Product data sheet
Specifications
                                             TeSys Deca contactor - 3P(3 NO) -
                                             AC-3/AC-3e - <= 440 V 25 A - 415 V
                                             AC coil
                                             LC1D25N7
                                                                                               Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range                            TeSys
                                 TeSys Deca
Product name                     TeSys D
                                 TeSys Deca
Product or component type        Contactor
Device short name                LC1D
Contactor application            Motor control
                                 Resistive load
Utilisation category             AC-3
                                 AC-4
                                 AC-1
                                 AC-3e
Poles description                3P
Power pole contact composition   3 NO
[Ue] rated operational voltage   Power circuit: <= 690 V AC 25...400 Hz
                                 Power circuit: <= 300 V DC
[Ie] rated operational current   25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
                                 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
                                 25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Motor power kW                   5.5 kW at 220...230 V AC 50/60 Hz (AC-3)
                                 11 kW at 380...400 V AC 50/60 Hz (AC-3)
                                 11 kW at 415...440 V AC 50/60 Hz (AC-3)
                                 15 kW at 500 V AC 50/60 Hz (AC-3)
                                 15 kW at 660...690 V AC 50/60 Hz (AC-3)
                                 5.5 kW at 400 V AC 50/60 Hz (AC-4)
                                 5.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
                                 11 kW at 380...400 V AC 50/60 Hz (AC-3e)
                                 11 kW at 415...440 V AC 50/60 Hz (AC-3e)
                                 15 kW at 500 V AC 50/60 Hz (AC-3e)
                                 15 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power HP (UL / CSA)        3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
                                 2 hp at 115 V AC 50/60 Hz for 1 phase motors
                                 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
                                 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
                                 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
                                 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
Control circuit type             AC at 50/60 Hz
[Uc] control circuit voltage     415 V AC 50/60 Hz
Auxiliary contact composition    1 NO + 1 NC
[Uimp] rated impulse withstand   6 kV conforming to IEC 60947
voltage
Overvoltage category             III
Jan 17, 2022                                                                               1
[Ith] conventional free air        10 A (at 60 °C) for signalling circuit
thermal current                    40 A (at 60 °C) for power circuit
Irms rated making capacity         140 A AC for signalling circuit conforming to IEC 60947-5-1
                                   250 A DC for signalling circuit conforming to IEC 60947-5-1
                                   450 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity            450 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand   240 A 40 °C - 10 s for power circuit
current                            380 A 40 °C - 1 s for power circuit
                                   50 A 40 °C - 10 min for power circuit
                                   120 A 40 °C - 1 min for power circuit
                                   100 A - 1 s for signalling circuit
                                   120 A - 500 ms for signalling circuit
                                   140 A - 100 ms for signalling circuit
Associated fuse rating             10 A gG for signalling circuit conforming to IEC 60947-5-1
                                   63 A gG at <= 690 V coordination type 1 for power circuit
                                   40 A gG at <= 690 V coordination type 2 for power circuit
Average impedance                  2 mOhm - Ith 40 A 50 Hz for power circuit
[Ui] rated insulation voltage      Power circuit: 690 V conforming to IEC 60947-4-1
                                   Power circuit: 600 V CSA certified
                                   Power circuit: 600 V UL certified
                                   Signalling circuit: 690 V conforming to IEC 60947-1
                                   Signalling circuit: 600 V CSA certified
                                   Signalling circuit: 600 V UL certified
Electrical durability              1.65 Mcycles 25 A AC-3 at Ue <= 440 V
                                   1.4 Mcycles 40 A AC-1 at Ue <= 440 V
                                   1.65 Mcycles 25 A AC-3e at Ue <= 440 V
Power dissipation per pole         3.2 W AC-1
                                   1.25 W AC-3
                                   1.25 W AC-3e
Front cover                        With
Mounting support                   Rail
                                   Plate
Standards                          CSA C22.2 No 14
                                   EN 60947-4-1
                                   EN 60947-5-1
                                   IEC 60947-4-1
                                   IEC 60947-5-1
                                   UL 508
                                   IEC 60335-1
Product certifications              CCC
                                   LROS (Lloyds register of shipping)
                                   BV
                                   CSA
                                   GOST
                                   DNV
                                   UL
                                   RINA
                                   GL
                                   UKCA
Connections - terminals            Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
                                   Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
                                   Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
                                   Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
                                   Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
                                   Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
                                   Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end
                                   Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end
                                   Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end
                                   Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end
                                   Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid without cable end
                                   Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid without cable end
Tightening torque                  Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                   Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                   Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                                   Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
                                   Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
                                   Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Operating time                     12...22 ms closing
                                   4...19 ms opening
Safety reliability level           B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
                                   B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability              15 Mcycles
  2
                                                                                                                   Jan 17, 2022
Maximum operating rate           3600 cyc/h 60 °C
Complementary
Coil technology                  Without built-in suppressor module
Control circuit voltage limits   0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
                                 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
                                 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
                                 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA               70 VA 60 Hz cos phi 0.75 (at 20 °C)
                                 70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in     7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
VA                               7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation                 2…3 W at 50/60 Hz
Auxiliary contacts type          type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
                                 type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency     25...400 Hz
Minimum switching current        5 mA for signalling circuit
Minimum switching voltage        17 V for signalling circuit
Non-overlap time                 1.5 ms on de-energisation between NC and NO contact
                                 1.5 ms on energisation between NC and NO contact
Insulation resistance            > 10 MOhm for signalling circuit
Environment
IP degree of protection          IP20 front face conforming to IEC 60529
Protective treatment             TH conforming to IEC 60068-2-30
Pollution degree                 3
Ambient air temperature for      -40…60 °C
operation                        60…70 °C with derating
Ambient air temperature for      -60…80 °C
storage
Operating altitude               0...3000 m
Fire resistance                  850 °C conforming to IEC 60695-2-1
Flame retardance                 V1 conforming to UL 94
Mechanical robustness            Vibrations contactor open: 2 Gn, 5...300 Hz
                                 Vibrations contactor closed: 4 Gn, 5...300 Hz
                                 Shocks contactor closed: 15 Gn for 11 ms
                                 Shocks contactor open: 8 Gn for 11 ms
Height                           85 mm
Width                            45 mm
Depth                            92 mm
Net weight                       0.37 kg
Packing Units
Unit Type of Package 1           PCE
Number of Units in Package 1     1
Package 1 Weight                 414 g
Package 1 Height                 5 cm
Package 1 width                  9.2 cm
Package 1 Length                 11.2 cm
Unit Type of Package 2           S02
Jan 17, 2022                                                                                        3
Number of Units in Package 2   20
Package 2 Weight               8.641 kg
Package 2 Height               15 cm
Package 2 width                30 cm
Package 2 Length               40 cm
Package 3 Height               77 cm
Offer Sustainability
Sustainable offer status        Green Premium product
REACh Regulation               REACh Declaration
REACh free of SVHC             Yes
EU RoHS Directive              Compliant
                               EU RoHS Declaration
Toxic heavy metal free         Yes
Mercury free                   Yes
RoHS exemption information     Yes
China RoHS Regulation          China RoHS declaration
                                Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure       Product Environmental Profile
Circularity Profile             End of Life Information
WEEE                           The product must be disposed on European Union markets following specific waste collection and
                               never end up in rubbish bins
PVC free                       Yes
California proposition 65      WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
                               trioxide, which is known to the State of California to cause cancer. For more information go to
                               www.P65Warnings.ca.gov
Contractual warranty
Warranty                       18 months
  4
                                                                                                                Jan 17, 2022