Ee89 2
Ee89 2
ENGINEERING SPECIFICATION
                               EE SPEC : 89/2
Summary
This document specifies requirements for design, installation and commissioning of fixed
earthing systems at major substations. It is intended for use as part of Invitations to Tender or
for schemes involving Competition in Connections or for connections where the customer
site will be designed to accommodate WPD >33kV intake equipment. It does not replace
ST:TP21B which is for internal WPD use and contains guidance on the application of the
above requirements.
1.1          This document specifies requirements for design, installation and commissioning
             of fixed earthing systems at major substations.
2.0 SCOPE
2.1          This document is intended for use as part of Invitations to Tender or for schemes
             involving Competition in Connections or for connections where the customer site
             will be designed to accommodate WPD >33kV intake equipment. It does not
             replace ST:TP21B which is for internal WPD use and, whilst meeting the
             requirements set out in this document, provides additional guidance on the
             application of these requirements.
3.2 Standards
3.3          Whilst the IEC base document is listed for information, the prime document
             which shall take priority is the British Standard enacting the European Standard
             (EN) or European Harmonisation Document (HD).
EARTH IMPEDANCE                     The impedance between the earthing system and remote
                                    reference earth.
EARTH POTENTIAL                     The difference in potential which may exist between a point
                                    on the ground and remote reference earth.
EARTH RESISTANCE                    The resistance of the earth between the earth electrode and
                                    remote reference earth.
EARTHING CONDUCTOR                  Conductor which connects plant and equipment to the earth
                                    electrode.
HOT SITE                            A substation where the rise of earth potential exceeds the
                                    appropriate CCITT level. The CCITT level is 430V RMS
                                    unless the power circuits contributing to the earth fault
                                    currents are high reliability type, having an operating voltage
                                    of 33kV or greater and controlled by switchgear with main
                                    protection that will clear both a line or busbar earth fault
                                    current within 500ms and generally within 200ms. In this
                                    latter case the CCITT level is 650V RMS.
HOT ZONE                            The area over which the rise of earth potential may exceed
                                    the appropriate CCITT level.
STEP VOLTAGE                        The part of the earth potential rise due to an earth fault which
                                    can be picked up by a person with a step-width of 1m,
                                    assuming that the current is flowing via the human body from
                                    foot to foot.
6.1.2        The risk of electric shock shall be controlled by use of voltage limits derived from
             the C1 current-time curve of IEC 60479-1.
6.1.3        The short-time current rating of earthing system components that may carry fault
             current shall be consistent with the specified rating of the plant (e.g. as specified in
             the Invitation to Tender) and current division. Back-up protection operation shall
             be assumed with an operating time of 3s.
6.1.4        The thermal rating of earth electrode shall be in excess of the current-time curve
             defined by protective devices.
6.1.5        Earthing system components that are not required to carry earth fault current
             (intentional or otherwise) shall be sized according to mechanical and corrosion
             performance considerations.
6.1.6        Lifetime ownership cost considerations shall include purchase cost, corrosion
             performance and theft deterrence.
6.2.1        Earthing systems shall be installed such that the design requirements are met. The
             method of installation shall:
             a)     Employ safe systems of work, controlling the risk of electric shock and
                    applying WPD’s Distribution Safety Rules
             b)     Avoid damage to/from other works (e.g. drains, cables etc)
             c)     Maximise the lifetime by suitable measures where hostile soil conditions
                    exist.
7.0 DESIGN
7.1.1        Perform soil resistivity measurements at two representative locations near the
             substation using the Wenner test method and appropriate probe spacings (i.e. 1m,
             1.5m, 2m, 3m, 4.5m, 6m, 9m, 13.5m, 27m, 36m and 54m).
7.1.2        Analyse the soil resistivity data, taking account of available geotechnical data,
             using CDEGS RESAP software (full, unrestricted version) and determine a
             representative multi-layer soil model.
7.2.1        The substation earthing system layout shall be based upon the following but
             modified as necessary to meet the fundamental requirements:
7.2.2        Special arrangements are required for substations containing G.I.S switchgear due
             primarily to high-frequency switching transients. Special arrangements are also
             required for substations containing air-cored reactors due to the possibility of
             induced currents from strong localised magnetic fields.
7.3.1        The resistance, RES, of the substation mesh earth electrode arrangement in the soil
             model shall be determined. This shall be performed using CDEGS MALT/MALZ
             software, whichever is more appropriate. NB MALZ is necessary for large
             electrode systems (e.g. wind farms).
