This Electrician's Guide, published by the Institution of Electrical Engineers, aims to assist electricians in performing installation work according to the IEE Regulations without extensive calculations. The guide emphasizes the importance of understanding the regulations for those electricians who work independently and may not have design support. Additionally, it highlights the historical context of supply voltage levels in the UK and the transition towards standardized European voltage levels.

Uploaded by

lebanonxtra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views301 pages

IEE Regulation

This Electrician's Guide, published by the Institution of Electrical Engineers, aims to assist electricians in performing installation work according to the IEE Regulations without extensive calculations. The guide emphasizes the importance of understanding the regulations for those electricians who work independently and may not have design support. Additionally, it highlights the historical context of supply voltage levels in the UK and the transition towards standardized European voltage levels.

Uploaded by

lebanonxtra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 301

Contents----------------------

1 - The IEE Regulations, BS 7671, and 5 - Earthing Cont'd


this Guide 5.7 - Earthed concentric wiring
1.1 - The need for this Electricians Guide 5.7.1 What is earthed concentric wiring
1.2 - The IEE Regulations 5.7.2 Requirements for earthed concentric
1.2.1 International basis wiring
1.2.2 The Sixteenth Edition 5.8 - Other protection methods
1.2.3 Plan of the Sixteenth Edition 5.8.1 Class II equipment
5.8.2 Non-conducting location
2 - Installation requirements and 5.8.3 Earth-free bonding
characteristics 5.8.4 Electrical separation
2.1 - Introduction 5.9 - Residual current devices(RCDs)
2.2 - Safety requirements 5.9.1 Why we need residual current devices
2.2.1 Scope of the Regulations 5.9.2 Principle of residual current devices
2.2.2 Legal status of the 5.9.3 Regulations for residual current
Regulations devices
2.2.3 New inventions and methods 5.9.4 Fault-voltage operated circuit
2.2.4 Safety Requirements breakers
2.2.5 Supplies for safety services 5.10 - Combined functional and protective earthing
2.3 - Definitions
2.4 - Assessment of general 6 - Circuits
characteristics 6.1 - Basic requirements for circuits
2.4.1 Introduction 6.2 - Maximum demand and diversity
2.4.2 Purposes, supplies and -6.2.1 Maximum demand
structure 6.2.2 Diversity
2.4.3 External influences 6.2.3 Applied diversity
2.4.4 Compatibility 6.3 - BS1363 socket outlet circuits
2.4.5 Maintainability 6.3.1 The fused plug
2.5 - Low voltage generating sets 6.3.2 The ring final circuit
2.6 - Standards 6.3.3 The radial circuit
2.7 - Undervoltage 6.4 - Industrial socket outlet circuits
6.4.1 Introduction
3 - Installation control and protection 6.4.2 BS 196 socket outlet circuits
3.1 - Introduction 6.4.3 BS EN 60309-1 (BS 43453) socket
3.2 - Switching outlet circuits
3.2.1 Switch positions 6.5 - Other circuits
3.2.2 Emergency switching 6.5.1 Lighting circuits
3.2.3 Switching for mechanical 6.5.2 Cooker circuits
maintenance 6.5.3 Off-peak appliance circuits
3.2.4 Functional switching 6.6 - Circuit segregation
3.3 - Isolation 6.6.1 Segregating circuits
3.3.1 Isolator definition -6.6.2 Electro-magnetic compatibility(EMC)
3.3.2 Isolator situation 6.6.3 Lift and hoist shaft circuits
3.3.3 Isolator positions
3.3.4 Semiconductor isolators 7 - Special Installations
3.3.5 Isolator identification 7.1 - Introduction
3.4 - Electric shock protection 7.2 - Bath tubs and shower basins
3.4.1 The nature of electric shock 7.2.1 Introduction
3.4.2 Resistance of the shock path 7.2.2 Bath and shower room requirements
3.4.3 Contact with live conductors 7.3 - Swimming pools
3.4.4 Protection from contact 7.3.1 Introduction
3.4.5 Direct contact protection 7.3.2 Special requirements for swimming
3.4.6 Indirect contact protection pools
3.4.7 Protection for users of 7.4 - Sauna rooms
equipment outdoors 7.4.1 Introduction
3.5 - High temperature protection 7.4.2 Special requirements for saunas
3.5.1 Introduction 7.5 - Installations on construction sites
3.5.2 Fire protection 7.5.1 Introduction
3.5.3 Protection from burns 7.5.2 Special regulations for construction
3.6 - Overcurrent protection sites
3.6.1Introduction 7.6 - Agricultural and horticultural installations
3.6.2 Overload 7.6.1 Introduction
3.6.3 Fuses 7.6.2 Agricultural installations
3.6.4 Circuit breakers 7.6.3 Electric fence controllers
3.6.5 Protecting conductors 7.6.4 Horticultural installations
3.7 - Protection from faults 7.7 - Restrictive conductive locations
3.7.1 Introduction 7.7.1 Introduction
3.7.2 Prospective short-circuit (PSC) 7.7.2 Special requirements
3.7.3 Operating time 7.8 - Earthing for combined functional and
3.7.4 Conductors of reduced protective purposes
current-carrying capacity 7.8.1 Introduction
3.7.5 Back-up protection 7.8.2 Special regulations for equipment with
3.7.6 Insulation monitoring high earth currents
3.8 - Short circuit and overload protection 7.9 - Caravan, motor caravan and caravan park
3.8.1 Combined protection installations
3.8.2 Current limited by supply 7.9.1 Introduction
characteristic 7.9.2 Caravan installations
3.8.3 Protection omitted 7.9.3 Caravan park installations
3.8.4 Protection of conductors in 7.10 - Highway power supplies and street
parallel furniture
3.8.5 Absence of protection 7.10.1 Introduction
3.8.6 Discrimination 7.10.2 Highway and street furniture
regulations
4 - Cables, conduits and trunking 7.11 - Heating appliances and installations
4.1- Introduction -7.11.1 Introduction
4.1.1Cable insulation materials 7.11.2 Electrode boilers and water heaters
4.2 - Cables 7.11.3 Instantaneous water heaters
4.2.1 Non-flexible low voltage 7.11.4 Surface, floor, soil and road warming
cables installations
4.2.2 Cables for overhead lines 7.12 - Discharge lighting
4.2.3 Flexible low voltage cables 7.12.1 Low voltage discharge lighting
and cords 7.12.2 High voltage discharge lighting
4.2.4 Cables carrying alternating 7.13 - Underground and overhead wiring
currents 7.13.1 Overhead wiring types
4.2.5 Corrosion 7.13.2 Maximum span lengths and
4.3 - Cable choice minimum heights
4.3.1 Cable types 7.13.3 Underground wiring
4.3.2 Current carrying capacity of 7.14 - Outdoor installations and garden building
conductors 7.14.1 Temporary garden buildings
4.3.3 Methods of cable installation 7.14.2 Garden installations
4.3.4 Ambient temperature 7.15 - Installation of machines and transformers
correction factors 7.15.1 Rotating machines
4.3.5 Cable grouping correction 7.15.2 Transformers
factors 7.16 - Reduced voltage systems
4.3.6 Thermal insulation correction 7.16.1 Types of reduced voltage
factors 7.16.2 Separated extra-low voltage(SELV)
4.3.7 When a number of correction 7.16.3 Functional extra-low voltage(FELV)
factors applies 7.16.4 Reduced voltage
4.3.8 Protection by semi-enclosed 7.17 - Marinas
(rewirable) fuses 7.17.1 Introduction
4.3.9 Cable rating calculation 7.17.2 The marina electrical installation
4.3.10 Special formulas for grouping 7.18 - Medical locations
factor calculation 7.18.1 Introduction
4.3.11 Cable volt drop 7.18.2 Recommendations for medical
4.3.12 Harmonic currents and locations
neutral conductors 7.19 - Exhibitions, shows and stands
4.3.13 Low smoke-emitting cables 7.19.1 Introduction
4.3.14 The effects of animals, plants 7.19.2 Recommendations for exhibitions,
& insects etc.
4.4 - Cable supports, joints and
terminations 8 - Inspection and testing
-- 4.4.1 Cable supports and protection 8.1 - Introduction
4.4.2 Cable bends 8.1.1 The tester
4.4.3 Joints and terminations 8.1.2 Why do we need inspection and
4.5 - Cable Enclosures testing
4.5.1 Plastic and metal conduits 8.1.3 Information needed by the tester
4.5.2 Ducting and trunking 8.2 - Inspection
4.5.3 Cable capacity 8.2.1 Notices and other identification
4.6 - Conductor and cable identification 8.2.2 Inspection
4.6.1 Conduits 8.2.3 Periodic Inspection
4.6.2 Identification of fixed wiring 8.3 - Testing sequence
conductors 8.3.1 Why is correct sequence important
4.6.3 Colours for flexible cables and 8.3.2 Correct testing sequence
cords 8.4 - Continuity tests
8.4.1 Protective conductor continuity
5 - Earthing 8.4.2 Ring final circuit continuity
5.1 - The earthing principle 8.4.3 Correct polarity
5.1.1 What is earthing 8.4.4 Measurement of R1+R2
5.1.2 The advantage of earthing 8.5 - Insulation tests
5.1.3 The disadvantages of earthing 8.5.1 Testing insulation resistance
5.2 - Earthing systems 8.5.2 Testing of non-conducting floors and
5.2.1 System classification walls
5.2.2 TT Systems 8.5.3 Tests of barriers and enclosures
5.2.3 TN-S System 8.5.4 Tests for electrical separation of
5.2.4 TN-C-S system circuits
5.2.5 TN-C system 8.6 - Earth testing
5.2.6 IT System 8.6.1 Testing earth electrodes
5.3 - Earth-fault loop impedance 8.6.2 Measuring earth-fault loop impedance
5.3.1 Principle and prospective short-circuit current
5.3.2 The importance of loop 8.6.3 Testing residual current
impedance devices(RCDs)
5.3.3 The resistance-impedance 8.7 - Test instrument requirements
relationship 8.7.1 Basic requirements
5.3.4 Earth-fault loop impedance 8.7.2 Accuracy and resolution
values 8.8 - Supporting paperwork
5.3.5 Protective conductor 8.8.1 Why bother with paperwork
impedance 8.8.2 Electrical installation certificate
5.3.6 Maximum circuit conductor 8.8.3 Installation alterations and additions
length 8.8.4 Periodic inspection and testing
5.4 - Protective conductors 8.8.5 Minor electrical installation works
5.4.1 Earthing conductors certificate
5.4.2 Protective conductor types 9 - Data Cabling and Networks
5.4.3 Bonding conductors 9.1 - What is data cabling and why do we need it
5.4.4 Protective conductor cross- 9.2 - What are digital systems
section assessment 9.3 - Copper or glass fibre
5.4.5 Protective conductor cross- 9.4 - System design and categories
section calculation 9.5 - Installing data cabling
5.4.6 Unearthed metalwork 9.6 - Useful information
5.5 - Earth electrodes
5.5.1 Why must we have earth
electrodes
5.5.2 Earth electrode types
5.6 - Protective multiple earthing(PME)
5.6.1 What is protective multiple
earthing
5.6.2 Increased fire risk
5.6.3 Broken neutral conductor
5.6.4 Special requirements PME-fed
installations

This Electrician's Guide

The Institution of Electrical Engineers (lEE) has published an 'On-site guide' with the 16th edition
of its Regulations, which is intended to enable the electrician to carry out 'certain specified
installation work' without further reference to the Regulations. Publicity for this guide before its
issue stated 'the electrician is generally not required to perform any calculations'. When printed,
this was changed to 'to reduce the need for detailed calculations'.

In the opinion of the Author, this attitude is incorrect. It assumes that behind every electrician
there is a designer who will provide him with precise details of exactly what he is to do. This is, of
course, what happens in some cases, but totally ignores all those electricians (probably a
majority) who are left to work entirely on their own, who have to do their own calculations and
make their own decisions. These same electricians are subject to the law, so that a failure to
implement the IEE Regulations which leads to an accident, may result (and has resulted) in a
prison sentence.

It would be foolish to suppose that this Electrician's Guide could totally replace the complete
Regulations, which are made up of over two hundred and fifty A4 pages, together with a total of
eight associated 'guides'. Certainly, every electrician who does not have the advantage of expert
design advice should equip himself with the complete Regulations and with the associated
guides. However, it is the belief of the Author that this Electrician's Guide will help the average
electrician to understand, and to implement, these very complicated Regulations in the safest and
most cost-effective way possible.

Note on Supply Voltage Level


For many years the supply voltage for single-phase supplies in the UK has been 240V +/- 6%,
giving a possible spread of voltage from 226V to 254 V. For three-phase supplies the voltage was
415 V +/- 6%, the spread being from 390 V to 440V. Most continental voltage levels have been
220/380V.

In 1988 an agreement was reached that voltage levels across Europe should be unified at 230V
single phase and 400V three-phase with effect from January 1st, 1995. In both cases the
tolerance levels have become -6% to +10%, giving a single-phase voltage spread of 216 V to 253
V, with three-phase values between 376V and 440 V. It is proposed that on January 1st, 2003 the
tolerance levels will be widened to +/- 10%.

Since the present supply voltages in the UK lie within the acceptable spread of values, Supply
Companies are not intending to reduce their voltages in the near future. This is hardly surprising,
because such action would immediately reduce the energy used by consumers (and the income
of the Companies) by more than 8%.

In view of the fact that there will be no change to the actual voltage applied to installations, it has
been decided not to make changes to the calculations in this book. All are based on the 240/415V
supply voltages which have applied for many years and will continue so to do.

In due course, it is to be expected that manufacturers will supply appliances rated at 230 V for
use in the UK. When they do so, there will be problems. A 230 V linear appliance used on a 240
V supply will take 4.3% more current and will consume almost 9% more energy. A 230 V rated 3
kW immersion heater, for example, will actually provide almost 3.27kw when fed at 240 V. This
means that the water will heat a little more quickly and that there is unlikely to be a serious
problem other than that the life of the heater may be reduced, the level of reduction being difficult
to quantify.

Life reduction is easier to specify in the case of filament lamps. A 230 V rated lamp used at 240 V
will achieve only 55% of its rated life (it will fail after about 550 hours instead of the average of
1,000 hours) but will be brighter and will run much hotter, possibly leading to overheating
problems in some luminaires. The starting current for large concentrations of discharge lamps will
increase dramatically, especially when they are very cold. High pressure sodium and metal halide
lamps will show a significant change in colour output when run at higher voltage than their rating,
and rechargeable batteries in 230 V rated emergency lighting luminaires will overheat and suffer
drastic life reductions when fed at 240V

There could be electrical installation problems here for the future!

International Basis

All electricians are aware of 'The Regs'. For well over one hundred years they have provided the
rules which must be followed to make sure that electrical installations are safe.

A publication such as 'the Regs' must be regularly updated to take account of technical changes,
and to allow for the 'internationalisation' of the Regulations. The ultimate aim is that all countries
in the world will have the same wiring regulations. National differences make this still a dream,
but we are moving slowly in that direction. The 15th Edition, when it was published in 1981, was
the first edition of the IEE Regulations to follow lEC guidelines, and as such was novel in Great
Britain. It was totally different from anything we had used before. The 16th Edition has not come
as such a shock; certainly there are changes when we compare it with 'the 15th', but the two
follow similar paths to reach the common destination of safety. Any electrician who has come to
terms with the 15th should have little difficulty in working to the 16th.

A word is necessary about the identification of parts of this Electrician's Guide and of the IEE
Regulations. In this Electrician's Guide, Regulation numbers are separated by a hyphen and
indicated by placing them in square brackets. Thus, [514-06-03] is the third Regulation in the sixth
group or subsection of Section 4 of Chapter 1 in Part 5. To avoid confusion, sections and sub-
sections of this Electrician's Guide are divided by full points and enclosed in curly brackets.
Hence, {5.4.6} is the sixth sub-section of section 4 of chapter 5 of this Electrician's Guide.
The Sixteenth Edition

This latest Edition of the lEE Wiring Regulations was published in May 1991. It was permissible to
use the 15th Edition for installations put into service before January 1st, 1993. However, from
now onwards the 16th Edition must be used. The current trend is to move towards a set of wiring
regulations with world-wide application. IEC publication 364 'Electrical Installations of Buildings'
has been available for some time, and the 16th Edition is based on many of its parts. The
European Committee for Electrotechnical Standardisation (CENELEC) uses a similar pattern to
IEC 364 and to the Wiring Regulations.

The introduction of the Free European Market in 1993 might well have caused serious problems
for UK electrical contractors because whilst the lEE Wiring Regulations were held in high esteem,
they had no legal status which would require Continentals who were carrying out installation work
in the UK to abide by them. This difficulty was resolved in October 1992 when the lEE Wiring
Regulations became a British Standard, BS 7671, giving them the required international standing.

It does not follow that an agreed part of lEG 364 will automatically become part of the IEE Wiring
Regulations. For example, the lEE Wiring Regulations Committee is unable to agree with
international rules which allow the installation of sockets in bathrooms, and so sockets are not
allowed in these situations when we follow the 16th Edition.

BS 7671 recognises all harmonised standards (or Harmonised Documents, HDs) which have
been agreed by all member states of the European Union. BS EN standards are harmonised
standards based on harmonised documents and are published without addition to or deletion
from the original HDs. When a BS EN is published the relevant BS is superseded and is
withdrawn. A harmonised standard eg BS 7671, may have additions but not deletions, from the
original standard. lEG and CENELEC publications follow the pattern which will be shown in
{1.2.3}, and it is not always easy to find which Regulations apply to a given application. For
example, if we need to find the requirements for bonding, there is no set of Regulations with that
title to which we can turn. Instead, we need to consider five separate parts of the Regulations,
which in this case are:

1 [Chapter 131 Regulation [130-04-01],


2 [Section 413] Regulations [413-02-15, 413-02-27 & 413-02-29],
3 [Section 514] Regulation [514-13-01],
4 [Section 541] complete, and
5 [Section 547] complete.

The question arises 'how do we know where to look for all these different Regulations'? The
answer is two-fold. First, the Regulations themselves have a good index. Second, this
Electrician's Guide also has a useful index, from which the applicable sub-section can be found.
At the top of each sub-section is a list of all applicable Regulations.

The detail applying to a particular set of circumstances is thus spread in a number of parts of the
Regulations, and the overall picture can only be appreciated after considering all these separate
pieces of information. This Guide is particularly useful in drawing all this information together.
Plan of the Sixteenth Edition

The regulations are in seven parts as shown in {Table 1.1}

Table 1.1 - Arrangement of the 16th Edition Parts

Part 1 - Scope, objects and fundamental requirements for safety


Part 2 - Definitions
Part 3 - Assessment of general characteristics
Part 4 - Protections for safety
Part 5 - Selection and erection of equipment
Part 6 - Special installation or locations – particular requirements
Part 7 - Inspection and testing

Also included in the Regulations are six Appendices, listed in {Table 1.2}. Unlike the 15th Edition,
which was complete in itself, the 16th Edition has a number of publications called 'Guides' which
include much material previously to he found in Appendices. These Guides must he considered
to form part of the Regulations; their titles are shown in {Table 1.3
}
Table 1.2 - Appendices to the 16th Edition

Appendix 1 - British Standards to which reference is made in The Regulations


Appendix 2 - Statutory regulations and associated memoranda
Appendix 3 - Time/current characteristics of overcurrent protective devices.
Appendix 4 - Current carrying capacities and voltage drop for cables and flexible cords
Appendix 5 - Classification of external influences
Appendix 6 - Forms of Completion and Inspection certificate

It is important to understand the relationship of the Appendices and of the Guidance Notes.
Appendices provide information which the designer must have if his work is to comply with the
Regulations. Other information, such as good practice, is contained in the Guidance Notes.
Publication of the On-Site Guide, together with the first six of the Guidance Notes has resulted in
minor changes and additions to The Electricians' Guide. This Edition includes these changes.
Further changes will be made when the final Guidance Note is published by the lEE.

It is also important to have an understanding of the layout of the Regulations, so that work can be
clearly identified. Each Part is divided into Chapters, which in turn are broken down into Sections,
and then into Groups or Sub-sections, within which are to be found the actual regulations
themselves. The particular regulation is identified by a number, such as 471-13-03. Note that this
Regulation number is spoken as 'four seven one dash one three dash zero three' and NOT as
'four hundred and seventy one dash thirteen dash three'

Table 1.3 - Guides and Guidance Notes to the Regulations

1 - On-site guide
2 - Selection and erection
3 - Isolation and switching
4 - Inspection and testing
5 - Protection against fire
6 - Protection against electric shock
7 - Protection against overcurrents
8 - Special installations and locations

Note that whenever a group of digits is separated by a hyphen, the numbers represent a
regulation; they are further identified in this Guide by placing them in square brackets, eg [471-
13-03]. The apparent duplication of work within the Regulations may seem to be strange, but is
necessary if the internationally agreed layout is to be followed.

Part 4 Protection for safety


Application of protective measures
Chapter 47
for safety

Section 471 Protection against electric shock

Group 471-13 Special provisions and exemptions

Regulation 471-
Areas reserved for
13~3

The international nature of the Regulations sometimes provides some strange reading. For
example, regulations [413-02-21 to 413-02-26] deal with systems which are earthed using the IT
method, described in {5.2.6} of this Electrician's Guide. However, such a system is not accepted
for public supplies in the UK and is seldom used except in conjunction with private generators.

1.3.1 - The rationale for this guide

In the first section of this chapter the reason for writing this guide has been explained in general
terms. Two statements in (120-01-02) point out a need for detailed guidance. They are:

1. - The Regulations are intended to be cited in their entirety if referred to in any contract.
2. - They are not intended to instruct untrained persons.

The first statement indicates the need for the Regulations to be written clearly and
unambiguously, using language which will be understood by lawyers. If they were not, differences
of opinion and interpretation would arise, which might not only lead to complicated law suits, but
could possibly result in some unsafe installation work. This need for clarity does not always run
parallel with technical clarity. The electrician, as well as his designer, if he has one, sometimes
has difficulty in deciding exactly what a regulation requires, as well as the reasons for the
regulation to be a requirement in the first place.

The second statement makes it clear that the legal wording of the Regulations is paramount, and
that it will not be simplified to make its meaning more obvious to the electrician who is not an
expert in legal matters.

The object of this Electrician's Guide is to clarify the meaning of the Regulations and to explain
the technical thinking behind them as far as is possible in a publication of this size. It is not
possible to deal in detail with every Regulation. A choice has been made of those regulations
which are considered to be most often met by the electrician in his everyday work. It must be
appreciated that this Electrician's Guide cannot (and does not seek to) take the place of the
Regulation's, but merely to complement them. In some cases the 16th Edition provides detailed
guidance, and where Tables contain such information its source is given. In other cases, where
no guidance is otherwise provided, the Author makes suggestions in Tables which carry no
details of the source.

1.3.2 - Using the Electrician's Guide

A complete and systematic study of this Electrician's Guide should prove to be of great value to
those who seek a fuller understanding of the Regulations. However, it is appreciated that perhaps
a majority of readers will have neither the time nor the inclination to read in such wide detail, and
will want to use the book for reference purposes. Having found the general area of work, using
either the contents' list or the index of this Electrician's Guide, the text should help them to
understand the subject. In the event of a regulation number being known, the cross reference
index to this Electrician's Guide will show where an explanation can be found.

It has been previously stated that it is necessary for associated regulations to be spread out in
various Parts and Chapters of the Wiring Regulations. In this Electrician's Guide they are
collected together, so that, for example, all work on Earthing will be found in Chapter 5, on
Testing and Inspection in Chapter 8, and so on. This Electrician's Guide is not a textbook of
electrical principles. If difficulty is experienced in this respect, reference should be made to
'Electrical Craft Principles' by the same author, published by the IEE. This book has been written
specifically for electricians.
2.1 - Introduction

The first three parts of the Regulations lay


the foundations for more detailed work later.

Scope, object and fundamental requirements for safety applies to all


Part 1
installations and sets out their purposes as well as their status.

Part 2 Definitions details the precise meanings of terms used.

Assessment of general characteristics is concerned with making sure that the


Part 3 installation will be fit for its intended purposes under all circumstances. The
assessment must be made before the detailed

2.2.1 - Scope of the Regulations

[Chapter 11] details exactly which installations are covered in the Regulations. The Regulations
apply to all electrical installations except those relating to railway rolling stock, ships, offshore oil
and gas rigs, aircraft, mines, quarries, radio interference equipment, lightning conductors other
than bonding them to the electrical installation and those aspects of like installations covered by
BS 5655. The 16th Edition includes, for the first time, installations associated with swimming
pools, saunas, highway power supplies, street furniture and caravan parks and pitches.

Although the Regulations cover them, certain types of installation such as electric signs,
emergency lighting, flameproof systems, fire detection and alarm systems, telecommunication
systems and surface heating devices, are not fully covered. In such cases, the appropriate BS
(British Standard) must be consulted as well as the Regulations. IEE Guidance Notes,
particularly Note 4 (Protection Against Fire) give useful information Equipment used as part of an
installation but not constructed on site (a good example is switchgear) is not directly covered
except that it is required to comply with the appropriate BS.

The Regulations apply to all installations fed at voltages included in the categories Extra-low-
voltage and Low-voltage. The values of these classifications are shown in {Table 2.1}.

Table 2.1 - Voltage Classification

Extra-low Voltage Not exceeding 50 V ac or 120 V dc

Greater than extra-low voltage but not exceeding


Low-voltage 1000 V ac or 1500 V dc between conductors
--600 V ac or --900 V dc from any conductor to earth

2.2.2 -Legal status of the Regulations

The Regulations are intended to provide safety to people or to livestock from fire, shock and
burns in any installation which complies with their requirements. They are not intended to take the
place of a detailed specification, but may form part of a contract for an electrical installation. The
Regulations themselves contain the legal requirements for electrical installations, whilst the
Guidance Notes indicate good practice.
In premises licensed for public performances, such as theatres, cinemas, discos and so on, the
requirements of the licensing authority will apply in addition to the Regulations. In mine and
quarry installations the requirements of the Health and Safety Commission must he followed and
are mandatory.

In Scotland, the lEE Regulations are cited in the Building Regulations, so they must be followed.
Whilst failure to comply with the Regulations has not generally been a criminal offence, those who
complete such installations may he liable to prosecution in the event of an accident caused by the
faulty wiring system.

The Electricity at Work Regulations 1989 became law on 1.1.92 in Northern Ireland and on 1.1.90
in the rest of the UK. Their original form made it clear that compliance with lEE Regulations was
necessary, although it did not actually say so. The only buildings in which it may be argued that
people are not at work are homes, so only domestic installations are not required to follow the
requirements of the lEE Regulations, although even in these situations a prosecution may follow
an accident. It may be helpful to mention 'The Guide to Electrical Safety at Work' by John
Whitfield, also published by EPA Press, which provides useful explanations of these Regulations.

The IEE Wiring Regulations became BS 7671 on 2nd October 1992 so that the legal enforcement
of their requirements is easier, both in connection with the Electricity at Work Regulations and
from an international point of view. The Construction (Design & Management) Regulations (CDM)
were made under the Health & Safety at Work Act and implemented on 1.1.96. They require that
installation owners and their designers consider health and safety requirements during the design
and construction and throughout the life of an installation, including maintenance, repair and
demolition. The Provision and Use of Work Equipment Regulations (1998), also made under the
Health and Safety at Work Act, impose health and safety requirements on the use of machines,
equipments, tools and installations which are used at work.

2.2.3 -New inventions or methods

The Regulations indicate clearly that it is intended that only systems and equipment's covered by
the Regulations should he used. However, in the event of new inventions or methods being
applied, these should give at least the same degree of safety as older methods which comply
directly.

Where such new equipment's or methods are used, they should be noted on the Electrical
Installation Certificate (see {8.8.2}) as not complying directly with the requirements of the
Regulations.

2.2.4 -Safety requirements

Safety is the basic reason for the existence of the Wiring Regulations. [Chapter 13] has the title
'Fundamental Requirements for Safety' and really contains, in shortened form, the full safety
requirements for electrical installations. It has been said that the twenty short regulations in
Chapter 13 ore the Regulations and that the rest of the publication simply serves to spell out their
requirements in greater detail. For example, [512-04-01], part of the Common Rules for the
Selection and Erection of Equipment, has precisely the same meaning as [130-02-02] in requiring
that the installation should be capable of carrying the maximum power required by the system
when it is functioning in the way intended. It is important to appreciate that the Electricity at Work
Regulations apply to all electrical installations, covering designers, installers, inspectors, testers
and users. The regular inspection and testing of all electrical installations is a requirement of the
Electricity at Work Regulations.

Perhaps the most basic rule of all, {130-2-02], is so important that it should be quoted in lull. It
states:-

Good workmanship and proper materials shall be used

The details of [Chapter 13] are covered more fully later in this Guide.

The Building Regulations 1991 and the Building Standards (Scotland) Regulations 1990 require
all new and refurbished dwellings to be fitted with mains operated smoke alarms. For a single
family dwelling with no more than two floors there must be at least one alarm on each floor,
installed within 7 m of kitchens and living rooms and within 3 m of all bedroom doors. The alarms
must have battery backup, must be interconnected so that detection of smoke by one operates all
the alarms, and must be wired to a separate way in a distribution board or to a local, regularly
used lighting circuit. Cables do not need special fire retardant properties and do not need to be
segregated. The smoke alarm system must not be protected by an RCD.

BS 5839 Part 6 ”Code of practice for the design and installation of fire detectors in alarm
systems“ provides useful information, as does Appendix B of IEE Guidance Note 4.

2.2.5 - Supplies for safety services

Safety services are special installations which come into use in an emergency, to protect from, or
to warn of, danger and to allow people to escape. Thus, such installations would include fire
alarms and emergency lighting, supplies for sprinkler system pumps, as well as specially
protected circuits to allow lifts to function in the event of fire.

The special needs of safety circuits will often be required by authorities other than the IEE
Regulations, especially where people gather in large numbers. For example, safety circuits in
cinemas are covered by the Cinematograph Regulations 1955, administered by the Rome Office
in England, Wales and Northern Ireland and in Scotland by the Secretary of State.

Safety circuits cannot be supplied by the normal installation, because it may fail in the dangerous
circumstances the systems are there to guard against. The permitted sources of supply include
cells and batteries, standby generators (see {2.5}) and separate feeders from the mains supply.
The latter must only be used if it is certain that they will not fail at the same time as the main
supply source.

[Chapter 56] contains six sections and a total of twenty-one Regulations, detailing the
requirements for safety services. In effect, the circuits concerned must comply with all of the rest
of the Regulations, and with some additional needs.

The safety source must have adequate duration. This means, for example, that battery operated
emergency lighting must stay on for the time specified in the applicable British Standard (BS
5266). Since such installations may be called on to operate during a fire, they must not be
installed so that they pass through fire risk areas and must have fire protection of adequate
duration.

Safety circuits must be installed so that they are not affected by faults in normal systems and
overload protection can be omitted to make the circuits less liable to failure. Safety sources must
be in positions which are only open to skilled or instructed persons, and switchgear, control gear
and alarms must be suitably labelled to make them clearly identifiable.

2.3 - Definitions

Any technical publication must make sure that its readers are in no doubt about exactly what it
says. Thus, the meanings of the terms used must be defined to make them absolutely clear. For
this purpose, [Part 2] includes about one hundred and sixty definitions of words used. For
example, the term 'low voltage' is often assumed to mean a safe level of potential difference. As
far as the Regulations are concerned, a low voltage could be up to 1000 V ac or 1500 V dc!

Important definitions are those for skilled and instructed persons. A skilled person is one with
technical knowledge or experience to enable the avoidance of dangers that may be associated
with electrical energy dissipation. An instructed person is one who is adequately advised or
supervised by skilled persons to enable dangers to be avoided.

An interesting new definition in the 1997 (second) amendments, is one for an ordinary person ,
who is neither skilled nor instructed. The same amendments also change the circuit categories for
segregation of systems (see {6.6.2}). The system voltage is now categorised as Band I, which
includes ELV systems for such applications as signalling, bell and alarm installations, and Band
II, covering all other voltages normally used for electrical installations, such as our standard 230
V, 400 V systems (which are much more likely in the UK to measure as 240 V, 415V systems).

The reader of the Regulations should always consult [Part 2] if in doubt, or even if he suspects
that there could possibly be a different meaning from the one assumed. If the word or phrase
concerned is not included in [Part 2], BS 4727.

'Glossary of electrotechnical, power, telecommunication, electronics, lighting and colour terms'


should he consulted.

2.4.1 -Introductions

Before planning and carrying out an electrical installation, thought must be given to factors
affecting its effective operation, but some basic information will be needed concerning the supply
system. The Electricity Supply Company will provide information concerning the number of
phases, phase sequence and voltage of the supply. They will also give information as to the
prospective short circuit current {3.7.2}. Details of the supply protection and the external earth
fault loop impedance {5.3) for the site concerned will be given.
The installation designer will also need to consider other matters, such as the purpose of the
installation, the external influences which may affect it {2.4.3}, the compatibility of its equipment
{2.4.4} and its maintainability {2.4.5}.

2.4.2 -Purposes, supplies and structure

[Chapter 31] includes regulations which effectively provide a check list for the designer to ensure
that all the relevant factors have been taken into account.

An abbreviated check list would include the items shown in {Table 2.2}. Where equipment's or
systems have different types of supply, such as voltage or frequency, they must be separated so
that one does not influence the other.

Table 2.2 - Initial check list for the designer


) The maximum demand

b) The number and type of live conductors

c) The type of earthing arrangement

d) The nature of supply, including:

i) nominal voltage(s)

ii) nature of current (a.c. or d.c.) and frequency

iii) prospective short circuit current at the supply


intake

iv) earth fault loop impedance of the supply to the


intake position

v) suitability of the installation for it’s required


purposes, including maximum demand

vi) type and rating of the main protective device


(supply main fuse)

e) the supplies for safety services and standby


purposes

f) the arrangement of installation circuits.

2.4.3 - External influences

This subject is a very clear example of the way that the lEE Wiring Regulations follow an
international pattern. As no final agreement on the subject of external influences had been
reached when the Sixteenth Edition was published, [Chapter 32] was effectively missing from the
edition. It will be provided by an amendment when an agreement is reached internationally which
also meets the requirements of the UK. A great deal of extra data on external influences has now
(January 1997) been published in Appendix. C of the second edition of Guidance Note 1.
[Appendix 5] gives a list of how external influences are to be indicated in three categories, A, B
and C. the second letter refers to the nature of the external influence. These letters are different
for each of the categories, and are shown in {Table 2.3}. Next follows a number, rising in some
cases to 8, which indicates the class within each external influence. For example:-

BA5 indicates:
B = utilisation
A = capability
5 = skilled persons

The ability of an enclosure to withstand the ingress of solid objects and of water is indicated by
the index of protection (IP) system of classification. The system is detailed in BS EN 60529, and
consists of the letters IP followed by two numbers. The first number indicates the degree of
protection against solid objects, and the second against water. If, as is sometimes the case,
either form of protection is not classified, the number is replaced with X. Thus, IPX5 indicates an
enclosure whose protection against solid objects is not classified, but which will protect against
water jets.

Table 2.3 - External influences

Environment (A) AA Ambient temperature

AB Humidity

AC Altitude

AD Water

AE Foreign bodies

AF Corrosion

AG Impact

AH Vibration

AJ Other mechanical stresses

AK Flora (plants)

AL Fauna (animals)

AM Radiation

AN Solar (sunlight)

AP Seismic (earthquakes)

AQ Lightning

AR Wind

Utilisation (B) BA Capability(such as physical handicap)


BB Resistance

BC Contact with earth

BD Evacuation (such as difficult)

BE Materials (fire risk)

Building (C) CA Materials (combustible or non-flammable)

CB Structure (spread of fire etc.)

Other letters are also used as follows:-

W -placed after IP indicates a specified degree of weather protection


S - after the numbers indicates that the enclosure has been tested against water penetration
when not in use
M -after the numbers indicates that the enclosure has been tested against water penetration
when in use.

A great deal of extra data on external influences has now been published in Appendix C of the
2nd edition of Guidance Note 1. A more complicated system involving the use of additional and of
supplementary letters has been adopted internationally, as has an impact protection code (the 1K
Code). These details are beyond the scope of this Guide but full details are found in Appendix B
of the 2nd Ed. of Guidance Note I

An abbreviated form of the information concerning the meanings of the two numbers of the IP
system is shown in {Table 2.4}.

The EMC (Electromagnetic Compatibility) Regulations are now in force and require that electrical
installations are designed and constructed so that they do not cause electromagnetic interference
with other equipment's or systems and are themselves immune to electromagnetic interference
from other systems. The full implications of these Regulations for electrical installations are not
yet fully understood.

Table 2.4 - Numbers in the I P system

Mechanical
First Second Water protection
protection
Number Number against
against

0 Not protected 0 Not protected

Solid objects
1 exceeding 1 Dripping water
50mm

Solid objects Dripping water


2 exceeding 2 when tilted up to
12mm 15°

Solid objects
3 3 Spraying water
exceeding
2.5mm

Solid objects
4 exceeding 4 Splashing Water
1.0mm

5 Dust protected 5 Water jets

6 Dust tight 6 Heavy seas

Effects of
- - 7
immersion

- - 8 Submersion

One extremely important external influence which is often overlooked by the electrician (as well
as the designer) is the effect of testing. The application of a potential of 500 V d.c. during an
insulation test can be fatal to many parts of an electrical installation, such as movement indicators
(PIRs), electronic starter switches, computers, etc. A sensible policy is to provide a clear and
durable notice at the mains position listing the details and location of all pieces of equipment
which must be disconnected before an insulation test is carried out.

2.4.4 -Compatibility

One part of an electrical installation must not produce effects which are harmful to another part.
For example, the heavy transient starting current of electric motors {7.15.1} may result in large
voltage reductions which can affect the operation of filament and discharge lamps. Again, the use
of some types of controlled rectifier will introduce harmonics which may spread through the
installation and upset the operation of devices such as electronic timers. Computers are likely to
be affected by the line disturbances produced by welding equipment fed from the same system.
'Noisy' supplies, which contain irregular voltage patterns, can be produced by a number of
equipment's such as machines and thermostats. Such effects can result in the loss of data from
computers, point-of-sale terminals, electronic office equipment, data transmission systems, and
so on. Separate circuits may be necessary to prevent these problems from arising, together with
the provision of 'clean earth' systems.

Very strict European laws limiting the amount of electromagnetic radiation permitted from
electrical installations and appliances apply from January 1st, 1996 (the Electromagnetic
Compatibility, or EMC, Directive (see {6.6.2}). Equipment and installations must:

1. not generate excessive electromagnetic disturbances that could interfere with


other equipment's (such as radio sets), and

2. have adequate immunity to electromagnetic disturbances to allow proper


operation in its normal environment.

2.4.5 -Maintainability

When designing and installing an electrical system it is important to assess how often
maintenance will be carried out and how effective it will be. For example, a factory with a staff of
fully trained and expertly managed electricians who carry out a system of planned maintenance
may well be responsible for a different type of installation from that in a small motor-car repair
works which does not employ a specialist electrician and would not consider calling one except in
an emergency.

In the former case there may be no need to store spare cartridge fuses at each distribution board.
The absence of such spares in the latter case may well lead to the dangerous misuse of the
protective system as untrained personnel try to keep their electrical system working.

The electrical installation must be installed so that it can be easily and safely maintained, is
always accessible for additional anal installation work. Maintenance and operation and so that the
built-in protective devices will always provide the expected degree of safety. Access to lighting
systems is a common problem, and unless the luminaires can be reached from a stable and level
surface, or from steps of a reasonable height, consideration should be given to the provision of
hoisting equipment to enable the lighting system to be lowered, or the electrician raised safely to
the luminaires.

2.5 - Low voltage generating sets

A completely new Section of 24 Regulations was introduced by the 1997 amendments dealing
with low voltage generating sets. This set of Regulations was numbered Section 551, the existing
[551 - Transformers] being renumbered as 555 to accommodate it.

Where low voltage or extra-low voltage generating sets are used to power an installation, (a) as
the sole means of supply, or (b) as a backup in case of failure of the supply, or (c) for use in
parallel with the supply, these Regulations apply. Self-contained systems, operating at extra-low
voltage, which include the source of energy (usually batteries) as well as the load are not
covered.

Generating sets, for the purpose of these Regulations, include not only rotating machines
powered by combustion engines, turbines and electric motors, but also photovoltaic cells (which
convert energy from light into electricity) and electrochemical accumulators or batteries.
Protection of circuits fed from generators must be no less effective than those applying to mains-
fed systems. Voltage and frequency variations are much more likely with generators than with a
mains supply, and it must be ensured that they do not cause danger or damage t6 the equipment.

Protection of persons and of equipment must be at least as effective in the case of an installation
fed permanently or occasionally by a generating set as for a mains-fed installation. Special
requirements for bonding apply where static invertors are used. A static invertor is an electronic
system which produces an ac supply at a given voltage, frequency and waveform from a dc
source (often from a battery). When two or more generating sets operate in parallel, circulating
harmonic currents are a possibility. Such currents are at frequencies which are multiples of the
normal supply frequency, and will possibly result in overloading of the connecting cables unless
steps are taken to reduce or remove them. When not intended to run in parallel with the mains
supply, for example when used as a standby system. interlocks and switching must be provided
to ensure that parallel operation is not possible.

When a generating set is intended as a standby system for use in place of the mains supply in
the event of failure, precautions must be taken to ensure that the generator cannot operate in
parallel with the mains. Methods include an interlock between the operating systems of the
changeover switches, a system of locks with a single transferable key, a three-position break-
before-make changeover switch, or an automatic changeover switch with an interlock.

Where generators are intended to operate in parallel with the mains supply, the Supply Company
must be consulted to ensure that the generator is compatible in all respects (including power
factor, voltage changes, harmonic distortion, unbalance, starting, synchronising and voltage
fluctuation) with the mains supply. In the event of any of the above parameters becoming
incompatible with the mains supply, the generating set must be automatically disconnected. Such
disconnection must also occur if its voltage or frequency stray outside the limits of protection. It
must be possible to isolate the generating set from the mains supply, and that means of isolation
must always be accessible to the supply company.

2.6 - Standards

Every item of equipment which forms part of an electrical installation must be designed and
manufactured so that it will be safe to use. To this end all equipment should, wherever possible,
comply with the relevant British Standard; a list of the standards applying to electrical installations
is included in the Regulations as [Appendix Ii. Increasingly we are meeting equipment which has
been produced to the standards of another country. It is the responsibility of the designer to check
that such a standard does not differ from the British Standard to such an extent that safety would
be reduced. If the electrician is also the designer, and this may well happen in some cases, the
electrician carries this responsibility.

Foreign standards may well be acceptable, but it is the responsibility of the designer to ensure
that this is so. In the event of equipment not complying with the BS concerned, it is the
responsibility of the installer to ensure that it provides the same degree of safety as that
established by compliance with the Regulations.

A harmonised documant (HD) is one agreed by all member nations of CENELEC. These
documents may be published in individual countries with additions (BS 7671 is one such) but not
with deletions. BS EN documents are Standards agreed by all CENELEC members and
published without additions or deletions. Such EN standards supersede the original British
Standard.

An increasing number of electrical contractors are registered as having satisfied the British
Standards Institution that they comply fully with BS 5750 - Quality Assurance~ This standard is
not concerned directly with the Wiring Regulations, but since compliance with them is an
important part of the organisation's assurance that its work is of the highest quality, registration
under BS 5750 implies that the Wiring Regulations are followed totally.

2.7 - Undervoltage

This chapter of the Regulations deals with the prevention of dangers that could occur if voltage
falls to a level too low for safe operation of plant and protective devices. Another problem covered
is the danger that may arise when voltage is suddenly restored to a system which has previously
been on a lower voltage or without voltage at all. For example, a machine which has stopped due
to voltage falling to a low level may be dangerous if it restarts suddenly and unexpectedly when
full voltage returns. A motor starter with built-in undervoltage protection will be explained in
{7.15.1}.

The attention of the installer and the designer is drawn to the possibility that low voltage may
cause equipment damage. Should such damage occur, it must not cause danger. Where
equipment is capable of operating safely at low voltage for a short time, a time delay may be used
to prevent switching off at once when under-voltage occurs. This system may prevent plant
stoppages due to very short time voltage failures. However, such a delay must not prevent the
immediate operation of protective systems.
Installation control and protection
3.1 - Introduction 3.5 - High temperature protection
3.2 - Switching 3.6 - Overload currents
3.3 - Isolation 3.7 - Protection from faults
3.4 - Electric shock protection
3.8 - Short circuit and overload
------- protection

3.1 -Introduction

Electrical installations must be protected from the effects of short circuit and over-load.
In addition, the people using the installations, as well as the buildings containing them,
must be protected from the effects of fire and of other hazards arising from faults or from
misuse.

Not only must automatic fault protection of this kind be provided, but an installation must
also have switching and isolation which can be used to control it in normal operation, in
the event of emergency, and when maintenance is necessary.

This Chapter will consider those regulations which deal with the disconnection of
circuits, by both manual and automatic means, the latter in the event of shock, short
circuit or overload. It does not include the Regulations which concern automatic
disconnection in the event of an earth fault: these are considered in {Chapter 5}.

In order that anyone operating or testing the installation has full information concerning
it, a diagram or chart must be provided at the mains position showing the number of
points and the size and type of cables for each circuit, the method of providing protection
from direct contact (see {3.4.5}) and details of any circuit in which there is equipment,
such as passive infra-red detectors or electronic fluorescent starters, vulnerable to the
high voltage used for insulation testing.

3.2.1 - Switch positions

A switch is defined as a device which is capable of making or breaking a circuit under


normal and under overload conditions. It can make, but will not necessarily break, a short
circuit, which should be broken by the overload protecting fuse or circuit breaker. A
switching device may be marked with ON and OFF positions, or increasingly, the
numbers 1 for ON and 0 for OFF are being used.

A semiconductor device is often used for switching some lighting and heating circuits,
but will not be suitable for disconnecting overloads; thus, it must be backed up by a
mechanical switch. The semiconductor is a functional switch but must NOT be used as an
isolator.
{Figure 3.1} shows which poles of the supply need to be broken by the controlling
switches. For the TN-S system (earth terminal provided by the Electricity Company), the
TNC-S system (protective multiple earthing) and the TT system (no earth provided at the
supply), all phase conductors MUST be switched, but NOT the protective (earth)
conductor.

The neutral conductor need not be broken except for:


1 - the main switch in a single-phase installation, or
2 - heating appliances where the element can be touched, or
3 - autotransformers (not exceeding 1.5 kV) feeding discharge lamps

The neutral will need to he disconnected for periodic testing, and provision must be made
for this; it is important that the means of disconnection is accessible and can only be
completed with the use of a tool.

The protective conductor should never be switched, except when the supply can he taken
from either of two sources with earth Systems which must slot be connected together. In
this case the switches needed in the protective conductors must be linked to the phase
switches so that it is impossible for the supply to be provided unless the earthing
connection is present.

Fig 3.1 Supply system broken by switches

(a)TN-C Systems (b) TN-S, TN-C-S (c) TT Systems

Every circuit must be provided with a switching system so that it can be interrupted on
load. In practice, this does not mean a switch controlling each separate circuit; provided
that loads are controlled by switches, a number of circuits may be under the overall
control of one main switch. An example is the consumer unit used in the typical house,
where there is usually only one main switch to control all the circuits, which are provided
with individual switches to operate separate lights, heaters, and so on. If an installation is
supplied from more than one source there must he a separate main switch for each source,
and each must be clearly marked to warn the person switching off the supplies that more
than one switch needs to he operated.

It should he noted that a residual current device (RCD) may be used as a switch provided
that its rated breaking capacity is high enough.

3.2.2 -Emergency switching

Emergency switching is defined as rapidly cutting the supply to remove hazards. For
example, if someone is in the process of receiving an electric shock, the first action of a
rescuer should he to remove the supply by operating the emergency switch, which may
well be the main switch. Such switching must be available for all installations. Note that
if there is more than one source of supply a number of main switches may need to be
opened (see 3.2.1). The designer must identify all possible dangers, including electric
shock, mechanical movement, excessive heat or cold and radiation dangers, such as those
from lasers or X-rays.

In the special case of electric motors, the emergency switching must be adjacent to the
motor. In practice, such switching may take the form of a starter fitted close to the motor,
or an adjacent stop button (within 2 m) where the starter is remote. Where a starter or
contactor is used as an emergency switch, a positive means must be employed to make
sure that the installation is safe. For example, operation should be when the operating coil
is de-energised, so that an open circuit in the coil or in its operating circuit will cause the
system to be switched off {Fig 3.2}. This is often called the 'fail-safe' system.
Fig 3.2 - Two circuit breakers linked to a common stop circuit.
The system is 'fail-safe'

To prevent unexpected restarting of rotating machines, the 'latching off' stop button
shown in {Fig 3.3} is sometimes used. On operation, the button locks (latches) in the off
position until a positive action is taken to release it.

In single-phase systems, it must he remembered that the neutral is earthed. This


means that if the stop buttons are connected directly to the neutral, a single earth fault on
the stop button circuit would leave the operating coil permanently fed and prevent the
safety system from being effective. It is thus essential for the operating coil to be directly
connected to the neutral, and the stop buttons to the phase. Such an earth fault would then
operate the protective device and make the system safe.

The means of emergency switching must be such that a single direct action is required to
operate it. The switch must be readily accessible and clearly marked in a way that will be
durable. Consideration must be given to the intended use of the premises in which the
switch is installed to make sure as far as possible that the switching system is always easy
to reach and to use. For example, the switch should not be situated at the back of a
cupboard which, in use, is likely to be filled with materials making it impossible to reach
the switch.
In cases where operation could cause danger to other people (an example is where
lighting is switched off by operating the emergency switch), the switch must be available
only for operation by instructed persons. Every fixed or stationary appliance must be
provided with a means of switching which can be used in an emergency. If the device is
supplied by an unswitched plug and socket, withdrawal of the plug is NOT acceptable to
comply with this requirement,' such action is acceptable for functional switching {3.2.4}.

Fig 3.3 'latching-off' stop button

Where any circuit operates at a p.d. (potential difference) exceeding low voltage a
fireman's emergency switch must be provided. Such installations usually take the form of
discharge lighting (neon signs), and this requirement applies for all external systems as
well as internal signs which operate unattended. The purpose is to ensure the safety of
fire fighters who may, if a higher voltage system is still energised, receive dangerous
shocks when they play a water jet onto it. The fireman's switch is not required for
portable signs consuming 100 W or less which are supplied via an easily accessible plug
and socket.

The fireman's switch must meet the following requirements

1. -The switch must be mounted in a conspicuous position not more than 2.75m
from the ground.

2. -It must be coloured red and have a label in lettering at least 13 mm high
'FIREMAN'S SWITCH'. On and off positions should be clearly marked, and the OFF
position should be at the top. A lock or catch should be provided to prevent accidental
reclosure.

3. -For exterior installations the switch should be close to the load, or to a notice in
such a position to indicate clearly the position of the well-identified switch.

4. -For interior installations, the switch should be at the main entrance to the
building.
5. -Ideally, no more than one internal and one external switch must be provided.
Where more become necessary, each switch must be clearly marked to indicate exactly
which parts of the installation it controls.

6. -Where the local fire authority has additional requirements, these must be
followed.

7. -The switch should be arranged on the supply side of the step-up sign transformer

3.2.3 Switching for mechanical maintenance

Mechanical maintenance is taken as meaning the replacement and repair of non-electrical


parts of equipment, as well as the cleaning and replacement of lamps. Thus, we are
considering the means of making safe electrical equipment which is to be worked on by
non-electrical people.

Such switches must be:

1. -easily and clearly identified by those who need to use them


2. -arranged so that there can be no doubt when they are on or off
3. -close to the circuits or equipment they switch
4. -able to switch off full load current for the circuit concerned
5. -arranged so that it is impossible for them to be reclosed unintentionally.

Where mechanical maintenance requires access to the interior of equipment where live
parts could be exposed, special means of isolation are essential. Lamps should be
switched off before replacement.

3.2.4 Functional switching

Functional switching is used in the normal operation of circuits to switch them on and
off. A switch must be provided for each part of a circuit which may need to be controlled
separately from other parts of the installation. Such switches are needed for equipment
operation, and a group of circuits can sometimes be under the control of a single switch
unless separate switches are required for reasons of safety. Semiconductor switches may
control the current without opening the poles of the supply. Fuses and links must not be
used as a method of switching.

A plug and socket may be used as a functional switching device provided its rating does
not exceed 16 A. It will be appreciated that such a device must not be used for emergency
switching (see {3.2.2}).

3.3.1 Isolator definition

An isolator is not the same as a switch. It should only be opened when not carrying
current, and has the purpose of ensuring that a circuit cannot become live whilst it is out
of service for maintenance or cleaning. The isolator must break all live supply
conductors; thus both phase and neutral conductors must be isolated. It must, however, be
remembered that switching off for mechanical maintenance (see {3.2.3}) is likely to be
carried out by non-electrically skilled persons and that they may therefore unwisely use
isolators as on-load switches. To prevent an isolator, which is part of a circuit where a
circuit breaker is used for switching, from being used to break load current, it must be
interlocked to ensure operation only after the circuit breaker is already open. In many
cases an isolator can be used to make safe a particular piece of apparatus whilst those
around it are still operating normally.

3.3.2 Isolator situation

Isolators are required for all circuits and for all equipment, and must be adjacent to the
system protected.

As for a switch, the isolator must be arranged so that it will not close unintentionally due
to vibration or other mechanical effect. It must also, where remote from the circuit
protected, be provided with a means of locking in the OFF position to ensure that it is not
reclosed whilst the circuit is being worked on. The isolator should also be provided,
where necessary, with means to prevent reclosure in these circumstances. This may be a
padlock system to enable the device to be locked in the OFF position, a handle which is
removable in the off position only, etc.

It is particularly important for motors and their starters to be provided with


adjacent isolation to enable safe maintenance.

The special requirements for isolating discharge lamp circuits operating at voltages
higher than low voltage will be considered in {7.12.2}.

3.3.3 Isolator positions

Every circuit must have its means of isolation, which must be lockable in the OFF
position where remote from the equipment protected. The OFF position must be clearly
marked in all cases so that there is no doubt in the mind of the operator as to whether his
circuit is isolated and thus safe to work on. Adequate notices and labels must be
displayed to ensure safe and proper isolation and to supplement locks to prevent
inadvertent re-closing of isolators when this could cause danger. For single phase
systems, both live conductors (phase and neutral) must be broken by the isolator (TT
system). On three phase supplies, only the three phases (R, Y, and B or LI, L2 and L3)
need to be broken, the neutral being left solidly connected (TN-S and TNC-S systems).

This neutral connection is usually through a link which can be removed for testing.
Clearly, it is of great importance that the link is not removed during normal operation, so
it must comply with one or both of the following requirements:
1. - it can only be removed by using tools, and/or

2. - it is accessible only to skilled persons.

In many circuits capacitors are connected across the load. There are many reasons for
this, the most usual in industrial circuits being power factor correction. When the supply
to such a circuit is switched off, the capacitor will often remain charged for a significant
period, so that the isolated circuit may be able to deliver a severe shock to anyone
touching it.

The Regulations require that a means of discharging such capacitors should be provided.
This usually takes the form of discharge resistors {Fig 3.4}, which provide a path for
discharge current. These resistors are connected directly across the supply, so give rise to
a leakage current between live conductors. This current is reduced by using larger
resistance values, but this increases the time taken for the capacitors to discharge to a safe
potential difference. In practice, a happy medium is struck between these conflicting
requirements, resistors with values of about 100K Ohms being common.

Fig 3.4 Discharge resistors connected to a three-phase capacitor bank

When isolating a circuit so that it can be worked on, care must be taken to ensure that
there is no uninterruptible power supply (UPS) or other standby system which may make
it dangerous although isolated from the mains supply.
3.3.4 Semiconductor isolators

Semiconductors are very widely used in electrical installations, from simple domestic
light dimmers (usually using triacs) to complex speed controllers for three phase motors
(using thyristors). Whilst the semiconductors themselves are functional switches,
operating very rapidly to control the circuit voltage, they must NOT be used as isolators.

This is because when not conducting (in the OFF position) they still allow a very small
leakage current to flow, and have not totally isolated the circuit they control. {Figure 3.5}
shows semiconductors in a typical speed control circuit.

Fig 3.5 - Speed control for a dc motor fed from a three-phase supply

3.3.5 Isolator identification

The OFF position on all isolators must be clearly marked and should not be indicated
until the contacts have opened to their full extent to give reliable isolation. Every isolator
must be clearly and durably marked to indicate the circuit or equipment it protects. If a
single isolator will not cut off the supply from internal parts of an enclosure, it must be
labelled to draw attention to the possible danger. Where the unit concerned is suitable
only for off-load isolation, this should be clearly indicated by marking the isolator "Do
NOT open under load".

3.4.1 - The nature of electric shock

The nervous system of the human body controls all its movements, both conscious and
unconscious. The system carries electrical signals between the brain and the muscles,
which are thus stimulated into action

The signals are electro-chemical in nature, with levels of a few millivolts, so when the
human body becomes part of a much more powerful external circuit, its normal
operations are swamped by the outside signals. The current forced through the nervous
system of the body by external voltage is electric shock.

All the muscles affected receive much stronger signals than those they normally get and
operate very much more violently as a result. This causes uncontrolled movements and
pain. Even a patient who is still conscious is usually quite unable to counter the effects of
the shock, because the signals from his brain, which try to offset the effects of the shock
currents, are lost in the strength of the imposed signals.

