Centrifugal Liquid Chillers: Installation Instructions
Centrifugal Liquid Chillers: Installation Instructions
MODEL YK (STYLE H)
R-134a or R-513A
Issue Date:
June 21, 2019
FORM 160.76-N1
ISSUE DATE: 06/21/2019
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
materials under pressure, rotating components, and rigging, installation, and operating/service personnel. It
both high and low voltage. Each of these items has the is expected that these individuals possess independent
potential, if misused or handled improperly, to cause training that will enable them to perform their assigned
bodily injury or death. It is the obligation and respon- tasks properly and safely. It is essential that, prior to
sibility of operating/service personnel to identify and performing any task on this equipment, this individual
recognize these inherent hazards, protect themselves, shall have read and understood the on-product labels,
and proceed safely in completing their tasks. Failure this document and any referenced materials. This in-
to comply with any of these requirements could result dividual shall also be familiar with and comply with
in serious damage to the equipment and the property in all applicable industry and governmental standards and
regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2 JOHNSON CONTROLS
FORM 160.76-N1
ISSUE DATE: 06/21/2019
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Installation Checklist/Start-Up Request 160.76-CL1
Unit Start-Up Checklist 160.76-CL2
Installation and Reassembly - Unit 160.76-N3
Installation - MVVSD - 2300 VAC to 6600 VAC 160.00-N6
Installation - MVVSD - 10 kV to 13.8 kV 160.00-N8
Wiring Diagrams - Field Connections - Unit-Mounted SSS or Remote Mounted MVSSS, MVEMS 160-76-PW1
Wiring Diagrams - Field Connections - Remote Mounted MVSSS 160-76-PW2
Wiring Diagrams - Field Connections - Remote Mounted MVVSD 160-76-PW3
Wiring Diagrams - Field Connections - LVVSD 160-76-PW7
Wiring Diagrams - OptiView Control Center and EMS 160.76-PW5
Wiring Diagrams - OptiView Control Center and SSS, LVVSD 160.76-PW6
Wiring Diagrams - Field Control Modifications 160.76-PW4
Unit Operation and Maintenance 160.76-O1
Operation - OptiView Panel 160.76-O2
Operation - Variable Speed Drive - TM Model 160.00-O1
Operation and Maintenance - Solid State Starter (Mob B) 160.00-O2
Operation - Variable Speed Drive - VSD and LVD Model 160.00-O4
Operation - Variable Speed Drive - HYP Model 160.00-O10
Operation - Floor Mounted MVSSS 160.00-O5.1
Operation - Unit Mounted MVSSS 160.00-O7
Operation - MVVSD - 2300 VAC to 6600 VAC 160.00-O6
Operation - MVVSD - 10 kV to 13.8 kV 160.00-O8
JOHNSON CONTROLS 3
FORM 160.76-N1
ISSUE DATE: 06/21/2019
NOMENCLATURE
SYSTEM NOMENCLATURE
YK 6A 6Q Q7 – EM H
4 JOHNSON CONTROLS
FORM 160.76-N1
ISSUE DATE: 06/21/2019
TABLE OF CONTENTS
SECTION 1 - INTRODUCTION..................................................................................................................................7
General.............................................................................................................................................................. 7
Field Assembled Units Only.............................................................................................................................. 7
Shipment........................................................................................................................................................... 8
Inspection – Damage – Shortage...................................................................................................................... 9
Chiller Data Plate.............................................................................................................................................. 9
Long-Term Storage............................................................................................................................................ 9
Rigging............................................................................................................................................................ 12
Location........................................................................................................................................................... 12
Motors............................................................................................................................................................. 13
Foundation...................................................................................................................................................... 13
Clearance........................................................................................................................................................ 13
SECTION 2 - INSTALLATION.................................................................................................................................19
Rigging Unit to Final Location......................................................................................................................... 19
Locating and Installing Isolator Pads............................................................................................................... 19
Checking the Isolation Pad Deflection............................................................................................................. 19
Leveling the Unit.............................................................................................................................................. 19
Installing Optional Spring Isolators.................................................................................................................. 19
Piping Connections......................................................................................................................................... 19
Evaporator and Condenser Water Piping........................................................................................................ 20
Unit Piping....................................................................................................................................................... 21
Refrigerant Relief Piping................................................................................................................................. 22
Control Panel Positioning................................................................................................................................ 23
Control Wiring.................................................................................................................................................. 23
Power Wiring................................................................................................................................................... 23
Oil Pump – 3 Phase Starter............................................................................................................................. 23
Insulation......................................................................................................................................................... 24
Installation Check – Request for Start-up Service...........................................................................................24
Compressor Units ........................................................................................................................................ 28
Evaporator Compact Waterboxes – A Through L Evaporators - Ft-In. (mm)................................................... 32
Evaporator Compact Waterboxes – M Through Z Evaporators - Ft-In. (mm)................................................. 33
Condenser Compact Waterboxes – Standard - Ft-In. (mm)............................................................................ 36
Evaporator Marine Waterboxes - Ft-In. (mm).................................................................................................. 39
Condenser Marine Waterboxes - Ft-In. (mm).................................................................................................. 42
Weights........................................................................................................................................................... 45
JOHNSON CONTROLS 5
FORM 160.76-N1
ISSUE DATE: 06/21/2019
LIST OF FIGURES
LIST OF TABLES
TABLE 1 - Available Compressor/Evaporator/Condenser/Motor Combinations����������������������������������������������������� 26
TABLE 2 - Dimensions – Compressor Units�����������������������������������������������������������������������������������������������������������29
TABLE 3 - Dimensions (End) – Evaporator Compact Waterboxes ������������������������������������������������������������������������34
TABLE 4 - Dimensions (End) – Condenser Compact Waterboxes - Standard������������������������������������������������������� 37
TABLE 5 - Dimensions (End) – Evaporator Marine Waterboxes ���������������������������������������������������������������������������40
TABLE 6 - Dimensions (End) – Condenser Marine Waterboxes ���������������������������������������������������������������������������43
TABLE 7 - Approximate Unit Weight Including Motor for Hybrid Falling Film Evaporator Units ����������������������������� 45
TABLE 8 - Approximate Evaporator Marine Waterbox Weights lb (kg)
(To Be Added To Standard Unit Weights Shown On Table 7)���������������������������������������������������������������� 45
TABLE 9 - Condenser Marine Waterbox Weights lb (kg)
(To Be Added To Standard Unit Weights Shown In Table 7)������������������������������������������������������������������ 46
TABLE 10 - SI Metric Conversion���������������������������������������������������������������������������������������������������������������������������47
6 JOHNSON CONTROLS
FORM 160.76-N1
ISSUE DATE: 06/21/2019
SECTION 1 - INTRODUCTION 1
GENERAL
This manual describes the installation of a YORK YK The services of a Johnson Controls representative will
Mod "H" Centrifugal Chiller. This unit can be shipped be furnished to check the installation, supervise the
as a single factory assembled, piped, wired package, initial start-up and operation of all chillers installed
requiring a minimum of field labor to make chilled within the Continental United States.