7.4.1        The chain impedance of overhead towers and impedance of external horizontal
             electrode shall be determined using ER S34 or equivalent. The substation earth
             impedance, ZE, shall be determined from the sum of the parallel impedances.
7.5.1        The total time to clear each relevant earth fault on the WPD system for use in
             touch and step voltage assessment shall be provided by WPD.
7.6.1        The current flowing into ZE, IE, shall be determined from the total fault current, IF,
             by allowing for current returning via other (non-ZE) paths:
7.6.3        The earth potential rise (EPR), UE, = IE x ZE = IES x RES, shall be determined for
             the internal and external fault conditions.
7.7.1        EATS 41-24 defines touch and step voltage limits by fault clearance time. The
             appropriate limits shall be determined for the internal and external fault conditions
             assuming correct protection operation.
7.8.1        The earth electrode layout shall be analysed in the soil model using CDEGS
             MALT/MALZ software, whichever is more appropriate. The worst-case touch
             and step voltages across the substation, internal and external to the compound
             fence, including nearby buildings, shall be determined.
7.8.2        Compliance with the touch and step limits shall be checked, taking account of any
             effective high resistivity ground surface covering (i.e. aggregate, tarmacadam etc).
             For a ground surface covering to be considered effective it shall meet the
             requirements of Table F1 in Appendix F. The electrode layout shall be adjusted
             as necessary to achieve touch and step voltage compliance taking account of all
             the fundamental design requirements.
7.8.3        Reducing the depth of the earth electrode reduces touch potential and increases
             step potential. A minimum depth of 0.5m applies to conductors included in RES to
             minimise variation should surface soil freeze.
7.9.1        The detailed design shall include connection of the following to the substation
             earth electrode mesh via two independent routes:
7.9.2        The design shall include connection of the following to the substation earth
             electrode:
7.9.3        Note, where frame-leakage busbar protection is present, the bonding shall not
             circumvent the associated current transformers.
7.9.4        Above ground exposed conductive parts that can attain different potentials and
             would present a hand-to-hand touch hazard shall be either:
7.9.6        Stance earth mats shall be provided to control touch potential for metalwork
             which is not fully integral with the main equipment:
7.9.7        The earth mat design shall ensure control of touch potential for all operator
             positions.
7.9.8        The earth mat shall be connected direct to the handle with a spur connection to the
             substation earth mesh electrode below ground level.
7.9.9 See below for cable sheath earthing and for fence and gate requirements.
7.10.1       Only Approved Materials shall be used to construct the formal substation earthing
             system. These are given in Appendix A by standard and role. Other materials
             may be offered for consideration for approval.
7.10.2 Aluminium shall not be used below ground level or within 150mm of it.
7.11.1 Appropriate size for each part of the earthing system depends on function:
             a)     Earthing conductor that may carry fault current to the earth electrode
             b)     Bonding conductor that is not reasonably likely to carry fault current
             c)     Earth electrode.
7.12.1       Earthing conductor that may carry fault current intentionally (e.g. connection to
             transformer neutral or phase-earth fault thrower) or following insulation
             breakdown or other failure (e.g. fallen conductor) shall have a short-time current
             rating consistent with Clause 6.1.3. For switchgear the requirements for earthing
             of the enclosure set out in BS EN 60298, clause 5.3.1 shall also be met, subject to
             the minimum conductor size requirements in 7.12.8 below.
7.12.2       Where, through switching the System Earth, connection can be made solid rather
             than through a neutral earthing device, earthing conductor ratings shall take
             account of this possible operational arrangement.
7.12.3       For 'critical' connections that are duplicated (e.g. connections to transformer
             neutrals etc) each connection shall be fully rated.
7.12.5       Consideration shall be given to faults fed from one system voltage into that of
             another system voltage (e.g. 132kV conductor dropping onto 33kV equipment if
             physically possible).
7.12.6       For simplicity, selected standard sizes are given by substation type in Table 1
             below. Note that these assume all joints are welded or brazed and shall be
             checked against the requirements above.
7.12.8       Where the required short-time current rating implies a cross-sectional area less
             than 70mm2 copper-equivalent (ce), a minimum of 70mm2 ce shall apply. The
             minimum permissible thickness of copper and aluminium strip shall be 3mm and
             4mm, respectively. For stranded copper conductor the minimum strand diameter
             shall be 3mm.
7.12.9       Fence earthing conductor, connecting the fence to its earth electrode, shall be a
             minimum of 70mm2 ce.
