules which guarantees the proper
controller with a scalability warranty. the controller. working of the controller.

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Powered by FPT_IVECO

Control & Power Panel


1. CM Control Panel.
2. CP Power Panel.
3. On/Off Switch..
4. Emergency Stop.
5. Main Line Circuit Breaker for overload protection.
6. Main bus /hardwire connection panel with safety
protection.

CE-7 Auto-start multilingual control panel

1. Voltage between each Phase & Neutral 8. Fuel level


2. Voltage between Phases 9. Oil pressure, coolant temperature, oil temperature
3. Current (amps) on each Phase 10. Battery voltage, battery charging alternator voltage
4. Frequency 11. Engine Speed
5. Active, Aparent & Reactive Power 12. Hours running
6. Power Factor 13. Multilingual (Spanish, English, French, Italian, Portuguese,
7. Instant Power (KwH) and Accumulative power) Polish, German, Chinesse, Russian, Swedish, Norwegian)

Engine Alarms Genset Alarms Mains Alarms

1. High coolant temperature. 1. Over-load 1. Maximum Mains Voltage.


2. Low oil pressure. 2. Unbalanced voltage 2. Minimum Mains Voltage.
3. Battery charge alternator 3. Over voltage 3. Maximum Mains Frequency.
4. Start failure. 4. Under voltage 4. Minimum Mains Frequency.

5. Low water level. 5. Over frequency 5. Mains phase sequence failure.


6. Fuel storage. 6. Under frequency 6. Mains power failure.

7. Overspeed. 7. Over load 7. Mains contactor switching failure.


8. Underspeed. 8. Short-circuit

9. Low battery voltage. 9. Inverse Power


10. High coolant temperature by sensor. 10. Asymmetry among phases Programmable Alarms:
There are 5 programmable alarms on
11. Low oil pressure by sensor. 11. Genset contactor Failure
text and action that could be
12. Low fuel level by sensor. associated to any engine alarms and
showed on the auxiliary led 1 and 2
13. Unexpected shutdown.
of the display
14. Stop failure.
15. Low engine temperature.
16. Genset voltage drops.
17. Emergency stop.

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Controllers Features Open Skid
Powered by FPT_IVECO

CEM 7 CEC 7 CEA 7 CEM7 + CEC7


GENERATOR READINGS
Voltage among phases • • • •
Voltage among phases and neutral • • • •
Amperage • • • •
Frequency • • • •
Apparent power (kVA) • • • •
Active power (kW) • • • •
Reactive power (kVAr) • • • •
Power factor • • • •

MAINS READINGS
Voltage among phases x • • •
Voltage among phase and neutral x • • •
Amperage x • • •
Frequency x • • •
Aparent power x x • •
Active power x x • •
Reactive power x x • •
Power factor x x • •

ENGINE READINGS
Coolant temperature • x • •
Oil pressure • x • •
Fuel level (%) • x • •
Battery voltage • x • •
R.P.M. • x • •
Battery charge alternator voltage • x • •

ENGINE PROTECTIONS
High water temperature • x • •
High coolant temperature by sensor • x • •
Low engine temperature by sensor • x • •
Low oil pressure • x • •
Low oil pressure by sensor • x • •
Low coolent level • x • •
Unexpected shutdown • x • •
Fuel storage • x • •
Fuel storage by sensor • x • •
Stop failure • x • •
Battery voltage failure • x • •
Battery charge alternator failure • x • •
Overspeed • x • •
Underspeed • x • •
Start failure • x • •
Emergency Stop • • • •

ALTERNATOR PROTECTIONS
High frequency • • • •
Low frequency • • • •
High voltage • • • •
Low voltage • • • •
Short-circuit • x • •
Asymmetry among phases • • • •
Incorrect phase sequence • • • •
Inverse power • x • •
Overload • x • •
Genset signal droop • • • •

• Standard
x Not included NOTE: All protections are programmable to make “warning” or “stop with
• Optional cooling time” or “without”

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Powered by FPT_IVECO
Controllers Features

CEM 7 CEC 7 CEA 7 CEM7 + CEC7


COUNTERS
Total hour counter • • • •
Partial hour counter • • • •
Kilowatimeter • • • •
Starts valid counters • • • •
Starts failure counters • • • •
Maintenance • • • •

COMUNICATIONS
RS232 • • • •
RS485 • • • •
Modbus IP • • • •
Modbus • • • •
CCLAN • x • •
Software for PC • • • •
Analogic modem • • • •
GSM/GPRS modem • • • •
Remote screen • x • •
Telesignal •(8+4) •(8+4) •(8+4)
J1939 • x • •

FEATURES
Alarms history (10) / (•+100) -10 (10) / (•+100) (10) / (•+100)
External start • • • •
Start inhibition • • • •
Mains failure start •(CEC7) • • •
Start under normative EJP • x • •
Genset contactor activation • x x •
Main & Genset contactor activation x • • •
Fuel transfer control • x • •
Engine temperature control • x • •
Manual override • x • •
Programmable alarms • x • •
Genset start function in test mode • x • •
Programmable outputs • x • •
Multilingual • • • •

SPECIAL FUNCTIONS
Positioning GPS • • •
Synchronization with mains • • •
Mains Synchronism • • •
Second Cero suppression • • •
RAM 7 • • •
Remote screen • • •
Timer • • •

• Standard CEC7: available when the controller CEC7 is incorparted to the installation
x Not included MPS 5.0: available application when the module MPS 5. has been incorporated to the panel.
• Optional Note: AS5 + CC2 configuration, will have all CEM7 funcionality plus CEC7 mains readings.

