0% found this document useful (0 votes)
177 views50 pages

C5 Installation Instructions

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views50 pages

C5 Installation Instructions

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 50

Centurion™ - C5 Series

Application Controller

Installation Manual

00-02-0963
2022-08-29
Section 50
BEFORE BEGINNING INSTALLATION OF THIS FW MURPHY
PRODUCT:

 Please read the following information before installing the Centurion


controller. This installation information is intended for Centurion
controller only.
 Visually inspect the product for any damage during shipping.
 Before proceeding please visit our website and review our support
documentation including Wiring the Murphy Way.
www.fwmurphy.com/uploaded/WIR_Murphy_Way.pdf
 Disconnect all power and be sure machine is inoperative before
beginning installation.
 Installation is to be done only by a qualified technician of the
Responsible Body.
 Observe all Warnings and Cautions at each section in these
instructions.
 Device shall be wired in accordance with NEC, CEC or other local
code, as applicable.
 Please contact FW Murphy immediately if you have any questions.
For Class I, Division 2:

THIS EQUIPMENT IS AN OPEN-TYPE DEVICE AND IS MEANT TO BE INSTALLED IN AN


ENCLOSURE SUITABLE FOR THE ENVIRONMENT SUCH THAT THE EQUIPMENT IS
ONLY ACCESSIBLE WITH THE USE OF A TOOL.

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C


AND D OR NON-HAZARDOUS LOCATIONS ONLY.

WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS


POWER HAS BEEN REMOVED OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING – EXPLOSION HAZARD – DO NOT REPLACE BATTERIES UNLESS THE AREA


IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.

TEMPERATURE CODE OF T4 FOR ALL MODELS.

PROVIDES NONINCENDIVE FIELD WIRING OUTPUTS/INPUTS WHEN WIRED


ACCORDING TO DRAWINGS 50-08-0102 (C5-1-X, C5-2-X) and 50-08-0093 (MV-5-X).

For AEX/EX Class I, Zone 2:

THE EQUIPMENT SHALL ONLY BE USED IN AN AREA OF POLLUTION DEGREE 2.

THE EQUIPMENT SHALL BE INSTALLED COMPLETELY WITHIN AN ENCLOSURE THAT


PROVIDES A MINIMUM INGRESS PROTECTION OF IP 54 IN ACCORDANCE WITH
UL60079-0 AND ONLY ACCESSIBLE BY THE USE OF A TOOL.

THE WIRE SIZE, TORQUE RATING OF 12-24 AWG, 0.37-0.44 ft. lbs. (0.4-0.5 Nm), AND
SUITABLE SUPPLY WIRE TEMPERATURE RATING OF 97ºC MINIMUM SHALL BE
PROVIDED FOR THE INPUT POWER TERMINAL BLOCK.

ALL MARKING INFORMATION EXCEPT FOR SERIAL NUMBER/DATE CODES SHALL BE


REPEATED.

PROVIDES NONINCENDIVE FIELD WIRING OUTPUTS/INPUTS WHEN WIRED


ACCORDING TO DRAWINGS 50-08-0102 (C5-1-X, C5-2-X) and 50-08-0093 (MV-5-X).

SPECIAL CONDITIONS FOR USE IECEx/ATEX Zone 2:

THE EQUIPMENT SHALL ONLY BE USED IN AN AREA OF NOT MORE THAN POLLUTION
DEGREE 2, AS DEFINED IN IEC/EN 60664-1.

THE EQUIPMENT SHALL BE INSTALLED IN AN ENCLOSURE THAT PROVIDES A DEGREE


OF PROTECTION NOT LESS THAN IP 54 IN ACCORDANCE WITH IEC/EN 60079-0 AND
ONLY ACCESSIBLE BY THE USE OF A TOOL.
THIS PAGE IS INTENTIONALY LEFT BLANK
Table of Contents
Installation Manual .....................................................................................................................1

Operation Manual Location ......................................................................................................1

Centurion™ C5 Controller Kit and Tools ................................................................................1

Inspecting Package Contents.......................................................................................1


Tools Needed ...............................................................................................................1
Installation ...................................................................................................................................2

Enclosure / Environmental Requirements ....................................................................2


M-VIEW ® Display Dimensions......................................................................................3
Install the Display .........................................................................................................4
Install the Main Module Controller ................................................................................7
Wire Connections.......................................................................................................................8

Wire Diagram — MV-5-C Display .................................................................................8


Entity Parameters — MV-5-C Display ..........................................................................9
Wire Diagram — MV-7T Display ................................................................................10
Wire Diagram — MV-10T Display ..............................................................................10
Wire Diagram — MV-12T Display ..............................................................................10
Wire Diagram — Centurion C5 Controller ..................................................................11
Entity Parameters — Centurion C5 Controller............................................................12
Power Supply and Grounding ....................................................................................16
General Wiring Recommendation ..............................................................................16
Terminal Keys, Blocks and Headers ..........................................................................19
Recommended Wiring Practice for Centurion C5 Terminal Blocks ............................20
Thermocouple / RTD Inputs (Pins 1 – 16b) ................................................................21
Analog Inputs (Pins 18 – 23b) ....................................................................................22
Digital Inputs (Pins 30 – 61b) .....................................................................................23
Power (Pins 62 – 63)..................................................................................................24
Magnetic Pickup, MPU (Pins 62b – 65)......................................................................25
Analog Outputs (Pins 66 – 659b) ...............................................................................25
Relay Outputs (Pins 70 – 81) .....................................................................................26
FET DC+ (Pins 83 – 89) .............................................................................................27
FET DC– (Pins 90 – 93b) ...........................................................................................28
RS485 (Pins 94 – 101) ...............................................................................................29
RS232 (Pins 96 – 105) ...............................................................................................31
CAN (Pins 106 – 111) ................................................................................................32
Modbus Address ........................................................................................................33
Ethernet......................................................................................................................34
USB 1 Host ................................................................................................................36
USB 2 Device .............................................................................................................37
Wi-Fi (C5-1)................................................................................................................38
Accessories ..............................................................................................................................39

Replacement Parts and Assemblies ..........................................................................39


Software Configuration Tool .......................................................................................39
Specifications ...........................................................................................................................40

C5 Series Main I/O Module ........................................................................................40


M-VIEW ® Monochrome LCD Display .........................................................................41
M-VIEW ® Touch Series Displays ...............................................................................42
Installation Manual
This manual applies to Centurion C5-1 and C5-2 Application Controllers. C5 and C5 Series
refers to both application controllers.