7.13.1       To minimise conductor theft, it is preferred that, where suitable, the steel support
             structure is utilized as a conductor, replacing copper/aluminium earthing
             conductor for part of the earthing conductor path. See Standard Substation
             Construction drawing numbers XP1062 and XP1063. The steel support structure
             shall not be used to replace copper/aluminium earthing conductor for earth
             connections to earth switches or fault throwers and nor for connections to surge
             arresters or capacitor voltage transformers.
7.14.1       Bonding conductor that is not reasonably likely to carry fault current shall be a
             minimum of 50mm2 ce (e.g. inter-gatepost bond, hand-rail bond, metal lamp-post
             or security post bond. However, for bonds which may be subject to movement
             (i.e. gate-gatepost bonds and metal trench cover bonds) a minimum of 35mm2 ce
             shall apply. The minimum permissible thickness of copper and aluminium strip
             shall be 3mm and 4mm, respectively. For stranded copper conductor the minimum
             strand diameter shall be 3mm.
7.15.1       Each section of the interconnected earth mesh shall have a short-time current
             rating:
7.15.2       Spur connections shall be fully rated where they connect to above ground earthing
             conductor. In other cases, the spur connections shall be rated according to the
             distribution of fault current.
7.15.3       In addition to the above, earth electrode shall be a minimum of 70mm2 ce and,
             where applicable, the minimum permissible thickness of copper strip shall be
             3mm. For stranded copper conductor the minimum strand diameter shall be 3mm.
7.15.5       To avoid excessive temperature rise at the surface of the earth electrode it is
             necessary to provide sufficient surface area in contact with the soil. The total
             surface area of the buried bare earth electrode system shall be determined. The
             adequacy of this value shall be checked using the formula in EA TS 41-24
             assuming a three second fault. Appendix D gives the formula.
7.16.1.1     Three-core power cables shall have their sheaths and armouring earthed at each
             end. Depending on the earth fault current that can flow in the cable sheaths it
             may be necessary to interconnect the ends with separate earth electrode.
7.16.1.3     Care is required with the routing of sheath earthing with respect to current
             transformers to avoid protection maloperation by through fault current or
             capacitive current.
7.16.2 Multicore Sheath, Pilot Cable Sheath and Gas/Oil Pressure Alarm Earthing
7.16.2.1     Multicore cable sheaths entirely within the substation shall generally be earthed at
             each end by connection to the substation earthing system. If it is necessary to
             single-point earth multicore cable sheaths, precautions shall be taken to control
             induced touch voltage to not exceed 50V.
7.16.2.2     Pilot cable sheaths and gas/oil pressure alarms from remote external cables require
             special consideration and each installation shall be individually assessed.
7.16.3.2     To control hand-to-hand touch hazards between exposed conductive parts that can
             attain different potentials, two mutually exclusive arrangements for the substation
             compound fence are permitted:
7.16.3.3     Consideration shall be given to the touch voltage on the fence. Where necessary,
             a perimeter potential grading electrode shall be provided.
7.16.3.4     Gates in substation compound fences shall be connected together via their
             gateposts.
7.16.3.5     Metal fences which abut the substation compound fence shall be effectively
             separated either by:
             a)     2m physical separation, or
             b)     Effective shrouding/insulation.
7.16.4.1     Care is required with the positioning of overhead line stay wires relative to the
             substation compound fence and substation earthing system. The following
             arrangements are permitted:
7.16.4.2     Note that failure to insulate the stay from the pole steelwork may cause the steel
             stay to corrode at an accelerated rate.
7.16.4.3     Overhead line stays shall not be installed such that they compromise the
             independent earthing of a fence from a substation earthing system.
7.16.5.1     The earthing associated with surge arrestors and capacitor voltage transformers
             shall provide effective high-frequency and power-frequency earthing.
7.16.5.2     Where the two functions (i.e. high-frequency earthing and power-frequency
             earthing) are nominally performed by separate conductors care shall be taken to
             ensure that the power-frequency current flowing in the ‘high-frequency’ path does
             not exceed its power-frequency rating.
7.16.5.5.1 Minimise impedance and, in particular, inductance of the above ground earthing
           conductor:
             a)     Ensure there are no ‘sharp bends’. Where practicable use a minimum bend
                    radius of 20cm.
             b)     Avoid ‘loops’ where possible. If loops cannot be avoided (e.g. bund walls
                    for transformer surge arrestors), avoid loop length more than eight times the
                    width of the loop open end (as flashover is possible). Minimise loop length
                    relative to the width of the open end.
