EA16
Generator Automatic Voltage Regulator
                   Operation Manual
      Universal 16Amp Self Excited Automatic Voltage Regulator
      for use in 220 / 380 / 440 / 480 VAC brushless generators
                      with paralleling compatibility
___________________________________
1                                                                 EA16
1. SPECIFICATION
Sensing Input                                              Analogue Voltage Input
   Voltage       170 ~ 510 VAC, Single Phase 2 wires          Max. ±5VDC. ±10% @ ±3VDC
                 Voltage is DIP Switch selectable
                                                           Over Excitation Protection
   Frequency     50/60 Hz, DIP Switch selectable
                                                              Max Output DCV 95% 20Sec
Power Input
                                                           External Volts Adjustment
   Voltage       60 ~ 300 VAC, Single Phase 2 wires
                                                              ± 5% with 2K ohm 1 watt trimmer
Output
                                                           Unit Power Dissipation
   Voltage       Max. 90 VDC @ 240 VAC input
                                                               Max. 10 watt
   Current       Continuous 16A
                 Intermittent 20A for 10 sec               Under Frequency Protection ( Factory Setting )
   Resistance    Min. 5 ohm                                   50/60 Hz DIP SW selectable
Voltage Regulation                                         Soft Start Ramp Time
    < ± 0.5% ( with 4% engine governing )                      2 sec.
Voltage Build-up                                           Dimensions
    Residual voltage at AVR terminal > 5 VAC                  156mm L * 106mm W * 43mm H
Thermal Drift                                              Weight
   0.03% per °C change in AVR ambient                         450g ± 2%
Load Current Compensation
   1A or 5A Max. 7% @ PF0.5 DIP Switch Selectable
The EA16 AVR is an update of the EA15A AVR. It is similar to the original EA15A in power and voltage
sensing capabilities but with new enhanced paralleling functions; the user can now select the CT inputs either
1 & 5 Amp or use new A1 & A2 analogue signal inputs terminals for use with PLC paralleling controls. It has
new over-voltage excitation safety circuits to prevent damage caused by the accidental detachment of the
sensing wires or irregularities on the generator’s excitation circuits.
                                                                            ATTENTION
                                                       1. AVR can be mounted directly on the engine,
                                                          genset, switchgear, control panel, or any position
                                                          that will not affects operation. For dimension
                                                          reference, please see Figure 1.
                                                       2. All voltage readings are to be taken with an
                                                          average-reading      voltmeter  Meggers     and
                                                          high-potential test equipment must not be used.
                     High Temperature
                                                          Use of such equipment could damage the AVR.
                                                       3. Secure all wiring connection. Do not install AVR at a
                                                          place with high vibrations to prevent loose
                                                          connections. For safety do not touch the heat sink
                                                          while in operation.
                                                       4. Fuse specification : 16A / 250V slow blow type.
                                                       5. Terminal:"Fast-On" terminals 6.35mm (1/4 inch) &
                                        UNIT : mm         With 4mm crimping terminal.
   Figure 1   Outline Drawing
    ___________________________________
    2                                                                                                     EA16
2. CONNECTION TERMINAL                                  2. DROOP:Select switch S1 or S2 pending on the
                                                           secondary current of the CT that you are using.
1. P1, P2 : Power Input Terminals from 60 to               Voltage droop works when the CT and the AVR
   300VAC 50/60Hz -16A rated.                              senses that the output of the generator voltage
                                                           and current waveforms are out of synch and the
2. F+, F−:Maximum Output current 16A.
                                                           AVR droops the output voltage of the generator
3. VS1, VS2:Voltage sensing input terminals, Volts         to correct it.
   selected using DIP SW1 for 220V or 400V.
                                                        3. STAB:If the generator output voltage oscillate,
4. S1, S2:Load Current Compensation (Droop), CT            adjusting the STAB potentiometer will stabilize
   secondary current input selected by using DIP           the output voltage, over adjustment will result in
   SW 1A or 5A (If droop not used leave terminals          high voltage variation when load is applied. Use
   open).                                                  an analog type multimeter when making this
                                                           adjustment. Connect the meter to terminals F+
5. VR1, VR2:External Voltage trim use, 2K Ohms 1
                                                           and F− and slowly adjust STAB potentiometer to
   watt trimmer for ±5% voltage adjustment. Keep
                                                           the point when the pointer stops moving.
   terminals shorted when not in use.