Operation Manual Location


After installation, please review the Centurion C5 Operations Manual prior to placing the
controller into service. In order to access the Centurion C5 Operation Manual, please visit the
product page to download or print a copy located under the literature tab.

www.fwmurphy.com/Centurion_C5

Centurion™ C5 Controller Kit and Tools


The following instructions will guide you through installing the Centurion C5 controller.

Inspecting Package Contents


Before attempting to install the product, ensure all parts are accounted for and inspect each
item for damage (which sometimes occurs during shipping).

Centurion C5 Controller kit includes:


 Centurion C5 Controller
 Centurion C5 Installation Manual (this document) p/n 00-02-0963.

Tools Needed
 Use a 1/4 in. drill bit to make the approximately sized 0.250 in. mounting holes.

 Use a 5/16 in. nut driver to secure star nuts.

 Use a cutout tool (i.e. saw, punch press or cutting wheel) to create the mounting hole
according to the dimensions.

Section 50 00-02-0963
2022-08-29 -1-
Installation
Enclosure / Environmental Requirements
The Centurion Main Module and all M-VIEW displays must be mounted in an enclosure
meeting the requirements of IP54 or greater according to the intended use and environmental
conditions and in accordance with UL standards and accessible only by use of a tool.

NOTE: IP requirement is ONLY for North America and IECEx/ATEX


Zones UL 60079, IEC/EN 60079-0

- Operating temperature -40° to 85°C (-40° to 185°F)


- Altitudes up to 2,000m (6,500ft) (air pressure 0.8/1.1 bar)
- Air with normal oxygen content (typical 21% v/v)
- Maximum relative humidity 95% non-condensing for temperatures up to 85°C (185°F)
- Temperature Class T4
- ic: intrinsic safety (for EPL Gc)
- Increased safety (for EPL Gc)

Section 50 00-02-0963
2022-08-29 -2-
M-VIEW® Display Dimensions

Section 50 00-02-0963
2022-08-29 -3-
Install the Display
Prepare the Panel – All M-VIEW Models
1. Determine the location of the display on the customer-supplied flat or enclosed panel.
Plan the display mounting for easy wiring and access.
2. Measure the specified measurements shown in the diagram of the screen side. Doing
so will ensure there is adequate real estate to provide clearance for the front edges of
the housing to mount flush against the outside surface of your panel. The cut-out
measurement will be smaller.
3. Use the diagram to measure and mark the specified dimensions shown in the panel cut-
out diagram. This is your cut-out measurement.
4. Cut the hole in the panel following your marks matching the diagram as a guideline.
NOTE: Check for clearance fit of controller in the cutout before proceeding
with drilling mounting holes.

5. If applicable, drill holes where indicated for the mounting screws.


MV-5-C Display
The Centurion display can be mounted in the same hole cutouts as the Centurion C4 display.
Eight studs and star nuts secure the display bezel to the mounting surface.

Backside of MV-5-C showing gasket, studs and tightening sequence

1. Insert the display backside first, from the front side of the panel.
2. Ensure that there is adequate clearance for the edges of the display housing and the
back of the case is flush against the outside surface of your panel.
3. Install eight star nuts to the studs from the backside of the panel.
4. Tighten the 5/16” star nuts in sequence to 9 in. lbs. (1 Nm). Do not overtighten.

Section 50 00-02-0963
2022-08-29 -4-
MV-7T, MV-10T and MV12T Displays
Through-Panel Mount
Once the cutout is prepared in the panel, the M-VIEW Touch can be mounted in the cutout and
secured with mounting clips.

1. An O-ring is provided to enable sealing. Inspect the O-ring on the display and ensure it
is free from any nicks and properly secured in position.

2. Insert the M-VIEW Touch display back side first, from the front side of the panel.
3. Ensure that there is adequate clearance for the edges of the display housing and the
back of the case is flush against the outside surface of your panel.
4. Install the mounting clips with screws from the back side of the panel to the display
housing and panel.
5. Tighten the mounting clips to 60 in. lbs. (10.5 Nm) evenly for uniform gasket
compression. Do not overtighten.

6. Ensure there is a good seal between the controller and the mounting panel.

Section 50 00-02-0963
2022-08-29 -5-
Stand Mount
Four mount-tapped screw holes (M4 x 0.7, 5 mm deep) are located on the rear of the panels
for stand or wall mounting.

MV-7T MV-12T with stand mount

Tapped Screw Hole Locations

Section 50 00-02-0963
2022-08-29 -6-
Install the Main Module Controller
The Centurion C5 controller can be mounted vertically or horizontally on a standard DIN rail.

Four clamp-type feet along the bottom of the controller attach to the DIN rail; however, rail
stops are recommended to prevent sliding.

Section 50 00-02-0963
2022-08-29 -7-
Wire Connections
Wire Diagram — MV-5-C Display

Section 50 00-02-0963
2022-08-29 -8-
Entity Parameters — MV-5-C Display

RS232 J6
Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J6
RS232
±15.0 ±60 - 22.2 2.99 ±30 ±60 - 0 0.001
Transmit/Recieve
Pins 1, 2, 3, 4
Pin
Ground Reference Non-ic
5

RS485 J11
Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
Pins
±5.0 ±60 - 22.2 999.9 ±12.0 ±60 - 0 0.01
1, 2
Pin
Ground Reference Non-ic
3

Pins ±5.0 ±60 - 22.2 999.9 ±12.0 ±60 - 0 0.01


4, 5
DC- Ground Pin

USB
Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J7
Type A 5.04 ±25 - 128 889.8 ±5 ±500 - 0 110.2
Pin 1
J7
Ground Non-ic
Pin 4
Pin
Ground Non-ic
Tab1, Tab2
J8
Type B 5.04 ±25 - 128 889.8 ±5 ±500 - 0 110.2
Pin 1
J8
Ground Non-ic
Pin 4
J8
Shield Ground Reference Non-ic
Pins 5, 6

CAN Per Channel


Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[pF]
J9
Pins 4.5 100 - 8 999.9 ±24 100 - 51 267
1, 2, 3, 4
5 Ground Reference Non-ic

Ethernet Per Port


Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J10 3.3 ±61.5 - 21.2 999.9 3.3 ±60 - 0 0.04

Section 50 00-02-0963
2022-08-29 -9-
Wire Diagram — MV-7T Display

Wire Diagram — MV-10T Display

Wire Diagram — MV-12T Display

Section 50 00-02-0963
2022-08-29 - 10 -
Wire Diagram — Centurion C5 Controller
When applicable, shielded cables may be used on any I/O connection shown. If shielded cable
is utilized, only one end of the shielded cable should be grounded.