water connections, condenser water connections, re- The Johnson Controls Warranty may be
frigerant atmospheric relief connections, and electri- voided if the following restrictions are not
cal power connections. Refrigerant and oil charges are adhered to:
shipped separately unless optional condenser isolation
valves are ordered.
Chillers can also be shipped dismantled when required • Do not open valves or connections under any cir-
by rigging conditions, but generally it is more econom- cumstances, as such action will result in loss of
ical to enlarge access openings to accommodate the the factory nitrogen charge.
factory assembled unit. Chillers shipped dismantled
MUST be field assembled under the supervision of a • Do not dismantle or open the chiller for any rea-
Johnson Controls representative, but otherwise instal- son except under the supervision of a Johnson
lation is as described in this instruction. Controls representative.
• When the units are shipped dismantled, notify the
FIELD ASSEMBLED UNITS ONLY
nearest Johnson Controls office in ample time for
Use Unit - Installation Instructions (Form 160.76-N3) a Johnson Controls representative to supervise
in conjunction with this installation instruction. This in- rigging the unit to its operating position and the
struction is furnished with all units that are assembled assembly of components.
in the field.
• Do not make final power supply connections to
the compressor motor or control center.
COMPRESSOR
CONTROL
CENTER
VSD PANEL
CONDENSER
LD15222
EVAPORATOR
JOHNSON CONTROLS 7
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
• Do not charge the compressor with oil. • Compressor/motor assembly removed from
shells and skidded. Evaporator/condenser is
• Do not charge the unit with refrigerant.
not skidded.
• Do not attempt to start the system.
• All wiring integral with compressor is left on
• Do not run hot water (110°F / 43°C max) or steam it, and all conduit is left on shell. All open-
through the evaporator or condenser at any time. ings on compressor, oil separator, and shell
are closed and charged with dry nitrogen
SHIPMENT (2 psig to 3 psig) (115/122 kPa).
The chiller may be ordered and shipped in any of the • Miscellaneous packaging of control center,
following forms: tubing, water temperature controls, wiring,
Form 1 – Factory Assembled Unit, complete with mo- oil, isolators, solid state starter (option), and
tor, refrigerant and oil charges. so on. The refrigerant charge is shipped sepa-
rately.
• The motor/compressor assembly mounted, Units shipped dismantled MUST be re-
with all necessary interconnecting piping assembled by, or under the supervision of,
assembled. OptiView™ Control Center is a Johnson Controls representative. Refer
mounted on the unit. Complete unit factory to Installation - Unit (Form 160.76-N3)
leak tested, evacuated and charged with
refrigerant.
An optional Solid State Starter or Variable Form 7 – S
plit Shells – Shipped as three major assem-
Speed Drive can be factory mounted and blies. Unit first factory assembled, refriger-
wired. ant piped, wired and leak tested; then dis-
mantled for shipment.
• Miscellaneous material – Four (4) vibration
isolation pads (or optional spring isolators • Compressor/motor assembly removed from
and brackets). K7 units are shipped with 8 shells and skidded.
Vibration Isolation Pads.
• The evaporator and condenser shells are sep-
Form 2 – Factory Assembled Unit, complete with mo- arated at tube sheets and are not skidded. The
tor (refrigerant and oil charges shipped sepa- refrigerant lines between shells are flanged
rately). and capped, requiring no welding.
• The motor/compressor assembly mounted, • All wiring integral with compressor is left on
with all necessary interconnecting piping it. All wiring harnesses on the shells are re-
assembled. OptiView™ Control Center is moved. All openings on the compressor and
mounted on the unit. Complete unit fac- shells are closed and charged with dry nitro-
tory leak tested, evacuated and charged with gen (2 psig to 3 psig) (115/122 kPa).
holding charge of nitrogen.
