0% found this document useful (0 votes)
180 views9 pages

Design Laundry and Boiler

This document provides calculations for the laundry and heating requirements of the Fantazia Beach hotel which has 560 double rooms. It calculates the needed capacity for washers, dryers, ironers and other laundry equipment based on linen usage. It also calculates the hotel's hot water and heating needs for guest rooms, kitchen, laundry and pool based on occupancy, water usage and temperature requirements to determine the necessary boiler and storage capacities.

Uploaded by

mohammad hamdan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
180 views9 pages

Design Laundry and Boiler

This document provides calculations for the laundry and heating requirements of the Fantazia Beach hotel which has 560 double rooms. It calculates the needed capacity for washers, dryers, ironers and other laundry equipment based on linen usage. It also calculates the hotel's hot water and heating needs for guest rooms, kitchen, laundry and pool based on occupancy, water usage and temperature requirements to determine the necessary boiler and storage capacities.

Uploaded by

mohammad hamdan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 9

HOTEL LAUNDRY CALCULATION SHEET

PROJECT NAME : Fantazia Beach


OWNER :
OPERATOR :
CLASS : 4 STARS
NO. OF ROOMS : 560 DOUBLE ROOMS

DATA

KG LINEN /ROOM/DAY : 9
BED CHANGES /WEEK : 7
NO. OF WORKING DAYS / WEEK : 6
NO. OF WORKING HOURS / DAY : 14
ESTIMATED OCCUPANCY : 80%
WASHING CYCLE TIME : 45
LOADING AND UNLOADING TIME : 15

DRYING PERCENTAGE OF WASHING CAPACITY : 65%


DRYING CYCLE : 20
LOADING AND UNLOADING : 10

IRONING PERCENTAGE OF WASHING CAPACITY : 45%

DRYCLEAN PERCENTAGE OF WASHING CAPACITY : 3%

REQUIRED WASHING CAPACITY (KG LINEN / HR=KG LINEN / LOAD) : 336


REQUIRED DRYING CAPACITY : 131
REQUIRED IRONING CAPACITY : 151
REQUIRED DRYCLEANING CAPACITY (KG LINEN/HR=KG LINEN/LOAD) : 10
NUMBER OF STUFF UNIFORMS TO BE FINISHED : 40

HEATING :

REQUIRED EQUIPMENT RATINGS

TYPE CAPACITY QTY

WASHER EXTRACTOR WASHER 125 KG 2


WASHER 55 KG 1
WASHER 35 KG 1
WASHER 16.5 KG 1

DRYER DRYER 77 KG 2
DRYER 34 KG 1
DRYER 17.5 KG 1

IRONER JENROLL 1R 800X3000 1


FOLDER

DRYCLEAN DRY CLEAN RS 102 1

ADDITIONAL LAUNDRY EQUIPMENT

RECEIVING AREA
WEIGHING SCALE 1
DOUBLE SINK UNIT 1

FINISHING AREA
IRONING BOARD 2
UTILITY LAUNDRY PRESS FOR SHIRTS 1
UTILITY LAUNDRY PRESS FOR TROUSERS 1
FORM FINISHER FOR UNIFORMS
BODY AND BOSSOM PRESS
SINGLE BUCK CABINET SHIRT PRESS
COLLAR CUFF AND YOKE PRESS
SLEEVER PRESS
TWOL FOLDER

DRYCLEAN AREA
STEAM FINISHING BOARD 1
SPOTTING BOARD 1
FORM FINISHER 1
UTILITY DRYCLEAN PRESS 1
VACUUM UNIT

ACCESSORIES
GARMENT CONVEYOR
MARKING MACHINE 1
SEWING MACHINE 1
AIR COMPRESSORS
AIR DRYER
WORKING TABLES 5
WET LINEN CARTS 5
DRY LINEN CARTS 5
ROLL CONTAINERS LOT
SHELVING UNITS LOT
MOBILE GARMENT RAIL 6
MIN
MIN

MIN
MIN

KG/LOAD
KG/LOAD
KG/HR
KG/LOAD
UNIF./HR
HOTEL HEATING POWER CALCULATION SHEET

PROJECT NAME : Fantazia Beach


OWNER :
OPERATOR :
CLASS : 4 STARS
NO. OF ROOMS : 616 DOUBLE ROOMS
560 DOUBLE ROOMS + 10% STAFF HOUSING

DATA
TOTAL HOT WATER CONSUMPTION FOR GUEST ROOM PER DAY : 250
KITCHEN HOT WATER CONSUMPTION PER MEAL : 21
LAUNDRY HOT WATER CONSUMPTION PER KG LINEN : 8
ESTIMATED OCCUPANCY : 100%
AVERAGE BOILER WORKING HOURS : 14