A good example is the 'no-let-go' effect. Here, a person touches a conductor which sends
shock currents through his hand. The muscles respond by closing the fingers on the
conductor, so it is tightly grasped. The person wants to release the conductor, which is
causing pain, but the electrical signals from his brain are swamped by the shock current
and he is unable to let go of the offending conductor.

The effects of an electric shock vary considerably depending on the current


imposed on the nervous system, and the path taken through the body. The subject is very
complex but it has become clear that the damage done to the human body depends on two
factors:

1. -the value of shock current flowing, and


2. -the time for which it flows.

These two factors have governed the international movement towards making electrical
installations safer.

3.4.2 -Resistance of the shock path

In simple terms the human body can be considered as a circuit through which an applied
potential difference will drive a current. As we know from Ohm's Law, the current
flowing will depend on the voltage applied and the resistance of the current path. Of
course, we should try to prevent or to limit shock by aiming to stop a dangerous potential
difference from being applied across the body. However, we have to accept that there are
times when this is impossible, so the important factor becomes the resistance of the
current path.
The human body is composed largely of water, and has very low resistance. The skin,
however, has very high resistance, the value depending on its nature, on the possible
presence of water, and on whether it has become burned. Thus, most of the resistance to
the passage of current through the human body is at the points of entry and exit through
the skin. A person with naturally hard and dry skin will offer much higher resistance to
shock current than one with soft and moist skin; the skin resistance becomes very low if it
has been burned, because of the presence of conducting particles of carbon.

In fact, the current is limited by the impedance of the human body, which includes self
capacitance as well as resistance. The impedance values are very difficult to predict,
since they depend on a variety of factors including applied voltage, current level and
duration, the area of contact with the live system, the pressure of the contact, the
condition of the skin, the ambient and the body temperatures, and so on.

Fig 3.6 Path of electric shock current

Figure 3.6 is a simplified representation of the shock path through the body, with an
equivalent circuit which indicates the components of the resistance concerned. It must be
appreciated that the diagram is very approximate; the flow of current through the body
will, for example, cause the victim to sweat, reducing the resistance of the skin very
quickly after the shock commences. Fortunately, people using electrical installations
rarely have bare feet, and so the resistance of the footwear, as well as of the floor
coverings, will often increase overall shock path resistance and reduce shock current to a
safer level.

Guidance Note 7 (Special Locations) provides data on the impedance of the human body.
However, the figures are complicated by the fact that values differ significantly from
person to person; it would be sensible to assume a worst case possibility which suggests
that the impedance of the human body from hand to foot is as low as 500 Ohms. Since
this calculates to a body current of 460 mA when the body has 230 V applied, we are
considering a fatal shock situation.
There are few reliable figures for shock current effects, because they differ from person
to person, and for a particular person, with time. However, we know that something over
one milliampere of current in the body produces the sensation of shock, and that one
hundred milliamperes is likely quickly to prove fatal, particularly if it passes through the
heart.

If a shock persists, its effects are likely to prove to be more dangerous. For
example, a shock current of 500 mA may have no lasting ill effects if its duration is less
than 20 ms, but 50 mA for 10 s could well prove to be fatal. The effects of the shock will
vary, but the most dangerous results are ventricular fibrillation (where the heart beat
sequence is disrupted) and compression of the chest, resulting in a failure to breathe.

The resistance of the shock path is of crucial importance. The Regulations insist on
special measures where shock hazard is increased by a reduction in body resistance and
good contact of the body with earth potential. Such situations include locations
containing bath tubs or showers, swimming pools, saunas and so on. The Regulations
applying to these special installations are considered in {Chapter 7}.

Another important factor to limit the severity of electric shock is the limitation of earth
fault loop impedance. Whilst this impedance adds to that of the body to reduce shock
current, the real purpose of the requirement is to allow enough current to flow to operate
the protective device and thus to cut off the shock current altogether quickly enough to
prevent death from shock.

How quickly this must take place depends on the level of body resistance expected.
Where sockets are concerned, the portable appliances fed by them are likely to be
grasped firmly by the user so that the contact resistance is lower. Thus, disconnection
within 0.4 s is required. In the case of circuits feeding fixed equipment, where contact
resistance is likely to he higher, the supply must be removed within 5 s. For situations
where earth contact is likely to be good, such as farms and construction sites,
disconnection is required within 0.2 s. Earth fault loop impedance is considered more
fully in {Chapter 5}.

3.4.3 -Contact with live conductors

In order for someone to get an electric shock he or she must come into contact with a live
conductor. Two types of contact are classified.

1 - Direct contact

An electric shock results from contact with a conductor which forms part of a circuit and
would be expected to be live. A typical example would be if someone removed the plate
from a switch and touched the live conductors inside (see {Fig 3.7}). Overcurrent
protective systems will offer no protection in this case, but it is possible that an RCD with
an operating current of 30 mA or less may do so.
Fig 3.7 Direct contact

2 - Indirect contact.

An electric shock is received from contact with something connected with the electrical
installation which would not normally be expected to be live, but has become so as the
result of a fault. This would be termed an exposed conductive part. Alternatively, a shock
may be received from a conducting part which is totally unconnected with the electrical
installation, but which has become live as the result of a fault. Such a part would be
called an extraneous conductive part.

An example illustrating both types of indirect contact is shown in (Fig 3.81.) Danger in
this situation results from the presence of a phase to earth fault on the kettle. This makes
the kettle case live, so that contact with it, and with a good earth (in this case the tap)
makes the human body part of the shock circuit.

The severity of the shock will depend on the effectiveness of the kettle protective
conductor system. If the protective system had zero resistance, a 'dead short' would be
caused by the fault and the protecting fuse or circuit breaker would open the circuit. The
equivalent circuit shown in {Fig 3.8(b)} assumes that the protective conductor has a
resistance of twice that of the phase conductor at 0.6 Ohms, and will result in a potential
difference of 160 V across the victim. The higher the protective circuit resistance, the
greater will be the shock voltage, until an open circuit protective system will result in a
240 V shock.

If the protective conductor had no resistance during the short time it took for the circuit to
open, the victim would be connected across a zero resistance which would result in no
volt drop regardless of the level reached by the fault current, so there could be no shock.
The shock level thus depends entirely on the resistance of the protective system. The
lower it can be made, the less severe will be the shocks which may be received.

To sum up this subsection: Direct contact is contact with a live system which should
he known to he dangerous and Indirect contact concerns contact with metalwork
which would he expected to he at earth potential, and thus safe. The presence of
socket outlets close to sinks and taps is not prohibited by the IEE Wiring
Regulations, hut could cause danger in some circumstances. It is suggested that
special care be taken, including consultation with the Health and Safety Executive in
industrial and commercial situations.

Fig 3.8 In direct contact: Left-side) fault condition

Right-side) equivalent circuit, assuming a fault resistance of zero

3.4.4 -Protection from contact

Four methods of protection are listed in the Regulations.

1. Protection by separated extra-low voltage (SELV)


This voltage is electrically separated from earth and from other systems, is provided by a
safety source, and is low enough to ensure that contact with it cannot produce a
dangerous shock in people with normal body resistance or in livestock. The system is
uncommon.

2. Protection by protective extra-low voltage (PELV)


The method has the same requirements as SELV but is earthed at one point. Protection
against direct contact may not be required if the equipment is in a building, if the output
voltage level does not exceed 25 V rms or 60 V ripple-free dc in normally dry locations,
or 6 V rms ac or 15 V ripple-free dc in all other locations.
3. Protection by functional extra-low voltage (FELV)
This system uses the same safe voltage levels as SELV, but not all the protective
measures required for SELV are needed and the system is widely used for supplies to
power tools on construction sites {7.5}. The voltage must not exceed 50 V ac or 120 V dc.
The reason for the difference is partly that direct voltage is not so likely to produce
harmful shock effects in the human body as alternating current, and partly because the
stated value of alternating voltage is r.m.s. and not maximum.

As {Fig 3.9} shows, such a voltage rises to a peak of nearly 71 V, and in some
circumstances twice this voltage level may be present. The allowable 120 V dc must be
ripple free.

Fig 3.9 An alternating supply of 50V may provide 141 V when the supply is rectified

{Figure 3.10} shows how a 120 V direct voltage with an 80 V peak-to-peak ripple will
give a peak voltage of 160 V. The allowable ripple is such that a 120 V system must
never rise above 140 V or a 60 V system above 70 V. It is interesting to note that a direct
voltage with a superimposed ripple is more likely to cause heart fibrillation {3.4.2} than
one which has a steady voltage. Unlike the SELV system, functional extra low voltage
supplies are earthed as a normal installation. Direct contact is prevented by enclosures
giving protection to IP2X (which means that live parts cannot be touched from outside by
a human finger - see {Table 2.4}) or by insulation capable of withstanding 500 V r.m.s. a.c.
for one minute.

Fig 3.10 Increased peak value of a direct voltage with a ripple


It must be quite impossible for the low voltage levels of the normal installation to appear
on the SELV system, and enclosures/insulation used for their separation must be
subjected to the same insulation resistance tests as for the higher voltage. Any plugs used
in such a circuit must not be interchangeable with those used on the higher voltage
system. This will prevent accidentally applying a low voltage to an extra low voltage
circuit.

4. Protection by limitation of discharge energy


Most electrical systems are capable of providing more than enough energy to cause death
by electric shock. In some cases, there is too little energy to cause severe damage. For
example, most electricians will be conversant with the battery-operated insulation
resistance tester. Although the device operates at a lethal voltage (seldom less than 500 V
dc) the battery is not usually capable of providing enough energy to give a fatal shock. In
addition, the internal resistance of the instrument is high enough to cause a volt drop
which reduces supply voltage to a safe value before the current reaches a dangerous level.
This does not mean that the device is safe: it can still give shocks which may result in
dangerous falls or other physical or mental problems.

The electric cattle fence is a very good example of a system with limited energy. The
system is capable of providing a painful shock to livestock, but not of killing the animals,
which are much more susceptible to the effects of shock than humans.

3.4.5 -Direct contact protection

The methods of preventing direct contact are mainly concerned with making sure that
people cannot touch live conductors. These methods include:

1. -the insulation of live parts - this is the standard method. The insulated conductors
should be further protected by sheathing, conduit, etc.

2. -the provision of barriers, obstacles or enclosures to prevent touching (IP2X).


Where surfaces are horizontal and accessible, IP4X protection (solid objects wider than 1
mm are excluded - see {Table 2.4}), applies

3. -placing out of reach or the provision of obstacles to prevent people from reaching
live parts

4. -the provision of residual current devices (RCDs) provides supplementary


protection {5.9} but only when contact is from a live part to an earthed part.

3.4.6 -Indirect contact protection

There are three methods of providing protection from shock after contact with a
conductor which would not normally be live:
1. -making sure that when a fault occurs and makes the parts live, it results in the
supply being cut off within a safe time. In practice, this involves limitation of earth fault
loop impedance, a subject dealt with in greater detail in {5.3}.

2. -cutting off the supply before a fatal shock can be received using a residual
current device {5.9}.

3. -applying local supplementary equipotential bonding which will ensure that the
resistance between parts which can be touched simultaneously is so low that it is
impossible for a dangerous potential difference to exist between them. It is important to
stress that whilst this course of action will eliminate the danger of indirect contact, it will
still be necessary to provide disconnection of the supply to guard against other faults,
such as overheating.

It is important to appreciate that in some cases a dangerous voltage may be maintained if


an un-interruptible power supply (UPS) or a standby generator with automatic starting is
in use.

3.4.7 -Protection for users of equipment outdoors

Because of the reduced resistance to earth which is likely for people outdoors, special
requirements apply to portable equipment used by them. Experience shows that many
accidents have occurred whilst people are using lawn mowers, hedge trimmers, etc. There
must he a suitable plug (a weather-proof type if installed outdoors) installed in a position
which will not result in the need for flexible cords of excessive length. The plug must be
protected by an RCD with a rating no greater than 30 mA. Where equipment is fed from a
transformer (eg the centre tapped 110 V system on construction sites), the transformer
primary must be fed through a 30 mA rated RCD.

These requirements do not apply to extra-low voltage sockets installed for special
purposes, such as exterior low voltage garden lighting (see {7.14.2}).

3.5.1 -Introduction

The Regulations are intended to prevent both fires and burns which arise from electrical
causes. Equipment must be selected and installed with the prevention of fire and burns
fully considered. Section 421, added in the 1994 amendments, require that persons,
equipment and materials adjacent to electrical equipment must be protected from fire,
burns and effects limiting the safe functioning of equipment. Three categories of thermal
hazard are associated with an electrical installation.

1. -ignition arising directly from the installation,


2. -the spread of fire along cable runs or through trunking where proper fire stops
have not been provided, and
3. -burns from electrical equipment.
The heat from direct sunlight will add significantly to the temperature of cables, and
20°C must be added to the ambient temperature when derating a cable subject to direct
sunlight, unless it is permanently shaded in a way which does not reduce ventilation.
Account must also be taken of the effect of the ultra-violet content of sunlight on the
sheath and insulation of some types of cable.

Some types of electrical equipment are intended to become hot in normal service, and
special attention is needed in these cases. For example, electric surface heating systems
must comply fully with all three parts of BS 6351. Part 1 concerns the manufacture and
design of the equipment itself, Part 2 with the design of the system in which it is used,
and Part 3 its installation, maintenance and testing.

3.5.2 -Fire protection

Where an electrical installation or a piece of equipment which is part of it is, under


normal circumstances, likely to become hot enough to set fire to material close to it, it
must be enclosed in heat and fire resistant material which will prevent danger. Because of
the complexity of the subject, the Regulations give no specific guidance concerning
materials or clearance dimensions. It is left to the designer to take account of the
circumstances arising in a particular situation. When fixed equipment is chosen by the
installation user or by some other party than the designer or the installer, the latter are
still responsible for ensuring that the installation requirements of the manufacturers are
met.

The same general principle applies in cases where an equipment may emit arcs or hot
particles under fault conditions, including arc welding sets. Whilst it may be impossible
in every case to prevent the outbreak of fire, attention must be paid to the means of
preventing its spread.

For example, any equipment which contains more than 25 litres of flammable
Fig 3.11 Precautions for equipment which contains flammable liquid

liquid, must be so positioned and installed that burning liquid cannot escape the vicinity
of the equipment and thus spread fire. {Figure 3.11} indicates the enclosure needed for
such a piece of equipment, for example an oil-filled transformer. In situations where fire
or smoke could cause particular hazards, consideration should be given to the use of low
smoke and fire (LSF) cables. Such cables include those with thermosetting insulation and
mineral-insulated types.

Perhaps a word is needed here concerning the use of the word 'flammable'. It means
something which can catch fire and burn. We still see the word inflammable in everyday
use, with the same meaning as flammable. This is very confusing, because the prefix 'in'
may be taken as meaning 'not', giving exactly the opposite meaning. 'Inflammable' should
never be used, 'non-flammable' being the correct term for something which cannot catch
fire.

Under some conditions, especially where a heavy current is broken, the current may
continue to flow through the air in the form of an arc. This is more likely if the air
concerned is polluted with dust, smoke, etc. The arc will be extremely hot and is likely to
cause burns to both equipment and to people; metal melted by the arc may be emitted
from it in the form of extremely hot particles which will themselves cause fires and burns
unless precautions are taken. Special materials which are capable of withstanding such
arc damage are available and must be used to screen and protect surroundings from the
arc.

Some types of electrical equipment, notably spotlights and halogen heaters, project
considerable radiant heat. The installer must consider the materials which are subject to
this heat to ensure that fire will not occur. Enclosures of electrical equipment must be
suitably heat-resisting. Recessed or semi-recessed luminaires mounted in ceiling voids
must be given special attention to ensure the heat they produce cannot result in fire.
Equipment that focuses heat, such as radiant heaters and some luminaires, must be
mounted so that excessive temperatures are not reached in adjacent surfaces, The
installation of a protecting RCD with a rating not exceeding 300 mA will sometimes
prevent a fire in the event of an earth fault.

Additions to an installation or changes in the use of the area it serves may give rise to fire
risks. Examples are the addition of thermal insulation, the installation of additional cables
in conduit or trunking, dust or dirt which restricts ventilation openings or forms an
explosive mixture with air, changing lamps for others of higher rating, missing covers on
joint boxes and other enclosures so that vermin may attack cables, and so on.

3.5.3 - Protection from burns

The Regulations provide a Table showing the maximum allowable temperatures of


surfaces which could be touched and thus cause burns. The allowable temperature
depends on whether the surface is metallic or non-metallic, and on the likely contact
between the hand and the surface. Details follow in {Table 3.1}.

Table 3.1 Allowable surface temperatures for accessible parts


(taken from [Table 42A] of BS 7671: 1992)

Part Surface material Max. Temp (°C)

Hand held Metallic 55

Non-metallic 65

May be touched but not held Metallic 70

Non-metallic 80

Need not be touched in normal use Metallic 80

Non-metallic 90

Other measures intended to prevent water and hot air systems causing burns are
contained in Section 424, which was added in the 1994 amendments. They include the
requirement that the elements of forced air heaters cannot be switched on until the rate of
air flow across them is sufficient to ensure that the air emitted is not too hot, and that
water heaters and steam raisers are provided with non self-resetting controls where
appropriate. The suitability for connection of high temperature cables must be established
with the manufacturer before cables running at more than 700C are connected.

Special attention must be paid to the likely temperature of hot surfaces where they may
be touched by the very young, very old or the infirm.

3.6.1 - Introduction

'Overcurrent' means what it says - a greater level of current than the materials in use will
tolerate for a long period of time. The term can be divided into two types of excess
current.

1 Overload currents
These are currents higher than those intended to be present in the system. If such currents
persist they will result in an increase in conductor temperature, and hence a rise in
insulation temperature. High conductor temperatures are of little consequence except that
the resistance of the conductor will be increased leading to greater levels of voltage drop.

Insulation cannot tolerate high temperatures since they will lead to deterioration and
eventually failure. The most common insulation material is p.v.c. If it becomes too hot it
softens, allowing conductors which press against it (and this will happen in all cases
where a conductor is bent) to migrate through it so that they come close to, or even move
beyond, the insulation surface. For this reason, p.v.c. insulation should not normally run
at temperatures higher than 70°C, whereas under overload conditions it may have
allowable temperatures up to 115°C for a short period during transient conditions.

2 Short circuit currents


These currents will only occur under fault conditions, and may be very high indeed. As
we shall shortly show (see {3.6.3 and 3.6.4}) such currents will open the protective devices
very quickly. These currents will not flow for long periods, so that under such short-term
circumstances the temperature of p.v.c. insulation may be allowed to rise to 160°C.

The clearance time of the protective device is governed by the adiabatic equation which
is considered more fully in {3.7.3}.

3.6.2 -Overload

Overload currents occur in circuits which have no faults but are carrying a higher current
than the design value due to overloaded machines, an error in the assessment of diversity,
and so on. When a conductor system carries more current than its design value, there is a
danger of the conductors, and hence the insulation, reaching temperatures which will
reduce the useful life of the system.

The devices used to detect such overloads, and to break the circuit for protection against
them, fall into three main categories:
1. -Semi-enclosed (rewirable) fuses to BS 3036 and cartridge fuses for use in plugs
to BS 1362.
2. -High breaking capacity (HBC) fuses to BS 88 and BS 1361. These fuses are still
often known as high rupturing capacity (HRC) types.
3. -Circuit breakers, miniature and moulded case types to BS EN 60898.

Examination of the characteristics of these devices {Figs 3.13 to 3.19} indicates that they
are not the 'instant protectors' they are widely assumed to be. For example, an overloaded
30 A semi-enclosed fuse takes about 100 s to 'blow' when carrying twice its rated current.
If it carries 450 A in the event of a fault (fifteen times rated current), it takes about 0.1 s
to operate, or five complete cycles of a 50 Hz supply.

HBC fuses are faster in operation, but BS 88 Part 2 specifies that a fuse rated at 63 A or
less must NOT operate within one hour when carrying a current 20% greater than its
rating. For higher rated fuses, operation must not be within four hours at the same
percentage overload. The latter are only required to operate within four hours when
carrying 60% more current than their rated value.

Circuit breakers are slower in operation than is generally believed. For example, BS EN
60898 only requires a 30 A miniature circuit breaker to operate within one hour when
carrying a current of 40 A. At very high currents operation is described by the BS as
'instantaneous' which is actually within 0.01 seconds.
All protective devices, then, will carry overload currents for significant times without
opening. The designer must take this fact into account in his calculations. The circuit
must be designed to prevent, as far as possible, the presence of comparatively small
overloads of long duration.

The overload provisions of the Regulations are met if the setting of the device:
1. -exceeds the circuit design current
2. -does NOT exceed the rating of the smallest cable protected

In addition, the current for operation must not be greater than 1.45 times the rating of the
smallest cable protected.

The overload protection can be placed anywhere along the run of a cable provided there
are no branches, or must be at the point of cable size reduction where

Fig 3.12 Time/current characteristics


a) 30 A semi-enclosed fuse b) 30 A miniature circuit breaker type 3

this occurs. There must be NO protection in the secondary circuit of a current


transformer, or other situation where operation of the protective device would result in
greater danger than that caused by the overload. Fuses and circuit breakers controlling a
small installation are commonly grouped in a consumer's unit at the mains position.
Backless types are still available, and they must be filled with a non-combustible back on
installation.

There are some circuits which have widely varying loads, and it would be unfortunate if
the protection operated due to a severe but short-lived overload. In such cases, the heating
effect of the currents must be taken into account so that the overload setting is based on
the thermal loading.

3.6.3 -Fuses
Fuses operate because the fuse element is the 'weak link' in the circuit, so that overcurrent
will melt it and break the circuit. The time taken for the fuse link to break the circuit (to
'blow') varies depending on the type of fuse and on the characteristic of the device. The
time/current characteristic of a typical fuse is shown in {Fig 3.12(a)}. Curves for other
types and ratings of fuses are shown in {Figs 3.13 to 3.15}. The figures are adapted from
Appendix 3 of the BS 7671: 1992.

Where the current carried is very much greater than the rated value (which is usually
associated with a fault rather than with an overload) operation is usually very fast. For
small overloads, where the current is not much larger than the rated value, operation may
take a very long time, as indicated.

Fig 3.13 Time/current characteristics of semi-enclosed fuses to BS 3036

A graph with linear axes would need to be very large indeed if the high current/short time
and the low current/long time ends of the characteristic were to be used to read the time
to operate for a given current. The problem is removed by using logarithmic scales,
which open out the low current and short time portions of the scales, and compress the
high current and long time portions.
This means that the space between two major lines on the axes of the graph represents a
change of ten times that represented by the two adjacent lines. In other words, a very
much increased range of values can be accommodated on a graph of a given size.

Fig 3.14 Time/current characteristics of cartridge fuses to BS 1361

Rewirable (semi-enclosed) fuses to BS 3036 may still be used, but as they can easily have
the wrong fuse element (fuse wire) fitted and have low breaking capacity {3.7.2} they are
not recommended for other than small installations. Where used, they are subject to the
derating requirements which are explained in {4.3.8}. The diameter of copper wires for use
as elements in such fuses is shown in {Table 3.2}.

Table 3.2 Sizes of tinned copper wire fuse elements


(from [Table 53A] of BS 7671: 1992)

Fuse element rating (A) Wire diameter (mm)

3 0.15

5 0.20

10 0.35

15 0.50
20 0.60

25 0.75

30 0.85

45 1.25

60 1.53

All fuses must be clearly labelled with the fuse rating to make replacement with the
wrong fuse as unlikely as possible. It must not be hazardous to make or break a circuit
by insertion or removal of a fuse.

3.6.4 -Circuit breakers

Circuit breakers operate using one or both of two principles. They are:

1. - Thermal operation relies on the extra heat produced by the high current warming a
bimetal strip, which bends to trip the operating contacts,

2. - Magnetic operation is due to the magnetic field set up by a coil carrying the current,
which attracts an iron part to trip the breaker when the current becomes large enough.

Fig 3.15 Time/current characteristics of cartridge fuses to BS 88 Part 2


Thermal operation is slow, so it is not suitable for the speedy disconnection required to
clear fault currents. However, it is ideal for operation in the event of small but prolonged
overload currents. Magnetic operation can be very fast and so it is used for breaking fault
currents; in many cases, both thermal and magnetic operation are combined to make the
circuit breaker more suitable for both overload and fault protection. It must be
remembered that the mechanical operation of opening the contacts takes a definite
minimum time, typically 20 ms, so there can never be the possibility of truly
instantaneous operation. A typical time/current characteristic for a circuit breaker is
shown {Fig. 3.12(b)}

All circuit breakers must have an indication of their current rating. Miniature circuit
breakers have fixed ratings but moulded case types can be adjusted. Such adjustment
must require the use of a key or a tool so that the rating is unlikely to be altered except by
a skilled or instructed person.

There are many types and ratings of moulded case circuit breakers, and if they are used,
reference should be made to supplier's literature for their characteristics. Miniature circuit
breakers are manufactured in fixed ratings from 5 A to 100 A for some types, and in six
types, type B giving the closest protection. Operating characteristics for some of the more
commonly used ratings of types 1, 3, B and D are shown in {Figs 3.16 to 3.19}. The
characteristics of Type C circuit breakers are very similar to those of Type 3.

BS3871, which specified the miniature circuit breakers Types 1 to 4 was withdrawn in
1994 and has been replaced with BS EN 60898:1991 (EN stands for "European norm"),
although it is possible that circuit breakers to the old standard will still be on sale for five
years from its withdrawal. In due course, it is intended that only types B, C and D will be
available, although it will be many years before the older types cease to be used. Short
circuit ratings for the newer types will be a minimum of 3 kA and may be as high as 25
kA - the older types had short circuit ratings which were rarely higher than 9 kA.

The time/current characteristics of all circuit breakers {Figs 3.16 to 3.19} have a vertical
section where there is a wide range of operating times for a certain current. Hence, with a
fixed supply voltage, the maximum earth fault loop impedance is also fixed over this
range of time. The operating current during the time concerned is a fixed multiple of the
rated current. For example, a Type 2 MCB has a multiple of 7 (from {Table 3.3}) so a 30
A device of this type will operate over the time range of 0.04 s to 8 s at a current of 7 x
30 A = 210 A.

Table 3.3 Operating time ranges and current multiples for MCBs
over fixed current section of characteristic

MCB Type Range of operating times (s) Current multiple of rating

1 0.04 to 20 x4

2 0.04 to 8 x7

3 0.04 to 5 x10

B 0.04 to 13 x5

C 0.04 to 5 x10

D 0.05 to 3 x20

Table 3.4 A comparison of types of protective device


Miniature circuit
Semi-enclosed fuses HBC fuses
breakers

Very low initial cost Medium initial cost High initial cost

Low replacement
Medium replacement cost Zero replacement cost
cost

Low breaking Very high breaking Medium breaking


capacity capacity capacity

Table 3.5 Comparison of miniature circuit breaker types


Type Will not Will trip in Typical application
trip in

100ms at 100ms at
rating rating

1 2.7 x 4x Low inrush currents (domestic installations)

2 4x 7x General purpose use

3 7x 10 x High inrush currents (motor circuits)

B 3x 5x General purpose use (close protection)

Commercial and industrial applications with


C 5x 10 x
fluorescent fittings

Applications where high in-rush currents are


D 10 x 50 x
likely (transformers, welding machines)
{Table 3.4} shows a comparison of the three main types of protective device in terms of
cost, whilst {Table 3.5} compares the available types of MCB.

3.6.5 -Protecting conductors

The prime function of overload protection is to safeguard conductors and cables from
becoming too hot. Thus the fuse or circuit breaker rating must be no greater than that of
the smallest cable protected. Reference to the time/current characteristics of protective
devices {Figs 3.13 to 3.19} shows that a significantly greater current than the rated value is
needed to ensure operation.

Thus, the current at which the protective device operates must never be greater than 1.45
times the rating of the smallest cable protected. For example, consider a cable system
rated at 30 A and protected by a miniature circuit breaker type 3, rated at 32 A. Reference
to (Fig 3.17 shows that a prolonged overload of about 38 A will open the breaker after
about 104 seconds (about two and a half hours!). The ratio of operating current over rated
current is thus 38/30 or 1.27, significantly lower than the maximum of 1.45. All circuit
breakers and HBC fuses listed in {3.6.2 sections 2 and 3} will comply with the Regulations
as long as their rating does not exceed that of the smallest cable protected.

Semi-enclosed (rewirable) fuses do not operate so closely to their ratings as do circuit


breakers and HBC fuses. For example, the time/current characteristics of

Fig 3.16 Time/current characteristics for some miniature circuit breakers Type 1
Fig 3.17 Time/current characteristics for some miniature circuit breakers Type 3.
Type C -MCBs have very similar characteristics to Type 3
{Fig 3.13} show that about 53 A is needed to ensure the operation of a 30 A fuse after
10,000 s, giving a ratio of 53/30 or 1.77. For rewirable fuses, the Regulations require that
the fuse current rating must not exceed 0.725 times the rating of the smallest cable
protected. Considering the 30 A cable protected by the 32 A miniature circuit breaker
above, if a rewirable fuse replaced the circuit breaker, its rating must not be greater than
0.725 x 30 or 21.8 A.

Since overload protection is related to the current-carrying capacity of the cables


protected, it follows that any reduction in this capacity requires overload protection at the
point of reduction. Reduced current-carrying capacity may be due to any one or more of:

Fig 3.18 Time/current characteristics for some miniature circuit breakers Type B
Fig 3.19 Time/current characteristics for some miniature circuit breakers Type D
1. -a reduction in the cross-sectional area of the cable
2. - a different type of cable
3. -the cable differently installed so that its ability to lose heat is reduced
4. -a change in the ambient temperature to which the cable is subjected
5. -the cable is grouped with others.

{Figure 3.20} shows part of a system to indicate how protection could be applied to
conductors with reduced current carrying capacity.

Fig 3.20 Position and rating of devices for overload protection

In fact, the calculated fuse sizes for {Fig 3.20a)} of 72.5 A, 21.75 A and 7.25 A are not
available, so the next lowest sizes of 60 A, 20 A and 5 A respectively must be used. It
would be unwise to replace circuit breakers with semi-enclosed fuses because difficulties
are likely to arise. For example, the 5 A fuse used as the nearest practical size below 7.25
A is shown in {Fig 3.13} to operate in 100 5 when carrying a current of 10 A. Thus, if the
final circuit is actually carrying 10 A, replacing a 10 A circuit breaker with a 5 A fuse
will result in the opening of the circuit. The temptation may be to use the next semi-
enclosed fuse size of 15 A, but that fuse takes nearly seven minutes to operate at a current
of 30 A. Clearly, the cable could well be damaged by excessive temperature if
overloaded.

The device protecting against overload may be positioned on the load side of
(downstream from) the point of reduction, provided that the unprotected cable length
does not exceed 3 m, that fault current is unlikely, and that the cable is not in a position
that is hazardous from the point of view of ignition of its surroundings. This Regulation is
useful when designing switchboards, where a short length of cable protected by conduit
or trunking feeds a low-current switch fuse from a high current fuse as in {Fig 6.2}.
All phase conductors must be protected, but attention must be paid to the need to break at
the same time all three line conductors to a three-phase motor in the event of a fault on
one phase, to prevent the motor from being damaged by 'single-phasing'. Normally the
neutral of a three phase system should not be broken, because this could lead to high
voltages if the load is unbalanced. Where the neutral is of reduced size, overload
protection of the neutral conductor may be necessary, but then a circuit breaker must be
used so that the phases are also broken.

3.7.1 - Introduction

3.7.2 - Prospective short-circuit current (PSC)

3.7.3 - Operating time

3.7.4 - Conductors of reduced current-carrying


---------- capacity

3.7.5 - Back-up protection

3.7.6 - Insulation monitoring

3.7.1 -Introduction

The overload currents considered in the previous section are never likely to be more than
two to three times the normal rated current. Fault currents, on the other hand, can well be
several hundreds, or even several thousands of times normal. In the event of a short
circuit or an earth fault causing such current, the circuit must be broken before the cables
are damaged by high temperatures or by electromechanical stresses. The latter stresses
will be due to the force on a current carrying conductor which is subject to the magnetic
field set up by adjacent conductors. This force is proportional to the current, and to the
magnetic field strength. Since the field strength also depends on the current, force is
proportional to the square of the current. If the current is one thousand times normal,
force will be one million times greater than usual! Fault protection must not only be able
to break such currents, but to do so before damage results. Abrasion of cable insulation
by movement is usually prevented by normal fixings or by being enclosed in conduit or
trunking. Support must he provided to cables in busbar chambers.

3.7.2 -Prospective short-circuit current (PSC)

The current which is likely to flow in a circuit if line and neutral cables are short circuited
is called the prospective short circuit current (PSC). It is the largest current which can
flow in the system. and protective devices must be capable of breaking it safely. The
breaking capacity of a fuse or of a circuit breaker is one of the factors which need to be
considered in its selection. Consumer units to BS EN 60439-4 and BS 88 (HBC) fuses are
capable of breaking any probable prospective short-circuit current, but before using other
equipment the installer must make sure that their breaking capacity exceeds the PSC at
the point at which they are to he installed.

The effective breaking capacity of overcurrent devices varies widely with their
construction. Semi-enclosed fuses are capable of breaking currents of 1 kA to 4 kA
depending on their type. whilst cartridge fuses to BS 1361 will safely break at 16.5 kA
for type 1 or 33 kA for type II. BS 88 fuses are capable of breaking any possible short-
circuit current. Miniature circuit breakers to BS EN60898 have their rated breaking
capacity marked on their cases in amperes (not kA) although above 10000 A the MCB
may be damaged and lower breaking currents (75% for 10000 A and 50% above that
level) must be used for design purposes.

Prospective short circuit current is driven by the e.m.f. of he secondary winding of the
supply transformer through an impedance made up of the secondary winding and the
cables from the transformer to the fault {Fig 3.21}. The impedance of the cables will
depend on their size and length, so the PSC value will vary throughout the installation,
becoming smaller as the distance from the intake position increases. (313-01-01] requires
the PSC to be 'assessed' by 'calculation, measurement, enquiry or inspection'. In practice,
this can be difficult because it depends to some extent on impedance's which are not only
outside the installation in the supply system, but are also live. If the impedance of the
supply system can be found, a straightforward calculation using the formula of {Fig
3.21} can be used, but this is seldom the case. An alternative is to ask the local Electricity
Company. The problem here is that they are likely to protect themselves by giving a
figure which is usually at least 16 kA in excess of the true value. The problem with using
this figure is that the higher the breaking capacity of fuses and circuit breakers are (and
this must never be less than the PSC for the point at which they are installed), the higher
will be their cost.. {Table 3.6} gives a method of arriving at PSC if the type and length of
the service cable is known,

Fig 3.21 Prospective short circuit current (PSC)


Table 3.6 - Estimation of PSC at the intake position

Length of PSC (kA) up to PSC (kA) over


supply cable 25mm2 AI, 35mm2 AI,
(m)

16mm2 Cu supply 25mm2 Cu supply


-
cable cable

5 10.0 12.0

10 7.8 9.3

15 6.0 7.4

20 4.9 6.2

25 4.1 5.3

30 3.5 4.6

40 2.7 3.6

50 2 3.0

The table is not applicable in London, where the density of the distribution system means
that higher values may apply. In this case it will be necessary to consult London
Electricity.

There are two methods for measuring the value of PSC, but these can only be used when
the supply has already been connected. By then, the fuses and circuit breakers will
already be installed.

The first method is to measure the impedance of the supply by determining its voltage
regulation, that is, the amount by which the voltage falls with an increase in current. For
example, consider an installation with a no-load terminal voltage of 240 V. If, when a
current of 40 A flows, the voltage falls to 238 V, the volt drop will be due to the
impedance of the supply.

Thus Zs = systems volt drop = 240 – 238 Ω = 2 Ω = 0.05 Ω


current 40 40
Then PSC = Uo = 240 A = 4800 A or 4.8 kA
Zs 0.05

A second measurement method is to use a loop impedance tester see { 5.3 and 8.6.2 }
connected to phase and neutral (instead of phase and earth) to measure supply impedance.
This can then be used with the supply voltage as above to calculate PSC. Some
manufacturers modify their earth-loop testers so that this connection is made by selecting
'PSC' with a switch. The instrument measures supply voltage, and calculates, then
displays, PSC.
A possible difficulty in measuring PSC, and thus being able to use fuses or circuit
breakers with a lower breaking capacity than that suggested by the Supply Company, is
that the supply may be reinforced. More load may result in extra or different transformers
and cables being installed, which may reduce supply impedance and increase PSC.

3.7.3 -Operating time

Not only must the short-circuit protection system open the circuit to cut off a fault, but it
must do so quickly enough to prevent both a damaging rise in the conductor insulation
temperature and mechanical damage due to cable movement under the influence of
electro-mechanical force. The time taken for the operation of fuses and circuit breakers of
various types and ratings is shown in {Figs 3.13 to 3.19}. When the prospective short
circuit current (PSC) for the point at which the protection is installed is less than its
breaking capacity there will be no problem.

When a short circuit occurs there will be a high current which must be interrupted
quickly to prevent a rapid rise in conductor temperature.

The position is complicated because the rise in conductor temperature results in an


increase in resistance which leads to an increased loss of energy and increased heating
(W = l²Rt), where W is the energy (J) and R is the resistance Ω. The Regulations make
use of the adiabatic equation which assumes that all the energy dissipated in the
conductor remains within it in the form of heat, because the faulty circuit is opened 50
quickly. The equation is:

t= k²S²

where t = the time for fault current to raise conductor temperature to the highest
permissible level

k = a factor which varies with the type of cable

S = the cross-sectional area of the conductor (mm²)

I = the fault current value (A) - this will be the PSC

Some cable temperatures and values of k for common cables are given in {Table 3.7}.

Table 3.7 Cable temperatures and k values (copper cable)

Assumed initial Limiting final


Insulation material k
temperature (°C) temperature(°C)

p.v.c 70 160 115


85°C p.v.c 85 160 104
90°C thermosetting 90 250 143
Mineral, exposed to touch
70 160 115
or p.v.c. covered
Mineral not exposed to touch 105 250 135
As an example, consider a 10 mm² cable with p.v.c. insulation protected by a 40 A fuse to
BS 88 Part 2 in an installation where the loop impedance between lines at the point where
the fuse is installed is 0.12 Ω. If the supply is 415 V three phase, the prospective short
circuit current (PSC) will be:
I = UL A = 415 A = 3.46 kA
Z 0.12
from {Table 3.7}, k = 115
t = k²S² = 115² x 10² = 0.110s
-I² 34602

{Figure 3.15} shows that a 40 A fuse to BS 88 Part 2 will operate in 0.1 5 when carrying a
current of 400 A. Since the calculated PSC at 3460 A is much greater than 400 A. the
fuse will almost certainly clear the fault in a good deal less than 0.1 s. As this time is less
than that calculated by using the adiabatic equation (0.11 s) the cable will be unharmed in
the event of a short circuit fault.

It is important to appreciate that the adiabatic equation applies to all cables, regardless of
size. Provided that a protective device on the load side of a circuit has a breaking capacity
equal to or larger than the PSC of the circuit then that circuit complies with the PSC
requirements of the Regulations (see {Fig 3.22} and see also the note in {7.15.1} concerning
the use of dual rated fuses for motor protection).

3.7.4 - Conductors of reduced current-carrying capacity

Short circuit protection must be positioned at every point where a reduction in cable-
current carrying capacity occurs, as for overload protection {Fig 3.20}. However, if short
circuit protection on the supply side of the point of reduction (for example, at the
incoming mains position) has a characteristic that protects the reduced conductors, no
further protection is necessary {Fig 3.22 }.

Even if not protected by a suitable device on the supply side, short circuit protection may
be positioned on the load side of the reduction in rating if the conductors do not exceed 3
m in length, and are protected by trunking and conduit, and are not close to flammable
materials, This reduction is particularly useful
Fig 3.22 Short circuit protective device protecting a circuit of reduced cross-
sectional area

when connecting switchgear {Fig 3.23}. It should he noted that the 'tails' provided to
connect to the supply system should always be of sufficient cross-sectional area to carry
the expected maximum demand, and should never be smaller than 25 mm² for live
conductors and 16 mm2 for the main earthing conductor.

Fig 3.23 Short-circuit protection not required for short switch gear connections

3.7.5 -Back-up protection

There are times when the overload protection has insufficient breaking capacity safely to
interrupt the prospective short circuit current at the point of the installation where it is
situated. An instance would be where a large number of low-rated miniature circuit
breakers each with a breaking capacity of 3 kA are fed by a large cable. In the event of a
short circuit which gives a current of 8 kA, there is a good chance that the miniature
circuit breaker concerned will be unable to break the fault.
Perhaps the fault current may continue to flow in the form of an arc across the opened
circuit breaker contacts, causing a very high temperature and the danger of fire. Of
course, if this happened the circuit breaker would be destroyed.

Fig 3.24 Back-up protection

The normal method of protection is to 'back up' the circuit with a protective device which
has the necessary breaking capacity. For example, the group of miniature circuit breakers
mentioned above could be backed up by an HBC fuse as shown in (Fig 3.24}.

It will be appreciated that when a protective device operates it does not do so


instantaneously, and fault current will flow through it to the circuit it seeks to protect.
The time for which such a current flows is a critical factor in the damage that may be
done to the system before the fault clears. Damage applies to cables, switchgear,
protective devices, etc. if the fault is not cleared quickly enough. This damage will be the
result of the release of the energy of the fault current, and the system designer will aim to
minimise it by calculation and by consulting manufacturer's data of energy let-through.

3.7.6 -Insulation monitoring

In some special applications, usually IT systems, the insulation effectiveness of an


installation or of an item of equipment is monitored continuously. This is done by the
injection of a signal, usually at less than 50V, which measures insulation resistance.
When this resistance falls below a preset level an alarm is triggered and/or the circuit
concerned is switched off automatically. The setting of the monitor must be arranged so
that it can only be altered by an authorised person, and to that end it must be possible to
alter the setting only with a special tool.
3.8.1 - Combined protection

3.8.2 - Current limited by supply characteristic

3.8.3 - Protection omitted

3.8.4 - Protection of conductors in parallel

3.8.5 - Absence of protection

3.8.6 - Discrimination

3.8.1 -Combined protection

In many practical applications, most types of fuses and circuit breakers are suitable for
both overload and short circuit protection. Care must be taken, however, to ensure that
the forms of protection are chosen so that they are properly co-ordinated to prevent
problems related to excessive let-through of energy or to lack of discrimination {3.8.6}.

3.8.2 -Current limited by supply characteristic

If a supply has a high impedance, the maximum current it can provide could be less than
the current carrying capacity of the cables in the installation. In such a case, no overload
or short circuit protection is required.

This situation is very unlikely with a supply taken from an Electricity Company, but
could well apply to a private generating plant.

3.8.3 -Protection omitted

There are cases where a break in circuit current due to operation of a protective device
may cause more danger than the overload or fault. For example, breaking the supply to a
lifting electromagnet in a scrap yard will cause it to drop its load suddenly, possibly with
dire consequences. If the field circuit of a dc motor is broken, the reduction in field flux
may lead to a dangerous increase in speed. A current transformer has many more
secondary than primary turns, so dangerously high voltages will occur~if the secondary
circuit is broken.

In situations like these the installation of an overload alarm will give warning of the
faulty circuit, which can be switched off for inspection when it is safe to do so. The
possibility of short circuits in such cables will be reduced if they are given extra
protection.

Probably the most usual case of omission of protection is at the incoming mains position
of a small installation. Here, the supply fuse protects the installation tails and the
consumer's unit. The unprotected equipment must, however, comply with the
requirements for otherwise unprotected systems listed in {3.7.4}.

3.8.4 -Protection of conductors in parallel

The most common application of cables in parallel is in ring final circuits for socket
outlets, whose special requirements will he considered in {6.3.2}. Cables may otherwise be
connected in parallel provided that they are of exactly the same type, run together
throughout their length, have no branches and are expected to share the total circuit
current in proportion to their cross-sectional area. It is not recommended that cables are
connected in parallel at all except in ring final circuits..

Overload protection must then be provided for the sum of the current-carrying capacities
of the cables. If, for example, two cables with individual current ratings of 13 A are
connected in parallel, overload protection must be provided for 26 A.

Account must also be taken of a short circuit which does not affect all the cables: this is
made less likely by the requirement that they should run close together. In {Fig 3.25}, for
example, the 30 A cable with the short circuit to neutral must be able to carry more than
half the short circuit current without damage until the protection opens.

Fault current sharing in these circumstances depends on the inverse of the ratio of the
conductor resistance's. If, for example, the fault on one cable were to occur close to the
connection to the protective device, almost all of the fault current would be carried by the
short length from the protection to the fault.

In these circumstances there would be little protection for the faulty cable, and it would
be prudent to provide protection with the installation of a suitable RCD.

Fig 3.25 Cables in parallel The lower resistance path will carry the higher fault
current

3.8.5 -Absence of protection

The protection described in this Chapter applies to conductors, but not necessarily to the
equipment fed. This is particularly true where flexible cords are concerned. For example,
a short circuit in an appliance fed through a 0.5 mm2 flexible cord from a 13 A plug may
well result in serious damage to the cord or the equipment before the fuse in the plug can
operate.

3.8.6 -Discrimination

Most installations include a number of protective devices in series, and they must operate
correctly relative to each other if healthy circuits are not to be disconnect ed.
Discrimination occurs when the protective device nearest to the fault operates, leaving all
other circuits working normally.

Fig 3.26 System layout to explain discrimination

{Figure 3.26} shows an installation with a 100 A main fuse and a 30 A submain fuse
feeding a distribution board containing 10 A fuses. If a fault occurs at point Z, the 100 A
fuse will operate and the whole installation will be disconnected. If the fault is at X, the
10 A fuse should operate and not the 30 A or 100 A fuses. A fault at Y should operate the
30 A, and not the 100 A fuse. If this happens, the system has discriminated properly.

Lack of discrimination would occur if a fault at X caused operation of the 30 A or 100 A


fuses, but not the 10 A fuse. This sounds impossible until we remember the time/current
fuse characteristics explained in {3.6.3}. For example, {Fig 3.27} shows the superimposed
characteristics of a 5 A semi-enclosed fuse and a 10 A miniature circuit breaker which we
shall assume are connected in series.

If a fault current of 50 A flows, the fuse will operate in 0.56 s whilst the circuit breaker
would take 24 s to open. Clearly the fuse will operate first and the devices have
discriminated. However, if the fault current is 180 A, the circuit breaker will open in
0.016 s, well before the fuse would operate, which would take 0.12 s. In this case, there
has been no discrimination.

To ensure discrimination is a very complicated matter, particularly where an installation


includes a mixture of types of fuse, or of fuses and circuit breakers. Manufacturers'
operating characteristics must be studied to ensure discrimination. As a rule of thumb
where fuses or circuit breakers all of the same type are used, there should be a doubling
of the rating as each step towards the supply is taken.
When fault current is high enough to result in operation of the protective device within 40
ms (two cycles of a 50 Hz supply), the simple consideration of characteristics as shown in
Fig. 3.27 may not always result in correct discrimination and device manufacturers
should be consulted.

When RCDs are connected in series, discrimination between them is also important, the
rule here being that a trebling in rating applies with each step towards the supply (see also
{8.6.3}).

Fig 3.27 To illustrate a lack of discrimination

Chapter 4 : Cables, conduits and trunking

4.1 - Cable insulation materials 4.4 - Cable supports, joints and terminations
4.2 - Cables 4.5 - Cable enclosures
4.3 - Cable choice 4.6 - Conductor and cable identification

4.1 - Cable insulation materials

Rubber
For many years wiring cables were insulated with vulcanised natural rubber (VIR). Much
cable of this type is still in service, although it is many years since it was last
manufactured. Since the insulation is organic, it is subject to the normal ageing process,
becoming hard and brittle. In this condition it will continue to give satisfactory service
unless it is disturbed, when the rubber cracks and loses its insulating properties. It is
advisable that wiring of this type which is still in service should be replaced by a more
modern cable. Synthetic rubber compounds are used widely for insulation and sheathing
of cables for flexible and for heavy duty applications. Many variations are possible, with
conductor temperature ratings from 60°C to 180°C, as well as resistance to oil, ozone and
ultra-violet radiation depending on the formulation.

Paper
Dry paper is an excellent insulator but loses its insulating properties if it becomes wet.
Dry paper is hygroscopic, that is, it absorbs moisture from the air. It must be sealed to
ensure that there is no contact with the air. Because of this, paper insulated cables are
sheathed with impervious materials, lead being the most common. PILC (paper insulated
lead covered) is traditionally used for heavy power work. The paper insulation is
impregnated with oil or non-draining compound to improve its long-term performance.
Cables of this kind need special jointing methods to ensure that the insulation remains
sealed. This difficulty, as well as the weight of the cable, has led to the widespread use of
p.v.c. and XLPE (thermosetting) insulated cables in place of paper insulated types.

P.V.C.
Polyvinyl chloride (p.v.c.) is now the most usual low voltage cable insulation. It is clean
to handle and is reasonably resistant to oils and other chemicals. When p.v.c. burns, it
emits dense smoke and corrosive hydrogen chloride gas. The physical characteristics of
the material change with temperature: when cold it becomes hard and difficult to strip,
and so BS 7671 specifies that it should not be worked at temperatures below 5°C.
However a special p.v.c. is available which remains flexible at temperatures down to -
20°C.

At high temperatures the material becomes soft so that conductors which are pressing on
the insulation (eg at bends) will 'migrate' through it, sometimes moving to the edge of the
insulation. Because of this property the temperature of general purpose P.V.C. must not
be allowed to exceed 70°C, although versions which will operate safely at temperatures
up to 85°C are also available. If p.v.c. is exposed to sunlight it may be degraded by ultra-
violet radiation. If it is in contact with absorbent materials, the plasticiser may be 'leached
out' making the p.v.c. hard and brittle.

LSF (Low smoke and fume)


Materials which have reduced smoke and corrosive gas emissions in fire compared with
p.v.c. have been available for some years. They are normally used as sheathing
compounds over XLPE or LSF insulation, and can give considerable safety advantages in
situations where numbers of people may have to be evacuated in the event of fire.

Thermosetting (XLPE)
Gross-linked polyethylene (XLPE) is a thermosetting compound which has better
electrical properties than p.v.c. and is therefore used for medium- and high-voltage
applications. It has more resistance to deformation at higher temperatures than p.v.c.,
which it is gradually replacing. It is also replacing PILC in some applications.
Thermosetting insulation may be used safely with conductor temperatures up to 90°C
thus increasing the useful current rating, especially when ambient temperature is high. A
LSF (low smoke and fume) type of thermosetting cable is available.

Mineral
Provided that it is kept dry, a mineral insulation such as magnesium oxide is an excellent
insulator. Since it is hygroscopic (it absorbs moisture from the air) this insulation is kept
sealed within a copper sheath. The resulting cable is totally fireproof and will operate at
temperatures of up to 250°C. It is also entirely inorganic and thus non-ageing. These
cables have small diameters compared with alternatives, great mechanical strength, are
waterproof, resistant to radiation and electromagnetic pulses, are pliable and corrosion
resistant. In cases where the copper sheath may corrode, the cable is used with an overall
LSF covering, which reduces the temperature at which the cable may be allowed to
operate. Since it is necessary to prevent the ingress of moisture, special seals are used to
terminate cables. Special mineral-insulated cables with twisted cores to reduce the effect
of electromagnetic interference are available.

4.2.1 -Non-flexible low voltage cables

4.2.2 - Cables for overhead lines

4.2.3 - Flexible low voltage cables and cords

4.2.4 - Cables carrying alternating currents

4.2.5 - Corrosion

4.2.1 -Non-flexible low voltage cables

Types of cable currently satisfying the Regulations are shown in {Fig 4.1}.

a) Non-armoured pvc-insulated cables - Fig 4.1a

1 - pvc sheath

2 - PVC insulation

3 - copper conductor: solid.


stranded or flexible

b) Armoured PVC-insulated cables - Fig 4.1b


1 - PVC sheath

2 - armour-galvanised steel wire

3 - PVC bedding

4 - PVC insulation

5 - copper conductor

c) Split-concentric PVC insulated cables - Fig 4.1c

5 - earth continuity conductor:


1- PVC oversheath
---- bare copper wires

2 - Melinex binder 6 - PVC phase insulation

3 - PVC strings 7- copper conductors

4 - neutral conductor:
---- black PVC-covered wires

d) Rubber-insulated (elastomeric) cables - Fig 4.1d

1 - textile braided and


---- compounded

2 - 85°C rubber insulation

3 - tinned copper conductor

e) Impregnated-paper insulated lead sheathed cables - Fig 4.1e


1 - PVC oversheath 6- filler

7 - screen of metal tape intercalated


2 - galvanised steel wire armour
---- with paper tape

3 - bedding 8- impregnated paper insulation

4 - sheath: lead or lead alloy 9 - Carbon paper screen

5 - copper woven fabric tape 10 - shaped stranded conductor

f) Armoured cables with thermosetting insulation - Fig 4.1f

1- PVC oversheath

2- galvanised steel wire armour

3 - taped bedding

4- XLPE insulation

5 - solid aluminium conductor

g) Mineral-insulated cables Fig 4.1g

1 - LSF oversheath

2- copper sheath

3 - magnesium oxide insulation

4 - copper conductors
h) Consac cables - Fig 4.1h

1- extruded PVC or polythene


4- paper belt insulation
oversheath

2- thin layer of bitumen containing a


5- paper core insulation
---- corrosion inhibitor

3- extruded smooth aluminium


6 - solid aluminium conductors
sheath

i) Waveconal cables - Fig 4.1i

1 - extruded PVC oversheath

2 - aluminium wires

3 - rubber anti-corrosion bedding

4 - XLPE core insulation

5 - solid aluminium conductors

[Table 52B] gives the maximum conductor operating temperature for the various types of
cables. For general purpose p.v.c this is 70°C. Cables with thermosetting insulation can
be operated with conductor temperatures up to 90°C but since the accessories to which
they are connected may be unable to tolerate such high temperatures, operation at 70°C is
much more usual. Other values of interest to the electrician are shown in [ Table 3.7 ].
Minimum cross-sectional areas for cables are shown in [ Table 4.1 ].

Table 4.1 - Minimum permitted cross-sectional areas for cables


(from Table 52C of BS 7671: 1992)

conductor cross sectional area


type of circuit
material (mm²)

power and lighting circuits copper 1.0

(insulated conductors) aluminium 16.0

signalling and control circuits copper 0.5

flexibles, more than 7 core copper 0.1

bare conductors and busbars copper 10.0

- aluminium 16.0

bare conductors for signalling and


copper 4.0
control

4.2.2 - Cables for overhead lines

Any of the cables listed in the previous subsection are permitted to be used as overhead
conductors provided that they are properly supported. Normally, of course, the cables
used will comply with a British Standard referring particularly to special cables for use as
overhead lines. Such cables include those with an internal or external catenary wire,
which is usually of steel and is intended to support the weight of the cable over the span
concerned.

Since overhead cables are to be installed outdoors, they must be chosen and installed so
as to offset the problems of corrosion. Since such cables will usually be in tension, their
supports must not damage the cable or its insulation. More information on corrosion is
given in {4.2.5} and on the selection and installation of overhead cables will be found in
{7.13.1}.

4.2.3 - Flexible low voltage cables and cords

By definition flexible cables have conductors of cross-sectional area 4 mm² or greater,


whilst flexible cords are sized at 4 mm² or smaller. Quite clearly, the electrician is nearly
always concerned with flexible cords rather than flexible cables.
{Figure 4.2} shows some of the many types of flexible cords which are available.

a) Braided circular - Fig 4.2a

1 - oversheath - PVC 4 - insulation - pvc coloured

2 - braid - plain copper wire 5 - Conductors - plain Copper

3 - inner sheath - pvc

b) Unkinkable - Fig 4.2b

1- rubber layer collectively


textile braided semi-embedded

2- insulation (Cores) 60°C


rubber

3 -conductors - tinned copper

c) Circular sheathed - Fig 4.2c

1 - sheath - rubber or pvc

2 - insulation 60°C rubber or pvc

3 - conductors - tinned copper

d) Flat twin sheathed - Fig 4.2d


1 - sheath - PVC

2 - insulation - pvc

3 - conductors - plain copper

e) Braided circular insulated with glass fibre - Fig 4.2e

1 - glass braided overall

2 - insulation - silicon rubber

3 - conductors - stranded Copper

f) Single core p.v.c. - insulated non-sheathed - Fig 4.2f

1 - insulation - pvc

2 - conductors - plain copper

Flexible cables should not normally be used for fixed wiring, but if they are, they must be visible
throughout their length. The maximum mass which can be supported by each flexible cord is
listed in (Table 4H3A), part of which is shown here as (Table 4.2).

Table 4.2 - Maximum mass supported by twin flexible cord


Cross-sectional area (mm²) Maximum mass to be supported (kg)
0.5 2
0.75 3
1.0 5
1.25 5
1.5 5

The temperature at the cord entry to luminaires is often very high, especially where filament
lamps are used. It is important that the cable or flexible cord used for final entry is of a suitable
heat resisting type, such as 150°C rubber- insulated and braided. (Fig 4.3) shows a short length
of such cord used to make the final connection to a luminaire.
Fig 4.3 - 150°C rubber-insulated and braided flexible cord used
for the final connection to a luminaire

4.2.4 Cables carrying alternating currents

Alternating current flowing in a conductor sets up an alternating magnetic field which is


much stronger if the conductor is surrounded by an iron-rich material, for example if it is
steel wire armoured or if it is installed in a steel conduit. The currents in a twin cable, or
in two single core cables feeding a single load, will be the same. They will exert opposite
magnetic effects which will almost cancel, so that virtually no magnetic flux is produced
if they are both enclosed in the same conduit or armouring. The same is true of three-
phase balanced or unbalanced circuits provided that all three (or four, where there is a
neutral) cores are within the same steel armouring or steel conduit.