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Powered by FPT_IVECO
Generating Sets Standard and Optional Features
Engine
· Diesel engine
· 4 strokes-cycle
· Water-cooled
· 12V Electrical system
· Radiator with blowing fan
· water separator decanting filter (no visible level)
· Electronic governor
· Low water level sensor
· Dry air cleaner
· Hot components and radiator guards
· Mobile components guards
Optional : · Sender WT
· Senders OP

Alternator
· Self-excited and Self-regulated
· 4 poles
· AVR governor
· IP23 protection degree
· Insulation H class
· Single drive-shaft
· Flexible disc coupling

Electrical system
· Control and power electric panel, with measurements devices and controller (according to necessity and configuration)
· 4 poles circuit breaker
· Earth leakage protection adjustable (time & sensibility) standard in M5 and AS5 configuration with MCCB
· Battery charger (standard on automatic control panels)
· Pre-heating resistance (standard on automatic control panels) / water jacket heater
· Battery charge alternator with ground connection
· Starting battery/ies installed and connected to the engine (supports included)
· Ground connection electrical installation with connection ready for ground pike (not supplied)
Optional : · Battery disconnector

Open set version


· Emergency stop button
· Oil sump extraction kit
· Steel made chassis
· Antivibration shock absorber
· Chassis with integrated fuel tank
· Fuel level sensor
· High mechanical strenght
· Powder coating
· Drain cap fuel tank
· Steel made residential silencer -15db(A) attenuation
Optional : · Fuel transfer pump
· Steel made residential silencer -35db(A) attenuation.

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Powered by FPT_IVECO

Application Data

Exhaust System
Maximum exhaust temperature 100% Stand By ºC 550
Exhaust Gas Flow 100% Stand By Kg/s 0,262
Maximum allowed back pressure kPa 6
Heat evacuated through exhaut pipe KCal/Kwh 614

Air Inlet System


Intake Air Flow 100% Stand By m3/h 754
Cooling Air Flow 100% Stand By m3/s 3,8
Alternator fan air flow m3/s 0,514

Starting System
Starting Motor Kw 3
Starting Motor CV 4,08
Recommended Battery Capacity Ah 185
Auxiliary Voltage Vcc 12

Fuel System
Fuel Oil Specifications Diesel
Fuel Tank L 250

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Dimensions Powered by FPT_IVECO

Weight and Dimensions


(L) Length mm 2.900
(H) Height mm 1.634
(W) Width mm 900
Shipping Volume seaworthy (standard suplier) m3 4,26
(*) Dry weight Kg 1.695
Fuel tank capacity L. 250
Autonomy Hours 7
(*) (with standard accesories) STANDARD VERSION

Himoinsa reserve the right of modify any characteristic without prior notice.
Weights and dimensions based on products standar and dry / illustrations may include optional equipment.
Technical data here described correspond with the available information at the moment of printing.
Industrial design under patent.

Local Distritutor

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
CONTROL PANEL MODEL Model: HFW-200 T5
INDUSTRIAL RANGE
M5 Open Skid
Digital manual auto-start control panel and thermal magnetic protection (according to voltage and Powered by FPT_IVECO
phase) and differential relay. CEM7

AS5

CC2
Himoinsa External ATS WiITH visualization display. CEC7

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
CONTROL PANEL MODEL Model: HFW-200 T5
INDUSTRIAL RANGE
AS5 + CC2 Open Skid
Automatic with mains control and ATS with visualization. The visualization will be in the genset and Powered by FPT_IVECO
in the ATS box. CEM7+CEC7

AC5
Automatic Mains Failure control panel. Wall mounted Automatic control panel including transfer
switch with thermal magnetic protection (according to voltage and phase). CEA7

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com
Model: HFW-200 T5
INDUSTRIAL RANGE
Open Skid
Powered by FPT_IVECO
PDF Summary
Created : 12/05/2011 14:04
Author : Himoinsa
Number of pages : 13
Report Type: Data Sheet - Industrial range
Generated by: HIMOINSA Engineering Dept.
Page 1. Genset data
Page 2. Engine Specifications
Page 3. Generator Specifications
Page 4. Control Panels models + General Description
Page 5. Control box and power, CE7 Panel, Alarms
Page 6. Controller features (I)
Page 7. Controller features (II)
Page 8. Generator Features & Options
Page 9. Installation Data
Page 10. Dimensions
Page 11. Control Panel Model
Page 12. Control Panel Model
Page 13. PDF Summary (ID454E3439373538)

Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 19 12 17 | Export Fax +34 968 19 04 20 E-mail:info@himoinsa.com | www.himoinsa.com