7.16.5.6.1 Minimise the high-frequency impedance of buried earth electrode at the point(s)
           where surge current would enter:
             b)     Increase mesh ‘density’ in the horizontal plane to further fill the effective
                    volume, up to a radius of 20-50m. Spacing between parallel mesh electrodes
                    of the mesh shall be on an ‘exponential’ basis with highest mesh density
                    closest to the rod (e.g. spacings between parallel electrodes of 0.6m, 1.6m,
                    4.4m within a 12m mesh square).
c) Integrate the above into the substation power frequency earthing system.
7.16.6.2     Note that if protection signalling through the capacitor voltage transformer is
             employed then care is required as carrier equipment may be relatively remote.
             Specialist advice shall be sought.
             a)         Drawing showing earthing design and including electrode layout, depth and
                        materials, including sizes.
             b)         Design report
             c)         CDEGS input files in electronic format on CDROM
7.17.3       Post-installation earth test(s) shall be performed to verify the design has been
             achieved. Interpretation shall be via CDEGS, MALT/MALZ software, whichever
             is more appropriate. Where the measurements indicate the design objectives have
             not been met then remedial action shall be taken.
8.1 Safety
8.1.1        To minimise the risk of electric shock it is necessary to control the hazards
             presented by:
8.1.2        Safe working methods shall be used. In addition to the normal requirements for
             safe working, appropriate control measures may include:
8.2.1        Damage to power cables and multicore cables due to high voltage transients or
             thermal effects of earth fault current on/in earth electrode shall be prevented by
             adequate separation. In the absence of other information, it shall be assumed that
             150mm separation meets this requirement.
8.2.2        Where separation is not practical, suitable protection shall be applied. To achieve
             this a suitable covering shall be applied. The length of covering shall be
             minimised and shall be such that it does not compromise the earthing design.
8.3 Joints
8.3.3        Precautions shall be taken to prevent corrosion (e.g. bimetallic (dissimilar metals)
             and chemical).
8.4.1        Earth electrode shall not be installed direct into highly corrosive soil. Where
             necessary, non-corrosive soil or other suitable products shall be imported to
             achieve this requirement - refer to Tables E1 and E2 in Appendix E. In
             particularly hostile soil, other measures may be required. Soils which shall be
             considered potentially hostile are given in Table E3 of Appendix E.
8.4.2        Soil around earth electrode shall be free of stones for a radius of 150mm and
             firmly compacted.
8.5.1        To prevent theft of the earth electrode by pulling it out of the ground sections of
             the electrode may be encased in Marconite concrete or low sulphur concrete.
8.5.2        Earthing conductor theft can be discouraged by suitable fixing to structures and
             use of security-coded paint where required. For security fixing to concrete,
             stainless steel anchors (i.e. Alcomet FNA II or approved equivalent) shall be used,
             generally spaced at 300mm centres. For security fixing to steel support structures,
             M12 x 40 stainless steel countersunk screw, M12 stainless steel round flat washer
             and M12 stainless steel shear nut shall be used, generally spaced at 300mm
             centres; holes shall be 14mm diameter, countersunk on rear face; measures shall
             be taken to prevent corrosion where tape is fixed along its length to structural
             steelwork – see Standard Substation Construction drawing numbers XP1062 and
             XP1063.
8.6.1        To reduce possible body current, high resistivity material shall be applied to the
             surface in major substations where touch hazards may arise (e.g. open terminal
             compound, around control building with earthed external metalwork etc).
             Suitable materials and required thickness are given in Appendix F.
8.8.1        The addition of metalwork (e.g. lamp-posts, noise enclosures etc) may cause the
             design to be compromised such that unsafe touch voltages could arise. Examples
             include:
8.8.2        Options for controlling the touch voltages include locating the metalwork such
             that it is a minimum of 1m within the earth 'mesh'. This will not normally cause
             an unsafe touch hazard unless the design did not control the touch voltage in the
             particular area concerned.
8.8.3 Where the equipment is to be sited beyond the earth 'mesh', options include:
             a)     Ensuring there are no metallic parts exposed (e.g. plastic lighting column).
                    If it has a power supply ensure this is derived from the substation LV AC
                    supply using insulated sheath cable.
             b)     Extending the earth mesh to enclose the metalwork with 1m separation
                    around the perimeter. If this compromises an intentional 2m separation with
                    the compound fence move the fence or use insulated panels.