An alternating flux in an iron core results in iron losses, which result in power loss
appearing as heat in the metal enclosure. It should be remembered that not only will the
heat produced by losses raise the temperature of the conductor, but that the energy
involved will be paid for by the installation user through his electricity meter. Thus, it is
important that all conductors of a circuit are contained within the same cable, or are in the
same conduit if they are single-core types (see {Fig 4.4}).
Fig 4.4 Iron losses in the steel surrounding a cable when it carries alternating
current

a) twin conductors of the same single-phase circuit - no losses


b) single cone conductor- high losses

A similar problem will occur when single-core conductors enter an enclosure through
separate holes in a steel end plate {Fig 4.5}.

Fig 4.5 Iron losses when single-core cables enter a steel enclosure through separate holes

For this reason, single-core armoured cables should not be used. If the single core cable
has a metal sheath which is non-magnetic, less magnetic flux will be produced. However,
there will still be induced e.m.f. in the sheath, which can give rise to a circulating current
and sheath heating.

If mineral insulated cables are used, or if multi-core cables are used, with all
conductors of a particular circuit being in the same cable, no problems will result. The
copper sheath is non-magnetic, so the level of magnetic flux will be less than for a steel
armoured cable; there will still be enough flux, particularly around a high current cable,
to produce a significant induced e.m.f. However, multi-core mineral insulated cables are
only made in sizes up to 25 mm² and if larger cables are needed they must be single core.

{Figure 4.6(a)} shows the path of circulating currents in the sheaths of such single core
cables if both ends are bonded. {Figure 4.6(b)} shows a way of breaking the circuit for
circulating currents.
Fig 4.6 Circulating currents in the metal sheaths of single core cables
(a) bonded at both ends (b) circulating currents prevented by single point bonding

[523-05-01] calls for all single core cable sheaths to be bonded at both ends unless they
have conductors of 70 mm² or greater. In that case they can be single point bonded if they
have an insulating outer sheath, provided that:

i) e.m.f. values no greater than 25 V to earth are involved, and


ii) the circulating current causes no corrosion, and
iii) there is no danger under fault conditions.

The last requirement is necessary because fault currents will be many times greater than
normal load currents. This will result in correspondingly larger values of alternating
magnetic flux and of induced e.m.f.

4.2.5 - Corrosion

The metal sheaths and armour of cables, metal conduit and conduit fittings, metal
trunking and ducting, as well as the fixings of all these items, are likely to suffer
corrosion in damp situations due to chemical or electrolytic attack by certain

materials, unless special precautions are taken. The offending materials include:

1. -unpainted lime, cement and plaster,

2. -floors and dados including magnesium chloride,

3. -acidic woods, such as oak,

4. -plaster undercoats containing corrosive salts,


5. -dissimilar metals which will set up electrolytic action.

In all cases the solution to the problem of corrosion is to separate the materials between
which the corrosion occurs. For chemical attack, this means having suitable coatings on
the item to be installed, such as galvanising or an enamel or plastic coating. Bare copper
sheathed cable, such as mineral insulated types, should not be laid in contact with
galvanised material like a cable tray if conditions are likely to be damp. A p.v.c. covering
on the cable will prevent a possible corrosion problem.

To prevent electrolytic corrosion, which is particularly common with aluminium-


sheathed cables or conduit, a careful choice of the fixings with which the aluminium
comes into contact is important, especially in damp situations. Suitable materials are
aluminium, alloys of aluminium which are corrosion resistant, zinc alloys complying
with BS 1004, porcelain, plastics, or galvanised or sheradised iron or steel

4.3.1 - Cable types 4.3.8 - Protection by semi-enclosed (rewirable)


fuses
4.3.2 - Current carrying capacity of 4.3.9 - Cable rating calculation
conductors
4.3.3 - Methods of cable installation 4.3.10 - Special formulas - grouping factor
calculation
4.3.4 - Ambient temperature correction 4.3.11 - Cable volt drop
factors
4.3.5 - Cable grouping correction factors 4.3.12 - Harmonic currents and neutral conductors
4.3.6 - Thermal insulation correction factors 4.3.13 - Low smoke-emitting cables
4.3.7 - When a number of correction 4.3.14 - The effects of animals, insects and plants
--------- factors applies

4.3.1 - Cable types

When choosing a cable one of the most important factors is the temperature attained by
its insulation (see {4.1.1}); if the temperature is allowed to exceed the upper design value,
premature failure is likely. In addition, corrosion of the sheaths or enclosures may result.
For example, bare conductors such as busbars may be operated at much higher
temperatures than most insulated conductors.

However, when an insulated conductor is connected to such a high temperature system,


its own insulation may be affected by heat transmitted from the busbar, usually by
conduction and by radiation. To ensure that the insulation is not damaged:

either the operating temperature of the busbar must not exceed the safe temperature for
the insulation,
or the conductor insulation must be removed for a suitable distance from the connection
with the busbar and replaced with beat resistant insulation (see {Fig 4.7}).

It is common sense that the cable chosen should be suitable for its purpose and for the
surroundings in which it will operate. It should not be handled and installed in unsuitable
temperatures. P.V.C. becomes hard and brittle at low temperatures, and if a cable
insulated with it is installed at temperatures below 5°C it may well become damaged.

[522] includes a series of Regulations which are intended to ensure that suitable cables
are chosen to prevent damage from temperature levels, moisture, dust and dirt, pollution,
vibration, mechanical stress, plant growths, animals, sunlight or the kind of building in
which they are installed. As already mentioned in {3.5.2}, cables must not produce,
spread, or sustain fire.

[527-01] contains six regulations which are intended to reduce the risk of the spread of
fire and are concerned with choosing cables with a low likelihood of flame propagation
(see BS 4066, BS 476, BS EN 50085 and BS EN 50086). A run of bunched cables is a
special fire risk and cables in such a situation should comply with the standards stated
above.

Fig 4.7 Insulation of a cable connected to hot busbar

BS 6387 covers cables which must be able to continue to operate in a fire. These special
cables are intended to be used when it is required to maintain circuit integrity for longer
than is possible with normal cables. Such cables are categorised with three letters. The
first indicates the resistance to fire alone (A,B,C and S) and the second letter is a W and
indicates that the cable will survive for a time at 650°C when also subject to water (which
may be used to tackle the fire). The third letter (X, Y or Z) indicates the resistance to fire
with mechanical shock. For full details of these special cables see the BS.

4.3.2 - Current carrying capacity of conductors


All cables have electrical resistance, so there must be an energy loss when they carry
current. This loss appears as heat and the temperature of the cable rises. As it does so, the
heat it loses to its surroundings by conduction, convection and radiation also increases.
The rate of heat loss is a function of the difference in temperature between the conductor
and the surroundings, so as the conductor temperature rises, so does its rate of beat loss.

A cable carrying a steady current, which produces a fixed heating effect, will get hotter
until it reaches the balance temperature where heat input is equal to heat loss {Fig 4.8}.
The final temperature achieved by the cable will thus depend on the current carried, how
easily heat is dissipated from the cable and the temperature of the cable surroundings.

PVC. is probably the most usual form of insulation, and is very susceptible to damage by
high temperatures. It is very important that p.v.c. insulation should not be allowed
normally to exceed 70°C, so the current ratings of cables are designed to ensure that this
will not happen. Some special types of p.v.c. may be used up to 85°C. A conductor
temperature as high as 160°C is permissible under very short time fault conditions, on
the assumption that when the the fault is cleared the p.v.c. insulation will dissipate the
heat without itself reaching a dangerous temperature.

Fig 4.8 Heat balance graph for a cable

A different set of cable ratings will become necessary if the ability of a cable to shed its
beat changes. Thus, [Appendix 4] has different Tables and columns for different types of
cables, with differing conditions of installation, degrees of grouping and so on. For
example, mineral insulation does not deteriorate, even at very high temperatures. The
insulation is also an excellent heat conductor, so the rating of such a cable depends on
how hot its sheath can become rather than the temperature of its insulation.

For example, if a mineral insulated cable has an overall sheath of LSF or p.v.c., the
copper sheath temperature must not exceed 70°C, whilst if the copper sheath is bare and
cannot be touched and is not in contact with materials which are combustible its
temperature can be allowed to reach 150°C. Thus, a 1mm² light duty twin mineral
insulated cable has a current rating of 18.5 A when it has an LSF or p.v.c. sheath, or 22 A
if bare and not exposed to touch. It should be noticed that the cable volt drop will be
higher if more current is carried (see{4.3.11}). [Appendix 4] includes a large number of
Tables relating to the current rating of cables installed in various ways. The use of the
Tables will be considered in more detail in {4.3.4 to 4.3.11}.

4.3.3 - Methods of cable installation

We have seen that the rating of a cable depends on its ability to lose the heat produced in
it by the current it carries and this depends to some extent on the way the cable is
installed. A cable clipped to a surface will more easily be able to dissipate heat than a
similar cable which is installed with others in a conduit,

[Table 4A] of [Appendix 4] lists twenty standard methods of installation, each of them
taken into account in the rating tables of the same Appendix. For example, two 2.5 mm²
single core p.v.c. insulated non-armoured cables drawn into a steel conduit (installation
method 3) have a current rating of 24 A {Table 4.6}. A 2.5 mm² twin p.v.c. insulated and
sheathed cable, which contains exactly the same conductors, has a current rating of 27 A
{Table 4.7} when clipped directly to anon-metallic surface. Cables sheathed in p.v.c. must
not be subjected to direct sunlight, because the ultra-violet component will leach out the
plasticiser, causing the sheath to harden and crack. Cables must not be run in the same
enclosure (e.g. trunking, pipe or ducting) as non-electrical services such as water, gas, air,
etc. unless it has been established that the electrical system can suffer no harm as a result.
If electrical and other services have metal sheaths and are touching, they must be bonded.
Cables must not be run in positions where they may suffer or cause damage or
interference with other systems. They should not, for example, be run alongside hot pipes
or share a space with a hearing induction loop.

Special precautions may need to be taken where cables or equipment are subject to
ionising radiation. Where a wiring system penetrates a load bearing part of a building
construction it must he ensured that the penetration will not adversely affect the integrity
of the construction.

The build-up of dust on cables can act as thermal insulation. In some circumstances the
dust may be flammable or even explosive. Design cable runs to minimise dust
accumulation: run cables on vertically mounted cable ladders rather than horizontal cable
trays. When cables are run together, each sets up a magnetic field with a strength
depending on the current carried. This field surrounds other cables, so that there is the
situation of current-carrying conductors situated in a magnetic field. This will result in a
force on the conductor, which is usually negligible under normal conditions but which
can become very high indeed when heavy currents flow under fault conditions. All cables
and conductors must be properly fixed or supported to prevent damage to them under
these conditions.

4.3.4 - Ambient temperature correction factors

The transfer of heat, whether by conduction, convection or radiation, depends on


temperature difference - heat flows from hot to cold at a rate which depends on the
temperature difference between them. Thus, a cable installed near the roof of a boiler
house where the surrounding (ambient) temperature is very high will not dissipate heat so
readily as one clipped to the wall of a cold wine cellar.

[Appendix 4] includes two tables giving correction factors to take account of the ability
of a cable to shed heat due to the ambient temperature. The Regulations use the symbol
Ca to represent this correction factor. The tables assume that the ambient temperature is
30°C and give a factor by which current rating is multiplied for other ambient
temperatures.

For example, if a cable has a rating of 24 A and an ambient temperature correction factor
of 0.77, the new current rating becomes 24 x 0.77 or 18.5 A. Different values are given
depending on whether the circuit in question is protected by a semi-enclosed (rewirable)
fuse or some other method of protection. The most useful of the correction factors are
given in {Table 4.3}.

In {Table 4.3}, '70°C m.i.' gives data for mineral insulated cables with sheaths covered in
p.v.c. or LSF or open to touch, and '105°C m.i.' for mineral insulated cables with bare
sheaths which cannot be touched and are not in contact with combustible material. The
cable which is p.v.c. sheathed or can be touched must run cooler than if it is bare and not
in contact with combustible material, and so has lower correction factors.

Mineral insulated cables must have insulating sleeves in terminations with the
same temperature rating as the seals used.

Where a cable is subjected to sunlight, it will not be able to lose heat so easily as
one which is shaded. This is taken into account by adding 200°C to the ambient
temperature for a cable which is unshaded.

Table 4.3 Correction factors to current rating for ambient temperature


-------------- (Ca) (from [Tables 4C1 and 4C2] of BS 7671: 1992)

Ambient
Type of insulation
temperature

(°C) 70°C p.v.c 85°C rubber 70°C m.i 105°C m.i

25 1.03 (1.03) 1.02 (1.02) 1.03 (1.03) 1.02 (1.02)

30 1.00 (1.00) 1.00 (1.00) 1.00 (1.00) 1.00 (1.00)

35 0.94 (0.97) 0.95 (0.97) 0.93 (0.96) 0.96 (0.98)

40 0.87 (0.94) 0.90 (0.95) 0.85 (0.93) 0.92 (0.96)

45 0.79 (0.91) 0.85 (0.93) 0.77 (0.89) 0.88 (0.93)

50 0.71 (0.97) 0.80 (0.91) 0.67 (0.86) 0.84 (0.91)

55 0.61 (0.84) 0.74 (0.88) 0.57 (0.79) 0.80 (0.89)


Figures in brackets apply to semi-enclosed fuses
used for overload protection

4.3.5 - Cable grouping correction factors

If a number of cables is installed together and each is carrying current, they will all warm
up. Those which are on the outside of the group will be able to transmit heat outwards,
but will be restricted in losing heat inwards towards other warm cables. Cables 'buried' in
others near the centre of the group may find it impossible to shed heat at all, and will rise
further in temperature {Fig 4.9}.

Fig 4.9 The need for the grouping correction factor Cg


a) widely spaced cables dissipate heat easily
b) A closely packed cable cannot easily dissipate heat and so its temperature rises

Because of this, cables installed in groups with others (for example, if enclosed in a
conduit or trunking) are allowed to carry less current than similar cables clipped to, or
lying on, a solid surface which can dissipate heat more easily. If surface mounted cables
are touching the reduction in the current rating is, as would be expected, greater than if
they are separated. {Figure 4.9} illustrates the difficulty of dissipating heat in a group of
cables.

For example, if a certain cable has a basic current rating of 24 A and is installed in
a trunking with six other circuits (note carefully, this is circuits and not cables), Cg has a
value of 0.57 and the cable current rating becomes 24 x 0.57 or 13.7 A. The symbol Cg is
used to represent the factor used for derating cables to allow for grouping. {Table 4.4}
shows some of the more useful values of Cg.

The grouping factors are based on the assumption that all cables in a group are carrying
rated current. If a cable is expected to carry no more than 30% of its grouped rated
current, it can be ignored when calculating the group rating factor. For example, if there
are four circuits in a group but one will be carrying less than 30% of its grouped rating,
the group may be calculated on the basis of having only three circuits.
The grouping factor may also be applied to the determination of current ratings for cables
as explained in {3.8}.

Table 4.4 - Correction factors for groups of cables

Number of
Correction factor Cg
circuits

Enclosed or
- Clipped to non-metallic surface
clipped

- - Touching Spaced*

2 0.80 0.85 0.94

3 0.70 0.79 0.90

4 0.65 0.75 0.90

5 0.60 0.73 0.90

6 0.57 0.72 0.90

7 0.54 0.72 0.90

8 0.52 0.71 0.90

9 0.50 0.70 0.90

10 0.48 ---------- 0.90

* ‘Spaced’ means a gap between cables at least equal to cable diameter.

4.3.6 - Thermal insulation correction factors

The use of thermal insulation in buildings, in the forms of cavity wall filling, roof space
blanketing, and so on. is now standard. Since the purpose of such materials is to limit the
transfer of heat, they will clearly affect the ability of a cable to dissipate the heat build up
within it when in contact with them,

The cable rating tables of [Appendix 4] allow for the reduced heat loss for a cable which
is enclosed in an insulating wall and is assumed to be in contact with the insulation on
one side. In all other cases, the cable should be fixed in a position where it is unlikely to
be completely covered by the insulation. Where this is not possible and a cable is buried
in thermal insulation for 0.5 m (500 mm) or more, a rating factor (the symbol for the
thermal insulation factor is Ci) of 0.5 is applied, which means that the current rating is
halved.

Table 4.5 - Derating factors (CI) for cables up to 10mm² in cross-


sectional
---------------- area buried in thermal insulation.

Length in insulation (mm) Derating factor (CI)

50 0.89

100 0.81

200 0.68

400 0.55

500 or more 0.50

If a cable is totally surrounded by thermal insulation for only a short length (for example,
where a cable passes through an insulated wall), the heating effect on the insulation will
not be so great because heat will be conducted from the short high-temperature length
through the cable conductor. Clearly, the longer the length of cable enclosed in the
insulation the greater will be the derating effect. {Table 4.5} shows the derating factors
for lengths in insulation of up to 400 mm and applies to cables having cross-sectional
area up to 10 mm².

Commonly-used cavity wall fillings, such as polystyrene sheets or granules, will have an
adverse effect on p.v.c. sheathing, leeching out some of the plasticiser so that the p.v.c.
becomes brittle. In such cases, an inert barrier must be provided to separate the cable
from the thermal insulation. PVC cable in contact with bitumen may have some of its
plasticiser removed: whilst this is unlikely to damage the cable, the bitumen will become
fluid and may run.

4.3.7 - When a number of correction factors applies

In some cases all the correction factors will need to be applied because there are parts of
the cable which are subject to all of them. For example, if a mineral insulated cable with
p.v.c. sheath protected by a circuit breaker and with a tabulated rated current of 34 A is
run within the insulated ceiling of a boiler house with an ambient temperature of 45°C
and forms part of a group of four circuits, derating will be applied as follows:

Actual current rating (lz)


= tabulated current (It) x ambient temperature factor(Ca) x group factor (Cg) x thermal
insulation factor (Ci)
= 34 x 0.77 x 0.65 x 0.5A = 8.5A

In this case, the current rating is only one quarter of its tabulated value due to the
application of correction factors. A reduction of this sort will only occur when all the
correction factors apply at the same time. There are many cases where this is not so. If,
for example, the cable above were clipped to the ceiling of the boiler house and not
buried in thermal insulation, the thermal insulation factor would not apply.
Then, Iz = It x Ca x Cg = 34 x 0.77 x 0.65 A = 17.0 A

The method is to calculate the overall factor for each set of cable conditions and then to
use the lowest only. For example, if an the way to the boiler house the cable is buried in
thermal insulation in the wall of a space where the temperature is only 20°C and runs on
its own, not grouped with other circuits, only the carrection factor for thermal insulation
would apply. However, since the cable is then grouped with others, and is subject to a
high ambient temperature, the factors are:

Ci = 0.5
Ca x Cg = 0.77 x 0.65 = 0.5

The two factors are the same, so either fbut not both) can be applied. Had they been
different, the smaller would have been used.

4.3.8 -Protection by semi-enclosed (rewirable) fuses

If the circuit concerned is protected by a semi-enclosed (rewirable) fuse the cable size
will need to be larger to allow for the fact that such fuses are not so certain in operation
as are cartridge fuses or circuit breakers. The fuse rating must never be greater than 0.725
times the current carrying capacity of the lowest-rated conductor protected.

In effect, this is the same as applying a correction factor of 0.725 to all circuits protected
by semi-enclosed (rewirable) fuses. The ambient temperature correction factors of {Table
4.3} are larger than those for other protective devices to take this into account.

4.3.9 - Cable rating calculation

The Regulations indicate the following symbols for use when selecting cables:

Iz is the current carrying capacity of the cable in the situation where it


is installed

It is the tabulated current for a single circuit at an ambient


temperature of 30°C

Ib
is the design current, the actual current to be carried by the cable

In is the rating of the protecting fuse or circuit breaker

is the operating current for the fuse or circuit breaker (the current
I2
at which the fuse blows or the circuit breaker opens)

Ca is the correction factor for ambient temperature

Cg is the correction factor for grouping

Ci is the correction factor for thermal insulation.


The correction factor for protection by a semi-enclosed (rewirable) fuse is not given a
symbol but has a fixed value of 0.725.

Under all circumstances, the cable current carrying capacity must be equal to or greater
than the circuit design current and the rating of the fuse or circuit breaker must be at least
as big as the circuit design current. These requirements are common sense, because
otherwise the cable would be overloaded or the fuse would blow when the load is
switched an.

To ensure correct protection from overload, it is important that the protective


device operating current (I2) is not bigger than 1.45 times the current carrying capacity of
the cable (Iz). Additionally, the rating of the fuse or circuit breaker (In) must not be
greater than the the cable current carrying capacity (Iz) It is important to appreciate that
the operating current of a protective device is always larger than its rated value. In the
case of a back-up fuse, which is not intended to provide overload protection, neither of
these requirements applies.

To select a cable for a particular application, take the following steps: (note that to save
time it may be better first to ensure that the expected cable for the required length of
circuit will] not result in the maximum permitted volt drop being exceeded {4.3.11}).

1. -Calculate the expected (design) current in the circuit (Ib)

2. -Choose the type and rating of protective device (fuse or circuit breaker) to be
used (In)

3. -Divide the protective device rated current by the ambient temperature


----- correction factor (Ca) if ambient temperature differs from 30°C

4. - Further divide by the grouping correction factor (Cg)

5. -Divide again by the thermal insulation correction factor (CI)

6. -Divide by the semi-enclosed fuse factor of 0.725 where applicable

7. -The result is the rated current of the cable required, which must be chosen
----- from the appropriate tables {4.6 to 4.9}.

Observe that one should divide by the correction factors, whilst in the previous
subsection we were multiplying them. The difference is that here we start with the design
current of the circuit and adjust it to take account of factors which will derate the cable.
Thus, the current carrying capacity of the cable will be equal to or greater than the design
current. In {4.3.7} we were calculating by how much the current carrying capacity was
reduced due to application of correction factors.
{Tables 4.6 to 4.9} give current ratings and volt drops for some of the more commonly
used cables and sizes. The Tables assume that the conductors and the insulation are
operating at their maximum rated temperatures. They are extracted from the Regulations
Tables shown in square brackets e.g. [4D1A]

The examples below will illustrate the calculations, but do not take account of volt drop
requirements (see {4.3.11}).

Example 4.1

An immersion heater rated at 240 V, 3 kW is to be installed using twin with protective


conductor p.v.c. insulated and sheathed cable. The circuit will be fed from a 15 A
miniature circuit breaker type 2, and will be run for much of its 14 m length in a roof
space which is thermally insulated with glass fibre. The roof space temperature is
expected to rise to 50°C in summer, and where it leaves the consumer unit and passes
through a 50 mm insulation-filled cavity, the cable will be bunched with seven others.
Calculate the cross-sectional area of the required cable.

First calculate the design current Ib

=
Ib=
P 3000A 12.5A
=
-U 240

The ambient temperature correction factor is found from {Table 4.3} to be 0.71. The group
correction factor is found from {Table 4.4} as 0.52. (The circuit in question is bunched
with seven others, making eight in all).

The thermal insulation correction factor is already taken into account in the current rating
table (4D2A ref. method 4] and need not be further considered. This is because we can
assume that the cable in the roof space is in contact with the glass fibre but not enclosed
by it. What we must consider is the point where the bunched cables pass through the
insulated cavity. From {Table 4.5} we have a factor of 0.89.

The correction factors must now be considered to see if more than one of them applies to
the same part of the cable. The only place where this happens is in the insulated cavity
behind the consumer unit. Factors of 0.52 (Cg) and 0.89 (CI) apply. The combined value
of these (0.463), which is lower than the ambient temperature correction factor of 0.71,
and will thus be the figure to be applied. Hence the required current rating is calculated:-

Table 4.6 - Current ratings and volt drops for unsheathed single core p.v.c. insulated
cables

Cross In In In In
Clipped Clipped
sectional conduit conduit conduit conduit Volt drop Volt drop
direct direct
area in in on wall on wall
thermal thermal
insulation insulation

(mm²) (A) (A) (A) (A) (A) (A) (mV/A/m) (mV/A/m)

3 or 4 2 3 or 4 2 3 or 4 3 or 4
- 2 cables 2 cables
cables cables cables cables cables cables

1.0 11.0 10.5 13.5 12.0 15.5 14.0 44.0 38.0

1.5 14.5 13.5 17.5 15.5 20.0 18.0 29.0 25.0

2.5 19.5 18.0 24.0 21.0 27.0 25.0 18..0 15.0

4.0 26.0 24.0 32.0 28.0 37.0 33.0 11.0 9.5

6.0 34.0 31.0 41.0 36.0 47.0 43.0 7.3 6.4

10.0 46.0 42.0 57.0 50.0 65.0 59.0 4.4 3.8

16.0 61.0 56.0 76.0 68.0 87.0 79.0 2.8 2.4

Table 4.7 - Current ratings and volt drops for sheathed multi-core p.v.c.-insulated cables

In In
Cross conduit conduit In In
Clipped Clipped
sectional in in conduit conduit Volt drop Volt drop
direct direct
area thermal thermal on wall on wall
insulation insulation

(mm²) (A) (A) (A) (A) (A) (A) (mV/A/m) (mV/A/m)

3 or 4 3 or 4 3 or 4 3 or 4
- 2 core 2 core 2 core 2 core
core core core core

1.0 11.0 10.0 13.0 11.5 15.0 13.5 44.0 38.0

1.5 14.0 13.0 16.5 15.0 19.5 17.5 29.0 25.0

2.5 18.5 17.5 23.0 20.0 27.0 24.0 18.0 15.0

4.0 25.0 23.0 30.0 27.0 36.0 32.0 11.0 9.5

6.0 32.0 29.0 38.0 34.0 46.0 41.0 7.3 6.4

10.0 43.0 39.0 52.0 46.0 63.0 57.0 4.4 3.8

16.0 57.0 52.0 69.0 62.0 85.0 76.0 2.8 2.4

Iz = in = 15 A = 32.4 A
Cg x Ci 0.52 x 0.89
From {Table 4.7}, 6 mm² p.v.c. twin with protective conductor has a current rating of 32
A. This is not quite large enough, so 10 mm²with a current rating of 43 A is indicated.
Not only would this add considerably to the costs, but would also result in difficulties due
to terminating such a large cable in the accessories.

A more sensible option would be to look for a method of reducing the required cable size.
For example, if the eight cables left the consumer unit in two bunches of four, this would
result in a grouping factor of 0.65 (from {Table 4.4}). Before applying this, we must check
that the combined grouping and thermal insulation factors (0.65 x 0.89 = .0.58) are still
less than the ambient temperature factor of 0.71, which is the case.

Table 4.8 - Current ratings of mineral insulated cables clipped direct

p.v.c. p.v.c. Bare Bare


Cross- p.v.c.
sheath Sheath 3 sheath sheath
sectional Volt Sheath
2 x single x single or 2x 3x
area 3 core
or twin twin single single

(mm²) (A) (A) (A) (A) (A)

1.0 500v 18.5 16.5 16.5 22.0 21.0

1.5 500v 24.0 21.0 21.0 28.0 27.0

2.5 500v 31.0 28.0 28.0 38.0 36.0

4.0 500v 42.0 37.0 37.0 51.0 47.0

1.0 750v 20.0 17.5 17.5 24.0 24.0

1.5 750v 25.0 22.0 22.0 31.0 30.0

2.5 750v 34.0 30.0 30.0 42.0 41.0

4.0 750v 45.0 40.0 40.0 55.0 53.0

6.0 750v 57.0 51.0 51.0 70.0 67.0

10.0 750v 78.0 69.0 69.0 96.0 91.0

16.0 750v 104.0 92.0 92.0 127.0 119.0

Note that in (Tables 4.8 and 4.9) 'P.V.C. Sheath means bare and exposed to touch or
having an over-all covering of p.v.c. or LSF and 'Bare' means bare and neither exposed to
touch nor in contact with combustible materials.

Table 4.9 - Volt drops for mineral insulated cables


Cross-
Single-phase Single- Three-phase Three-
sectional
p.v.c. Sheath phase bare p.v.c. Sheath phase bare
area

(mm²) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)

1.0 42.0 47.0 36.0 40.0

1.5 28.0 31.0 24.0 27.0

2.5 17.0 19.0 14.0 16.0

4.0 10.0 12.0 9.1 10.0

6.0 7.0 7.8 6.0 6.8

10.0 4.2 4.7 3.6 4.1

16.0 2.6 3.0 2.3 2.6

This leads to a cable current rating of 15 A = 25.9 A


0.65 x 0.89

This is well below the rating for 6 mm² of 32 A, so a cable of this size could be selected.

Example 4.2
The same installation as in Example 4.1 is proposed. To attempt to make the cable size
smaller, the run in the roof space is to be kept clear of the glass fibre insulation. Does this
make any difference to the selected cable size?

There is no correction factor for the presence of the glass fibre, so the calculation of Iz
will be exactly the same as Example 4.1 at 32.4 A.

This time reference method I (clipped direct) will apply to the current rating {Table 4.7}.
For a two core cable, 4.0 mm², two core has a rating of 36 A, so this Will be the selected
size.

It is of interest to notice how quite a minor change in the method of installation, in this
case clipping the cable to the joists or battens clear of the glass fibre, has reduced the
acceptable cable size.

Example 4.3
Assume that the immersion heater indicated in the two previous examples is to be
installed, but this time with the protection of a 15 A rewirable (semi-enclosed) fuse.
Calculate the correct cable size for each of the alternatives, that is where firstly the cable
is in contact with glass fibre insulation, and secondly where it is held clear of it.
This time the value of the acceptable current carrying capacity Iz will be different
because of the need to include a factor for the rewirable fuse as well as the new ambient
temperature and grouping factors for the rewirable fuse from {Tables 4.3 and 4.4}.

Iz = in = 15 A = 45.7 A
Cg x Ca x 0.725 0.52 x 0.87 x 0.725

In this case, the cable is in contact with the glass fibre, so the first column of {Table 4.7} of
current ratings will apply. The acceptable cable size is 16 mm² which has a current rating
of 57 A.

This cable size is not acceptable on the grounds of high cost and because the conductors
are likely to be too large to enter the connection tunnels of the immersion heater and its
associated switch. If the cables leaving the consumer unit are re-arranged in two groups
of four, this will reduce the grouping factor to 0.65, so that the newly calculated value of
Iz is 36.6 A. This means using 10 mm² cable with a current rating of 43A (from {Table
4.7}), since 6 mm² cable is shown to have a current rating in these circumstances of only
32 A. By further rearranging the cables leaving the consumer unit to be part of a group of
only two, Cg is increased to 0.8, which reduces Iz to 29.7 A which enables selection of a
6 mm² cable.

Should it be possible to bring the immersion heater cable out of the consumer unit on its
own, no grouping factor would apply and Iz would fall to 23.8 A, allowing a 4 mm² cable
to be selected.

Where the cable is not in contact with glass fibre there will be no need to repeat the
calculation of Iz, which still has a value of 29.7 A provided that it is possible to group the
immersion heater cable with only one other where it leaves the consumer unit. This time
we use the 'Reference Method 1 (clipped direct)' column of the current rating {Table 4.7},
which shows that 4 mm² cable with a current rating of 36 A will be satisfactory.

Examples 4.1, 4.2 and 4.3 show clearly how forward planning will enable a more
economical and practical cable size to be used than would appear necessary at first. It is,
of course, important that the design calculations are recorded and retained in the
installation manual.

Example 4.4
A 415 V 50 Hz three-phase motor with an output of 7,5 kW, power factor 0.8 and
efficiency 85% is the be wired using 500 V light duty three-core mineral insulated p.v.c.
sheathed cable. The length of run from the HBC protecting fuses is 20 m, and for about
half this run the cable is clipped to wall surfaces. For the remainder it shares a cable tray,
touching two similar cables across the top of a boiler room where the ambient
temperature is 50°C. Calculate the rating and size of the correct cable.

The first step is to calculate the line current of the motor.


Input = output = 7.5 x 100 kW = 8.82 kW
efficiency 85

Line current Ib = P = 8.82 x 103 A = 15.3 A


------------------------- √3 x UL x cos∅ √3 x 415 x 0.8

We must now select a suitable fuse. {Fig 3.15} for BS 88 fuses shows the 16 A size to be
the most suitable. Part of the run is subject to an ambient temperature of 50°C, where the
cable is also part of a group of three, so the appropriate correction factors must be applied
from {Tables 4.3 and 4.4}.

Iz = In =---------- 16A = 34.2A


Cg x Ca ------0.70x 0.67

Note that the grouping factor of 0.70 has been selected because where the cable is
grouped it is clipped to a metallic cable tray, and not to a non-metallic surface. Next the
cable must be chosen from {Table 4.8}. Whilst the current rating would be 15.3 A if all of
the cable run were clipped to the wall, part of the run is subject to the two correction
factors, so a rating of 34.2 A must be used. For the clipped section of the cable (15.3 A),
reference method I could be used which gives a size of 1.0 mm² (current rating 16.5 A).
However, since part of the cable is on the tray (method 3) the correct size for 34.2 A will
be 4.0 mm², with a rating of 37 A.

4.3.10 - Special formulas for grouping factor calculation

In some cases the conductor sizes where cables are grouped and determined by the
methods shown in {4.3.9} can be reduced by applying some rather complex formulas
given in [Appendix 4].

Whilst it is true that in many cases the use of these formulas will show the installer that it
is safe for him to use a smaller cable than he would have needed by simple application of
correction factors, this is by no means always the case. There are many cases where their
application will make no difference at all. Since this book is for the electrician, rather
than for the designer, the rather complicated mathematics will be omitted.

4.3.11 - Cable volt drop

All cables have resistance, and when current flows in them this results in a volt drop.
Hence, the voltage at the load is lower than the supply voltage by the amount of this volt
drop.

The volt drop may be calculated using the


basic Ohm's law formula

U=IxR

where U is the cable volt drop (V


I is the circuit
current (A), and

R is the circuit resistance Ω(Ohms)

Unfortunately, this simple formula is seldom of use in this case, because the cable
resistance under load conditions is not easy to calculate.

[525-01-03] indicates that the voltage at any load must never fall so low as to impair the
safe working of that load, or fall below the level indicated by the relevant British
Standard where one applies.

[525-01-02] indicates that these requirements will he met if the voltage drop does not
exceed 4% of the declared supply voltage. If the supply is single-phase at the usual level
of 240 V, this means a maximum volt drop of 4% of 240 V which is 9.6 V, giving (in
simple terms) a load voltage as low as 230.4 V. For a 415 V three-phase system,
allowable volt drop will be 16.6 V with a line load voltage as low as 398.4 V.

It should be borne in mind that European Agreement RD 472 S2 allows the


declared supply voltage of 230 V to vary by +10% or -6%. Assuming that the supply
voltage of 240 V is 6% low, and allowing a 4% volt drop, this gives permissible load
voltages of 216.6 V for a single-phase supply, or 374.5 V (line) for a 415 V three-phase
supply.

To calculate the volt drop for a particular cable we use {Tables 4.6, 4.7 and 4.9}. Each
current rating table has an associated volt drop column or table. For example, multicore
sheathed non-armoured P.V.C. insulated cables are covered by {Table 4.7} for current
ratings, and volt drops. The exception in the Regulations to this layout is for mineral
insulated cables where there are separate volt drop tables for single- and three-phase
operation, which are combined here as {Table 4.9}.

Each cable rating in the Tables of [Appendix 4] has a corresponding volt drop figure in
millivolts per ampere per metre of run (mV/A/m). Strictly this should be mV/(A m), but
here we shall follow the pattern adopted by BS 7671: 1992. To calculate the cable volt
drop:

1. -take the value from the volt drop table (mV/A/m)


2. - multiply by the actual current in the cable (NOT the current rating)
3. -multiply by the length of run in metres
4. -divide the result by one thousand (to convert millivolts to volts).

For example, if a 4 mm² p.v.c. sheathed circuit feeds a 6 kW shower and has a length of
run of 16 m, we can find the volt drop thus:

From {Table 4.7}, the volt drop figure for 4 mm² two-core cable is 11 mV/A/m.
Cable current is calculated from I = P = 6000 A = 25 A
U 240----
-

Volt drop is then 11 x 25 x 16 V = 4.4 V


1000

Since the permissible volt drop is 4% of 240 V, which is 9.6 V, the cable in question
meets volt drop requirements. The following examples will make the method clear.

Example 4.5
Calculate the volt drop for the case of Example 4.1. What maximum length of cable would
allow the installation to comply with the volt drop regulations?

The table concerned here is {4.7}, which shows a figure of 7.3 mV/A/m for 6 mm² twin
with protective conductor pvc insulated and sheathed cable. The actual circuit current is
12.5 A, and the length of run is 14 m.

Volt drop = 7.3 x 12.5 x 14 = 1.28 V


V
1000

Maximum permissible volt drop is 4% of 240 V = 4 of 240 V = 9.6 V


100

If a 14 m run gives a volt drop of 1.28 V, 9.6 x 14m = 105m


the length of run for a 9.6 V drop will be: 1.28

Example 4.6
Calculate the volt drop for the case of {Example 4.2}. What maximum length of cable
would allow the installation to comply with the volt drop regulations?

The Table concerned here is {4.7} which shows a volt drop figure for 4.0 mm² cable of
11mV/A/m, with the current and the length of run remaining at 12.5 A. and 14 m
respectively.
Volt drop = 11 x 12.5 x 14 V = 1.93 V
1000

Maximum permissible volt drop is 4% of 240 V = 4 of 240 V = 9.6 V


100

If a 14 m run gives a volt drop of 1.93 V, 9.6 x 14m = 70m


the length of run for a 9.6 V drop will be: 1.93

Example 4.7
Calculate the volt drop for the cases of {Example 4.3} for each of the alternative
installations. What maximum length of cable would allow the installation to comply with
the volt drop regulations in each case?

In neither case is there any change in cable sizes, the selected cables being 6 mm² in the
first case and 4 mm² in the second. Solutions are thus the same as those in {Examples 4.5
and 4.6} respectively.

Example 4.8
Calculate the volt drop and maximum length of run for the motor circuit of {Example 4.4}.

This time we have a mineral insulated p.v.c. sheathed cable, so volt drop figures will
come from {Table 4.9}. This shows 9.1 mV/A/m for the 4 mm² cable selected, which must
be used with the circuit current of 15.3 A and the length of run which is 20 m.

Volt drop = 9.1 x 15.3 x 20 V = 2.78 V


1000

Maximum permissible volt drop is 4% of 415 V = 4 of 415V = 16.6 V


100

Maximum length of run for this circuit 16.6 x 20m = 119m


with the same cable size and type will be: 2.78

The 'length of run' calculations carried out in these examples are often useful to the
electrician when installing equipment at greater distances from the mains position.
It is important to appreciate that the allowable volt drop of 4% of the supply voltage
applies to the whole of an installation. If an installation has mains, sub-mains and final
circuits, for instance, the volt drop in each must be calculated and added to give the total
volt drop as indicated in {Fig 4.10}.

All of our work in this sub-section so far has assumed that cable resistance is the only
factor responsible for volt drop. In fact, larger cables have significant self inductance as
well as resistance. As we shall see in Chapter 5 there is also an effect called impedance
which is made up of resistance and inductive reactance (see {Fig 5.8(a)}).

Inductive reactance XL = 2(pi)fL


where XL = inductive reactance in Ωohms
(pi) = the mathematical constant 3.142
f = the system frequency in hertz (Hz)
L = circuit self inductance in henrys (H)

It is clear that inductive reactance increases with frequency, and for this reason the volt
drop tables apply only to systems with a frequency lying between 49 Hz and 61 Hz.

Fig 4.10 Total volt drop in large installations

For small cables, the self inductance is such that the inductive reactance, is small
compared with the resistance. Only with cables of cross-sectional area 25 mm² and
greater need reactance be considered. Since cables as large as this are seldom used on
work which has not been designed by a qualified engineer, the subject of reactive volt
drop component will not be further considered here.

If the actual current carried by the cable (the design current) is less than the rated
value, the cable will not become as warm as the calculations used to produce the volt
drop tables have assumed, The Regulations include (in [Appendix 4]) a very complicated
formula to be applied to cables of cross-sectional area 16 mm² and less which may show
that the actual volt drop is less than that obtained from the tables. This possibility is again
seldom of interest to the electrician, and is not considered here.

4.3.12 - Harmonic currents and neutral conductors

A perfectly balanced three-phase system (one with all three phase loads identical in all
respects) has no neutral current and thus has no need of a neutral conductor. This is often
so with motors, which are fed through three core cables in most cases.

Many three-phase loads are made up of single-phase loads, each connected between one
line and neutral. It is not likely in such cases that the loads will be identical, so the neutral
will carry the out-of-balance current of the system. The greater the degree of imbalance,
the larger the neutral current.

Some three-phase four-core cables have a neutral of reduced cross-section on the


assumption that there will be some degree of balance. Such a cable must not he used
unless the installer is certain that severe out-of-balance conditions will never occur.
Similar action must be taken with a three-phase circuit wired in single-core cables. A
reduced neutral conductor may only be used where out-of-balance currents will be very
small compared to the line currents.

A problem is likely to occur in systems which generate significant third harmonic


currents. Devices such as discharge lamp ballasts and transformers on low load distort the
current waveform. Thus, currents at three times normal frequency (third harmonics) are
produced, which do not cancel at the star point of a three-phase system as do normal
frequency currents, but add up, so that the neutral carries very heavy third harmonic
currents. For this reason, it is important not to reduce the cross-sectional area of a neutral
used to feed discharge lamps (including fluorescent lamps).

In some cases the neutral current may be considerably larger than the phase currents.
Where the load concerned is fed through a multi-core cable, it may be prudent to use
five-core (or even six-core) cables, so that two (or three) conductors may be used in
parallel for the neutral.

In some cases it may be necessary to insert overload protection in a neutral conductor.


Such protection must be arranged to open all phase conductors on operation, but not the
neutral. This clearly indicates the use of a special circuit breaker.

It is very important that the neutral of each circuit is kept quite separate from those of
other circuits. Good practice suggests that the separate circuit neutrals should be
connected in the same order at the neutral block as the corresponding phase conductors at
the fuses or circuit breakers.
4.3.13 - Low smoke-emitting cables

Normal p.v.c. insulation emits dense smoke and corrosive gases when burning. If cables
are to be run in areas of public access, such as schools, supermarkets, hospitals, etc, the
designer should consider the use of special cables such as those with thermo-setting or
elastomeric insulation which do not cause such problems in the event of fire. This action
is most likely to be necessary in areas expected to be crowded, along fire escape routes,
and where equipment is likely to suffer damage due to corrosive fumes.

4.3.14 - The effects of animals, insects and plants

Cables may be subject to damage by animals and plants as well as from their
environment. Rodents in particular seem to have a particular taste for some types of cable
sheathing and can gnaw through sheath and insulation to expose the conductors. Cables
impregnated with repellent chemicals are not often effective and may also fall foul of the
Health and Safety Regulations. Rodents build nests, often of flammable materials,
leading to a fire hazard. Care should be taken to avoid cable installation along possible
vermin runs, but where this cannot be avoided, steel conduit may be the answer.

Mechanical damage to wiring systems by larger animals such as cattle and horses can
often be prevented by careful siting of cable runs and outlets. Attention must also be
given to the fact that waste products from animals may be corrosive. Access by insects is
difficult to prevent, but vent holes can be sealed with breathers. Damage by plants is a
possible hazard, the effect of tree roots on small lighting columns being an obvious
problem area.

4.4.1 Cable supports and protection

Cables must be fixed securely at intervals which are close enough to ensure that there
will be no excessive strain on the cable or on its joints and terminations, and to prevent
cable loops appearing which could lead to mechanical damage. {Table 4.10} indicates
minimum acceptable spacings of fixings for some common types of cables.

Table 4.10 Maximum spacing for cable supports

Overall cable p.v.c. sheathed Mineral insulated

diameter Horizontal Vertical Horizontal Vertical

(mm) (mm) (mm) (mm) (mm)

up to 9 250 400 600 800

10 to 15 300 400 900 1200

16 to 20 350 450 1500 2000

21 to 40 400 550 2000 3000


Where cable runs are neither vertical nor horizontal, the spacing depends on the angle as
shown in {Fig 4.11}.

Where a cable is flat in cross-section as in the case of a p.v.c. insulated and sheathed
type, the overall diameter is taken as the major axis as shown in {Fig 4.12}.

Fig 4.11 Spacing of support clips on angled runs

Fig 4.12 Effective diameter of a flat cable

The Regulations are concerned to protect hidden cables from damage. Thus, where cables
are run beneath boarded floors, they must pass through holes drilled in the joists which
are at least 50 mm below the top surface of the joist. This is to prevent accidental damage
due to nails being driven into the joists. The hole diameters must not exceed one quarter
of the depth of the joist and they must be drilled at the joist centre (the neutral axis). Hole
centres must be at least three diameters apart, and the holes must only be drilled in a zone
which extends 25% to 40% of the beam length from both ends.

An alternative is to protect the cable in steel conduit. It is not practicable to thread rigid
conduit through holes in the joists, so the steel conduit may be laid in slots cut in the
upper or lower edges as shown in {Fig 4.13}. The depth of the slot must be no greater
than one eighth of the joist depth and notches must be in a zone extending from 10% to
25% of the beam length from both ends.

Fig 4.13 Support and protection for cables run under floors

Where cable runs are concealed behind plaster they must he installed in 'acceptable zones'
which are intended to reduce the danger to the cables and to people who drill holes or
knock nails into walls. Cable runs must only follow paths which are horizontal or vertical
from an outlet, or be within 150 mm of the top (but not the bottom) of the wall, or within
150 mm of the angle formed by two adjoining {Fig 4.14} Acceptable installation zones
for concealed cables. The diagonal cable must be enclosed in earthed metal walls. Where
a cable run has to be diagonal, it must be protected by being enclosed in steel conduit, or
must be a cable with an earthed metal sheath (such as mineral insulated cable), or an
insulated concentric cable. In this latter case, the phase conductor will be surrounded by
the neutral, so that if a nail or a screw penetrates the cable it will be impossible for it to
become live. The possible zones are shown in (Fig 4.14). The internal partition walls of
some modern buildings are very thin, and where cables complying with the requirements
above are within 50 mm of the surface on the other side, they will require protection.
Fig 4.14 Acceptable installation zones for concealed cables. The diagonal cable must
be enclosed in earthed metal.

There are cases where cables are enclosed in long vertical runs of trunking or conduit.
The weight of the cable run, which effectively is hanging onto the top support, can easily
cause damage by compressing the insulation where it is pulled against the support. In
trunking there must be effective supports no more than 5 m apart, examples of which are
shown in Fig 4.15, whilst for conduit the run must be provided with adaptable boxes at
similar intervals which can accommodate the necessary supports.
Fig 4.15 Support for vertical cables in trunking

The top of a vertical conduit or trunking run must have a rounded support to reduce
compression of insulation. The diameters required will be the same as those for cable
bends given in {4.4.2}.

Support for overhead conductors is considered in {7.13}

4.4.2 - Cable bends

If an insulated cable is bent too sharply, the insulation and sheath on the inside of the
bend will be compressed, whilst that on the outside will be stretched, This can result in
damage to the cable as shown in {Fig 4.16}.
The bending factor must be used to assess the minimum acceptable bending radius,
values for common cables being given in {Table 4.11}.
Fig 4.16 Damage to cable insulation due to bending

Type of insulation Overall diameter Bending factor

p.v.c. Up to 10mm 3 (2)

p.v.c. 10mm to 25mm 4 (3)

p.v.c. Over 25mm 6

mineral any 6*

The figures in brackets apply to unsheathed single-core stranded p.v.c.


cables when installed in conduit, trunking or ducting.

* Mineral insulated cables may be bent at a minimum radius of three cable


diameter provided that they will only be bent once. This is because the
copper sheath will ‘work harden’ when bent and is likely to crack if
straightened and bent again.

Table 4.11 Bending factors for common cables

The figures in brackets apply to unsheathed single-core stranded p.v.c. cables when
installed in conduit, trunking or ducting.

* Mineral insulated cables may be bent at a minimum radius of three cable diameter
provided that they will only be bent once. This is because the copper sheath will ‘work
harden’ when bent and is likely to crack if straightened and bent again.

The factor shown in the table is that by which the overall cable diameter {Fig 4.12}
must be multiplied to give the minimum inside radius of the bend. For example,
2.5 mm² twin with protective conductor sheathed cable has a cross-section 9.7 mm
x 5.4 mm. Since the Table shows a factor of 3 for this size, the minimum inside
radius of any bend must be 3 x 9.7 = 29.1 mm.
4.4.3 - Joints and terminations

The normal installation has many joints, and it follows that these must all remain safe and
effective throughout the life of the system. With this in mind, regulations on joints
include the following:

1. -All joints must be durable, adequate for their purpose, and mechanically strong.

2. -They must be constructed to take account of the conductor material and


insulation, as well as temperature: eg, a soldered joint must not be used where the
temperature may cause the solder to melt or to weaken. Very large expansion forces are
not uncommon in terminal boxes situated at the end of straight runs of large cables when
subjected to overload or to fault currents.

3. - All joints and connections must be made in an enclosure complying with the
appropriate British Standard.

4. - Where sheathed cables are used, the sheath must be continuous into the joint
enclosure {Figure 4.17}.

5. -All joints must be accessible for inspection and testing unless they are buried in
compound or encapsulated, are between the cold tail and element of a heater such as a
pipe tracer or underfloor heating system, or are made by soldering, welding, brazing or
compression.

Fig 4.17 Failure to enclose non-sheathed cables

4.5.1 - Plastic and metal conduits

4.5.2 - Ducting and trunking

4.5.3 - Cable capacity of conduits and trunking

4.5.1 - Plastic and metal conduits


A system of conduits into which unsheathed cables can be drawn has long been a
standard method for electrical installations. The Regulations applying to conduit systems
may be summarised as follows:

1. - All conduits and fittings must comply with the relevant British Standards.

2. -Plastic conduits must not be used where the ambient temperature or the
temperature of the enclosed cables will exceed 60°C. Cables with thermo-setting
insulation are permitted to run very hot, and must be suitably down-rated when installed
in plastic conduit. To prevent the spread of fire, plastic conduits (and plastic trunking)
must comply with ignitability characteristic 'P' of ES 476 Part 5.

3. -Conduit systems must be designed and erected so as to exclude moisture, dust


and dirt. This means that they must be completely closed, with box lids fitted. To ensure
that condensed moisture does not accumulate, small drainage holes must be provided at
the lowest parts of the system.

4. - Proper precautions must be taken against the effects of corrosion (see {4.2.5}), as well
as against the effects of flora (plant growths) and fauna (animals). Protection from rusting
of steel conduit involves the use of galvanised (zinc coated) tubing, and against
electrolytic corrosion the prevention of contact between dissimilar metals eg steel and
aluminium. Any additional protective conductor must be run inside the conduit or its
reactance is likely to be so high that it becomes useless if intended to reduce fault loop
impedance.

5. - A conduit system must be completely erected before cables are drawn in. It must be
free of burrs or other defects which could damage cables whilst being inserted.

6. - The bends in the system must be such that the cables drawn in will comply with the
minimum bending radius requirements {4.4.2}.

7. - The conduit must be installed so that fire cannot spread through it, or through holes cut in
floors or walls to allow it to pass. This subject of fire spread will be considered in greater detail in
{4.5.2}

8. - Allowance must be made, in the form of expansion loops, for the thermal expansion
of long runs of metal or plastic conduit. Remember that plastic expands and contracts
more than steel.

9. - Use flexible joints when crossing building expansion joints

Table 4.12 - Maximum spacing of supports for conduits

Conduit diameter Rigid metal (m) Rigid insulating (m)

(mm) Horizontal Vertical Horizontal Vertical


Up to 16 0.75 1.0 0.75 1.0

16 to 25 1.75 2.0 1.5 1.75

25 to 40 2.0 2.25 1.75 2.0

Over 40 2.25 2.5 2.0 2.0

4.5.2 - Ducting and trunking

Metal and plastic trunkings are very widely used in electrical installations. They must be
manufactured to comply with the relevant British Standards, and must be installed so as
to ensure that they will not be damaged by water or by corrosion (see {4.2.5}).

Table 4.13 Support spacings for trunking

Typical trunking size Metal Insulating

(mm) Horizontal Vertical Horizontal Vertical

Up to 25 x 25 0.75 1.0 0.5 0.5

Up to 50 x 25 1.25 1.5 0.5 0.5

Up to 50 x 50 1.75 2.0 1.25 1.25

Up to 100 x 50 3.0 3.0 1.75 2.0

If it is considered necessary to provide an additional protective conductor in parallel with


steel trunking, it must be run inside the trunking or the presence of steel between the live
and protective cables will often result in the reactance of the protective cable being so
high that it will have little effect on fault loop impedance. Trunking must be supported as
indicated in {Table 4.13}. The table does not apply to special lighting trunking which is
provided with strengthened couplers. Where crossing a building expansion joint a
suitable flexible joint should be included.

Where trunking or conduit passes through walls or floors the hole cut must be made good
after the first fix on the construction site to give the partition the same degree of fire
protection it had before the hole was cut. Since it is possible for fire to spread through the
interior of the trunking or conduit, fire barriers must be inserted as shown in {Fig 4.18}.
An exception is conduit or trunking with a cross-sectional area of less than 710 mm², so
that conduits up to 32 mm in diameter and trunking up to 25 mm x 25 mm need not be
provided with fire barriers. During installation, temporary fire barriers must be provided
so that the integrity of the fire prevention system is always maintained.
Fig 4.18 Provision of fire barriers in ducts and trunking

Since trunking will not be solidly packed with cables (see {4.5.3}) there will be room for
air movement. A very long vertical trunking run may thus become extremely hot at the
top as air heated by the cables rises; this must be prevented by barriers as shown in {Fig
4.19}. In many cases the trunking will pass through floors as it rises, and the fire stop
barriers needed will also act as barriers to rising hot air.

Lighting trunking is being used to a greater extent than previously In many cases, it
includes copper conducting bars so that luminaires can be plugged in at any point,
especially useful for display lighting.

The considerably improved life, efficiency and colour rendering properties of extra-low
voltage tungsten halogen lamps has led to their increasing use, often fed by lighting
trunking. It is important here to remember that whilst the voltage of a 12 V lamp is only
one twentieth of normal mains potential, the current for the same power inputs will be
twenty times greater. Thus, a trunking feeding six 50 W 12 V lamps will need to he rated
at 25 A.
Fig 4.19 Heat barriers provided in vertical cable ways

4.5.3 - Cable capacity of conduits and trunking

Not oflly must it be possible to draw cables into completed conduit and trunking systems,
but neither the cables nor their enclosures must be damaged in the process. If too many
cables are packed into the space available, there will be a greater increase in temperature
during operation than if they were given more space. It is important to appreciate that
grouping factors (see {4.3.5}) still apply to cables enclosed in conduit or trunking.

To calculate the number of cables which may be drawn into a conduit or trunkmg, we
make use of four tables ({Tables 4.14 to 4.17}). For situations not covered by these tables,
the requirement is that a space factor of 45% must not be exceeded. This means that not
more than 45% of the space within the conduit or trunkmg must be occupied by cables,
and involves calculating the cross-sectional area of each cable, including its insulation,
for which the outside diameter must be known. The cable factors for cables with
thermosetting insulation are higher than those for pvc insulation when the cables are
installed in trunking, but the two are the same when drawn into conduit (see {Table 4.14})
Fig 4.20 Low voltage luminaire on lighting trunking

The figures in {Table 4.14} may be high when applied to some types of plastic trunking
due to the large size of the internal lid fixing clips.

To use the ({Tables 4.14 to 4.17}). the cable factors for all the conductors must be added.
The conduit or trunking selected must have a factor (otherwise called 'term') at least as
large as this number,

Example 4.9
The following single-core p.v.c. insulated cables are to be run in a conduit 6 m long with
a double set: 8 x 1,4 x 2.5 and 2 x 6 mm². Choose a suitable size.

Table 4.14 - Cable factors (terms) for conduit and trunking

Factor Factor for Factor for trunking


Type of Conductor
for trunking pvc thermosetting
conductor c.s.a. (mm²)
conduit insulation insulation

Solid 1.0 16 3.6 3.8

Solid 1.5 22 8.0 8.6

Stranded 1.5 22 8.6 9.1

Solid 2.5 30 11.9 11.9

Stranded 2.5 30 12.6 13.9

Stranded 4.0 43 16.6 18.1

Stranded 6.0 58 21.2 22.9


Stranded 10.0 105 35.3 36.3

Stranded 16.0 145 47.8 50.3

Stranded 25.0 217 73.9 75.4

Table 4.15 - Cable factors (terms) for straight runs up to 3m.

Type of conductor Conductor c.s.a. (mm²) Cable factor

Solid 1.0 22

Solid 1.5 27

Solid 2.5 39

Stranded 1.5 31

Stranded 2.5 43

Stranded 4.0 58

Stranded 6.0 88

Stranded 10.0 146

Table 4.16 - Conduit factors (terms)

Length of run between boxes (m)

1 2 3 4 5 6 8 10

Conduit, straight -

16mm 290 290 290 171 171 167 158 150

20mm 460 460 460 286 278 270 256 244

25mm 800 800 800 514 500 487 463 442

32mm 1400 1400 1400 900 878 857 818 783

Conduit, one bend -

16mm 188 177 167 158 150 143 130 120

20mm 303 286 270 256 244 233 213 196

25mm 543 514 487 463 442 422 388 258


32mm 947 900 857 818 783 750 692 643

Conduit, two bends -

16mm 177 158 143 130 120 111 97 86

20mm 286 256 233 213 196 182 159 141

25mm 514 463 422 388 358 333 292 260

32mm 900 818 750 692 643 600 529 474

For 38mm conduit use the 32mm factor x 1.4.


