Thermal-Magnetic Circuit Breakers 3600/3900
Description
Single pole thermal-magnetic circuit breaker with tease-free, trip-free, snap action mechanism and two button operation (M-type TM CBE to EN 60934). Designed for plug-in mounting with E-T-A sockets 17-P10-Si, 23-P10-Si, 63-P10-Si; or panel mounting using E-T-A clips. Featuring an unprotected shunt tap terminal and optional auxiliary contacts. Type 3900 offers lower internal resistance values and is fitted as standard with auxiliary contacts and an intermediate reset position in which all contacts are isolated. Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Process control systems, instrumentation, communications systems, rail vehicles.
3600
standard type
3900
low-resistance type
Ordering information
Type No. 3600 standard version with shunt tap terminal -3 3900 low-resistance version Terminal design P10 blade terminals 6.3-0.8 (QC .250) Auxiliary contacts (3900: intermediate position as standard) Si with blade terminals 6.3-08,one each NO/NC, Si60 special auxiliary contact (only 3900) 1 NO, closed in the intermediate and ON position ZR-Si auxiliary contacts with intermediate position (only 3600) ZR-Si60 special auxiliary contact (only 3600) 1 NO, closed in the intermediate and ON position Si3-R special auxiliary contacts, 2 NC contacts with reset button (not approved) Current ratings 0.05...16 A (type 3600) 0.05...10 A (type 3900) 3600 - P10 - Si 10 A ordering example
Technical data
For further details please see chapter: Technical Information Voltage rating AC 240 V, 50/60 Hz; DC 65 V (UL: AC 250 V; DC 65 V) Current rating range 3600: 0.05...16 A 3900: 0.05...10 A Auxiliary circuit 1 A, AC 240 V / DC 65 V Typical life 5,000 operations at 1 x IN, inductive 5,000 operations at 2 x IN, resistive Ambient temperature -30...+60 C (-22...+140 F) Insulation co-ordination rated impulse pollution (IEC 60664 and 60664 A) withstand voltage degree 2.5 kV 2 reinforced insulation in operating area Dielectric strength (IEC 60664 and 60664A) test voltage operating area AC 3,000 V main/aux. circuit AC 1,500 V aux. circuit 4-5/6-7 AC 840 V Insulation resistance >100 M (DC 500 V) Interrupting capacity Icn 3600 3900 0.05...0.8 A 0.05...0.2 A self-limiting 1...2 A 0.3...2 A 200 A 2.5...16 A 2.5...10 A 400 A Interrupting capacity IN UN (UL 1077) 0.05...16 A AC 250 V 1,000 A type 3600: 0.05...16 A DC 80 V 1,000 A Degree of protection operating area IP40 (IEC 60529/DIN 40050) terminal area IP00 Vibration 5 g (57-500 Hz), 0.38 mm (10-57 Hz) to IEC 60068-2-6, test Fc 10 frequency cycles/axis Shock 25 g (11 ms) to IEC 60068-2-27, test Ea Corrosion 96 hours at 5 % salt mist to IEC 60068-2-11, test Ka Humidity 240 hours at 95 % RH to IEC 60068-2-3, test Ca Mass approx. 45 g
The exact part number required can be built up from the table of choices shown above. Ordering references for optional features should be omitted if not required.
