Centrifugal Liquid Chillers: Operations and Maintenance
Centrifugal Liquid Chillers: Operations and Maintenance
YMC2 Model A
with OptiView™ Control Center
8.1415 in
R-134a
Issue Date:
May 19, 2021
Form 160.78-O1
Issue date: 05/19/2021
Important!
Read before proceeding!
General safety guidelines
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
materials under pressure, rotating components, and rigging, installation, and operating/service personnel. It
both high and low voltage. Each of these items has the is expected that these individuals possess independent
potential, if misused or handled improperly, to cause training that will enable them to perform their assigned
bodily injury or death. It is the obligation and respon- tasks properly and safely. It is essential that, prior to
sibility of operating/service personnel to identify and performing any task on this equipment, this individual
recognize these inherent hazards, protect themselves, shall have read and understood the on-product labels,
and proceed safely in completing their tasks. Failure this document and any referenced materials. This in-
to comply with any of these requirements could result dividual shall also be familiar with and comply with
in serious damage to the equipment and the property in all applicable industry and governmental standards and
regulations pertaining to the task in question.
Safety symbols
The following symbols are used in this document to alert the reader to specific situations:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
Ensure power is removed from the input side of the VSD at all times when the chiller is under vacuum
(less than atmospheric pressure). The VSD maintains voltage to ground on the motor when the chiller
is off while voltage is available to the VSD. Insulating properties in the motor are reduced in vacuum
and may not insulate this voltage sufficiently.
2 JOHNSON CONTROLS
Form 160.78-O1
Issue date: 05/19/2021
Revision notes
Revisions made to this document are indicated in the following table. These revisions are to technical information,
and any other changes in spelling, grammar, or formatting are not included.
Associated literature
JOHNSON CONTROLS 3
Form 160.78-O1
Issue date: 05/19/2021
System nomenclature
Y M C 2 - S 0756 A A
YORK Mod level
Magnetic bearing Refrigerant R-134a
Centrifugal chiller Capacity in kW
S = Single stage
T = Two stage
Compressor nomenclature
M1 B - 197 F A A
Motor Gas path revision level
Motor design level Impeller design revision level
Impeller tip diameter (mm)
Rotation
F = Forward
R = Reverse
Vessel nomenclature
E A 25 14 271 B R 1 1 F C R
Inlet from front view
Vessel
R = Right
E = Evaporator
L = Left
C = Condenser
Heat exchanger mod level Waterbox type
C = Compact
Nominal inside diameter (inches)
M = Marine
Nominal length (feet) Water connection type
Marketing tube number F = Flanges
Tube code G = Grooved Standard
B = 3/4 in. Code 1 A = Victaulic AGS
C = 3/4 in. Code 2 Number of passes
D = 3/4 in. Code 3 Vessel refrigerant pressure code Water side pressure code
E = 3/4 in. Code 4 R = Code 180 1 = 150 psi
2 = 1 in. Code 1 S = Code 235 3 = 300 psi
3 = 1 in. Code 2 T = Code 300
4 = 1 in. Code 3 U = Code 350
5 = 1 in. Code 4 V = Code 400
4 JOHNSON CONTROLS
Form 160.78-O1
Issue date: 05/19/2021
Table of contents
SECTION 3 - MAINTENANCE..............................................................................................................................17
Renewal parts................................................................................................................................................. 17
Checking system for leaks.............................................................................................................................. 17
Leak testing during operation................................................................................................................. 17
Conducting R-22 pressure test........................................................................................................................ 17
Vacuum testing................................................................................................................................................ 18
Vacuum dehydration........................................................................................................................................ 19
Operation................................................................................................................................................19
Refrigerant charging........................................................................................................................................ 20
Checking the refrigerant charge during unit shutdown.................................................................................... 20
Handling refrigerant for dismantling and repairs............................................................................................. 21
Megging the motor.......................................................................................................................................... 21
Condensers and evaporators.......................................................................................................................... 21
General...................................................................................................................................................21
Chemical water treatment......................................................................................................................21