• Miscellaneous packaging of control center,
An optional Solid State Starter or Variable tubing, water temperature controls, wiring,
Speed Drive can be factory mounted and oil isolators, solid state starter (option), etc.;
wired. refrigerant charge shipped separately.
Units shipped dismantled MUST be re-
• Miscellaneous material – Four (4) vibration
assembled by, or under the supervision of,
isolation pads (or optional spring isolators).
a Johnson Controls representative. Refer
K7 units are shipped with 8 Vibration Isola-
to Installation - Unit (Form 160.76-N3)
tion Pads.
Form 3 – D
riveline Separate From Shells – Shipped as
two major assemblies. Unit first factory assem- When more than one chiller is involved, the major
bled, refrigerant piped, wired and leak tested; parts of each unit are marked to prevent mixing of as-
then dismantled for shipment. semblies. (Piping and Wiring Drawings to be furnished
by Johnson Controls)
8 JOHNSON CONTROLS
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
Miscellaneous packaging of tubing, water temperature Do not break the seal or remove closures until ready
controls, wiring, isolators, etc. The unit is shipped with for set up. Use the following procedure to relieve pres-
refrigerant charge. See Table 7 on Page 45. sure (see Figure 3 on page 10).
Failure to follow the following procedures
65° will cause severe personal injury or death
Min. to operators themselves or people on-site.
65° It is the obligation and responsibility of
Min.
operators to identify and recognize the
Lifting inherent hazards of material under pres-
Holes sure and to protect themselves.
Lifting
Holes
LD27908
JOHNSON CONTROLS 9
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
5
4
3
ITEM DESCRIPTION
8 1 Tag Warning Dennison 8E
9 2 Gauge Press 2 Dia 0-30
3 Tag GlvSt Wire Speed
4 Bush Pipe 3/4 - 14 NPTE X
5 Valve, Transducer 1/4 NPTE X
6 Flange Cover
7 Gasket
Nozzle without flanges 8 Victaulic Coupling
(Lines 4 in. through 12 in.) 9 Sealing Cap
8
10 JOHNSON CONTROLS
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
To relieve pressure, complete the following steps: When relieving the pressure from com-
pressor, shells, or system, conduct the 1
1. Check that the working space is open and has nitrogen to outside to prevent the potential
good ventilation. If not, it does not have good ven- risk of asphyxiation..
tilation, and you should connect a hose or pipe to
the valve (Item 5) and route it to outside.
2. Slowly open the valve (Item 5) until fully opened.
Shipment Form 1/10
3. Monitor the pressure gauge (Item 2). The pressure The unit is shipped with refrigerant charge; it is not
should decline gradually. necessary to relieve the pressure. DO NOT try to open
4. When the pointer of pressure gauge stops moving any valves to relieve pressure or open closures, cap, or
and no nitrogen is released from the valve (Item plugs on the compressor, shells, and elsewhere on the
5), no positive pressure exists in the waterbox. system.
5. When there is no positive pressure in the water- Reclaim the refrigerant in the system before carrying
box, it is safe to remove the flange cover (Item 6) out any service activities on the refrigeration system.
or sealing cap (Item 9). Fully relieve system pressure and then repair.
6. Close the valve (Item 5) and remove the warning The unit is charged with tons of refriger-
tag (Item 1). ant; if an uncontrollable leak is found,
inform all of the relevant people to evacu-
Shipment Form 2/3/7/9 ate from the building to prevent risk of
All openings on the compressor, shells including evap- asphyxiation.
orator and condenser, and oil reservoir are closed and Never touch the refrigerant that is leak-
charged with nitrogen (2 psig to 3 psig). To remove the ing, especially the liquid refrigerant; this
closures, sealing caps, or sealing plug under pressure is will cause severe freezing to your hands
extremely dangerous, and may cause severe injury or or body.
death to the operator or people on-site.
Before trying to remove the closures,
caps, or plugs on compressor and shells,
relieve the pressure in compressor, shells,
or system that are charged with nitrogen
by opening the valves on them slowly until
fully open.
JOHNSON CONTROLS 11
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
LD19197
Rigging and lifting should only be done by a professional rigger in accordance with a written rigging
and lifting plan. The most appropriate rigging and lifting method depends on job specific factors,
such as the rigging equipment available and site needs. Therefore, a professional rigger must deter-
mine the rigging and lifting method to be used, and it is beyond the scope of this manual to specify
rigging and lifting details.
RIGGING LOCATION
The complete standard chiller is shipped without skids. YORK Chillers are furnished with vibration isola-
(When optional skids are used it may be necessary to tor mounts for basement or ground level installations.
remove the skids so riggers skates can be used under Units may be located on upper floor levels providing
the unit end sheets to reduce overall height.) the floor is capable of supporting the total unit operat-
ing weight and optional spring isolators are used.
Each unit has four (4) lifting holes (two in each end)
in the end sheets, which should be used to lift the unit. Sufficient clearance to facilitate normal
service and maintenance work must be
Care should be taken at all times during rigging and provided all around and above the unit
handling of the chiller to avoid damage to the unit and and particularly space provided at either
its external connections. Lift only using holes shown in end to permit cleaning or replacement
Figure 4 on page 13. of evaporator and condenser tubes – see
Do not lift the unit with slings around Clearance. A doorway or other sufficiently
motor/compressor assembly or by means large opening properly located may be
of eyebolts in the tapped holes of the used. The chiller should be located in an
compressor motor assembly. Do not turn indoor location where temperatures range
a unit on its side for rigging. Do not rig from 40°F to 110°F (4.4°C to 43.3°C).
vertically.