For 50mm conduit use the 32mm factor x 2.6.
For 63mm conduit use the 32mm factor x 4.2.

Table 4.17 Trunking factors (terms)

Dimensions of trunking (mm x mm) Factor

37.5 x 50 767

50 x 50 1037

25 x 75 738

37.5 x 75 1146

50 x 75 1555

75 x 75 2371

25 x 100 993

37.5 x 100 1542

50 x 100 2091

75 x 100 3189

100 x 100 4252

Consulting {Table 4.14} gives the following cable factors:

16 for 1 mm², 30 for 2.5 mm² and 58 for 6 mm²

Total cable factor is then (8 x 16) + (4 x 30) + (2 x 58)

= 128 + 120 + 116 = 364

The terrn "bend" means a right angle bend or a double set.


{Table 4.16} gives a conduit factor for 20 mm conduit 6 m long with a double set
as 233, which is less than 364 and thus too small. The next size has a conduit factor of
422 which will be acceptable since it is larger than 364.

The correct conduit size is 25 mm diameter.

Example 4.10
The first conduit from a distribution board will be straight and 10 m long. It is to enclose
4 x 10 mm² and 8 x 4 mm² cables. Calculate a suitable size.

From {Table 4.14}, cable factors are 105 and 43 respectively. Total cable factor:

=(4 x 105) + (8 x 43) = 420 + 344 = 764

From ({Table 4.15}, a 10 m long straight 25 mm conduit has a factor of 442. This is too
small, so the next size, with a factor of 783 must be used.

The correct conduit size is 32 mm diameter.

Example 4.11
A 1.5 m straight length of conduit from a consumer's unit encloses ten 1.5 mm² and four
2.5 mm² solid conductor p.v.c. insulated cables. Calculate a suitable con duit size.

From ({Table 4.15} (which is for short straight runs of conduit) total cable factor will be:

= (10 x 27) + (4 x 39) = 426

Table 4.16 shows that 20 mm diameter conduit with a factor of 460 will be necessary.

Example 4.12
A length of trunking is to carry eighteen 10 mm², sixteen 6 mm², twelve 4 mm², and ten
2.5 mm² stranded single p.v.c. insulated cables. Calculate a suitable trunking size.

The total cable factor for trunking is calculated with data from {Table 4.14}.

18 x 10mm² at 36.3 = 18 x 36.3 = 653.4

16 x 6mm² at 22.9 = 16 x 22.9 = 366.4

12 x 4mm² at 15.2 = 12 x 15.2 = 182.4

10 x 2.5mm² at 11.4 = l0 x ll.4 = 114.0

- Total cable factor = 1316.2

From the trunking factor {Table 4.17}, two standard trunking sizes have factors slightly
greater than the cable factor, and either could be used .
They are 50 mm x 75 mm at 1555, and 37.5 mm x 100 mm at 1542.
4.6.1 - Conduits

4.6.2 - Identification of fixed wiring conductors

4.6.3 - Colours for flexible cables and cords

4.6.1 - Conduits

The 'electrical' colour to distinguish conduits from pipelines of other services is orange
(BS 1710). Oversheaths for mineral insulated cables are often the same colour, which is
also used to identify trunking and switchgear enclosures.

4.6.2 - Identification of fixed wiring conductors

Colour is used to identify the conductors of a wiring system where it is possible to colour
the insulation. Where it is not, numbers are used. The requirements for identification of
fixed wiring are shown in {Fig 4.21}. There is as yet no requirement to use brown and
blue to identify the phase and neutral conductors of fixed wiring, although this applies to
flexible cords and cables (see {4.6.3}. The colour green on its own is prohibited, although
green and yellow stripes identify the protective conductor. The functional earth conductor
for telecommunication circuits is identified by the colour cream.
Fig 4.21 Identification of fixed wiring

Some cables comply with HD 324:1977 and have blue insulation on the neutral
conductor. This colour does not comply with BS 7671 and if such cables are used, they
must be correctly identified at their terminations by the use of black cable markers or
black tape.

4.6.3 -Colours for flexible cables and cords

Unlike the cores of fixed cables, which may be identified by sleeves or tapes where they
are connected, flexibles must be identified throughout their length. The colour
requirements are shown in {Fig 4.22}.
Fig 4.22 Care colours for flexible cables and cords

Chapter 5 : Earthing

5.1 - The earthing principle 5.6 - Protective multiple earthing (PME)


5.7 -
Earthed
5.2 - Earthing Systems
concentric
wiring
5.8 - Other
5.3 - Earth fault loop impedance protection
methods
5.9 -
Residual
5.4 - Protective conductors current
devices
(RCDs)
5.10 -
Combined
5.5 - Earth electrodes functional
and
protective
---------
earthing

5.1.1 - What is earthing?

5.1.2 - The advantages of earthing

5.1.3 - The disadvantages of earthing


5.1.1 - What is earthing?

The whole of the world may be considered as a vast conductor which is at reference
(zero) potential. In the UK we refer to this as 'earth' whilst in the USA it is called
'ground'. People are usually more or less in contact with earth, so if other parts which are
open to touch become charged at a different voltage from earth a shock hazard exists (see
{3.4}). The process of earthing is to connect all these parts which could become charged to
the general mass of earth, to provide a path for fault currents and to hold the parts as
close as possible to earth potential. In simple theory this will prevent a potential
difference between earth and earthed parts, as well as permitting the flow of fault current
which will cause the operation of the protective systems.

The standard method of tying the electrical supply system to earth is to make a direct
connection between the two. This is usually carried out at the supply transformer, where
the neutral conductor (often the star point of a three-phase supply) is connected to earth
using an earth electrode or the metal sheath and armouring of a buried cable. {Figure 5.1}
shows such a connection. Lightning conductor systems must be bonded to the installation
earth with a conductor no larger in cross-sectional area than that of the earthing
conductor.

Fig 5.1 - Three-phase delta/star transformer


showing earthing arrangements
5.1.2 - The advantages of earthing

The practice of earthing is widespread, but not all countries in the world use it.

There is certainly a high cost involved, so there must be some advantages. In fact
there are two. They are:

1. - The whole electrical system is tied to the potential of the general mass of earth and
cannot 'float' at another potential. For example, we can be fairly certain that the neutral of
our supply is at, or near, zero volts (earth potential) and that the phase conductors of our
standard supply differ from earth by 240 volts.

2. - By connecting earth to metalwork not intended to carry current (an extraneous


conductive part or a an exposed conductive part) by using a protective conductor, a path
is provided for fault current which can be detected and, if necessary, broken. The path for
this fault current is shown in {Fig 5.2}.

Fig 5.2 Path for earth fault current (shown by arrows)

5.1.3 - The disadvantages of earthing

The two important disadvantages are:

1. - Cost: the provision of a complete system of protective conductors, earth electrodes,


etc. is very expensive.

2. - Possible safety hazard: It has been argued that complete isolation from earth will
prevent shock due to indirect contact because there is no path for the shock current to
return to the circuit if the supply earth connection is not made (see {Fig 5.3(a)}). This
approach, however, ignores the presence of earth leakage resistance (due to imperfect
insulation) and phase-to-earth capacitance (the insulation behaves as a
dielectric). In many situations the combined impedance due to insulation resistance and
earth capacitive reactance is low enough to allow a significant shock current
(see {Fig 5.3(b)}).

Fig 5.3 - Danger in an unearthed system

a) apparent safety: no obvious path for shock current


b) actual danger: shock current via stray resistance and capacitance

5.2.1 -System classification

5.2.2 - TT systems

5.2.3 - TN-S system

5.2.4 - TN-C-S system

5.2.5 - TN-C system

5.2.6 - IT system

5.2.1 -System classification

The electrical installation does not exist on its own; the supply is part of the overall
system. Although Electricity Supply Companies will often provide an earth terminal, they
are under no legal obligation to do so. As far as earthing types are concerned, letter
classifications are used.

The first letter indicates the type of supply earthing.


T -indicates that one or more points of the Supply are directly earthed (for
example, the earthed neutral at the transformer).
I -indicates either that the supply system is not earthed at all, or that the earthing
includes a deliberately-inserted impedance, the purpose of which is to limit fault current.
This method is not used for public supplies in the UK.

The second letter indicates the earthing arrangement in the installation.


T - all exposed conductive metalwork is connected directly to earth.
N - all exposed conductive metalwork is connected directly to an earthed supply
conductor provided by the Electricity Supply Company.

The third and fourth letters indicate the arrangement of the earthed supply conductor
system.
S - neutral and earth conductor systems are quite separate.
C - neutral and earth are combined into a single conductor.

A number of possible combinations of earthing systems in common use is indicated in the


following subsections.

Protective conductor systems against lightning need to be connected to the installation


earthing system to prevent dangerous potential differences. Where a functional earthing
system is in use, the protective requirements of the earthing will take precedence over the
functional requirements.

5.2.2 - TT systems

This arrangement covers installations not provided with an earth terminal by the
Electricity Supply Company. Thus it is the method employed by most (usually rural)
installations fed by an overhead supply. Neutral and earth (protective) conductors must
be kept quite separate throughout the installation, with the final earth terminal connected
to an earth electrode (see {5.5}) by means of an earthing conductor.

Effective earth connection is sometimes difficult. Because of this, socket outlet circuits
must be protected by a residual current device (RCD) with an operating current of 30 mA
{5.9}. {Fig 5.4} shows the arrangement of a TT earthing system.

Fig 5.4 - TT earthing system


5.2.3 - TN-S system

This is probably the most usual earthing system in the UK, with the Electricity Supply
Company providing an earth terminal at the incoming mains position. This earth terminal
is connected by the supply protective conductor (PE) back to the star point (neutral) of
the secondary winding of the supply transformer, which is also connected at that point to
an earth electrode. The earth conductor usually takes the form of the armour and sheath
(if applicable) of the underground supply cable. The system is shown diagrammatically in
{Fig 5.5}.

Fig 5.5 - TN-S earthing system

5.2.4 - TN-C-S system

In this system, the installation is TN-S, with separate neutral and protective conductors.
The supply, however, uses a common conductor for both the neutral and the earth. This
combined earth and neutral system is sometimes called the 'protective and neutral
conductor' (PEN) or the 'combined neutral and earth' conductor (CNE). The system,
which is shown diagrammatically in {Fig 5.6}, is most usually called the protective
multiple earth (PME) system, which will be considered in greater detail in {5.6}.

Fig 5.6 - TN-C-S earthing system - protective multiple earthing

5.2.5 -TN-C system


This installation is unusual, because combined neutral and earth wiring is used in both the
supply and within the installation itself. Where used, the installation will usually be the
earthed concentric system, which can only be installed under the special conditions listed
in {5.7}.

5.2.6 - IT system

The installation arrangements in the IT system are the same for those of the TT system
{5.2.2}. However, the supply earthing is totally different. The IT system can have an
unearthed supply, or one which is not solidly earthed but is connected to earth through a
current limiting impedance.

The total lack of earth in some cases, or the introduction of current limiting into the earth
path, means that the usual methods of protection will not be effective. For this reason, IT
systems are not allowed in the public supply system in the UK. An exception is in
medical situations such as hospitals. Here it is recommended that an IT system is used for
circuits supplying medical equipment that is intended to be used for life-support of
patients. The method is also sometimes used where a supply for special purposes is taken
from a private generator.

5.3.1 - Principle

5.3.2 - The importance of loop impedance

5.3.3 - The resistance/impedance relationship

5.3.4 - Earth-fault loop impedance values

5.3.5 - Protective conductor impedance

5.3.6 - Maximum circuit conductor length

5.3.1 - Principle

The path followed by fault current as the result of a low impedance occurring between
the phase conductor and earthed metal is called the earth fault loop. Current is driven
through the loop impedance by the supply voltage.

The extent of the earth fault loop for a TT system is shown in {Fig 5.7}, and is made up
of the following labelled parts.
Fig 5.7 The earth fault loop

l. - the phase conductor from the transformer to the installation

2 . -the protective device(s) in the installation

3 . -the installation phase conductors from the intake position


to the fault

4. - the fault itself (usually assumed to have zero impedance)

5. - the protective conductor system

6. - the main earthing terminal

7. - the earthing conductor

8. - the installation earth electrode

9. - the general mass of earth

10. - the Supply Company's earth electrode

11. - the Supply Company's earthing conductor

12 . -the secondary winding of the supply transformer


For a TN-S system (where the Electricity Supply Company provides an earth terminal),
items 8 to 10 are replaced by the PE conductor, which usually takes the form of the
armouring (and sheath if there is one) of the underground supply cable.

For a TN-C-S system (protective multiple earthing) items 8 to 11 are replaced by the
combined neutral and earth conductor.

For a TN-C system (earthed concentric wiring), items 5 to 11 are replaced by the
combined neutral and earth wiring of both the installation and of the supply.

It is readily apparent that the impedance of the loop will probably be a good deal higher
for the TT system, where the loop includes the resistance of two earth electrodes as well
as an earth path, than for the other methods where the complete loop consists of metallic
conductors.

5.3.2 - The importance of loop impedance

The earth fault loop impedance can be used with the supply voltage to calculate the earth-
fault current.

IF = Uo
Zs
where IF = fault current, A
Uo = phase voltage, V
Zs = loop impedance

For example, if a 240 V circuit is protected by a 15 A semi-enclosed fuse and has an


earth-fault loop impedance of 1.6 Ohms, the earth-fault current in the event of a zero
impedance earth fault will he:

IF
Uo 240
= 150 A
= A
=
Zs 1.6

This level of earth-fault current will cause the fuse to operate quickly. From {Fig 3.13} the
time taken for the fuse to operate will be about 0.15 s. Any load current in the circuit will
be additional to the fault current and will cause the fuse to operate slightly more quickly.
However, such load current must not be taken into account when deciding disconnection
time, because it is possible that the load may not be connected when the fault occurs.

Note that there is no such thing as a three-phase line/earth fault, although it is possible for
three faults to occur on the three lines to earth simultaneously. As far as calculations for
fault current are concerned, the voltage to earth for standard UK supplies is always 240
V, for both single-phase and three-phase systems. Thus the Tables of maximum earth-
fault loop impedance which will be given in {5.3.4} apply both to single- and to three-
phase systems.
5.3.3 - The resistance/impedance relationship

Resistance, measured in ohms, is the property of a conductor to limit the flow of current
through it when a voltage is applied.

I= U
R
where I = current, A
U
applied voltage. V
=
R circuit resistance,
= Ohms

Thus, a voltage of one volt applied to a one ohm resistance results in a current of one
ampere.

When the supply voltage is alternating, a second effect, known as reactance (symbol X) is
to be considered. It applies only when the circuit includes inductance and/or capacitance,
and its value, measured in ohms, depends on the frequency of the supply as well as on the
values of the inductance and/or the capacitance concerned. For almost all installation
work the frequency is constant at 50 Hz. Thus, inductive reactance is directly
proportional to inductance and capacitive reactance is inversely proportional to
capacitance.

Xl = 2(pi)fL and Xc = 1
2(pi)fC
Xl
where inductive reactance (Ohms)
=
Xc = capacitive reactance (Ohms)
(pi) = the mathematical constant (3.142)
f = the supply frequency (Hz)
L = circuit inductance (H)
C = circuit capacitance (F)

Resistance (R) and reactance (Xl or Xc) in series add together to produce the circuit
impedance (symbol z), but not in a simple arithmetic manner. Impedance is the effect
which limits alternating current in a circuit containing reactance as well as resistance.

Z =U
I
where Z = impedance (Ohms)
U = applied voltage (V)
I = current (A)

It follows that a one volt supply connected across a one ohm impedance results in a
current of one ampere.
When resistance and reactance are added this is done as if they were at right angles,
because the current in a purely reactive circuit is 90° out of phase with that in a purely
resistive circuit. The relationships between resistance, reactance and impedance are:

a) resistive and capacitive circuit - b) resistive and inductive circuit


Fig 5.8 Impedance diagrams

These relationships can be shown in the form of a diagram applying Pythagoras' theorem
as shown in {Fig 5.8}. The two diagrams are needed because current lags voltage in the
inductive circuit, but leads it in the capacitive. The angle between the resistance R and
the impedance Z is called the circuit phase angle, given the symbol a (Greek 'phi'). If
voltage and current are both sinusoidal, the cosine of this angle, cos a, is the circuit power
factor, which is said to be lagging for the inductive circuit, and leading for the capacitive.

In practice, all circuits have some inductance and some capacitance associated with them.
However, the inductance of cables only becomes significant when they have a cross-
sectional area of 25 mm² and greater. Remember that the higher the earth fault loop
impedance the smaller the fault current will be. Thus, if simple arithmetic is used to add
resistance and reactance, and the resulting impedance is low enough to open the
protective device quickly enough, the circuit will be safe. This is because the
Pythagorean addition will always give lower values of impedance than simple addition.

For example, if resistance is 2 Ohms and reactance 1 Ohm, simple arithmetic addition
gives

Z = R + X – 2 + 1 = 3 Ohms
and correct addition gives
Z = √(R² + X²)
= √(2² + 1²) = √ 5 = 2.24 Ohms
If 3 Ohms is acceptable, 2.24 Ohms will allow a larger fault current to flow which will
operate the protective device more quickly and is thus even more acceptable.

5.3.4 - Earth-fault loop impedance values

The over-riding requirement is that sufficient fault current must flow in the event of an
earth fault to ensure that the protective device cuts off the supply before dangerous shock
can occur. For normal 240 V systems, there are two levels of maximum disconnection
time. These are:

For socket outlet circuits where equipment could be tightly grasped: 0.4 s

For fixed equipment where contact is unlikely to be so good: 5 s

The maximum disconnection time of 5 s also applies to feeders and sub-mains.

It must be appreciated that the longest disconnection times for protective devices, leading
to the longest shock times and the greatest danger, will be associated with the lowest
levels of fault current, and not, as is commonly believed, the highest levels.

Where the voltage is other than 240 V, [Table 41A] gives a range of disconnection times
for socket outlet circuits, of which the lowest is 0.1 s for voltages exceeding 400 V.

In general, the requirement is that if a fault of negligible impedance occurs between a


phase and earth, the earth-fault loop impedance must not be greater than the value
calculated from..

Zs < Uo
Ia

where Zs = the earth fault loop impedance (Ohms)


Uo = the system voltage to earth(V)
Ia = the current causing automatic disconnection
(operation of the protective device) in the required time [A]).

The earth fault loop values shown in [Tables 5.1, 5.2 and 5.4] depend on the supply voltage
and assume, as shown in the Tables, a value of 240 V. Whilst it would appear that 240 V
is likely to be the value of the supply voltage in Great Britain for the foreseeable future, it
is not impossible that different values may apply. In such a case, the tabulated value for
earth fault loop impedance should be modified using the formula:-

Zs = Zt x U
U240

where Zs = is the earth fault loop impedance required for safety


Zt = is the tabulated value of earth fault loop impedance
U = is the actual supply voltage
U240 = is the supply voltage assumed in the Table.

As an alternative to this calculation, a whole series of maximum values of earth fault loop
impedance is given in {Table 5.1} (from [Table 41B]) for disconnection within 0.4 s. The
reader should not think that these values are produced in some mysterious way - all are
easily verified using the characteristic curves {Figs 3.13 to 3.19}.

For example, consider a 20 A HRC fuse to BS88 used in a 240 V system. The fuse
characteristic is shown in {Fig 3.15}, and indicates that disconnection in 0.4 s requires a
current of about 130 A. It is difficult (if not impossible) to be precise about this value of
current, because it is between the 100 A and 150 A current graduations.

Using these values,


Zs
Uo = 240 Ohms = 1.84 Ohms
=
Ia 130

Reference to {Table 5.1} shows that the stated value is 1.8 Oh,s, the discrepancy being due
to the difficulty in reading the current with accuracy. {Tables 5.1 and 5.2} give maximum
earth-fault loop impedance values for fuses and for miniature circuit breakers to give a
minimum disconnection time of 0.4 s in the event of a zero impedance fault from phase
to earth.

The reason for the inclusion of fixed equipment as well as distribution circuits in {Table
5.2} will become apparent later in this sub-section.

Table 5.1 - Maximum earth-fault loop impedance for 240 V socket


---------------- outlet circuits protected by fuses
Fuse rating (A) Maximum earth-fault loop impedance (Ohms)
Cartridge Semi-enclosed
- Cartridge BS 1361
BS 88 BS3036
5 - 10.9 10.0
6 8.89 - -
10 5.33 - -
15 - 3.43 2.67
20 1.85 1.78 1.85
30 - 1.20 1.14
32 1.09 - -
40 0.86 - -
45 - 0.60 0.62

Table 5.2 - Maximum earth-fault loop impedance for 240 V circuits


-----------------protected by miniature circuit breakers to give compliance
---------------- with 0.4 s disconnection time
- Maximum earth-fault loop impedance (Ohms)
Device MCB
MCB MCB MCB MCB
rating type 3
type 1 type 2 type B type D
(A) and type C
5 12.00 6.86 4.80 - 2.40
6 10.00 5.71 4.00 8.00 2.00
10 6.00 3.43 2.40 4.80 1.20
15 4.00 2.29 1.60 - 0.80
16 3.75 2.14 1.50 3.00 0.75
20 3.00 1.71 1.20 2.40 0.60
25 2.40 1.37 0.96 1.92 0.48
30 2.00 1.14 0.80 - 0.40
32 1.88 1.07 0.75 1.50 0.38
40 1.5 0.86 0.60 1.20 0.30

The severity of the electric shock received when there is a phase to earth fault (indirect
contact) depends entirely on the impedance of the circuit protective conductor. We saw in
{3.4.3} and {Fig 3.8} how the volt drop across the protective conductor is applied to the
person receiving the shock. Since this volt drop is equal to fault current times protective
conductor impedance, if the protective conductor has a lower impedance the shock
voltage will he less. Thus it can be sustained for a longer period without extreme danger.

Socket outlet circuits can therefore have a disconnection time of up to 5 s provided that
the circuit protective conductor impedance's are no higher than shown in {Table 5.3} for
various types of protection.

The reasoning behind this set of requirements becomes clearer if we take an example.
{Table 5.3} shows that a 40 A cartridge fuse to BS 88 must have an associated protective
conductor impedance of no more than 0.29 Ohms if it is to comply. Now look at the
time/current characteristic for the fuse {Fig 3.15} from which we can see that the current
for operation in 5 s is about 170 A. The maximum volt drop across the conductor (the
shock voltage) is thus 170 x 0.29 or 49.3 V.

Table 5.3 - Maximum impedance of circuit protective conductors to


---------------- allow 5 s disconnection time for socket outlets
- Maximum impedance of circuit protective conductor
Fuse Fuse Fuse MCB
Rating MCB MCB MCB MCB
BS 88 BS BS type 3
(A) type 1 type 2 type B type D
1361 3036 &C
5 - 3.25 3.25 2.50 1.43 1.00 - 0.50
6 2.48 - - 2.08 1.19 0.83 1.67 0.42
10 1.48 - - 1.25 0.71 0.50 1.00 0.25
15 - 0.96 0.96 0.83 0.48 0.33 - -
16 0.83 - - 0.78 0.45 0.31 0.63 0.16
20 0.55 0.55 0.63 0.63 0.36 0.25 0.50 0.12
25 0.43 - - - - - - 0.10
30 - 0.36 0.43 0.42 0.24 0.17 - -
32 0.34 - - 0.39 0.22 0.16 0.31 0.08
40 0.26 - - 0.31 0.18 0.13 0.25 0.06
45 - 0.18 0.24 0.28 0.16 0.11 0.22 0.06

Table 5.4 - Maximum earth-fault loop impedance for 240 V fixed


---------------- equipment distribution circuits protected by fuses
- Maximum earth-fault loop impedance
Device rating Cartridge Cartridge Semi-enclosed
(A) BS 88 BS 1361 BS 3036
5 - 17.1 -
6 14.1 - -
10 7.74 - -
15 - 5.22 5.58
16 4.36 - -
20 3.04 2.93 4.00
30 - 1.92 2.76
32 1.92 - -
40 1.41 - -
45 - 1.00 1.66
50 1.09 - -

Application of the same reasoning to all the figures gives shock voltages of less than 50
V. This limitation on the impedance of the CPC is of particular importance in TT systems
where it is likely that the resistance of the earth electrode to the general mass of earth will
be high.
The breaking time of 5 s also applies to fixed equipment, so the earth-fault loop
impedance values can be higher for these circuits, as well as for distribution circuits. For
fuses, the maximum values of earth-fault loop impedance for fixed equipment are given
in {Table 5.4}.

No separate values are given for miniature circuit breakers. Examination of the
time/current characteristics {Figs 3.16 to 3.19} will reveal that there is no change at all in
the current causing operation between 0.4 s and 5 s in all cases except the Type 1. Here,
the vertical characteristic breaks off at 4 s, but this makes little difference to the
protection. In this case, the values given in {Table 5.2} can be used for fixed equipment as
well as for socket outlet circuits. An alternative is to calculate the loop impedance as
described above.

5.3.5 - Protective conductor impedance

It has been shown in the previous sub-section how a low-impedance protective conductor
will provide safety from shock in the event of a fault to earth. This method can only be
used where it is certain that the shock victim can never be in contact with conducting
material at a different potential from that of the earthed system in the zone he occupies.
Thus, all associated exposed or extraneous parts must be within the equipotential zone
(see {5.4}). When overcurrent protective devices are used as protection from electric
shock, the protective conductor must be in the same wiring system as, or in close
proximity to, the live conductors. This is intended to ensure that the protective conductor
is unlikely to he damaged in an accident without the live conductors also being cut.

{Figure 5.9} shows a method of measuring the resistance of the protective conductor,
using a line conductor as a return and taking into account the different cross-sectional
areas of the phase and the protective conductors.

Fig 5.9 - Measurement of protective conductor resistance

Taking the cross-sectional area of the protective conductor as Ap and that of the line
(phase or neutral) conductor as Al , then

Rp = resistance reading x Al
Al + Ap

For example, consider a reading of 0.72 Ohms obtained when measuring a circuit in the
way described and having 2.5 mm² line conductors and a 1.5 mm² protective conductor.
The resistance of the protective conductor is calculated from:

Rp = R x Al = 0.72 x 2.5 Ohms


Al + Ap 2.5 + 1.5

= 0.72 x 2.5 Ohms = 0.45 Ohms


4.0

5.3.6 - Maximum circuit conductor length

The complete earth-fault loop path is made up of a large number of parts as shown in {Fig
5.7}, many of which are external to the installation and outside the control of the installer.
These external parts make up the external loop impedance (Ze). The rest of the earth-fault
loop impedance of the installation consists of the impedance of the phase and protective
conductors from the intake position to the point at which the loop impedance is required.

Since an earth fault may occur at the point farthest from the intake position, where the
impedance of the circuit conductors will be at their highest value, this is the point which
must be considered when measuring or calculating the earth-fault loop impedance for the
installation. Measurement of the impedance will he considered in {8.6.2}. Provided that
the external fault loop impedance value for the installation is known, total impedance can
be calculated by adding the external

Table 5.5 - Resistance per metre of copper conductors at 20°C for


---------------- calculation of R1 + R2
Conductor cross-sectional area Resistance per metre run
(mm²) (m ohms / m)
1.0 18.1
1.5 12.10
2.5 7.41
4.0 4.61
6.0 3.08
10.0 1.83
16.0 1.15
25.0 0.727
Note that to allow for the increase in resistance with increased temperature
under fault conditions the values of {Table 5.5} must be multiplied by 1.2 for
p.v.c. insulated cables (see {Table 8.7})

impedance to that of the installation conductors to the point concerned. The combined
resistance of the phase and protective conductors is known as R1+ R2. The same term is
sometimes used for the combined resistance of neutral and protective conductors (see
{8.4.1}). In the vast majority of cases phase and neutral conductors have the same cross-
sectional area and hence the same resistance.

For the majority of installations, these conductors will be too small for their reactance to
have any effect (below 25 mm² cross-sectional area reactance is very small), so only their
resistance's will be of importance. This can be measured by the method indicated in {Fig
5.9}, remembering that this time we are interested in the combined resistance of phase and
protective conductors, or can be calculated if we measure the cable length and can find
data concerning the resistance of various standard cables. These data are given here as
{Table 5.5}.

The resistance values given in {Table 5.5} are for conductors at 20°C. Under fault
conditions the high fault current will cause the temperature of the conductors to rise and
result in an increase in resistance. To allow for this changed resistance, the values in
{Table 5.5} must be multiplied by the appropriate correction factor from Table {8.7}. It
should be mentioned that the practice which has been adopted here of adding impedance
and resistance values arithmetically is not strictly correct. Phasor addition is the only
perfectly correct method since the phase angle associated with resistance is likely to he
different from those associated with impedance, and in addition impedance phase angles
will differ from one another. However, if the phase angles are similar, and this will be so
in the vast majority of cases where electrical installations are concerned, the error will be
acceptably small.

It is often assumed that higher conductor temperatures are associated with the higher
levels of fault current. In most cases this is untrue. A lower fault level will result in a
longer period of time before the protective device operates to clear it, and this often
results in higher conductor temperature.

Example 5.1
A 7 kW shower heater is to be installed in a house fed with a 240 V TN-S supply system
with an external loop impedance (Ze) of 0.8 Ohms. The heater is to be fed from a 32 A
BS 88 cartridge fuse. Calculate a suitable size for the p.v.c. insulated and sheathed cable
to be used and determine the maximum possible length of run for this cable. It may be
assumed that the cable will not be subject to any correction factors and is clipped direct to
a heat conducting surface throughout its run.

First calculate the circuit current.


I =P= 7000 A = 29.2 A
U 240
Next, select the cable size from {Table 4.7} (which is based on [Table 4D2A]) from which
we can see that 4 mm² cable of this kind clipped direct has a rating of 36 A. The 2.5 mm²
rating of 27 A is not large enough. We shall assume that a 2.5 mm² protective conductor
is included within the sheath of the cable.

Now we must find the maximum acceptable earth-fault loop impedance for the circuit.
Since this is a shower, a maximum disconnection time of 0.4 s will apply, so we need to
consult {Table 5.1}, which gives a maximum loop impedance of 1.09 Ohms for this
situation. Since the external loop impedance is 0.8 Ohms, we can calculate the maximum
resistance of the cable.

R cable = max. loop impedance - external impedance


=1.09 - 0.8 Ohms = 0.29 Ohms

This assumes that resistance and impedance phase angles are identical, which is not
strictly the case. However, the difference is unimportant.

The phase conductor (4 mm²) has a resistance of 4.6 m Ohms/m and the 2.5 mm²
protective conductor 7.4 mOhms/m, so the combined resistance per metre is 4.6 + 7.4 =
12.0 m Ohms/m. The cable will get hot under fault conditions, so we must apply the
multiplier of 1.2.

Effective resistance of cable per metre = 12.0 x 1.2 m Ohms/m


= 14.4 m Ohms/m

The maximum length of run in metres is thus the number of times 14.4 mOhms will
divide into 0.29 Ohms.

Maximum length of run = 0.29 x 1000 m = 20.1 m


14.4

This is not quite the end of our calculation, because we must check that this length of run
will not result in an excessive volt drop. From {Table 4.7} based on [Table 4D2B] a 4 mm²
cable of this kind gives a volt drop of 11 mV/A/m.

Volt drop = 11 x circuit current (A) x length of run (m) divided by 1000
Volt drop = 11 x 29.2 x 20.1 V = 6.46 V
1000

Since the permissible volt drop is 4% of 240 V or 9.6 V, this length of run is acceptable.

5.4.1 - Earthing conductors

5.4.2 - Protective conductor types


5.4.3 - Bonding conductors

5.4.4 - Protective conductor cross-section


assessment

5.4.5 - Protective conductor cross-section calculation

5.4.6 - Unearthed metalwork

5.4.1 - Earthing conductors

The earthing conductor is commonly called the earthing lead. It joins the installation
earthing terminal to the earth electrode or to the earth terminal provided by the Electricity
Supply Company. It is a vital link in the protective system, so care must be taken to see
that its integrity will be preserved at all times. Aluminium conductors and cables may
now be used for earthing and bonding, but great care must be taken when doing so to
ensure that there will be no problems with corrosion or with electrolytic action where
they come into contact with other metals.

Where the final connection to the earth electrode or earthing terminal is made there must
be a clear and permanent label Safety Electrical Connection - Do not remove (see {Fig
5.17}). Where a buried earthing conductor is not protected against mechanical damage but
is protected against corrosion by a sheath, its minimum size must be 16 mm² whether
made of copper or coated steel. If it has no corrosion protection, minimum sizes for
mechanically unprotected earthing conductors are 25 mm² for copper and 50 mm² for
coated steel.

If not protected against corrosion the latter sizes again apply, whether protected from
mechanical damage or not.

Earthing conductors, as well as protective and bonding conductors, must be protected


against corrosion. Probably the most common type of corrosion is electrolytic, which is
an electro-chemical effect between two different metals when a current passes between
them whilst they are in contact with each other and with a weak acid. The acid is likely to
be any moisture which has become contaminated with chemicals carried in the air or in
the ground. The effect is small on ac supplies because any metal removed whilst current
flows in one direction is replaced as it reverses in the next half cycle. For dc Systems,
however, it will be necessary to ensure that the system remains perfectly dry (a very
difficult task) or to use the 'sacrificial anode' principle.

A main earth terminal or bar must be provided for each installation to collect and connect
together all protective and bonding conductors. It must be possible to disconnect the
earthing conductor from this terminal for test purposes, but only by the use of a tool. This
requirement is intended to prevent unauthorised or unknowing removal of protection.

5.4.2 - Protective conductor types


The circuit protective conductor (increasingly called the 'c.p.c.') is a system of conductors
joining together all exposed conductive parts and connecting them to the main earthing
terminal. Strictly speaking, the term includes the earthing conductor as well as the
equipotential bonding conductors.

The circuit protective conductor can take many forms, such as:

1. - a separate conductor which must be green/yellow insulated if equal to or less than 10


mm2 cross-sectional area.

2. - a conductor included in a sheathed cable with other conductors

3. - the metal sheath and/or armouring of a cable

4. - conducting cable enclosures such as conduit or trunking

5. - exposed conductive parts, such as the conducting cases of equipment

This list is by no means exhaustive and there may be many other items forming parts of
the circuit protective conductor as indicated in {Fig 5.10}. Note that gas or oil pipes must
not be used for the purpose, because of the possible future change to plastic (non-
conducting) pipes.

Fig 5.10 Some types of circuit protective conductor


Fig 5.11 Protective connection for socket outlet in conduit system

It is, of course, very important that the protective conductor remains effective throughout
the life of the installation. Thus, great care is needed to ensure that steel conduit used for
the purpose is tightly jointed and unlikely to corrode. The difficulty of ensuring this point
is leading to the increasing use of a c.p.c. run inside the conduit with the phase
conductors. Such a c.p.c. will, of course, always be necessary where plastic conduits are
used. Where an accessory is connected to a system (for example, by means of a socket
outlet) which uses conduit as its c.p.c., the appliance (or socket outlet) earthing terminal
must be connected by a separate conductor to the earth terminal of the conduit box (see
{Fig 5.11}). This connection will ensure that the accessory remains properly earthed even
if the screws holding it into the box become loose, damaged or corroded.

Fig 5.12 Separate additional protective conductor with flexible conduit


A separate protective conductor will be needed where flexible conduit is used, since this
type of conduit cannot be relied upon to maintain a low resistance conducting path (see
{Fig 5.12}).

5.4.3 - Bonding conductors

The purpose of the protective conductors is to provide a path for earth fault current so
that the protective device will operate to remove dangerous potential differences, which
are unavoidable under fault conditions, before a dangerous shock can be delivered.
Equipotential bonding serves the purpose of ensuring that the earthed metalwork
(exposed conductive parts) of the installation is connected to other metalwork
(extraneous conductive parts) to ensure that no dangerous potential differences can occur.
The resistance of such a bonding conductor must be low enough to ensure that its volt
drop when carrying the operating current of the protective device never exceeds 50 V.

Fig 5.13 Main bonding connections

R
Thus 50
<
Ia
where R is the resistance of the bonding conductor
Ia is the operating current of the protective device.

Two types of equipotential bonding conductor are specified.

1. - Main equipotentiol bonding conductors


These conductors connect together the installation earthing system and the metalwork of
other services such as gas and water. This bonding of service pipes must be effected as
close as possible to their point of entry to the building, as shown in {Fig 5.13}. Metallic
sheaths of telecommunication cables must be bonded, but the consent of the owner of the
cable must he obtained before doing so. The minimum size of bonding conductors is
related to the size of the main supply conductors (the tails) and is given in {Table 5.6}.
2. - Supplementary bonding conductors
These conductors connect together extraneous conductive parts - that is, metalwork
which is not associated with the electrical installation but which may provide a
conducting path giving rise to shock. The object is to ensure that potential differences in
excess of 50 V between accessible metalwork cannot occur; this means that the resistance
of the bonding conductors must be low (see {Table 5.7}). {Figure 5.14} shows some of the
extraneous metalwork in a bathroom which must be bonded.

Table 5.6 - Supplementary bonding conductor sizes


Circuit protective
Supplementary bonding conductor size
conductor size
- Not protected Mechanically protected
1.0 mm² 4.0 mm² 2.5 mm²
1.5 mm² 4.0 mm² 2.5 mm²
2.5 mm² 4.0 mm² 2.5 mm²
4.0 mm² 4.0 mm² 2.5 mm²
6.0 mm² 4.0 mm² 4.0 mm²
10.0 mm² 6.0 mm² 6.0 mm²

Fig 5.14 Supplementary bonding in a bathroom


The cross-sectional areas required for supplementary bonding conductors are shown in
{Table 5.6}. Where connections are between extraneous parts only, the conductors may
be 2.5 mm² if mechanically protected or 4 mm²if not protected. If the circuit protective
conductor is larger than 10 mm², the supplementary bonding conductor must have have at
least half this cross-sectional area. Supplementary bonding conductors of less than 16
mm² cross sectional area must not be aluminium. {Fig 5.15} shows the application of a
supplementary bonding conductor to prevent the severe shock which could otherwise
occur between the live case of a faulty electric kettle and an adjacent water tap.

There will sometimes be doubt if a particular piece of metalwork should be bonded. The
answer must always be that bonding will be necessary if there is a danger of severe shock
when contact is made between a live system and the metal work in question. Thus if the
resistance between the metalwork and the general mass of earth is low enough to permit
the passage of a dangerous shock current, then the metalwork must be bonded.

The question can be resolved by measuring the resistance (Rx) from the metalwork
concerned to the main earthing terminal. Using this value in the formula:

Ib = Uo
Rp + Rx

will allow calculation of the maximum current likely to pass through the human body
where :

Ib -is the shock current through the body (A)


Uo - Is the voltage of the supply (V)
RP -is the resistance of the human body (Ohms) and
Rx - is the measured resistance from the metalwork concerned
to the main earthing terminal (Ohms)

The resistance of the human body, RP can in most cases be taken as 1000 Ohms although
200 Ohms would be a safer value if the metalwork in question can be touched by a
person in a bath. Although no hard and fast rules are possible for the value of a safe
shock current, Ib, it is probable that 10 mA is seldom likely to prove fatal. Using this
value with 240 V for the supply voltage, uo, and 1000 Ohms as the human body
resistance, RP, the minimum safe value of RP calculates to 23 kOhms. If the safer values
of 5 mA for Ib and 200 Ohms for RP are used, the value of Rx would be 47.8 kOhms for
a 240 V supply.
Fig 5.15 Supplementary bonding conductor in a kitchen

To sum up when in doubt about the need to bond metalwork, measure its resistance to the
main earthing terminal. If this value is 50 kOhms or greater, no bonding is necessary. In a
situation where a person is not wet, bonding could be ignored where the resistance to the
main earthing terminal is as low as 25 kOhms. To reduce the possibility of bonding
conductors being disconnected by those who do not appreciate their importance, every
bonding connection should be provided with a label like that shown in Fig. 5.17.

5.4.4 - Protective conductor cross-section assessment

A fault current will flow when an earth fault occurs. If this current is large enough to
operate the protective device quickly, there is little danger of the protective conductor and
the exposed conductive parts it connects to earth being at a high potential to earth for
long enough for a dangerous shock to occur. The factors determining the fault current are
the supply voltage and the earth-fault loop impedance (see{5.3}).

The earth fault results in the protective conductors being connected in series across the
supply voltage {Fig 5.16}. The voltage above earth of the earthed metalwork (the voltage
of the junction between the protective and phase conductors) at this time may become
dangerously high, even in an installation complying with the Regulations. The people
using the installation will be protected by the ability of the fuse or circuit breaker in a
properly designed installation to cut off the supply before dangerous shock damage
results.
Fig 5.16 -The effect of protective conductor resistance on shock voltage

a) effective resistance of a ring circuit protective conductor


b) potential differences across healthy protective conductor in the event of an earth fault

Table 5.7 - Main earthing and main equipotential bonding conductor


----------------- sizes for TN-S and TN-C-S supplies
Phase Earthing conductor Main
Main equipotential
conductor (or (not buried or equipotential
bonding conductor
neutral for PME protected against bonding
for PME supplies
supplies ) mechanical damage) conductor
csa mm² csa mm² csa mm² csa mm²
4 4 6 10
6 6 6 10
10 10 6 10
16 16 10 10
25 16 10 10
35 16 10 10
50 25 16 16
70 35 16 25

Remember that lower fault levels result in a longer time before operation of the protective
device. Since the cross-sectional area of the protective conductor will usually be less than
that of live conductors, its temperature, and hence its resistance, will become higher
during the fault, so that the shock voltage will be a higher proportion of the supply
potential (see {Fig 5.16}).

{Fig 5.16} shows the circuit arrangements, with some typical phase- and
protective-conductor resistances. In this case, a shock voltage of 140 V will be applied to
a person in contact with earthed metal and with the general mass of earth. Thus, the
supply must he removed very quickly. The actual voltage of the shock depends directly
on the relationship between the phase conductor resistance and the protective conductor
resistance. If the two are equal, exactly half the supply voltage will appear as the shock
voltage.

For socket outlet circuits, where the shock danger is highest, the maximum protective
conductor resistance values of {Table 5.3} will ensure that the shock voltage never exceeds
the safe value of 50 V. If the circuit concerned is in the form of a ring, one quarter of the
resistance of the complete protective conductor round the ring must not be greater than
the {Table 5.3} figure. The reason for this is shown in {Fig 5.16(a)}. This assumes that the
fault will occur exactly at the mid point of the ring. If it happens at any other point,
effective protective conductor resistance is lower, and safer, than one quarter of the total
ring resistance.

{Table 5.7} allows selection (rather than calculation) of sizes for earthing and bonding
conductors. The rules applying to selection are:

For phase conductors up to 16 mm², the protective conductor has the same size as the
phase conductor.

For phase conductors from 16 mm² to 35 mm², the protective conductor must be 16 mm²

For phase conductors over 35 mm², the protective conductor must have at least half the
c.s.a. of the phase conductor. The minimum cross-sectional area of a separate CPC is 2.5
mm² if mechanically protected and 4mm² if not.

Note that Regional Electricity Companies may require a minimum size of earthing
conductor of 16 mm² at the origin of the installation. Always consult them before
designing an installation.

5.4.5 - Protective conductor cross-section calculation

The c.s.a. of the circuit protective conductor (c.p.c.) is of great importance since

the level of possible shock in the event of a fault depends on it (as seen in {5.4.4}).

Safety could always be assured if we assessed the size using {Table 5.7} as a basis.

However, this would result in a more expensive installation than necessary because we
would often use protective conductors which are larger than those found to be acceptable
by calculation. For example. twin with cpc insulated and sheathed cables larger than 1
mm² would be ruled out because in all other sizes the CPC is smaller than required by
{Table 5.7}.

In very many cases, calculation of the CPC size will show that a smaller size than that
detailed in {5.4.4} is perfectly adequate. The formula to be used is:

S= √(Ia²t)
k
S is the minimum protective conductor cross-
where
sectional area (mm2)
Ia is the fault current (A)
t is the opening time of the protective device (s)
k is a factor depending on the conductor material
and insulation, and the initial and maximum insulation
temperatures.

This is the same formula as in {3.7.3}, the adiabatic equation, but with a change in the
subject. To use it, we need to have three pieces of information, Ia, t and k.

1) To find Ia
Since Ia = Uo we need values for Ia = uo and Zs
Zs

is simply the supply voltage, which in


Uo
most cases will be 240V.
is the earth-fault loop impedance
Zs assuming that the fault has zero
impedance.

Since we must assume that we are at the design stage, we cannot measure the loop
impedance and must calculate it by adding the loop impedance external to the installation
(Ze) to the resistance of the conductors to the furthest point in the circuit concerned. This
technique was used in {5.3.6}.

Thus, Zs = Ze + R1 + R2 where R1 and R2 are the resistances of the phase and protective
conductors respectively from {Table 5.5}.

2) To find t
We can find t from the time/current characteristics of {Figs 3.13 to 3.19} using the value of
Ia already calculated above. For example, if the protective device is a 20 A miniature
circuit breaker type I and the fault current is 1000 A, we shall need to consult {Fig 3.16},
when we can read off that operation will be in 0.01 s (10 ms). (It is of interest here to
notice that if the fault current had been 80 A the opening time could have been anything
from 0.04 s to 20 s,so the circuit would not have complied with the required opening
times).

3) To find k
k is a constant, which we cannot calculate but must obtain from a suitable table of values.
Some values of k for typical protective conductors are given in {Table 5.8}.

It is worth pointing out here that correctly installed steel conduit and trunking will always
meet the requirements of the Regulations in terms of protective conductor impedance.
Although appearing a little complicated, calculation of acceptable protective conductor
size is worth the trouble because it often allows smaller sizes than those shown in {Table
5.7}.

Table 5.8 - Values of k for protective conductors


Initial
Final temp Conductor
Nature of protective conductor temp. K
(°C) material
(°C)
p.v.c. insulated, not in cable
30 160 Copper 143
or bunched
- 30 160 Aluminium 95
- 30 160 Steel 52
-
p.v.c. insulated, in cable
70 160 Copper 115
or bunched
- 70 160 Aluminium 76

Steel conduit or trunking 50 160 Steel 47


-
Bare conductor 30 200 Copper 159
- 30 200 Aluminium 105
- 30 200 Steel 58

Example 5.2
A load takes 30 A from a 240 V single phase supply and is protected by a 32 A HBC fuse
to BS 88. The wiring consists of 4 mm² single core p.v.c. insulated cables run in trunking,
the length of run being 18 m. The earth-fault loop impedance external to the installation
is assessed as 0.7 Ohms. Calculate the cross-sectional area of a suitable p.v.c. sheathed
protective conductor.

This is one of those cases where we need to make an assumption of the answer to the
problem before we can solve it. Assume that a 2.5 mm² protective conductor will be
acceptable and calculate the combined resistance of the phase and protective conductors
from the origin of the installation to the end of the circuit. From {Table 5.5}, 2.5 mm²
cable has a resistance of 7.4 mohms/m and 4 mm² a resistance of 4.6 mOhms/m. Both
values must be multiplied by 1.2 to allow for increased resistance as temperature rises
due to fault current.

Thus, R1 + R2 = (7.4 + 4.6) x 1.2 x 18 Ohms = 12.0 x 1.2 x 18 = 0.26 Ohms


1000 1000
This conductor resistance must be added to external loop impedance to give the total
earth-fault loop impedance.

Zs = Ze + Rl + R2 = 0.7+ 0.26 Ohms = 0.96 Ohms

We can now calculate the fault current:

la = Uo = 240 = 250A
Zs 0.96

Next we need to find the operating time for a 32 A BS 88 fuse carrying 250 A.
Examination of {Fig 3.15} shows that operation will take place after 0.2 s.

Finally, we need a value for k. From {Table 5.8} we can read this off as 115, because the
protective conductor will be bunched with others in the trunking.

We now have values for Ia, t and k so we can calculate conductor size.

S= √(Ia²t) = √(250² x 0.02) mm² = 0.97 mm²


k 115

This result suggests that a 1.0 mm² protective conductor will suffice. However, it may he
dangerous to make this assumption because the whole calculation has been based on the
resistance of a 2.5 mm² conductor. Let us start again assuming a 1.5 mm² protective
conductor and work the whole thing through again.

The new size protective conductor has a resistance of 18.1 mOhms/m, see {Table 5.5}, and
with the 4 mm² phase conductor gives a total conductor resistance, allowing for increased
temperature, of 0.491 Ohms. When added to external loop impedance this gives a total
earth-fault loop impedance of 1.191 Ohms and a fault current at 240 V of 202 A. From
{Fig 3.15} operating time will be 0.6 s. The value of k will be unchanged at 115.

S= √(Ia²t) = √(202² x 0.6) mm² = 1.36 mm²


k 115

Thus, a 1.5 mm² protective conductor can be used in this case. Note that if the size had
been assessed rather than calculated, the required size would be 4 mm², two sizes larger.
A point to notice here is that the disconnection time with a 1.5mm² protective conductor
is 0.6 s, which is too long for socket outlet circuits (0.4 s max.).

Example 5.3
A 240 V, 30 A ring circuit for socket outlets is 45 m long and is to be wired in 2.5 mm²
flat twin p.v.c. insulated and sheathed cable incorporating a 1.5 mm² cpc. The circuit is to
be protected by a semi-enclosed (rewirable) fuse to BS 3036, and the earth-fault loop
impedance external to the installation has been ascertained to be 0.3 Ohms. Verify that
the 1.5 mm² cpc enclosed in the sheath is adequate.

First use {Table 5.5} to find the resistance of the phase and cpc conductors. These are 7.4
mOhms/m and 12.1 mOhms/m respectively, so for a 45 m length and allowing for the
resistance increase with temperature factor of 1.2.

R1 + R2 = (7.4 + 12.1) x 1.2 x 45 Ohms = 19.5 x 1.2 x 45 Ohms = 1.05 Ohms


1000 1000

Zs = Ze + R1+ R2 = 0.3 + 1.05 Ohms = 0.3 + 0.263 Ohms = 0.563 Ohms


4 4

The division by 4 is to allow for the ring nature of the circuit.

Ia = Uo = 240 A = 426A
Zs 0.563

We must then use the time/current characteristic of {Fig 3.13} to ascertain an operating
time of 0.10 s.

From {Table 5.8} the value of k is 115.

Then S = √(Ia²t) = √(426² x 0.10) mm² = 1.17 mm²


k 115

Since this value is smaller than the intended value of 1.5 mm², this latter value will be
satisfactory.

Example 5.4
A 240 V single-phase circuit is to be wired in p.v.c. insulated single core cables enclosed
in plastic conduit. The circuit length is 45 m and the live conductors are 16 mm² in cross-
sectional area. The circuit will supply fixed equipment, and is to be protected by a 63 A
HBC fuse to BS 88. The earth-fault loop impedance external to the installation has been
ascertained to be 0.58 Ohms. Calculate a suitable size for the circuit protective conductor.

With the information given this time the approach is somewhat different. We know that
the maximum disconnection time for fixed equipment is 5 s, so from the time/current
characteristic for the 63 A fuse {Fig 3.15} we can see that the fault current for
disconnection will have a minimum value of 280 A.

Thus,
Uo = 240 Ohms = 0.857 Ohms
Zs =
Ia 280
If we deduct the external loop impedance, we come to the resistance of phase and
protective conductors.

R1 +R2 = Zs-Ze = 0.857-0.58Ohms = 0.277 Ohms

Converting this resistance to the combined value of R1 and R2 per metre,

(R1 + R2) per metre = 0.277 x 1000 mOhms/m = 5.13 mOhms/m


45 x 1.2

Consulting {Table 5.5} we find that the resistance of 16 mm² copper conductor is 1.15
mOhms/m, whilst 10 mm² and 6 mm² are 1.83 and 3.08 mOhms/m respectively. Since
1.15 and 3.08 add to 4.23, which is less than 5.13, it would seem that a 6 mm² protective
conductor will be large enough. However, to be sure we must check with the adiabatic
equation.

R1 + R2 = (1.15+3.08) x 1.2 x 45 Ohms = 0.228 Ohms


1000

Zs = Ze+(R1 +R2) = 0.58+0.228 Ohms = 0.808 Ohms

Ia = Uo = 240 A = 297 A
Zs 0.808

From {Fig 3.15} the disconnection time for a 63 A fuse carrying 297 A is found to he 3.8s.
From {Table 5.8} the value of k is 115.

Then S = √(Ia²t) = √(297² x 3.8) mm² = 5.03 mm²


k 115

Since 5.03 is less than 6 then a 6 mm² protective conductor will be large enough to satisfy
the requirements

5.4.6 - Unearthed metalwork

If exposed conductive parts are isolated, or shrouded in non-conducting material, or are


small so that the area of contact with a human body is limited, it is permissible not to
earth them. Examples are overhead line metalwork which is out of reach, steel
reinforcing rods within concrete lighting columns, cable clips, nameplates, fixing screws
and so on. Where areas are accessible only to skilled or instructed persons, and where
unauthorised persons are unlikely to enter due to the presence of warning notices, locks
and so on, earthing may be replaced by the provision of obstacles which make direct
contact unlikely, provided that the installation complies with the Electricity at Work
Regulations, 1989
5.5.1 -Why must we have earth electrodes?

5.5.2 - Earth electrode types

5.5.1 -Why must we have earth electrodes?

The principle of earthing is to consider the general mass of earth as a reference (zero)
potential. Thus, everything connected directly to it will be at this zero potential, or above
it by the amount of the volt drop in the connection system (for example, the volt drop in a
protective conductor carrying fault current). The purpose of the earth electrode is to
connect to the general mass of earth.

With the increasing use of underground supplies and of protective multiple earthing
(PME) it is becoming more common for the consumer to be provided with an earth
terminal rather than having to make contact with earth using an earth electrode.

5.5.2 - Earth electrode types

Acceptable electrodes are rods, pipes, mats, tapes, wires, plates and structural steelwork
buried or driven into the ground. The pipes of other services such as gas and water must
not be used as earth electrodes although they must be bonded to earth as described in
{5.4.3}. The sheath and armour of a buried cable may be used with the approval of its
owner and provided that arrangements can be made for the person responsible for the
installation to be told if the cable is changed, for example, for a type without a metal
sheath.

The effectiveness of an earth electrode in making good contact with the general mass of
earth depends on factors such as soil type, moisture content, and so on. A permanently-
wet situation may provide good contact with earth, but may also limit the life of the
electrode since corrosion is likely to be greater. If the ground in which the electrode is
placed freezes, there is likely to be an increase in earth resistance. In most parts of the
UK an earth electrode resistance in the range 1 Ohm to 5 Ohms is considered to be
acceptable.

The method of measuring the resistance of the earth electrode will be considered in
{8.6.1}; the resistance to earth should be no greater than 220 Ohms. The earthing
conductor and its connection to the earth electrode must be protected from mechanical
damage and from corrosion. Accidental disconnection must be avoided by fixing a
permanent label as shown in {Fig 5.17} which reads:
Fig 5.17 Connection of earthing conductor to earth electrode

5.6.1 - What is protective multiple earthing?

5.6.2 - Increased fire risk

5.6.3 - Broken neutral conductor

5.6.4 - Special requirements PME-fed installations

5.6.1 - What is protective multiple earthing?

If a continuous metallic earth conductor exists from the star point of the supply
transformer to the earthing terminal of the installation, it will run throughout in parallel
with the installation neutral, which will be at the same potential. It therefore seems
logical that one of these conductors should be removed, with that remaining acting as a
combined protective and neutral conductor (PEN). When this is done, we have a TN-C-S
installation {5.2.4}. The combined earth and neutral system will apply only to the supply,
and not to the installation.

Because of possible dangers with the system which will be explained in the following
sub-sections, PME can be installed by the Electricity Supply Company only after the
supply system and the installations it feeds have complied with certain requirements.
These special needs will be outlined in {5.6.4}.

The great virtue of the PME system is that neutral is bonded to earth so that a phase to
earth fault is automatically a phase to neutral fault. The earth-fault loop impedance will
then be low, resulting in a high value of fault current which will operate the protective
device quickly. It must be stressed that the neutral and earth conductors are kept quite
separate within the installation: the main earthing terminal is bonded to the incoming
combined earth and neutral conductor by the Electricity Supply Company. The difficulty
of ensuring that bonding requirements are met on construction sites means that PME
supplies must not be used. Electricity Supply Regulations forbid the use of PME supplies
to feed caravans and caravan sites.

5.6.2 - Increased fire risk

As with other systems of earth-fault protection, PME does not prevent a fault occurring,
but will ensure that the fault protection device operates quickly when that fault appears.
For example, if a fault of 2 Ohms resistance occurs in a 240 V circuit protected by a 20 A
semi-enclosed fuse in a system with an earth-fault loop impedance of 6 Ohms, the fault
current will be 240/(2 + 6) A = 240/8 A = 30 A. The fuse would not blow unless the
circuit were already loaded, when load current would add to fault current. If the circuit
were fully loaded with a load current of 20 A, total current would be 50 A and the fuse
would blow after about 18 s. During this time, the power produced in the fault would be:

P = I²R = 30²x6 = 5400W or 5.4kW

This could easily start a fire. If, however, the earth-fault loop impedance were I Ohm,
current would be 80 A and the fuse would blow in about 1.6 s and limit the energy in the
fault circuit

5.6.3 - Broken neutral conductor

The neutral of a supply is often common to a large number of installations. In the


(unlikely) event of a broken neutral, all the consumers on the load side of the break could
have a combined neutral and earth potential of the same level as the phase system (240 V
to earth). This situation could be very dangerous, because all earthed metalwork would be
at 240 V above the potential of the general mass of earth.

