TYPE4 Checker User Manual
TYPE4 Checker User Manual
TYPE4 Checker
Instruction Manual
                                            1
                                                                                 AS0112C-P
                         Table of contents
Introduction                                                                3
Chapter 1      Overview and preparation                                     4
               1-1 What’s the service checker?                              4
               1-2 Preparation                                              6
                                 1-2-1 Essential materials                  6
                                 1-2-2 Other materials to prepare           7
                                 1-2-3 Required to do before recording      8
Chapter 2      Installing the checker software                              10
               2-1 Obtainment of software (new/update)                      10
               2-2 Installation procedure                                   10
               2-3 Removal of software                                      11
Chapter 3      Connecting to the unit                                       12
               3-1 D3-NET (F1,F2) connection                                12
               3-2 Connecting power supply                                  13
Chapter 4      Overview of the checker software                             14
               4-1 Start up the checker software                            14
               4-2 Quit the checker software                                14
               4-3 Overview of the checker software function                15
Chapter 5      Recording operation data                                     16
               5-1 Viewing operation data                                   16
                                5-1-1 Customer info selection               16
                                5-1-2 Network map display                   19
                                5-1-3 Switching modes                       21
                                5-1-4 Detailed info input                   23
                                5-1-5 Operation data display                26
               5-2 Recording setup                                          30
                                5-2-1 Setup recording                       30
               5-3 Centralized operation                                    32
Chapter 6      Playback of recorded operation data                          34
               6-1 Playing operation data                                   34
               6-2 Viewing customer/network map information                 37
               6-3 CSV output (export function)                             39
Chapter 7      Other functions                                              41
               7-1 Data transfer                                            41
               7-2 Customer information                                     43
               7-3 Option setting                                           44
                                7-3-1 Setup COM port                        44
                                7-3-2 Prohibit/permit centralized control   45
                                7-3-3 Change display language               46
                                7-3-4 Change display unit of measure        46
               7-4 Help function                                            47
Frequently asked questions                                                  48
Specification                                                               52
                                                                                        2
                                                                                                          AS0112C-P
                                       Introduction
Thank you for purchasing TYPE4 Checker.
This document instructs how to use TYPE4 Checker and Windows PC software for TYPE4 Checker (TYPE4
software). Please read carefully this document before using and use for correct use.
There could be a risk of unexpected accidents unless respecting cautions in this document.
 Functions, ways to use this software, and supported VRV models by this software are different based on
 software version. In this document, instructions are targeted at V1.3.0.0 or later version.
 PC software for TYPE3 Checker does not work with TYPE4 Checker. If you have not installed TYPE4 software
 to your PC, please obtain it before using.
 To obtain the latest information (manual, software), please check on Daikin webpage or ask your national
 Daikin distributor.
 https://www.daikin.com/products/ac/services/index.html
                                                                                                                 3
                                                                                                                  AS0112C-P
 1) Overview
 Service checker is the tool which visualizes operation data (sensor readings, actuator status, operation mode,
 etc.) of VRV air conditioning units.
 2) Composition
 Service checker consists of two main components (TYPE4 checker box, TYPE4 checker software). It works with
 Windows PC which is connected to TYPE4 checker box by USB cable. It is necessary to install TYPE4 checker
 software to your Windows PC before using.
 • TYPE4 checker components (see 1-2-1 Essential materials)
 • Windows PC (see 1-2-2 Other materials to prepare)
                                                                                    VRV
                        USB cable (included)
 TYPE4 software
 (download)
                                              TYPE4
              Windows PC
                                         checker box
                                                        D3-NET connection wire
                                                        (field procurement)
[Software update]
Supporting new VRV models is realized by PC software, so it is necessary to update TYPE4 checker software
for supporting newly introduced products.
3) Purpose
  (Note) This tool is not designed for permanent installation such as continuous monitoring or long term data
  logging and such ways of using are not guaranteed. If a permanent monitoring is necessary, please consider
  using remote monitoring service.
 This tool is distributed as service part from local distributor of Dakin. Please contact your local Daikin distributor
 for purchasing TYPE4 checker box as the other spare parts.