12 JOHNSON CONTROLS
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
LD19569
Figure 4 - RIGGING
MOTORS CLEARANCE
The YK open motor is air cooled. Check state, local, Clearances should be adhered to as follows:
and other codes for ventilation requirements.
• Rear and above unit – 2 ft (61 cm).
The minimum clearance to the nearest wall must be at
• Front of unit – 3 ft (91 cm).
least one-quarter of the length of the fan cover diame-
ter. Check the cooling fan condition. Clean the air inlet • Tube Removal – 12 ft (4.3 m) (either end)
and outlet openings to ensure that there is free airflow
over the motor. Tube removal - 12*ft (3.6 m) (either end)
For units that are shipped disassembled, before rigging *14 ft (4.3 m) on shell codes; K-F, H-F,
is completed, make sure that the eyebolts are properly K-K, O-O, M-K, Q-Q
selected and tightened. Use all of the designed eyebolts *16 ft (4.9 m) on shell codes; L-L, P-P,
to lift the motor. The coupling alignment must be ful- N-L, R-R
filled correctly.
FOUNDATION
A level floor, mounting pad or foundation must be pro-
vided by others, capable of supporting the operating
weight of the unit.
JOHNSON CONTROLS 13
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
LD28106 LD28107
UNIT WEIGHT UP TO 16,365 Lbs (7,423 Kgs) UNIT WEIGHT 16,366 - 28,835 Lbs (7,424 - 13,080 Kgs)
LD28108
LD28109
UNIT WEIGHT 28,836 - 53,530 Lbs (13,081 - 24,281 Kgs) UNIT WEIGHT 53,531 - 100,464 Lbs (24,283 - 45,559 Kgs)
9"
(229)
LD28110 LD28111
UNIT WEIGHT 100,465 - 130,000 Lbs (45,570 - 58,967 Kgs) UNIT WEIGHT UP TO 200,928 Lbs (UP TO 91,332 Kgs)
Mounting 3/8”
Bracket (10)
Pad 3/4”
(19)
LD19571a
DETAIL A
14 JOHNSON CONTROLS
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
1
Compressor Code - Q, P, H, K1 - K3 Shipment Forms 1, 2, 3, 7, 9, 10
SHELL
END SHEET
DIA.
HOLE
LD28112
SHELL
LD28113
JOHNSON CONTROLS 15
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
SHELL SHELL
END END
5 1/2” 1 3/8” 5 1/2” 1 3/8” SHEET
(35) SHEET
(140) (35)
(140) CAP
CAP
SCREW SCREW
ADJUSTING ADJUSTING
BOLT BOLT
1 1
(25” (25”
) )
(17 7” (15 6”
7” 8) 2)
(1 6”
)
8)
52
(17
4-SPRING ISOLATORS 4-SPRING ISOLATORS
LD19572 LD19573
UNIT WEIGHT UNIT WEIGHT
10,000 to 19,563 19,564 Lbs UP TO 35,009 Lbs
(4,536 to 8,873 Kgs) (8,874 Kgs UP TO 15,880 Kgs)
END SHELL
SHELL
SHEET
END
SHEET
6-
5 1/2" 1
(1 /4" CAP
59
(140) ) SCREW
CAP ADJUSTING
SCREW BOLT
ADJUSTING
BOLT
(22 9” 9” 29)
9) (2
16 JOHNSON CONTROLS
FORM 160.76-N1
Section 1 - INTRODUCTION
ISSUE DATE: 06/21/2019
/4"
5 1 3)
16 (13
1/
(41 4"
6- 3)
1
(1 /4" CAP
59
)
SCREW
CAP
ADJUSTING SCREW
BOLT
ADJUSTING
BOLT
12-SPRING ISOLATORS
3-SPRING ISOLATORS
LD19580 LD19581
UNIT WEIGHT UNIT WEIGHT
89,341 Lbs UP TO 115,000 Lbs 115,000 Lbs. UP TO 190,000 Lbs
(40,526 Kgs UP TO 52,163 Kgs) (52,163 Kgs UP TO 86,183 Kgs)
JOHNSON CONTROLS 17
FORM 160.76-N1
ISSUE DATE: 06/21/2019
18 JOHNSON CONTROLS
FORM 160.76-N1
ISSUE DATE: 06/21/2019
SECTION 2 - INSTALLATION
CHECKING THE ISOLATION PAD DEFLECTION After the unit is leveled (and wedged in place for op-
tional spring isolators) the piping connections may be
Check all isolation pads for the proper deflection made; chilled water, condenser water and refrigerant
while also checking to see if the unit is level. Each pad relief. The piping should be arranged with offsets for
must be deflected approximately 0.10 in. (2.5 mm) to flexibility, and adequately supported and braced inde-
0.20 in. (5 mm). If an isolation pad is under-deflected, pendently of the unit to avoid strain on the unit and
shims must be placed between the unit tube sheet and vibration transmission. The hangers must allow for
the top of the pad to equally deflect all pads. alignment of pipe. Isolators (by others) in the piping
and hangers are highly desirable, and may be required
LEVELING THE UNIT
by specifications, in order to effectively utilize the vi-
The longitudinal alignment of the unit should be bration isolation characteristics of the vibration isola-
checked by placing a level on the top center of the tion mounts of the unit.
evaporator shell under the compressor/motor assem-
bly. Transverse alignment should be checked by plac- Check for piping alignment – Upon completion of
ing a level on top of the shell end sheets. piping, a connection in each line as close to the unit
as possible should be opened, by removing the flange
bolts or coupling and checked for piping alignment. If
JOHNSON CONTROLS 19
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
any of the bolts are bound in their holes, or if the con- flow path for the starter heat exchanger to regulate cooling
nection springs are out of alignment, the misalignment above the equipment room dewpoint for applications using
must be corrected by properly supporting the piping or cooling sources other than evaporative air-exchange meth-
by applying heat to anneal the pipe. ods, such as wells, bodies of water, and chilled water. The
If the piping is annealed to relieve stress, temperature control valve should be the type to open on in-
the inside of the pipe must be cleaned of creasing drive coolant temperature, fail-closed, and set for a
scale before it is finally bolted in place. temperature above dewpoint. It can be requested as factory-
supplied on a chiller order by special quotation.
