Product: WM 30 Oil, Gas and Dual Fuel Version
Product: WM 30 Oil, Gas and Dual Fuel Version
The Monarch® Trademark has represented performance and quality in burner industry for over 50 years
2
2
Digital.                        Compact.                          Quiet.
Digital combustion management   The streamlined shape of the      Thanks to the newly designed
system ensures economical and   burner casing and the specially   blower unit, the new monarch®
safe burner operation. The      designed air intake make it       burners operate with lower
operation is simple.            possible to achieve high          sound levels.
                                capacity with compact size.
                                                                                                  3
                                                                                                  3
Digital
Digital combustion management                                    Flexible communication possibilities              Advantages of new technology
means optimum combustion results,                                The integrated interface makes it                 Digital combustion management makes
always repeatable operating points                               possible to receive and send all required         burner operation user friendly and safe.
and easy handling.                                               information and control commands from             The most important benefits are:
                                                                 and to the BMS system. If required, a
Weishaupt WM 30 series oil, gas and                              modem can be installed so that remote             • No additional burner controls are
dual fuel burners are equipped with                              monitoring and remote diagnostic                    required since this function is already
electronic fuel air ratio controller and                         function can be activated.                          taken care by the combustion
digital combustion manager as                                                                                        manager. Fuses and eventually
standard. Modern heating applications                            Communication with remote control                   mains dis-connect switch are the
require precise and always repeatable                            system or with BMS system                           only addi-tional items required.
correct mixture of fuel and air. Only this                       The system supports several communi-
way, optimum combustion values can be                            cation protocols for connecting to BMS            • Less installation work means less
guaranteed over extended periods of                              system if data has to be exchanged                  errors: the burners are tested as a
time.                                                            between burners and other heating                   complete unit at the factory.
                                                                 systems with PLC devices.
Simple operation                                                 For control and management functions,             • Commissioning and service work take
The programming of burner function is                            Weishaupt offers ProGraf NT –                       less time. The initial presetting of the
performed via the Display and Control                            a software product that provides real               burner is carried out at the factory. On
unit. The unit is connected to the                               time solution to meet all requirements.             site, only the site specific operating
combustion manager via a BUS system.                                                                                 points have to be adjusted.
    System overview
    Digital Combustion Management                                       W-FM50                       W-FM54           W-FM 100             W-FM 200
    Combustion manager for intermittent operation                          l                              l               l                     l
    Combustion manager for continuous operation                            l2)                                            l                     l
    Flame sensor for intermittent operation                         ION/QRA2/QRB                         QRA2       ION/QRI/QRB          ION/QRI/QRB
    Flame sensor for continuous operation                                 ION                                      ION/QRI/QRA73        ION/QRI/QRA73
    Number of actuator (max.)                                             2 pcs                          3 pcs          4 pcs                 6 pcs
    Actuator with stepping motor                                           l                              l               l                     l
    Compatible with Variable Speed Drive operation                         l                              l                                     l
    O2-Trim (optional)                                                                                                                          l
    Single fuel operation                                                  l                                              l                     l
    Dual fuel operation                                                                                   l               l                     l
    Valve proving system for gas valves                                    l                              l               l                     l
    Integrated self tuning PID-Modulating controller for
                                                                                                                          l                     l
    Temperature or Pressure
    Removable ABE control unit (max. distance)                        65 ft (20 m)                 65 ft (20 m)     325 ft (100 m)        325 ft (100 m)
    Fuel meter interface                                                   l 1)
                                                                                                          l   1)
                                                                                                                                                l
    Combustion efficiency display (w/ optional sensor)                                                                                          l
    eBUS / MOD BUS interface                                               l                              l               l                     l
    PC interface                                                           l                              l               l                     l
    1)                                            2)
         Not in conjunction with VFD operation         Gas operation only in conjunction with flamerod
4
Digital
Digital combustion management                                    Flexible communication possibilities              Advantages of new technology
means optimum combustion results,                                The integrated interface makes it                 Digital combustion management makes
always repeatable operating points                               possible to receive and send all required         burner operation user friendly and safe.
and easy handling.                                               information and control commands from             The most important benefits are:
                                                                 and to the BMS system. If required, a
Weishaupt WM 30 series oil, gas and                              modem can be installed so that remote             • No additional burner controls are
dual fuel burners are equipped with                              monitoring and remote diagnostic                    required since this function is already
electronic fuel air ratio controller and                         function can be activated.                          taken care by the combustion
digital combustion manager as                                                                                        manager. Fuses and eventually
standard. Modern heating applications                            Communication with remote control                   mains dis-connect switch are the
require precise and always repeatable                            system or with BMS system                           only addi-tional items required.
correct mixture of fuel and air. Only this                       The system supports several communi-
way, optimum combustion values can be                            cation protocols for connecting to BMS            • Less installation work means less
guaranteed over extended periods of                              system if data has to be exchanged                  errors: the burners are tested as a
time.                                                            between burners and other heating                   complete unit at the factory.
                                                                 systems with PLC devices.
Simple operation                                                 For control and management functions,             • Commissioning and service work take
The programming of burner function is                            Weishaupt offers ProGraf NT –                       less time. The initial presetting of the
performed via the Display and Control                            a software product that provides real               burner is carried out at the factory. On
unit. The unit is connected to the                               time solution to meet all requirements.             site, only the site specific operating
combustion manager via a BUS system.                                                                                 points have to be adjusted.
    System overview
    Digital Combustion Management                                       W-FM50                       W-FM54           W-FM 100             W-FM 200
    Combustion manager for intermittent operation                          l                              l               l                     l
    Combustion manager for continuous operation                            l2)                                            l                     l
    Flame sensor for intermittent operation                         ION/QRA2/QRB                         QRA2       ION/QRI/QRB          ION/QRI/QRB
    Flame sensor for continuous operation                                 ION                                      ION/QRI/QRA73        ION/QRI/QRA73
    Number of actuator (max.)                                             2 pcs                          3 pcs          4 pcs                 6 pcs
    Actuator with stepping motor                                           l                              l               l                     l
    Compatible with Variable Speed Drive operation                         l                              l                                     l
    O2-Trim (optional)                                                                                                                          l
    Single fuel operation                                                  l                                              l                     l
    Dual fuel operation                                                                                   l               l                     l
    Valve proving system for gas valves                                    l                              l               l                     l
    Integrated self tuning PID-Modulating controller for
                                                                                                                          l                     l
    Temperature or Pressure
    Removable ABE control unit (max. distance)                        65 ft (20 m)                 65 ft (20 m)     325 ft (100 m)        325 ft (100 m)
    Fuel meter interface                                                   l 1)
                                                                                                          l   1)
                                                                                                                                                l
    Combustion efficiency display (w/ optional sensor)                                                                                          l
    eBUS / MOD BUS interface                                               l                              l               l                     l
    PC interface                                                           l                              l               l                     l
    1)                                            2)
         Not in conjunction with VFD operation         Gas operation only in conjunction with flamerod
4
Compact and Quiet
The newly developed Weishaupt              Flexible control capability                   Applications
monarch® WM 30 burner is compact,          WM 30 burners are available with the          Weishaupt WM 30 oil, gas and dual fuel
efficient and quiet. It is the continua-   following control options:                    burners are suitable to be used for the
tion of the 50 years success history       Oil:    3-stage (T)                           following:
of the legendary monarch® series.                  modulating (R)                        • Installation on heat exchanger
                                           Gas: Sliding two stage or                     • Hot water boiler
Advanced blower fan technology                     modulating (ZM)                       • Steam boiler and high pressure hot
Right from early development phase                                                          water boiler
of this new burner generation, future      This allows flexible control possibilities,   • Intermittent and continuous operation
oriented blower fan technology has         which make the burner universally             • Hot air generator
been utilized to achieve a compact,        adaptable to various applications. Both       The combustion air must be free from
streamined design and low operating        versions result in a smooth, trouble free     any aggressive substances (Halogen,
noise.                                     start and reliable operation.                 Chloride, Fluoride, etc) and contamina-
                                                                                         tion (dust, building materials, vapours,
Innovative air damper control              Various versions are available to             etc). For many cases an external air
The newly developed air damper control     meet different emission and                   ducting to the burner is recommended
provides a high degree of linearity over   operation requirements:                       as an option.
the entire operating range.
