CSU600A / AT
Current supply units
CSU600A / AT
Current supply units
▪▪Compact and rugged
▪▪Quick and easy to use
▪▪Broad application range
▪▪Excellent weight/performance ratio
Description Application example
These high-current supply units have two main fields of IMPORTANT
application. The first is to conduct primary tests on protective Read the User’s manual before using the instrument.
relays. A primary test shows whether all parts of the protection
system are functioning together properly within the specified time Primary test of protective relay equipment and low-
limits under operating conditions. voltage circuit breaker
1. Connect the CSU600A’s current outputs across the current trans-
The second field of application involves conducting current tests former (diagram A) or to the breaker terminals (diagram B).
on low-voltage circuit breakers and overcurrent devices. 2. Connect Timer TM200’s start input to output T and the stop
input to the protective relay equipment’s auxiliary contact.
The CSU600A™ is a compact instrument which, together with
3. Set the current.
Timer TM200™ and an external ammeter, meets stringent 4. Execute the test.
requirements for accuracy, easy handling and performance. This 5. Read the time from TM200.
current supply unit is ideal for a) performance and turn-ratio tests
of current transformers, b) primary tests of protective relays,
c) current tests on low- and high-voltage circuit breakers and d)
commissioning tests that require variable currents.
The CSU600AT™ provides a more comprehensive solution. It has
a built-in timer and an analog ammeter that provide rough current
settings quickly and easily. As a result, connection time has been
TM200
reduced to the bare minimum. Ammeter TM200
The CSU600A and CSU600AT current supply units have an
excellent weight/performance ratio. A B
CSU600A / AT
Current supply units
Specifications Measurement section
Specifications are valid at nominal input voltage and an ambient Output for external am- 600/6 A
temperature of +25°C, (77°F). Specifications are subject to change meter
without notice. Inaccuracy ±0.5%
Environment Timer (only CSU600AT)
Application field The instrument is intended for use Range 0-999.999 s
in high-voltage substations and
Resolution 1 ms
industrial environments.
Inaccuracy ±0.02% of shown value + 0 to 2 ms
Temperature
Other Output for starting external timer
Operating 0°C to +50°C (32°F to +122°F)
Storage & transport -40°C to +70°C (-40°F to +158°F) Outputs, AC, intermittent output 1) (CAT I)
Humidity 5% – 95% RH, non-condensing 115 V mains voltage 230 V mains voltage
CE-marking Current Load Minimum out- Load time Minimum
time put voltage output vol-
EMC 2004/108/EC tage
LVD 2006/95/EC 0A Cont. 6.0 V Cont. 9.5 V
General 75 A – – Cont. 9.3 V
Mains voltage 115 or 230 V AC, 50 / 60 Hz 100 A Cont 5.6 V 1h 9.0 V
Power consumption (max) 115 V, 667 VA cont. (interm. 3738 VA) 200 A 15 min 5.3 V 5 min 8.5 V
230 V, 851 VA cont. (interm. 6440 VA) 300 A 1.5 min 4.9 V 2 min 8.0 V
Protection Thermal cut-outs and miniature 400 A 1 min 4.6 V 1 min 7.5 V
circuit breakers 500 A 20 s 4.2 V 30 s 7.0 V
Dimensions 600 A 15 s 3.9 V 20 s 6.5 V
Instrument 356 x 203 x 241 mm 1) Maximum load time from cold state 25°C (77°F). Not valid for repeated tests.
(14.0” x 8.0” x 9.5”)
Maximum cable lengths at 600 A
Transport case 610 x 290 x 360 mm
(24.0” x 11.4” x 14.2”) 115 V mains 2 x 5 m (16 ft), 70 mm²
Weight 21.9 kg (48 lbs) 230 V mains 2 x 5 m (16 ft), 50 mm²
38.3 kg (84.4 lbs) with accessories 2 x 10 m (33 ft), 70 mm²
and carrying case 2 x 15 m (49 ft), 95 mm²
Current cables 2 x 5 m (16 ft), 50 mm²
Ordering information
Item Art. No.
CSU600A
Complete with: Cable set GA-05052,
Transport case GD-00182
115 V Mains voltage BF-11190
230 V Mains voltage BF-12290
CSU600AT
Complete with: Cable set GA-05052,
Transport case GD-00182
115 V Mains voltage BF-21190
230 V Mains voltage BF-22290
Optional
Cable set 5 m (for 115 V)
2 x 5 m (16 ft), 70 mm2
Weight: 8.4 kg (18 lbs) GA-07052
Cable set 10 m
2 x 10 m (33 ft), 70 mm2
Weight: 16.8 kg (37 lbs) GA-07102
Cable set 15 m
2 x 15 m (49 ft), 95 mm2
Weight: 29.4 kg (65 lbs) GA-09152
TM200
External timer
See the TM200 for more information BE-29090
Cable set GA-05052
SWEDEN UK Other Technical Sales Offices Registered to ISO 9001 and 14001
Megger Sweden AB Archcliffe Road Dover Dallas USA, Norristown USA, Subject to change without notice.
Eldarvägen 4, Box 2970 CT17 9EN England Toronto CANADA, Trappes FRANCE, Art.No. ZI-BF05E • Doc. BF0225BE • 2009
SE-187 29 TÄBY T +44 (0) 1304 502101 Oberursel GERMANY, Johannesburg CSU600A-AT_DS_en_V01
T +46 8 510 195 00 F +44 (0) 1304 207342 SOUTH AFRICA, Kingdom of BAHRAIN www.megger.com
Megger is a registered trademark
F +46 8 510 195 95 Mumbai INDIA, Chonburi THAILAND
E seinfo@megger.com Sydney AUSTRALIA