                                                                                                                          4
                                                                                                                AS0112C-P
D3-NET connection
      port
                                                                                     Main switch
Main switch Red colored LED will lit if you toggle this switch.
                               Connecting to Windows PC by USB cable. This port is for power supply (5VDC)
         USB 2.0 port
                               from PC USB port and communication with PC.
         (Type-B)
                               * Please use the USB cable which is included in the TYPE4 package.
                               Connection port for D3-NET communication cable.
         D3-NET connection     (This is not for power supply terminal, please do not apply power line. If you
         port                  connect power supply to this port, TYPE4 Checker box will be broken and
                               burnt.)
                                                                                                                       5
                                                                                                          AS0112C-P
1-2 Preparation
Preparations for materials to be necessary for VRV operation data recording will be explained in this section.
Standard components which are required for VRV operation data recording are below.
                                                                                                                   6
                                                                                                               AS0112C-P
  1) Required PC specification
  •PC type
                •   Windows PC
                •   CPU 1GHz+, Memory 2GB+, HDD 20GB+
                •   Windows7 SP1 or later, Windows 8.0 /8.1 /10
                •   USB port
 For control signal wiring, use vinyl cords or cables with two-core and sheathed as follow.
 • Vinyl cabtyre cylindrical cord                                         VCTF              JISC3306
 • Vinyl-insulated vinyl sheathed cable for control                       CVV               JISC3401
 • Vinyl-insulated vinyl sheathed, cylindrical cable for control          CVS               JISC3401
 • Vinyl-insulated vinyl sheathed, cylindrical cable                      VVR               JISC3342
 • 600V vinyl cabtyre cable                                               VCT               JISC3312
 Cautions:
 1. Do not use multiple-cored wires with 3 cores or more.
 2. Use wires with a cross section of 0.75mm2 -1.25mm2.
 3. Do not make wires bound in control- signal wiring. Do not make long-distance wiring by having signal wires
     bound packed with tapes, tie-laps and the like.
 4. Wire the signal wires away from power lines to prevent the effects of electric noise. Since Daikin’s air
    conditioners and related products will generate much lower electric noises, it allows to have a distance of
    minimum 50mm between the power lines and the control signal wires.
                                                                                                                      7
                                                                                                                   AS0112C-P
After finishing preparation of materials, further preparation is needed for executed as the listed procedure.
Following the instruction of Chapter 2 (Installing the checker software), install checker software.
            PC
                                                                 Checker box   (Back: USB 2.0 terminal (Type-B))
                                USB cable
                                (included)
A connector B connector
 3) Confirmation of connection
To avoid troubles such as PC and Checker connection, please check connection between PC and Checker as
instructions listed below.
[How to confirm]
Connection check can be done without connecting checker and VRV.
[Confirmation procedure]
•Connect PC and Checker, turn on Checker
•Start Checker software
•Select correct COM port which is connected to Checker (default selection is COM1)
                                                                                                                          8
                                                                                                               AS0112C-P
    (2) Select COM port to be used in Select Port window
(Note) In case of no COM port with “Silicon Labs CP210x USB to UART Bridge”
[OK case]
Wait for about 10sec, if there will be no [Not OK case] messages shown, connection is OK.
[Not OK case]
Wait for about 10sec, if there will be messages like “Port could not be opened”, “It could not be started, please
  check connection” are shown, communication was not executed correctly. Please go back (exit) once and
  check COM port setting in option menu. Then please check again.
                                                                                                                      9
                                                                                                                  AS0112C-P
                                                                                                                           10
                                                                                                                    AS0112C-P
C:¥Users¥[username]¥AppData¥Local¥Checker4
If you would like to remove all files from your PC, please just delete Checke4 folder.
If you would like to keep recorded data, keep C:¥Users¥[username]¥AppData¥Local¥Checker4¥D3Data folder.
If your PC has older version of TYPE4 checker software such as V1.2.2.1, please uninstall from control panel.
(Older version can coexist with newer version if you would like keep older version.)