                                           ZM version                                    Permissible ambient conditions:
Reduced noise level                        Standard version for gas and dual fuel        • Ambient temperature
Right from the earliest developmental      burners.                                        -10 to +40 °C (14 to 104F)
stage of this new burner generation,                                                       -15 to +40 °C (5 to 104F)
particular emphasis was placed on low      LN (LowNOx) version                           • Air humidity: max. 80 % relative
operational noise level.                   Low NOx version of WM gas burners.              humidity, no condensation
                                           The low NOx emission is achieved by           • Suitable only for indoor operation
Quick commissioning, easy                  increased recirculation of combustion         • For installation in unheated rooms
maintenance                                gases.                                          under some circumstances special
All WM 30 burners are shipped out                                                          solutions are required (contact
with an adjustable mixing head. Final      Compliance to certain emission require-         Weishaupt)
adjustment is to be performed via          ment is also dependant on combustion
commissioning program in the               chamber geometry, volume loading and          Any discrepancy from the above
combustion manager.                        design of the combustion system.              described applications requires written
                                                                                         confirmation from Weishaupt Corpora-
Despite its compact design all compo-      3LN multiflam® version                        tion. The maintenance interval could be
nents such as oil nozzles, mixing head,    Low NOx - Oil/ Gas/ Dual fuel burner          shortened according to conditions
air damper and combustion manager          equipped with multiflam mixing head for       where the burners are installed.
are easily accessible. Therefore           the most stringent emission require-
maintenance and service work can be        ments. The low NOx emission is                Approvals
performed easily and quickly. The          achieved by fuel distribution principle.      WM 30 series burners are in
standard hinged flange allows ideal                                                      compliance with most European and
service position for the burner.           Suitable fuels                                North American applicable standards.
                                           Natural gas
Matching to various combustion             Propane
chamber geometries can be performed        Light Oil #2 according to ASTM D396
directly on the burner. The flame and
the ignition process can be observed       Different type of fuel requires written
via the integrated viewing port.           confirmation from Weishaupt.
6
The most important advantages at a
                                                         Burner motor               Digital combustion manager
glance:                                                                             and burner mounted control
• Digital combustion management with                                                and display unit
  electronic fuel air ratio controller
                                                                     Flame              Electronic
• Quiet operation due to air inlet                                monitoring            ignition unit
  equipped with sound absorbing
  material as standard                                                                           Burner housing can
• High performance blower due to                                                                 be hinged open to
  specially designed blower geometry                                                             the left or right
  and air damper control system                                                                                       Mixing assembly
• All WM 30 burners are equipped
  with adjustable flame tube to match
  required firing rate
• Protection class IP 54 as standard
• Easy access to all components, such
  as: mixing head, air damper and
  combustion manager
• Safe operation with sliding two stage/
  modulating operation as standard
  depending on type of modulating
  controller
• Computer aided function test of each
  individual burner in factory
• Excellent price to performance ratio
• Worldwide service network
                                                                                                                               Gas butterfly
                                                                                                                               stepping motor
                                                                                     Sound attenuated
                                                                                     air regulator
                                                                                                                                           7
Overview of operating modes
Burner’s nomenclature
    Operation with oil                                                                                     Operation with gas
ZM-T l l l
ZM-R l l l l
Nomenclature
    WM – GL 30              /   3      –A      /       ZM – T
                                                       ZM – R
                                                         Version
                                                         T = 3-stage
                                                         R = sliding stage or modulating
                                            Revision
                     Size           Capacity
               G = Gas
               L = #2 Oil
      Weishaupt monarch® burner series
8
Burner selection WM 30
Oil burners vers. T and R
         Burner model                                      WM-L30/1-A/ T and /R                                                Burner model                            WM-L30/2-A/ T and /R
         Combustion head                                   WM-L30/1, 222K x 45                                                 Combustion head                         WM-L30/2, 222K x 45
         Capacity MBTU/h                #2 Oil             2,730 – 10,580                                                      Capacity MBTU/h           #2 Oil        3,070 – 13,995
“WC                                                                                                                   “WC
6                                                                                                                     7
5 6
                                                                                                                      5
4
                                                                                                                      4
3
                                                                                                                      3
2
                                                                                                                      2
1
                                                                                                                      1
0
                                                                                                                      0
-1 -1
-2                                                                                                                    -2
     0    1,000    2,000    3,000       4,000      5,000   6,000      7,000      8,000     9,000   10,000   11,000         0     1,500   3,000   4,500     6,000    7,500   9,000   10,500   12,000   13,500   15,000
MBTU/hr MBTU/hr
         Burner model                                      WM-L30/3-A/ R                                              The firing rates are based on an installation altitude
         Combustion head                                   WM-L30/3, 257K x 62
         Capacity MBTU/h                #2 Oil             3,750 – 19,450                                             of 1,640 ft (500 m). A reduction of burner capacity of 1 %
                                                                                                                      for every 325 ft (100 m) should be taken into considera-
                                                                                                                      tion in case of installation altitude above 0 ft.
“WC
8
7
                                                                                                                      Voltages and frequencies:
6
                                                                                                                      The burners are equipped with three phase motor
5                                                                                                                     in 208 - 600 V, 60 Hz as standard. Different voltage and
4                                                                                                                     frequency are available upon request.
3
-1
-2
     0     2,000    4,000     6,000        8,000       10,000      12,000     14,000     16,000    18,000   20,000
                                                    MBTU/hr
#2 oil with flame tube
close
open
                                                                                                                                                                                                                        9
Burner selection WM G30
Gas and dual fuel burners vers. ZM-T and ZM-R
          Burner model
                    WM-G30/1-A ZM                                                                                              Burner model
                                                                                                                                         WM-G30/2-A ZM
                    WM-GL30/1-A ZM-T and ZM-R                                                                                            WM-GL30/2-A ZM-T and ZM-R
    Combustion head WM-G(L)30/1, 222K x 45                                                                               Combustion head WM-G(L)30/2, 222K x 45
    Capacity MBTU/h Natural gas 1,195 – 10,580                                                                           Capacity MBTU/h Natural gas 1,535 – 13,995
                    Propane     1,700 – 10,580                                                                                           Propane     2,050 – 13,995
 “WC                #2 Oil      2,730 – 10,580                                                                        “WC                #2 Oil      3,070 – 13,995
 6                                                                                                                    7
5 6
                                                                                                                      5
 4
                                                                                                                      4
 3
                                                                                                                      3
 2
                                                                                                                      2
 1
                                                                                                                      1
 0
                                                                                                                      0
-1 -1
 -2                                                                                                                   -2
      0    1,000    2,000    3,000     4,000      5,000   6,000      7,000      8,000     9,000   10,000   11,000          0     1,500   3,000   4,500   6,000    7,500   9,000   10,500   12,000   13,500   15,000
MBTU/hr MBTU/hr
          Burner model
                    WM-G30/3-A ZM                                                                                    The firing rates are based on an installation altitude
                    WM-GL30/3-A ZM-R
    Combustion head WM-G(L)30/3, 260K x 62                                                                           of 0 ft (0 m). A reduction of burner capacity of 1 % for
    Capacity MBTU/h Natural gas 2,050 – 19,450                                                                       every 325 ft (100 m) should be taken into consideration
                    Propane     3,070 – 19,450                                                                       in case of installation altitude above 0 ft.