To prevent such an event, the Electricity Supply Company connects its combined neutral
and earth conductor to earth electrodes at frequent intervals along its run. Whilst this does
not entirely remove the danger, it is much reduced. For example, the assumed earth
resistance values of {Fig 5.18} show that the maximum possible potential to earth in this
case would be 96 V. In practice, much lower resistance values for the earth connections
will reduce this voltage. The Electricity Supply Company goes to very great lengths to
ensure the integrity of its neutral conductor.
Fig 5.18 Danger due to broken neutral in a PME system

5.6.4 - Special requirements PME-fed installations

An installation connected to a protective multiple earth supply is subject to special


requirements concerning the size of earthing and bonding leads, which are generally
larger in cross-section than those for installations fed by supplies with other types of
earthing. Full discussions with the Electricity Supply Company are necessary before
commencing such an installation to ensure that their needs will be satisfied. The cross-
sectional area of the equipotential bonding conductor is related to that of the neutral
conductor as shown in {Table 5.9}

Table 5.9 - Minimum cross-sectional area of main equipotential


----------------- bonding conductor for PME-fed installations
Neutral conductor c.s.a. Main equipotential bonding conductor c.s.a
(mm²) (mm²)
35 or less 10
Over 35 and up to 50 16
Over 50 and up to 95 25

Danger can arise when the non-current carrying metalwork of an installation is connected
to the neutral, as is the case with a PME-fed system. The earth system is effectively in
parallel with the neutral, and will thus share the normal neutral current. This current will
not only be that drawn by the installation itself, but may also be part of the neutral current
of neighbouring installations.

It follows that the earth system for an installation may carry significant current (of the
order of tens of amperes) even when the main supply to that installation is switched off.
This could clearly cause a hazard if a potentially explosive part of an installation, such as
a petrol storage tank, were the effective earth electrode for part of the neutral current of a
number of installations. For this reason, the Health and Safety Executive has banned the
use of PME in supplies for petrol filling stations. Such installations must be fed from TN-
S supply systems (RSE booklet RS(C)41
- 'Petrol Filling Stations: Construction and Operation').
5.7.1 - What is earthed concentric wiring?

5.7.2 - Requirements for earthed concentric wiring

5.7.1 - What is earthed concentric wiring?

This is the TN-C system {5.2.5} where a combined neutral and earth (PEN) conductor is
used throughout the installation as well as for the supply. The PEN conductor is the
sheath of a cable and therefore is concentric with (totally surrounds) the phase
conductor(s). The system is unusual, but where employed almost invariably uses mineral
insulated cable, the metallic copper sheath being the combined neutral and earth
conductor.

5.7.2 - Requirements for earthed concentric wiring

Earthed concentric wiring may only be used under very special conditions, which usually
involve the use of a private transformer supply or a private generating plant. Since there
is no separate path for earth currents, it follows that residual current devices (RCDs) will
not be effective and therefore must not be used. The cross-sectional area of the sheath
(neutral and earth conductor) of a cable used in such a system must never be less than 4
mm² copper, or 16 mm² aluminium or less than the inner core for a single core cable. All
multicore copper mineral insulated cables comply with this requirement, even a I mm²
two core cable having the necessary sheath cross-sectional area. However, only single
core cables of 6 mm² and below may be used. The combined protective and neutral
conductors (sheaths) of such cables must not serve more than one final circuit.

Wherever a joint becomes necessary in the PEN conductor, the contact through the
normal sealing pot and gland is insufficient; an extra earth tail must be used as shown in
{Fig 5.19}. If it becomes necessary to separate the neutral and protective conductors at
any point in an installation, they must not be connected together again beyond that point.

Fig 5.19 Earth tail seal for use in earthed concentric wiring

5.8.1 - Class II equipment

5.8.2 - Non-conducting location

5.8.3 - Earth-free bonding


5.8.4 - Electrical separation

5.8.1 - Class II equipment

Class H equipment has reinforced or double insulation. As well as the basic insulation for
live parts, there is a second layer of insulation, either to prevent contact with exposed
conductive parts or to make sure that there can never be any contact between such parts
and live parts. The outer case of the equipment need not be made of insulating material; if
protected by double insulation, a metal case will not present any danger. It must never be
connected with earth, so connecting leads are two-core, having no protective conductor.
The symbol for a double-insulated appliance is shown in {Fig 5.20}.

Fig 5.20 British Standard symbol for double insulation

To make sure that the double insulation is not impaired, it must not be pierced by
conducting parts such as metal screws. Nor must insulating screws be used, because there
is the possibility that they will be lost and will be replaced by metal screws. Any holes in
the enclosure of a double Insulated appliance, such as those to allow ventilation, must be
so small that fingers cannot reach live parts (IP2X protection). Class II equipment must
be installed and fixed so that the double insulation will never be impaired, and so that
metalwork of the equipment does not come into contact with the protective system of the
main installation. Where the whole of an installation is comprised of Class II equipment,
so that there is no protective system installed, the situation must be under proper
supervision to make sure that no changes are made which will introduce earthed parts.

5.8.2 - Non-conducting location


The non-conducting location is a special arrangement where there is no earthing
or protective system because:

1. - there is nothing which needs to be earthed

2. - exposed conductive parts are arranged so that it is impossible to touch two of them,
or an exposed conducting part and an extraneous conductive part, at the same time. The
distance between the parts must be at least 2 m, or 1.25 m if they are out of arm's reach.
An alternative is to erect suitable obstacles, or to insulate the extraneous conductive parts.

Examples of extraneous conductive parts are water and gas pipes, structural steelwork,
and even floors and walls which are not covered with insulating material. Insulation tests
on floors and walls are considered in {8.5.2}. There must be no socket outlets with
earthing contacts in a non-conducting location. This type of installation could cause
danger if earthed metal were introduced in the form of a portable appliance fed by a lead
from outside the location.

The potential reached by exposed metalwork within the situation is of no importance


because it is never possible to touch two pieces of metalwork with differing voltage
levels at the same time. Care must be taken, however, to make sure that a possible high
potential cannot be transmitted outside the situation by the subsequent installation of a
conductor such as a water or gas pipe. A notice must be erected to state that a non-
conducting location exists, and giving details of the person in charge who alone will
authorise any work to be undertaken in, or will authorise any equipment to be taken into,
the location. If two faults to exposed conductive parts occur from conductors at different
potentials (such as a phase and a neutral) and there is a defective bonding system,
dangerous potential differences could occur between exposed conductive parts. To
prevent this possibility, double pole fuses or circuit breakers must provide overload
protection in non-conducting locations.

Non-conducting locations are unusual, and their use must be limited to situations where
there is continuous and proper supervision to ensure that the requirements are fully met
and are properly maintained. This type of installation should only be considered after
consulting a fully qualified electrical engineer.

5.8.3 - Earth-free bonding

The Regulations permit the provision of an area in which all exposed metal parts are
connected together, but not to earth. Inside the area, there can be no danger, even if the
voltage to earth is very high, because all metalwork which can be touched will be at the
same potential. Care is necessary, however, to prevent danger to people entering or
leaving the area, because then they may be in contact with parts which are inside and
others which are outside the area, and hence at differing potentials. A notice must be
erected to warn that the bonding conductors in the system must not he connected to earth,
and that earthed equipment must not be brought into the situation.
As in the case of non-conducting locations, this type of installation is unusual, and must
only be undertaken when designed and specified by a fully qualified electrical engineer.
The area inside the protected system is often referred to as a 'Faraday cage'.

5.8.4 - Electrical separation

Safety from shock can sometimes be ensured by separating a system completely from
others so that there is no complete circuit through which shock current could flow. It
follows that the circuit must be small to ensure that earth impedance's are very high and
do not offer a path for shock current (see {Fig 5.3(b)}). The source of supply for such a
circuit could be a battery or a generating set, but is far more likely to be an isolating
transformer with a secondary winding providing no more than 500 V. Such a transformer
must comply with BS EN 60742, having a screen between its windings and a secondary
winding which has no connection to earth.

There must be no connection to earth and precautions must he taken to ensure, as far as
possible, that earth faults will not occur. Such precautions would include the use of
flexible cords without metallic sheaths, using double insulation, making sure that flexible
cords are visible throughout their length of run, and so on. Perhaps the most common
example of a separated circuit is the bathroom transformer unit feeding an electric shaver.
By breaking the link to the earthed supply system using the double wound transformer,
there is no path to earth for shock current (see {Fig 5.21}).

Fig 5.21 Bathroom shaver socket to BS EN 60742

5.9.1 - Why do we need residual current devices?

5.9.2 - The principle of the residual current device


5.9.3 - Regulations for residual current devices

5.9.4 - Fault voltage operated circuit breakers

5.9.1 - Why do we need residual current devices?

{5.3} has stressed that the standard method of protection is to make sure that an earth fault
results in a fault current high enough to operate the protective device quickly so that fatal
shock is prevented. However, there are cases where the impedance of the earth-fault loop,
or the impedance of the fault itself, are too high to enable enough fault current to flow. In
such a case, either:

1. - current will continue to flow to earth, perhaps generating enough heat to start a fire,
or

2. - metalwork which is open to touch may be at a high potential relative to earth,


resulting in severe shock danger.

Either or both of these possibilities can be removed by the installation of a residual


current device (RCD).

In recent years there has been an enormous increase in the use of initials for residual
current devices of all kinds. The following list, which is not exhaustive, may be helpful to
readers:

RCD residual current device


RCCD residual current operated circuit breaker
SRCD socket outlet incorporating an RCD
PRCD portable RCD, usually an RCD incorporated into a plug
RCBO an RCCD which includes overcurrent protection
SRCBO a socket outlet incorporating an RCBO

5.9.2 - The principle of the residual current device

The RCD is a circuit breaker which continuously compares the current in the phase with
that in the neutral. The difference between the two (the residual current) will he flowing
to earth, because it has left the supply through the phase and has not returned in the
neutral (see {Fig 5.22}). There will always be some residual current in the insulation
resistance and capacitance to earth, but in a healthy circuit such current will he low,
seldom exceeding 2 mA.
Fig 5.22 The meaning of the term residual current

The purpose of the residual current device is to monitor the residual current and to switch
off the circuit quickly if it rises to a preset level. The arrangement of an RCD is shown in
simplified form in {Fig 5.23}. The main contacts are closed against the pressure of a
spring, which provides the energy to open them when the device trips. Phase and neutral
currents pass through identical coils wound in opposing directions on a magnetic circuit,
so that each coil will provide equal but opposing numbers of ampere turns when there is
no residual current. The opposing ampere turns will cancel, and no magnetic flux will be
set up in the magnetic circuit.

Residual earth current passes to the circuit through the phase coil but returns through the
earth path, thus avoiding the neutral coil, which will therefore carry less current. This
means that phase ampere turns exceed neutral ampere turns and an alternating magnetic
flux results in the core. This flux links with the search coil, which is also wound on the
magnetic circuit, inducing an e.m.f. into it. The value of this e.m.f. depends on the
residual current, so it will drive a current to the tripping system which depends on the
difference between phase and neutral currents. When the amount of residual current, and
hence of tripping current, reaches a pre-determined level, the circuit breaker trips,
opening the main contacts and interrupting the circuit.

For circuit breakers operating at low residual current values, an amplifier may be used in
the trip circuit. Since the sum of the currents in the phases and neutral of a three-phase
supply is always balanced, the system can be used just as effectively with three-phase
supplies. In high current circuits, it is more usual for the
Fig 5.23 Residual current circuit breaker

phase and neutral conductors to simply pass through the magnetic core instead of round
coils wound on it.

Operation depends on a mechanical system, which could possibly become stiff when old
or dirty. Thus, regular testing is needed, and the RCD is provided with a test button
which provides the rated level of residual current to ensure that the circuit breaker will
operate. All RCDs are required to display a notice which draws attention to the need for
frequent testing which can be carried out by the user, who presses a test button, usually
marked T. {Table 5.10} shows the required notice.

This installation, or part of it, is protected by a device which


automatically switches off the supply if an earth fault develops.
Test quarterly by pressing the button marked 'T' or 'Test'. The device
should switch off the supply, and should then be switched on to restore
the supply. If the device does not switch off the supply when the button
is pressed, seek expert advice

Table 5.10 - Periodic test notice for residual current device

The test circuit is shown in {Fig 5.23}, and provides extra current in the phase coil when
the test button is pressed. This extra current is determined by the value of the resistor R.

There are currently four basic types of RCD. Class AC devices are used where the
residual current is sinusoidal - this is the normal type which is in the most wide use. Class
A types are used where the residual current is sinusoidal and/or includes pulsating direct
currents - this type is applied in special situations where electronic equipment is used.
Class B is for specialist operation on pure direct current or on impulse direct or
alternating current. Class S RCDs have a built-in time delay to provide discrimination
(see below).
It must be understood that the residual current is the difference between phase and neutral
currents, and that the current breaking ability of the main contacts is not related to the
residual operating current value, There is a widely held misunderstanding of this point,
many people thinking that the residual current setting is the current breaking capability of
the device. It is very likely that a device with a breaking capacity of 100 A may have a
residual operating current of only 30 mA.

There are cases where more than one residual current device is used in an installation; for
example, a complete installation may be protected by an RCD rated at 100 mA whilst a
socket intended for equipment outdoors may be protected by a 30 mA device.
Discrimination of the two devices then becomes important. For example, if an earth fault
giving an earth current of 250 mA develops on the equipment fed by the outdoor socket,
both RCDs will carry this fault current, and both will become unbalanced. Since the fault
is higher than the operating current of both devices, both will have their trip systems
activated. It does not follow that the device with the smaller operating current will open
first, so it is quite likely that the 100 mA device will operate, cutting off the supply to the
complete installation even though the fault was on a small part of it. This is a lack of
discrimination between the residual current devices. To ensure proper discrimination, the
device with the larger operating current has a deliberate delay built into its operation. It is
called a time delayed RCD.

5.9.3 - Regulations for residual current devices

The primary purpose of the residual current device is to limit the severity of shock due to
indirect contact. In other words, it will detect and clear earth faults which otherwise
would could lead to dangerous potential differences between pieces of metalwork which
are open to touch. If the sensitivity of the device (its operating residual current) is low
enough, it may also be used to limit the shock received from direct contact in the case of
the failure of other measures. A problem which may occur here is nuisance tripping,
because the operating current may be so low that normal leakage current will cause
operation. For example an RCD with a sensitivity of 2 mA will switch off the supply as
soon as a shock current of 2 mA flows, virtually preventing a fatal shock. The difficulty
is that normal insulation resistance leakage and stray capacitance currents can easily
reach this value in a perfectly healthy system, and it may thus be impossible to keep the
circuit breaker closed. The sum of the leakage currents in circuits protected by an RCD
should never be more than 25% of the operating current of the device. Normal earth
leakage current from equipment and appliances will, of course vary with the condition of
the device. Maximum permitted leakage currents are listed in Appendix L of the 2nd
Edition of Guidance Note 1, and vary from 0.25 mA for Glass II appliances to 3.5mA for
information technology equipment (see {7.8.2})

Some RCDs (usually electronic types) will not switch off unless the mains supply is
available to provide power for their operation. In such a case, mains failure may prevent
tripping whilst danger is still present, (due to, for example, charged capacitors). Such
RCDs may only be used where there is another means of protection from indirect contact,
or where the only people using the installation are skilled or instructed so that they are
aware of the risk.

In some cases RCD are designed so that their operating parameters, such as the rated
residual current or the time delay, can be adjusted. If such an RCD can be operated by an
ordinary person (rather than by a skilled or instructed person then such adjustments must
only be possible by a deliberate act using a key or a tool which results in a visible
indication of the setting.

If a residual current circuit breaker is set at a very low sensitivity, it can prevent death
from electric shock entirely. However, the problem is that a safe current cannot be
determined, because it will vary from person to person, and also with the time for which
it is applied. The Regulations require a sensitivity of 30 mA for RCDs intended to
provide additional protection from direct contact.

An RCD must not be used in an installation with neutral and earth combined (TNG
system using a PEN conductor) because there will be no residual current in the event of a
fault to cause the device to operate, since there is no separate path for earth fault currents.

RCD protection is required for socket outlets where:

1. - they are part of a TT system (no earth terminal provided by the Electricity Supply
Company),

2. - they are installed in a bedroom which contains a shower cubicle, or

3. - the socket outlet(s) are likely to feed portable equipment used outdoors.

4. -they are installed in zones B or C of a swimming pool and comply with BS EN


60309-2.

Protection by an RCD with a rating of 30 mA is required for fixed electrical equipment


installed in a bathroom or in zone C of a swimming pool.

Although residual current devices are current-operated, there are circumstances where the
combination of operating current and high earth-fault loop impedance could result in the
earthed metalwork rising to a dangerously high potential. The Regulations draw attention
to the fact that if the product of operating current (A) and earth-fault loop impedance
exceeds 50, the potential of the earthed metalwork will be more than 50 V above earth
potential and hence dangerous. This situation must not be allowed to arise
Fig 5.24 - Danger with an RCD when earth-fault loop impedance is high. In this
case, p.d. from earth to exposed conductive parts will be 1000 Ohms x 0.09 A = 90 V

RCDs must he tested to ensure correct operation within the required operating times.
Such tests will be considered in {8.6.3}.

Special requirements apply to RCDs used to protect equipment having normally high
earth leakage currents, such as data processing and other computer-based devices. These
installations are considered in {7.8.2}.

5.9.4 - Fault voltage operated circuit breakers

These circuit breakers, commonly known in the trade as 'voltage ELCBs', were deleted
from the 15th Edition of the Wiring Regulations in 1985, and should not be installed. It is
advisable that installations where they are still in use should be carefully tested prior to a
change to residual current device protection.

5.10 - Combined functional and protective earthing

The previous section has made it clear that high earth leakage currents can cause
difficulties in protection. The increasing use of data processing equipment such as
computers has led to the need for filters to protect against transients in the installation
which could otherwise result in the loss of valuable data. Such filters usually include
capacitors connected between live conductors and earth. This has led to large increases in
normal earth currents in such installations, and to the need for special regulations for
them. Since these are special situations, they will be considered in detail in {7.8}.

Electrical disturbances on the earth system (known as 'earth noise') may cause
malfunctions of computer based systems, and 'clean' mains supplies and earth
systems may be necessary. A separate earthing system may be useful in such a case
provided that:
1. -the computer system has all accessible conductive parts earthed,

2. - the main earthing terminal of the computer earth system is connected directly to the
main earthing terminal,

3. -all extraneous conductive parts within reach of the computer system are earthed to the
main earthing terminal and not to the separate computer earth.

Supplementary bonding between the computer earth system and extraneous conductive
parts is not necessary.

Chapter 6 : Circuits

6.1. - Basic requirements for circuits 6.4 - Industrial socket outlet circuits
6.5 - Other
6.2 - Maximum demand and diversity
circuits
6.6 - Circuit
6.3 - BS1363 socket outlet circuits
segregation

6.1.1 - Basic requirements for circuits

The Regulations require that installations should be divided into circuits, the purposes
being:

1. - to prevent danger in the event of a fault by ensuring that the fault current is no greater
than necessary to operate the protective system. For example, a large three-phase motor
must be connected to a single circuit because the load cannot be subdivided. If, however,
a load consisted of three hundred lamps, each rated at 100 W, it would be foolish to
consider putting all this load onto a single circuit. In the event of a fault, the whole of the
lighting would be lost, and the fault current needed to operate the protective device
(single-phase circuit current would be 125 A at 240 V) would be high enough to cause a
fire danger at the outlet where the fault occurred. The correct approach would be to
divide the load into smaller circuits, each feeding, perhaps, ten lamps.

2. - to enable part of an installation to be switched off for maintenance or for testing


without affecting the rest of the system.

3. - to prevent a fault on one circuit from resulting in the loss of the complete installation
(see {3.8.6} on the subject of discrimination).

The number of final circuits will depend on the types of load supplied, and must be
designed to comply with the requirements for overcurrent protection, switching and the
current-carrying capacity of conductors. Every circuit must be separate from others and
must be connected to its own overcurrent protective fuse or circuit breaker in a switch
fuse, distribution board, consumer's unit, etc. See {Fig 6.1 and Fig 6.2}.

Fig 6.1 Typical arrangement for feeding final circuits in a domestic installation
Fig 6.2 An arrangement for main and final circuits in a large installation

A durable notice giving details of all the circuits fed is required to be posted in or near
each distribution board. The data required is the equipment served by each circuit, its
rating, its design current and its breaking capacity. When the occupancy of the premises
changes, the new occupier must be provided with full details of the installation (see
reference to the Operating Manual in {8.8.1}). This data must always be kept up to date.
6.2.1 -Maximum demand

6.2.2 - Diversity

6.2.3 - Applied diversity

6.2.1 -Maximum demand

Maximum demand (often referred to as MD) is the largest current normally carried by
circuits, switches and protective devices; it does not include the levels of current flowing
under overload or short circuit conditions, Assessment of maximum demand is
sometimes straightforward. For example, the maximum demand of a 240 V single-phase
8 kW shower heater can be calculated by dividing the power (8 kW) by the voltage (240
V) to give a current of 33.3 A. This calculation assumes a power factor of unity, which is
a reasonable assumption for such a purely resistive load.

There are times, however, when assessment of maximum demand is less obvious. For
example, if a ring circuit feeds fifteen 13 A sockets, the maximum demand clearly should
not be 15 x 13 = 195 A, if only because the circuit protection will not be rated at more
than 32 A. Some 13 A sockets may feed table lamps with 60 W lamps fitted, whilst
others may feed 3 kW washing machines; others again may not be loaded at all. Guidance
is given in {Table 6.1}.

Lighting circuits pose a special problem when determining MD. Each lamp-holder must
be assumed to carry the current required by the connected load, subject to a minimum
loading of 100 W per lampholder (a demand of 0.42 A per lampholder at 240 V).
Discharge lamps are particularly difficult to assess, and current cannot be calculated
simply by dividing lamp power by supply voltage. The reasons for this are:

1. - control gear losses result in additional current,

2 . -the power factor is usually less than unity so current is greater, and

3. - chokes and other control gear usually distort the waveform of the current so that it
contains harmonics which are additional to the fundamental supply current.

So long as the power factor of a discharge lighting circuit is not less than 0.85, the current
demand for the circuit can be calculated from:

current (A) = lamp power (W) x 1.8


supply voltage (V)

For example, the steady state current demand of a 240 V circuit supplying ten 65 W
fluorescent lamps would be:

I= 10 x 65 x 1.8 A = 4.88A
240

Switches for circuits feeding discharge lamps must be rated at twice the current they are
required to carry, unless they have been specially constructed to withstand the severe
arcing resulting from the switching of such inductive and capacitive loads.

Table 6.1 - Current demand of outlets

Type of outlet Assumed current demand


2 A socket outlet At least 0.5A
Other socket outlets Rated current
Connected load, with minimum
Lighting point
of 100 W
Shaver outlet, bell transformer
or any equipment of 5 W or May be neglected
less
10A + 30% of remainder + 5A
Household cooker
for socket in cooker unit

When assessing maximum demand, account must he taken of the possible growth in
demand during the life of the installation. Apart from indicating that maximum demand
must be assessed, the Regulations themselves give little help. Suggestions for the
assumed current demand of various types of outlet are shown in {Table 6.1}.

6.2.2 -Diversity

A domestic ring circuit typically feeds a large number of 13 A sockets hut is usually
protected by a fuse or circuit breaker rated at 30 A or 32 A. This means that if sockets
were feeding 13 A loads, more than two of them in use at the same time would overload
the circuit and it would be disconnected by its protective device.

In practice, the chances of all domestic ring sockets feeding loads taking 13 A is
small. Whilst there maybe a 3 kW washing machine in the kitchen, a 3 kW heater in the
living room and another in the bedroom, the chance of all three being in use at the same
time is remote. If they are all connected at the same time, this could be seen as a failure
of the designer when assessing the installation requirements; the installation should have
two ring circuits to feed the parts of the house in question.

Most sockets, then, will feed smaller loads such as table lamps, vacuum cleaner,
television or audio machines and so on. The chances of all the sockets being used
simultaneously is remote in the extreme provided that the number of sockets (and ring
circuits) installed is large enough. The condition that only a few sockets will be in use at
the same time, and that the loads they feed will be small is called diversity.
By making allowance for reasonable diversity, the number of circuits and their rating can
be reduced, with a consequent financial saving, but without reducing the effectiveness of
the installation. However, if diversity is over-estimated, the normal current demands will
exceed the ratings of the protective devices, which will disconnect the circuits - not a
welcome prospect for the user of the installation! Overheating may also result from
overloading which exceeds the rating of the protective device, but does not reach its
operating current in a reasonably short time. The Regulations require that circuit design
should prevent the occurrence of small overloads of long duration.

The sensible application of diversity to the design of an installation calls for experience
and a detailed knowledge of the intended use of the installation. Future possible increase
in load should also be taken into account. Diversity relies on a number of factors which
can only be properly assessed in the light of detailed knowledge of the type of
installation, the industrial process concerned where this applies, and the habits and
practices of the users, Perhaps a glimpse into a crystal ball to foresee the future could also
be useful!

6.2.3 -Applied diversity

Apart from indicating that diversity and maximum demand must be assessed, the
Regulations themselves give little help. Suggestions of values for the allowances
for diversity are given in {Table 6.2}.
Distribution boards must not have diversity applied so that they can carry the total load
connected to them.

Example 6.1
A shop has the following single-phase loads, which are balanced as evenly as possible
across the 415 V three-phase supply.

2 x 6 kW and 7 x 3kw thermostatically controlled water heaters


2 x 3 kW instantaneous water heaters
2 x 6 kW and 1 x 4 kW cookers
12 kW of discharge lighting (Sum of tube ratings)
8 x 30 A ring circuits feeding 13 A sockets.

Calculate the total demand of the system, assuming that diversity can be applied.
Calculations will be based on {Table 6.2}.

The single-phase voltage for a 415V three-phase system is 415/√ 3 = 240 V.

All loads with the exception of the discharge lighting can be assumed to be at unity
power factor, so current may be calculated from

l= P
U
Thus the current per kilowatt will be

1000 A = 4.17 A
240

Table 6.2 - Allowance for diversity

Note the following abbreviations :


X is the full load current of the largest appliance or circuit
Y is the full load current of the second largest appliance or circuit
Z is the full load current of the remaining appliances or circuits
Type of
Type of final circuit
premises
Small shops, Hotels, guest
Households
stores, offices houses
90% total 75% total
Lighting 66% total demand
demand demand
100% up to 10 A + 100%X + 100%X + 80%Y
Heating and power
50% balance 75%(Y+Z) + 60%Z
10 A + 30% balance + 100%X + 80%Y 100%X + 80%Y
Cookers
5 A for socket + 60%Z + 60%Z
100%X + 80%Y 100%X +
Motors (but not lifts)
+ 60%Z 50%(Y+Z)
Instantaneous water 100%X + 100%Y + 100%X + 100%Y 100%X +
heaters 25%Z + 25%Z 100%Y + 25%Z
Thermostatic water
100% 100% 100%
heaters
Floor warming
100% 100% 100%
installations
Thermal storage
100% 100% 100%
heating
100%X + 100%X +
Standard circuits 100%X + 40%(Y+Z)
50%(Y+Z) 50%(Y+Z)
Sockets and 100%X + 100%X + 75%Y
100%X + 40%(Y+Z)
stationary equip. 75%(Y+Z) + 40%Z

Water heaters (thermostatic)

No diversity is allowable, so the total load will be:


(2 x 6) + (7 x 3) kW = 12 + 21kw = 33kw
This gives a total single-phase current of I = 33 x 4.17 = 137.6 A

Water heaters (instantaneous)

100% of largest plus 100% of next means that in effect there is no allowable
diversity.
= 2 x 3 x 4.17 =
Single-phase current thus 25.0 A

Cookers

100% of largest = 6 x 4.17A = 25.0 A


= 80 x 6 x 4.17A
80% of second 20.0 A
=
=100
60% of remainder = 60 x 4 x 4.17 A = 10.0 A
=100
Total for cookers
= 55.O A

Discharge lighting

90% of total which must be increased to allow for power factor and control
gear losses.

Lighting current = 12 x 4.17 x 1.8 x 90 = 81.1 A


100

Ring circuits

First circuit 100%, 50 current is 30 A


= 7 x 30 x 75
75% of remainder 157.5 A
=
100
Total current demand for ring circuits = 187.5 A
Total single phase current demand = 486.2 A
486.2
Since a perfect balance is assumed, three phase line current =
A
=3
= 162 A

6.3.1 - The fused plug

6.3.2 - The ring final circuit


6.3.3 - The radial circuit

6.3.1 - The fused plug

In many situations there is a need for socket outlets to be closely spaced so that they are
available to feed appliances and equipment without the need to use long and potentially
dangerous leads. For example, the domestic kitchen worktop should be provided with
ample sockets to feed the many appliances (deep fat fryer, kettle, sandwich toaster,
carving knife, toaster, microwave oven, coffee maker, and so on) which are likely to be
used. Similarly, in the living room we need to supply television sets, video recorders,
stereo players, table lamps, room heaters, etc. In this case, more outlets will he needed to
allow for occasional rearrangement of furniture, which may well obstruct access to some
outlets.

If each one of these socket outlets were wired back to the mains position or to a local
distribution board, large numbers of circuits and cables would be necessary, with
consequent high cost. The alternative is the provision of fewer sockets with the penalties
of longer leads and possibly the use of multi-outlet adaptors. Because the ideal situation
will have closely-spaced outlets, there is virtually no chance of more than a small
proportion of them being in use at the same time, so generous allowance can be made for
diversity. Thus, cables and protective devices can safely he smaller in size than would he
needed if it were assumed that all outlets were simultaneously fully loaded.

Thus a ring circuit protected by a 30 A or 32 A device may well feed twenty socket
outlets. It follows that judgement must be used to make as certain as possible that the
total loading will not exceed the protective device rating, or its failure and inconvenience
will result. Two basic steps will normally ensure that a ring circuit is not overloaded.

1. - Do not feed heavy and steady loads (the domestic immersion heater is the most
obvious example) from the ring circuit, but make special provision for them on separate
circuits.

2. -Make sure that the ring circuit does not feed too great an area. This is usually
ensured by limiting a single ring circuit to sockets within an area not greater than one
hundred square metres.
Fig 6.3 Plug and socket to BS 1363

We have already indicated that a 30 A or 32 A fuse or circuit breaker is likely to protect a


large number of outlets. If this were the only method of protection, there could be a
dangerous situation if, for example, a flexible cord with a rating of, say, 5 A developed a
fault between cores. {Figure 3.13} shows that a 30 A semi-enclosed fuse will take 5 s to
operate when carrying a current of almost 90 A, so the damage to the cord would be
extreme. Because of this a further fuse is introduced to protect the appliance and its cord.
The fuse is inside the BS 1363 plug, and is rated at 13 A or 3 A, although many other
ratings up to 12 A, which are not recognised in the BSS, are available.

A plug to BS 1363 without a fuse is not available. The circuit protection in the
distribution board or consumer's unit covers the circuit wiring, whilst the fuse in the plug
protects the appliance and its cord as shown in {Fig 6.4}. In this way, each appliance can
be protected by a suitable fuse, for example, a 3 A fuse for a table lamp or a 13 A fuse for
a 3 kW fan heater.

Whilst the installer of the wiring is seldom concerned with the flexible cords of
appliances connected to it, he must still offer guidance to users. This will include fitting 3
A fuses in plugs feeding low rated appliances, and the use of flexible cords which are of
sufficient cross-section and are as short as possible in the circumstances concerned.
Generally, 0.5 mm² cords should be the smallest size connected to plugs fed by 30 A or
32 A ring circuits. Where the cord length must he 10 m or greater, the minimum size
should be 0.75 mm² and rubber-insulated cords are preferred to those that are PVC
insulated.

This type of outlet is not intended for use at high ambient temperatures. A common
complaint is the overheating of a fused plug and socket mounted in an airing cupboard to
feed an immersion beater; as mentioned above, it is not good practice to connect such a
load to a ring circuit, and if unavoidable, final connection should be through a fused spur
outlet.

Fig 6.4 Principle of appliance protection by plug fuse

The British fused plug system is probably the biggest stumbling block to the introduction
of a common plug for the whole of Europe (the 'europlug'). The proposed plug is a
reversible two~pin type, so would not comply with the Regulations in terms of correct
polarity. If we were to adopt it, every plug would need adjacent fuse protection, or would
need to be rewired back to its own protective device. In either case, the cost would be
very high.

Ring circuits fed from systems where no earth terminal is provided by the Electricity
Supply Company (TT systems) must be protected by an RCD rated at 30 mA, In all
installations, a socket intended to feed equipment outdoors must be individually protected
by a 30 mA RCD.

Where a socket is mounted on a vertical wall, its height above the floor level or

the working surface level level must be such that mechanical damage is unlikely. A
minimum mounting height of 150 mm is recommended.

6.3.2 - The ring final circuit

The arrangement of a typical ring circuit is shown in {Fig 6.5} and must comply with the
following requirements.
Fig 6.5 Ring circuit feeding socket outlets to BS 1363

1. - The floor area served by each ring must not exceed 100 m² for domestic situations,
Where ring circuits are used elsewhere (such as in commerce or industry) the diversity
must be assessed to ensure that maximum demand will not exceed the rating of the
protective device.

2. - Consideration should be given to the provision of a separate ring (or radial) circuit in
a kitchen.

3. -Where there is more than one ring circuit in the same building, the
installed sockets should be shared approximately evenly between them.

4. -Cable sizes for standard circuits are as follows:

a) p.v.c. insulated cable are 2.5 mm² for live (phase and neutral) conductors and
--- 1.5mm² for the CPC.

b) mineral insulated: 1.5mm²for all conductors.

These sizes assume that sheathed cables are clipped direct, are embedded in plaster, or
have one side in contact with thermally insulating material. Single core cables are
assumed to be enclosed in conduit or trunking. No allowance has been made for circuits
which are bunched, and the ambient temperature is assumed not to exceed 30°C.

5. - The number of unfused spurs fed from the ring circuit must not exceed the number of
sockets or fixed appliances connected directly in the ring.

6. -Each non-fused spur may feed no more than one single or one twin socket, or no
more than one fixed appliance.

7. -Fixed loads fed by the ring must be locally protected by a fuse of rating
no greater than 13 A or by a circuit breaker of maximum rating 16 A.

8. - Fixed equipment such as space heaters, water heaters of capacity greater than 15
litres, and immersion heaters, should not be fed by a ring, but provided with their own
circuits.

6.3.3 - The radial circuit

Two types of radial circuit are permitted for socket outlets. In neither case is the number
of sockets to be supplied specified, so the number will be subject to the constraints of
load and diversity. The two standard circuits are:

1. - 20 A fuse or miniature circuit breaker protection with 2.5 mm² live and 1.5mm²
protective conductors (or 1.5 mm² if m.i. cable) feeding a floor area of not more than 50
m². If the circuit feeds a kitchen or utility room, it must be remembered that a 3 kW
device such as a washing machine or a tumble dryer takes 12.5 A at 240 V and that this
leaves little capacity for the rest of the sockets.

2. - 32 A cartridge fuse to B888 or miniature circuit breaker feeding through 4 mm² live
and 2.5 mm² protective conductors (or 2.5 mm² and 1.5 mm² if m.i. Cable) to supply a
floor area no greater than 75m².

The arrangement of the circuits is shown in (Fig 6.6). 4mm² may seem to be a large cable
size in a circuit feeding 13 A sockets. It must be remembered, however, that the 2.5 mm²
ring circuit allows current to be fed both ways round the ring, so that two conductors are
effectively in parallel, whereas the 4 mm² cable in a radial circuit must carry all the
current.
Fig 6.6 - Radial circuits

Radial circuits can be especially economic in a long building where the completion of a
ring to the far end could effectively double the length of cable used. As for ring circuits,
danger can occur if flexible cords are too small in cross-section, or are too long, or if 3 A
fuses are not used where appropriate.

The minimum cross-sectional area for flexible cords should be:

0.5mm² where the radial circuit is protected by a 16 A fuse,


0.75mm² for a 20 A fuse,
or 1.0mm² for a 30 A or 32 A fuse.

6.4.1 - Introduction

6.4.2 - BS 196 socket outlet circuits

6.4.3 - BS EN 60309-1 (BS 4343)


--------- socket outlet circuits

6.4.1 - Introduction

There is no reason at all to prevent the installation of BS 1363 (13 A) socket outlets in
industrial situations. Indeed, where light industry, such as electronics manufacture, is
concerned, these sockets are most suitable. However, heavy duty industrial socket outlets
are available, and this type is the subject of this section.

6.4.2 - BS 196 socket outlet circuits

BS 196 sockets are two-pin, non-reversible, with a scraping earth connection. The fusing
in the plug can apply to either pole, or the plug may be unfused altogether.
Interchangeability is prevented by means of a keyway which may have any of eighteen
different positions, identified by capital letters of the alphabet (see {Fig 6.7}). They are
available with current ratings of 5 A, 15 A or 30 A.

Fig 6.7 Arrangement of socket outlet to BS 196.


Two of the eighteen possible keyway positions are shown

Circuit details for wiring ES 196 outlets can be summarised as:

1. - the maximum protective device rating is 32 A

2. - all spurs must be protected by a fuse or circuit breaker of rating no larger than 16 A -
this means that 30 A outlets cannot be fed from spurs

3. - the number of sockets connected to each circuit is unspecified, but proper judgement
must be applied to prevent failure of the protective device due to overload

4. - cable rating must be no less than that of the protective device for radial circuits, or
two thirds of the protective device rating for a ring circuit

5. - on normal supplies with an earthed neutral, the phase pole must be fused and the
keyway must be positioned at point B (see {Fig 6.7})
6. - when the socket is fed at reduced voltage from a transformer with the centre tap on its
secondary winding earthed {Fig 6.8}, both poles of the plug must be fused and the
keyway must be positioned at P.

Fig 6.8 - Circuit fed from a transformer with a centre-tapped secondary winding

6.4.3 -BS EN 60309-1 (BS 4343) socket outlet circuits

Plugs and sockets to BS EN 60309-1 are for industrial applications and are rated at 16 A,
32 A, 63 A and 125 A. All but the smallest size must be wired on a separate circuit, but
16 A outlets may be wired in unlimited numbers on radial circuits where diversity can be
justified. However, since the maximum rating for the protective device is 20 A, the
number of sockets will be small except where loads are very light or where it is certain
that few loads will be connected simultaneously. An arrangement of BS EN 60309-2
plugs and sockets is shown in {Fig 6.9}.

Fig 6.9 - Plugs and sockets to BS EN 60309-2

6.5.1 - Lighting circuits


6.5.2 - Cooker circuits

6.5.3 - Off-peak appliance circuits

6.5.1 - Lighting circuits

Lampholders and ceiling roses must not be used in installations where the supply voltage
exceeds 250 V. Where bayonet cap (BC) or edison screw (ES) lampholders are used, the
protective device rating is limited to the values shown in {Table 6.3}, unless the
lampholders and the associated wiring are enclosed within a fireproof enclosure, such as
a luminaire (lighting fitting), or unless they have separate over-current protection in the
form of a local fuse or circuit breaker.

Lampholders are often mounted within enclosed spaces such as lighting fittings, where
the internal temperature may become very high, particularly where filament lamps are
used. Care must be taken to ensure that the lampholders, and their associated wiring, are
able to withstand the temperature concerned. Where ES lampholders are connected to a
system with the neutral at earth potential (TT or TN systems) care must be taken to
ensure that the centre contact is connected to the phase conductor and the outer screw to
the neutral to reduce the shock danger in the event of touching the outer screw during
lamp changing (see {Fig 6.10}).

Table 6.3 - Overcurrent protection of lampholders


Type of lampholder - Maximum rating of protective device (A)
Bayonet cap SBC 6
BC 16
Edison screw SES 6
ES 16
GES 16
Fig 6.10 - Correct connection of ES lampholder

Ceiling roses must not have more than one flexible cord connected to them, and, like the
flexible cords themselves, must not be subjected to greater suspended weight than their
design permits (see {Table 4.2}). Lampholders in bath or shower rooms must be fitted with
a protective shield to prevent contact with the cap whilst changing the lamp (see {Fig
6.11}).

In large lighting installations, particularly where fluorescent fittings are involved,


consideration should be given to the use of luminaire support couplers (LSCs) or plugs
and sockets. Such arrangements facilitate the disconnection of luminaires for electrical
maintenance and for cleaning, and may also allow the complete testing of an installation
before erection of the luminaires. Many lighting installations are now controlled by
sophisticated software (which may switch off the lighting when daylight levels increase
or when a room has been unoccupied for a predetermined time). Such devices must be
installed to comply with the Regulations.
Fig 6.11 - Protective shield for a BC lampholder

6.5.2 - Cooker circuits

A cooker is regarded as a piece of fixed equipment unless it is a small table-mounted type


fed from a plug by a flexible cord. Such equipment must be under the control of a local
switch, usually in the form of a cooker control unit. This switch may control two cookers,
provided both are within 2 m of it. In many cases this control unit incorporates a socket
outlet, although often such a socket is not in the safest position for use to supply portable
appliances, whose flexible cords may be burned by the hotplates. It is often considered
safer to control the cooker with a switch and to provide a separate socket circuit. The
protective device is often the most highly rated in a') installation, particularly in a
domestic situation, so there is a need to ensure that diversity has been properly calculated
(see Table {6.2}).

The diversity applicable to the current demand for a cooker is shown in {Table 6.2} as 10
A plus 30% of the remainder of the total connected load, plus 5 A if the control unit
includes a socket outlet. A little thought will show that whilst this calculation will give
satisfactory results under most circumstances, there is a danger of triggering the
protective device under some circumstances. For example, at Christmas it is quite likely
that both ovens, all four hotplates and a 3 kW kettle could he simultaneously connected.
Just imagine the chaos which a blown fuse would cause! This alone is a very good reason
for being generous with cable and protective ratings.

Example 6.2
A 240 V domestic cooker has the following connected loads:

top oven 1.5 kW


main oven 2.5 kW
grill 2.0kw
four hotplates 2.0 kW each

The cooker control unit includes a 13 A socket outlet. Calculate a suitable rating for the
protective device.

The total cooker load is 1.5 + 2.5 + 2.0 + (4 x 2.0) kW = 14 kW

Total current =P= 14000 A = 58.3A


U 240==

The demand is is made up of:

= 10.0
the first 10 A
A
= 30 x (58.3 30 x 48.3 = 14.5
+ 30% of remainder
- 10) = A
100 100
+ allowance for socket outlet = 5.O
A
total = 29.5 A

A 30 A protective device is likely to be chosen. The cable rating will depend on


correction factors (see {Chapter 5}).

6.5.3 - Off-peak appliance circuits

All Electricity Supply Companies offer extremely economic rates for energy taken at off-
peak times, usually for seven hours each night (economy 7). The supply meter is usually
arranged so that off-peak inexpensive energy can only be obtained from a special pair of
terminals, whilst a second pair provide energy throughout the 24 hour period, charging
for it in terms of the times at which it is taken. In most cases, energy used at the cheap
rate must be stored for use at other times. There are two major methods of storing energy,
in both cases involving its conversion to heat.
1. -storage heaters, which are used for space heating. Circuits feeding them should
always be wired radially, with only one flexible outlet for each. This will help to avoid
problems in the event of the storage heater being changed for one of a different power
rating.

2. - immersion heaters, the energy being stored as hot water in a lagged tank for use
during the day. Since the amount of hot water used is variable, it is usually necessary to
have a method of increasing the water temperature should that heated at the cheap rate be
used up. This involves the use of a second immersion heater, or a single heater with a
double element. Since convection, and hence water heating, takes place mainly above the
active heater, an immersion heater placed low in the tank and fed by the off-peak supply
will heat the whole tank, whilst a second heater, placed higher in the tank and connected
to the normal supply, will be switched on when necessary to top up the temperature of the
hot water stored (Fig 6.12(a)). Sometimes a top mounted dual heater is used for the same
purpose as shown in (Fig 6.12(b)). The normal and off-peak heaters must be supplied
through totally separate circuits. 3 kW heaters must be connected permanently to a
double pole switch and not fed via a plug and socket.

Fig 6.12 - Arrangement of immersion heaters for off-peak supplies

6.6.1 - Segregating circuits

6.6.2 - Electromagnetic compatibility (EMC)

6.6.3 - Lift and hoist shaft circuits

6.6.1 - Segregating circuits

The 15th and 16th editions of the IEE Wiring Regulations applied segregation of circuits
which need to be kept apart by classifying them in four separate categories (the Regs
themselves only mentioned three categories, but since two types of circuit both
categorised as 3 had to be separated from each other, there were effectively four
categories).
The second amendments to BS 7671 (published in 1997) have simplified the situation.
There are now only two categories, which are known as voltage bands.

Voltage Band I is defined as levels of voltage which are too low to provide serious
electric shocks; effectively this limits the band to extra-low voltage (ELV), including
telecommunications, signalling, bell, control and alarm circuits.

Voltage Band II covers all voltages used in electrical installations not included in Band
I. This means that all 230/400 V (240/415 V) supplies are included in Band II.

As expected, BS 7671 prohibits Band I and Band II cables sharing the same cable
enclosure or multicore cable unless: every cable is insulated for the highest voltage
present,
or each conductor in a multicore cable is insulated for the highest voltage present, unless
conductors of the two bands are separated by an earthed metal screen,
or they are installed in separate compartments of a trunking or ducting system, or they are
installed on a tray with a partition providing separation,
or a separate conduit or ducting system is provided for each band.

This does mean that BS 7671 allows circuits such as those for fire alarm Systems,
emergency lighting, telephones, data transmission, intruder alarms, sound systems, bell
and call systems, etc., may now be run together without segregation. BS 5838: 1988, on
the other hand. makes it clear that fire alarm cables must be separated from all others, and
IEE Guidance Note 4 requires that escape lighting cables should be mineral insulated or
separated from all others by at least 300 mm. Care must be taken to ensure that circuits
are not affected by electrical interference, both electrostatic (due to electric fields) or
electro-magnetic (due to electro-magnetic fields). In some ways this makes the circuit
designer's task more difficult, because he must now ensure that there will be no
interference, whereas before, he simply had to ensure that the required segregation was
employed.

In some instances it will be necessary for circuit outlets for both voltage bands to share a
common box; switchplate or block. In such a case, the connections of circuits of differing
bands must be segregated by a partition, which must be earthed if of metal.

6.6.2 - Electromagnetic compatibility (EMC)

All electrical equipment must be selected and installed so that it will not affect the supply
or cause harmful effects to other equipment. One of the harmful effects is
electromagnetic interference (EMI). Whenever current flows in a conductor it sets up a
magnetic field; a change in the current will result in a corresponding change in the
magnetic field, which will result in the induction of electromotive force (voltage) in any
conducting system subject to the field. Whilst induced voltages will usually be very
small, they may be considerable when rates of change of current are heavy (for example,
circuits feeding lift motors) or when there is a lightning strike in the vicinity.
The effects are most pronounced when large metal loops are formed by circuits (perhaps
power and data circuits) which are run at a distance from each other but have common
earthing and bonding. Power and data cables need to follow common routes to prevent
aerial loops which will be subject to induced e.m.f., but with sufficient spacing to prevent
interference between them (see{Table 6.4}). The emission standard is BS EN 50081 and
the immunity standard BS EN 50082.

The designer needs to consider EMC when planning an installation, and may decide that
some of the following measures are appropriate:

providing surge protectors and filters for sensitive equipment, proper separation of power
and other cables to limit electro-magnetic interference (EMI),
using bonding connections which are as short as possible, screening sensitive equipment
and bonding of metal enclosures, and avoiding inductive loops by using the same route
for cables of different systems.

This list is far from exhaustive.

Table 6.4 - Proposed EMI cable separation distances


Power
Power
cable Min. separation btw Min separation btw
cable
voltage power & signal cables, power & signal cables,
current
m m

115 V 0.25 ----5 A 0.24


240 V 0.45 --15 A 0.35
415 V 0.58 --50 A 0.50
3.3 kV 1.10 100 A 0.60
6.6 kV 1.25 300 A 0.85
11 kV 1.40 600 A 1.05

6.6.3 - Lift and hoist shaft circuits

A lift shaft may well seem to be an attractive choice for running cables, but this is not
permitted except for circuits which are part of the lift or hoist installation (see {Fig
6.13}). The cables of the lift installation may be power cables fixed in the shaft to feed
the motor(s), or control cables which feed call buttons, position indicators, and so on.
Trailing cables will feed call buttons, position indicators, lighting and telephones in the
lift itself.
Fig 6.13 - Cables installed in lift or hoist shafts

Chapter 7 : Special Instalations

1. - Introduction --2. - Bath tubs and shower basins

--4. - Sauna
--3. - Swimming pools
rooms

--6. -
Agricultural
--5. - Installations on construction sites
&
horticultural

--8. -
Earthing for
--7. - Restrictive conductive locations
function &
protection

10. -
Highway
--9. - Caravan, motor homes, caravan parks power &
street
furniture

11. - Heating appliances & installations 12. -


Discharge
lighting

14. -
Outdoor
13. - Underground & overhead wiring installations
& garden
buildings

16. -
15. - Installations of machines & Reduced
transformers voltage
systems

18. -
17. - Marinas Medical
locations

19. - Exhibitions, shows and stands

7.1 - Introduction

The Regulations apply to all electrical installations in buildings. There are some
situations out-of-doors, as well as special indoor ones, which are the subject of special
requirements due to the extra dangers they pose, and these will be considered in this
chapter. These Regulations are additional to all of the other requirements, and not
alternatives to them.

7.3.1 - Introduction

7.3.2 - Special requirements for swimming pools

7.3.1 - Introduction

People using a swimming pool are often partly unclothed and wet. The absence of
clothing (particularly shoes) will remove much of their protection from shock (see {3.4}),
and the water on their skin will tend to short circuit its natural protection. Thus, such
people are very vulnerable to electric shock due to their reduced body resistance, so
special measures are needed to ensure that the possibility of contact (either direct or
indirect) is much reduced. Only separated extra-low voltage (SELV) equipment may be
installed, other than water heaters in zones B and C, and equipment specially designed to
be safe in the vicinity of swimming pools.

Special Regulations for electrical installations in swimming pools are new in the 16th
Edition. Guidance Note 7 makes it clear that the basins of fountains intended to be
occupied by persons (becoming quite common in some leisure applications) are subject to
the same regulations as swimming pools; in fact the relevant Chapter in the note is titled
"Swimming Pools and Fountains". Where it is not intended that people should occupy the
basin of a fountain, requirements are relaxed as detailed at the end of 7.3.2. The
Regulations classify zones around the pool, the arrangements being as follows:

Zone A
is the inside of the pool, including chutes and flumes, as well as apertures in the pool
walls
and floor which are accessible to the bathers.

Zone B
is a volume above the pool to 2.5 m above the rim, plus the same height above the
surrounding floor area on which people may walk, extending horizontally 2.0 m outwards
from the rim. If the pool rim is above the surrounding floor level, the zone extends 2.5 m
above the rim. Where the pool is provided with diving or spring boards, starting blocks or
a chute, the zone also includes the volume enclosed by a vertical plane 1.5 m from the
edge of the board and extending upwards to 2.5 m above the highest surface which will
be used by people. or by the ceiling if there is one.

Zone C
is the volume extending 1.5 m horizontally from the boundary of Zone B and 2.5 m
vertically above the floor.

The extents of the three zones are shown in {Fig 7.3}. Although limited by walls or fixed
partitions the zones do extend through doorways and other openings.

Fig 7.3 Dimensions of zones for swimming pools


7.3.2 - Special requirements for swimming pools

Appliance and sockets for use in these high-risk areas must be separated extra-low
voltage (SELV) type, at a potential not exceeding 12 V ac or 30 V dc. Such equipment
must be protected to level IP2X, which means that it must be impossible to touch live
parts with a finger, or must have insulation capable of withstanding a voltage level of 500
V r.m.s. for one minute. The safety source (a transformer in most cases), must be
installed outside zones A, B and C. An exception is the supply to floodlights (often they
will be under water) which can be fed at up to 18 V, if in zones B or C, or 12 V if in zone
A (submerged), each floodlight being powered by a separate transformer or a separate
secondary winding of a transformer having multiple secondary windings.

Normal luminaires are not permitted in zones A or B, so general illumination is best


provided by luminaires mounted higher than 2.5 m above floor level. This is zone C,
where protection must be by electrical separation (see {5.8.4}) or by 30 mA residual
current device(s). If RCDs are used, care must be taken to ensure that devices are not
tripped by high leakage currents on starting; the use of multiple circuits, each with its
own RCD, is advised. Attention is drawn to the difficulty of servicing luminaires
mounted above the pool.

Usually, protection against direct contact will be by means of earthed equipotential


bonding and automatic disconnection of the supply in the event of a fault (the same as for
most other installations), and the special requirements are:

1. - all extraneous conductive parts, including non-insulating floors, must be bonded


together and to earth. If the floor within zones B and C is not insulated or if a PME
supply is used (see{5.6}) a metal grid must be installed in the floor and connected to the
local supplementary bonding. The exception to this is any SELV system, which must
remain unconnected to the main earthing system.

2. - the earth fault loop impedance must be low enough so as to allow disconnection
within 0.4 s (see {5.3}).

In no case is it permissible to rely for protection against direct contact on obstacles,


placing out of reach, a non-conducting location or earth-free equipotential bonding. If
wiring is run on the surface it must not be metallic sheathed and must not he run in metal
conduit or metal trunking, except in zone C.

Enclosures used for wiring systems or appliances at swimming pools are subject to
special requirements, which depend on whether water jets will be used for cleaning
purposes. If they will be used, protection must be to IPX8, (submersion in water), within
the pool (Zone A) and IPX5, which means that there must be effective protection against
such water jets (see {Table 2.1}). If water jets will not be used, protection depends on the
zone (see {7.3.1}) in which the system or appliance is situated. The requirements are:
Zone A
IPX8, which means protection from submersion in water,

Zone B
IPX4, so that protection is provided against splashing water, and

Zone C
indoor pools, IPX2, which gives protection against dripping water when inclined at 15°;
and outdoor pools, 1PX4, which gives protection against splashing water.

There must be no switchgear, control gear or accessories installed within zones A or B,


except for small pools where socket outlets are necessary and cannot possibly be installed
outside zone B. In this case, BS 4343 socket outlets may be installed provided they are at
least 1.25 m (arms' reach) outside zone A, are at least 0.3 m above the floor, and are
protected by an RCD with a 30 mA rating or are protected by electrical separation [413-
05] with the necessary isolating transformer situated outside zones A, B and C. Wiring
must not be metallic sheathed, or enclosed in metallic conduit or trunking if run on the
surface. Joint boxes may be used, but they must be inaccessible if installed in zones A or
B. Instantaneous water heaters complying with BS 3456 may be installed in zones B and
C.

Socket outlets (in zone C only - but see above for small pools) must be to industrial
standard BS 4343, and a shaver outlet to BS EN 60742 may also be installed in zone C
(5.8.4). If electric floor heating is used around a pool, it must have its metal sheath, or a
covering metal grid if there is no metallic sheath, connected to the local equipotential
bonding. Fire alarm, audio and public address equipment should ideally be outside zones
A and B, but where this is not possible must be more than 1.25 metres outside zone A.
Loudspeakers must be out of reach of anyone in the water or at the poolside, and if
portable microphones are used they must be connected by way of a suitable isolating
transformer. Radio microphones will reduce the danger of shock. Hard wired telephones
are not permitted in any zone, and if required, cordless telephones must be used with the
base unit outside the zones. Where the basin of a fountain is not intended to be occupied
by people, installations in zones A and B may be protected by electrical separation (see
{5.8.4}) or by automatic disconnection of the supply using an RCD with an operating
current not exceeding 30 mA.

7.5.1 - Introduction

7.5.2 - Special regulations for construction sites

7.5.1 - Introduction

The electrical installation on a construction site is there to provide lighting and power to
enable the work to proceed. By the very nature of the situation, the installation will be
subjected to the kind of ill treatment which is unlikely to be applied to most fixed
installations. Those working on the site may be ankle deep in mud and thus particularly
susceptible to a shock to earth, and they may be using portable tools such as drills and
grinders in situations where danger is more likely than in most factory situations. The
difficulty of ensuring that bonding requirements are met on construction sites means that
PME supplies must not be used to supply them.

Installations will also, by definition, he temporary. As the construction proceeds they will
be moved and altered. It is usual for such installations to be subjected to thorough
inspection and testing at intervals which will never exceed three months. A formal visual
inspection of 110 V equipment should take place monthly; the effectiveness of each RCD
should be tested before every use by pressing its test button.

As well as the erection of new buildings, the requirements for construction sites will also
apply to:

1. - sites where repairs, alterations or additions are carried out

2. - demolition of buildings

3. - public engineering works

4. -civil engineering operations, such as road building, coastal protection, etc.

The special requirements for construction sites do not apply to temporary buildings
erected for the use of the construction workers, such as offices, toilets, cloakrooms,
dormitories, canteens, meeting rooms, etc. These situations will not change as
construction progresses, and are thus subject to the general requirements of the
Regulations.