Section 50 00-02-0963
2022-08-29 - 11 -
Entity Parameters — Centurion C5 Controller
Inputs/Outputs are only for connections for devices located in Class I, Division 2, Groups A, B, C, D or
Class I, Zone 2, Group IIC Hazardous location or ordinary Nonhazardous location or IECEx/ATEX Zone
2, Group IIC with Non-incendive. Simple Apparatus, Intrinsically Safe or approved device with entity
concept parameters (Uo, Io, Po, Co, Lo, Ui, Ii, Pi, Ci, Li) appropriate for connection to associated
apparatus with entity concept parameters as listed in the tables.
NOTES:
1. The output current of this associated apparatus is limited by a resistor such that the output
voltage-current plot is a straight line drawn between open-circuit voltage and short-circuit
current. The entity concept allows interconnection of intrinsically safe apparatus with associated
apparatus not specifically examined in combination as a system when the approved vales of
Voc (or Uo) and Isc (or Io) for the associated apparatus are less than or equal to Vmax (Ui) and
Imax (Ii) for the intrinsically safe apparatus. Capacitance and inductance of the field wiring from
the intrinsically safe equipment to the associated apparatus shall be calculated and must be
included in the system calculations. Cable capacitance, Ccable, plus intrinsically safe equipment
capacitance, Ci must be less than the marked capacitance, Ca (or Co), shown on any
associated apparatus used. The same applies for inductance (Lcable, Li and La or Lo,
respectively). Where the cable capacitance and inductance per foot are not known, the following
values shall be used: Ccable = 60 pF/ft., Lcable = 0.2 μH/ft.
Nonhazardous Location
or
Hazardous (Classified) Location
Hazardous (Classified) Location
Class I, Div 2 Grps A, B, C and D
Class I, Div 2 Grps A, B, C and D
Class I, Zone 2, Group IIC
Class I, Zone 2, Group IIC
IECEx/ATEX Zone 2, Group IIC
IECEx/ATEX Zone 2, Group IIC

Ui ≥ Uo; Ii ≥ Io; Co ≥ Ci + Ccable; Lo ≥ Li + Lcable

2. This associated apparatus may also be connected to non-incendive or simple apparatus as


defined in Article 504.2 and installed and temperature classified in accordance with Article
504.10 (B) of the National Electrical Code (ANSI/NFPA 70) or other local codes, as applicable.
Examples of simple apparatus are general-purpose contact/switch, thermocouple and RTD.

Section 50 00-02-0963
2022-08-29 - 12 -
3. For intrinsically safe devices selected associated apparatus must be third-party listed as
providing intrinsically safe circuits for the application or have Voc or Vt not exceeding Vmax (or
Uo not exceeding Ui), Isc or It not exceeding Imax (or Io not exceeding Ii), and the Po of the
associated apparatus must be less than or equal to the Pmax or Pi of the intrinsically safe
equipment. Examples of “simple apparatus” are general-purpose contact/switch, thermocouple
and RTD.
4. For intrinsically safe devices selected associated apparatus must be third party listed as
providing intrinsically safe circuits for application, and have Voc or Vt not exceeding Vmax (or
Uo not exceeding Ui), Isc or It not exceeding Imax (or Io not exceeding Ii), and the Po of the
associated apparatus must be less than or equal to the Pmax or Pi of the intrinsically safe
equipment.
5. Where multiple circuits extend from the same piece of associated apparatus, they must be
installed in separate cables or in one cable having suitable insulation. Refer to Article 504.30(B)
of the National Electrical Code (ANSI/NFPA 70) and Instrument Society of America
Recommended Practice ISA RP12.6 for installing intrinsically safe equipment.
6. Intrinsically safe circuits must be wired and separated in accordance with Article 504.20 of the
National Electrical Code (ANSI/NFPA 70) or other local codes, as applicable.
7. This associated apparatus has not been evaluated for use in combination with another
associated apparatus.
8. Control equipment must not use or generate more than 250 V rms or dc with respect to earth.
9. For installations in which both the Ci and Li of the intrinsically safe apparatus exceeds 1% of the
Co and Lo parameters of the associated apparatus (excluding the cable), then 50% of Co and
Lo parameters are applicable and shall not be exceeded.
10. This equipment is suitable for use in non-hazardous locations and hazardous locations Zone 2,
Group IIC T4 or Class I, Division 2, Groups A, B, C, D Temperature Code T4 Installations.
11. If an inductive load does not have an internal flyback diode, it is recommended you install a 1A
600V diode in parallel with the load (1N4005 – EC P/N 36-16-1002).
12. Use two conductor cable with foil shield and drain wire for MPU input.
13. This equipment must be mounted in an enclosure meeting the requirements of IP54 or greater
according to the intended use and environmental conditions.
14. Installation is to be done only by a qualified technician of the responsible body.
15. Device shall be wired in accordance with NEC, CEC or other local code, as applicable.