                                                                                                                          11
                                                                                                                AS0112C-P
                                            TYPE4
                 PC                    checker box
                                                           D3-NET connection wire
[Connection procedure]
     (1) Connect with D3-NET connection wire prepared in 1-2 Preparation part in this manual.
     Please connect wire to D3-NET terminal of checker first. (If connect to D3-NET terminal of VRV and F1-F2
     will be short-circuited, unit could be damaged)
(2) Connect another end of D3-NET connection wire to communication terminal (F1-F2) of VRV unit.
         [Warning]
         Please connect to communication terminal of VRV (outdoor unit or indoor unit) or centralized
         controller. If it would be connected to power terminal, there is a possibility of fatal accident by
         electric shock or damage of the unit.
          [Caution]
          1. It’s not necessary to correspond F1-F2 of the transmission terminal of VRV to F1-F2 of the
          checker like F1-F1 or F2-F2 respectively (no polarity).
          2. Recommended connection point of VRV unit is F1-F2 terminal of OUT-OUT connection of outdoor
          unit, but it can be connected to indoor unit or centralized controller.
          3. In case of connecting to indoor unit, please connect to the last indoor unit of the line to avoid
          sub-branching.
          4. To extend wiring length (up to hundreds of meters), it could cause affection to the unit’s
          operation. Please be aware of electric interference such as taking enough distance from power line.
                                                                                                                      12
                                                                                                                 AS0112C-P
   •When connecting to the VRV unit for the first time, the unit will change to stand-by mode for several minutes to
   scan all the connected indoor and outdoor units. The system will automatically resume after finishing auto-
   scanning (for 2nd time and onwards, system would not enter stand-by status by choosing saved network map).
   •Data refresh interval depends on the refresh interval of connected VRV model (normally between 1 min to 5
   min) regardless of data saving interval setting of checker software.
   •In case of DTA109 adapter (D3-NET expander) is installed, Checker cannot collect operation data beyond the
   point of DTA109 (for example, if you connect Checker in main bus, operation data of VRV systems in branch bus
   cannot be monitored).
   •If Wiring Adaptor for Electrical Appendices (1) or (2) (KRP2A or KRP4A) are installed to the same D3-NET line, an
   error will be displayed to BMS or other centralized control system. To avoid this error, it is necessary to prohibit
   centralized control function of checker software (see 7-3-2 Prohibit/permit centralized control).
     [Procedure]
    (1) Please connect your PC to Checker USB port (Type-B) by the USB cable which came with Checker package.
      [Caution]
      Power is supplied from USB terminal. Do not connect AC power to D3-NET (F1,F2) terminal.
      (If AC power is connected to the D3-NET port, checker will be burned and broken.)
(2) Please switch the Checker on. Red LED will be lit on power switch.
                                                                                                                          13
                                                                                                                   AS0112C-P
     [Procedure]
     1) From (Start[ button, select [Program] and select checker software.
           [ Windows 7 ]                                    [ Windows 10 ]
                                                                                                                                14
                                                                                                            AS0112C-P
2) By selecting “Setting”>”Exit”, checker software can be quit.
3) By pressing F12 key on your PC, below dialog will appear. By pressing Yes button to exit the program.
                                                                                                                    15
                                                                                                                 AS0112C-P
  (Note) “Record only” without data management can be selected, it is recommended to use customer
  information for better management of each data.
      [Procedure]
      (1) In main menu, click [Record] button. Proceeding to [Customer selection]
                                                                                                                       16
                                                                                                        AS0112C-P
• Press [New customer] to record data for a new customer with registration of customer information.
  Proceeding to [Customer data input] screen. Please proceed to (3)
• To use existing customer information, please select desired customer and press [Select customer]
  button to proceed [Network map selection] screen. Please proceed to (4)
• To use edit and use existing customer information, please select desired customer and press [Edit cust.
  Data] button to proceed to [Edit cust. Data] screen. Please proceed to (3)
• In case of recording only without customer information management, please press [Record only]
  button. Please proceed to (5)
  (Note)
  1. In case of [Record only], operation data will be overwritten every time. Please be aware.
  2. In case of [Record only], VRV system will stand by every time. So it is recommended to enter customer
  information to avoid unnecessary system stand-by.