Chilled Water
Foreign objects which could lodge in, or block flow
EVAPORATOR AND CONDENSER WATER
through, the evaporator and condenser tubes must be
PIPING
kept out of the water circuit. All water piping must be
The evaporator and condenser liquid heads of the chill- cleaned or flushed before being connected to the chiller
er have nozzles which are grooved, suitable for weld- pumps, or other equipment.
ing 150 psig DWP flanges or the use of flexible cou-
plings. Factory mounted flanges are optional. Permanent strainers (supplied by others) are required
in both the evaporator and condenser water circuits to
The nozzles and water pass arrangements are furnished protect the chiller as well as the pumps, tower spray
in accordance with the job requirements (refer to Prod- nozzles, chilled water coils and controls, etc. The
uct Drawings) furnished with the job. Standard units are strainer must be installed in the entering chilled water
designed for 150 psig DWP on the water side. If job re- line, directly upstream of the chiller.
quirements are for greater than 150 psig DWP, check the
unit data plate before applying pressure to evaporator or Water piping circuits should be arranged so that the
condenser to determine if the chiller has provisions for the pumps discharge through the chiller, and should be
required DWP. controlled as necessary to maintain essentially constant
chilled and condenser water flows through the unit at
Inlet and outlet connections are identified by labels
all load conditions.
placed adjacent to each nozzle.
The coolant temperature inside any JCI-supplied liquid- If pumps discharge through the chiller, the strainer may
cooled motor starter must be maintained above the dewpoint be located upstream from pumps to protect both pump
temperature in the equipment room to prevent condensing and chiller. (Piping between strainer, pump and chill-
water vapor inside the starter cabinet. Therefore, an addi- er must be very carefully cleaned before start-up.) If
tional temperature-controlled throttle valve is needed in the pumps are remotely installed from the chiller, strainers
should be located directly upstream of the chiller.
COOLING
TOWER
CONTROLLED COOLING
TOWER BYPASS VALVE
(IF NECESSARY) C = COMPRESSOR
STRAINER M = MOTOR
CONDENSER
FLOW SWITCH
COOLING TOWER COOLING
PUMP UNIT
EVAPORATOR
COOLING UNIT
CODEPAK STRAINER
CHILLED WATER PUMP
LD08529
Figure 8 - SCHEMATIC OF A TYPICAL PIPING ARRANGEMENT
20 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
JOHNSON CONTROLS 21
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
VENT TO ATMOSPHERE
CONDENSATION
TRAP
CONDENSER
DUAL RELIEF SEE NOTE
VALVES
EVAPORATOR
22 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
JOHNSON CONTROLS 23
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
24 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
2
Tape Insulation Hot Gas
to Filter Drier Connection
CONDENSER
CONDENSER
EVAPORATOR
EVAPORATOR
2” Liquid
Level Indicator
Refigerant from
Oil Cooler to Cooler
Input Drain
Liquid Line and
Hot Gas
Connection Tape Insulation Charging
around flanges to
allow for removal
LD12649
JOHNSON CONTROLS 25
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
4C, 4D, 4E, 4F, 4G, 4H, 4I 4P, 4Q, 4R, 4S, 42, 43, 44, 45
CH-CZ 5CE-5CU
Q5, Q6, Q7 6A, 6B, 6C, 6D, 6E, 6F, 6W*, 6X* 4P, 4Q, 4R, 4S, 42, 43, 44, 45
EH-EZ 5EE-5EU
6A, 6B, 6C, 6D, 6E, 6F, 6W*, 6X* 6P, 6Q, 6R, 6S, 6T, 63, 64
GK, GL, GN, GP, GC, GE, EC, EE, EG, EK, EL,
G5, G7, G9, G1, G3 E1, E3, E5, E6, E7, E9
HK, HL, HN, HP, HC, HE, FC, FE, FG, FK, FL, CH-CZ 5CE-5CU
P8, P9
H5, H7, H9, H1, H3 F1, F3, F5, F6, F7, F9 EH-EZ 5EE-5EU