WARNING:
EXPLOSION HAZARD - DO NOT DISCONNECT THE EQUIPMENT OR ACTUATE SWITCHES
WHEN THE EQUIPMENT IS ENERGIZED AND AN EXPLOSIVE ATMOSPHERE IS PRESENT.
EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

Section 50 00-02-0963
2022-08-29 - 13 -
Entity Parameters — Centurion C5 Controller (continued)

Thermocouple/RTD Inputs (Per Pin)


Designation Uo[V] Io[mA] Po[mW] Lo[H] Co[µF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J1
Pins
2, 4, 6, 8, 4.4 1.0 4.4 80 999.9 30.0 17.0 - 0 0.1
10, 12, 14,
16
J1
Pins
1, 2b, 3, 4b,
5, 6b, 7, 8b, 4.4 1.0 4.4 80 995.1 30.0 17.0 - 0.022 4.9
9, 10b, 11,
12b, 13,
14b, 15, 16b

Analog Inputs (Per Pin)


Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[mF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J2-J3
AI1-AI8
- - - - - 10.3 51.6 - 0 0.1
Pins
18-25
J3
AI9-AI12
4.4 1.0 - 80 995.1 10.3 51.6 - 0.022 4.9
Pins
26-29
J2-J3
AB+
- - - - - - - - - -
Pins
18b-29b
B- Ground Pin

Digital Inputs (Per Pin)


Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J4-J6
DI1-DI32
30 5.2 - 2.95 0.120 30 17 - 0 0.1
Pins
30-31
J4-J6
B+1 to B+32
30 12.66 - 500 0.120 - - - 0 0.1
Pins
30b-61b

Analog Outputs(Per Pin)


Designation Uo[mV] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J8
Pins 30 38.5 - 54 0.120 - - - 0 0.1
66-69
J8
Pins Analog Output Ground
66b-69b

Section 50 00-02-0963
2022-08-29 - 14 -
Entity Parameters — Centurion C5 Controller (continued)

RS485/RS232
Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J12
RS485
Pins ±5.0 ±60 - 22.2 999.9 ±12.0 ±60 - 0 0.01
94, 95
100, 101
J12
Pins Shield Connection Ground
S1, S2
J12
RS232
Shield Reference Ground
Pins
96,102
J12
RS232
Transmit/Receive
±15.0 ±60 - 22.2 2.99 ±30 ±60 - 0 0.001
Pins
97-99
103-105

CAN Per Channel


Designation Uo[V] Io[mA] Po[mW] Lo[H] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[pF]
J13
Pins ±4.5 ±5 - 3.2 999.9 ±24 100 - 0 267
106-111

USB
Designation Uo[V] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J16
±5.19 ±25 - 128 889.8 ±5 ±500 - 0 110.2
Type A
J17
±3.3 ±25 - 128 999.8 ±5 ±500 - 0 0.200
Type B

Ethernet Per Port


Designation Uo[mV] Io[mA] Po[mW] Lo[mH] Co[uF] Ui[V] Ii[mA] Pi[mW] Li[mH] Ci[uF]
J14-J15 3.3 ±61.5 - 21.2 999.9 3.3 ±60 - 0 0.1

Section 50 00-02-0963
2022-08-29 - 15 -
Power Supply and Grounding
Please refer to the Wire Diagram — Centurion C5 Controller for grounding requirements.

NOTE: Follow the instructions for protective earthing.

General Wiring Recommendation


It is essential that the following practices be adhered to.

Terminals for Safe Circuits


Terminals for intrinsically safe circuits shall be separated from terminals for non-intrinsically
safe circuits by one or more of the methods given. There methods of separation shall also be
applied where intrinsic safety can be impaired by external wiring which, if disconnected from
the terminal, can come in contact with conductors or components.

When separation is accomplished by distance then the clearance between bare conducting
parts and terminals shall be at least 50 mm.

Care should be exercised in the layout of terminals and in the wiring method used so that
contact between circuits is unlikely if a wire becomes dislodged.

Section 50 00-02-0963
2022-08-29 - 16 -
Terminal Separation
When separation is accomplished by locating terminals for intrinsically safe and non-
intrinsically safe circuits in separate enclosures or by use of either an insulating partition or an
earthed metal partition between terminals with common cover, the following applies:

 Partitions used to separate terminals shall be within 1.5 mm of the enclosure walls or
alternatively shall provide a minimum distance of 50 mm between bare conduction parts
of terminals when measured in any direction around the partition.
 Metal partitions shall be earthed and shall have sufficient strength and rigidity to ensure
that they are not likely to be damaged during field wiring. Such partitions shall be at
least 0.45 mm thick or shall conform to 10.6.3 of Standard 60079-11 if of lesser
thickness. In addition, metal partitions shall have sufficient current-carrying capacity to
prevent burn-through or loss of earth connection under fault conditions.
 Non-metallic insulating partitions shall have an appropriate CTI, sufficient thickness and
shall be so supported that they cannot readily be deformed in a manner that would
defeat their purpose. Such partitions shall be at least 0.9 mm thick or shall conform to
10.6.3 of Standard 60079-11 if of lesser thickness.
The clearances and creepage distances between the bare conducting parts of terminals of
separate intrinsically safe circuits and to earthed or potential-free conducting parts shall be
equal to 0.8 mm (for 32V “ic” clearance).

Where separate intrinsically safe circuits are being considered, the clearance between bare
conducting parts of external connection facilities shall meet the following:

 At least 6 mm between the separate intrinsically safe circuits.


 At least 3 mm from earthed parts, if connection has not been considered in the safety
analysis.

Section 50 00-02-0963
2022-08-29 - 17 -
Terminal Separation Schematic

Callout Description
1 Chassis
2 Load
3 Non-intrinsically safe circuits defined by Um
4 Part of intrinsically safe circuit not itself intrinsically safe
5 Intrinsically safe circuit
6 Dimensions of separation in the apparatus
7 Dimensions to which general industrial standards are applicable
8 Dimensions to separation in the apparatus
Dimensions to 6.2.1 for output terminals between separate intrinsically safe circuits
9
and between intrinsically safe to non intrinsically safe circuits
10 Protective components as applicable in accordance with 8.9

Section 50 00-02-0963
2022-08-29 - 18 -
Terminal Keys, Blocks and Headers
Some keys on the terminal block are visible by the raised area and color, while others may
only have the raised area. This is an example of the keys on four terminal blocks.

Key raised and color Key raised no color

IMPORTANT: Never align the Terminal keys, doing so will block proper mating of the
terminal block to header.
Terminal blocks and headers are equipped with blocking-type keys. When connecting, Do Not
align the key on the terminal block with the key on the header. Doing so will block proper
mating of the terminals. This example shows the correct and incorrect connection.