 “WC                #2 Oil      3,750 – 19,450
 8
 7
                                                                                                                     Voltages and frequencies:
 6
                                                                                                                     The burners are equipped with three phase motor
 5                                                                                                                   in 208 - 600 V, 60 Hz as standard. Different voltage and
 4                                                                                                                   frequency are available upon request.
 3
-1
 -2
      0     2,000    4,000     6,000      8,000       10,000      12,000     14,000     16,000    18,000   20,000
                                                  MBTU/hr
 Natural gas with flame tube                            Propane with flame tube                                     #2 Oil with flame tube
 close                                                  close                                                       close
 open                                                   open                                                        open
10
Burner selection WM G30
Gas burners vers. ZM-LN
         Burner model    WM-G30/1-A ZM-LN                                                                                   Burner model    WM-G30/2-A ZM-LN
         Combustion head WM-G30/1 LN, 210 x 60                                                                              Combustion head WM-G30/2 LN, 210 x 60
         Capacity MBTU/h Natural gas 1,195 – 9,550                                                                          Capacity MBTU/h Natural gas 1,365 – 12,970
                         Propane     1,700 – 9,550                                                                                          Propane     1,700 – 12,970
“WC                                                                                                                “WC
6                                                                                                                  7
5 6
                                                                                                                   5
4
                                                                                                                   4
3
                                                                                                                   3
2
                                                                                                                   2
1
                                                                                                                   1
0
                                                                                                                   0
-1 -1
-2                                                                                                                 -2
     0    1,000    2,000    3,000     4,000      5,000   6,000      7,000      8,000     9,000   10,000   11,000        0     1,500   3,000   4,500   6,000     7,500   9,000   10,500   12,000   13,500   15,000
MBTU/hr MBTU/hr
         Burner model    WM-G30/3-A ZM-LN                                                                          The firing rates are based on an installation altitude
         Combustion head WM-G30/3 LN, 250 x 90
         Capacity MBTU/h Natural gas 2,050 – 18,430                                                                of 0 ft (0 m). A reduction of burner capacity of 1 % for
                         Propane     2,730 – 18,430                                                                every 325 ft (100 m) should be taken into consideration
                                                                                                                   in case of installation altitude above 0 ft.
“WC
8
7
                                                                                                                   Voltages and frequencies:
6
                                                                                                                   The burners are equipped with three phase motor
5                                                                                                                  in 208 - 600 V, 60 Hz as standard. Different voltage and
4                                                                                                                  frequency are available upon request.
3
-1
-2
     0     2,000    4,000     6,000      8,000       10,000      12,000     14,000     16,000    18,000   20,000
                                                  MBTU/hr
Natural gas with flame tube                            Propane with flame tube
close                                                  close
open                                                   open
                                                                                                                                                                                                                    11
Standard scope of supply
 Description                                              WM-L30-T   WM-L30-R   WM-G30 ZM/LN   WM-GL30 ZM-T   WM-GL30 ZM-R
Oil hoses l l – l l
Magnetic clutch   – l l
IP 54 protection l l l l l
 l Standard
  Optional
12
Burner selection WM G30
Gas and dual fuel burners vers. ZM-T and ZM-R
          Burner model
                    WM-G30/1-A ZM                                                                                              Burner model
                                                                                                                                         WM-G30/2-A ZM
                    WM-GL30/1-A ZM-T and ZM-R                                                                                            WM-GL30/2-A ZM-T and ZM-R
    Combustion head WM-G(L)30/1, 222K x 45                                                                               Combustion head WM-G(L)30/2, 222K x 45
    Capacity MBTU/h Natural gas 1,195 – 10,580                                                                           Capacity MBTU/h Natural gas 1,535 – 13,995
                    Propane     1,700 – 10,580                                                                                           Propane     2,050 – 13,995
 “WC                #2 Oil      2,730 – 10,580                                                                        “WC                #2 Oil      3,070 – 13,995
 6                                                                                                                    7
5 6
                                                                                                                      5
 4
                                                                                                                      4
 3
                                                                                                                      3
 2
                                                                                                                      2
 1
                                                                                                                      1
 0
                                                                                                                      0
-1 -1
 -2                                                                                                                   -2
      0    1,000    2,000    3,000     4,000      5,000   6,000      7,000      8,000     9,000   10,000   11,000          0     1,500   3,000   4,500   6,000    7,500   9,000   10,500   12,000   13,500   15,000
MBTU/hr MBTU/hr
          Burner model
                    WM-G30/3-A ZM                                                                                    The firing rates are based on an installation altitude
                    WM-GL30/3-A ZM-R
    Combustion head WM-G(L)30/3, 260K x 62                                                                           of 0 ft (0 m). A reduction of burner capacity of 1 % for
    Capacity MBTU/h Natural gas 2,050 – 19,450                                                                       every 325 ft (100 m) should be taken into consideration
                    Propane     3,070 – 19,450                                                                       in case of installation altitude above 0 ft.
 “WC                #2 Oil      3,750 – 19,450
 8
 7
                                                                                                                     Voltages and frequencies:
 6
                                                                                                                     The burners are equipped with three phase motor
 5                                                                                                                   in 208 - 600 V, 60 Hz as standard. Different voltage and
 4                                                                                                                   frequency are available upon request.