Standard current ratings and typical internal resistance values
Current rating (A) Internal resistance () 3600 3900 Current rating (A) Internal resistance () 3600 3900
0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 1.5 2 2.5
447 131 40 19.3 10.4 7.1 4.3 2.5 1.67 0.61 0.38 0.24
211 48 12.4 5.4 3.1 2.0 1.32 0.76 0.49 0.21 0.101 0.078
3 4 5 6 7 8 10 12 14 15 16
0.19 0.090 0.061 0.041 0.034 0.02 0.02 0.02 0.02 0.02 0.02
0.054 0.035 0.025 0.02 0.02 0.02 0.02
Approvals
Authority 3600: VDE (EN 60934) CSA/UL UL 3900: VDE (EN 60934) Voltage ratings AC 240 V; DC 65 V AC 250 V; DC 80 V DC 65 V AC 240 V; DC 65 V Current ratings 0.05...16 A 0.05...16 A 0.05...25 A 0.05...10 A
Issue A
www.e-t-a.com
2 - 55
Thermal-Magnetic Circuit Breakers 3600/3900
Dimensions
-P10-Si
OFF ON 11.5 .453
Internal connection diagrams
with shunt terminal (standard) and auxiliary contacts (-Si) only 3600
line 1 line 1 5 7
11 .433
6.5 .256 4 .157
8.5 .335
5 .197
51 2.01
2 .079
I>
3 (from IN=8 A)
I> 2
3 (from IN=8 A)
19 .748
1 4 6 3 7 5 2 10 .394
Switching position with auxiliary contacts and reset button (-Si3-R)
6.8 .268 6 x 6.8 = 40.8 6 x .268 = 1.61 blade terminals DIN 46244-A6.3-0.8 (QC .250)
OFF position line 1 5 7 intermediate position line 1 5 7 ON position line 1 5 7
current rating in A 13 .512 2
43 1.69 20 .787 11.5 .453
I> 2
3 (from IN=8 A)
I> 2
3 (from IN=8 A)
I> 2
3 (from IN=8 A)
8.5 .335
50 1.97
11 .433
-Si3-R -Si60 -ZR-Si60 -ZR-Si
OFF
ON
11.5 .453
Switching position with special auxiliary contact (-Si60, -ZR-Si60)
6.5 .256 4 .157 8.5 .335
OFF position line 1 7 intermediate position line 1 7 ON position line 1 7
5 .197
51 2.01
2 .079
I>
3 (from IN=8 A)
I> 2
3 (from IN=8 A)
I> 2
3 (from IN=8 A)
19 .748
1 4 6 3 7 5 2 10 .394
6.8 .268 6 x 6.8 = 40.8 6 x .268 = 1.61 current rating in A 13 .512 2 43 1.69 20 .787 11.5 .453
Switching position with intermediate position and auxiliary contacts (3600: -ZR-Si, 3900: -Si)
blade terminals DIN 46244-A6.3-0.8 (QC .250)
OFF position line 1 5 7 intermediate position line 1 5 7 ON position line 1 5 7
I> 2
3 (from IN=8 A)
I> 2
3 (from IN=8 A)
I> 2
3 (from IN=8 A)
8.5 .335
50 1.97
Intermediate position: Holding down reset button and actuating manual release simultaneously.
Installation drawing
operating area (reinforced insulation)
Terminal design -P10
1
20 .787
1 4
5 2
mounting area
2 .079
12.5 .492
38 1.50
This is a metric design and millimeter dimensions take precedence ( mm ) inch
2 - 56
www.e-t-a.com
Issue A
Thermal-Magnetic Circuit Breakers 3600/3900
Typical time/current characteristics
3600 0.05 7 A
10000
AC1)
3600 8 16 A
10000
AC1)
3900 0.05 10 A
10000
DC2)
1000
1000
1000
100 Trip time in seconds Trip time in seconds
100 Trip time in seconds
100
10
10
10
0.1
0.1
0.1
0.01
0.01
0.01
0.001 1 2 4 6 8 10 20 40 60 80 100 times rated current +23 C +73.4 F -30 C -22 F
0.001 1 2 4 6 8 10 20 40 60 80 100 times rated current
0.001 1 2 4 6 8 10 20 40 60 80100 times rated current
+60 C +140 F
1) 2)
Magnetic tripping currents are increased by 20% on DC supplies. Magnetic tripping currents are decreased by 20% on AC supplies.
The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section 9 Technical information. Ambient temperature F -22 -4 +14 +32 +73.4 +104 +122 +140 C -30 -20 -10 0 +23 +40 +50 +60 Derating factor 0.76 0.79 0.83 0.88 1 1.08 1.16 1.24
Accessories
Module 17plus Modular power distribution system for circuit breakers 2210-S, 3600 or 3900. For technical details see product group 7. 19" Rack 19BGT2 2U for 18, 24 or 30 circuits. For technical data see product group 7.
19" Rack accommodating up to 30 E-T-A thermal-magnetic circuit breakers type 3600-P10-Si or 3900-P10-Si. For technical data see product group 7.