Cleaning evaporator and condenser tubes............................................................................................ 21
JOHNSON CONTROLS 5
Form 160.78-O1
Issue date: 05/19/2021
Tube fouling............................................................................................................................................21
Tube cleaning procedures......................................................................................................................22
Acid cleaning of tubes............................................................................................................................22
Testing for evaporator and condenser tube leaks.................................................................................. 22
Compressor..................................................................................................................................................... 23
Electrical controls............................................................................................................................................ 23
Maintenance inspections for YORK YMC2 chillers...........................................................................................24
Daily.......................................................................................................................................................24
Weekly....................................................................................................................................................24
Monthly (or more often as required)....................................................................................................... 24
Annually (more often if necessary)......................................................................................................... 24
SECTION 4 - TROUBLESHOOTING....................................................................................................................25
List of figures
List of tables
6 JOHNSON CONTROLS
Form 160.78-O1
Issue date: 05/19/2021
DIRECT-DRIVE
OPTIVIEW MOTOR
CONTROL COMPRESSOR
PANEL
MAGNETIC BEARING
CONTROLLER
CONDENSER
LIFTING
OPENINGS (4)
VSD
COOLANT
PIPING
LD14022
EVAPORATOR
COMPACT
WATER SIGHT
BOXES GLASS
System components
The YORK Model YMC2 Centrifugal Liquid Chiller The motor includes angular contact ball bearings only
is completely factory-packaged including evaporator, for control of the rotor during shutdown after rotation
condenser, compressor, motor, OptiViewTM Control is stopped or during shutdown due to loss of power to
Center, and all interconnecting unit piping and wiring. the magnetic bearings.
See Figure 1.
The bearing control center maintains proper shaft posi-
Compressor tion in the magnetic bearings and counts events where
the touchdown ball bearings may have been contacted
The compressor is a single-stage centrifugal type pow- during shaft rotation to alert the operation where a bear-
ered by a hermetic electric motor, on a common shaft ing check may be necessary. The condition of the touch-
with a cast aluminum, fully shrouded impeller. The im- down bearings can be assessed by qualified service tech-
peller is designed for balanced thrust and is dynamically nicians electronically without opening the unit.
balanced and over-speed tested. The compressor model
number includes gas path revision level at the end of the Ensure power is removed from the input
model string. Gas path revision level A includes pre-ro- side of the VSD at all times when the
tation vanes. Gas path revisions B has fixed inlet vanes. chiller is under vacuum (less than atmo-
spheric pressure). The VSD maintains
Motor voltage to ground on the motor when the
chiller is off while voltage is available to
The compressor motor is a hermetic permanent magnet
the VSD. Insulating properties in the mo-
high speed design with magnetic bearings. The com-
tor are reduced in vacuum and may not
pressor impeller is overhung from the end of the motor
insulate this voltage sufficiently.
shaft and has no bearings of it's own.
JOHNSON CONTROLS 7
Form 160.78-O1
Section 1 - System fundamentals
Issue date: 05/19/2021
Heat exchangers
Evaporator and condenser shells are fabricated from must be entered at chiller commissioning by a qualified
rolled carbon steel plates with fusion welded seams. service technician. Only a qualified service technician
Heat exchanger tubes are internally enhanced type. may modify these settings.
Evaporator While the chiller is shut down, the orifice will be pre
positioned to anticipate run. When the chiller is started,
The evaporator is a shell and tube, hybrid falling film,
if actual level is less than the level setpoint, a linearly
and flooded type heat exchanger. A distributor trough
increasing ramp is applied to the level setpoint. This
provides uniform distribution of refrigerant over tubes
ramp causes the setpoint to go from the initial refriger-
in the falling film section. Residual refrigerant floods
ant level to the programmed setpoint over a program-
the tubes in the lower section. Suction baffles are locat-
mable period of time. If the actual level is greater than
ed above the tube bundle to prevent liquid refrigerant
the setpoint upon run, there is no pulldown period,
carryover into the compressor. A 2 in. liquid level sight
it immediately begins to control to the programmed
glass is located on the side of the shell to aid in deter-
setpoint.
mining proper refrigerant charge. The evaporator shell
contains dual refrigerant relief valves unless condenser While the chiller is running, the refrigerant level is nor-
isolation is installed. mally controlled to the level setpoint.