 3
-1
 -2
      0     2,000    4,000     6,000      8,000       10,000      12,000     14,000     16,000    18,000   20,000
                                                  MBTU/hr
 Natural gas with flame tube                            Propane with flame tube                                     #2 Oil with flame tube
 close                                                  close                                                       close
 open                                                   open                                                        open
10
Accessories
Gas burners WM-G 30 vers. ZM and ZM-LN
 Accessories for version ZM                                                     WM-G 30/1-A   WM-G 30/2-A   WM-G 30/3-A
 Combustion head extension                                    by 6” (150 mm)    on request    on request    on request
                                                              by 12” (300 mm)   on request    on request    on request
 Solenoid valve for air pressure switch test                                    250 030 21    250 030 21    250 030 21
 continuous run fan or post purge
 Modulating controller KS20 mounted on burner (W-FM50)                          250 033 15    250 033 15    250 033 15
 Adapter for ducted air intake                                                  on request    on request    on request
 W-FM 100 (suitable for cont. operation)                      fitted            250 030 74    250 030 74    250 030 74
 instead of W-FM 50
                                                              loose             250 030 45    250 030 45    250 030 45
 W-FM 200 instead of W-FM 50 with built in                    fitted            250 030 75    250 030 75    250 030 75
 modulating controller and VFD control with
 optional fuel metering
                                                              loose             250 030 48    250 030 48    250 030 48
 Speed control with burner motor mounted                                        on request    on request    –
 VFD (W-FM 50/200 required)
 Speed control with separate VFD                                                on request    on request    on request
 (W-FM 50/200 required)
 Special voltages                                                               on request    on request    on request
14
Accessories
Dual fuel burners WM-GL30 vers. ZM-T and ZM-R
Accessories for version ZM-T                                                                        WM-GL 30/1-A   WM-GL 30/2-A
Combustion head extension                                          by 6” (150 mm)                   250 031 87     250 031 87
                                                                   by 12” (300 mm)                  250 031 88     250 031 88
Solenoid valve for air press. switch test - cont. run fan or post purge                             250 030 21     250 030 21
Adapter for ducted air intake                                                                       on request     on request
W-FM 100 (suitable for cont. operation) inst. W-FM 54              fitted                           250 031 78     250 031 78
with built in modulating controller
                                                                   loose                            on request     on request
W-FM 200 instead of W-FM 54 with built in modulating               fitted                           250 031 77     250 031 77
controller and VFD control with optional fuel metering
                                                                   loose                            on request     on request
Speed control with burner motor mounted                                                             on request     –
VFD (W-FM 54/200 required)
Speed control with separate VFD                                                                     on request     on request
(W-FM 54/200 required)
Oil hoses 50” (1300) mm instead of 40” (1000 mm)                                                    on request     on request
Oil meter VZ20                                                                                      on request     on request
Oil meter VZ020 with remote tansmitter LF                                                           on request     on request
Special voltages                                                                                    on request     on request
Accessories for version ZM-R                                                         WM-GL 30/1-A   WM-GL 30/2-A   WM-GL 30/3-A
Combustion head extension                                          by 6” (150 mm)    250 031 89     250 031 89     250 031 91
                                                                   by 12” (300 mm)   250 031 90     250 031 90     250 031 92
Solenoid valve for air press. switch test - cont. run fan or post purge              250 030 21     250 030 21     250 030 21
Adapter for ducted air intake                                                        on request     on request     on request
W-FM 100 (suitable for cont. operation) inst. W-FM 54              fitted            250 031 78     250 031 78     250 031 78
with built in modulating controller
                                                                   loose             on request     on request     on request
W-FM 200 instead of W-FM 54 with built in modulating               fitted            250 031 77     250 031 77     250 031 77
controller and VFD control with optional fuel metering
                                                                   loose             on request     on request     on request
Speed control with burner motor mounted                                              on request     –              –
VFD (W-FM 54/200 required)
Speed control with separate VFD                                                      on request     on request     on request
(W-FM 54/200 required)
Oil hoses 50” (1300) mm instead of 40” (1000 mm)                                     on request     on request     on request
Special voltages                                                                     on request     on request     on request
                                                                                                                                  15
Technical data
Oil burners
 Oil burners version T                                              WM-L30/1-A             WM-L30/2-A
 Burner motor 1)                         Weishaupt model            WM-D 132/120-2/7K5     WM-D 132/170-2/10K0
 Rated power                             HP (kW)                    10.6 (8.0)             16 (12)
 Full load amps (FLA)                    A (@460 V)                 14                     18
 Motor fuse (VΔ start)                   A                          25 A slow (external)   35 A slow (external)
 Speed (60 Hz)                           rpm                        3,500                  3,520
 Combustion manager                      model                      W-FM 50                W-FM 50
 Air stepping motor                      model                      SQM33                  SQM33
 Weight                                  lbs (kg)                   approx. 330 (150)      approx. 342 (155)
 Oil pump                                model                      J7                     TA2
 maximum flow rate                        GPH (l/h)                  123 (474)              165 (636)
 Oil hoses                               DN/Length                  1/2”/ 40” (13/ 1000)   3/4”/ 40” (20/ 1000)
16
Special equipment
Oil burners WM-L 30 vers. T and R
Special equipment version T                                                                         WM-L30/1-A / T   WM-L30/2-A / T
Combustion head extension                             by 6” (150 mm)                                210 031 03       210 031 03
                                                      by 12” (300 mm)                               210 031 04       210 031 04
Oil hoses 50” (1300 mm) in lieu of 39” (1000 mm)                                                    on request       on request
Connection for air intake duct                                                                      on request       on request
Oil meter                    VZ 020                                                                 210 031 14       210 031 14
                             VZ 020 with remote transmitter LF                                      210 031 13       210 031 13
Solenoid valve for air pressure switch test, continuous run fan or post purge                       250 030 21       250 030 21
Modulating controller KS20 mounted on burner (W-FM50)                                               250 033 15       250 033 15
W-FM 100 (suitable for continuous operation) in lieu of W-FM 50           fitted                    210 030 32       210 030 32
                                                                          loose                     210 030 88       210 030 88
W-FM 200 in lieu of W-FM 50 with built-in modulating
controller, speed control module with
optional fuel metering                                                    fitted                     210 030 10       210 030 10
                                                                          loose                     on request       on request
Flame sensor QRI in lieu of QRB                                                                     210 030 24       210 030 24
Special voltages                                                                                    on request       on request
                                                                                                                                      13
Fuel systems
 Gas train schematic*                                                                                   Oil function schematics
P M
                                                                                                        1    Strainer
                                                                                                        2    Oil solenoid valve in supply line
                                                                                                        3    Oil solenoid valve in return line
                                                                                                        4    Nozzle head with spill type nozzle
                                                                                                        5    Burner mounted oil pump
                                                                                                        6    Oil regulator
                                                                                                        7    Pressure switch in return line
18
Dimensions
                                                                                                                                      l2
                                                                                                                         l4
                                                                                                                                                                         b1
d1
                                                                                                                                             r1
                                                                                                                                                                        b3
                          h4
                                                                                   h1          d2
                                                                                            b6 b4
                         h3
                    h5
                                        I5                                        h2
                   h6
                                                                                                              8 mm                                                           b2
                                                                                                                                                  r2
                                                                                                                                                                                  b5
WM-L30/1-A R                   37.0          24.5    11.9 - 12.8 1.7                   19.1         20.0         10.3         11.9     22.4            17.3    39.1      43.7
                               (941)         (622)   (301 – 326) (43)     –            (484)        (508)        (261)        (301)    (570)           (440)   (992)     (1111)