KC, KE, KG, KK, KL, KC, KE, KG, KK, KL,
K1, K3, K5, K7, K9, K0, K1, K2, K3, K5, K7, K9,
HK, HL, HN, HP, HC, HE, FC, FE, FG, FK, FL,
H5, H7, H9, H1, H3 F1, F3, F5, F6, F7, F9
KC, KE, KG, KK, KL, KC, KE, KG, KK, KL,
K1, K3, K5, K7, K9, K0, K1, K2, K3, K5, K7, K9,
LC, LE, LG, LK, LL, LC, LE, LG, LK, LL, CN-CA 5CK-5CW
H9
L1, L3, L5, L7, L9 L0, L1, L2, L3, L5, L7, L9 EN-EA 5EK-5EW
OC, OE, OG, OK, OL, OC, OE, OG, OK, OL,
O1, O3, O5, O7, O9, O1, O3, O5, O7, O9,
PC, PE, PG, PK, PL, PC, PE, PG, PK, PL,
P1, P3, P5, P7, P9 P1, P3, P5, P7, P9
KC, KE, KG, KK, KL, KC, KE, KG, KK, KL,
K1, K3, K5, K7, K9, K0, K1, K2, K3, K5, K7, K9,
LC, LE, LG, LK, LL, LC, LE, LG, LK, LL,
L1, L3, L5, L7, L9 L0, L1, L2, L3, L5, L7, L9
KC, KE, KG, KK, KL,
MC, ME, MG, M1, M3, M5, K0, K1, K2, K3, K5, K7, K9,
NC, NE, NG, N1, N3, N5 LC, LE, LG, LK, LL,
L0, L1, L2, L3, L5, L7, L9
K1
OC, OE, OG, OK, OL, OC, OE, OG, OK, OL,
O1, O3, O5, O7, O9, O1, O3, O5, O7, O9,
PC, PE, PG, PK, PL, PC, PE, PG, PK, PL,
P1, P3, P5, P7, P9 P1, P3, P5, P7, P9
QC, QE, QG, QK, QL, QC, QE, QG, QK, QL,
Q3, Q5, Q7, Q9, Q1, Q3, Q5, Q7, Q9, CS-DC 5CN-5DC
RC, RE, RG, RK, RL, RC, RE, RG, RK, RL, ES-FC 5EN-5FB
R3, R5, R7, R9 R1, R3, R5, R7, R9
KC, KE, KG, KK, KL,
MC, ME, MG, M1, M3, M5, K0, K1, K2, K3, K5, K7, K9,
NC, NE, NG, N1, N3, N5 LC, LE, LG, LK, LL,
L0, L1, L2, L3, L5, L7, L9
OC, OE, OG, OK, OL, OC, OE, OG, OK, OL,
O1, O3, O5, O7, O9, O1, O3, O5, O7, O9,
K2
vPC, PE, PG, PK, PL, PC, PE, PG, PK, PL,
P1, P3, P5, P7, P9 P1, P3, P5, P7, P9
QC, QE, QG, QK, QL,
QC, QE, QG, QK, QL,
Q1, Q3, Q5, Q7, Q9,
Q3, Q5, Q7, Q9,
RC, RE, RG, RK, RL,
RC, RE, RG, RK, RL, R3, R5, R7, R9
R1, R3, R5, R7, R9
26 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
MOTOR CODES
COMPRESSOR EVAPORATOR SHELL CODES CONDENSER SHELL CODES
60 HZ 50 HZ
RC, RE, RG, RK, RL, RC, RE, RG, RK, RL,
2
R3, R4, R5, R7, R9 R1, R3, R5, R7, R9
SC,SE, SG, SH, SK, SC, SE, SG, SK,
S1, S2, S3, S4, S5, S7, S9 S1, S2, S3, S4, S5, S7, S9
TC, TE, TG, TH, TK, TC, TE, TG, TK, DA-DJ 5DA-5DH
K3
T1, T2, T3, T4, T5, T7, T9 T1, T2, T3, T4, T5, T7, T9 FA-FD 5FA-5FB
UC, UE, UG, UK, UC, UE, UG, UK,
U1, U2, U3, U5, U7, U8, U9 U1, U3, U9
VC, VE, VG, VK, VC, VE, VG, VK,
V1, V2, V3, V5, V7, V8, V9 V1, V3, V9
SC,SE, SG, SH, SK, SC,SE, SG, SK,
S1, S2, S3, S4, S5, S7, S9 S1, S2, S3, S4, S5, S7, S9
TC, TE, TG, TH, TK, TC, TE, TG, TK,
T1, T2, T3, T4, T5, T7, T9 T1, T2, T3, T4, T5, T7, T9
UC, UE, UG, UK, UC, UE, UG, UK,
U1, U2, U3, U5, U7, U8, U9 U1, U3, U9 DA-DJ 5DA-5DJ
K4
VC, VE, VG, VK, VC, VE, VG, VK, FA-FD 5FA-5FB
V1, V2, V3, V5, V7, V8, V9 V1, V3, V9
VC, VE, VG, VK, WC, WG,
V1, V2, V3, V5, V7, V8, V9 W1, W3, W4, W5, W6, W7, W9
XC, XE, XG, YC, YG,
X1, X3, X5, X6, X7, X9 Y1, Y2, Y3, Y4, Y5, Y7, Y9
VC, VE, VG, VK, WC, WG,
V1, V2, V3, V5, V7, V8, V9 W1, W3, W4, W5, W6, W7, W9
WC, WE, WG, WK, WC, WG,
W1, W2, W3, W5, W6, W7, W9 W1, W3, W4, W5, W6, W7, W9
YC, YE, YG, YK, ZC, ZG,
Y1, Y2, Y3, Y5, Y6, Y7, Y9 Z1, Z3, Z4, Z5, Z6, Z7, Z9
K7 DD-DL 5DD-5DL
XC, XE, XG, WC, WG,
X1, X3, X5, X6, X7, X9 W1, W3, W4, W5, W6, W7, W9
XC, XE, XG, YC, YG,
X1, X3, X5, X6, X7, X9 Y1, Y2, Y3, Y4, Y5, Y7, Y9
ZC, ZE, ZG, YC, YG,
Z1, Z2, Z3, Z5, Z7, Z9 Y1, Y2, Y3, Y4, Y5, Y7, Y9
JOHNSON CONTROLS 27
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
COMPRESSOR UNITS
COMPRESSOR
OPTIVIEW MOTOR
CONTROL
CENTER
CONDENSER
EVAPORATOR
(SHIPPING WIDTH)
LD07134
NOTES:
1. All dimensions are ft-inches (mm).
2. All dimensions are approximate. Certified dimensions are available on request.
3. For all waterboxes (compact boxes shown above), determine overall unit length by adding waterbox depth to tube sheet length.