8 JOHNSON CONTROLS
Form 160.78-O1
Section 1 - System fundamentals
Issue date: 05/19/2021
JOHNSON CONTROLS 9
Form 160.78-O1
Section 1 - System fundamentals
Issue date: 05/19/2021
Regardless of chiller compressor model, the chiller A final optional means to reduce capacity called hot
also has a mechanism called variable geometry dif- gas bypass (HGBP) is available regardless of compres-
fuser (VGD) at the exit of the impeller that was de- sor model. When selected for an application, HGBP is
signed to mitigate stall. Stall is an effect caused by used to re-circulate some refrigerant through the com-
slow refrigerant gas passing through the compressor at pressor without using it for cooling the chilled liquid.
reduced flow rates needed for low capacity operation. Although this does not reduce power consumption, it
Compressor models with gas path revision level B do greatly reduces the capacity of the chiller for maxi-
not have operating prerotation vanes, but use the VGD mum turndown.
also as a capacity control device instead.
The YMC2 uses these mechanisms in a controlled or-
der to maintain best efficiency.
10 JOHNSON CONTROLS
Form 160.78-O1
Section 1 - System fundamentals
Issue date: 05/19/2021
ROTOR COOLING
GAS VENT
(M1B-197FAA and M1B-205FAA)
COMPRESSOR
HOT GAS
BYPASS VALVE
PRE-ROTATION
VANES
DISCHARGE (M1B-197FAA and M1B-205FAA)
CHECK VALVE
SUCTION
DISCHARGE
LIQUID LEVEL
ISOLATION VALVE
VALVE
CONDENSER EVAPORATOR
SUCTION
BAFFLE
SUB-COOLER
JOHNSON CONTROLS 11
Form 160.78-O1
Issue date: 05/19/2021
12 JOHNSON CONTROLS
Form 160.78-O1
Issue date: 05/19/2021
Vent any air from the chiller waterboxes Throughout capacity control, the compressor speed is
before starting the water pumps. Failure maintained above the minimum required for the pre-
to do so will result in pass baffle damage. vailing head condition, to avoid surge. Otherwise, the
device maintaining capacity is controlled by a pro-
portional-integral-derivative control based on leaving
chiller liquid temperature. Pressure and motor current
overrides also apply as necessary to maintain operating
Start-up limits.
1. If the chilled water pump is manually operated,
Condenser water temperature control
start the pump. The Control Center will not al-
low the chiller to start unless chilled liquid flow The YORK YMC2 chiller is designed to use less power
is established through the unit. If the chilled liq- by taking advantage of lower than design temperatures
uid pump is wired to the Microcomputer Control that are naturally produced by cooling towers through-
Center the pump will automatically start, there- out the operating year. Exact control of condenser wa-
fore, this step is not necessary. ter such as a cooling tower bypass, is not necessary for
most installations. The minimum entering condenser
2. To start the chiller, press the RUN key on the
water temperature for other full and part-load condi-
Home Screen on the display panel.
tions is provided by the following equation:
For display messages and information pertaining
where:
to the operation of the OptiView™ Control Cen-
ter, refer to the YMC2 OptiViewTM Control Center ECWT = entering condensing water temperature
Operations Manual (Form 160.78-O2). LCHWT = leaving chilled water temperature
Any malfunctions which occur during At initial startup, entering condensing water tempera-
SHUTDOWN are also displayed. ture may be as much as 30°F (16.66°C) colder than the
standby chilled water temperature.
Min ECWT = LCHWT -30°F (16.66°C)
JOHNSON CONTROLS 13
Form 160.78-O1
Section 2 - System operating procedures
Issue date: 05/19/2021
An accurate record of readings serves as a valuable ref- 3. Check the entering and leaving chilled liquid tem-
erence for operating the system. Readings taken when peratures and evaporator pressure for compari-
a system is newly installed will establish normal condi- son with job design conditions on the SYSTEM
tions with which to compare later readings. Screen.