                                                        4. VOLT:Move to set the generator output voltage.
6. A1, A2:Analogue Voltage Input terminals used
                                                           Set DIP Switch 1 to the generator working
   for Power Factor correction from a external PLC-
                                                           voltage.
   The PLC controls provides a DC voltage signal to
   adjust the generator voltage. Max. Adjustment           Set SW1 to OFF (220V) for use from 170 to 260V
   range is ±5VDC. Keep terminals open when not            Set SW1 to ON (400V) for use from 340 to 510V
   used.
                                                           When using and external VR set it to the central
7. DIP Switch 1 to 4                                       position and adjust the AVR VOLT trim to the
   SW1:OFF 220VAC (170 to 260VAC)                          rated voltage.
       ON 400VAC (340 to 510VAC)
                                                                               NOTE
   SW2:OFF CT Secondary Input 1A
                                                          If the external VR is not used, short terminal
       ON CT Secondary Input 5A                           VR1 and VR2.
   SW3:OFF Generator Frequency 60Hz,
       52 ~ 61Hz Adjustment                             5. U/F:Under Frequency protection setting.
          ON Generator Frequency 50Hz,                     At 60Hz U/F factory set at 55Hz
          42 ~ 51Hz Adjustment                             At 50Hz U/F factory set at 45Hz
   SW4:OFF Over excitation protection enabled              To adjust the U/F setting, select the correct
       ON Over excitation protection disabled              system frequency, start engine and adjust engine
                                                           speed to the required U/F frequency (for
8. LED Indicator
                                                           example 55Hz or 45Hz), slow adjust U/F
   U/F:Under Frequency Indicator                           potentiometer until the U/F red LED turn ON,
   O/E:Over Excitation Indicator                           returning the engine speed to normal turn the
                                                           LED off.
3. ADJUSTMENT AND SETTING                                  Function of the Under Frequency trim pot:
1. TRIM works together with a bias voltage applied      ● During start up or shutdown, the engine speed
   to terminals A1 and A2. This signal is supplies by     changes going over or under its rated RPM (Hz).
   an external Power Factor Paralleling PLC. Use          This AVR has an Under Frequency circuit to
   the TRIM potentiometer to adjust the DC voltage        protect the AVR and exciter; you do not need to
   input that controls the level of the generator’s       disconnect the AVR when idling the engine.
   output voltage. When set counter-clockwise the
   control level is zero, and if moved clockwise the    ● If load is higher than the generator’s capacity, the
   maximum control range is 10%. The signal               Under Frequency activates, reducing the
   connected to A1 and A2 can be unipolar (0,+) or        generator’s     voltage     preventing   generator
   bipolar (+,−). Check with the manufacture of the       overload.
   Paralleling control PLC.
   ___________________________________
   3                                                                                                   EA16
6. Over Excitation Protection:                             3. Disconnect the AVR AC power input terminals
                                                              and restart the generator, re-measure the
● This AVR has over Excitation Protection
                                                              residual voltage. If this voltage is greater than
  preventing the generator from working under
                                                              5VAC, reconnect voltage regulator, and voltage
  unusually high excitation. Excitation Protection
                                                              build-up should be successful. If measured less
  includes generator overload, accident removal of
                                                              than 5VAC, repeat steps 5.1 and 5.2.
  sensing wires, and incorrect voltage setting.
  When problems occur, the AVR will gradually              4. If repeating steps 5.1 and 5.2 does not result in
  shutdown the excitation voltage to the minimum              generator voltage build-up, and residual is
  residual voltage. If the O/E LED turn ON and                greater than 5VAC, replace with a new voltage
  stays ON, you need to reset the AVR by shutting             regulator.
  the engine for 10 seconds. When working the
  generator in parallel this protection is not required,                       CAUTION
  the user can disable this function by placing the         Over excite may damage the AVR or the
  jumper from terminals JUMP 1 to 2. To reactivate          exciter.
  protection, place the jumper back to 2 and 3.