8.9.1        To prevent double-end earthed multicore cable sheath damage due to passage of
             earth fault current, earth electrode shall be connected between each end. If
             possible, the route of the multicore cable shall be made longer than that of the
             earth electrode connection.
8.10 Cables and Earth Electrode Passing Under Independently Earthed Fencing
8.10.1       Cables with uninsulated sheaths which pass under independently earthed
             compound fencing shall be insulated 2m either side to limit the fence potential
             rise.
8.11.1       Measures shall be applied at hot sites to telecommunication circuits and private
             pilots to protect equipment, personnel and telecommunication customers. These
             communication circuits shall be electrically isolated from the substation earthing
             system. They shall be terminated on appropriate isolating links and isolation
             equipment. For telecommunication circuits (e.g. BT) the telecommunication
             operator's requirements shall apply.
8.11.3       To maintain isolation, the communication cable on the substation side of the
             isolation equipment shall not run across or with the incoming communication
             cable.
8.11.4       Hot site status and associated hot zone shall be determined together with
             mitigation requirements.
8.12.1 New water service pipes into hot substations shall be non-metallic.
8.12.2       Metallic water service pipes shall be fitted with insulating insert(s) to prevent
             transfer of earth potential rise externally to other customers. The insert(s) shall
             provide a minimum 2m effective separation from the substation earthing system.
8.13 Records
             a)     Earth electrode layout with depths, material, sizes, connectivity and rod
                    position/depth, joint types
             b)     Earthing and bonding conductor layout, material, sizes, connectivity and
                    joint types
             c)     Method of fence/gate earthing and connectivity with substation earthing
                    system
             d)     Special measures (e.g. imported soil, anti-theft measures, insulation under
                    fences, insulating inserts in water services and isolation equipment)
             e)     Details of plant crossing under fences
             f)     Connectivity with towers and earthed poles
             g)     Connectivity with power cable sheaths
             h)     Stay positions
             i)     PVC/PVC insulation
             j)     External earth electrode.
8.13.2       A record of the post-installation earth test (required by clause 7.17.3) and its
             interpretation shall be provided.
9.0 COMMISSIONING
         a) Soil resistivity tests using approved earth tester. See 7.1.1 & 7.1.2.
         b) Joint resistance test using approved micro-ohmmeter of each joint in the earthing
            system.
The short-time current rating formula applicable to earthing conductors given in IEC 60724
is:
NB The ratings above assume brazed or welded joints. For bolted or crimped joints the de-
   rating multiplication factor shall apply as given in Table C3.
NB      The ratings above assume brazed or welded joints. For bolted or crimped joints the
        de-rating multiplication factor shall apply as given in Table C3.
The method of jointing may limit the rating. The permissible final temperature is reduced for
bolted or crimped joints to 250oC. Table C3 gives the de-rating multiplication factor.
NB: No de-rating should be applied to bolted joints onto substantial metalwork (e.g. HV
steelwork etc).
Table E1 - Non-corrosive soils suitable for import around copper earth electrode
Note that gravelly soils may need to be sieved to remove large particles and ensure good
contact with earth electrode.
Material
Bentonite
Marconite concrete
Low sulphur concrete
Table E2 –
Non-corrosive proprietary material suitable for import around copper earth electrode
Table E3 lists materials which may cause accelerated corrosion of earth electrode.
Geotechnical tests can be performed which may help quantify the problem. Difficulty may,
however, be encountered in interpreting the results.
The acidity or alkalinity of the soil can be determined using the standard test method given in
BS 1377-3. This determines the ‘pH’ of samples. Values less than 6 and greater than 10 are
considered hostile to copper.
BS 1377 also defines how the ‘redox potential’ of a soil sample can be determined. This
provides a means of assessing whether a soil is conducive to the activity of sulphate-reducing
bacteria, which cause corrosion of metals.
Unusually low soil resistivity (e.g. <10 ohm metres) may also be indicative of corrosive soil.
This is best measured using the Wenner four-probe test.
Table F1 –
Approved materials and required specification for substation surface covering
Note 1 Particles shall be hard, durable, inert and free from deleterious material (e.g. metallic
compositions).
SUPERSEDED DOCUMENTATION
This document supersedes EE SPEC : 89/1 dated November 2007 which should now be
withdrawn.
APPENDIX H
ASSOCIATED DOCUMENTATION
See section 3
APPENDIX I
IMPEMENTATION
Immediate
APPENDIX J
IMPACT
APPENDIX K
KEY WORDS
Competition in Connections, earth electrode, earthing, earthing system, hot site, hot zone,
tender, invitation to tender