Correct Incorrect

Correct Incorrect

Section 50 00-02-0963
2022-08-29 - 19 -
Recommended Wiring Practice for Centurion C5 Terminal Blocks
NOTE: The terminal block must be removed from the headers on the
control and any expansion modules before attempting any maintenance
on the wired system or any job requiring a hot work permit. Please ensure
that the work area is non-hazardous before removing or installing any
terminal block. The system should also be powered off in jobs involving
hot work permits, and any such instructions established by safety
standards at the job site must be complied with at all times.
Use a wire size between 12 AWG (max.) and 24 AWG (min.) to connect to the terminal strip
connector. Strip the insulation back 9/32 inches and twist the exposed wires tightly together.
Insert the exposed wire completely into the terminal strip and securely tighten the clamping
screw. Wires must be in good condition or replaced with new wires. When running wires, take
care not to damage the insulation and take precautions against later damage from vibration,
abrasion or liquids in conduits. An explosion-proof conduit is not required; however, wires
should be protected from damage by running them in a protective conduit or in sheaths where
appropriate.
Pitch 0.200 in. [5.08mm]
0.37 - 0.44 ft. lbs
Screw Torque
[0.5 – 0.6 Nm]
Stripping Length 9/32 in. (min.) [7 mm]
Wire Gauge 24 – 12 AWG/kcmil
Nominal voltage UN 300 V
Nominal current IN 10 A
Conductor cross section solid or stranded 0.2 – 2.5 mm2
Conductor cross section stranded, with ferrule with or without plastic sleeve 0.25 – 2.5 mm2
2 conductors with same cross section, solid 0.2 – 1 mm2
2 conductors with same cross section, stranded 0.2 – 1.5 mm2
2 conductors with same cross section, stranded, ferrules without plastic sleeve 0.25 – 1 mm2
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve 0.5 – 1.5 mm2

Section 50 00-02-0963
2022-08-29 - 20 -
Thermocouple / RTD Inputs (Pins 1 – 16b)
The Centurion is equipped with 8 two-wire thermocouple and /or three-wire RTD inputs.
Thermocouples are wired using cover artwork labeled as + and -, such as 1+ and 1-.
Thermocouple terminals can be seen labeled as 1 and 2 for TC 1 channel and 3 and 4 for TC
2 channel and so on.
When RTD is selected for the channel, 3 terminals are required. RTDs are wired using cover
artwork labeled with the same + and - but also includes an additional - (minus) for the sense
lead.
RTDs terminals can be seen labeled as 1, 2, 2b for the first channel and 3, 4, 4b for the next
channel and so on.
NOTE: This wiring differs from the MX4-R2 module wiring of RTDs.
Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: These circuits are not required to be in conduit if all the


requirements for ic protection are met and Authority Having Jurisdiction
(AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 21 -
Analog Inputs (Pins 18 – 23b)
The Centurion is equipped with 12 analog inputs marked 18 through 23b. Analog inputs 9
through 12 will supply 1mA for connection to resistive senders. 0 to 5Vdc or 4 to 20 mA.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: These circuits are not required to be in conduit if all the


requirements for ic protection are met and Authority Having Jurisdiction
(AHJ) allows.

Devices that are self-powered, 4-wire devices, such as flowmeters and VFD drives, do not
receive power from the panel and offer a pure current loop.

Section 50 00-02-0963
2022-08-29 - 22 -
Digital Inputs (Pins 30 – 61b)
The Centurion is equipped with 32 digital inputs marked 30 through 61 for the input and 30b
through 61b for ic protected power to loop through the external switch back to the input.
Alternately the external switch may use B+ or B- to activate the digital input. An LED lights
when the digital input is active. Inputs 31 and 32 can alternately be used as pulse counters.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: This associated apparatus may also be connected to non-


incendive or simple apparatus as defined in Article 504.2 and installed and
temperature classified in accordance with Article 504.10(B) of the National
Electrical Code (ANSI/NFPA 70), or other local codes, as applicable.
Examples of “simple apparatus” are general-purpose contact/switch,
thermocouples and RTD.

NOTE: These circuits are not required to be in conduit if all the


requirements for ic protection are met and Authority Having Jurisdiction
(AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 23 -
Power (Pins 62 – 63)
The 10-30 VDC power for the Centurion C5 is applied to the power supply terminals marked
62 B+ and 63 B−. An external 10 amp replaceable fuse protects the system from over-
currents. The power LED lights when power is applied to the system. Please refer the section
Power Supply and Grounding for illustrations.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: Run power directly from battery posts to controller power


terminals when battery is the power supply.
Maximum power ratings based on all I/O operating in the ON position with
10V supply. Typical based on 24V supply.

Section 50 00-02-0963
2022-08-29 - 24 -
Magnetic Pickup, MPU (Pins 62b – 65)
The MPU for the Centurion is applied to the magnetic pickup terminals marked 64 MPU- and
65 MPU+, MPU 5-40Vrms 30-10 kHZ. If used, the foil shield and drain wire of the cable
assembly may be terminated at 62b- or 63b-. The MPU sends the pulses to the controller,
which calculates the engine speed.
FW Murphy recommends using 00031022 Magnetic Pickup 4 in. Length and 00031023
Magnetic Pickup Cable 50 ft.
Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: The MPU input requires a minimum signal of 2 Vrms when


connected.

Analog Outputs (Pins 66 – 659b)


The Centurion is equipped with four 2-wire current transmitters for controlling various
processes. The supply voltage and measuring currents are supplied by the Centurion over the
same two wires. These transmitters are used to convert various process signals representing
flow, speed, position, level, temperature, pressure, etc., to 4-20mA DC for the purpose of
transmitting the signal over some distance with little or no loss of signal.
Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: The Centurion provides all operating power (~B+) to the


transmitter and receiver and any other loop components.
An important aspect of building a current loop system is avoiding ground
loops by wiring the return signal to the associate B- terminal.
These circuits are not required to be in conduit if all the requirements for ic
protection are met and Authority Having Jurisdiction (AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 25 -
Relay Outputs (Pins 70 – 81)
The Centurion is equipped with four SPDT (1 Form C) relays with 5A 30Vdc dry contacts. The
four relay contacts are marked 70 NO1 71 C1 72 NC1; 73 NO2 74 C2 75 NC2; 76 NO3 77 C3
78 NC3; and 79 NO4 80 C4 81 NC4. An LED lights when the relay is active.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: If an inductive load does not have an internal flyback diode, it is


recommended you install a 1A 600V PIV diode in parallel with the load.
(1N4005 – EC P/N 36-16-1002)
To ground ignition use pilot relay with 25 Ω 3 W series resistor to ground.
Interposing relays are recommended to interface with end devices that
require high current ratings or alternative voltage supplies.
Consult General Cautions for Solid-State Devices for best practices when
connecting to external inductive load devices such as relays or solenoids.
www.fwmurphy.com/other-support-resources/general-cautions-solid-state-
devices