WM-L30/2-A R                   37.0          24.5    11.9 - 12.8 1.7                   19.2         21.6         10.3         11.9     26.4            17.3    39.1      44.8
                               (941)         (622)   (301 – 326) (43)     –            (488)        (548)        (261)        (301)    (670)           (440)   (992)     (1137)
WM-L30/3-A R                   37.6          25.1    11.2 - 12.8 2.3                   19.4         21.6         10.3         11.9     26.4            17.3    39.1      44.8
                               (956)         (637)   (285 – 325) (58)     –            (494)        (548)        (261)        (301)    (670)           (440)   (992)     (1137)
WM-G30/1-A ZM                  45.1          32.6    13.7 - 14.7 9.8      5.0          15.7         20.0         10.3         11.9     22.4            17.3    39.1      43.7
                               (1146)        (827)   (349 – 374) (248)    (128)        (398)        (508)        (261)        (301)    (570)           (440)   (992)     (1111)
WM-G30/2-A ZM                  45.1          32.6    13.7 - 14.7 9.8      5.0          15.7         21.6         10.3         11.9     24.0            17.3    39.1      44.8
                               (1146)        (827)   (349 – 374) (248)    (128)        (398)        (548)        (261)        (301)    (610)           (440)   (992)     (1137)
WM-G30/3-A ZM                  45.9          33.3    13.7 - 15.3 10.6     5.8          15.7         21.6         10.3         13.7     26.4            17.3    39.1      44.8
                               (1166)        (847)   (349 – 389) (268)    (148)        (398)        (548)        (261)        (348)    (670)           (440)   (992)     (1137)
WM-GL30/1-A ZM-T               45.1          32.6    13.7 - 14.7 9.8      5.0          24.1         20.0         10.3         11.9     22.4            17.3    40.9      43.7
                               (1146)        (827)   (349 – 374) (248)    (128)        (612)        (508)        (261)        (301)    (570)           (440)   (1038)    (1111)
WM-GL30/2-A ZM-T               45.1          32.6    13.7 - 14.7 9.8      5.0          24.0         21.6         10.3         11.9     26.4            17.3    41.3      44.8
                               (1146)        (827)   (349 – 374) (248)    (128)        (610)        (548)        (261)        (301)    (670)           (440)   (1048)    (1137)
WM-GL30/1-A ZM-R               45.1          32.6    13.7 - 14.7 9.8      5.0          24.2         20.0         10.3         11.9     22.4            17.3    41.4      43.7
                               (1146)        (827)   (349 – 374) (248)    (128)        (615)        (508)        (261)        (301)    (570)           (440)   (1052)    (1111)
WM-GL30/2-A ZM-R               45.1          32.6    13.7 - 14.7 9.8      5.0          24.4         21.6         10.3         11.9     26.4            17.3    41.5      44.8
                               (1146)        (827)   (349 – 374) (248)    (128)        (619)        (548)        (261)        (301)    (670)           (440)   (1055)    (1137)
WM-GL30/3-A ZM-R               45.9          33.3    13.7 - 15.3 10.6     5.8          24.6         21.6         10.3         13.7     26.4            17.3    41.7      44.8
                               (1166)        (847)   (349 – 389) (268)    (148)        (625)        (548)        (261)        (348)    (670)           (440)   (1059)    (1137)
WM-G30/1-A ZM-LN               45.1          32.6    15.1 - 15.9 9.8      5.0          15.7         20.0         10.3         11.9     22.4            17.3    39.1      43.7
                               (1146)        (827)   (384 – 404) (248)    (128)        (398)        (508)        (261)        (301)    (570)           (440)   (992)     (1111)
WM-G30/2-A ZM-LN               45.1          32.6    14.7 - 16.3 9.8      5.0          15.7         21.6         10.3         11.9     24.0            17.3    39.1      44.8
                               (1146)        (827)   (374 – 414) (248)    (128)        (398)        (548)        (261)        (301)    (610)           (440)   (992)     (1137)
WM-G30/3-A ZM-LN               45.9          33.3    15.6 - 16.5 10.6     5.8          15.7         21.6         10.3         13.7     26.4            17.3    39.1      44.8
                               (1166)        (847)   (395 – 420) (268)    (148)        (398)        (548)        (261)        (348)    (670)           (440)   (992)     (1137)
All dimensions are approximate. Weishaupt reserves the right to make changes in light of future developments.
                                                                                                                                                                                       19
Dimensions
                  Ducted air intake                                                Boiler plate mounting dimensions                                       Mounting to heat exchanger
                  bottom
                                                                                   WM 30/1 and                        WM 30/3
                                                                                   WM 30/2                                                                                         1 Flange gasket
                                                                                                           d3
                                                                                                                                           d3                           60°
                                                                                                 90°
                                                                                                                                                                                   2 Refractory
     10.4 (265)
                                                                                                                      60°
                  9.6 (243)
                              8.7 (221)
                                                                                                                                                                                   3 Gap
                                          7.5 (190)
                                                                                   45°                                                               1
                                                                                                                30°
                                                       5.1 (130)
                                                      15.0 (381)                                                                                     2
                                                                                                 d4                              d4
                                                      15.9 (403)
                                                      16.7 (425)                                 d5                              d5
 WM-L30/1-A R                                            27.4 10.1     19.9              24.4         28.0      11.4        15.0          12.0 13.0         14.2
                                                         (695) (256)   (505)   –         (621)        (710)     (290)       (380)     M12 (305) (330)       (360)   –
 WM-L30/2-A R                                            27.4 10.1     19.9              24.4         28.3      11.8        15.0          12.0 13.0         14.2
                                                         (695) (256)   (505)   –         (621)        (720)     (300)       (380)     M12 (305) (330)       (360)   –
 WM-L30/3-A R                                            28.7 10.1     19.9              24.4         28.3      14.4        17.7          14.8 15.7         16.5
                                                         (730) (256)   (505)   –         (621)        (720)     (367)       (450)     M12 (375) (400)       (420)   –
 WM-G30/1-A ZM                                           27.4 10.1     19.9    8.3       24.4                   11.4        15.0          12.0 13.0         14.2
                                                         (695) (256)   (505)   (212)     (621)        –         (290)       (380)     M12 (305) (330)       (360)   DN 80
 WM-G30/2-A ZM                                           27.4 10.1     19.9    8.3       24.4                   11.8        15.0          12.0 13.0         14.2
                                                         (695) (256)   (505)   (212)     (621)        –         (300)       (380)     M12 (305) (330)       (360)   DN 80
 WM-G30/3-A ZM                                           28.7 10.1     19.9    9.1       24.4                   14.4        17.7          14.8 15.7         16.5
                                                         (730) (256)   (505)   (232)     (621)        –         (367)       (450)     M12 (375) (400)       (420)   DN 80
 WM-GL30/1-A ZM-T                                        27.4 10.1     19.9    8.3       24.4         26.8      11.4        15.0          12.0 13.0         14.2
                                                         (695) (256)   (505)   (212)     (621)        (680)     (290)       (380)     M12 (305) (330)       (360)   DN 80
 WM-GL30/2-A ZM-T                                        27.4 10.1     19.9    8.3       24.4         26.8      11.8        15.0          12.0 13.0         14.2
                                                         (695) (256)   (505)   (212)     (621)        (680)     (300)       (380)     M12 (305) (330)       (360)   DN 80
 WM-GL30/1-A ZM-R 27.4 10.1                                            19.9    8.3       24.4         28.0      11.4        15.0          12.0 13.0         14.2
                  (695) (256)                                          (505)   (212)     (621)        (710)     (290)       (380)     M12 (305) (330)       (360)   DN 80
 WM-GL30/2-A ZM-R 27.4 10.1                                            19.9    8.3       24.4         28.3      11.8        15.0          12.0 13.0         14.2
                  (695) (256)                                          (505)   (212)     (621)        (720)     (300)       (380)     M12 (305) (330)       (360)   DN 80
 WM-GL30/3-A ZM-R 28.7 10.1                                            19.9    9.1       24.4         28.3      14.4        17.7          14.8 15.7         16.5
                  (730) (256)                                          (505)   (232)     (621)        (720)     (367)       (450)     M12 (375) (400)       (420)   DN 80
 WM-G30/1-A LN                                           27.4 10.1     19.9    8.3       24.4                   11.0        15.0          12.0 13.0         14.2
                                                         (695) (256)   (505)   (212)     (621)        –         (280)       (380)     M12 (305) (330)       (360)   DN 80
 WM-G30/2-A LN                                           27.4 10.1     19.9    8.3       24.4                   11.7        15.0          12.0 13.0         14.2
                                                         (695) (256)   (505)   (212)     (621)        –         (296)       (380)     M12 (305) (330)       (360)   DN 80
 WM-G30/3-A LN                                           28.7 10.1     19.9    9.1       24.4                   14.0        17.7          14.8 15.7         16.5
                                                         (730) (256)   (505)   (232)     (621)        –         (356)       (450)     M12 (375) (400)       (420)   DN 80
 All dimensions are approximate. Weishaupt reserves the right to make changes in light of future developments.
20
Fuel savings, emisions reductions:
Patented multiflam® technology
Weishaupt’s patented multiflam®             The latest monarch® burners have adop-     Combustion values also depend on
technology allows compliance with          ted this technology and brought a com-     combustion chamber geometry. volume-
very stringent emission limits with-       bination of flexibility and low emissions   tric loading and boiler design. Certain
out the need for expensive additio-        into medium capacity range.                conditions such combustion chamber
nal equipment. The emissions re-                                                      dimensions, measurement tolerances,
duction is accomplished by using           Exemplary emission values                  temperature, humidity, etc. must be veri-
innovative mixing assembly and ap-         multiflam® 3LN version burners further      fied in order to guarantee emission le-
plying fuel distribution principles.       reduce NOx emissions below the level       vels.