For example, an increase in condenser approach tem- 4. Check the condenser saturation temperature on
perature (condenser temperature minus leaving con- the SYSTEM Screen.. This temperature is based
denser water temperature) may be an indication of on the condenser pressure that is detected by the
dirty condenser tubes. condenser transducer.
5. Check the compressor discharge temperature on
Operating inspections the SYSTEM Screen. During normal operation
By following a regular inspection using the display discharge temperature should not exceed 220°F
readings of the OptiView™ Control Center, and main- (104°C).
tenance procedure, the operator will avoid serious op- 6. Check the compressor motor current on the SYS-
erating difficulty. The following list of inspections and TEM Screen.
procedures should be used as a guide.
Chiller Location
CENTRIFUGAL
LIQUID CHILLER LOG SHEET System No.
Date
Time
Hour Meter Reading
O.A. Temperature Dry Bulb / Wet Bulb / / / / / / / / / /
Discharge Temperature
ure
Compressor
pped)
PRV % Open (If equipped)
Input Power
% Input FLA
Motor
% Motor FLA
DC Bus Voltage
perature
Magnetic Bearing Motor Housing Temperature
Controller Rotor Elongation
L
Suction Pressure GA
IFU
Refrigerant Corresponding Temperature
perature
N TR
Small Temperature Difference 2 CE
C
Evaporator
Supply Temperature YM
Supply Pressure
Liquid
Return Temperature
Return Pressure
Flow Rate - GPM (If equipped)
Discharge Pressure
Corresponding Temperature
perature ...an Energy-Sa
Refrigerant
ving
mperature
Subcooler Liquid Temperature approach to you
r
Small Temperature Difference Service needs..
.
Condenser
Refrigerant Level
Issue Date:
Supply Temperature June 30, 2011
Form 160.78-MR1
Supply Pressure (611)
New Release
Liquid
Return Temperature
Return Pressure
Flow Rate - GPM (If equipped)
Remarks: Form 160.78-MR1 (611)
New Release
Issue Date: June 30, 2011
LD16236
* NOTE: A
pad of 50 log sheets can be ordered from your local Johnson Controls branch by
requesting Form 160.78-MR1.
14 JOHNSON CONTROLS
Form 160.78-O1
Section 2 - System operating procedures
Issue date: 05/19/2021
7. Check for any signs of dirty or fouled condenser To stop the chiller, complete the following steps:
tubes. The temperature difference between water
leaving condenser and saturated condensing tem- 1. Push the soft shutdown key on the Home screen
perature should not exceed the difference record- of the OptiViewTM panel. The compressor will
stop automatically. In the event of an unusual cir- 2
ed for a new unit by more than 4°F (2.2°C).
cumstance requiring immediate stoppage, a safety
Weekly stop switch is located on the side of the control
panel. Normal stop eases the driveline to stop and
• Check the refrigerant charge. See Checking the
should always be used instead of the safety stop
refrigerant charge during unit shutdown in Sec-
during regular operation.
tion 3 - Maintenance.
2. Stop the chilled water pump. If the pump is not
Monthly wired into the Microcomputer Control Center, it
• Leak check the entire chiller. turns off automatically. The actual water pump
contact operation depends on the selection on the
Semi-annually (or more often as required) SETUP screen.
• Check controls.
3. Open the switch to the cooling tower fan motors,
Annually (more often if necessary) if used.
1. Evaporator and Condenser. Prolonged shutdown
a. Inspect and clean water strainers. If the chiller must be shut down for an extended period
b. Inspect and clean tubes as required. of time, for example, over the winter season, complete
the following procedure:
c. Inspect end sheets.
1. Test all system joints for refrigerant leaks with a
2. Compressor Drive Motor. leak detector. If any leaks are found, they should
• Meg motor windings. be repaired before allowing the system to stand
for a long period of time.