The equipment used must be suitable for the particular supply to which it is connected,
and for the duty it will meet on site. Where more than one voltage is in use, plugs and
sockets must be non interchangeable to prevent misconnection. Six levels of voltage are
recognised for a construction site installation. They are:

1. - 25 V single-phase SELV for portable hand-lamps in damp and confined situations,

2. - 50 V single-phase, centre-point earthed for hand lamps in damp and confined


situations,

3. - 400 V three phase, for use with fixed or transportable equipment with a load of more
----- than 3750 Watts,

4. - 230 V single phase, for site buildings and fixed lighting,

5. - 110 V three phase, for transportable equipment with a load up to 3750 Watts, and
6. - 110 V single phase, fed from a transformer, often with an earthed centre-tapped
secondary winding, to feed transportable tools and equipment, such as floodlighting, with
a load of up to 2 kW. This supply ensures that the voltage to earth should never exceed
55 V (see {Fig 7.5}). The primary winding of the transformer must be RCD-protected
unless the equipment fed is to be used indoors.

Fig 7.5 Arrangement of transformer for safety 110 V supply for a construction site

Supplies will normally be obtained from the Electricity Supply Company. Where a site is
remote, so that a generator must be used (IT supply system) special protective
requirements apply which are beyond the scope of this Guide, and the advice of a
qualified electrical engineer must be sought. Attention is drawn to BS 7375: 1966 Code
of Practice for the distribution of electricity on construction and building sites.

7.5.2 - Special regulations for construction sites

Construction site installations are like most others in that they usually rely on earthed
equipotential bonding and automatic disconnection for protecting from electric shock.
This is the system where an earth fault, which results in metalwork open to touch
becoming live, also causes a fault current which will open the protective device to
remove the supply within 0.4 s for socket outlet circuits or 5 s for fixed appliances. For
construction sites, where the prospective dangers are greater, there are additional
requirements. These are:

1. - The times within which disconnection must occur are reduced, except for fixed
equipment. Generally the times permitted are much reduced to reflect the more dangerous
nature of the construction site. These voltage-related disconnection times are given in
{Table 7.1} for TN systems, which are those where the Electricity Supply Company
provides an earthing terminal. Where values of maximum earth-fault loop impedance are
necessary to check compliance with this requirement, it must be appreciated that the
values of {Tables 5.1 and 5.2} no longer apply, and new values must be calculated using
the stated supply voltages, and disconnection currents read from {Figs 3.13 to 3.19} using
the maximum times from {Table 7.1}. For 240 V circuits with a maximum disconnection
time of 0.2 s, maximum permissible earth-fault loop values for various types of protective
device are shown in {Table 7.2}. Where the given values of earth-fault loop impedance
cannot be met, protection must be by means of RCDs with operating current not
exceeding 30 mA. The reduced connection times do NOT apply to 110 V centre-tapped
supplies, which are in any case required to be protected by RCDs with an operating
current not exceeding 30 mA.

For fixed installations (limited to main switchgear and principal protective devices) the
disconnection time is 5 s, so {Tables 5.2 and 5.4} can he used to find maximum earth-fault
loop impedance values.

Table 7.1 - Maximum disconnection times for construction site circuits


---------------- (TN systems)
Supply voltage (Uo) Disconnection time
(volts) (seconds)
120 0.35
220 to 277 0.20
400 and 480 0.05

Table 7.2 - Maximum earth-fault loop impedance values for 240 V


construction site circuits to give a maximum 0.2 s disconnection time
Type of protection Protection rating Max. loop impedance
(A) (ohms)
Cart. Fuse, BS 1361 5 9.60
15 3.00
20 1.55
30 1.00
Cart. Fuse BS 88 pt 2 6 7.74
10 4.71
16 2.53
20 1.60
25 1.33
32 0.92
MCB type 1 5 12.00
10 6.00
15 4.00
20 3.00
30 2.00
MCB type 2 5 6.86
10 3.43
15 2.29
20 1.71
30 1.14
MCB type 3 5 4.80
10 2.40
15 1.60
20 1.20
30 0.80
MCB type B 6 8.00
10 4.80
16 3.00
20 2.40
32 1.50

2. - In other installations the maximum shock voltage is given as 50 V, calculated from


the impedance of the protective system to earth in ohms multiplied by the fault current in
amperes. This was the basis of {Table 5.3}, but these data do not apply in this case. For
construction sites, the value is reduced to 25 V. For example, for a TN system, the
impedance of the circuit protective conductor (Zs) multiplied by the current rating of the
protective fuse or circuit breaker (In) must not exceed 25.

For a circuit protected by a 15 A miniature circuit breaker type 1, which must carry a
current of 60 A to trip in 5 s (see {Fig 3.16}), the impedance of the circuit protective
conductor must therefore be no greater than:

Zs = 25 = 25 Ohms = 0.42 ohms


In 60

Sockets on a construction site must be separated extra-low voltage (SELV) or protected


by a residual current circuit breaker (RCD) with an operating current of not more than 30
mA, or must be electrically separate from the rest of the supply, each socket being fed by
its own individual transformer. SELV is unlikely for most applications, because 12 V
power tools would draw too much current to be practical. Most sockets are likely to be
fed at 110 V from centre-tapped transformers so will comply with this requirement.

Distribution and supply equipment must comply with BS 4363, and, together with the
installation itself, must be protected to IP44. This means provision of mechanical
protection from objects more than 1 mm thick and protection from splashing water. Such
equipment will include switches and isolators to control circuits and to isolate the
incoming supply. The main isolator must be capable of being locked or otherwise secured
in the 'off' position. Emergency switches should disconnect all live conductors including
the neutral.

Cables and their connections must not be subjected to strain, and cables must not be run
across roads or walkways without mechanical protection. Circuits supplying equipment
must be fed from a distribution assembly including overcurrent protection, a local RCD if
necessary, and socket outlets where needed. Socket outlets must be enclosed in
distribution assemblies, fixed to the outside of the assembly enclosure, or fixed to a
vertical wall. Sockets must not be left unattached, as is often the case on construction
sites. Socket outlets and cable couplers must be to BS EN 60309-2. A typical schematic
diagram for a construction site system is shown in {Fig 7.6}.

Fig 7.6 - Single-phase distribution system for a construction site to BS 4363 and CP
1017

7.7.1 - Introduction

7.7.2 - Special requirements

7.7.1 - Introduction
A restrictive conductive location is one in which the surroundings consist mainly of
metallic or conductive parts, with which a person within the location is likely to come
into contact with a substantial portion of his body, and where it is very difficult to
interrupt such contact. An example could be a large metal enclosure, such as a boiler, in
which work must be carried out. Clearly, such a situation could result in considerable
danger to a worker, who may be lying inside the boiler whilst using an electric drill or
grinder.

7.7.2 - Special requirements

The person in the restrictive location is protected by the use of the separated extra-low
voltage (SELV) system. A SELV supply must be fed from a safety source, such as a
special step-down isolating transformer. Protection against direct contact by obstacles or
placing out of reach is not permitted.

Protection against indirect contact (touching parts which have become live as the result of
a fault) for fixed equipment is achieved by one of the following methods:

1. - if the supply is SELV, then protection from indirect contact is automatically


prevented because the system is totally isolated and has no earthing connections,

2. - for SELV protection can be by automatic disconnection, the protective device


opening the circuit within 0.4 s in the event of a fault. To ensure low earth-fault loop
impedance, the conductive location must again be solidly earthed,

3. - when SELV is used, protection by electrical isolation may be used. This means that
equipment in use is fed from the unearthed secondary winding of an isolating transformer
so that there is no path for earth currents. When more than one supply to equipment is
required, each must be from a separate transformer secondary winding,

4. - equipment to Class II may be used, with additional protection from an RCD with an
operating current not exceeding 30 mA.

Separated and isolating sources, other than those specified in 3) above, must be situated
outside the restrictive conductive location unless they are part of an installation in a
permanent restrictive conductive location. By its very nature an enclosed space is likely
to be dark, and handlamps will be needed by the operator. Socket outlets intended to feed
handlamps must be SELV, and these outlets can also he used to feed hand tools.
However, the limitation of 25 V on SELV means that the range of hand tools available is
very limited, and where higher voltages are used, sockets for this purpose can be fed
using electrical separation.

7.9.1 - Introduction

7.9.2 - Caravan installations


7.9.3 - Caravan park installations

7.9.1 - Introduction

A caravan is a leisure accommodation vehicle which reaches its site by being towed by a
vehicle. A motor caravan is used for the same purpose, but has an engine which allows it
to be driven; the accommodation module on a motor caravan may sometimes be removed
from the chassis. Caravans will often contain a bath or a shower, and in these cases the
special requirements for such installations (see{7.2}) will apply. Railway rolling stock is
not included in the definition as a caravan. Caravans used as mobile workshops will be
subject to the requirements of the Electricity at Work Regulations 1989 as well as BS
7671,1992.

All the dangers associated with fixed electrical installations are also present in and
around caravans. Added to these are the problems of moving the caravan, including
connection and disconnection to and from the supply, often by totally unskilled people.
Earthing is of prime importance because the dangers of shock are greater. For example,
the loss of the main protective conductor and a fault to the metalwork in the caravan is
likely to go unnoticed until someone makes contact with the caravan whilst standing
outside it (Fig {7.10}. The requirements of the Electricity Supply Regulations do not
allow the supply neutral to be connected to any metalwork in a caravan, which means that
PME supplies must not be used to supply them.

Fig 7.10 - Importance of earthing a caravan

7.9.2 - Caravan installations

The requirements for the electrical installation are listed below, numbers relating to those
shown on {Fig 7.11}.
1. - An inlet coupler to BS EN 60309-2 with its keyway at position 6h must be provided
no higher than 1.8 m above the ground.

2. - A spring hinged lid which will close to protect the coupler socket when travelling
must be fitted.

3. - A clear and durable notice must be provided beside the inlet coupler to indicate the
voltage, frequency and current of the caravan installation.

Fig 7.11 - Requirements for the installation in a caravan

4. - Protection by automatic disconnection (as for all other installations) but using double
pole MCBs to disconnect all live conductors, together with a double pole RCD
complying with BS 4293, BS EN 61008-1 or BS EN 61009-1 with an operating current
of 30 mA and means of isolating the complete caravan installation must be used.

5. - durable notice must be fixed beside the isolator with the wording shown in {Table
7.5},

Table 7.5 - Instructions for electricity supply


To Connect
Before connecting the caravan installation to the mains supply, check that
:
1. a) -the supply available at the caravan pitch supply point is suitable
for the caravan installation and appliances, and
b) - the caravan main switch is in the OFF position.
Open the cover to the appliance inlet provided at the caravan supply point
2.
and insert the connector of the supply flexible cable
3. Raise the cover from the electricity outlet provided on the pitch supply
point and insert the plug of the supply cable. The caravan supply flexible
cable must be fully uncoiled to avoid damage by overheating.
4. Switch ON at the caravan main switch
Check the operation of residual current devices, if any, fitted in the
5.
caravan by depressing the test button.
In case of doubt or if, after carrying out the above procedure the supply
does not become available, or if the supply fails, consult the caravan park
operator or his agent or a qualified electrician.
To Disconnect
Switch off at the caravan main isolating switch and unplug both ends of
6.
the cable.
Periodical Inspection
Preferably not less than once every three years and more frequently if the
vehicle is used more than normal average mileage for such vehicles, the
caravan electrical installation and supply cable should be inspected and
tested and a report on its condition obtained as prescribed in BS 7671
(formerly the Regulations for Electrical Installations) published by the
Institution of Electrical Engineers.

6. - All circuits must be provided with a protective conductor. All sockets are to be three
pin with earthed contact and must have no accessible conductive parts. If two or more
systems at different voltages are in use, the plugs of the differing systems must not be
interchangeable. ELV sources must be 12 V, 24 V or 48 V when dc, or 12 V, 24 V, 42 V
or 48 V when ac. Such ELV sockets must have their voltage clearly marked. Wiring may
be flexible or with at least seven strands in non-metallic conduit (wiring systems which
will allow fire to spread along them must not be used) or sheathed flexible cables, with
the smallest conductor being 1.5 mm2 in cross-sectional area. Where 240 V and extra-low
voltage circuits (usually 12 V) are both used, the cables of the two systems must be run
separately and must both be insulated for 240 V. Since the wiring will be subjected to
vibration when the caravan is moved, great care must be taken to ensure that bushes or
grommets are used where it passes through metalwork.

7. - Enclosed luminaires must be fixed directly to the structure or lining of the caravan.
Where luminaires are of the dual voltage type (240 V mains and 12 V battery supply)
they must be fitted with separate and different types of lampholder, with proper
separation between wiring of the two supplies, and be clearly marked to indicate the lamp
wattages and voltages. They must be designed so that both lamps can be illuminated at
the same time without causing damage.

8. - Pendant luminaires must have arrangements to secure them whilst the caravan is
being moved.

9. - All metal parts of the caravan, with the exception of metal sheets forming part of the
structure, must be bonded together and to a circuit protective conductor, which must not
be smaller than 4 mm² except where it forms part of a sheathed cable or is enclosed in
conduit.

10. - Sheathed cables must be supported at intervals of at least 400 mm where run
vertically, or 250 mm horizontally unless run in non-metallic rigid conduit.

11. - No electrical equipment may be installed in a compartment intended for the storage
of gas cylinders.

Where a caravan appliance may be exposed to the effects of moisture, it must be


protected to lp55 (protected from dust and from water jets). Every caravan which
includes an electrical installation must be provided with a flexible lead not more than 25
m long fitted with a BS EN 60309-2 plug and a BS EN 60309-2 connector with the
keyway at position 6h. The cross-sectional area of the cable must be related to the rated
current of the plug as shown by {Table 7.6}.

Table 7.6 - Cross-sectional areas of flexible cables


---------------- and cords for supplying caravan connectors
Rated current of plug (A) Cross-sectional area (mm²)
16 2.5
25 4.0
32 6.0
63 16.0

7.9.3 - Caravan park installations

These Regulations cover the arrangements for the supply of electrical energy to
individual plugs on a caravan or tent park. The plots on which caravans will stand are
referred to as caravan pitches.

As mentioned in {7.9.1} the supply to caravans must not be PME - this means that only TT
or TN-S systems may be used. If the supply system is PME, there must be separation of
the earthing systems of the pitch supplies and the incoming supply, which is usually best
effected at the main distribution board with a separate earth electrode for the pitch
supplies. The PME system may be used to supply permanent buildings such as toilet
blocks.

Wherever possible, the supplies to the plugs should be by means of underground cables
(see{7.13.3}). These cables should be installed outside the area of the caravan pitch to
ensure that they are not damaged by tent pegs (which are often used in erecting caravan
awnings) and ground anchors which are used to secure the caravans against the effects of
high winds. If the underground cables must be below the pitches, they must be provided
with additional protection. as shown in {Fig 7.22}.
If overhead supplies are used they must:
1. - be constructed with insulated, rather than bare, cables
2. - always be at least 2 m outside the area of every pitch
3. - have a mounting height of at least 3.5 m, which must be increased to 6 m where
vehicle movements are possible. Since in most cases the whole of the area of a caravan
site is subject to vehicle movements, most overhead systems will need to be at a
minimum height of 6 m. Poles or other supports for overhead wiring must be located or
protected so that they are unlikely to be damaged by vehicle movement.

There must be at least one supply socket for each pitch, the socket positioned so that it is
between 0.8 m and 1.5 m above ground level, and no more than 20 m from any point in
its pitch. The current rating must be at least 16 A, and the outlet must he to BS EN
60309-2, of the splash proof type to IPX4, and with the keyway at position 6h. If the
expected current demand for a pitch exceeds 16 A, extra sockets of higher rating must be
installed. A problem frequently arises due to the increasing use of 3 kW instantaneous
water heaters in caravans because supply systems have not usually been designed to
allow for such heavy loading.

Each socket must have its own individual overcurrent protection in the form of a fuse or
circuit breaker; to ensure that enough current will flow to open the protective device in
the event of an earth fault, it is recommended that the earth-fault loop impedance at the
plug should not exceed 2 Ohms. All sockets must be protected by an RCD complying
with BS 4293, BS EN 61008-1 or BS EN 61009-1 with a 30 mA rating, either
individually or in groups, which must consist of no more than three sockets (see {Fig
7.12}). Since a 30 mA RCD is also required within each caravan, the device protecting
the pitch socket(s) should be time delayed, to prevent the possibility of a fault in one
caravan from switching off the supply to other caravans.

Fig 7.12 - RCD protection for sockets at caravan pitches

7.11.1 - Introduction

7.11.2 - Electrode boilers and water heaters

7.11.3 - Instantaneous water heaters

7.11.4 - Surface, floor, soil and road warming


------------ installations

7.11.1 - Introduction

This section is concerned with the special requirements for devices and circuits which are
designed to produce heat for transfer to their surroundings. All water heaters (as well as
those for other liquids) must be provided with a thermostat or cut-out to prevent a
dangerous rise in temperature. Not only could the high temperature of the water or other
liquid be dangerous, but if allowed to boil, very high pressures, leading to the danger of
an explosion, could result if the liquid container were sealed.

7.11.2 - Electrode boilers and water heaters

An electrode heater or boiler is a device which heats the water contained, or raises steam.

Two or three electrodes are immersed in the water and a single- or three-phase supply is
connected to them. There is no element, the water being heated by the current which
flows through it between the electrodes. Electrode heaters and boilers must be used on
a.c. supplies only, or electrolysis will occur, breaking down the water into its components
of hydrogen and oxygen. The different requirements for single-phase and three-phase
boilers are shown below.

A - Three-phase heaters fed from a low voltage supply {Fig 7.13}


Fig 7.13 Three-phase electrode heater fed from a low voltage supply

The requirements are:

1. - a controlling circuit breaker which opens all three phase conductors and is provided
with protective overloads in each line,

2. - the shell of the heater bonded to the sheath and/or armour of the supply cable with a
conductor of cross-sectional area at least equal to that of each phase conductor,

3. - the shell of the heater bonded to the neutral by a conductor of cross-sectional area at
least equal to that of each phase conductor.

B - Three phase electrode heaters fed from a supply exceeding low voltage {Fig
7.14}

Fig 7.14 - Three-phase electrode boiler fed from a supply exceeding low voltage

The requirements are:

1. - a controlling circuit breaker filled with residual current tripping, set to operate when
the residual current is sustained arid exceeds 10% of the rated supply current. Sometimes
this arrangement will result in frequent tripping of the circuit breaker, in which case the
tripping current may be reset to 15% of the rated current arid/or a time delay device may
be fitted to prevent tripping due to short duration transients. See {5.9} for more
information concerning residual current devices,
2. - the shell of the heater must be bonded to the sheath or armour of the supply cable
with a conductor of current rating at least equal to the RCD tripping current, but with a
minimum cross-sectional area of 2.5 mm².

C - Single-phase electrode heaters {Fig 7.15}

Fig 7.15 - Single-phase electrode heater

The requirements for single-phase electrode heaters are:

1. - a double-pole linked circuit breaker with overload protection in each line,

2. - the shell of the heater bonded to the sheath and/or armour of the supply cable with a
conductor of current-carrying capacity at least equal to that of each live conductor,

3. - the shell of the heater bonded to the neutral,

4. - the supply must be one which has an earthed neutral.


D - Insulated single-phase electrode heater, not permanently piped to water supply

Fig 7.16 Insulated single-phase electrode heater, not piped in to a water supply

This small heater is usually fixed in position, but is filled by using a flexible hose or a
water container.

The requirements are:

1. - there must be no contact with earthed metal,

2. - the heater must be insulated and shielded to prevent the electrodes from being
touched,

3. - control must be by means of a single-pole fuse or by a circuit breaker and a


----- double pole switch,

4. - the shell of the heater must be bonded to the cable sheath.

7.11.3 - Instantaneous water heaters

Water heaters of this type are in general use to provide hot water for showers, making
drinks, and so on. They transfer heat from the element directly to the water flowing over
it, and therefore will be arranged to switch an only when water is flowing. In most cases,
the element of the heater has a fixed rating, and so transfers energy in the form of heat to
the water at a constant rate. The temperature rise of the water passing over the element
therefore depends on the inlet water temperature and the rate of water flow. If the
discharge rate is high, the energy provided by the element may be insufficient to raise the
water temperature to the desired level.
The slower the rate of flow, the hotter will become the water at the outlet. This is the
reason for the common complaint of being scalded whilst under the shower if someone
turns on a tap elsewhere, reducing the water pressure and the rate of flow over the
element. Some heaters are provided with an automatic cut-out to switch off the element if
a preset outlet temperature is exceeded. {Figure 7.17} shows, in graphical form, the
expected outlet water temperature for various water flow rates from 3 kW, 6 kW and 8
kW heaters assuming an inlet water temperature of 10°C.

Some heaters are provided with thyristors or triacs to continuously vary the heater rating
to maintain a desired water outlet temperature so long as the variation in the rate of flow
is not too great. These devices adjust the effective current flow by delaying the instant in
each half-cycle of the supply at which current begins to flow.

Fig 7.17 - Outlet temperatures from instantaneous water heater

The Regulations point out that a heater with an uninsulated element is unsuitable where a
water softener of the salt regenerative type is used because the increased conductivity of
the water is likely to lead to excessive earth leakage currents from the element. The
agreement of the Water Supply Authority is usually needed before installation.

It is essential that all parts of this type of heater are solidly connected to the metal water
supply pipe, which in turn is solidly earthed independently of the circuit protective
conductor. The heater must be controlled by a double pole linked switch. In the case of a
shower heater, if this switch is not built into the heater itself, a separate pull switch must
be provided adjacent to the shower, with the switch itself being out of reach of a person
using the shower. The arrangement of an instantaneous heater is shown in {Fig 7.18}. If
the neutral supply to a heater

Fig 7.18 - Instantaneous water heater

with an uninsulated element is lost, current from the phase will return via the water and
the earthed metal. Therefore, a careful check is necessary to ensure that there is no fuse,
circuit breaker or non-linked switch in the neutral conductor. A problem frequently arises
due to the increasing use of 3 kW instantaneous water heaters in caravans because supply
systems have not usually been designed to allow for such heavy loading.

7.11.4 - Surface, floor, soil and road warming installations

Most cables have conductors of very low resistance so that the passage of current through
them dissipates as little heat as possible. By using a cable with a higher conductor
resistance (typical resistance's for some of the resistive alloys used are from 0.013 to 12.3
Ohms/m) heat will be produced and will transfer to the medium in which the cable is
buried, There are many types of cable, a typical example being shown in {Fig 7.19}.
Fig 7.19 - One type of floor heating cable

Some of the many examples of the use of heating cables are:

1. - space heating, using the concrete floor slab as the storage medium,

2. - under-pitch application on sports grounds, to keep the playing surfaces free of frost
and snow,

3. - in roads, ramps, pavements and steps to prevent icing,

4. - surface heating cables, tapes and mats, used for frost protection, anti-condensation
heating, process heating to allow chemical reactions, drying, processing thermoplastic
and thermosetting materials, heating transport containers, etc.

5. - in rainwater drainage gutters to prevent blocking by ice and snow, and

6. - for soil warming to promote plant growth in horticulture.

The heating cables used in such situations must be able to withstand possible damage
from shovels, wheelbarrows, etc. during installation, as well as the corrosion and
dampness which is likely to occur during use. They must be completely embedded, and
installed so that they are not likely to suffer damage from cracking or movement in the
embedding material, which is often concrete. The loading of the installation must be such
that the temperatures specified for various types of conductor {Table 7.7} are not
exceeded. Where an electrical under-floor heating system is used in a bath or shower
room, it must either have an earthed metallic sheath which is supplementary bonded or be
covered by an overall earthed metallic grid which is similarly bonded.

Table 7.7 - Maximum conductor temperatures for


------------------ floor warming cables

Max conductor operating


Type of cable
temperature (°C)
General purpose, p.v.c. over conductor 70
Enamelled conductor, polychloroprene ins.
70
with p.v.c. sheath
Enamelled conductor, p.v.c. ins. overall 70
Enamelled conductor, p.v.c. ins. and lead
70
alloy sheathed
Heat resisting p.v.c. insulated 85
Synthetic rubber insulated 85
Mineral insulated copper sheathed *
Silicone treated woven glass insulation 180
* The operating temperature depends on the outer covering material, the type
of seal, the arrangement of the cold tails, and so on. Manufacturers’ data
must be consulted.

Where heating cables pass through, or run close to, materials which present a fire hazard,
they must be protected from mechanical damage by a fire-proof enclosure. Where normal
circuit cables are run through a heated floor, they must have the appropriate ambient
temperature correction factor applied {4.3.4}. Heating cables may he obtained ready
jointed to normal cables at their ends (cold tails) for connection to the supply circuit as
shown in {Fig 7.20}.

Fig 7.20 - Floor heating installation


7.13.1 - Overhead wiring types

7.13.2 - Maximum span lengths and minimum


heights

7.13.3 - Underground wiring

7.13.1 - Overhead wiring types

Most overhead wiring is carried out by the Electricity Supply Companies, and is not in
the domain of the electrician. However, wiring between buildings is often necessary, and
can be carried out using one or more of the following methods:

1. - rubber or p.v.c. insulated cables bound to a separate catenary wire,

2. - specialist cables with an integral catenary wire,

3. - p.v.c. Insulated and sheathed, or rubber insulated with an oil-resisting and flame
retardant sheath, provided that precautions are taken to prevent chafing of the insulation
or undue strain on the conductors,

4. and 5. bare or p.v.c. Insulated conductors on insulators. In this case, the height of the
cables and their positions must ensure that protection against direct contact is prevented,

6. - cable sheathed and insulated as in 3) above enclosed in a single unjointed length of


heavy-gauge steel conduit of at least 20 mm diameter.

Table 7.8 - Maximum span and minimum height for


----------------- overhead wiring between buildings
Type of Max. length
Minimum height above ground
system of span
At road
Accessible to Not accessible
- (m) crossings
vehicles (m) to vehicles (m)
(m)
1 No limit 5.8 5.2 3.5
Consult
2 5.8 5.2 3.5
manufacturer
3 3 5.8 5.2 3.5
4 30 5.8 5.2 3.5
Consult
5 5.8 5.2 3.5
manufacturer
6 3 5.8 5.2 3.0
7.13.2 - Maximum span lengths and minimum heights

The required information is contained in {Table 7.8} and {Fig 7.21}. Four special points
are worth noting here.

1. - in some locations where very tall traffic may be expected (eg. yacht marinas, or
where tall cranes are moved) heights above ground must be increased,

2. - in agricultural situations, the lower heights of 3.5 m and 3.0 m are not permitted,

3. - where caravan pitches are fed, overhead cables must be at least 2 m outside the
bounds of each pitch,

4. - overhead supplies to caravan pitches must have a minimum ground clearance of 6.0
m where there will be moving vehicles, and 3.5 m elsewhere.
Fig 7.21 - Overhead lines. Ground clearances shown are for places which are not
accessible to vehicular traffic - see {Table 7.8}

Table 7.8 - Maximum span and minimum height for


----------------- overhead wiring between buildings
Type of Max. length
Minimum height above ground
system of span
(see list At road
Accessible to Not accessible
in 7.13.1 (m) crossings
vehicles (m) to vehicles (m)
for key) (m)
1 No limit 5.8 5.2 3.5
Consult
2 5.8 5.2 3.5
manufacturer
3 3 5.8 5.2 3.5
4 30 5.8 5.2 3.5
Consult
5 5.8 5.2 3.5
manufacturer
6 3 5.8 5.2 3.0

NB All ground clearances are for positions not accessible to vehicular traffic

7.13.3 - Underground wiring

Three types of cable may be installed underground:

1. - armoured or metal sheathed or both

2. - p.v.c. insulated concentric type. Such a cable will have the neutral (and possibly the
protective conductor) surrounding the phase conductor. An example is shown in {Fig
4.1(c)}.

3. - Any suitable cable enclosed in conduit or duct which gives at least the same degree of
mechanical protection as an armoured cable.

No specific requirements for depth of burial are given in the Regulations, except that the
depth should be sufficient to prevent any disturbance of the ground reasonably likely to
occur during normal use of the premises. Hence, a cable to outbuildings installed under a
concrete path could be at 400 mm, whilst if running through a cultivated space which
could be subject to double digging would be less likely to disturbance if buried at 700
mm. For caravan pitches, cables should be installed outside the area of the pitch, unless
suitably protected, to avoid damage by tent pegs or ground anchors.
Cables must be identified by suitable tape or markers above the cable, so that anyone
digging will become aware of the presence of the cable. Cable covers may also offer both
identification and protection as shown in {Fig 7.22}.

It is often useful to lay a yellow cable marker tape just below ground level so that this
will be exposed by digging before the cable is reached. Careful drawings should also be
made to indicate the exact location of buried cables; such drawings will form part of the
installation manual (see {8.2.1}).

Fig 7.22 - Cable covers

7.15.1 - Rotating machines

The vast majority of motors used in industry are of the three-phase squirrel-cage
induction type. Smaller motors are usually single-phase induction machines. Induction
motors have important advantages, such as robustness, minimal maintenance needs, and
self starting characteristics, but all draw very high starting currents from their supplies
{Fig 7.23}. This starting current is a short-lived transient, and may usually be ignored
when calculating cable sizes.
Fig 7.23 - Starting current of an induction motor

Although the starting current may be several times the running current, the value
depending on the machine characteristics and the connected mechanical load, its short
duration will not lead to overheating in usual circumstances. If frequent starting is a
requirement, larger supply cables may be necessary to avoid damage to insulation. A
problem could arise when fast-acting fuses or circuit breakers are used for short-circuit
protection; the high starting current may result in operation of the protective device. A
common, but unsatisfactory, remedy for this difficulty is to increase the rating of the
protective device, leading to a loss of proper overload protection. A possible solution is to
use dual rated fuses (gM types). For example, a 25M40 fuse has a continuous rating of 25
A and the operating characteristics of a 40 A fuse.

A word is necessary concerning motor ratings. Many years ago it was decided to replace
the horsepower as the unit of output power with the kilowatt. Unfortunately, the old
horsepower is a very long time in dying. Many machines still have rating plates giving
output power in horsepower. The conversion is straightforward. Since one horsepower is
the same as 746 W, horsepower is converted to kilowatts by multiplying by 0.746.

It is sometimes practice to stop a motor very quickly by feeding it with a reverse current.
When this method is provided it is important that the machine does not begin to move in
the reverse direction if this would cause danger.

Where other types of motor, such as wound rotor and commutator induction or thyristor
fed dc types are used, the cables must be suitable for carrying running currents on full
load, which will usually mean that they are large enough to carry the short duration
starting currents.

Every motor rated at 0.37 kW (0.5 horsepower) or more must be fed from a starter which
includes overload protection. Such devices have time-delay features so that they will not
trip as a result of high starting current, but will do so in the event of a small but prolonged
overload. They have the advantages over fuses and single-pole circuit breakers that all
three lines of a three-phase system are tripped by an overload in any one of them. If only
one line were broken, the resulting 'single-phasing' operation of the motor could cause it
to overheat.

It is often necessary to provide a means to prevent automatic restarting after failure of the
supply. For example, if the supply to a machine shop fails, the machine operators are
likely to use the enforced break in production to clean and service their machines. If so,
when the supply is restored, the presence of hands, brushes, tools, etc. in the machines
when they automatically restart would cause serious danger. The necessary 'no-volt
protection' is obtained by using a starter of the type whose circuit is shown in {Fig 7.24}.
The coil is fed through the 'hold-in' contacts, which open when the supply fails; the motor
can then be operated only by pressing the 'start' button. This requirement does not apply
to protected motors which are required to restart automatically after mains failure.
Examples are motors supplying refrigeration and pumping plants. It is important that
lock-off stop buttons are not used as a means of isolation.

Fig 7.24 - Direct-on-line starter

7.15.2 -Transformers

Transformers are used more widely in the supply system than in the installation itself.
The link between the primary and secondary windings of a double wound transformer is
magnetic, not electric, so there is no electrical connection with the supply system, or with
its earthing system, from a circuit fed by the secondary winding of a transformer. This
loss of earthing may be an advantage where electrical separation is required, for example,
where an electric shaver in a bathroom is fed from the secondary winding of a
transformer (see {5.8.4}).
Step-up transformers must not be used in IT systems. In systems where they are
permitted, linked multipole switches must be provided so that the supply is
simultaneously disconnected from all live conductors, including the neutral.

7.17.1 - Introduction

7.17.2 - The marina electrical installation

7.17.1 - Introduction

Section 609 of BS 7671 is reserved for marinas, but at present has no content. The
following is thus based on Chapter 9 of Guidance Note 7, which in turn depends on lEG
Standard 364-7-709 and CENELEC standard HD 384-7-709. There can be little doubt
that before long this material will become part of the Regulations.

A marina is a location, often a harbour, for leisure craft to berth. Like residential
caravans, such craft require external power supplies, and this section is intended to ensure
the safety and standardisation of such supplies. The marina will often include shore based
facilities such as offices, workshops, toilets, leisure accommodation and so on; such
buildings are required to comply with the general requirements of the Regulations.

The electrical installation of a marina is subject to hazards not usually encountered


elsewhere, such as the presence of water and salt, the movement of the craft, increased
corrosion due to the presence of salt water and dissimilar metals, and the possibility of
equipment being submerged due to unusual wave activity in bad weather.

7.17.2 - The marina electrical installation

As for caravans, the neutral of a PME system must not be connected to the earthed
system of a boat so that the hazards which follow the loss of continuity in the supply PEN
conductor are avoided. This rules out the use of PME supplies for marinas. Where this is
the supply provided, it must be converted to a TI' system at the main distribution board
by provision of an separate earth electrode system of driven rods or buried mats with no
overlap of resistance area with any earth associated with the PME supply. If the marina is
large enough, it may be that the supply company will provide a separate transformer and
a TN-S system.

Shock protection
Protection by obstacles or by placing out of reach are not acceptable as methods of
preventing direct contact. A non-conducting location must not be used for protection
from indirect contact. Where a TN-S system is used, indirect protection must be provided
by an RCD which breaks all poles unless protection is provided by an on-shore isolating
transformer.

Wiring Systems
No aluminium cables may be used in marina installations.
Acceptable cables for fixed wiring are:
- those with thermoplastic, thermosetting or elastomeric insulation and sheath
installed
- in non-flexible non-metallic conduit, or in heavy-duty galvanised conduit,
- mineral insulated cable with extruded p.v.c. covering,
- armoured cables with sheaths of thermoplastic or elastomeric material.

A boat will move relative to the land due to wind and waves. Cables must be selected and
installed so that mechanical damage as a result of tidal and other movement of floating
structures is prevented. Cabling to bridge ramps, pontoons and movable jetties must be
carried out in flexible cables with EPR or thermosetting insulation and sheaths. Overhead
lines are not permitted. Conduit installations must be provided with apertures or holes to
allow for drainage.

It should be noted that p.v.c. cables are not usually suitable for continuous immersion in
water. Cables intended to be permanently immersed to a depth of 4 m or more should be
sheathed with lead; where the immersion is less than 4 m, cables should be armoured and
provided with polythene bedding and outer sheath. Due to possible problems with
corrosion, cable armouring must not be relied upon as a circuit protective conductor. A
separate CPC must be provided to which the armouring is securely connected. Cable
terminations must be protected against corrosion by selection of suitable materials, or by
the application of grease or mastic or paint. Buried cables will be required on-shore. It
must be remembered that such situations will be subjected to very weighty traffic as boat
trailers are moved. Unless the buried cables are above the water table they must be
suitable for continuous immersion.

Distribution boards
Distribution boards must be protected to IP44, and against the ingress of dust and sand.
Construction of glass reinforced plastic (GRP) gives better corrosion protection than
galvanised steel. Where mounted on fixed jetties, they must be at a minimum of 1 m
above the high water level; on floating jetties, they must be at least 750 mm above the
water. Boards must be fitted with locks to prevent unauthorised access, and with internal
barriers to prevent contact with live parts (to IP 2X) when the doors are open. Low power
heaters may be needed within the boards to prevent excessive condensation.

Socket outlets
A common installation method is to provide a feed from the shore to a floating pontoon
via a bridge or ramp, and then to equip the pontoon with socket outlets to feed the craft
moored to it. Socket outlets may be single- or three-phase. Where multiple single-phase
sockets are installed on the same pontoon, they must all be connected to the same phase
of the supply unless fed through isolating transformers. All socket outlets must be to BS
EN 60309-2 with keyways at 6R, protected to IPX4 minimum, coloured red if three-
phase and blue if single-phase. Single-phase sockets are usually rated at 16 A and three-
phase at 32 A, although higher ratings may be installed where the need arises. Socket
outlets should be positioned as close as possible to the berth of the vessel they feed, with
a minimum of one socket per berth, although up to six sockets may be provided in a
single enclosure. Each socket outlet must be provided with a means of isolation which
breaks all poles on T[ systems, and must be protected by an overcurrent device such as a
fuse or a circuit breaker. Groups of socket outlets must be RCD protected. Each socket or
group of sockets must be provided with a durable and legible notice giving instructions
for the electricity supply (see {Table 7.10}); alternatively the notice must be placed in a
prominent position or must be issued to each berth holder.

Table 7.10 - Instructions for electricity supply


Berthing instructions for connection to the shore supply
This marina provides power for use on you leisure craft with a direct
connection to the shore supply which is connected to earth. Unless you have
an isolating transformer fitted on board to isolate the electrical system of your
craft from the shore supply system, corrosion through electrolysis could
damage your craft or surrounding craft.
ON ARRIVAL
Ensure that the supply is switched off before inserting the craft
1
plug.
The supply to the berth is ***V, **Hz. The socket outlet will
2
accommodate a standard marine plug coloured ****.
For safety reasons, your craft must not be connected to any other
3 socket outlet than that allocated to you and the internal wiring on
your craft must comply with the appropriate standards.
Every effort must be made to prevent the connecting flexible
three-core cable from falling into the water if it should become
4
disengaged. For this purpose, securing hooks are provided
alongside socket outlets for anchorage at a loop of tie cord.
For safety reasons, only one leisure-craft connecting cable may
5
be connected to any one socket outlet.
The connecting flexible cable must be in one length, without signs
6 of damage, and not containing joints or other means to increase
it’s length.
The entry of moisture and salt into the leisure-craft inlet socket
7 may cause a hazard. Examine carefully and clean the plug and
socket before connecting the supply.
It is dangerous to attempt repairs or alterations, if any difficulty
8
arises, contact the marina management.
BEFORE LEAVING
Ensure that the supply is switched off before the connecting cable
1
is disconnected and any tie cord loops are unhooked.
The connecting flexible cable should be disconnected first from
any marina socket outlet and then from the leisure craft inlet
2 socket. Any cover that may be provided to protect the inlet from
the weather should be securely replaced. The connecting flexible
cable should be coiled up and stored in a dry location where it will
not be damaged.
**** Appropriate figures and colours must be inserted
either 220-250 V blue,
or 380-415 V red.

Inspection and testing


Inspection and testing must be carried out in full accordance with BS 7671 (see {Chapter
8}). Periodic testing must be at least annually, but may need to be more frequent if the
marina is exposed or subject to misuse.

7.19.1 - Introduction

7.19.2 - Recommendations for exhibitions,


----------- shows and stands

7.19.1 - Introduction

There is no section in BS 7671 dealing with exhibitions, shows and stands. The following
is thus based on Chapter 12 of Guidance Note 7, which in turn depends on a draft 'EC
Publication. There can be little doubt that before long this material will become part of
the Regulations. The subject matter deals with temporary electrical installations in
exhibitions, shows and stands, both indoor and outdoor within temporary or permanent
structures. There will be increased risks in these situations due to:

1. - the temporary nature of the installations,

2. - severe mechanical stresses,

3. - lack of permanent structures, and

4. - access by the general public.

Since these risks are greater than those usually encountered, additional measures are
necessary.

7.19.2 - Recommendations for exhibitions, shows and stands

Shock protection
Protection against direct contact (see {3.4.5}) by means of obstacles and placing out of
reach must not be used, and neither must non-conducting location and earth-free
equipotential bonding be used as protection against indirect contact (see {3.4.6}).
Automatic disconnection of the supply is the preferred method, but because of the
difficulty of bonding all accessible extraneous conductive parts, PME supplies (TN-C-S
system) must not be used for temporary or outdoor installations. A TN-S system (where
the supply company provides an earth) could be used, but a TT system (earthed using an
electrode) is preferable. The maximum disconnection times are reduced to 0.2 s for 240 V
and to 0.05 5 for 415 V systems, which means that the earth fault loop impedance values
are reduced to those shown in {Table 7.4} for agricultural applications. Livestock are often
present at agricultural shows. In this case, supplementary bonding must connect all
exposed conductive parts and extraneous conductive parts which can be touched by them.

Distribution circuits which are at an increased risk of damage must be protected by an


RCD with a 300 to 500 mA rating; to provide discrimination with other RCDs protecting
final circuits, they should be time delayed. All final circuits for socket outlets must be
protected by RCDs rated at 30 mA. Final circuits for lighting which are accessible to the
public must also be protected by 30 mA RCDs. However, loss of light in a crowded space
is likely to cause a serious hazard, and such areas should be fed from at least two separate
circuits with separate RCD protection. Extraneous conductive parts on vehicles, wagons,
caravans etc. must be bonded to the protective system using conductors of not less than 4
mm².

Fire protection
Because of the increased risk of fire and burns in these locations, it is very important to
follow the advice given in {3.5}. Where SELV or PELV Systems are used (see{3.4.4}) they
must be insulated and tested as if they were 240 V circuits. Stored material, such as
cardboard boxes and fodder, are a special fire hazard. Remotely or automatically
controlled motors must be fitted with manual reset controls against excess temperature
and must be accessible only to skilled persons. Lighting equipment, such as incandescent
lamps, spotlights, projectors, etc., must be suitably positioned and guarded to prevent
overheating to themselves or of. adjacent surfaces. Sufficient ventilation must he
provided to prevent the build-up of heat.

Isolation
Every separate temporary structure and each distribution circuit supplying outdoor
installations must he provided with its own easily accessible and clearly identified means
of isolation.

Equipment
Equipment must he mounted away from positions which may not be weather-proof. Tent
poles are the most obvious place to mount equipment, but are often the weak point in the
weather tightness of temporary structures. Switchgear should be mounted in closed
cabinets which can only be opened by a key or a tool, but isolators must be always
accessible.

Wiring Systems
The types and protection of cables is of particular importance, as is the current carrying
capacity. Wherever there is a risk of damage, mechanical protection or armoured cables
should be used - trailing flexibles should never exceed 2 m in length to reduce the risk of
tripping and of damage to the equipment and terminations. Underground cables should be
clearly marked, hearing in mind that structure support pins may be 1 m long. Where a fire
alarm is not installed, cables must be of the flame retardant, low smoke type or enclosed
in conduit or trunking to prevent the spread of fire. There must be no joints in cables
except as a connection into a circuit. Where lurninaires are mounted below 2.5 m (within
arm's reach) they must be firmly fixed and carefully sited to reduce danger to people and
the possibility of fire. Electric motors must have isolation equipment breaking all poles,
and must be provided with adjacent emergency stop systems. Socket outlets are subject to
particular abuse by users in these situations. They should:

1. - be adequate in number,

2. - preferably not he floor mounted, but if so, must be mechanically protected and
waterproof,

3. -have no more than one flexible cable or cord connected to each plug,

4. - never have multiway plug-in adapters connected, and

5. - have no more than one portable trailing block multiway socket connected by
means of a
----- flexible cord not exceeding 2 m in length.

Safety systems
Where a generator is used to supply the temporary installation, there must be full earthing
using separate earth electrodes. For TN systems, all exposed conductive parts must be
bonded back to the generator. Where the exhibition is held in a building, care must be
taken to ensure that temporary structures do not impede escape routes. Where an
exhibition is constructed out-of-doors, a fire alarm system must be installed to enclosed
areas, and emergency lighting must be provided for escape routes.

Inspection and testing


The electrical installations of all stands must be re-tested on site after each assembly.
Exhibitors and stall holders must be encouraged to visually check electrical equipment
for damage on a daily basis.

7.2.1 - Introduction
--------- Installations upto Jan 1st 2002
--------- Installations after Jan 1st 2002

7.2.2 - Bath and shower room requirements


----------Installations upto January 1st 2002

7.2.2A - Bath and shower room requirements


----------Installations after January 1st 2002
The April 2000 amendments to BS7671 (AMD 10983) have changed all of the Regulations
relating to bath and shower rooms. Although the principles remain the same, much of the
detail has been altered. For example, bath and shower rooms have now been split into
zones, as was previously the case only for swimming pools and saunas.

The amended regulations Section 601 may be used at once,


but must be used for all installations after January 1st, 2002.

Up to that time either set of Regulations may be applied, but whichever is chosen must be
used in its entirety. It is not permitted to mix the two versions of Section 601.

7.2.1 - Introduction - prior to January 1st, 2002

People using a bathroom are often unclothed and wet. The absence of clothing
(particularly shoes) will remove much of their protection from shock (see{3.4}), whilst the
water on their skin will tend to short circuit its natural protection. Thus, such people are
very vulnerable to electric shock due to their reduced body resistance, so special
measures are needed to ensure that the possibility of contact (either direct or indirect) is
much reduced. Guidance Note 7 (Special Locations) provides data on the impedance of
the human body. However, the figures are complicated by the fact that values differ
significantly from person to person; it would be sensible to assume a worst case
possibility which suggests that the impedance of the human body from hand to foot is as
low as 500 Ohms. Since this calculates to a body current of 460 mA at 230 V, we are
considering a fatal shock situation. When the fact that the impedance figures assume a
dry body are taken into account and may be halved for wet people, we come to a shock
current approaching I A! Attention is drawn to the fact that a bath used for medical
treatment may need special consideration, because the possible hazard is greater.

Appliances and sockets for use in these high-risk areas must be separated extra-low
voltage (SELV) type, at a potential not exceeding 12 V; the exception is a shaver unit fed
from a double wound transformer to BS EN 60742 (see {5.8.4}). Such equipment must be
protected to level IP2X, which means that it must be impossible to touch live parts with a
finger, and must have insulation capable of withstanding a voltage level of 500 V r.m,s.
for one minute. Such socket outlets, or fused connection units in a bathroom or a
bedroom containing a shower cubicle, must be protected by an RCD with an operating
current no greater than 30 mA,

The special requirements of this section do not apply to rooms (such as bedrooms)
containing an enclosed and prefabricated shower basin, provided that switches are not
mounted within 0.6 m or sockets within 2.5 m of the door opening as indicated in {Fig
7.1}.
7.2.1 Introduction - ( - after to January 1st, 2002 )

People using a bathroom are often unclothed and wet. The absence of clothing
(particularly shoes) will remove much of their protection from shock (see (3.4)), whilst
the water on their skin will tend to short- circuit its natural protection. Thus, such people
are very vulnerable to electric shock due to their reduced body resistance, so special
measures are needed to ensure that the possibility of contact (either direct or indirect) is
much reduced. Guidance note 7 (Special Locations) provides data on the impedance of
the human body. However, the figures are complicated by the fact that values differ
significantly from person to person; it would be sensible to assume a worst case
possibility which suggests the impedance of the human body from hand to foot is as low
as 500 ohms. Since this calculates to a body current of 460mA at 230V we are
considering a fatal shock situation. When the fact that the impedance values assume a dry
body are taken into account and may be halved for wet people, we come to a shock
current approaching 1 A! Attention is drawn to the fact that a bath used for medical
treatment or for disabled people may need special consideration, because the possible
hazard is greater. The special requirements of this section do not apply to rooms (such as
bedrooms) containing an enclosed and prefabricated shower basin, provided that switches
are not mounted within 0.6m or sockets within 2.4m of the shower door opening as
indicated in (Fig 7.1a) All socket outlets in such rooms must be protected by an RCD with
a rating no higher than 30mA. The special requirements do not apply to emergency
facilities in industrial areas and laboratories. Fig 7.1a) Permissible positions of switches
and socket outlets in a room containing a shower cubicle but no bath.

7.2.2 - Bath and shower room requirements


for installations up to 1st january 2002

Usually, protection against direct contact will be by means of earthed equipotential


bonding and automatic disconnection of the supply in the event of a fault (the same as for
most other installations), and the special requirements are:

1. -where the plumbing in the bathroom has been carried out using metal pipes
(usually of copper), all extraneous conductive parts must be bonded together and to earth
with BS 951 clamps (see {Fig 7.2}), and with no exposed metallic conductors. The
exception to this is any SELV system, which must remain unconnected to the main
earthing system

Fig 7.1 - Permissible positions of switches and socket outlets


in a room containing a shower cubicle but no bath
Fig 7.2 - Bonding requirements for a bathroom with a metal pipe
plumbing system [601-04-02] - the line showing bonding
connections does not represent the actual positions of the cable

2. - where the plumbing in the bathroom has been carried out using plastic pipes there is
no need for bonding at all other than to connect exposed metalwork of equipment such as
luminaires, heaters and showers to earth. It is not necessary to bond exposed copper pipes
provided that they are less then 0.5 m long.

3. - the earth fault loop impedance must be low enough to allow disconnection within 0.4
s (see {5.3}).

In no case within a bathroom is it permissible to rely for protection against direct contact
on obstacles, placing out of reach, a non-conducting location or earth-free equipotential
bonding. Switches must be out of reach of a person using the bath or shower, although
cord-pull and similar remotely controlled switches may be used. There must be no
switchgear, control gear or accessories installed within the bath or shower basin, whilst
wiring must not be metallic sheathed, or enclosed in metallic conduit or trunking if run on
the surface. The installation of equipment within a bath may sound ridiculous, but jacuzzi
pumps and devices to assist disabled people to get into and out of a bath are not
uncommon. Where, as is often the case, controls are mounted on the bath, the whole
system must be fed at no more than 12 V.

Lampholders must be provided with a protective shield (see {Fig 6.11}) if within 2.5 m of
the bath, or totally-enclosed luminaires must be used. Electrical equipment installed
beneath a bath (an example is a jacuzzi pump) must only be accessible after the use of
tools. If electric floor heating is used in a room containing a bath or a shower cubicle, it
must have its metal sheath, or a covering metal grid if there is no metallic sheath,
connected to the local equipotential bonding.

Guidance Note 7 makes it clear that before long bathrooms will be divided into zones
(not unlike those for a swimming pool) with strict requirements for the ingress of water
into equipment installed in these zones. The suggestion is based on Regulations already
agreed by CENELEC but not yet accepted in the UK,

7.2.2A - Bath and shower room requirements (amended)

The revised Regulations for bath and shower rooms are based on the dimensions of four zones
into which the space is divided.

Zone O.
is the interior of the bathtub or the shower basin. In those cases where a shower has no basin,
the zone extends 50mm above the floor and includes the volume within the vertical surface at a
radius of 1.2m from the water outlet position of a demountable shower head, or at a radius of
0.6m from the position of a fixed shower head.

Zone 1.
extends from Zone 0 up to 2.25m above the floor, and outwards to the extent of the bath or basin,
or the extent of Zone 0 as defined above where there is no shower basin. It includes the space
below a bath or shower tub or basin where that space is accessible without the use of a tool.

Zone 2.
extends outside Zone 1 for 0.6m horizontally and up to a height of 2.25m. If the ceiling height is
more than 2.25m, the space above Zone 1 up to 3m is also zone 2

Zone 3.
extends outside Zone 2 for 2.4m horizontally and up to a height of 2.25m. If the ceiling height is
more than 2.25m, the space above Zone 2 up to 3 m is also Zone 3

If the space under a bathtub or shower basin can only be accessed with the use of a tool, that
space is outside the zones. If no tool is required the space is Zone 1.

The extent of the zones is shown in Figs 7.1b) to 7.1g) in diagrams which are not to scale.

Figure 7.1b) - Zones for a bathroom (plan).


Note that the same zones apply to a shower room with a shower basin.

Figure 7.1c) - Zones for a bathroom (elevation).


Note that the same zones apply to a shower room with a shower basin.

Figure 7.1d) - Zones for a shower with no basin and a fixed head.

Figure 7.1e) - Zones for a shower room (elevation)


without a basin and having a fixed showerhead.

Where SELV (safety extra-low voltage, see (3.4.4) is used, protection against direct contact must
be provided by barriers or enclosures to IP2X (no finger contact) or by insulation which will
withstand 500 V a.c for one minute. PELV (which is earthed SELV) is not permitted in bath and
shower rooms. Local supplementary equipotential bonding must be installed to connect together
the exposed conductive parts of Class 1 and Class 11 equipment in Zones 1,2, and 3 together
with extraneous conductive parts, such as metal baths and shower trays, metallic pipes for water,
gas, central heating, air conditioning. etc in all zones. Accessible structural metal must also be
bonded, although this is unnecessary in the cases of metal door architrave's, window frames and
so on, unless these parts are connected to the metal structure of the building (see Fig 7.2, page
127, Electrician's Guide), which in practice is unlikely. These bonding requirements do not apply
to Zone 3 where a prefabricated shower or bath is installed in a bedroom.
In some cases, safety extra-low voltage (SELV) at 12V a.c. or 30V ripple-free d.c. is used within
bath and shower basin (for example for hoists used by disabled persons). Such systems must be
protected against direct contact by the use of barriers or enclosures to IP2X (not accessible by
human fingers) or must have insulation that will withstand a test voltage of 500 V a.c. for 1 min.
The safety source supplying such a SELV system must be situated outside Zones 0, 1 and 2.
Protections by obstacles (3.4.5), placing out of reach (3.4.5), or a non-conducting location (5.8.2)
are not allowed in bath or shower rooms.

In every zone, the only wiring permitted is that feeding equipment in that zone, or where it must
pass through that zone to reach another unless it is buried deeper than 50mm from the surface.
For example, wiring to fixed equipment in Zone 0 may have to pass through Zones 1, 2 and 3 to
reach its destination. Zone 2 may be used as a route for wiring needed to feed equipment in Zone
1 below the bath tub or shower or shower basin. In other words, the zones in a shower or
bathroom must not be used as routes for through wiring that feeds other services outside the
area.

Switch and control gear is permitted in any zone if such gear is incorporated in the equipment
installed there, which is suitable for use in that zone. No other switch or control gear is permitted
in Zone 0. In Zone 1, only switch and control gear for SELV may be installed, but the safety
source for the system must be installed outside Zones 0, 1 and 2. In Zones 2 and 3 or outside the
zones but within the bath or shower room, switches and socket outlets are permitted providing
that they are fed from an SELV source installed outside Zones 0, 1 and 2. The exception to this is
the socket outlet on a shaver supply unit that complies with BS EN 60742, Chapter 2, Section 1,
which may be installed in Zones 2 and 3. Insulated operating cords of pull switches are permitted
in Zones 1, 2 and 3 but they must comply with BS 3676. All equipment installed in Zone 3 must
be protected by an RCD with a rating not exceeding 30 mA.

Electrical equipment installed in a room containing a bath or shower must have protection against
the ingress of water as follows:-

in Zone 0, only equipment which is intended for that situation, water protected to IPX7 or

in Zones 1 and 2, IPX4 or


which is protection from splashing. Where water jets may be used for cleaning, such as in public
bath and shower facilities, IPX5 or applies, which gives protection against water jets.

in Zone 3, IPX5 or must again be used if cleaning by water jets is likely. See (Table 2.4.), for
details of the index of protection (IP) system.

Fixed current-using equipment may be installed in Zone 0 if this is the only reasonable location
for it and it is suitable for the conditions in the zone. Water heaters and shower pumps may be
installed in Zones 1 and 2, as may other equipments suitable for the conditions, provided that
they have the required protection against water and are protected by an RCD with a rating of not
more than 30 mA. In Zone 2, luminaires, fans, heating appliances and units for whirlpool baths
may also be installed, provided that they comply with the relevant standards. Electric under-floor
heating may be installed provided that below any zone a metallic grid or plate connected to the
local supplementary equipotential bonding covers it. SELV equipment may be used in any zone
provided that its safety source is installed outside Zones 0, 1 and 2.

Fig 7.1g) - Zones for a shower room without a basin and


having a demountable shower head.
Remember this Amendment is optional until 1.1.2002 Now return to Section 7.3, page 128 of
Published by EPA Press Tel 01799 541207 Fax 01799 541166

7.4.1 - Introduction

7.4.2 - Special requirements for saunas

7.4.1 - Introduction

A sauna is a room in which the air is heated to a high temperature, humidity usually being
very low, but occasionally increasing when water is deliberately poured over the heater.
People using a sauna are usually unclothed and often wet (mainly due to perspiration),
the absence of clothing (particularly shoes) removing much of their protection from
shock (see{3.4.2}).

Special Regulations for saunas are new in the 16th Edition. As with bathrooms and
swimming pools, zones are again classified, but this time they are concerned more with
temperature levels than contact with water.

Zone A
The volume within 0.5 m horizontally from the Sauna heater and extending from the
floor up to within 0.3 m from the ceiling.

Zone B
The volume covering the whole of the sauna room outside zone A up to 0.5 m above the
floor

Zone C
The volume directly above zone B and extending upwards to within 0.3 m from the
ceiling.

Zone D
The volume covering the whole floor area of the room and extending down from the
ceiling for a distance of 0.3 m, including the space in this volume directly above the
sauna heater.

The extents of the four zones are shown in {Fig 7.4}.


Fig 7.4 - Definition of zones for sauna rooms

7.4.2 - Special requirements for saunas

If separated extra-low voltage (SELV) is used, protection against direct contact must be
provided by:
1. - enclosures or barriers providing protection to IP24. This means protection against
entry of human fingers and from splashing water, and
2. -insulation which will withstand a voltage of 500 V r.m.s. for one minute.

Some of the standard measures for protection against both direct and indirect contact
must not be used in saunas. These are:
1. -obstacles,
2. -placing out of reach,
3. - non-conducting location, and
4. -earth free equipotential bonding.