    After entry of all information, please press [Save] button. By pressing [Select customer] button,
    you can go to [Network map selection] screen. If you need to return without saving, please press
    [Cancel] button.
  (Note)
  1. It is possible to manage multiple network map info under one customer name.
  2. One D3-NET line is managed as one network map, but it is necessary to mange D3-NET line which is
  split by DTA109 as different network map.
                                                                                                              17
                                                                                                          AS0112C-P
  • If there is network map which used for operation data recording in the past, please select desired
    network map and press [OK] button to proceed to [Network map] screen. Please proceed to [5-1-2:
    Network map display]
  • Even if in the site where you have recorded operation data before, if you are connecting to the
    different D3-NET system please press [New] button. Please proceed to (5)
  • To change the name of existing network map, please press [Edit map name] button. Please proceed
    to (6)
  • To delete existing network map, please press [Delete] button
  • To return, please press [Back] button
 In case of first time connection to D3-NET, connected system will be in stand-by status to obtain line and
 model (series) information from D3-Net with notification screen shown above. If the system can be
 changed to stand-by status, please press [OK] button to proceed to (6)
 (Note)
 1. By pressing [OK] button of (6) [Edit map name screen], system will be in stand-by status and will be
     thermostat-off for several minutes.
 2. If you use existing network map which was created before, confirmation screen would not shown for
     the 2nd time.
 2) After entering appropriate network map name, please press [OK] button to proceed
    [Network map display] screen. Then proceed to [5-1-2 Network map display]. Please press [Back]
     button to return.
                                                                                                                18
                                                                                                            AS0112C-P
     (Note1)
     •Without initialization of D3-NET line after adding/removing outdoor unit, indoor unit, BS unit or replacing
     control PCB, network map cannot be shown. In those cases please carry out D3-NET initialization before
     using checker.
     •In case of system stand-by is not allowed, please use past existing network map or carry out in the hours
     system stand-by is allowed.
     (Note2)
     •If you change date/time setting of PC after the point of [Network map display] screen, the order of
     recorded data could be mixed up and would not be recorded correctly. To avoid such an issue, please do
     not change date/time of your PC during recording the data.
                                                                                                                    19
                                                                                                           AS0112C-P
       Color                                            Status
                In unit error
       Red
                In communication error
      Violet
      White     In case of unit model (series) not detected with the number of units were
                identified. For the first several minutes system is in this status during auto scan.
   • In [Cent.] box, centralized group number is displayed. But this info is only sent while map is created, so
     this info cannot be shown if you used existing map.
     (if you entered group number in [Detailed data input], entered group number is shown.)
   • In [Airnet] box, Airnet address is displayed.
  (Note)
  1. If the color of icon is white, units are under detection. Operation data would not be displayed until completion
  of unit detection period will end. Please wait for until all icon will change to the color other than white.
     (If you start recording one of icon is still white (not recognized), data would not be recorded for those units)
  2. [System] in the upper left corner means refrigerant circuit basis. It is possible to collect operation data of
      multiple refrigerant circuit system.
(2) If it is not possible to display all units or system in one screen, please press [System] or
[System] button in the bottom left corner in the screen to move the screen in vertical direction.
                                                                                                                        20
                                                                                                             AS0112C-P
       A. Map mode
                      Map mode
                   Detail Data Input            Centralized operation            Update map
          (Note)
          Units on the same D3-NET line will be in stand-by status (thermostat-off) for several minutes.
          Please be aware of that. After completion of this sequence, system will resume automatically.
       B. Display mode
                                                 Display mode
                    Disp. op data                  Disp. Q’ty
          [Disp. op data]
          Proceeding to [Operation data display] screen to check operation data of selected system.
          Please proceed to “5-1-5 Operation data display”
                                       (Note)
                                       Please proceed to Operation data screen after all icons turn to the
                                       color other than white.