4. NOTICE OF USE
1. Installation Notice:(Refer to Figure 2 and 4).
● Only, a trained professional can Installation,
  calibrate and inspections this AVR.
● Install this AVR inside the generator enclosure
  away from moisture, corrosion and from any easy
  to reach area.
2. Generator Operation Notice:
● During operation, the temperature on the surface
  of the AVR can reach higher the 60 °C / 140°F.
● “DANGER” When the AVR is working never
  touch or ground the heat sink on the AVR. The
  AVR heat sink is an electrically live terminal.
  A warning sticker is in place on top of the heat
  sink.
5. FIELD FLASHING
When operating this AVR for the first time, the
polarity of the residual magnetism may be reversed
or too weak to achieve the necessary build-up on
the regulator. If reversing the field connections does
not induce build-up, and the residual voltage is less
than 5 VAC, shut down the Prime-mover and
proceed with the following steps:
1. Stop the generator and disconnect the field wires
   (F+ and F−), apply a DC Voltage using a
   batteries positive terminal to F+ and the negative
   terminal to F−, using a current-limiting resistor of
   3~5 ohms 20 watt.
2. Allow approximately 3 seconds before removing
   the battery.
    ___________________________________
    4                                                                                                   EA16
                                                                                                                          R
                                                  R
                                                          GEN                                                             S
                                                  S
GEN                                                                                                                       T
                                                  T
                                                                                                                          N
                                                  N
                                                               Field
    Field
                                                                             P1 P2 F+ F-    VS1 VS2    K    L
                P1 P2 F+ F-   VS1 VS2    K   L
             EA16A                                                         EA16A
                VR1 VR2                                                      VR1 VR2                  A1        A2
                                        A1   A2
                EXT. VR                                                      EXT. VR
                                                  S
                                                                       Figure 3    220V Connection
GEN
                                                  T
                                                                                                                          R
                                                  N
                                                              GEN                                                         S
                                                                                                                          T
    Field
                                                                                                                          N
                P1 P2 F+ F-   VS1 VS2    K   L                 Field
             EA16A
                VR1 VR2                                                      P1 P2 F+ F-    VS1 VS2    K    L
                                        A1   A2
                                                                           EA16A
                                                                             VR1 VR2                  A1        A2
                EXT. VR
                                                                             EXT. VR
            Figure 2      Paralleling Connection               Figure 4       380 / 480V Connection
                                                      Field
                                                                                                                              R
                                                                    GEN                                                       S
                                                                   Aux.                                                       N
                                                                 Winding
                                                                 60~300v
                                                                                  P1 P2 F+ F-   VS1 VS2     K        L
                                                                            EA16
                                                                                  VR1 VR2                  A1        A2
                                                                                  EXT. VR
                                                                       Figure 5    Auxiliary Winding
___________________________________
5                                                                                                                             EA16
6. TROUBLE SHOOTING
     SYMPTOM                         CAUSE                                   CORRECTION
  Voltage does not      Residual voltage below 5VAC         Reference from 5. Field Flashing
       build up         F+, F− polarity reversed            F+ and F− reverse the connection
                        F+, F−, P1, P2, VS1, VS2 not        Reference from Figure 3 and 4 connection
                        connected
                        Burnt fuse                          Change fuse 16A 250V
                        Ext. Switch (Breaker) not turned on Switch on (ON)
                        Engine RPM under speed              Increase engine speed / frequency above25HZ
   Out voltage low      Poor adjustment is made             Read start procedure carefully and adjust again
                        U/F protection activated            Increase generator speed
                        U/F activated / Incorrect voltage   Read user’s manual to select correct voltage
                        selection
  Out voltage high      Poor adjustment is made             Read start procedure carefully and adjust again
                        Incorrect voltage selection         Read user’s manual to select correct voltage
 Out voltage instable   Poor adjustment is made             Read start procedure carefully and adjust again
                        Field voltage requirement lower     Inquire our distributor to solve
                        the rang of regulator
※ Use only original supplied spare protection fuse for fuse replacement.
※ Please accept our sincere apology if any modification in performance, specification or appearance is
  made without prior notice.