Section 50 00-02-0963
2022-08-29 - 26 -
FET DC+ (Pins 83 – 89)
The Centurion is equipped with four High Side 100 mΩ max Switches. The four switches are
marked 82-83; 84-85; 86-87 and 88-89. An LED lights when the switch is active.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: If an inductive load does not have an internal flyback diode, it is


recommended you install a 1A 600V PIV diode in parallel with the load.
(1N4005 – EC P/N 36-16-1002)
To ground ignition, use pilot relay with 25 Ω 3 W series resistor to ground.
Interposing relays are recommended to interface with end devices that
require high current ratings or alternative voltage supplies.
Consult General Cautions for Solid-State Devices for best practices when
connecting to external inductive load devices such as relays or solenoids.
www.fwmurphy.com/other-support-resources/general-cautions-solid-state-
devices

Section 50 00-02-0963
2022-08-29 - 27 -
FET DC– (Pins 90 – 93b)
The Centurion is equipped with two Low Side 250 mΩ max Switches. The two switches are
marked 90-91 and 92-93. There are also two terminals, 92b- and 93b-, for shield termination.
The LED lights when the switch is active.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: If an inductive load does not have an internal flyback diode, it is


recommend you install a 1A 600V PIV diode in parallel with the load.
(1N4005 – EC P/N 36-16-1002)
To ground ignition use pilot relay with 25 Ω 3 W series resistor to ground.
Interposing relays are recommended to interface with end devices that
require high current ratings or alternative voltage supplies.
Consult General Cautions for Solid-State Devices for best practices when
connecting to external inductive load devices such as relays or solenoids.
www.fwmurphy.com/other-support-resources/general-cautions-solid-state-
devices

Section 50 00-02-0963
2022-08-29 - 28 -
RS485 (Pins 94 – 101)
The Centurion is equipped with two RS485 communications ports. The ports are marked 94 A1
95 B1 and 100 A2 101 B2 S2. There are also two terminals, S1 SHD1 and S2 SHD2, for shield
termination. The TX LED lights when the port is transmitting. The RX LED lights when the port
is receiving.
The recommended arrangement of the wires is as a connected series of point-to-point
(multidropped) nodes, i.e. a line or bus, not a star, ring or multiply connected network.

Section 50 00-02-0963
2022-08-29 - 29 -
Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: A is the non-inverting pin and should have a single pull-up


physically placed anywhere on the network. B is the inverting pin and
should have a single pull-down physically placed anywhere on the
network.
These circuits are not required to be in conduit if all the requirements for ic
protection are met and Authority Having Jurisdiction (AHJ) allows.
Consult RS-485 the Murphy Way for information on best practices for
connecting and communicating on RS-485.
www.fwmurphy.com/uploaded/documents/pdfs/rs-485murphyway.pdf

Section 50 00-02-0963
2022-08-29 - 30 -
RS232 (Pins 96 – 105)
The Centurion is equipped with two RS232 communications ports. The ports are marked 96
GND1; 97 TX1; 98 RX1; 99 DTR1 and 102 GND2; 103 TX2; 104 RX2; 105 DTR2. There are
also two terminals, NC and NC, that may be left unconnected or for shield termination. The
LED lights when the port is active transmitting and when the port is active receiving.
Because both ends of the RS-232 circuit depend on the ground pin being zero volts, problems
will occur where the voltage between the ground pin on one end and the ground pin on the
other is not zero. This may also cause a hazardous ground loop. Use of a common ground
limits RS-232 to applications with relatively short cables. If the two devices are far enough
apart or on separate power systems, the local ground connections at either end of the cable
will have differing voltages; this difference will reduce the noise margin of the signals.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: These circuits are not required to be in conduit if all the


requirements for ic protection are met and Authority Having Jurisdiction
(AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 31 -
CAN (Pins 106 – 111)
The Centurion is equipped with two CAN communications ports. The terminals marked 106
HI1; 107 LO1 and 109 HI2; 110 LO2. There are also two terminals, 108 SHD1 and 111 SHD2
that may be used for shield termination. The LED lights when the port is active transmitting and
when the port is active receiving.
The recommended arrangement of the wires is as a connected series of point-to-point
(multidropped) nodes, i.e. a line or bus, not a star, ring or multiply connected network. It is
recommended to use CAN bus Cable J1939/11 SAE Shielded, twisted pair, with 120 Ω
characteristic impedance. Install a 120 Ω terminating resistor (software selectable on the
Centurion) on the physical first and last node of the CAN network. All nodes must share a
common DC ground.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

NOTE: These circuits are not required to be in conduit if all the


requirements for ic protection are met and Authority Having Jurisdiction
(AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 32 -
Modbus Address
With the Modbus RTU Server Address Configuration, the operator may assign a unique
Modbus address to each controller (server) unit that may be in the system. This allows the
client controller to differentiate between the modules. For example, to name the controller
address 21, enable the switches labeled SW1: 1, 4, and 16 (1 + 4 +16 = 21).

NOTE: The subsequent address (Address + 1) is also reserved by


Centurion, and must not be used by any other device on the Modbus
network, or communication failures to devices using that address will
occur due to this conflict. Counting by 2's is necessary for additional
Centurion controllers present in the system.

C5-1 Shown

NOTE: Typically, this configuration is set to (1) by the factory.

Section 50 00-02-0963
2022-08-29 - 33 -
Ethernet

WARNING: Explosion hazard – Do not disconnect the Ethernet port unless the
power has been switched off or the area is known to be non-hazardous.

The Centurion is equipped with two Ethernet communications ports. The ports are marked
Ethernet 1 and Ethernet 2. An LED lights when the port is active transmitting or receiving a
message, and an LED lights to indicate Network and Module status.

An 8P8C modular connector (often called RJ45) is commonly used on Cat 5 cables in Ethernet networks.