                                           which can be achieved by standard mi-
Weishaupt multiflam® burners have           xing head. These additional reductions
been proven in the field for more than      are accomplished by using special mi-
10 years. They are especially suited for   xing assembly applying fuel distribution
applications with stringent emission li-   principles.
mits.
                                                                                                                            21
Burner selection Oil burners
WM30 multiflam® burners vers. 3LN
          Burner model                                  WM-L30/1-A R-3LN                                                  Burner model                             WM-L30/2-A R-3LN
          Combustion head                               WM-L30/1-3LN, Ø 215 / Ø 22                                        Combustion head                          WM30/2+3-3LN, Ø 220 / Ø 25
          Capacity MBTU/h                               #2 Oil         1,540 – 11,945                                     Capacity MBTU/h                          #2 Oil         2,050 – 15,360
 “WC                                                                                                             “WC
 10                                                                                                              10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
1 1
0 0
-1 -1
 -2                                                                                                              -2
      0    1,000    2,000   3,000   4,000    5,000   6,000    7,000     8,000   9,000   10,000 11,000   12,000        0    1,500   3,000   4,500   6,000   7,500   9,000   10,500   12,000   13,500   15,000   16,500
MBTU/hr MBTU/hr
          Burner model                                  WM-L30/3-A R-3LN *                                       The firing rates are based on an installation altitude
          Combustion head                               WM30/2+3-3LN, Ø 220 / Ø 25
          Capacity MBTU/h                               #2 Oil         2,050 – 17,065                            of 1,640 ft (500 m). Burner capacity is based on #2 oil
                                                                                                                 with calorific value of 140,000 BTU/Gallon
 “WC
 10
                                                                                                                 Voltages and frequencies:
  9                                                                                                              The burners are equipped with three phase motor
  8                                                                                                              in 208 - 600 V, 60 Hz as standard. Different voltage and
  7
                                                                                                                 frequency are available upon request.
  6
-1
 -2
      0     2,000     4,000     6,000       8,000    10,000    12,000     14,000    16,000    18,000    20,000
                                                    MBTU/hr
 * 57Hz operation with VFD
22
Burner selection gas and dual fuel burners
WM30 multiflam® burners vers. 3LN
         Burner model
                   WM-G30/1-A/ ZM 3LN                                                                                      Burner model
                                                                                                                                     WM-G30/2-A/ ZM 3LN
                   WM-GL30/1-A/ ZM-R 3LN                                                                                             WM-GL30/2-A/ ZM-R 3LN
   Combustion head WM30/1-3LN, Ø 215 / Ø 22                                                                          Combustion head WM30/2+3-3LN, Ø 220 / Ø 25
   Capacity MBTU/h Natural gas 1,365 – 11,945                                                                        Capacity MBTU/h Natural gas 1,710 – 15,355
                   Propane     1,365 – 11,945                                                                                        Propane     1,710 – 15,355
“WC                #2 Oil      1,535 – 11,945                                                                     “WC                #2 Oil      2,050 – 15,355
10                                                                                                                10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
1 1
0 0
-1 -1
-2                                                                                                                -2
     0    1,000    2,000   3,000   4,000    5,000    6,000    7,000     8,000   9,000   10,000 11,000   12,000         0    1,500   3,000   4,500   6,000   7,500   9,000   10,500   12,000   13,500   15,000   16,500
MBTU/hr MBTU/hr
         Burner model
                   WM-G30/3-A/ ZM 3LN *                                                                           The firing rates are based on an installation altitude
                   WM-GL30/3-A/ ZM-R 3LN *
   Combustion head WM30/2+3-3LN, Ø 220 / Ø 25                                                                     of 0 ft (0 m). A reduction of burner capacity of 1 % for
   Capacity MBTU/h Natural gas 1,710 – 17,065                                                                     every 325 ft (100 m) should be taken into consideration
                   Propane     1,710 – 17,065                                                                     in case of installation altitude above 0 ft.
“WC                #2 Oil      2,050 – 17,065
10
 5
                                                                                                                  frequency are available upon request.
 4
-1
-2
     0     2,000     4,000     6,000       8,000     10,000    12,000     14,000    16,000    18,000    20,000
                                                   MBTU/hr
* 57Hz operation with VFD
#2 Oil
                                                                                                                                                                                                                         23
Dimensions
                                                                                                                                      l2
                                                                                                                         l4
                                                                                                                                                                         b1
d1
                                                                                                                                             r1
                                                                                                                                                                        b3
                          h4
                                                                                   h1          d2
                                                                                            b6 b4
                         h3
                    h5
                                        I5                                        h2
                   h6
                                                                                                              8 mm                                                           b2
                                                                                                                                                  r2
                                                                                                                                                                                  b5
WM-L30/1-A R                   37.0          24.5    11.9 - 12.8 1.7                   19.1         20.0         10.3         11.9     22.4            17.3    39.1      43.7
                               (941)         (622)   (301 – 326) (43)     –            (484)        (508)        (261)        (301)    (570)           (440)   (992)     (1111)
WM-L30/2-A R                   37.0          24.5    11.9 - 12.8 1.7                   19.2         21.6         10.3         11.9     26.4            17.3    39.1      44.8
                               (941)         (622)   (301 – 326) (43)     –            (488)        (548)        (261)        (301)    (670)           (440)   (992)     (1137)
WM-L30/3-A R                   37.6          25.1    11.2 - 12.8 2.3                   19.4         21.6         10.3         11.9     26.4            17.3    39.1      44.8
                               (956)         (637)   (285 – 325) (58)     –            (494)        (548)        (261)        (301)    (670)           (440)   (992)     (1137)
WM-G30/1-A ZM                  45.1          32.6    13.7 - 14.7 9.8      5.0          15.7         20.0         10.3         11.9     22.4            17.3    39.1      43.7
                               (1146)        (827)   (349 – 374) (248)    (128)        (398)        (508)        (261)        (301)    (570)           (440)   (992)     (1111)
WM-G30/2-A ZM                  45.1          32.6    13.7 - 14.7 9.8      5.0          15.7         21.6         10.3         11.9     24.0            17.3    39.1      44.8
                               (1146)        (827)   (349 – 374) (248)    (128)        (398)        (548)        (261)        (301)    (610)           (440)   (992)     (1137)
WM-G30/3-A ZM                  45.9          33.3    13.7 - 15.3 10.6     5.8          15.7         21.6         10.3         13.7     26.4            17.3    39.1      44.8
                               (1166)        (847)   (349 – 389) (268)    (148)        (398)        (548)        (261)        (348)    (670)           (440)   (992)     (1137)
WM-GL30/1-A ZM-T               45.1          32.6    13.7 - 14.7 9.8      5.0          24.1         20.0         10.3         11.9     22.4            17.3    40.9      43.7
                               (1146)        (827)   (349 – 374) (248)    (128)        (612)        (508)        (261)        (301)    (570)           (440)   (1038)    (1111)
WM-GL30/2-A ZM-T               45.1          32.6    13.7 - 14.7 9.8      5.0          24.0         21.6         10.3         11.9     26.4            17.3    41.3      44.8
                               (1146)        (827)   (349 – 374) (248)    (128)        (610)        (548)        (261)        (301)    (670)           (440)   (1048)    (1137)
WM-GL30/1-A ZM-R               45.1          32.6    13.7 - 14.7 9.8      5.0          24.2         20.0         10.3         11.9     22.4            17.3    41.4      43.7
                               (1146)        (827)   (349 – 374) (248)    (128)        (615)        (508)        (261)        (301)    (570)           (440)   (1052)    (1111)
WM-GL30/2-A ZM-R               45.1          32.6    13.7 - 14.7 9.8      5.0          24.4         21.6         10.3         11.9     26.4            17.3    41.5      44.8
                               (1146)        (827)   (349 – 374) (248)    (128)        (619)        (548)        (261)        (301)    (670)           (440)   (1055)    (1137)
WM-GL30/3-A ZM-R               45.9          33.3    13.7 - 15.3 10.6     5.8          24.6         21.6         10.3         13.7     26.4            17.3    41.7      44.8
                               (1166)        (847)   (349 – 389) (268)    (148)        (625)        (548)        (261)        (348)    (670)           (440)   (1059)    (1137)
WM-G30/1-A ZM-LN               45.1          32.6    15.1 - 15.9 9.8      5.0          15.7         20.0         10.3         11.9     22.4            17.3    39.1      43.7
                               (1146)        (827)   (384 – 404) (248)    (128)        (398)        (508)        (261)        (301)    (570)           (440)   (992)     (1111)
WM-G30/2-A ZM-LN               45.1          32.6    14.7 - 16.3 9.8      5.0          15.7         21.6         10.3         11.9     24.0            17.3    39.1      44.8
                               (1146)        (827)   (374 – 414) (248)    (128)        (398)        (548)        (261)        (301)    (610)           (440)   (992)     (1137)
WM-G30/3-A ZM-LN               45.9          33.3    15.6 - 16.5 10.6     5.8          15.7         21.6         10.3         13.7     26.4            17.3    39.1      44.8
                               (1166)        (847)   (395 – 420) (268)    (148)        (398)        (548)        (261)        (348)    (670)           (440)   (992)     (1137)
All dimensions are approximate. Weishaupt reserves the right to make changes in light of future developments.