                                                                                                                   21
                                                                                                      AS0112C-P
C. Record mode
                                                                      Record mode
           PC rec set                    PC rec start
                                                                                                            22
                                                                                                                        AS0112C-P
                                                                (3)Save changes
                                                                                                    (4) Discard changes and revert
            (5) Close
                                                                                                     to the original info
             In [Network map display] screen, by pressing [Detail Data Input] button in [Map mode], this screen
             will appear and detailed information of corresponding system can be entered.
          [Procedure]
          (1) Please select corresponding unit from the drop down list in the upper left corner. The order of indoor unit
              is the order of auto address.
          (2) Please enter each item in [2. Detail data input]. Each item should be entered based on its necessity.
           Auto address                   Automatically acquired. In [Network map display] screen, icons are listed in
           (change not allowed)           the order of this address.
           Airnet address                 Automatically acquired. Address for Airnet is displayed in case of being set.
           (change not allowed)
                                                                                                                                     23
                                                                                                          AS0112C-P
* If you hit the ENTER key when the editable items such as Install site (name), Model number, Model name,
  or Centralized address is highlighted, next (right) item will be highlighted.
(from centralized address, install site of next line will be selected)
 If you hit SHIFT+ENTER key, previous item will be highlighted.
(from install site, centralized address of previous line will be selected)
  If you double click install site (name), Model number, Model name, or Centralized address, edit window
will be popped up.
  Model name and centralized address can be selected from the candidates of drop down list. You can edit
them directly. When you finished the editing, please press OK button. Edited information will be applied. If
the centralized address was invalid, error message will appear.
* Even if the OK button is pressed, changes would not be saved to you PC. When Save button will be pressed,
changes will be saved to your PC.
                                                                                                                24
                                                                                                             AS0112C-P
(Note)
•Once you replaced control PCB, auto address of network map will change.
•If you updated map, location of detailed information will move from appropriate place because
detailed info of each unit is stored in the order of auto address. To correct this situation please re-
arrange detailed info as the procedure instructed below.
(1) After updating the map, by double-clicking install site, Model number, Model name, or Centralized
    address, detailed data of the network map before updating will be displayed in [Detail Data Input]
    window.
(2) Select information which should be overwritten, then info will be listed in the first line of the
    window. Please check and press Confirm button.
* Just by pressing the Confirm button, changes would not be finalized yet. By pressing Save button
which will be described by (3), then changes will be saved.
(3) Information entered please press [Save] button. If centralized address is invalid, error message will
appear.
(4) Discard changes and revert to the original info: information will be reverted to the original content.
(5) After finishing input, please press [Close (esc)] button to return to [Network map display] screen.
                                                                                                                   25
                                                                                                                 AS0112C-P
   (2) Digital data graph                            (4) Inspection sheet display            You can jump to the other
                                                                                             unit in the same system
                                                                                                                          26
                                                                                                         AS0112C-P
   • Per unit, 8 analog data and 8 digital data can be displayed in the graph. Please select a desired
     parameter and click it again to show. Data will be shown in the graph screen with a colored square (□)
     will appear in the far left column.
   • By clicking same data on the graph will hide it from the graph.
                                                                                                               27
                                                                                                                            AS0112C-P
(4-4) Manual
input boxes
(4-7) Switch
between outdoor
units
                                                                                                                                       28
                                                                                                      AS0112C-P
(5) By pressing [X] button in the upper right corner, return to [Operation data display] screen
                                                                                                              29
                                                                                                                         AS0112C-P
     [Procedure]
     (1) Set [1. Record interval], [2. Record stop method], [3. Record system select]
      (Note)
      Data update interval differs from model but normally it is fixed at between 1 to 5 minutes (this value
      cannot be changed by checker because it is defined by unit). So if you shorten recording interval to
      very short time such as 5 sec, same value would be recorded in multiple times.
      * Actual data updated time is displayed in present data chart in the right.
      (2) To save changes, press [OK] button. To cancel changes, press [Cancel] button to
      return to [Network map] screen.