4. Water nozzles can be located on either end of unit. Add 1/2 in. (12 mm) to nozzle length for flanges connections.
5. To determine overall height, add dimension "M" in ADDITIONAL OPERATING HEIGHT on page 28 for the appropriate isolator type.
6. Use of motors with motor hoods may increase overall unit dimensions.
28 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
Q3 Q4 2
COMPRESSOR EVAPORATOR-CONDENSER EVAPORATOR-CONDENSER
SHELL CODES SHELL CODE
SERIES 2*-2* 4*-4* 2*-2* 4*-4*
5'-0" 5'-2" 5'-0" 5'-2"
A
(1524) (1575) (1524) (1575)
6'-9 3/8" 7'-5/8" 6'-7 13/16" 6'-11 7/16"
B
(2067)" (2149) (2027) (2119)"
1'-3" 1'-3 1/2" 1'-3" 1'-3 1/2"
C
(381) (394)" (381) (394)
1'-3" 1'-3 1/2" 1'-3" 1'-3 1/2"
D
(381) (394) (381) (394)
12'-0" 12'-0" 12'-0" 12'-0"
E
(3658) (3658) (3658) (3658)
JOHNSON CONTROLS 29
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
30 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
NOTE: OAH B dimension based on WEG L5010-WPI for H9 compressor and WEG L5809 for K1 and K2 compressor.
All dimensions are ft-in. (mm).
JOHNSON CONTROLS 31
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
1-PASS
FRONT
OF
UNIT 1-PASS
NO. OF EVAPORATOR
A H PASSES IN OUT
A H
AA AA 1
H A
M C C M
COMPRESSOR END FLOOR LINE MOTOR END
FRONT
2-PASS
OF
UNIT
2-PASS
B J NO. OF EVAPORATOR
PASSES IN OUT
DD C K DD
C B
BB BB 2
K J
M C C M
COMPRESSOR END FLOOR LINE MOTOR END
3-PASS
FRONT
OF
UNIT 3-PASS
F N NO. OF EVAPORATOR
PASSES IN OUT
DD G P DD G N
BB BB
3
P F
M C C M
32 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
FRONT
2
OF
UNIT
1-PASS
SHELL CODE
IN OUT
AA HH
M–Z
HH AA
FLOOR LINE
FRONT
OF
UNIT
2-PASS
SHELL CODE
IN OUT
CC BB
M, N, P, Q
KK JJ
FLOOR LINE
FRONT
OF
UNIT
SHELL 3-PASS
CODES IN OUT
GG NN
M–Z
PP FF
FLOOR LINE
JOHNSON CONTROLS 33
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
34 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
ONE-PASS
B
A
TWO-PASS
A A
THREE-PASS LD07619b
JOHNSON CONTROLS 35
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
FRONT
OF
UNIT
ONE-PASS 7
L R CONDENSER
IN OUT
FLOOR L R
LINE
R L
FRONT
OF
OUT UNIT OUT
L R TWO-PASS 7
CONDENSER
IN IN IN OUT
L L
FLOOR R R
LINE
FRONT
OF
OUT UNIT OUT
L R
THREE-PASS 7
CONDENSER
IN OUT
IN IN
L R
FLOOR R L
LINE
LD07131b
COMPRESSOR END MOTOR END
NOTE: Front side of the unit is the OptiView Control Center mounted on the evaporator.