                                                                                                                                                                                       19
Special equipment oil, gas and dual fuel burners
WM-30 multiflam® burners vers. 3LN
Oil burners WM-L30/... -A R-3LN                                                    WM-L30/1       WM-L30/2       WM-L30/3
Combustion head extension                               by 6” (150 mm)             on request     on request     on request
                                                        by 12” (300 mm)            on request     on request     on request
Connection for air intake duct                                                     on request     on request     on request
Solenoid valve for air pressure switch test, continuous run fan or post purge      250 030 21     250 030 21     250 030 21
W-FM 200 in lieu of W-FM 100 with built-in modulating
controller, speed control module with
optional fuel metering                                                    fitted    210 031 61     210 031 61     standard
                                                                          loose    on request     on request     on request
Speed control with burner motor mounted
VFD (W-FM 200 required)                                                            210 031 48     210 031 49     standard
Speed control with separate VFD
(W-FM 200 required)                                                                210 030 98     210 030 98     on request
Special voltages                                                                   on request     on request     on request
Gas and dual fuel burners WM-G(GL)30/... -A (ZM)R-3LN                              WM-GL 30/1-A   WM-GL 30/2-A   WM-GL 30/3-A
Combustion head extension                               by 6” (150 mm)             on request     on request     on request
                                                        by 12” (300 mm)            on request     on request     on request
Solenoid valve for air press. switch test - cont. run fan or post purge            on request     on request     on request
Flange adapter for ducted air intake                                               on request     on request     on request
W-FM 100 loose instead of burner mounted                                           on request     on request     on request
W-FM 200 instead of W-FM 100 with built in modulating
controller and VFD control with optional fuel metering                    fitted   210 031 61     210 031 61     standard
                                                                          loose    on request     on request     on request
Speed control with burner mounted
VFD (W-FM 54/200 required)                                                G        210 030 97     210 031 49     standard
                                                                          GL       on request     on request     on request
Speed control with separate VFD                                                    on request     on request     on request
(W-FM 54/200 required)
Special voltages                                                                   on request     on request     on request
                                                                                                                                25
Technical data
WM 30 multiflam® burner vers. 3LN
 Oil burners WM-L30/.. -A R 3LN                                     L30/1                  L30/2                  L30/3
 Burner motor                                Weishaupt model        WM-D 132/170-2/10K0 WM-D 132/210-2/14K0 WM-D 132/210-2/17K0
 Rated power                                 HP (kW)                16 (12)                20 (15)                22.8 (17)
 Full load amps (FLA)                        A (@460 V)             18                     25                     34
 Motor fuse (VΔ start)                       A                      35 A slow (external)   50 A slow (external)   60 A slow (external)
 Speed (60 Hz)                               rpm                    3,520                  3,520                  3,320 1)
 Combustion manager                          Model                  W-FM 100               W-FM 100               W-FM 200
 Flame sensor                                Type                   QRA73                  QRA73                  QRA73
 Stepping motor Air/Oil                      Model                  SQM 45                 SQM 45                 SQM 45
 Weight                                      lbs (kg)               approx. 445 (202)      approx. 445 (202)      approx. 530 (240)
 Oil pump                                    model                  TA4                    TA5                    Pump unit with motor
                                                                                                                  SMG1629
 maximum flow rate                            GPH (l/h)              327 (1260)             438 (1690)             389 (1500)
 Oil hoses                                   DN/ length             1”/ 50” (25/ 1300)     1”/ 50” (25/ 1300)     1”/ 50” (25/ 1300)
 1)
      max speed 57 Hz with frequency drive
26
Technical data
Gas and dual fuel burners
Gas burners WM-G30/.. -A ZM 3LN                                   G30/1                   G30/2                  G30/3
Burner motor                              Weishaupt model         WM-D 132/170-2/10K0 WM-D 132/210-2/14K0 WM-D 132/210-2/17K0
Rated power                               HP (kW)                 16 (12)                 20 (15)                22.8 (17)
Full load amps (FLA)                      A (@460 V)              18                      25                     34
Motor fuse (VΔ start)                     A                       35 A slow (external)    50 A slow (external)   60 A slow (external)
Speed (60 Hz)                             rpm                     3,520                   3,520                  3,320 1)
Combustion manager                        Model                   W-FM 100                W-FM 100               W-FM 200
Flame sensor                              Type                    Flame rod               Flame rod              Flame rod
Air/Gas stepping motor                    Model                   SQM45                   SQM45                  SQM45
Mixing head stepping motor                Model                   SQM45                   SQM48                  SQM48
Weight                                    lbs (kg)                approx. 406 (184)       approx. 406 (184)      approx. 439 (199)
Dual fuel burners WM-GL30/.. A ZM R 3LN                            WM-GL 30/1-A           WM-GL 30/2-A           WM-GL 30/3-A
Burner motor                              Weishaupt model          WM-D 132/170-2/10K0 WM-D 132/210-2/14K0 WM-D 132/210-2/17K0
Rated power                               HP (kW)                  16 (12)                20 (15)                22.8 (17)
Full load amps (FLA)                      A (@460V)                18                     25                     34
Motor fuse (VΔ start)                     A                        35 A slow (external)   50 A slow (external)   60 A slow (external)
Speed (60 Hz)                             rpm                      3,520                  3,520                  3,320 1)
Combustion manager                        Model                    W-FM 100               W-FM 100               W-FM 200
Flame sensor                              Type                     QRA73                  QRA73                  QRA73
Air/Gas stepping motor                    Model                    SQM45                  SQM45                  SQM45
Mixing head stepping motor                Model                    SQM45                  SQM48                  SQM48
Weight                                    lbs (kg)                 approx. 478 (217)      approx. 478 (217)      approx. 540 (245)
Oil pump                                  model                    TA4                    TA5                    Pump unit with motor
                                                                                                                 SMG1629
maximum flow rate                          GPH (l/h)                327 (1260)             438 (1690)             389 (1500)
Oil hoses                                 DN/ length               1”/ 50” (25/ 1300)     1”/ 50” (25/ 1300)     1”/ 50” (25/ 1300)
                                                                                                                                        27
Dimensions
                                                                                                         l2
 multiflam® version 3LN
                                                                                                    l4
                                                                                                                                           b1
                                                                                                                r1
                                                                                                                                      b3