All equipment must be protected to at least IP24, and no equipment other than the sauna
heater may be installed in zone A. There must be no socket outlets in a sauna room, nor
other switchgear which is not built into the sauna heater; lighting switches must be
positioned outside the sauna room. As well as having no socket outlets within the sauna
room, it is advisable not to install them close to the room at all, which could encourage
the introduction of portable appliances. In the lower part of the room where it will not be
so hot (zone B) there is no special requirement concerning the heat resistance of
equipment. If installed in zone C, equipment must he suitable for operation at an ambient
temperature of 125°C, and only luminaires, mounted so as to prevent them from
overheating, are allowed in zone D. All wiring must be carried out with flexible cables or
cords having 180°C rubber insulation complying with BS 6141: 1992, although where
higher rated cables are required they may be 180°C rubber insulated to BS 6007. All
wiring must be enclosed within insulated wiring enclosures such as plastic trunking.

There is no specific requirement to use RCD protection for sauna equipment, but where it
is desired to do so, attention is drawn to the high leakage currents common with sauna
heating elements, particularly when water is applied. The manufacturer should be
consulted to ensure that leakage currents are unlikely to cause problems with an RCD
rated at 30 mA. In some cases an RCD with a 100 mA rating may be more satisfactory.

7.6.1 - Introduction

7.6.2 - Agricultural installations

7.6.3 - Electric fence controllers

7.6.4 - Horticultural installations

7.6.1 - Introduction

Situations of these kinds will pose an increased risk of electric shock because people and
animals are more likely to be in better contact with earth than in other installations.
Animals are particularly vulnerable, because their body resistance is much lower than for
humans, and applied voltage levels which are quite safe for people may well prove fatal
for them. If animals are present, the electrical installation may be subjected to mechanical
damage (animals cannot be instructed to keep away from installations) as well as to a
greater corrosion hazard due to the presence of animal effluents.

The special requirements for agricultural and horticultural installations also apply to
locations where livestock are kept, such as stables, chicken houses, piggery's, etc. They
also apply to feed processing locations, lofts, and storage places for hay, straw and
fertilisers.

For these reasons, special Regulations apply to such installations, both indoors and
outdoors. It is important to recognise that dwelling houses on agricultural and
horticultural premises used solely for human habitation are excluded from these special
requirements.

7.6.2 - Agricultural installations


Of paramount importance where livestock are present is the indication that the levels of
separated extra-low voltage (SELV) are too high. Whilst the Regulations do not suggest a
safe voltage for animals, simply suggesting a level 'appropriate to the type of livestock', a
practical value is likely to be no higher than 25 V. Such systems, as well as those
complying with SELV requirements, must be protected to IP44 (ie, protected from solid
objects not exceeding 1 mm and from splashing water) or the insulation must be able to
withstand 500 V r.m.s. for one minute.

All socket outlets must be protected by residual current device(s) (RCDs) with an
operating current of no more than 30 mA. Whilst it is accepted that livestock cannot be
protected by earthed equipotential bonding and automatic disconnection (sometimes
known as EEBAD) because the voltages to which they would he subjected in the event of
a fault are unsafe for them, changes to standard installation requirements do offer some
additional protection. The requirements are:

1. - Disconnection times for the operation of protective devices are reduced, usually to
half the normal value. The maximum times are voltage related, and are shown in {Table
7.3}.

Table 7.3 - Maximum disconnection times for agricultural circuits for


----------------- livestock (TN systems)
Supply voltage (Uo) Disconnection time
(volts) (seconds)
120 0.35
220 to 277 0.20
400 and 480 0.05

The application of these reduced connection times leads to the reduced levels of
maximum earth-fault loop impedance, shown in {Table 7.4} for 240 V circuits.

2. -Fixed equipment and distribution circuits are permitted to have a disconnection


time of 5 s, which is the same as for normal installations, and require the maximum earth-
fault loop impedance values shown in {Tables 5.2 and 5.4}. An exception is where the
fixed equipment is fed from the same distribution board as circuits requiring
disconnection in 0.2 s at 240 V. In such a case Either the resistance of the main protective
conductor from the distribution board to the point of connection to the main equipotential
bonding system must be low enough to ensure that its volt drop when fault current flows
does not exceed 25 V,

or the distribution board must have its exposed conductive parts bonded to all extraneous
conductive parts (such as water pipes) in the area.

3. - The maximum of 25 V for the potential difference across the protective conductor
under fault conditions stated above is applied to all final circuits. This is half of the level
accepted in other installations, so the protective conductor resistance must have half the
normal value. Note that where an IT system (usually a generating plant) is used, special
requirements apply - these are outside the scope of this Guide, and advice must be sought
from a qualified electrical engineer.

4. - Supplementary equipotential bonding must be applied to connect together all exposed


and extraneous conductive parts which are accessible to livestock and the main protective
system. It is recommended that a metallic grid should be laid in the floor and connected
to the protective conductor.

5. - Where an RCD is used it is important to ensure that the earth electrode resistance is
not so high that the 25 V level will be exceeded before operation. This can be verified by
using the expression

RA = 25
IAn

where RA = the combined earth electrode and protective conductor resistance,


and An = the rated residual operating current of the RCD.

Application of the expression gives 833 Ohms for a 30 mA device, 250 Ohms for a 100
mA, 83 ohms for a 300 mA and 50 Ohms for a 500 mA. Values higher than 200 Ohms
should not be used or there may be instability. The resistance of the protective conductors
is usually negligible compared with that of the earth electrode.

The equipotential bonding required will create an earth zone, and special measures are
necessary where a circuit fed from this zone extends outside it. If the equipment could be
touched by a person in contact with the general mass of earth, disconnection time must
not exceed 0.2 s, even for fixed equipment. This means that {Table 7.4} will apply to such
circuits.

Fire is a particular hazard in agricultural premises where there may be large quantities of
loose straw or other flammable material. A particular fire hazard on agricultural premises
is damage to the wiring by rodents gnawing at cables. This effect can be reduced by cable
runs which are below ceilings rather than in roof spaces and by the use of steel conduits.
The Regulations require the protection of the system by an RCD with an operating
current not greater than 500 mA. In practice, a 300 mA rating is likely to be used. This
will result in problems of discrimination between this unit and those of lower operating
current rating unless the main RCD is of the time delayed type (see {5.9.3}). Care must be
taken to ensure that heaters are not in positions where they will ignite their surroundings;
a clearance of at least 500 mm is required for radiant heaters.

All electrical equipment must be protected to IP44, and chosen to be suitable to operate
under the onerous conditions they will experience. Wiring must be inaccessible to
livestock and must be vermin proof. In practice, this will probably mean enclosure in
galvanised steel conduit, or the use of mineral insulated cables, Switch and control gear
must be to IP44 and constructed of, or enclosed in, insulating material. Switches for
emergency use must not be in positions accessible to cattle, or where cattle may make
operation difficult. Emergency switches should disconnect all live conductors including
the neutral. It may be necessary to omit isolators in some cases to ensure that essential
supplies (such as broiler house fans) are not disconnected unintentionally. The likelihood
of panic amongst animals when emergencies occur must be taken into account.

Table 7.4 - Maximum earth-fault loop impedance values for 240 V


agricultural circuits to give a maximum 0.2 s disconnection time
Type of protection Protection rating Max. loop impedance
(A) (ohms)
Cart. Fuse, BS 1361 5 9.60
15 3.00
20 1.55
30 1.00
Cart. Fuse BS 88 pt 2 6 7.74
10 4.71
16 2.53
20 1.60
25 1.33
32 0.92
MCB type 1 5 12.00
10 6.00
15 4.00
20 3.00
30 2.00
MCB type 2 5 6.86
10 3.43
15 2.29
20 1.71
30 1.14
MCB type 3 5 4.80
10 2.40
15 1.60
20 1.20
30 0.80

7.6.3 - Electric fence controllers

Electric fences are in wide use to prevent animals from straying. In most cases they are
fed with very short duration pulses of a voltage up to 5 kV - however, the energy
involved is too small to cause dangerous shock. Usually animals very quickly learn that it
can be painful to touch a fence, and give it a wide berth. {Fig 7.7} indicates a typical
arrangement for an electric fence, the numbers in brackets in the following text relating to
the circled numbers on the diagram.

Controllers may be mains fed or battery operated. Controllers must be to BS EN 61011-1,


and not more than one controller may be connected to a fence (1). So that it will give a
short, sharp shock to animals, the high voltage output of the controller is connected
between the fence and an earth electrode. It is of obvious importance that the high voltage
pulses are not transmitted to the earthed system of a normal electrical installation because
the earth zones overlap (4). A method of checking the earth zone of an electrode is
described in {8.6.1}. For similar reasons it is important that the fence should never make
contact with other wiring systems (2), telephone circuits, radio aerials, etc; the installer
must also take account of induction from overhead lines, which may occur when the
fence runs for a significant distance below such a line.

Fig 7.7 - Electric fence controller

A mains operated fence controller must be installed so that interference by unauthorised


persons and mechanical damage is unlikely. It must not be fixed to a pole carrying mains
or telecommunication circuits, except that where it is fed by an overhead line consisting
of insulated conductors, it may be fixed to the pole carrying the supply (3).

7.6.4 - Horticultural installations

A horticultural installation is likely to be subject to the same wet and high-earth-contact


conditions experienced in agriculture, but will be free from the extra hazards associated
with the presence of animals. In other respects it is subject to the same requirements as an
agricultural installation as described in {7.6.2}. A type of load not so likely to be present in
the agricultural situation is the soil warming circuit often used in horticulture. The
relevant Regulations for such circuits are considered in {7.11.4}.

7.8.1 - Introduction

7.8.2 - Special regulations for equipment with


---------- high earth currents

7.8.1 - Introduction

Data processing equipment is extremely common. Such computer based equipment are
used in the office for word processing, handling accounts, dealing with wages and so on.
In the factory they control processes, and in the retail shop they are used for stock
control, till management and many other purposes. Even in the home we are starring to
see their use for security, for temperature control, for domestic banking services, etc.
Telecommunications equipment is also becoming more widely used.

All such equipment have a common danger of failing and losing their stored data if
subject to mains disturbances such as voltage spikes and transients. They are protected
from such failures by feeding the supplies to them via filter circuits, which are designed
to remove or reduce such voltage variations before they reach the sensitive circuitry. A
simple filter is shown in {Fig 7.8} and will almost always include resistive and capacitive
components which are connected from live conductors to earth. This will give rise to
increased earth currents, driven by supply voltage through the resistive and reactive
components. When the circuit, including the filter, is switched on, higher earth currents
will usually flow for a very short time whilst capacitors are charging.

Data processing and telecommunications equipment of this kind therefore has high levels
of earth current in normal use, although in most cases the earth current produced by a
filter will not exceed 3.5 mA. Where a number of equipments containing filters are fed
from a single circuit, the total supply current may be low due to the small demand of each
device, but the total earth leakage current may well be very high. Consequently, special
regulations apply to the protective and earthing conductors of such circuits.
Fig 7.8 Mains transient suppression filter

7.8.2 - Special regulations for equipment with high earth currents

Electricity Supply Regulation 26 indicates that the level of earth leakage current should
not normally exceed one ten thousandth part of the installation maximum demand (for
example, 10 mA earth leakage current for an installation with a maximum demand of 100
A). Data processing equipment is likely to have a higher leakage current than this, so
special regulations become necessary. Foremost is the requirement that where earthing is
used for functional purposes (to allow the filters to do their job) as well as protective
purposes, the protective function must take precedence. When the earth leakage current is
high, serious shocks are likely from accessible conductive parts which are connected to a
protective conductor which is not itself solidly connected to the main earth terminal.

Any piece of equipment having a leakage current exceeding 3.5 mA must be fitted with a
label adjacent to the primary power connection which reads:-

"HIGH LEAKAGE CURRENT


earth connection essential
before connecting the supply"

Stationary equipment with an earth leakage current exceeding 3.5 mA must be


permanently connected, or an industrial plug and socket to BS EN 60309-2 must be used.
When a socket outlet circuit may he expected to feed data processing equipment with
normal earth leakage current of more than 10 mA, or if the earth leakage current for a
circuit feeding fixed stationary equipment is greater than 10 mA, earthing must be
through a high integrity protective system complying with at least one of the following:

1. - a protective conductor of cross-sectional area at least 10 mm²

2. - duplicated protective conductors having separate connections and each of at least 4


mm² cross-sectional area
3. - duplicated protective cross-sectional areas of all the conductors is at least 10 mm², in
which case the metallic sheath, armour or braid of the cable may be one of the protective
conductors, provided that it complies with the adiabatic equation of [543-01-03] (see
{5.4.4})

4. - duplicated protective conductors, one of which can be metal conduit, trunking or


ducting, whilst the other is a 2.5 mm² conductor installed within it

5. - an earth monitoring device is used which switches off the supply automatically if the
protective conductor continuity fails (see [543-03-05])

6. - connection of the equipment to the supply through a double wound transformer, a


protective conductor complying with one of the arrangements 1 - 5 above connecting
exposed conductive parts to a point on the secondary winding.

The reason for these precautions is that if the circuit protective conductor should become
open circuit, leakage current could flow to earth through a person touching exposed
conductive parts with possibly lethal consequences.

The alternative to items 1 to 6 above is the use 13 A sockets to BS 1363. In all cases the
protective conductors must have a minimum size of 1.5 mm² with both ends of the ring
connected to separate earth terminals at the distribution board. There must be no spurs on
ring circuits, or branches on radial circuits, which must have a duplicate protective
conductor as shown in {Fig 7.9}. Where twin or triple socket outlets are used, they must
be provided with two earth terminals, one for each protective conductor. Where
protective conductors are not in the same sheath, conduit or trunking as circuit
conductors, they must be 4 mm²rather than 1.5 mm².

Fig 7.9 Radial circuit with duplicated protective conductor

Where an installation having more than one item of stationary equipment with earth
leakage current exceeding 3.5 mA is protected by an RCD the sum of the earth leakage
currents due to data processing equipment must not exceed 25% of the device tripping
current. Where this requirement cannot be met, connection must be via a double wound
transformer as in item 6 above. For other installations, no specific figure for the leakage
current as a percentage of tripping current is given; the requirement is that the normal
leakage current will be unlikely to cause unnecessary tripping [531-6]. The 25% limit
means effectively either that a single RCD with a high operating current must be used, or
that the installation must be subdivided to allow a number of lower rated RCDs to be
used. If the Electricity Supply Company does not provide an earthed terminal and an
installation electrode is required (TF system), the result of multiplying the total earth
leakage current in amperes and twice the resistance of the earth electrode in ohms must
not exceed 50 (volts). For normal TT systems, there is no need to double the earth
electrode resistance, so in the case of data processing equipment the earth electrode
resistance must effectively be half its value for other installations. Data processing
equipment must not he connected to a system which is not earthed in the normal way (IT
system).

7.10.1 - Introduction

7.10.2 - Highway and street furniture regulations

7.10.1 - Introduction

Regulations for highway power supplies feeding street furniture and street located
equipment are new to the 16th Edition. The need for such regulations has arisen because
of the increasing use of electrical supplies for street and footpath lighting, traffic signs,
traffic control and traffic surveillance equipment. These uses are described as street
furniture. Also covered by the Regulations is street located equipment which includes
telephone kiosks, bus shelters, advertising signs and car park ticket dispensers. As far as
the Regulations are concerned, no distinction is drawn between the two categories, both
street furniture and street located equipment being subject to their requirements.

It must not be thought that these Regulations apply only to installations on public
highways. They must also be followed in installations within private roads, car parks, and
other areas where people will be present. They do not apply to suppliers' works, which in
this context means the overhead or underground supplies feeding the equipment. It does
apply, however, to overhead or underground supplies installed to interconnect street
furniture or street located equipment from the point of supply.

7.10.2 - Highway and street furniture regulations


The equipment covered by these regulations is always, by definition, accessible to people
of all kinds; however, maintenance must only be carried out by skilled and/or instructed
persons. Thus, certain measures for protection in areas only open to skilled or instructed
persons are not appropriate here. For example. protection by barriers or by placing out of
reach must not be used, because those using the areas may not be aware of the dangers
which follow from climbing over barriers or reaching up to normally untouchable parts.
The equipment considered here usually has doors which give access to the live parts
inside. Such doors must not allow unauthorised access to live parts, and must therefore
either:

1. - be opened only with a special key or tool, or

2. - be arranged so that opening the door disconnects the live parts. The doors of street
furniture, such as lamp standards, are often damaged or even totally removed. Therefore,
live parts within must be protected by enclosures or barriers to give protection to IP2X, to
ensure that they cannot be touched.

Many types of street furniture and street located equipment are fed using overhead cables.
The usual protection against direct contact by 'placing out of reach' is acceptable for such
systems, but special regulations apply to the equipment fed. Where uninsulated low
voltage overhead conductors are more than 1.5 m vertically from the equipment, it may
be maintained by a suitably instructed person. If the vertical clearance is less than 1.5 m,
only a skilled person who has been trained in live working may be involved. All cables
buried directly should have a marker tape placed above them, 150 mm below the ground
surface. To prevent disturbance, burial depths are usually 450 mm below verges and 750
mm below the highway. Very careful plans and records must be kept to show exactly
where such cables are buried.

Protection against indirect contact (metalwork not normally expected to be live) cannot
be achieved in these installations by a non-conducting location, earth-free equipotential
bonding or electrical separation. The danger to the people who may touch metalwork is
no more in this case than with electrical equipment indoors, so a 5 s disconnection time is
acceptable where earthed equipotential bonding and automatic disconnection of the
supply is employed. To prevent the effects of a fault being 'imported' or 'exported',
adjacent metal structures should not be bonded to the circuit protection system.

Installations of this type are usually simple, often consisting of a single circuit feeding
lighting. Provided that there are no more than two circuits, there is no need to provide a
main switch or isolator, the supply cut-out (main supply fuse in most cases) being used
for this purpose if not rated at more than 16 A, but only by instructed persons. However,
where the supply is provided by a separate supplier (the Electricity Supply Company),
their consent to use of the cut-out for this purpose must first be obtained as with any other
installation.

Internal wiring in all street electrical equipment must comply with the normal
Regulations concerning protection, identification and support (see {4.5, 4.6 and 4.4.1}).
Attention is drawn particularly to the need to support cables in vertical drops against
undue stress. The notice indicating the need to provide periodic testing is unnecessary
where an installation is subject to a planned inspection and test routine.

Temporary installations such as those for Christmas or summer external lighting schemes
are usually connected to highway power supplies. In many cases, street furniture is
equipped with temporary supply units from which such installations can be fed. The
temporary supply unit must have a clear external label indicating the maximum current it
is intended to supply. Attention is drawn to the possibility of damage to existing cable
connections by the frequent connection and disconnection of temporary supplies. It is
recommended that a socket outlet, especially intended to feed temporary installations,
should be part of the temporary supply unit and should be fixed within the street furniture
enclosure. Such installations must comply with the requirements for construction site
installations (see{7.5}) and must not reduce the safety of the existing installation.

Highway equipment is usually subjected to vibration, corrosion and condensation, and


sometimes to vandalism. It should be chosen with such problems in mind. The heat
produced by lamps and control gear will usually be sufficient to prevent condensation
and corrosion, but thought should be given to the provision of a low power heater in other
cases.

Inspection and testing is necessary as for all electrical installations, and should be
synchronised with other maintenance work, such as white lining and re lamping, to avoid
inconvenience to highway users as far as is possible. In general, a period of six years
between tests is acceptable for fixed installations, and three months for temporary
systems.

7.12.1 - Low voltage discharge lighting

7.12.2 -High voltage discharge lighting

7.12.1 - Low voltage discharge lighting

The very high luminous efficiency of discharge lamps has led to their almost universal
application for industrial and commercial premises; the introduction of low rated types as
direct replacements for filament lamps is beginning to see their wider use in domestic
situations.

Discharge lamps are those which produce light as a result of a discharge in a gas.
Included are:

Fluorescent
Really low pressure mercury vapour lamps, very widely used for general lighting in
homes, shops, offices, etc.
High pressure mercury
Provide a very intense lighting level for outside use in situations where the (sometimes)
poor colour rendering is not important.

Low pressure sodium


The most efficient lamp of all, but its poor colour (orange) light output limits its use to
street and road lighting

High pressure sodium


The acceptable golden light colour enables the lamp to he used for road and outside
lighting in areas where better colour rendering is needed, as well as for large indoor
industrial applications.

Discharge lamps, unlike their incandescent counterparts, require control gear in the form
of chokes, ballasts, autotransformers and transformers. These devices result usually in a
lagging power factor, which is corrected, at least partially, by connecting capacitance
across the supply. This control gear should be positioned as close as possible to the
lamps. Because of low power factor and the inductive/capacitive nature of the load,
switches should be capable of breaking twice the rated current of a discharge lamp
system, and maximum demand is calculated by using a multiplying factor of 1.8 {6.2.1}.

Electronic devices are becoming increasingly common to provide high voltage pulses to
assist discharge lamps to strike (start). These pulses can cause problems with insulation
breakdown in some types of cable, particularly low voltage mineral insulated types.

7.12.2 -High voltage discharge lighting

Earlier versions of the 15th Edition of the Wiring Regulations included detailed
requirements for high voltage discharge lighting circuits, which almost always means
neon sign installations. The Regulations have now omitted most of this detail, which is
contained in BS 559. Any electrician who will be concerned with the high voltage aspects
of such installations should therefore take expert advice, which is likely to include
making reference to the BS.

Low voltage wiring to feed the transformers in this kind of installation is similar to most
other installations except that special requirements apply to the Fireman's Switch which
controls the installation and allows the fire service to make sure that high voltages have
been isolated before playing water on the system. These special requirements have been
covered in {3.2.2} and will not be repeated here.

7.14.1 - Temporary and garden buildings

7.14.2 - Garden installations


7.14.1 - Temporary and garden buildings

Many dwelling houses have buildings associated with them which are not directly part of
the main structure. These include garages, greenhouses, summer houses, garden sheds,
and so on. Many of them have an installation to provide for lighting and portable
appliances. It is important to appreciate that the lightweight (and sometimes temporary)
nature of such buildings does not reduce the required standards for the electrical
installation. On the contrary, the standards of both the installation and its maintenance
may need to be higher to allow for the arduous conditions.

Particular attention must be paid to the following:

1. - supplies to such outbuildings must comply with the requirements for overhead and
underground supplies stated in {7.13}, Garden layouts are very likely to change over a
period of time, so all cables should be buried to a depth of at least 450 mm with a route
marker tape at 150 mm. Cable runs must be recorded on careful drawings, and wherever
possible should follow the edges of the garden plot,

2. - the equipment selected and installed must be suitable for the environment in which it
is situated. For example, a heater for use in a greenhouse will probably meet levels of
humidity, temperature and spraying water not encountered indoors, and should be of a
suitably protected type,

3. - the earthing and bonding must be of the highest quality because of the increased
danger in outdoor situations. All socket outlets should be protected by 30 mA RCDs.

7.14.2 - Garden installations

Increasing use is being made of electrical supplies in the garden, for pond pumping
systems, lighting, power tools and so on. The following points apply:

1. - Socket outlets installed indoors but intended to provide outdoor supplies must be
protected by an RCD with a maximum operating current of 30 mA. Any portable
equipment not fed from a socket outlet must also be protected by an RCD with a 30 mA
operating current. Outdoor sockets also require the same RCD protection and must also
satisfy IP44 requirements (see {2.4.3}).

2. - Garden lighting, pond pumps and so on should preferably be of Class Ill construction,
supplied from a SELV system and having a safety isolating transformer supply. Where
240 V equipment must be used, it should be Class II double insulated (no earth) and
should be suitably protected against the ingress of dust or water. If accessible Class I
equipment is used its supply system must have an earth fault loop impedance low enough
to allow disconnection within 0.4 s in the event of an earth fault.

3. - Earthing must be given special attention. All buildings must be provided with 30 mA
RCD protection, but the Electricity Supply Company should be consulted to ascertain
their special requirements if the supply system uses the PME (TN-C-S) system. Where
the supplier does not provide an earth terminal, each outbuilding must be provided with
an adjacent earth electrode.

4. - Outbuildings are often of light construction and therefore are subject to extremes as
far as temperature swings are concerned. It is therefore important to bear this in mind
when selecting equipment and components.

5. - Extraneous conductive parts of an outbuilding which may become live due to a fault
should be bonded to the incoming protective conductor.

6. - Every outbuilding with an electrical supply should be provided with a means of


isolation to disconnect all live conductors including the neutral.

7. - All outbuildings where protection against direct contact is by earthed equipotential


bonding and automatic disconnection of the supply should have a disconnection time in
the event of an earth fault which does not exceed 0.4 s.

8. - Cables which are not buried must be shielded from direct sunlight, whose ultraviolet
content will affect plastics. Cables with ultra-violet protected sheaths may be used; the
preferred colour for such cables is black.

9. - Large garden ponds present a particular problem because of the probability that
sooner or later people will fall into them. In such a case, the Regulations applying to
swimming pools (see {7.3}) should be applied. Pumps and lighting should be SELV with
the safety source at least 3.5 m outside the edge of the pond. All cables in the pond must
be in ducts or conduits which are built into it and not be allowed to lie loose. All pond
equipment must be protected to IP55 (see {2.4.3}) or better.

7.16.1 - Types of reduced voltage

7.16.2 - Separated extra-low voltage (SELV)

7.16.3 - Functional extra-low voltage (FELV)

7.16.4 - Reduced voltage

7.16.1 - Types of reduced voltage

Most installations operate at low voltage, which is defined as up to 1000 V ac or 1500 V


dc between conductors, and up to 600 V ac or 900 V dc between conductors and earth.
Extra-low voltage is defined as not exceeding 50 V ac or 120 V dc between conductors or
from conductors to earth. Four types of reduced voltage system, all intended to improve
safety, are recognised by the Regulations. They are:

1. - separated extra-low voltage or SELV {7.16.2},


2. - functional extra-low voltage or FELV {7.16.3},

3. - reduced voltage {7.16.4},

4. - voltages at values lower than the maximum for ELV may be required to ensure the
safety
----- of people and of livestock in areas where body resistance is likely to be very low
{7.6}.

7.16.2 - Separated extra-low voltage (SELV)

The safety of this system stems from its low voltage level, which should never exceed 50
V ac or 120 V dc, and is too low to cause enough current to flow to provide a lethal
electric shock. The reason for the difference between ac and dc levels is shown in {Figs
3.9 & 3.10}.

It is not intended that people should make contact with conductors at this voltage; where
live parts are not insulated or otherwise protected, they must be fed at the lower voltage
level of 25 V ac or 60 V ripple-free dc although insulation may sometimes he necessary,
for example to prevent short-circuits on high power batteries. To qualify as a separated
extra-low voltage (SELV) system, an installation must comply with conditions which
include:

1. - it must be impossible for the extra-low voltage source to come into contact with a low
voltage system. It can be obtained from a safety isolating transformer, a suitable motor
generator set, a battery, or an electronic power supply unit which is protected against the
appearance of low voltage at its terminals,

2. - there must be no connection whatever between the live parts of the SELV system and
earth or the protective system of low voltage circuits. The danger here is that the earthed
metalwork of another system may rise to a high potential under fault conditions and be
imported into the SELV system.

3. - there must be physical separation from the conductors of other systems, the
segregation being the same as that required for circuits of different types {6.6},

4. - plugs and sockets must not be interchangeable with those of other systems; this
requirement will prevent a SELV device being accidentally connected to a low voltage
system,

5. - plugs and sockets must not have a protective connection (earth pin). This will prevent
the mixing of SELV and FELV devices. Where the Electricity at Work Regulations 1989
apply, sockets must have an earth connection, so in this case appliances must be double
insulated to class II so that they are fed by a two-core connection and no earth is required,

6. - luminaire support couplers with earthing provision must not be used.


7.16.3 - Functional extra-low voltage (FELV)

If a separated extra-low voltage (SELV) system is earthed, or if the insulation of the


supply which feeds it does not meet the necessary requirements, it ceases to be a SELV
system and becomes a functional extra-low voltage (FELV) system. This difference is
illustrated by {Fig 7.25}.

If a functional system only fails to be classified as a safety system because it is earthed, it


must then be protected by enclosures that prevent it being touched or by insulation
capable of withstanding a test voltage of 500 V r.m.s. for one minute. In such a case there
is no need for the earth-fault loop impedance of the extra-low voltage circuit to be low
enough to prevent danger; compliance of the safety source supply is sufficient. There is
therefore no need to bond and earth all associated non-current-carrying metalwork.

Such metalwork must, however, be bonded and earthed if the insulation between the low-
voltage supply circuit and the functional extra-low voltage circuit does not meet the
requirements stated above. In the event of the supply circuit being of the earth-free
bonded type {5.8.3} all non-current-carrying metalwork of the FELV system must he
connected to the non-earthed protective conductor of the supply circuit. Plugs and sockets
in FELV systems must not be interchangeable with those of other Supply systems in use
in the same premises.

becomes a functional extra-low voltage system when


Fig 7.25 - Earthing relationship, SELV and FELV systems

7.16.4 - Reduced voltage

In situations where the power requirements are high, extra-low voltage systems would
need to deliver very high currents. If an increased voltage can still lead to a safe system,
the current required will be reduced. We are therefore considering a voltage higher than
extra-low but lower than low voltage.

The highest voltage permitted for such systems is 110 V between conductors for both
single and three-phase systems, with voltages to earth of 55 V for single-phase and 65 V
for three-phase supplies {Fig 7.26}.

The reduced voltage supply can be taken from a double wound isolating transformer, or
from a suitable motor generator set, provided it has the unusual feature of a centre-tapped
winding. The system must be insulated and protected against direct contact as for a low
voltage installation. Earth-fault loop impedance must allow automatic disconnection in a
maximum of 5 s (see {Table 7.9}), or an RCD with an operating current of no more than
30 mA must be provided. The result of multiplying earth-fault loop impedance by the
RCD operating current (A) must not exceed 50 (V). Plugs, sockets and cable couplers in
the reduced voltage system must all be provided with protective conductor contacts (earth
pins) and must not be interchangeable with those of any other system in use at the same
location.
Fig 7.26 - Reduced voltage Systems

Table 7.9 - Maximum earth-fault loop impedance for 5 s


----------------- disconnection time in reduced voltage systems
Device rating MCB types C &
MCB type 1 MCB type 2 BS 88 fuse
(A) 3
55 63.5 55 63.5 55 63.5
- 55 V 63.5 V
V V V V V V
6 2.30 2.65 1.32 1.52 0.92 1.07 3.20 3.70
10 1.38 1.59 0.79 0.91 0.55 0.64 1.77 2.05
16 0.86 0.99 0.49 0.57 0.34 0.40 1.00 1.15
20 0.69 0.80 0.40 0.46 0.28 0.32 0.69 0.80
25 0.55 0.64 0.32 0.36 0.22 0.26 0.55 0.63
32 0.43 0.50 0.25 0.28 0.17 0.20 0.44 0.51
50 0.28 0.32 0.16 0.18 0.11 0.13 0.25 0.29
Note : 63.5 V is the voltage to earth (to the star point) of a 110 V
---------- three-phase supply.

7.18.1 - Introduction

7.18.2 - Recommendations for medical location

7.18.1 - Introduction

There is no section 610 in BS 7671, although the intention is that it should be reserved for
medical locations and associated areas. The following is thus based on Chapter 9 of
Guidance Note 7, which in turn depends on draft lEG Publication 364. The draft standard
excludes medical electrical equipment, which is covered by IEC 601-01 : 1988 or BS
5724 : Part I: 1989 and BS EN 60601-01. There can be little doubt that before long this
material will become part of the Regulations. Medical locations are often hospitals, but
may also include private clinics, medical and dental surgeries, health-care centres and
dedicated medical areas in the workplace.

The use of medical electrical equipment is split into three categories:

1. - Life-support: infusion pumps, dialysis machines and ventilators;

2. - Diagnostic: X-ray machines, magnetic resonance imagers, blood pressure monitors,


electroencephalograph (EEG) and electrocardiograph (EGG) equipment;

3. - Treatment: surgical diathermy and defibrillators,

This equipment is increasingly used on patients under acute care. Supplies to it require
enhanced reliability and safety, as well as measures to reduce electromagnetic
interference.

Shock hazards are covered in {3.4} and indicate that currents as low as 10 mA passing
through the human body can result in muscular paralysis (an inability to move) followed
by respiratory paralysis (an inability to breathe). At about 25 mA ventricular fibrillation
(loss of normal heart muscle rhythm) may occur and may be fatal.

The impedance of the human body (see {3.4.2}) may be considerably reduced during
certain clinical procedures. For example, the skin resistance is reduced during surgery
and defensive capacity either reduced by medication or removed altogether while
anaesthetised. Special hazards occur during heart surgery, where electrical conductors
may be placed within the heart , or with the use of conductive catheters. Under these
conditions currents as low as a few tens of micro-amperes may well result in death.

7.18.2 - Recommendations for medical locations

Patient safety
Since the hazard to people will depend on the treatment being administered, hospital
locations are divided into groups as follows:

1. - Group Zero: where no treatment or diagnosis using medical electrical equipment is


administered, e.g. consulting rooms;

2. - Group One: where medical electrical equipment is in use, but not for treatment of
heart (intracardiac) conditions;

3. - Group Two: where medical electrical equipment is in use for heart (intracardiac)
conditions.
TN-C systems (where earth and neutral are combined - see {5.2.5}) is not allowed in
medical locations because load currents in PEN conductors and parallel paths can cause
electromagnetic interference to medical equipment. Protection against direct contact must
be by insulation of live parts and by barriers or enclosures. SELV and PELV systems (see
{3.4.4}) may be used in Group One and in Group Two locations, but is limited to 25 V
r.m.s. a.c. or 60 V ripple free d.c. Even at these voltages, protection of live parts by
insulation or by barriers or enclosures is essential. Exposed conductive parts of PELV
systems must be connected to the local equipotential bonding conductor. FELV Systems
(see {3.4.4}) may be used in Group Zero locations only.

Protection against indirect contact may be by automatic disconnection of the supply (see
{3.4.6}), by electrical separation (see {5.8.4}), or by the use of Class II equipment (see
{5.8.4}) except as indicated below:

For TN Systems (see {5.2.3} and {5.2.4}) any medical equipment in Group One or in
Group Two locations which is situated within 2.5 m above the floor or within 1.5 m
horizontally from the edge of the bed, operating table, etc., on which the patient is lying,
called the patient environment (see {Fig 7.27}), must be RCD protected, the rating of the
device being 30 mA or less if the circuit protection does not exceed 32 A, or 300 mA or
less if the circuit protection exceeds 32 A. Note, however, that in Group Two locations,
RCDs may only be used for X-ray units or for equipment with a rated power greater than
5 kvA,

Fig 7.27 - The patient environment

For IT systems (see {5.2.2}) used in Group One and Group Two situations, the same
requirements apply as in TN systems with earth fault protection provided by RCDs.

For IT Systems (see {5.2.6)) it is recommended that an IT system is used for circuits
supplying medical equipment that is intended to be used for life-support of patients. This
is because the total absence of an earthing system makes indirect contact an impossibility.
Any medical equipment in Group Two which is situated in the patient environment (see
{Fig 7.27}) must have a safety isolating transformer incorporated into its IT system, and
must have an insulation monitoring device. This device must have:
1. - acoustic and visual alarms that are triggered at the first earth fault, and

2. - an a.c. internal resistance of at least 100 kOhms, and

3. - a test voltage not exceeding 25 V, and

4. - a test current not exceeding 1 mA even under fault conditions, and

5. - activation when the insulation resistance falls to less than 50 kOhms, and

6. - activation when any wiring or earth is disconnected.

If a socket outlet on a patient bedhead location in a Group Two situation is supplied from
an IT system, it must be fed from at least two separate circuits. Socket outlets in a Group
Two situation fed from other systems (TN-S or TT) must be clearly marked to distinguish
them from IT system socket outlets. Any wiring system within a Group Two location
must supply only the equipment and fittings in that group (see {Fig 7.28}.

Fig 7.28 Distribution network with insulation monitoring

Supplementary equipotential bonding


This bonding is required within Groups One and Two locations, the resistance of the
bonding conductors not exceeding 0.2 Ohms. In Group Two locations circuits supplying
electrical equipment situated within the patient environment (see {Fig 7.27}), the voltage
between extraneous conductive parts and the protective conductor system must never
exceed 20 mV, even under fault conditions. This figure is based on the leakage current
through the patient never exceeding 50 mA. Assuming a body impedance of 1 kOhm, this
gives a maximum voltage of 50 mV, 30 mV of which is assumed to be the volt drop from
the socket outlet to the equipment.
Explosion risk
The gases used as anaesthetics in operating theatres are flammable if present in high
concentrations. Provided that there is adequate ventilation (20 air changes per hour) no
special precautions are necessary for the electrical installation.

Standby power supplies


The failure of the power supply may well have fatal consequences, for example if the
lighting fails in an operating theatre, or the feed to a life support system is lost in an
intensive care unit. Safety power supplies are split into three categories depending on
how quickly the supply is restored after failure. The time periods are 0.5 s, which applies
to operating theatre lighting and where the standby system will be an uninterruptible
power supply unit (UPS), 15 s for most essential hospital supplies, where a standby
generator is likely, and more than 15 s, which is likely to apply to offices, staff
accommodation and so on. Emergency lighting fed from a safety source is required at
escape routes, exit signs and locations of essential services in Groups One and Two
locations.

Department of Health recommendations


The Department provides guidance through its Health Technical Memoranda (HTM)
series of publications. These extremely detailed volumes are available from HMSO
bookshops.

8.1 - Introduction 8.5 - Insulation tests


8.2 - Inspection 8.6 - Earth testing
8.3 - Testing sequence 8.7 - Test instrument requirements
8.4 - Continuity tests 8.8 - Supporting paperwork

8.1.1 - The tester

The person who carries out the test and inspection must be competent to do so, and must
be able to ensure his own safety, as well as that of others in the vicinity. It follows that he
must be skilled and have experience of the type of installation to be inspected and tested
so that there will be no accidents during the process to people, to livestock, or to
property. The Regulations do not define the term 'competent', but it should be taken to
mean a qualified electrician or electrical engineer

8.1.2 - Why do we need inspection and testing?


There is little point in setting up Regulations to control the way in which electrical
installations are designed and installed if it is not verified that they have been followed.
For example, the protection of installation users against the danger of fatal electric shock
due to indirect contact is usually the low impedance of the earth-fault loop; unless this
impedance is correctly measured. this safety cannot be confirmed. in this case the test
cannot be carried out during installation, because part of the loop is made up of the
supply system which is not connected until work is complete.

In the event of an open circuit in a protective conductor, the whole of the earthed system
could become live during the earth-fault loop test. The correct sequence of testing {8.3}
would prevent such a danger, but the tester must always be aware of the hazards applying
to himself and to others due to his activities. Testing routines must take account of the
dangers and be arranged to prevent them. Prominent notices should be displayed to
indicate that no attempt should be made to use the installation whilst testing is in
progress.

The precautions to be taken by the tester should include the following:

1. -make sure that all safety precautions are observed

2. - have a clear understanding of the installation, how it is designed and how it has been
installed

3. - make sure that the instruments to be used for the tests are to the necessary
standards (BS 4743 and BS 5458) and have been recently recalibrated to ensure their
accuracy

4. - check that the test leads to be used are in good order, with no cracked or broken
insulation or connectors, and are fused where necessary to comply with the Health and
Safety Executive Guidance Note GS38

5. - be aware of the dangers associated with the use of high voltages for
insulation testing. For example, cables or capacitors connected in a circuit which has
been insulation tested may have become charged to a high potential and may hold it for a
significant time.

The dangers associated with earth-fault loop impedance testing have been mentioned in
{5.3}.

8.1.3 - Information needed by the tester

The installation tester, as well as the user, must be provided with clear indications as to
how the installation will carry out its intended purpose.
Table 8.1 - Typical schedule of circuits

Fuse
Circuit Cable Feeding
(BS 88)
A1 32A 2.5mm² p.v.c. (X) Ring circuit, printing section
A2 32A 2.5mm² p.v.c. (X) Ring circuit, drawing office sockets
A3 32A 2.5mm² p.v.c. (X) Ring circuit, main office sockets
A4 32A 4.0mm² p.v.c. (Z) Store room printer
A5 spare - -
A6 spare - -
- - - -
B1 10A 1.5mm² p.v.c. (Y) Lighting, printing section
B2 10A 1.5mm² p.v.c. (Y) Lighting, drawing office
B3 10A 1.5mm² p.v.c. (Y) Lighting, main office
B4 10A 1.5mm² p.v.c. (Y) Lighting, corridors and toilets
B5 spare - -
B6 spare - -
- - - -
C1 32A 2.5mm² p.v.c. (X) Ring circuit, paper store
C2 32A 2.5mm² p.v.c. (X) Ring circuit, binding section
C3 spare - -
C4 spare - -
C5 10A 1.5mm² p.v.c. (Y) Lighting, paper store
C6 10A 1.5mm² p.v.c. (Y) Lighting, binding section

To this end, the person carrying out the testing and inspection must be provided with the
following data:

1. - the type of supply to be connected, ie single- or three- phase

2. - the assessed maximum demand (6.2.1)

3. - the earthing arrangements for the installation

4. - full details of the installation design, including the number and position of mains gear
and of circuits, (see {Table 8.1},{Fig 8.1} and {Table 8.2} for a typical example)
5 . - all data concerning installation design, including calculation of live and
protective conductor sizes, maximum demand, etc.

6 . -the method chosen to prevent electric shock in the event of an earth fault.

7 . -a list of all circuits or equipment vulnerable to damage by testing


(see{8.2.1 item 3})

Without this complete information the tester cannot verify either that the installation will
comply with the Regulations, or that it has been installed in full accordance with the
design.

Fig 8.1 Typical mains gear schematic diagram. See also {Tables 8.1 & 8.2}

Table 8.2 - Typical mains gear schedule


Supplying BS 88 fuse
Item Situation Cable size
and type size
Dist.board A -
2-way 30A Switch room 16mm² p.v.c. 4 x 32A
Ground floor
TP&N Sockets (S) (2 spare ways)
Dist.board B -
2-way 15A Switch room Ground floor 6mm² p.v.c. 4 x 10A
TP&N Lighting (T) (2 spare ways)

Dist.board C -
2-way 30A Upper floor 16mm² p.v.c.
Upper store 2 x 32A
TP&N Installation (S)
2 x 10A
(2 spare ways)

Board A -
Dist. Board A
Switch-fuse Switch room 16mm² p.v.c.
3 X 60 A
60A TP&N (S)

Board B -
Dist. Board B
Switch-fuse Switch room 6mm² p.v.c. 3 X 30 A
30A TP&N (T)

Board C -
Switch-fuse Switch room Dist. Board C 16mm² p.v.c.
3 X 60 A
60A TP&N (S)
Main fuse-
-
switch
Switch room Complete 70mm² p.v.c. 3 x 100 A
100A TP&N
installation (R)

8.2.1 - Notices and other identification

The installation tester, as well as the user, must have no difficulty in identifying circuits,
fuses, circuit breakers, etc. Re must make sure that the installation is properly equipped
with labels and notices, which should include:

I. - Labels for all fuses and circuit breakers to indicate their ratings and the circuits
protected

2 . - Indication of the purpose of main switches and isolators

3. - A diagram or chart at the mains position showing the number of points and the size
and type
---- of cables for each circuit, the method of providing protection from direct contact and
details of
---- any circuit in which there is equipment such as passive infra-red detectors or
electronic
-----fluorescent starters vulnerable to the high voltage used for insulation testing.
4. - Warning of the presence of voltages exceeding 250 V on an equipment or enclosure
where such a voltage would not normally be expected.

5. - Warning that voltage exceeding 250 V is present between separate pieces of


equipment which are within arm's reach

6. - A notice situated at the main intake position to draw attention to the need for periodic
testing (see {Table 8.12})

7 . -A warning of the danger of disconnecting earth wires at the point of


connection of:

a). - the earthing conductor to the earth electrode

b). - the main earth terminal, where separate from main switchgear

c). - bonding conductors to extraneous conductive parts The notice should read

Safety electrical connection - do not remove

8. - A notice to indicate the need for periodic testing of an RCD as indicated in {5.9.2}

9.-A notice for caravans so as to draw attention to the connection and


disconnection procedure as indicated in {Table 7.5}

10. - Warning of the need for operation of two isolation devices to make a piece of
equipment
-------safe to work on where this applies

11. - A schedule at each distribution board listing the items to be disconnected (such as
semiconductors) so that they will not be damaged by testing.

12. - A drawing which shows clearly the exact position of all runs of buried cables.

8.2.2 – Inspection

Before testing begins it is important that a full inspection of the complete installation is
carried out with the supply disconnected. The word 'inspection' has replaced 'visual
inspection', indicating that all the senses (touch, hearing and smell, as well as sight) must
be used. The main purpose of the inspection is to confirm that the equipment and
materials installed:
1. - are not obviously damaged or defective so that safety is reduced

2. - have been correctly selected and erected

3. - comply with the applicable British Standard or the acceptable equivalent

4. - are suitable for the prevailing environmental conditions

An inspection checklist is shown in Table 8.3. Some inspections are best carried out
whilst the work is in progress. A good example is the presence of fire barriers within
trunking or around conduit where they pass through walls.

Table 8.3 - Inspection check list


1 Identification of conductors
2 Mechanical protection for cables, or routing in safe zones
3 Connection of conductors
4 Correct connection of lampholders, socket outlets, etc.
5 Connection of single-pole switches in phase conductors only
Checking of design calculations to ensure that correct live and
6 protective conductors have been selected in terms of their current-
carrying capacity and volt drop
7 Presence of fire barriers, suitable seals and protection against fire
8 Protection of live parts by insulation to prevent direct contact
Protection against indirect contact by the use of:-
------a) - protective conductors
9
------b) -earthing conductors
------c) -main and supplementary equipotential bonding conductors
10 Prevention of mutual detrimental influence
11 Electrical separation
12 Undervoltage protective devices
13 Use of Class II equipment
14 Labelling of fuses, circuit breakers, switches and terminals
The settings and ratings of devices for protection against indirect
15
contact and against overcurrent
16 The presence of diagrams, instructions, notices, warnings, etc.
Selection of protective measures and equipment in the light of the
17
external influences involved

8.2.3 - Periodic inspection


No electrical installation, no matter how carefully designed and erected, can be expected
to last forever. Deterioration will take place due to age as well as due to normal wear and
tear. With this in mind, the Regulations require regular inspection and testing to take
place so that the installation can be maintained in a good and a safe condition. It is now a
requirement of the Regulations that the installation user should be informed of the need
for periodic testing, and the date on which the next test is due. A notice, fixed at or near
the origin of the installation, must state the required intervals between periodic
inspections and tests."

Accessories, switchgear etc should be carefully examined for signs of overheating.


Structural changes may have impaired the safety of an installation, as may have changes
in the use of space. The use of extension leads must be discouraged, if only because of
the relatively high loop impedance they introduce.

It is important to appreciate that the regular inspection and testing of all electrical
installations is a requirement of the Electricity at Work Regulations. The time interval
concerned will, of course, depend on the type of installation and on the way in which it is
used. {Table 8.4} shows the suggested intervals between periodic tests and inspections.

Table 8.4 - Suggested intervals between


------------- periodic tests and inspections
Maximum period
Type of installation
between inspections
Domestic premises 10 years
Commercial premises 5 years
Educational establishments 5 years
Hospitals 5 years
Industrial premises 3 years
Cinemas 1 year*
Churches 5 years
Leisure complexes 1 year
Places of public entertainment 1 year
Theatres, etc. 1 year*
Agricultural and horticultural 3 years
Caravans 3 years
Caravan sites 1 year*
Emergency lighting 3 years
Fire alarm systems 1 year
Launderettes 1 year*
Petrol filling stations 1 year*
Public Houses 5 years
Marinas 1 Year
Highway power supplies 6 years
Temporary installation 3 months
Where maximum periods are marked *
there is a legal requirement for retests at these intervals

8.3.1 - Why is correct sequence important?

Testing can be hazardous, both to the tester and to others who are within the area of the
installation during the test. The danger is compounded if tests are not carried out in the
correct sequence.

For example, it is of great importance that the continuity, and hence the effectiveness, of
protective conductors is confirmed before the insulation resistance test is carried out. The
high voltage used for insulation testing could appear on all extraneous metalwork
associated with the installation in the event of an open-circuit protective conductor if
insulation resistance is very low.

Again, an earth-fault loop impedance test cannot be conducted before an installation is


connected to the supply, and the danger associated with such a connection before
verifying polarity, protective system effectiveness and insulation resistance will be
obvious.

Any test which fails to produce an acceptable result must be repeated after remedial
action has been taken. Any other tests, whose results may have been influenced by the
fault concerned must also be repeated.

8.3.2 - Correct testing sequence

Some tests will be carried out before the supply is connected, whilst others cannot be
performed until the installation is energised. {Table 8.5} shows the correct sequence of
testing to reduce the possibility of accidents to the minimum.

Table 8.5 - Correct sequence for safe testing

BEFORE CONNECTION OF THE SUPPLY

1 Continuity of protective conductors


2 Main and supplementary bonding continuity
3 Continuity of ring final circuit conductors
4 Insulation resistance
5 Site applied insulation
6 Protection by separation
7 Protection by barriers and enclosures
8 Insulation of non-conducting floors and walls
9 Polarity
Earth electrode resistance if an earth electrode resistance tester is
10
used
WITH THE SUPPLY CONNECTED
Earth electrode resistance if an earth-fault loop tester or the
11
ammeter and voltmeter method are used
12 Confirm correct polarity
13 Earth-fault loop impedance
14 Correct operation of residual current devices
15 Correct operation of switches and isolators

8.4 Continuity Tests

8.4.1 - Protective conductor continuity

All protective and bonding conductors must be tested to ensure that they are electrically
safe and correctly connected. {8.7.1} gives test instrument requirements. Provided that the
supply is not yet connected, it is permissible to disconnect the protective and
equipotential conductors from the main earthing terminal to carry out testing. Where the
mains supply is connected, as will be the case for periodic testing, the protective and
equipotential conductors must not be disconnected because if a fault occurs these
conductors may rise to a high potential above earth. In this case, an earth-fault loop tester
can be used to verify the integrity of the protective system.

Where earth-fault loop impedance measurement of the installation is carried out, this will
remove the need for protective conductor tests because that conductor forms part of the
loop. However, the loop test cannot be carried out until the supply is connected, so testing
of the protective system is necessary before supply connection, because connection of the
supply to an installation with a faulty protective system could lead to danger.

There are three methods for measurement of the resistance of the protective conductor.
1. - Using the neutral conductor as a return lead
A temporary link is made at the distribution board between neutral and protective
conductor systems. Don't forget to remove the link after testing. The low resistance tester
is then connected to the earth and neutral of the point from which the measurement is
taken (see {Fig 8.2}). This gives the combined resistance of the protective and neutral
conductors back to the distribution board. Then

Rp = R x An
An + Ap

where
Rp -is the resistance of the protective conductor
R -is the resistance reading taken
An - is the cross-sectional area of the neutral conductor
Ap - is the cross-sectional area of the protective conductor.

Note that the instrument reading taken in this case is the value of the resistance R1 + R2
calculated from {Table 5.5} (see {8.4.4}). This method is only valid if both conductors have
the same length and both are copper; in most cases where steel conduit or trunking is not
used as the protective conductor, the test will give correct results.

Fig 8.2 - Protective conductor continuity test using the


neutral conductor as the return lead

2. - Using a long return lead


This time a long lead is used which will stretch from the main earthing terminal to every
point of the installation.

First, connect the two ends of this lead to the instrument to measure its resistance. Make a
note of the value, and then connect one end of the lead to the main earthing terminal and
the other end to one of the meter terminals.

Second, take the meter with its long lead still connected to the point from which
continuity measurement is required, and connect the second meter terminal to the
protective conductor at that point.
The reading then taken will be the combined resistance of the long lead and the protective
conductor, so the protective conductor value can be found by subtracting the lead
resistance from the reading.

Rp = R - RL
where
Rp -is the resistance of the protective conductor
R - is the resistance reading taken
RL -is the resistance of the long lead

Some modem electronic resistance meters have a facility for storing the lead resistance at
the touch of a button, and for subtracting it at a further touch.

3. - Where ferrous material forms all or part of the protective conductor


There are some cases where the protective conductor is made up wholly or in part by
conduit, trunking, steel wire armour, and the like. The resistance of such materials will
always be likely to rise with age due to loose joints and the effects of corrosion. Three
tests may be carried out, those listed being of increasing severity as far as the current-
carrying capacity of the protective conductor is concerned. They are:

1 - A standard ohmmeter test as indicated in 1 or 2 above. This is a low current test which
may not show up poor contact effects in the conductor. Following this test, the conductor
should be inspected along its length to note if there are any obvious points where
problems could occur.

2 - If it is felt by the inspector that there may be reasons to question the soundness of the
protective conductor, a phase-earth loop impedance test should be carried out with the
conductor in question forming part of the loop. This type of test is explained more fully
in {8.4.4}

3 - If it is still felt that the protective conductor resistance is suspect, the high current test
using 1.5 times the circuit design current (with a maximum of 25 A) may be used (see
{Fig 8.3}. The protective circuit resistance together with that of the wander lead can be
calculated from:

voltmeter reading (V)


ammeter reading (A)
Fig 8.3 - High-Current ac test of a protective conductor

Subtracting wander lead resistance from the calculated value will give the resistance of
the protective system.

The resistance between any extraneous conductive part and the main earthing terminal
should he 0.05 Ohms or less; all supplementary bonds are also required to have the same
resistance.

8.4.2 - Ring final circuit continuity

The ring final circuit, feeding 13 A sockets, is extremely widely used, both in domestic
and in commercial or industrial situations. It is very important that each of the three rings
associated with each circuit (phase, neutral and protective conductors) should be
continuous and not broken. If this happens, current will not be properly shared by the
circuit conductors. {Fig 8.4} shows how this will happen. {Fig 8.4(a)} shows a ring
circuit feeding ten socket outlets, each of which is assumed to supply a load taking a
current of 3 A. In simple terms, current is then shared between the conductors, so that
each could have a minimum current carrying capacity of 15 A. {Fig 8.4(b)} shows the
same ring circuit with the same loads, but broken between the ninth and tenth sockets. It
can be seen that now one cable will carry only 3 A whilst the other (perhaps with a
current rating of 20 A) will carry 27 A. The effect will occur in any broken ring, whether
simply one live conductor or both are broken.

Fig 8.4 - illustrating the danger of a break in a ring final circuit


a) unbroken ring with correct current sharing
b) broken ring with incorrect current sharing

It is similarly important that there should be no 'bridge' connection across the circuit. This
would happen if, for example, two spurs from different points of the ring were connected
together as shown in {Fig 8.5}, and again could result in incorrect load sharing between
the ring conductors.
The tests of the ring final circuit will establish that neither a broken nor a bridged ring has
occurred. The following suggested test is based on the Guidance Note on Inspection and
Testing issued by the IEE.

Fig 8.5 - A 'bridged' ring final circuit

Test 1
This test confirms that complete rings exist and that there are no breaks. To complete the
test, the two ends of the ring cable are disconnected at the distribution board. The phase
conductor of one side of the ring and the neutral from the other (P1 and N2J are
connected together, and a low resistance ohmmeter used to measure the resistance
between the remaining phase and the neutral (P2 and Ni). {Figure 8.6} shows that this
confirms the continuity of the live conductors. To check the continuity of the circuit
protective conductor, connect the phase and CPC of different sides together (P1 and E2)
and measure the resistance between phase and CPC of the other side (P2 and El). The
result of this test will be a measurement of the resistance of live and protective
conductors round the ring, and if divided by four gives (Ri + R2) which will conform
with the values calculated from {Table 5.5}.
Fig 8.6 - Test to confirm the continuity of a ring final circuit

Test 2
This test will confirm the absence of bridges in the ring circuit, see {Fig 8.7}. First, the
phase conductor of one side of the ring is connected to the neutral of the other (P1 and
N2) and the remaining phase and neutral are also connected together (P2 -and Ni). The
resistance is then measured between phase and neutral contacts of each socket on the
ring. If the results of these measurements are all substantially the same (within 0.05
Ohms), the absence of a bridge is confirmed. If the readings are different, this will
indicate the presence of a bridge or may be due to incorrect connection of the ends of the
ring. If they are connected P1 to NI and P2 to N2 then readings will increase or reduce as
successive measurements round the ring are taken, as is the case where a bridge exists.
Whilst this misconnection is easily avoided when using sheathed cables, a mistake can be
made very easily if the system consists of single-core cables in conduit. It may be of
interest to note that the resistance reading between phase and neutral outlets at each
socket should be one quarter of the phase/neutral reading of Test 1.

Measurements are also taken at each socket on the ring between the phase and the
protective conductor with the temporary connection made at the origin of the ring
between P1 to E2 and between P2 to El. Substantially similar results will indicate the
absence of bridges.
Fig 8.7 - Test to confirm the absence of bridges in a ring final circuit

8.4.3 - Correct polarity

If a single-pole switch or fuse is connected in the neutral of the system rather than in the
phase, a very dangerous situation may result as illustrated in {Fig 8.8}.

Fig 8.8 - The danger of breaking the neutral of a circuit


Fig 8.9 - Polarity test of an installation

It is thus of the greatest importance that single-pole switches, fuses and circuit breakers
are connected in the phase (non-earthed) conductor, and verification of this connection is
the purpose of the polarity test. Also of importance is to test that the outer (screw)
connection of E S lampholders is connected to the earthed (neutral) conductor, as well as
the outer contact of single contact bayonet cap (BC) lampholders. The test may be carried
out with a long wander lead connected to the phase conductors at the distribution hoard
and to one terminal of an ohmmeter or a continuity tester on its low resistance scale. The
other connection of the device is equipped with a shorter lead which is connected in turn
to switches, centre lampholder contacts, phase sockets of socket outlets and so on. A very
low resistance reading indicates correct polarity (see {Fig 8.9}).