AMBIANT TEMPERATURE 15
REQUIRED HOT WATER TEMPERATURE FOR DOMESTIC USE : 65
REQUIRED HOT WATER TEMPERATURE FOR UTILITY USE : 65
ESTIMATED WATER HARDNESS : 300
ESTIMATED PERCENTAGE CONDENSATE RETURN : 40%
FUEL TYPE : LIGHT OIL

SWIMMING POOL WATER SURFACE AREA : 746


SWIMMING POOL WATER VOLUME : 795

HOT WATER FOR DOMESTIC USE

ESTIMATED TOTAL HOT WATER CONSUMPTION PER DAY : 154,000


NUMBER OF PEAKS FOR HOT WATER CONSUMPTION : 2
DURATION PER PEAK : 4

HOT WATER CONSUMPTION PER HOUR : 19,250


RECOMMENDED HOT WATER RECOVERY : 19,250
REQUIRED HOT WATER STORAGE CAPACITY : 19,250
REQUIRED HEATING POWER : 1,119

HOT WATER FOR UTILITY USE

#1 HOT WATER FOR KITCHEN


TOTAL NUMBER OF MEALS PER PEAK : 1,232
TOTAL HOT WATER CONSUMPTION PER PEAK : 25,872
NUMBER OF PEAKS : 2
DURATION PER PEAK : 4
HOT WATER CONSUMPTION PER HOUR : 6,468
REQUIRED HOT WATER RECOVERY : 6,468
REQUIRED HOT WATER STORAGE CAPACITY : 6,468

#2 HOT WATER FOR LAUNDRY


LINEN CAPACITY PER HOUR : 0
HOT WATER CONSUMPTION PER HOUR : 0
REQUIRED HOT WATER RECOVERY : 0
REQUIRED HOT WATER STORAGE CAPACITY : 0

REQUIRED HOT WATER RECOVERY FOR UTILITIES : 6,468


REQUIRED HOT WATER STORAGE CAPACITY : 6,468
REQUIRED HEATING POWER FOR UTILITIES : 376

LAUNDRY

REQUIRED POWER FOR STEAM HEATING : 1,360

SWIMMING POOL

REQUIRED SWIMMING POOL WATER TEMPERATURE : 27


HEAT LOSS FROM EXPOSED POOL WATER SURFACE AT 27OC : 0.72
MAXIMUM HEAT LOSS FROM EXPOSED POOL WATER SURFACE AT 27OC : 1.31

REQUIRED POWER FOR HEATING UP : 154


REQUIRED POWER TO COMPENSATE HEAT LOSS : 534
MAXIMUM REQUIRED POWER TO COMPENSATE HEAT LOSS : 979

TOTAL POWER REQUIRED FOR ENTIRE HOTEL HEATING LOAD : 3,390


10% ADDED POWER FOR 90% SYSTEM EFECIENCY : 3,766

REQUIRED STEAM BOILER CAPACITY AT 70% OCC. : 3,876


REQUIRED FEED WATER TANK STORAGE CAPACITY : 4,983
REQUIRED SOFTNER CAPACITY IN GRAINS (DUPLEX) : 91,794
REQUIRED SOFTNER CAPACITY IN LITERS : 105
REQUIRED DAILY FUEL TANK STORAGE CAPACITY : 5,273

REQUIRED EQUIPMENT RATINGS

TYPE QTY CAPACITY

STEAM BOILER 2 4000 KG/HR


SOFTNER 1
DOSING PUMP 2

FEED WATER TANK 1 5000 LIT


DAILY FUEL TANK 1 5000 LIT
BLOW DOWN VESSEL 1 300 LIT

STORAGE HEAT EX. 2 12000 LIT 7500 KW


INST. HEAT EX. 1 714 KW
INST. HEAT EX. 1 173 KW
INST. HEAT EX. 1 92 KW

H.W. CIR. PUMPS


H.P. HEADDER 1 10BAR
M.P. HEADDER 1 8BAR
REDUCTION STATION 1 10-8 BAR
REDUCTION STATION 1 10-5 BAR

CHIMNEY 2
LIT. / DAY
LIT / MEAL
LIT/KG

O
C
O
C
O
C
PPM

M2
M3

LITER
PEAKS
HOURS

LIT/HR
LIT/HR
LIT
KW

MEAL
LIT / PEAK
PEAKS
HOURS
LIT/HR
LIT./HR.
LITER

KG/HR
LIT/HR
LIT/HR
LITER

LIT/HR
LITER
KW

KW

O
C
KW / M2
KW / M2

KW
KW
KW

KW
KW

KG/HR
LIT
GRAINS
LIT
LIT