                                                                                                                               30
                                                                                                           AS0112C-P
(3) To start periodic record to PC data drive, press [PC rec start] button in [Network map] screen. “PC
Red.” sign will be indicated in the upper left corner. Besides button will be changed to [PC rec end]
“PC Rcd.”
(4) If you need to manually stop periodic recording, press [Period. rec end] button. If you select [Auto] in
[Record end method], recording will end in the set time automatically.
(5) In case of disconnection of communication with TYPE4 Checker box, [Communicating(Error)] will be
shown. Please check connection and retry recording.
[Communicating(Error)] display
                                                                                                                 31
                                                                                                           AS0112C-P
    (Note)
    If the centralized group number is not set yet, it is necessary to set them.
    Connect TYPE4 checker box to D3-NET line and setup customer information from checker software, please
    show [Network map display] screen. With this condition, centralized operation will be possible if you set
    necessary centralized group number by indoor unit remote controller.
     In [Network map display] screen, press [Centralized operation] button in [Map mode], [Centralized
     operation] screen will appear.
Color Status
                                                                            Red          Error
                                                                            Violet   Comm. Error
                                                                            Green      Running
                                                                            Gray         Stop
      • In this screen, indoor unit which can be controlled centrally are listed as icon in the order of
        centralized group number.
      • Icon color will change based on the status
                                                                                                                 32
                                                                                                              AS0112C-P
[Procedure]
(1) Select desired indoor unit icon and execute centralize operation such as alteration of set values, etc.
                                                                                                                    33
                                                                                            AS0112C-P
        [Disp. op data]
        Showing operation data, please proceed to (3)
        [CSV data output]
        Exporting csv format data, please proceed to [6-3: CSV output]
        [Delete]
        Removing operation data
        [Back]
        Return to main menu
                                                                                                  34
                                                                                                              AS0112C-P
                                                                         Buttons
                                                                         (see below for details)
                 Button                                            Description
         <-->         Magnify        Make time scale (X-axis) of the graph smaller (short time line)
         -> <-        Minify         Make time scale (X-axis) of the graph larger (long time line)
          < --        Go back        Move timeline to backward (50% of X-axis time scale)
          -- >        Proceed        Move timeline to forward (50% of X-axis time scale)
           <-         Left           Move cursor (vertical line) to the left
           ->         Right          Move cursor (vertical line) to the right
(4) Max/Min value of analog data and error code can be searched (digital data cannot be searched).
Present value list in the right, click to highlight desired data item and press [Search] button.
                                                                                                                         35
                                                                                       AS0112C-P
(6) Inspection sheet can be created by pressing button in the bottom of this screen.
• Please refer to [5-1-5 Operation data display] for details of inspection sheet
                                                                                             36
                                                                                                           AS0112C-P
      Customer information and network map (system/line information) can be checked by recorded data. By
      this data, it is possible to check customer/customer’s VRV system, model information stored in PC.
      [Procedure]
      (1) In main menu, press [Customer data] button to proceed to [Customer selection] screen.
                                                             2. Press [OK]
           1. Select desired map
                                                                                                                 37
                                                                               AS0112C-P
                                                                                     38
                                                                                                             AS0112C-P
    To utilize recorded data by the other software such as Excel, data export to csv format is supported.
    *CSV format: comma separated value data
    [Procedure]
    (1) In main menu, press [Play] button to [Customer data selection] screen
                                                                                                                   39
                                                                                                                AS0112C-P
 (Note)
 1. CSV file will be exported 1 file per unit (both outdoor/indoor)
     For example the system with 1 outdoor unit and 8 indoor unit, 1 csv file for outdoor unit and 8 csv
     files for indoor units will be exported.
 2. If recorded period is too long to store all data in one csv file, it could be exported in multiple files.
(4) [Save As] screen. Select location to save and enter file name, then press [Save] button
                                                                                                                      40
                                                                                                              AS0112C-P
 (Note)
 •Data can be copied directly from PC folder location by Windows explorer, it is not easy to locate them so it’s
 much more convenient to use this function.