36 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
JOHNSON CONTROLS 37
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
A A
ONE PASS
B
A
TWO PASS
A A
LD07619b
THREE PASS
38 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
FRONT FRONT 2
OF UNIT OF UNIT
L R L R
COMPRESSOR END MOTOR END FLOOR LINE COMPRESSOR END MOTOR END FLOOR LINE
FRONT FRONT
OF UNIT OF UNIT
L R L R
COMPRESSOR END MOTOR END FLOOR LINE COMPRESSOR END MOTOR END FLOOR LINE
FRONT FRONT
OF UNIT OF UNIT
L R L R
COMPRESSOR END MOTOR END FLOOR LINE COMPRESSOR END MOTOR END FLOOR LINE
LD07175b
JOHNSON CONTROLS 39
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
40 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
F
LD01342B_1
JOHNSON CONTROLS 41
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
L R L R
L R L R
L R L R
LD07178b
42 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
JOHNSON CONTROLS 43
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
K
H J
LD01342C
44 JOHNSON CONTROLS
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
WEIGHTS
Table 7 - APPROXIMATE UNIT WEIGHT INCLUDING MOTOR FOR HYBRID FALLING FILM EVAPORATOR
UNITS
UNIT COMPRESSOR
SHIPPING WEIGHT, OPERATING WEIGHT, EST. REFRIGERANT 2
LB (KG) LB (KG) CHARGE, LB (KG)1
2C-2E Q3, Q4 10083 (4574) 12094 (5486) 690 (313)
4C-4I Q3, Q4, Q5, Q6, Q7 13458 (6104) 16492 (7481) 914 (415)
6A-6X Q5, Q6, Q7 15766 (7151) 20021 (9081) 1357 (616)
G-E P8, P9 20241 (9181) 22137 (10041) 1208 (548)
H-F P8, P9, H9 22525 (10217) 26591 (12061) 1377 (625)
K-K P8, P9, H9, K1 27139 (12310) 30212 (13704) 1811 (821)
L-L H9, K1 24342 (11041) 27766 (12594) 2181 (989)
M-K K1, K2 27459 (12455) 31295 (14195) 1919 (870)
N-L K1, K2 29138 (13217) 33387 (15144) 2322 (1053)
O-O H9, K1, K2 30639 (13898) 35238 (15984) 2338 (1060)
P-P H9, K1, K2 32539 (14760) 37497 (17008) 2849 (1292)
Q-Q K1, K2 34646 (15718) 41751 (18938) 2800 (1270)
R-R K1, K2, K3 37095 (16826) 45078 (20447) 3305 (1499)
S-S K3, K4 52471 (23800) 65080 (29520) 3267 (1482)
T-T K3, K4 56274 (25525) 70161 (31824) 3701 (1679)
U-U K3, K4 57220 (25955) 71984 (32651) 3417 (1550)
V-V K3, K4 61122 (27724) 77361 (35090) 3870 (1755)
V-W K4, K7 63659 (28875) 81292 (36873) 4396 (1994)
X-Y K4, K7 85185 (38639) 108946 (49417) 4915 (2229)
W-W K7 n/a n/a n/a
Y-Z K7 n/a n/a n/a
X-W K7 n/a n/a n/a
Z-Y K7 n/a n/a n/a
NOTE: 1Refrigerant charge quantity and weights will vary based on tube count and configuration. Use for reference only.
JOHNSON CONTROLS 45
FORM 160.76-N1
Section 2 - INSTALLATION
ISSUE DATE: 06/21/2019
Table 9 - CONDENSER MARINE WATERBOX WEIGHTS LB (KG) (TO BE ADDED TO STANDARD UNIT
WEIGHTS SHOWN IN TABLE 7)
SHIPPING WEIGHT OPERATING WEIGHT
UNIT COMPRESSOR INCREASE, LB (KG) INCREASE, LB (KG)
1-PASS 2-PASS 3-PASS 1-PASS 2-PASS 3-PASS
2P-23 Q3, Q4 496 (225) 286 (130) 462 (210) 1060 (481) 600 (272) 880 (399)
4P-45 Q3, Q4, Q5, Q6, Q7 634 (288) 411 (186) 600 (272) 1478 (670) 976 (443) 1384 (628)
6P-64 Q5, Q6, Q7 862 (391) 573 (260) 766 (347) 2062 (935) 1324 (601) 1742 (790)
E P8, P9 1380 (626) 643 (292) 1899 (861) 1944 (882) 1184 (537) 1352 (613)
F H9 1380 (626) 643 (292) 1899 (861) 1944 (882) 1184 (537) 1352 (613)
K H9, K1 1912 (867) 940 (426) 2686 (1218) 2711 (1230) 1712 (777) 1906 (865)
L H9, K1 1912 (867) 940 (426) 2711 (1230) 2711 (1230) 1712 (777) 1912 (867)
K K1, K2 1912 (867) 940 (426) 2686 (1218) 2711 (1230) 1712 (777) 1906 (865)
L K1, K2 1912 (867) 940 (426) 2686 (1218) 2711 (1230) 1712 (777) 1906 (865)
O H9, K1, K2 2088 (947) 1005 (456) 4042 (1833 4376 (1985) 1876 (851) 2292 (1040)
P H9, K1, K2 2088 (947) 1005 (456) 4042 (1833 4376 (1985) 1876 (851) 2292 (1040)
Q K1, K2 3496 (1586) 1823 (827) 6420 (2912) 6610 (2998) 3262 (1480) 3656 (1658)
R K1, K2, K3 3496 (1586) 1823 (827) 6420 (2912) 6610 (2998) 3262 (1480) 3656 (1658)
S K3, K4 3548 (1609) 1814 (823) 3658 (1659) 5828 (2644) 2626 (1191) 5517 (2502)
T K3, K4 3548 (1609) 1814 (823) 3658 (1659) 5828 (2644) 2626 (1191) 5517 (2502)
U K3, K4 3616 (1640) 1851 (840) 3734 (1694) 6103 (2768) 2736 (1241) 5762 (2614)
V K3, K4 3616 (1640) 1851 (840) 3734 (1694) 6103 (2768) 2736 (1241) 5762 (2614)
W K4, K7 5006 (2271) 2443 (1108) 4938 (2240) 8527 (3868) 3346 (1518) 7409 (3361)
Z K7 n/a n/a n/a n/a n/a n/a
Y K4, K7 5916 (2683) 2914 (1322) 5930 (2690) 9827 (4457) 4117 (1867) 9038 (4100)
46 JOHNSON CONTROLS
FORM 160.76-N1
ISSUE DATE: 06/21/2019
TEMPERATURE
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 7.22°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range
JOHNSON CONTROLS 47
5000 Renaissance Drive, New Freedom, Pennsylvania USA 17349 1-800-524-1330 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2019 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 160.76-N1 (619)
Issue Date: June 21, 2019
Supersedes: 160.76-N1 (419)