d2 d 1
 d2 d1
                h4
                                                             h1
                                                                                                               r2
                                                                                            8 mm                                           b2
           h3
                               I5                       h2
I3 I1
                     h5                                                                                              r2
                                                                                                                                      b4
h6
                                                                      1
                                                                                                              Burner flame tube needs to prot-
                                                                                       d1
                                                                                       d2
                                                                                       d6
l3
28
Burner-                           Dimensions in inches (mm)
model                             l1     l2       l3     l4          l5       b1      b2       b3       b4      h1      h2      h3      h4      h5      h6
WM-L30/1-A R-3LN                  45.9   33.3      18.6     10.6     5.8      19.2    21.6     10.3     24.8    28.7    10.1    19.9            28.3    24.4
                                  (1166) (847)     (473)    (268)    (148)    (488)   (548)    (261)    (630)   (730)   (256)   (505)   –       (720)   (621)
WM-L30/2-A R-3LN                  45.9   33.3      18.9     10.6     5.8      19.4    21.6     10.3     26.4    28.7    10.1    19.9            28.3    24.4
                                  (1166) (847)     (480)    (268)    (148)    (494)   (548)    (261)    (670)   (730)   (256)   (505)   –       (720)   (621)
WM-L30/3-A R-3LN                  45.9   33.3      18.9     10.6     5.8      17.6    21.6     10.3     26.4    28.7    10.1    19.9            28.3    24.4
                                  (1166) (847)     (480)    (268)    (148)    (446)   (548)    (261)    (670)   (730)   (256)   (505)   –       (720)   (621)
WM-G30/1-A ZM-3LN                 45.9   33.3      18.6     10.6     5.8      15.7    21.6     10.3     24.8    28.7    10.1    19.9    9.1             24.4
                                  (1166) (847)     (473)    (268)    (148)    (398)   (548)    (261)    (630)   (730)   (256)   (505)   (232)   –       (621)
WM-G30/2-A ZM-3LN                 45.9   33.3      18.9     10.6     5.8      15.7    21.6     10.3     26.4    28.7    10.1    19.9    9.1             24.4
                                  (1166) (847)     (480)    (268)    (148)    (398)   (548)    (261)    (670)   (730)   (256)   (505)   (232)   –       (621)
WM-G30/3-A ZM-3LN                 45.9   33.3      18.9     10.6     5.8      15.7    21.6     10.3     26.4    28.7    10.1    19.9    9.1             24.4
                                  (1166) (847)     (480)    (268)    (148)    (398)   (548)    (261)    (670)   (730)   (256)   (505)   (232)   –       (621)
WM-GL30/1-A ZM-R-3LN              45.9   33.3      18.6     10.6     5.8      24.4    21.6     10.3     24.8    28.7    10.1    19.9    9.1     28.3    24.4
                                  (1166) (847)     (473)    (268)    (148)    (619)   (548)    (261)    (630)   (730)   (256)   (505)   (232)   (720)   (621)
WM-GL30/2-A ZM-R-3LN              45.9   33.3      18.9     10.6     5.8      24.6    21.6     10.3     26.4    28.7    10.1    19.9    9.1     28.3    24.4
                                  (1166) (847)     (480)    (268)    (148)    (625)   (548)    (261)    (670)   (730)   (256)   (505)   (232)   (720)   (621)
WM-GL30/3-A ZM-R-3LN              45.9   33.3      18.9     10.6     5.8      17.6    21.6     10.3     26.4    28.7    10.1    19.9    9.1     28.3    24.4
                                  (1166) (847)     (480)    (268)    (148)    (446)   (548)    (261)    (670)   (730)   (256)   (505)   (232)   (720)   (621)
All dimensions are approximate. Weishaupt reserves the right to make changes in light of future developments.
                                                                                                                                                                29
Burner selection gas and dual fuel burners
WM30 multiflam® burners vers. 3LN
         Burner model
                   WM-G30/1-A/ ZM 3LN                                                                                      Burner model
                                                                                                                                     WM-G30/2-A/ ZM 3LN
                   WM-GL30/1-A/ ZM-R 3LN                                                                                             WM-GL30/2-A/ ZM-R 3LN
   Combustion head WM30/1-3LN, Ø 215 / Ø 22                                                                          Combustion head WM30/2+3-3LN, Ø 220 / Ø 25
   Capacity MBTU/h Natural gas 1,365 – 11,945                                                                        Capacity MBTU/h Natural gas 1,710 – 15,355
                   Propane     1,365 – 11,945                                                                                        Propane     1,710 – 15,355
“WC                #2 Oil      1,535 – 11,945                                                                     “WC                #2 Oil      2,050 – 15,355
10                                                                                                                10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
1 1
0 0
-1 -1
-2                                                                                                                -2
     0    1,000    2,000   3,000   4,000    5,000    6,000    7,000     8,000   9,000   10,000 11,000   12,000         0    1,500   3,000   4,500   6,000   7,500   9,000   10,500   12,000   13,500   15,000   16,500
MBTU/hr MBTU/hr
         Burner model
                   WM-G30/3-A/ ZM 3LN *                                                                           The firing rates are based on an installation altitude
                   WM-GL30/3-A/ ZM-R 3LN *
   Combustion head WM30/2+3-3LN, Ø 220 / Ø 25                                                                     of 0 ft (0 m). A reduction of burner capacity of 1 % for
   Capacity MBTU/h Natural gas 1,710 – 17,065                                                                     every 325 ft (100 m) should be taken into consideration
                   Propane     1,710 – 17,065                                                                     in case of installation altitude above 0 ft.
“WC                #2 Oil      2,050 – 17,065
10
 5
                                                                                                                  frequency are available upon request.
 4
-1
-2
     0     2,000     4,000     6,000       8,000     10,000    12,000     14,000    16,000    18,000    20,000
                                                   MBTU/hr
* 57Hz operation with VFD
#2 Oil
                                                                                                                                                                                                                         23
That is not a Facade. Weishaupt has been one of the leading
company in heating and combustion industry since years
with headquarter in Schwendi and branches all over the
world. That is Reliability.
                    Weishaupt is              Trustworthy, quality,
                    Reliability.              good customer service,
                    The family business       innovation and experi-
                    in Schwendi was           ence are values on
                    established by Max        which the Pioneer Max
                    Weishaupt in 1932.        Weishaupt established
                    Represented in 55         his company. All this
                    countries by branch of-   combined in a word is
                    fices and subsidiaries    reliability.
                    Weishaupt is interna-
                    tional leader in the      Therefore stands
                    areas of combustion       Weishaupt today.
                    technology and heating
                    applications.
                                                                                       Weishaupt Corporation
                                                                                       6280 Danville Road
                                                                                       Mississauga, ON L5T 2H7, Canada
                                                                                       Ph: (905) 564 0946
                                                                                       Fax: (905) 564 0949
                                                                                       www.weishaupt-corp.com