   [Procedure]
                                                      (1) In main menu, press [Data transfer] button to
                                                      proceed to [Data transfer] screen
                                                                                                                    41
                                                                                                         AS0112C-P
* If there are same name of operation data in the destination, below dialog will be shown.
           * If there are same name of customer data in the destination, below dialog will be shown.
           Meanings of each button are same as above.
                                                                                                               42
                                                                                                            AS0112C-P
     Checker software manages operation data by customer basis. Therefore customer ID is mandatory
     field to enter in customer information. If the operation data is recorded from [Record only] without
     managing data by customer information, every time VRV unit will be D3-NET initialization status and
     thermostat-OFF condition. So customer information management is highly recommended.
     (Note)
     Other than [Customer data] menu, customer information can be entered from [Record] menu.
     [Procedure]
     (1) In main menu, press [Customer data] button to proceed to [Customer selection] screen.
(2) To create a new customer, press [New customer] button to proceed to below screen.
     (3) [Customer ID] is used for distinguishing customer, please enter in alphanumerical characters.
     (4) [Customer name] is displayed in [Operation data selection] screen etc. It is highly recommended to enter.
     (5) Other items are entered based on their necessities (they are not mandatory fields).
     (6) After finishing entry, press [Save] button. Return without saving, press [Cancel] button.
                                                                                                                     43
                                                                                                               AS0112C-P
                                                        Click the top box (list) and select COM port from listed port
                                                        number. From listed COM port numbers, please select COM
                                                        port number which comes with “Silicon Labs CP210x USB to
                                                        UART Bridge” in the middle box.
Note) In case of no COM port with “Silicon Labs CP210x USB to UART Bridge”
                                                                                                                        44
                                                                                                                  AS0112C-P
It is possible to stop sending centralized control command from checker by this setting.
     Checker has a centralized operation function, it regularly transmits data as a centralized controller to the
     connected D3-NET line.
     To prohibit centralized control by this function, data transmission as centralized controller can be
     stopped by checker.
    1) It cannot be added any devices which might cause influences to D3-NET communication. In case of a lot of
    units connected to the same D3-NET line and communication is very busy, but it is necessary to capture data
    without affection to D3-NET.
    2) Under circumstance of no centralized controller is allowed to connect, but it is necessary to capture data.
    Or existing supervisor controller such as BMS controls VRV units by KRP2A or KRP4A. (see Q-101)
    [Limitations]
    If the centralized control function is prohibited, limitations listed below will apply.
                                                                                                                           45
                                                                                                               AS0112C-P
                                                                                                                     46
                                                                                    AS0112C-P
    1) Help
         Showing help (manual) screen                            Help
     2) Supported model
                                                                 PDF viewer
     3) Version info
       Software version can be checked
                                                                                          47
                                                                                                                 AS0112C-P
 [Q-101]
 Error is generated if checker is connected to the system which Wiring Adaptor for Electrical Appendices (1) or (2)
 (KRP2A or KRP4A) adapter is installed.
 [Phenomenon]
 The other supervising system (BMS) controls VRV via Wiring adapter for electrical appendices and checker is
 connected to this system, supervising system causes air conditioner error.
 [Cause]
 Wiring Adaptor for Electrical Appendices (1) or (2) (KRP2A or KRP4A) cannot coexist with the other centralized
 controllers because centralized controller’s operation command conflicts with the commands from the supervising
 system. Checker has centralized controller function, adapter sends status of centralized controller conflicted
 condition to BMS. This error itself is just a warning and does not affect operation of VRV system, but BMS system
 recognizes error status and record it in its history. Besides VRV system will be in restart stand-by (thermostat-off)
 due to connection of checker to the D3-NET line. As a result, it looks like VRV system stopped by error due to
 connection of checker.
 [Countermeasure]
 By connecting checker, error will be submit to supervising system. But VRV system itself is not affected and can be
 running without errors. After the removal of checker, alarm on supervising system will stop. In this case
 countermeasures listed below are possible to take.
1. Asking customer to ignore alarms while checker is connected (in case of short term connection).
 3.   Cut J5 wire of KRP4A adapter PCB to kill alarm related to function for duplication of centralized controller.
      *Please be aware if this wire is cut, duplication of centralized controller can no longer alerted.