To avoid the use of a long test lead, a temporary connection of phase to protective
systems may be made at the mains position. A simple resistance test between phase and
protective connections at each outlet will then verify polarity. In the unlikely event of the
phase and protective conductor connections having been transposed at the outlet, correct
polarity will still be shown by this method; this error must he overcome by visual
verification -

Don't forget to remove the temporary connection afterwards!

Special care in checking polarity is necessary with periodic tests of installations already
connected to the supply, which must be switched off before polarity testing. It is also
necessary to confirm correct connection of supply phase and neutral. Should they be
transposed, all correctly-connected single-pole devices will be in the neutral, and not in
three phase conductor.

One practical method of checking polarity and continuity of ring or radial circuits
for socket outlets is to connect two low power lamps to a 13 A plug. One is connected
between phase and neutral, and the other between phase and earth. Plugging in at each
socket tests correct polarity and the continuity of live and protective conductors when
both indicators light. It is important where RCD protection is employed to use very low
power indicator lamps such as neon or LED devices (with suitable current limiting
resistors where necessary). The smallest filament lamp will take sufficient current from
phase to earth to trip most RCDs.

8.4.4 - Measurement of R1 + R2

In {5.3.6} and in {Table 5.5} we considered the value of the resistance of the phase
conductor plus that of the protective conductor, collectively known as (R1 + R2). This
can be measured with a low resistance reading ohmmeter as described in item 1 of {8.4.1}
(strictly the phase, rather than the neutral resistance is being measured here, but there
should be no difference) and will be necessarily at the ambient temperature which applies
at the time. Multiplication by the correction factor given in {Table 8.6} will adjust the
measured resistance to its value at 20°C.

Table 8.6 - Correction factors for ambient temperature


Test ambient temperature °C Correction factor
5 1.06
10 1.04
15 1.02
20 1.00
25 0.98

These will be the resistance values at 20°C and must be adjusted to take account of the
increase in resistance of the conductor material due to the increased temperature under
normal operating conditions. This second correction factor depends on the ability of the
insulation to allow the transmission of heat, and values will be found in {Table 8.7} for
three of the more common types of insulating material.

An alternative method for measuring (R1 + R2) is to carry out a loop impedance test at
the extremity of the final circuit and to deduct the external loop impedance for the
installation (Ze). Strictly it is not correct to add and subtract impedance and resistance
values, but any error should be minimal.

Table 8.7 - Temperature correction factors for insulation


Insulation type Correction factor
Bunched or as a Not bunched or
-
cable core sheathed cable
p.v.c. 1.20 1.04
85°C rubber 1.26 1.04
90°C thermosetting 1.28 1.04
8.5.1 - Testing insulation resistance

A low resistance between phase and neutral conductors, or from live conductors to earth,
will result in a leakage current. This current could cause deterioration of the insulation, as
well as involving a waste of energy which would increase the running costs of the
installation. Thus, the resistance between poles or to earth must never be less than half of
one meg ohm (0.5 M Ohms) for the usual supply voltages. In addition to the leakage
current due to insulation resistance, there is a further current leakage in the reactance of
the insulation, because it acts as the dielectric of a capacitor. This current dissipates no
energy and is not harmful, but we wish to measure the resistance of the insulation, so a
direct voltage is used to prevent reactance from being included in the measurement.
Insulation will sometimes have high resistance when low potential differences apply
across it, but will break down and offer low resistance when a higher voltage is applied.
For this reason, the high levels of test voltage shown in {Table 8.8} are necessary. {8.7.1}
gives test instrument requirements.

Before commencing the test it is important that:

1. - electronic equipment which could be damaged by the application of the high test
voltage should be disconnected. Included in this category are electronic fluorescent
starter switches, touch switches, dimmer switches, power controllers, delay timers,
switches associated with passive infrared detectors (PIRs), RCDs with electronic
operation etc. An alternative to disconnection is to ensure that phase and neutral are
connected together before an insulation test is made between them and earth.

2 . -capacitors and indicator or pilot lamps must be disconnected or an


inaccurate test reading will result.

Table 8.8 - Required test voltages and minimum resistance


Nominal circuit voltage Test Minimum insulation
voltage resistance
(V) (M Ohms)
Extra-low voltage circuits supplied from
250 0.25
a safety transformer
Up to 500 V except for above 500 0.5
Above 500 V up to 1000 V 1000 1.0
The insulation resistance tester must be capable of maintaining the required
voltage when providing a steady state of current of 1mA.

Where any equipment is disconnected for testing purposes, it must be subjected to its
own insulation test, using a voltage which is not likely to result in damage. The result
must conform with that specified in the British Standard concerned, or be at least 0.5 M
Ohms if there is no Standard.
The test to earth {Fig 8.10} must be carried out on the complete installation with the
main switch off, with phase and neutral connected together, with lamps and other
equipment disconnected, but with fuses in, circuit breakers closed and all circuit switches
closed. Where two-way switching is wired, only one of the two strapper wires will be
tested. To test the other, both two-way switches should be

Fig 8.10 - Insulation test to earth

Fig 8.11 - Insulation tests between poles

operated and the system retested. If desired, the installation can be tested as a whole,
when a value of at least 0.5 M Ohms should be achieved, see {Fig 8.10}. In the case of a
very large installation where there are many earth paths in parallel, the reading would be
expected to be lower. If this happens, the installation should be subdivided and retested,
when each part must meet the minimum requirement.

The tests to earth {Fig 8.10} and between poles {Fig 8.11} must be carried Out as
indicated, with a minimum acceptable value for each test of 0.5 M Ohms. However,
where a reading of less than 2 M Ohms is recorded for an individual circuit, (the
minimum value required by the Health and Safety Executive), there is the possibility of
defective insulation, and remedial work may be necessary. A test result of 2 M Ohms
may sometimes be unsatisfactory. If such a reading is the result of a re-test, it is necessary
to consult the data from previous tests to identify deterioration. A visual inspection of
cables to determine their condition is necessary during periodic tests; perished insulation
may not always give low insulation readings

As indicated above, tests on SELV and PELV circuits are carried out at 250 V. However
tests between these circuits and the live conductors of other circuits must be made at 500
V. Tests to earth for PELV circuits are at 250 V, whilst FELV circuits are tested as LV
circuits at 500 V. Readings of less than 5 M will require further investigation.

8.5.2 - Tests of non-conducting floors and walls

Where protection against indirect contact is provided by a non-conducting location, the


following requirements apply.

1. - there must be no protective conductors

2. - if socket outlets are used they must not have an earthing contact

3. - it should be impossible for any person to touch two exposed conductive parts at the
same time

4 . -floors and walls must be insulating.

To test this last item and so to make sure that the floors and walls are non-conducting,
their insulation has to be tested.

The requirements are shown in {Fig 8.12}, the electrodes used for making contact
Fig 8.12 - Insulation test of floors and walls for non-conducting location

with floors and walls being a special type which are pressed onto the surface with a force
of not less than 750 N (77 kg or 169 lb) for floors or 250 N (26 kg or 56 lb) for walls. The
resulting insulation resistance of not less than three points on each surface, one of which
must be between 1 m and 1.2 m from an extraneous conductive part (if there is one),
measured at 500 V, must not be less than 0.5 MOhms. Attention is drawn to the natural
reduction in the insulation resistance of a surface as humidity increases. Where insulation
is applied to an extraneous conductive part to provide a non-conducting location, this
insulation must be tested with an alternating p.d. of 2 kV. In normal use, the leakage
current should not exceed I mA.

8.5.3 - Tests of barriers and enclosures

Throughout the Regulations reference is made to the use of barriers and enclosures to
prevent contact with live parts (direct contact). If manufactured equipment's comply with
the British Standards concerned, they will not need further testing, but where barriers and
enclosures have been provided during erection of the installation, they must be tested.
Full details of the IP classification system will be found in {Table 2.1}, but the two most
common tests are for:

1. - IP2X - no contact can be made with a probe 12 mm in diameter and 80 mm long


- in other words, a human finger

2. - IP4X - no contact can be made with a rod of diameter 1 mm.

8.5.4 - Tests for electrical separation of circuits

This section is concerned with tests necessary to ensure the safety of separated extra-low
voltage (SELV), protective extra-low voltage (PELV) and functional extra-low voltage
(FELV) circuits which are explained in {7.16}. In general, the requirement is a thorough
inspection to make sure that the source of low voltage (most usually a safety isolating
transformer) complies in all respects with the British Standard concerned, followed by an
insulation test between the extra-low voltage and low voltage systems. The test is unusual
in that a 500 V dc supply (from an insulation resistance tester) must be applied between
the systems for one minute, after which the insulation resistance must not be less than 5
MOhms for SELV or PELV systems, or 0.5 MOhms for FELV systems. A further test at
3750 V dc for one minute is passed if no flashover occurs. This test in particular can be
dangerous, and special care should be taken.

For SELV and FELV circuits, additional inspection must ensure that the low voltage
requirements (not exceeding 50 V ac or 120 V dc) are met. If the voltage exceeds 25 V ac
or 70 V dc (60 V ripple-free), barriers and enclosures must be tested to IP2X (see {Table
2.1})and a 500 V dc insulation test applied for one minute between the live conductors
and metal foil wrapped round the insulation should produce a result of at least 0.5
MOhms
When insulation testing on electrically isolated circuits or on equipment which might be
damaged by the test voltage, phase and neutral must be connected together and the test
applied between them and earth.

8.6.1 - Testing earth electrodes

The earth electrode, where used, is the means of making contact with the general mass of
earth. Thus it must be tested to ensure that good contact is made. A major consideration
here is to ensure that the electrode resistance is not so high that the voltage from earthed
metalwork to earth exceeds 50 V. Where an RCD is used, this means that the result of
multiplying the RCD operating current (in amperes) by the electrode resistance (in ohms)
does not exceed 50 (volts). for normal dry locations, or 25 (volts) for construction sites
and agricultural premises.

If a 30 mA RCD is used, this allows a maximum electrode resistance of 1,666 Ohms,


although it is recommended that earth electrode resistance should never be greater than
200 Ohms. A maximum value of 100 ohm is proposed in a draft amendment of BS 7430,
Code of Practice for Earthing.

There are several methods for measurement of the earth electrode resistance. In all cases,
the electrode must be disconnected from the earthing system of the installation before the
tests commence.
Fig 8.13 - Measurement of earth electrode resistance with a dedicated tester

1. - Using a dedicated earth resistance tester


The instrument is connected as shown in {Fig 8.13} with terminals C1 and P1 being
connected to the electrode under test (X). To ensure that the resistance of the test leads
does not affect the result, separate leads should be used for these connections. If the test
lead resistance is negligible, terminals Ci and P1 may be bridged at the instrument and
connected to the earth electrode with a single lead.

Terminals C2 and P2 are connected to temporary spikes which are driven into the ground,
making a straight line with the electrode under test. It is important that the test spikes are
far enough from each other and from the electrode under test. If their resistance areas
overlap, the readings will differ for the reason indicated in {Fig 8.14}. Usually the
distance from X to Y will be about 25 m, but this depends on the resistivity of the ground.
To ensure that resistance areas do not overlap, second and third tests are made with the
electrode Z 10% of the X to Y distance nearer to, and then 10% further from, X. If the
three readings are substantially in agreement, this is the resistance of the electrode under
test. If not, test electrodes Y and Z must be moved further from X and the tests repeated.

The tester provides an alternating output to prevent electrolytic effects. If the resistance to
earth of the temporary spikes Y and Z is too high, a reduction is likely if they are driven
deeper or if they are watered.
Fig 8.14 - Effect of overlapping resistance areas
a) resistance areas not overlapping
b) resistance areas overlapping

2. - Using a transformer, ammeter and voltmeter


The system is connected as shown in {Fig 8.15}. Current, which can be adjusted by
variation of the resistor R, is passed through the electrode under test (X) to the general
mass of earth and hence to the test electrode Y. The voltmeter connected from X to Z
measures the volt drop from X to the general mass of earth. The electrode resistance is
calculated from:

voltmeter reading (V)


ammeter reading (A)

As in the case of the dedicated tester, the test electrode Z must again be moved and extra
readings taken to ensure that resistance areas do not overlap. It is important that the
voltmeter used has high resistance (at least 200 Ohms /V) or its low resistance in parallel
with that of the electrode under test will give a false result.
Fig 8.15 - Measurement of earth electrode resistance
with a transformer, ammeter and voltmeter

3. - Using an earth fault loop impedance tester


The tester is connected between the phase at the origin of the installation and the earth
electrode under test as shown in {Fig 8.16}. The test is then carried out, the result being
taken as the electrode resistance although the resistance of the protective system from the
origin of the installation to the furthest paint of the installation must be added to it before
its use to verify that the 50 V level is not exceeded. If an RCD with a low operating
current is used, the protective system resistance is likely to be negligible by comparison
with the permissible electrode resistance.
Fig 8.16 - Measurement of earth electrode resistance using an earth-fault loop tester

It is most important to ensure that earthing leads and equipotential bonds are reconnected
to the earth electrode when testing is complete

8.6.2 - Measuring earth-fault loop impedance and


prospective short-circuit current

The nature of the earth-fault loop and its significance have been considered in detail in
{5.3}. Since the loop includes the resistance of phase and protective conductors within the
installation, the highest values will occur at points furthest from the incoming supply
position where these conductors are longest. A measurement within the installation will
give the complete earth-fault loop impedance far the point at which it is taken (Zs), or the
earth-fault loop impedance external to the installation (Ze) may be measured at the
supply position. Internal loop measurements should be taken at points furthest from the
intake to give the highest possible results.

In simple terms, the impedance of the phase-to-earth loop is measured by connecting a


resistor (typically 10 Ohms) from the phase to the protective conductor as shown in {Fig
8.17}. A fault current, usually something over 20 A, circulates in the fault loop, and the
impedance of the loop is calculated within the instrument by dividing supply voltage by
the value of this current. The resistance of the added resistor must be subtracted from this
calculated value before the result is displayed. An alternative method is to measure the
supply voltage both before and whilst the loop current is flowing. The difference is the
volt drop in the loop due to the current, and loop impedance is calculated from voltage
difference divided by current.
Fig 8.17 - Simple principle of earth-fault loop testing

Since the loop current is very high, its duration must be short and must be limited to two
cycles (or four half-cycles) or 40 ms for a 50 Hz supply. The current is usually switched
by a thyristor or a triac, the firing time being controlled by an electronic timing circuit It
is very important to have already checked the continuity of the protective system before
carrying out this test. A break in the protective system, or a high resistance within it,
could otherwise result in the whole of the protective system being directly connected to
the phase conductor for the duration of the test. Commercial testers are usually fitted with
indicator lamps to confirm correct connection or to warn of reversed polarity. {Fig 8.18}
shows a typical earth-fault loop tester connected to a socket outlet so that its loop
impedance can be measured. If the circuit to be measured includes socket outlets, the
tester is connected as indicated in {Fig 8.18}. Special leads for connection to phase and
to earth are provided by suppliers for all other circuits.

Fig 8.18 - Earth-fault loop tester connected for use


Before testing, the main equipotential bonding conductors are disconnected (BUT NOT
THE CONNECTION WITH EARTH) to prevent parallel earth return paths and to ensure
that there is no reliance on the service pies for gas and water for effective earthing,
(REMEMBER TO RECONNECT THE MAIN EQUIPOTENTIAL BONDING AFTER
THE TEST).

Tests must be carried out at the origin of the installation, at each distribution board, at all
fixed equipment, at all socket outlets, at 10% of all lighting outlets (choosing points
farthest from the supply) and at the furthest point of every radial circuit. The test should
be repeated at least once to allow for the effect of transient variations in the supply
voltage.

A modified version of the earth-fault loop tester, which effectively measures the phase to
neutral impedance and calculates then displays the value of the current which would flow
if the supply voltage were applied to this impedance are readily available. The principle
of such a PSC tester is described in {3.7.2}.

Since the test result is dependent on the supply voltage, small variations will affect the
reading. Thus, the test should be repeated several times to ensure consistent results. The
test resistor will be connected across the mains for the duration of each test. and will
become very hot if frequent tests are made. Some testers will then 'lock out' to prevent
further testing until the resistor temperature falls to a safe value.

The earth fault loop impedance measured as described will be for installation cables
at ambient temperature, unless the circuit concerned has been in use immediately before
the test, when it will be the impedance at normal operating temperature. Under normal
operating conditions, cable temperature will rise, and so will the resistive component of
the impedance. This effect is difficult to calculate, and a practical alternative is to ensure
that the measured values of earth fault loop impedance do not exceed three quarters of the
maximum values shown in {Tables 5.1, 5.2 or 5.4} as appropriate.

The effect of supply voltage on the calculation of earth fault loop impedance is
considered in {5.3.4}.

A circuit protected by an RCD will need special attention, because the earth-fault loop
test will draw current from the phase which returns through the protective system. This
will cause an RCD) to trip. Therefore, any RCDs must be bypassed by short circuiting
connections before earth-fault loop tests are carried out. It is, of course, of the greatest
importance to ensure that such connections are removed after testing. One manufacturer
supplies a patented loop tester which does not require RCDs to be short circuited and
which will not cause them to trip

when the earth-fault loop test is made. Some instruments limit the test current to 15 mA
so as not to trip RCDs with ratings of 30 mA and above. Whilst such tests may often be
useful, they do not test the integrity of the system under fault current conditions.
When loop testing at lighting units controlled by passive infrared detectors (PIRs), there
may he damage to the associated electronic switches unless they are short-circuited
before testing.

An alternative to the use of a dedicated earth-fault loop impedance tester is to measure


the combined resistance of the phase and protective conductors from the incoming
position to the point for which earth-fault loop impedance is required (this is R1 + R2 -
see {8.4.4}) and to add to it the external earth-fault loop impedance (Ze) which can be
obtained from the electricity supplier. All earth-fault loop impedance test results should
be carefully compared with the data in [Tables 41B and 41D], adjusted to allow for
ambient temperature, or with figures provided by the designer. To ensure that ambient
temperature is taken into account, the results should never exceed three quarters of the
values given in [Tables 41B and 41D].

8.6.3 - Testing residual current devices (RCDs)

Residual current devices should comply with BS 4293 and are described in (5.9), from
which it will be seen that they are provided with a built-in self test system which is
intended to be operated regularly by the user. BS 7671 requires that correct operation of
this test facility should be checked, and that other tests are also carried out. The time
taken for the device to operate must be measured, so the old type of 'go, no-go' tester is
no longer adequate. {8.7.1} gives test instrument requirements.

RCD tests are carried out with a special tester which is connected between phase and
protective conductors on the load side of the RCD after disconnecting the load {Fig
8.19}. A precisely measured current for a carefully timed period is drawn from the phase
and returns via the earth, thus tripping the device. The tester measures and displays the
exact time taken for the circuit to be opened. This time is very short, in most cases being
between 10 and 20 ms, although it can be much longer, especially for S-types which have
delayed operation.
Fig 8.19 - Connections for an RCD tester

1. - General purpose non-delayed RCDs


This is a general purpose type of RCD which is intended to operate very quickly at its
rated current. Three tests are required:

a) -50% of the rated tripping current applied for 2 s should not trip the
device,

b) -100% of rated tripping current, which should not he applied for more than 2 s,
must cause the device to trip within 200 ms (0.2 s), and

c) -where the device is intended to provide supplementary protection against direct


contact, a test current of 150 mA, applied for no more than 50 ms, should cause the
device to operate within 40 ms.

2. - Time-delayed RCDs
In {5.9.2} we discussed the need for discrimination between RCDs. This type is
deliberately delayed in its operation to make sure that other devices which are connected
downstream of it will operate more quickly. A 3:1 discrimination ratio is required
between two RCDs which are connected in series, and this must be verified before
testing. It means that the delayed RCD must have an operating current at least three times
that of the non-delayed type. For example, to discriminate properly with a 30 mA device,
a second connected on the supply side would need to have an operating current of at least
90 mA (in practice, a 100 mA RCD is likely to be used).

The test for the time-delayed RCD consists of applying 100% of the normal rated current,
when the device should trip within the time range of:
50% of rated time delay plus 200 ms, and
100% of rated time delay plus 200 ms.

For example, an RCD with a rated tripping time of 300 ms should trip within a time range
of:

(150 + 200) ms = 350 ms and


(300+200) ms = 500 ms

An RCD tester is an electronic device which draws current from the supply for its
operation. This current is usually of the order of a few milliamperes which is taken from
the phase and neutral of the supply under test, and will have no effect on the
measurement of single-phase systems. However, if a three-wire three-phase system (there
is no neutral with this supply) is being tested, the tester must be connected to a neutral
conductor to provide the power it needs for operation. Thus, its operating current will
flow through a line conductor and return through the neutral, giving a basic imbalance. A
'no-trip' test must also be carried out, during

Fig 8.20 - RCD tester connected for use

which the RCD must not operate when 50% of the rated tripping current is applied for 2
s. The extra current to power the tester, which adds to the test current, may then cause
operation. It is necessary in this case to obtain from the RCD manufacturer the value of
this current and to take it into account before failing a device on the 50% test.

The RCD tester is connected to the device to be tested by plugging it into a suitable
socket outlet (see {Fig 8.20}) or by connecting to phase and neutral with special leads
obtainable from the instrument supplier.
8.7.1 - Basic requirements

Guidance Note 3 - Inspection and Testing - makes it clear that instrument accuracy is
required to be at least that shown later in this sub-section for the various types of
instrument. Regular recalibration using standards traceable to National Standards is now
required, together with checking after any incident which has involved mechanical
mishandling. Many electrical installers will not be used to sending their instruments
regularly for recalibration, but must now do so. Guidance Note 3 is not specific on the
time intervals at which recalibration must be carried out, but it would seem sensible for
occasionally used instruments to receive attention every two years, whilst those used
frequently are likely to need recalibration annually.

If installations are to be tested to show that they comply with BS 7671, the following
instruments will be necessary. After the name of the instrument are brief notes which
may be helpful in choosing a new instrument or in deciding if one already to hand will be
satisfactory. The first four instruments listed are absolutely essential for all tests, although
the low resistance tester and the insulation resistance tester may be combined in a single
instrument. An instrument which can test continuity, insulation resistance, earth-fault
loop impedance and the operation of RCDs is available from many manufacturers, and
will save a great deal of time in changing instruments and test leads - even more time can
be saved with an instrument which will save the test results for downloading to a
computer. The last two instruments will not often be required on simple installations,
since applied voltage and earth electrode resistance tests are often not needed. All
instruments used should conform to the appropriate British Standard safety specification
(BS EN 61010 for electronic types, and BS 5458 for electrical instruments). Test leads,
including prods and clips, must be in good order and have no cracked or broken
insulation. Fused test leads are recommended to reduce the risk of arcing under fault
conditions.

The basic accuracy of +5% quoted below is for digital instruments. Analogue instruments
should have an accuracy of +2% at full scale deflection, which will give the required
accuracy of +5% over the useful part of their scales.

Low resistance ohmmeter


Instruments to BS EN 61557-4 will comply.
Basic instrument accuracy required is +/- 5%
Test voltage ac or dc, between 4 V and 24 V
Test current not less than 200 mA
Able to measure to within 0.01 Ohms (resolution of 0.01)
May be the continuity range of an insulation resistance tester.

Insulation resistance tester


Direct test voltage depends on the circuit under test, but will be:-
250 V for extra-low voltage circuits
500 V for other circuits supplied at up to 500 V
1000 V for circuits rated between 500 V and 1000 V.
Must be capable of delivering a current of 1 mA at the minimum allowable resistance
level, which is:-

250 kOhms for the 250 V tester


500 kOhms for the 500 V tester
1 MOhms for the 1,000 V tester
Basic instrument accuracy required is +/-5%
Must have a facility to discharge capacitance up to 5 microF which has become charged
during the test
May be combined with the low resistance ohmmeter

Earth-fault loop impedance tester


Instruments to BS EN 61557-2 will comply
Must provide 20 to 25 A for up to two cycles or four half-cycles
Basic instrument accuracy required is +/-5%
Able to measure to within 0.01 Ohms (resolution of 0.01)
Instruments to BS EN 61557-3 will comply

Residual current device (RCD) tester


Must perform the required range of tests (see (8.6.3))
Suitable for standard RCD ratings of 6.10, 30, 100, 300 and 500 mA
Must NOT apply full rated test current for more than 2 s
Currents applied must be accurate to within +/-10%
Able to measure time to within 1 ms (resolution of 1)
Must measure opening time with an accuracy of +/-5%

Applied voltage tests


Must apply a steadily increasing voltage measured with an accuracy of +/-5%
Must have means of indicating when breakdown has occurred
Must be able to maintain the test voltage for at least one minute
Maximum output current must not exceed 5 mA
Maximum output voltage required is 4,000 V

Earth electrode resistance tester


Basic instrument accuracy required is +/-5%
Must include facility to check that the resistance to earth of temporary test spikes are
within limits
Able to measure to within 0.01 Ohms (resolution of 0.01)

8.7.2 - Accuracy and resolution

The sub-section above has indicated the levels of accuracy and resolution required of the
instruments needed to test an electrical installation. The purpose of this subsection will be
to explain the meaning of these two terms.
Accuracy
This term describes how closely the instrument is able to produce and display a correct
result, and is usually expressed as a percentage. For example, if a voltage has a true level
of 100 V and is measured by a voltmeter as 97 V, this is an error of -3 V. Expressed in
terms of the true voltage, it is an error of three volts in one hundred volts, or three per
cent (3%). In this case the reading is low, so the true error would be -3%. Had the error
been +3% the reading would have been 103 V. In most cases we do not know if the
reading is high or low, so the error is expressed as a percentage which may be positive or
negative. Thus, if the voltmeter gave a reading of 100 V but was known to have an
accuracy of ± 4%, the actual voltage could lie anywhere in the range from:

100 + (4/100) x l00V to 100 - (4/100) x 100 V


or 100 + 4 V to 100 - 4 V
which is between 104 V and 96 V

The values given in the Guide are called basic instrument accuracy's which indicate the
possible error with the instrument itself. In practice, there are many factors which affect
the value which is to be measured, and which will further reduce the accuracy. These are
divided into two types.

Instrument errors are largely due to the fact that the true error is not constant, varying
from point to point over the instrument range. Other factors, such as battery voltage,
ambient temperature, operator's competence, and the position in which the instrument is
held or placed (such as vertical or horizontal) will also affect the reading.

Field errors concern external influences which may also reduce accuracy, and may
include capacitance in the test object, external magnetic fields due to cables and
equipment, variations in mains voltage during the test period, test lead resistance, contact
resistance, mains pickup, thermocouple effects, and so on.

It is important to appreciate that percentage accuracy is taken in terms of the full scale
reading of an analogue instrument, or the highest possible reading of a digital type. Thus,
in a multi-range instrument, it is related to the scale employed, not to the reading taken.
For example, if an ohmmeter with a known error of ± 5% is on its 100 Ohms scale and
reads 8 Ohms, the true reading will lie between

8+ 100 x 5 Ohms = 8 + 5 Ohms =13 Ohms and


100

8
100 x 5 Ohms = 8 - 5 Ohms = 3 Ohms
-
100
and not between 8 ± 8x5 Ohms = 8 ± 0.4 Ω or 7.6 Ω and 8.4 Ω
100
Thus it can be seen that the highest accuracy will result from using the lowest possible
scale on a multi-range instrument.

Resolution
This term deals with the ability of an instrument to display a reading to the required
degree of accuracy. For example, if we were measuring the earth-fault loop impedance of
a socket outlet circuit protected by a 30 A miniature circuit breaker type 2, we would
need to ensure that the impedance value was not more than 1.14 Ohms {Table 5.2}. If this
were done using a digital meter with three digits and a lowest range of 99.9 Ohms, we
could obtain a reading of 1.1 Ohms or another of 1.2 Ohms, but not 1.14 2. This would
indicate that the instrument resolution was to the nearest 0.1 Ohm, which usually is not
close enough for electrical installation measurements. If the same three-digit instrument
had a lower scale of 9.99 Ohms, it would be capable of reading 1.14 Ohms and would
have a resolution of 0.01.

8.8.1 - Why bother with paperwork?

When an installation is complete, including additions or alterations to an existing


installation, the persons responsible for the work must report to the owner that it is
complete and ready for service. This is in the form of an electrical installation certificate
which must be separately signed to verify the design, the construction and the inspection
and test aspects (see {8.8.2}) to confirm that the installation complies with BS7671.
Sometimes, the person ordering the work is not the user, in which case it must be ensured
that the user has copies of the forms for inclusion in the installation manual.

This certificate will verify that the installation is safe to use and ready for service, and
should be signed by a competent person who should preferably be one of the following:

1. - a professionally qualified electrical engineer, or

2. - a member of the ECA (Electrical Contractors' Association), or

3. - a member of the ECA of Scotland, or

4. - an approved contractor of the NICEIC (National Inspection Council for Electrical


Installation Contracting), or

5. - a qualified person acting on behalf of one of the above.

In all cases, the Certificates must state for whom the qualified person is acting. The
installer should also compile an operational manual for the installation, which will
include all the relevant data, including:

1. - a full set of circuit and schematic drawings,


2 . -all design calculations for cable sizes, cable volt drop, earth-loop
impedance, etc.

3 . -leaflets or manufacturers' details for all the equipment installed,

4 . -'as fitted' drawings of the completed work where applicable,

5 . -a full specification,

6. - copies of the electrical installation certificate, together with any other commissioning
--- --records,

7. - a schedule of dates for periodic inspection and testing,

8 . -the names, addresses and telephone numbers of the designer, the installer,
and the inspector/tester.

This requirement will be new to many electrical installation installers. Its rationale is to
ensure that future owners or users of the installation, as well as those who maintain it or
who may modify it, have full information. If difficulty is experienced in preparing the
operational manual, reference to BS 4884 and to BS 4940, may be helpful. Records of
the results of all tests (in the form of Electrical Installation and Periodic Test and
Inspection Certificates) should be kept, ideally with the Operational Manual, for the life
of the installation.

8.8.2 - Electrical installation certificate

Following completion of inspection and testing, an electrical installation certificate,


together with particulars of the electrical installation and a schedule of test results, must
be provided to the person who ordered the work. It must be signed three times (by the
designer, the installer and the inspector/tester) to certify that the installation has been
designed, constructed, inspected and tested in accordance with BS 7671 (BS 7671 the
16th Edition of the lEE Wiring Regulations).

but a single-signature version of the certificate may be used where design, construction,
inspection and testing are all the work of the same person.

The form of the certificate giving particulars of the electrical installation and of
completion and inspection is given as {Table 8.9}. In some cases, where there are good
reasons and where a qualified electrical engineer has given his approval, the installation
may not comply fully with the Regulations. In such a case, full details of the departures
must be stated on the completion and inspection certificate as indicated in {Table 8.9},
although this table may be expanded and redesigned as necessary to cover the particular
installation under test. A full schedule of test results must be appended to the Electrical
Installation Certificate and the Periodic Inspection Report. The complete certificate must
be handed (or sent) to the person ordering the work, together with a copy to be given to
the user of the installation where different. The installer, designer and tester should also
keep copies for their records. The recommended intervals between periodic inspections
and tests should be as indicated in {Table 8.4}.

8.8.3 - Installation alterations and additions

The changes in the occupation and uses of situations where there are electrical
installations make alterations and additions a common occurrence. Before commencing
alterations and additions to an installation it is very important to verify that the existing
supply system, installation and earthing arrangements are capable of feeding the proposed
new installation safely. For example, the additional installation in a large extension to a
house may impose extra loads on the supply system which it is incapable of meeting. It is
the responsibility of the person carrying out the extra work to ensure that it, as well as the
existing installation, will function safely and correctly. The tester must check that all
materials made redundant by the installation changes, such as cables, wooden pattresses
etc., and which may be responsible for the spread of fire, are removed. Additionally, the
inspector must look for other prospective fire risks, such as:

1. - flexible cords not securely held by cord grips,

2. -a dangerous increase in the use of adaptors,

3. -worn or otherwise damaged flexible cords,

4. - signs of overheating of appliances, plugs and connectors,

5. - over-rated lamps fitted to luminaires, and

6. -heaters with insecure or missing guards.

It is not his responsibility to rectify defects and faults in the existing installation, but he
must test and inspect it, reporting deviations on the electrical installation certificate which
is provided on completion of the work. Should dangerous defects be found in an existing
installation it would be clearly irresponsible of the person carrying out the alterations or
extensions not to bring them to the urgent attention of the user.

8.8.4 - Periodic inspection and testing

The importance of regular inspection and testing of electrical installations cannot be


overstated, but unfortunately it is an aspect of electrical safety which is very often
overlooked. It is now a requirement of the Regulations that the installer of an installation
must tell the user of the need for periodic test and inspection and the date on which such
attention is required. Probably the good contractor will institute a system so that a
reminder is sent to the customer at the right time. Suggested intervals between
inspections and tests are shown in {Table 8.4}. The results of sample tests should be
compared with those taken when the installation was last tested and any differences
noted. Unless the reasons for such differences can be clearly identified as relating only to
the sample concerned, more tests must be carried out. If these, too, fail to comply with
the required values, the complete installation must be retested and the necessary
correcting action taken.

The inspection and testing must be carried out with the same degree of care as is required
for a new installation. In fact, more care is often needed because dangers can occur to the
testers and to others in the situation in the event of failure of parts of an installation such
as the protective system. The tester must look out for additions to the installation, or for
changes in the use of the area it serves, either of which may give rise to fire risks.
Included may he the addition of thermal insulation, the installation of additional cables in
conduit or trunking, dust or dirt which restricts ventilation openings or forms an
explosive mixture with air, changing lamps for others of higher rating, missing covers on
joint boxes and other enclosures so that vermin may attack cables, and so on.

The sequence of periodic tests differs slightly from that for initial tests {8.3.2} because in
this case the supply will always be connected before testing starts. The tests required and
the sequence in which they must be performed are shown in {Table 8.13}. There will be
cases where necessary information in the form of charts, diagrams, tables, etc., is not
available. The tester will then need to investigate the installation more thoroughly to
make sure that he is fully conversant with it before he can carry out his work.

It must be clearly understood that a retest of a working installation may not be as fall as
that carried out before the installation was put into service. For example, it may be
impossible to switch off certain systems such as computers, and if full testing is not
possible, this should be made clear on the certificate. In such cases, the installation
should be carefully inspected to ensure that possible dangers become apparent. In some
cases it may be necessary to carry out measurements, such as the value of the earth
leakage current, which will indicate the health of the system without the need to
disconnect it.

A sample of 10% of switching devices must be thoroughly internally inspected and


tested. If results are poor, the procedure must be extended to include all switches. The
condition of conductor insulation and other protection against direct contact must also be
inspected at all distribution boards and at samples of switchgear, luminaires, socket
outlets, etc. There should be no signs of damage, overloading or overheating.

Protective and equipotential bonding conductors must not be disconnected from the main
earthing terminal unless it is possible first to isolate the supply. The tester must ensure
that a durable notice to the wording given in {Table 8.12} is fixed at the mains position.

On completion a full electrical installation certificate must be submitted. Additional


matters to report are:

1 . -full test results to enable comparison with earlier tests, from which the
rate of deterioration of the installation (if any) can be assessed.
2. - the full extent of the parts of the system tested notes of omissions may be very
important

3 . -any restrictions which may have been imposed on the tester and which
may have limited his ability to report fully

4 . -any dangerous conditions found during testing and inspection, non-


compliance with the Regulations, or any variations which are likely to arise in
the future.

Where an installation was constructed to comply with au earlier Edition of the


Regulations, tests should be made as required by the 16th Edition as far as it is applicable
and the position fully explained, with suggestions of necessary action, in the Electrical
Installation report.

Table 8.12 - Notice - periodic inspection and testing

IMPORTANT
This installation should be periodically inspected and tested and a report on
its condition obtained, as prescribed in BS 7671 (formerly The IEE Wiring
Regulations for Electrical Installations) published by the Institution of
Electrical Engineers.
Date of last inspection…………………………
Recommended date of next inspection…………………………
Table 8.13 - Sequence of periodic testing
Continuity of protective conductors and earthed equipotential
1
bonding.
2 Polarity
3 Earth fault loop impedance
4 Insulation resistance
5 Operation of switches and isolators
6 Operation of residual current devices
-
together with the following where appropriate
-

7 Continuity of ring final circuit conductors

8 Earth electrode resistance

9 Manual operation of circuit breakers


10 Electrical separation of circuits
11 Insulation resistance of non-conducting floors and walls

8.8.5 - Minor electrical installation works certificate

This simplified certificate is provided by the installer after completion of additions,


alterations or replacements to the existing electrical installation which do not extend to
the provision of a new circuit. Examples include the addition of a socket outlet or a
lighting point to an existing circuit, or to the replacement or repositioning of a light
switch. A separate certificate must be provided for each circuit on which work has been
carried out.

Chapter 9 : Data cabling and networks

9.4 - System design and categories


9.1 - What is data cabling and why do
------- we need it?

9.2 - What are digital systems? 9.5 - Installing data cabling


9.3 - Copper or glass fibre? 9.6 - Useful information

9.1 - What is data cabling and why do we need it?

First of all, why should a book concerned with the Wiring Regulations seek to cover the
subject of data cabling, to which the Regulations (BS 7671) do not apply? The simple
answer must be that most of today’s electricians are almost certain to be concerned with
the technology sooner or later, and an introduction to the subject will be useful.

Data cabling (often referred to as a network) has become extremely common in business
and in academic installations, and will shortly almost certainly be a necessity for many
domestic applications. Data terminals and computers these days are seldom separate
”stand alone“ items, but are networked together, so that all can communicate with the
others and so that the data input to them may be collected and analysed centrally. For
example, all the tills in a supermarket must be linked so that any price changes can be
relayed to all of them simultaneously, and so that the sales information they obtain from
the bar code readers can be gathered centrally to provide exact data concerning the
merchandise checked out. Again, all the individual computers in a college will be linked
by a network so that all can use a single set of programs, such as for word processing.

The system to interconnect these systems is the data cabling which forms the network. In
its most basic form it will consist of copper cables which exist in pairs, which are twisted
throughout their length as an aid in combating the problem of interference due to
”electrical noise“ from other electrical wiring and equipment. One method of ensuring
that there will be no interference is to send the signals in the form of light. A glass fibre
cable is used as path for light pulses injected at one end by a laser and read at the other
end by a photocell. Both of these methods will be considered here. However, it must be
appreciated that one chapter like this one can only provide the briefest coverage, and that
a specialist work, or a training course, is necessary to obtain a fuller understanding of the
subject.

9.2 - What are digital systems?

Data networks are already digital and telephones are fast becoming so. That means that
the signals carried are not waves (like sine waves) which are subject to deterioration as
they are fed through cables, but consist of a series of pulses. If a distorted wave is
received, it is usually impossible to reshape it to the form it had when transmitted because
we have no information to tell us what that shape was originally. If a digital pulse
becomes distorted, it can be reshaped, because we know that it was rectangular.
Information sent digitally is encoded using the binary system, which has only two
numbers, 1 and 0. The rectangular pulse represents 1 and the absence of a pulse at the
expected time is a 0. Some of the low value binary equivalents of decimal numbers are
shown in Table 9.1

A lot more numbers are required in the binary system than in the decimal, and vast
numbers of binary digits will be required to represent a complex wave-shape, such as that
generated by the microphone in a telephone. Modern electronics is quite able to handle
these large numbers of digits, so most means of communication are becoming digital.

Table 9.1 - Some decimal numbers and their binary equivalents


Decimal Binary Decimal Binary Decimal Binary Decimal Binary
1 00001 9 01001 17 10001 25 11001
2 00010 10 01010 18 10010 26 11010
3 00011 11 01011 19 10011 27 11011
4 00100 12 01100 20 10100 28 11100
5 00101 13 01101 21 10101 29 11101
6 00110 14 01110 22 10110 30 11110
7 00111 15 01111 23 10111 31 11111
8 01000 16 10000 24 11000 32 100000

The increasing introduction of cabling systems with higher bandwidths are allowing
digital systems to become faster and their use is becoming commonplace. Wireless
systems, using radio waves in place of cables are being developed; but such systems, of
course, require little or no data cabling
9.3 - Copper or glass fibre?

Since they involve little cabling, wireless systems will not be considered here

Copper cabling exists in two major types, the unshielded twisted pair (UTP) and the
shielded twisted pair (STP). Coaxial cable is used in special applications where radio and
television signals are carried. UTP cables usually consist of four twisted pairs of wires
enclosed in an overall sheathing. To reduce interference, each pair has a different number
of twists per unit length. These cables can be used for alarm systems and voice-only
telephones (category 1) at the lower bandwidths, up to data applications up to 100 MHz
(category 5). Higher frequency cables have more twists in a given length.

Unshielded twisted pair cables may be susceptible to radio and electrical interference,
this disadvantage being reduced in the shielded twisted pair (STP) cable. The shielding
(of braiding or of foil) increases the size and the cost of the cable, and also requires
effective earthing (in the USA they call it grounding). STP cables may also have greater
loss at higher frequencies, and are more expensive, both to purchase and to install, not
only because they are larger, but because shielded connectors must be used. In simple
terms UTP cables are adequate for situations where there is unlikely to be interference
from fluorescent lighting and machinery such as motors, welders, and so on.

Fibre optic cables (in the USA they spell it fiber) have a very thin core of glass (usually
ultra-pure fused silica) with a protective sheath. Light is injected into the cable by a laser
or light-emitting diode, and changed back to an electrical signal at the receiving end by a
photocell. The fibre-optic cable is able to carry signals over greater distances than are
copper cables, and at greater speed; it can also be used over a greater bandwidth. Since it
is not an electrical system, it is immune from electromagnetic and lightning interference.
Other advantages over copper cabling are vastly increased signal capacity (due to the
very high frequency of light), lower transmission losses, lower cost of basic materials and
much smaller cable size. The reduced transmission loss can often allow simpler networks,
by having only one central point of administration with all data cabling fed back to it. At
the time of writing, fibre networks are still more expensive than those with copper cables,
but the gap is narrowing. For very high bandwidth applications fibre networks are the
only solution. Category 5 systems can operate with copper cables, but some think that
they are better served by fibre optic systems. It seems likely that when categories 6 and 7
arrive they will need fibre to support them.

9.4 - System design and categories

The consideration of the design of data cabling systems is beyond the space available
here, if only because of their diversity. A local area network (LAN) is, as the name
indicates, confined to a particular location. It may cover, for example, the data
requirements for a small organisation, or the departmental requirements of a larger one.
Normally, a LAN will use only one category of data cable. The network is likely to be
used for transmission of e-mail between the computers connected to it, and to attach all of
these computers to a wide area network (WAN) or to the Internet. All the computers
connected to the LAN can usually share programs loaded onto any of them, security
being provided by the use of passwords for certain access options.

A wide area network (WAN) is one that usually connects together a series of local area
networks. The distance involved may be small, where the LANs connected are all in the
same building, but may be very large indeed if they are in separate cities or even in
different continents. In the latter case, satellites or transoceanic cabling are likely to be
used for interconnection..

All data cabling is divided into categories depending on the bandwidth that the cabling
can transmit. Categories 1 and 2 cover systems installed generally before 1995;
categories 3 and 5 are being installed in the late 1990s. Category 4 is seldom used, having
been overtaken by category 5, and the very high speed categories 6 and 7 are about to
appear as the second millennium dawns. Table 9.2 shows some applications of the
various categories and further data can be found in Table 9.9..

Table 9.2 - Cable categories


Category Bandwidth Applications
Non-critical applications, such as alarm circuits, voice
1 100 kHz
only telephones, etc.
2 1 MHz General low speed data
3 16 MHz Minimum standard for new installations.
4 20 MHz Data up to 20 Mbps. Seldom used.
Data up to 100 Mbps. The most usual for new
5 100 MHz
installations.
Wider bandwidth systems.
6* 200 MHz
* Likely to be widely used in the future.
Very much wider bandwidth systems.
7* 600 MHz
* Likely to be widely used in the future.

categories 6 and 7 are not yet standardised.

9.5 - Installing data cabling

Twisted-pair and optical fibre cables must be tested before installation in accordance with
the manufacturer’s specification. Great care must be taken to avoid electrostatic discharge
damage, which can result from the charge held by the operator, which may be due, for
example, to walking on certain types of carpet which include man-made fibres. The
chassis of the equipment on which work is intended must be securely earthed, and an
earthed wrist strap worn by the operator.

The following lists of good and bad practices should be followed.


Good practice – things to DO
Locate the main cross-connect near the centre of the area concerned so that
cable distances are limited.
Always use more cable than you need. Leave plenty of slack.
Each horizontal cable should be terminated on a dedicated
telecommunications outlet.
Ensure that cables are at a sufficient distance from equipment that may
generate heat or electromagnetic interference.
Maintain the twist of all cable pairs right up to the point of termination.
Label both ends of each cable.
Use connecting hardware that is compatible with the installed cable.
Tie and dress cables neatly with a minimum bending radius of four times the
cable diameter.
Test each part of the network as it is installed.
All metallic conduit or trunking must be earthed.

Bad practice – things to AVOID


Do not allow cable lengths to exceed the allowable maximum.
Do not create multiple appearances of the same cable at several distribution
points (bridge taps).
Do not leave wire pairs untwisted.
Do not over-tighten cable ties, do not use staples and do not bend cables
sharply.
Do not use connecting hardware that is of a lower category than the cable
being used.
Do not join cables to increase their length – replace with a longer cable.
Do not secure cables so that there is stress on the terminations.
Limit cable bundles to 50 cables to avoid crushing the lower cables.
Prevent kinks occurring in cables during pulling.
Do not use undue strain when cable pulling.
When cable routes pass through walls, the hole should be suitably sleeved
and cables should enter and leave the hole at 90o to the wall.
Make sure that the network is thoroughly tested on completion.

9.6 - Useful information

Data cabling was first used in the USA, and as a result most of the terms used were
coined there. Since they may not always be familiar to the installation electrician, some
of the most common terms are defined in Table 9.3
Table 9.3 - Some data cabling terms explained
A reduction in power or amplitude of the
Attenuation transmitted signal. In cables, usually expressed
in decibels per unit length.
Attenuation to crosstalk The difference between attenuation and
ratio (ATR ) crosstalk measured in decibels.

Cable and connecting hardware that comprise


Backbone cabling the main and intermediate cross-connections
(often known as ”cross-connects“).

The multiple appearances of the same cable pair


Bridged tap
or fibre at several distribution points.
The end-to-end transmission path connecting
Channel
any two points to which equipment is connected.
A connection scheme between cabling runs,
subsystems and equipment using patch cords or
Cross-connection
jumpers that attach to connecting hardware at
each end.
Noise or interference caused by electromagnetic
Crosstalk coupling from one signal path to another and
usually expressed in decibels.
A standard unit to express transmission gain or
Decibel (dB) loss as derived from a ratio of signal amplitudes
or power (see Table 9.13).
Crosstalk measured at the opposite end from
Equal level far-end cross- which the disturbing signal is transmitted
talk (ELFEXT) normalised by the attenuation contribution of the
cable or cabling.
Crosstalk measured at the opposite end from
Far-end crosstalk (FEXT)
which the disturbing signal is transmitted.
A communications system where electrical data
Fibre optic transmission are converted to light energy and transmitted
through optical fibres.
A cross-connect of horizontal cabling to other
Horizontal cross-connect
cabling, such as horizontal, backbone or
(HC)
equipment.
An assembly of two or more cables, of the same
Hybrid cable or of different types or categories, covered by
one overall sheath.
An assembly of twisted-pairs without connectors
Jumper wire on either end used to join telecommunications
links at a cross-connect.
Near-end crosstalk Cross-talk measured at the end from which the
(NEXT) disturbing signal is transmitted.
Patch cord A length of cable with connectors on one or both
ends used to join telecommunications links at a
cross-connect.
A private switching system usually serving an
Private branch exchange
organisation, such as a business, located on the
(PBX)
customer’s premises.
The amount of time that passes between when a
Propagation delay signal is transmitted and when it is received at
the opposite end of the cable or cabling
A method of securing wire to a quick clip, in
which the insulated wire is placed in the terminal
Punch down groove and pushed down with a special tool. As
the wire is seated, the terminal displaces the
wire insulation to make an electrical connection.
An electrical contact used to provide an
Quick clip insulation displacement connection to
telecommunications cables.
The unearthed (ungrounded) conductor of the
Ring conductor
two in a cable pair.
A balanced twisted-pair cable surrounded by
Screened twisted-pair
metallic braid, foil, or both, and bound in a single
(ScTP)
cable sheath.
A cable surrounded by a metallic braid, foil, or
Shielded twisted-pair both, and bound in a single plastic sheath
(STP-A) containing balanced twisted-pair conductors that
are individually sheathed.
The earthed (grounded) conductor of the two in
Tip conductor
a cable pair.
Unshielded twisted-pair A cable with multiple pairs of twisted insulated
(UTP) copper conductors bound in a single sheath.
The manufacturing process that physically binds
Webbed conductors the conductor insulation of the wire pairs of an
unshielded twisted-pair cable.

Table 9.4 - Some abbreviations used in


----------------- data cabling
It is usual today for initials to replace a set of words, and these abbreviations can cause great
confusion. Some of the abbreviations commonly found in data cabling and networks are given in
Table 9.4. Many of them originate in the USA.

Table 9.4 - Some abbreviations used in data cabling


ACR Attenuation-to –crosstalk ratio
ANSI American National Standards Institute
ATR Attenuation-to –crosstalk ratio
AWG American wire gauge
BD Building distributor
BFOC Bayonet fibre optic connector
CD Campus distributor
CDDI Copper distributed data interface
CP Consolidation point
CPE Consumer premises equipment
CSA Canadian Standards Association
dB Decibel
DP Demarcation point
EIA Electronic Industries Alliance
ELFEXT Equal level far-end crosstalk
EMC Electromagnetic compatibility
EMI Electromagnetic interference
EMR Electromagnetic radiation
ER Equipment room
ESD Electrostatic discharge damage
FCC Federal Communications Commission
FD Floor distributor
FEXT Far-end crosstalk
FRNC Flame-retardant non-corrosive
FTP Foil twisted-pair
HC Horizontal cross-connect
IC Intermediate cross-connect
IDC Insulation displacement connection
IEC International electrotechnical commission
ISD Integrated services digital network
ISO International standards organisation
KTS Key telephone system
LAN Local area network

LCL Longitudinal conversion loss

LEC Local exchange carrier


LED Light emitting diode
LFH Low fire hazard
LSOH Low smoke zero halogen
MC Main cross-connect
NEMA National Electrical Manufacturers Association
NEXT Near-end crosstalk
NFPA National Fire Protection Association
NVP Nominal phase velocity of propagation
PBX Private branch exchange
PE Polyethylene
PIMF Pair in metal foil
PP Patch panel
PVC Polyvinyl chloride
RF Radio frequency
RMS Rack mount space
SC Subscriber connector
ScTP Screened twisted-pair
STP-A Shielded twisted-pair
S/FTP Foil and braid twisted-pair
STP Shielded twisted-pair
TC Telecommunications closet
TDM Time division multiplexing
TIA Telecommunications Industry Association
TO Telecommunications outlet
TP Transition point
UPS Uninterruptible power supply
UTP Unshielded twisted-pair
WA Work area
WAN Wide area network
WDM Wave division multiplexing
X Cross-connect

Table 9.5 - Colour coding for backbone


----------------- UTP data cables

The colour coding for backbone unshielded twisted-pair cables is given in Table 9.5
Table 9.5 - Colour coding for backbone UTP data cables
Tip Ring Tip Ring
conductors conductors conductors conductors
White/blue Pair 1 Blue/white Black/brown Pair 14 Brown/black
White/orange Pair 2 Orange/white Black/slate Pair 15 Slate/black
White/green Pair 3 Green/white Yellow/blue Pair 16 Blue/yellow
White/brown Pair 4 Brown/white Yellow/orange Pair 17 Orange/yellow
White/slate Pair 5 Slate/white Yellow/green Pair 18 Green/yellow
Red/blue Pair 6 Blue/red Yellow/brown Pair 19 Brown/yellow
Red/orange Pair 7 Orange/red Yellow/slate Pair 20 Slate/yellow
Red/green Pair 8 Green/red Violet/blue Pair 21 Blue/violet
Red/brown Pair 9 Brown/red Violet/orange Pair 22 Orange/violet
Red/slate Pair 10 Slate/red Violet/green Pair 23 Green/violet
Black/blue Pair 11 Blue/black Violet/brown Pair 24 Brown/violet
Black/orange Pair 12 Orange/black Violet/slate Pair 25 Slate/violet
Black/green Pair 13 Green/black

Table 9.6 - Colour code for horizontal UTP


----------------- data cabling

Table 9.6 shows the colour coding for unshielded twisted-pairs


used for horizontal cabling.

Table 9.6 - Colour code for horizontal UTP data cabling

Pair number Colours Pair number Colours


1 white-blue : blue 3 white-green : green
2 white-orange : orange 4 white-brown : brown

The standards listed in Table 9.7 will replace older documents HD608, EN50167,
EN50168 and EN50169. In the USA TIA/EIA standards apply. The standards have no
coherent numbering system.

Table 9.7 - European standards for data cabling


Standard number Brief description
EN 50173 Information technology generic cabling systems. The
most important data cables standard for Europe.
Generic specification for multi-element metallic cables
prEN 50288-1
used in analogue and digital communications control.
Sectional specification for screened cables
prEN 50288-2
characterised up to 100 MHz.
Sectional specification for unscreened cables
prEN 50288-3
characterised up to 100 MHz.
Sectional specification for screened cables
prEN 50288-4
characterised up to 600 MHz.

Table 9.7 - European standards for data cabling

ISO is the International Standards Organisation, which together with the IEC,
International Electrotechnical Commission, defines data cabling standards for Europe,
dividing cables into classes

TIA is the USA Telecommunications Industries Association, and EIA the Electronic
Industries Alliance, which together define standards for the USA, dividing cables into
categories.

Table 9.8 - provides a comparison of European and USA classifications.

Table 9.8 - Comparison of ISO/IEC and TIA/EIA classifications


ISO/IEC classifications TIA/EIA categories
Class C Category 3
Class D Category 5
Class D (PDAM 3) Category 5e
Class E Future category 6
Class F Future category 7

Table 9.9 shows measurements (worst pair-pair) made at 16 MHz.

Table 9.9 - Near-end cross-talk (NEXT) loss


----------------- for Categories 3, 4 & 5 data cables
Cable
3 4 5 6* 7*
category
Bandwidth
16 20 100 200 300
(MHz)
Frequency
Atten NEXT Atten NEXT Atten NEXT Atten NEXT Atten NEXT
(MHz)
0.064 9 - 0.8 - 0.8 -
0.150 - 53 - 68 - 74
0.256 1.3 - 1.1 - 1.1 -
0.512 1.8 - 1.5 - 1.5 -
0.772 2.2 43 1.9 58 1.8 64
1 2.6 41 2.1 56 2.1 62 1.9 74.3 2.0 80
4 5.6 32 4.3 47 4.3 43 3.8 65.3 3.8 80
10 9.8 26 7.2 41 6.6 47 6.1 59.3 6.0 80
16 13.1 23 8.9 38 8.2 44 7.8 56.2 7.6 80
20 10.2 36 9.2 42 8.8 54.8 8.5 80
31.25 11.8 40 11.1 51.9 10.6 80
62.5 17.1 35 16.1 47.4 15 75.3
100 22.0 32 20.9 44.3 19 71.1
155 26.8 41.4
175 25 67.3
200 30.9 39.8
300 33 63.7
600 50 60.0

ISO is the International Standards Organisation, which together with the IEC,
International Electrotechnical Commission, defines data cabling standards for Europe,
dividing cables into classes

TIA is the USA Telecommunications Industries Association, and EIA the Electronic
Industries Alliance, which together define standards for the USA, dividing cables into
categories.

Table 9.8 - provides a comparison of European and USA classifications.

Table 9.8 - Comparison of ISO/IEC and TIA/EIA classifications


ISO/IEC classifications TIA/EIA categories
Class C Category 3
Class D Category 5
Class D (PDAM 3) Category 5e
Class E Future category 6
Class F Future category 7

Table 9.9 shows measurements (worst pair-pair) made at 16 MHz.

Table 9.9 - Near-end cross-talk (NEXT) loss


----------------- for Categories 3, 4 & 5 data cables
Cable
3 4 5 6* 7*
category
Bandwidth
16 20 100 200 300
(MHz)
Frequency
Atten NEXT Atten NEXT Atten NEXT Atten NEXT Atten NEXT
(MHz)
0.064 9 - 0.8 - 0.8 -
0.150 - 53 - 68 - 74
0.256 1.3 - 1.1 - 1.1 -
0.512 1.8 - 1.5 - 1.5 -
0.772 2.2 43 1.9 58 1.8 64
1 2.6 41 2.1 56 2.1 62 1.9 74.3 2.0 80
4 5.6 32 4.3 47 4.3 43 3.8 65.3 3.8 80
10 9.8 26 7.2 41 6.6 47 6.1 59.3 6.0 80
16 13.1 23 8.9 38 8.2 44 7.8 56.2 7.6 80
20 10.2 36 9.2 42 8.8 54.8 8.5 80
31.25 11.8 40 11.1 51.9 10.6 80
62.5 17.1 35 16.1 47.4 15 75.3
100 22.0 32 20.9 44.3 19 71.1
155 26.8 41.4
175 25 67.3
200 30.9 39.8
300 33 63.7
600 50 60.0