Twisted-pair Ethernet standards are such that the majority of cables can be wired straight-
through (pin 1 to pin 1, pin 2 to pin 2 and so on), but others may need to be wired in the
crossover form (receive to transmit and transmit to receive). The Centurion can automatically
detect another computer connected with a straight-through cable and then automatically
introduce the required crossover, if needed with no intervention by the installer. 10BASE-T and
100BASE-TX only require two pairs (pins 1-2, 3-6) to operate. Since Category 5 cable has four
pairs, the spare pairs (pins 4–5, 7–8) in 10- and 100-Mbit/s configurations are not used.

Section 50 00-02-0963
2022-08-29 - 34 -
The Centurion uses auto negotiation, an Ethernet procedure by which two connected devices
choose common transmission parameters, such as speed, duplex mode and flow control. In
this process, the connected devices first share their capabilities regarding these parameters
and then choose the highest performance transmission mode they both support. The
Centurion supports 10 and 100 Mbit/s over two-pair Cat5 or better cable.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

C5-1 Shown

NOTE: These circuits are not required to be in conduit if all requirements


for ic protection are met and Authority Having Jurisdiction (AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 35 -
USB 1 Host

WARNING: Explosion hazard – Do not disconnect the USB port unless the power
has been switched off or the area is known to be non-hazardous.

The Centurion is equipped with a USB 2.0 standard communications port. The port is marked
USB 1.

The USB 2.0 standard-A type of USB plug is a flattened rectangle that inserts into a receptacle on the USB host.
The host controller directs traffic flow to devices, so no USB device can transfer any data on
the bus without an explicit request from the host controller. The throughput of each USB port is
determined by the slower speed of either the USB port or the USB device connected to the
port.

The Centurion connects to storage devices using a set of standards called the USB mass
storage device class (MSC or UMS).

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

C5-1 Shown

NOTE: These circuits are not required to be in conduit if all the


requirements for ic protection are met and Authority Having Jurisdiction
(AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 36 -
USB 2 Device

WARNING: Explosion hazard – Do not disconnect the USB port unless the power
has been switched off or the area is known to be non-hazardous.

The Centurion is equipped with a USB 2.0 standard communications port. The ports is marked
USB 2.

The USB 2.0 standard-B type of USB plug has a square shape with beveled exterior corners

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

When the Centurion is first connected to a USB host, the USB device enumeration process is
started. The connected host controller directs traffic flow to the Centurion. There is no transfer
of any data on the bus without an explicit request from the host controller.

C5-1 Shown

NOTE: These circuits are not required to be in conduit if all the


requirements for ic protection are met and Authority Having Jurisdiction
(AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 37 -
Wi-Fi (C5-1)
The Centurion C5-1 (only) is equipped with a Wi-Fi communications port. The port is marked
WIFI. The Centurion allows communications directly from one computer to another without an
access-point intermediary. The Wi-Fi signal range depends on the frequency band, power
output, antenna gain and type. Line-of-sight is the thumbnail guide, but reflection and refraction
can have a significant impact. An access point compliant with either 802.11b or 802.11g, using
the stock antenna might have a range of 100 m (330 ft). Due to the complex nature of radio
propagation at typical Wi-Fi frequencies, particularly the effects of signal reflection off trees
and buildings, range can only be approximated for any given area in relation to a transmitter.
Wi-Fi connections can be disrupted or the internet speed lowered by having other devices in
the same area. Many 2.4 GHz 802.11b and 802.11g access points default to the same channel
on initial startup, contributing to congestion. Wi-Fi pollution, or an excessive number of access
points in the area especially on the neighboring channel, can prevent access and interfere with
other devices use of other access points, caused by overlapping channels in the 802.11g/b
spectrum, as well as with decreased signal-to-noise ratio (SNR) between access points.

Important: For Entity Parameters or Power Supply and Grounding, refer to Wire Connections.

C5-1 Shown

NOTE: These circuits are not required to be in conduit if all the


requirements for ic protection are met and Authority Having Jurisdiction
(AHJ) allows.

Section 50 00-02-0963
2022-08-29 - 38 -
Accessories
Replacement Parts and Assemblies

Part Number Description Notes


C5-1 Centurion Controller Centurion Configurable – Standard
(Main Module) Centurion Custom – Option

C5-2 Centurion Controller Centurion Configurable – Standard


(Main Module) Centurion Custom – Option

Specify Model MV-5-C display Standard, Auto sync to C5

MV-7T display

MV-10T display Optional, Auto sync to C5

MV-12T display

50703852 MX4-R2 expansion I/O module


Optional
50703853 MX5-R2 expansion I/O module

50000774 Ignition noise (choke) filter

00032696 C5 Plug kit Printed replacement terminal plugs for main I/O module

Printed replacement terminal plugs for MX4-R2 expansion I/O


00032656 MX4-R2 Plug kit
module

Printed replacement terminal plugs for MX5-R2 expansion I/O


00032657 MX5-R2 Plug kit
module

Centurion configuration tool is software for modifying sequence


Centurion configuration tool for of operation, set points, timers, faults and displays for
50702313
user application setup Centurion. Includes file transfer utilities for configuration and
upgrades.

Software Configuration Tool


The Centurion Configuration Tool is the configuration software for modifying sequence of
operation, set points, timers, faults and displays* for Centurion C5. This tool can be
downloaded from the Centurion Forum at http://forum.fwmurphy.com. The forum also hosts
knowledge base articles and quick troubleshooting steps including those exchanged by other
users. Please contact your sales personnel to gain access to the forum. In case the Centurion
C5 has been custom programmed from the factory, please contact your sales channel for any
modifications to the sequence of operations.

*Display configuration and other settings for display are only for use with the display Module.