                                                                                                                         48
                                                                                                            AS0112C-P
     [Q-201]
     About software update
     [Countermeasure]
     Download update software from DIL business portal site.
     https://global1d.daikin.com/business_portal/login/
     [Q-202]
     When trying to install the checker software, alert dialog is shown and installation cannot be
     executed.
       [ Windows 7 ]                                    [ Windows 10 ]
      [Cause]
      No access rights of software installation is available for your PC user account.
      [Countermeasure]
      Ask your IT administrator for software installation permission or login with administrator level password to
      your PC if you have administrator right but not logged in with administrator account.
                                                                                                                     49
                                                                                                    AS0112C-P
[Q-203]
About frequently asked error message and possible actions (communication between PC and checker)
[Error: 5-3]
    1                  Selected COM port number does not match with actual COM port which is
          Probable     connected to the checker. Default setting of COM port number is “COM1”.
          causes       If the checker is connected to the other port number, your PC cannot
                       communicate with the checker.
Measures Please change COM port number which matches with your PC COM port.
          Probable     PC COM port is already used by the other software or occupied by the other
          causes       software which did not correctly quit.
    2
                       Quit the software which is using COM port. If COM port will be still
          Measures
                       occupied, please restart Windows.
[Error: 6-1]
          Probable
                       Selected incorrect COM port number.
          causes
    1
                       Check the COM port which is connected to checker cable and change to
          Measures
                       valid COM port number from option menu of checker software.
                       Faulty connection between PC and checker.
          Probable     a. Connected to incorrect port (connector)?
          causes       b. Invalid cable is used?
    2
                       c. Faulty cable (poor contact, disconnection ,etc.)
                       Check connection status of PC communication port, connection cable
          Measures
                       condition or try another connection cable.
                                                                                                          50
                                                                                                                 AS0112C-P
      [Q-301]
      All parameters persist on same value (do not change at all)
      [Cause]
      Checker records operation data received from VRV units, but if no communication data comes, the last
      parameters which was correctly received are recorded instead of blank, - - , or 00. Thus if there is no data is
      available due to disconnected wiring or electric interference, same value (last correctly received data) is
      recorded after this point.
      [Countermeasure]
      Check and correct D3-NET wiring.
      [Q-302]
      Even if an error code is indicated on the remote controller such as L5 (inverter overcurrent), checker does not
      show the corresponding error code. There are no inverter retry (stand-by).
      [Cause]
      Normally L5 (inverter overcurrent) error immediately stops compressor, then the direct cause of L5 error
      disappear and error status will be automatically reset. Like this kind of instantaneous state error codes,
      remote controller retains the error code even the error status itself will be removed. But checker dose not
      have such a function (retaining instantaneous error code until user reset operation), so these error codes
      cannot be captured.
      [Countermeasure]
      It is not possible to make checker to do same behavior as remote controller does due to technical difficulties
      (timing of cancellation of error status differs from model/series). Please check them by the other parameters
      such as inverter current value or others.
      [Q-402]
      In map mode screen, outdoor unit icon is displayed but no operations data is shown. Besides outdoor unit
      icon remains white and would not change to the other colors.
      [Cause]
      Operation data cannot be displayed because the software cannot recognize the outdoor unit. Outdoor unit
      data format differs from model/series which requires update of checker software to collect operation data.
      Therefore if connected outdoor unit is not supported yet, checker software can recognize it as an outdoor
      unit but it cannot recognize model information and collect operation data.
      [Countermeasure]
      Software update to the version which supports connected model or later. Please refer to the supported
      model list.
                                                                                                                        51
                                                                                                       AS0112C-P
                                             Specification
 Specification list of TYPE4 Checker
                  Item                                                Spec
      Dimension                     125(W) x 85(D) x 40(H) mm
      Weight                        200g (approximately)
      Power supply                  5V DC 200mA
Operating temp/RH -10~55 deg, 95%RH or below (only except for condensation status)
52