Issue A
www.e-t-a.com
2 - 57
Thermal-Magnetic Circuit Breakers 3600/3900
Accessories
Sockets 17-P10-Si 17-P10-Si-20025 (up to 16 A max. load) mounted with adapter Retaining clip Y 300 581 11 to special order.
slot fitting labels from Phoenix, Weidmller polarized blade terminal DIN 46244-A6.3-0.8 (QC .250) 10 .394 retaining clip
Bus bar (10-way) (supplied as a complete package) for socket 17 (for max. 100 A continuous load) X 211 157 01 with terminal X 211 157 02 without terminal (more positions available on request)
Phoenix terminal AKG 35 max.cross section 35 mm2 (AWG 2) cylinder head screw washer M4x4 ISO1207 A 4.3 DIN 125 nickel plated nickel plated
-P10
2 .079
6.3 depth .248 10 mm (.394 in.)
1 11 23 2(k)
8.5 .335
10 .394
1 2(k) 12
female connector
25.8 1.02
5 .197 41.3 1.63
1.4 .055
23
45.8 1.80
12 24 2(i)
33.3 1.31
11
24 2(i)
M4 Cu rail, tin-plated
6.5 .256
80 3.15
12.5 .492 symmetrical rail EN 50022-35x7.5 adapter X20040901 G-profile EN 50035-G32 7 .276 12.8 .504
polarization recess
154.8 6.09
Sockets 17-P70-Si 17-P70-Si-20025 (up to 16 A max. load) mounted with adapter Retaining clip Y 300 581 11 to special order.
slot fitting labels from Phoenix, Weidmller blade terminal DIN 46244 part 2 C profile (2xA2.8-0.8) (QC 2x.110) 10 .394 retaining clip
Insulate sleeving for bus bar Y 303 824 01
9 .354 17 .669 5.4 .213 125 4.92
-P70
2.8 depth .110 10 mm (.394 in.)
1 11 23 2(k) 12 24 2(i)
10 .394
1 2(k) 12 24 2(i)
Connector bus links -P10 X 210 588 01/ 1.5 mm2 (AWG 16), brown up to 13 A max. load X 210 588 02/ 2.5 mm2 (AWG 14), black up to 20 A max. load X 210 588 03/ 2.5 mm2 (AWG 14), red up to 20 A max. load X 210 588 04/ 2.5 mm2 (AWG 14), blue up to 20 A max. load
45.8 1.80 100 quick-connect tabs 6.3 (.250) DIN 46247 tinned brass, insulated
25.8 1.02
8.5 .335
33.3 1.31
5 .197 41.3 1.63
11 23
1.4 .055
6.5 .256
80 3.15
12.5 .492 symmetrical rail EN 50022-35x7.5 adapter X20040901 G-profile EN 50035-G32
polarization recess
Sockets 23-P10-Si 63-P10-Si (up to 16 A max. load) Retaining clip Y 300 581 03 to special order.
polarized blade terminals DIN 46244-A6.3-0.8 (QC .250) 7.4 .291 7.4 .291 retaining clip 21 .827
Extraction tool Y 301 398 02
~70 ~2.76
56 2.21
22.2 .874 6 x .268 = 1.61 6.8 .268
4.4 .173
12.5 .492
6.25 .246 50 1.97 57.4 2.26 6 x 6.8 = 40.8
10 .394
Mounting clip Y 300 504 02 (2 pcs needed per unit)
1.9 .075 2 .079 1 .039 7.5 .295
46 1.81
25 .984
2 .079
12.5 .492 polarized recess
4.4 .173
6 .236 30 1.18
75 2.95
0.5 .020 12.5 .492
7.3 .287
60.4 2.38 50 1.97
8.5 .335
8 .315
This is a metric design and millimeter dimensions take precedence ( mm ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted.
M4 16.5 .650 20 .787
2 - 58
www.e-t-a.com
2 .079
12.5 .492
50 1.97 57.4 2.26 64 2.52
64 2.52
Installation drawing with mounting clips Y 300 504 02
50 1.97
3.5 .138
10 .394 pressure-relief joint (1.1 mm (.043 in.) thick constriction)
Issue A