Section 50 00-02-0963
2022-08-29 - 39 -
Specifications
C5 Series Main I/O Module
• Operating temperature: -40° to 185° F (-40° to 85° C) • 11 Communication ports:
• Power input: 30 W max 10-30 VDC - Two SERIAL RS232:
• Configuration: PC-based Centurion Configuration Software > Protocol: MODBUS RTU (server)
• Application firmware: - Two SERIAL RS485:
- Standard offers a user-configurable experience > Protocol: MODBUS RTU (server)
- Centurion Custom option offers highly customized applications - One USB: Host Type A (data log access, firmware updates)
Integrate with Rockwell Automation Processors as I/O module to - One USB: Server Type B (firmware updates)
write IEC 61131-3 logic (Ladder Logic, Structured Text, Function - Two CAN:
Block Diagram). > One proprietary for FW Murphy hardware
• All I/O options individually software selectable: No jumper required. > One reserved for J1939 Engine ECU
• Clock: Battery backed internal real-time clock, - Two Ethernet 10/100 (DLR):
approximately 10 years unpowered service life > Protocol: Modbus TCP/IP (server)
12 Analog inputs*: > EtherNet/IP (CIP)
- 0-24 mA or 0-5 VDC, 15-bit hardware - One WiFi: Optional C5-1 only
- 4 resistive potentiometer measurement • Third-party approvals:
• 32 Digital inputs*: - North America:
- NO or NC (active high/active low) intrinsically safe - Class I, Div 2, Grps A,B,C,D Haz. Loc, T4
- Optically isolated DC digital inputs (active high/active low) - Class I, Zone 2, AEx ec [ic] nC IIC T4 Gc
Ex ec [ic] nC IIC T4 Gc X
with LED indicators
- Polarity sense / wire fault detection on normally closed - ATEX Zone 2:
systems II 3G Ex ec [ic] nC IIC T4 Gc
- Approved for use with general purpose switches in DEMKO 18 ATEX 1926X
hazardous areas -40°C ≤ Tamb ≤ +85°C
• Eight temperature inputs*: - IECEx Zone 2:
- J or K Type Thermocouples Ex ec [ic] nC IIC T4 Gc
- 3-wire 100Ω Pt RTD temperature inputs*** IECEx UL 18.0072X
- Open, short DC-, short DC+ wire fault detection -40°C ≤ Tamb ≤ +85°C
- Cold junction compensation
• One magnetic pickup input/AC run signal: * Non-incendive.
- 30 to 10 kHz, 4.5 VAC rms min, 40 VAC rms max. ++ Applies only to Centurion TM Custom Applications and Rockwell Automation ®
• 10 digital outputs:
Processor configurations.
- LED indicators:
- 4 relay outputs, form C, dry contacts *** RTD=Resistive Temperature Device, American RTD Standard, TCR 0.00392,
- 4 FET outputs (source) units Ohms/Ohm / deg. between 0-100 C.
- 2 FET outputs (sink)
• Four analog outputs:
- 4-20 mA, 16-bit hardware

C5-1 Shown

Section 50 00-02-0963
2022-08-29 - 40 -
M-VIEW® Monochrome LCD Display
• Operating temperature: -40° to 185° F (-40° to 85° C)
• Power input: 11 W max 10-30 VDC
• Screen: 320 x 240 pixels, LCD display with backlight
• User interface: 12-key keypad set point entry, alarm
acknowledgment, start, stop, reset, etc.
• Communications:
- RS232-1/RS485-1 (MODBUS RTU client)
- RS485-2 (MODBUS RTU server)
- 1 USB Server Type B (firmware updates)
- 1 USB Host Type A (reserved)
- CAN x 2
>1 proprietary for FW Murphy Hardware
>1 reserved for J1939 engine ECU
• Customizable process screens (up to nine):
- Line by line
- Gage
- Control loop
- Generic register
• Built-in screens (examples):
- Digital input status and polarity
- Digital output status
- Temperature input status/fault
- Fault snapshot (mirror of line-by-line)
- Alarm log
• Third-party approvals for MV-5-C Display:
- North America:
- Class I, Div 2, Grps A,B,C,D Haz. Loc. T4
- Class I, Zone 2, AEx ec ic [ic] IIC T4 Gc
Ex ec ic [ic] IIC T4 Gc X
- ATEX Zone 2:
II 3G Ex ec ic [ic] IIC T4 Gc
DEMKO 18 ATEX 1926X
-40°C ≤ Tamb ≤ +85°C
- IECEx Zone 2:
Ex ec ic [ic] IIC T4 Gc
IECEx UL 18.0072X
-40°C ≤ Tamb ≤ +85°C

Section 50 00-02-0963
2022-08-29 - 41 -
M-VIEW® Touch Series Displays
• Operating temperature: -4° to 140° F (-20° to 60° C)
• Power input:
- MV-7T, 15 W max 10-30 VDC (36 W max with modules)
- MV-10T, 22 W max 10-30 VDC (52 W max with modules)
- MV-12T, 23 W max 10-30 VDC (57 W max with modules)
• Screen (sunlight readable):
- MV-7T, 800x480 pixels, 7” widescreen
Brightness 1000 cd/m2
- MV-10T, 640x480 pixels, 10.4” screen
Brightness 2500 cd/m2
- MV-12T, 1280x800 pixels, 12” widescreen
Brightness 1600 cd/m2
• User interface: resistive analog touchscreen
• Communication interface
- 2x RS232
- 1x RS485
- 2x USB host type A (file transfer, data logging, USB device)
- 1x USB server (program/firmware updates)
- 2 Ethernet 10/100 Base TX (RJ45)
• Communication protocols:
- EtherNet/IP (CIP)
- Modbus TCP/IP
- Modbus RTU standard
- 300 plus available, web server
Third-party approvals:
CE approved
- EN 61326-1 immunity to industrial
Locations emission CISPR 11 Class A
- IEC/EN 61010-1
- RoHS compliant
ATEX approved
- II 3 G Ex ic nA IIC T4 Gc
- II 3 D Ex tc IIIC T135°C Dc
- DEMKO 14 ATEX 1387X
- EN 60079-0, -11, -15, -31
IECEx approved
- Ex ic nA IIC T4 Gc
- Ex tc IIIC T135°C Dc
- IECEx UL 15.0035X
- IEC 60079-0, -11, -15, -31
UL approved
cULus listed for ordinary location:
File #E302106
- UL 61010-1, -2-201
cULus listed for hazardous location:
File #E317425
- Class I, Division 2, Groups A, B, C and D
- Class II, Division 2, Groups F and G
- Class III, Division 2 ANSI/ISA 12.12.01,
C22.2 No. 213-M1987, 157-92
IP66 Enclosure rating (Face only)
Type 4X outdoor enclosure rating (face only)
ABS type approval for shipboard applications

Section 50 00-02-0963
2022-08-29 - 42 -
Notes

Section 50 00-02-0963
2022-08-29 - 43 -

You might also like