3. Inspect and service electrical components as nec-
essary. During long idle periods, the tightness of the sys-
tem should be checked periodically.
4. Perform refrigerant analysis.
2. If freezing temperatures are encountered while
Need for maintenance or service the system is idle, carefully drain the cooling wa-
ter from the cooling tower, condenser, condenser
If the system is malfunctioning in any manner or the pump, and the chilled water system-chilled water
unit is stopped by one of the safety controls, see the pump and coils.
Operation Analysis Chart shown in Table 3 (Section 4
- Troubleshooting). After consulting this chart, if you Open the drains on the evaporator and condenser
are unable to make the correct repairs or adjustments liquid heads to ensure complete drainage. Drain
to start the compressor or the particular issue continues the VSD cooling system.
to hinder the performance of the unit, call the nearest
3. If freezing temperatures are encountered for peri-
Johnson Controls District Office. Failure to report con-
ods longer than a few days, the refrigerant should
stant troubles could damage the unit and increase the
be recovered to containers to prevent leakage
cost of repairs.
from O-ring joints.
Stopping the system 4. On the SETUP Screen, disable the clock. This
conserves the battery.
The OptiView™ Control Center can be programmed
to start and stop automatically (maximum - once each 5. Open the main disconnect switches to the com-
day) whenever required. Refer to the YMC2 OptiViewTM pressor motor, condenser water pump and the
Control Center Operation Manual (Form 160.78-O1). chilled water pump. Open the 115 V circuit to the
Control Center.
JOHNSON CONTROLS 15
Form 160.78-O1
Issue date: 05/19/2021
16 JOHNSON CONTROLS
Form 160.78-O1
Issue date: 05/19/2021
Section 3 - Maintenance
Renewal parts
For any required Renewal Parts, refer to the YMC2 Unit To test with R-22, complete the following steps:
Renewal Parts Manual (Form 160.78-RP1). 3
1. With no pressure in the system, charge R-22 gas
Checking system for leaks into the system through the charging valve to a
pressure of 2 psig (14 kPa).
Leak testing during operation
2. Build up the system pressure with dry nitrogen
The refrigerant side of the system is carefully pressure to approximately 75 psig to 100 psig (517 kPa to
tested and evacuated at the factory. 690 kPa). To be sure that the concentration of re-
frigerant has reached all parts of the system test
After the system has been charged, the system should
for the presence of refrigerant with a leak detector
be carefully leak tested with a R-134a compatible leak
at an appropriate service valve.
detector to be sure all joints are tight.
3. Test around each joint and factory weld. It is im-
If any leaks are indicated, they must be repaired im-
portant that this test be thoroughly and carefully
mediately. Usually, leaks can be stopped by tighten-
done, spending as much time as necessary and us-
ing flare nuts or flange bolts. However, for any major
ing a good leak detector.
repair, the refrigerant charge must be removed. See
Handling refrigerant for dismantling and repairs in 4. To check for refrigerant leaks in the evaporator
this section. and condenser, open the vents in the evaporator
and condenser heads and test for the presence of
Conducting R-22 pressure test refrigerant. If no refrigerant is present, the tubes
and tube sheets may be considered tight. If refrig-
With the R-134a charge removed and all known leaks
erant is detected at the vents, remove the heads,
repaired, the system should be charged with a small
locate the leak using a soap test or leak detector,
amount of R-22 mixed with dry nitrogen so that a ha-
and repair the leak.
lide torch or electronic leak detector can be used to de-
tect any leaks too small to be found by the soap test.
LD00949
JOHNSON CONTROLS 17
Form 160.78-O1
Section 3 - Maintenance
Issue date: 05/19/2021
*Gauge Absolute
Boiling
Inches of temperatures
mercury (Hg) Millimeters of
below one psia of mercury Microns water
standard (Hg) °F
atmosphere
*One standard atmosphere = 14.696 psia Notes: psia = lb per sq. in. gauge pressure
= 760 mm Hg absolute pressure at 32°F = Pressure above atmosphere
psia = lb per sq. in. absolute pressure
= 29.921 in. Hg absolute at 32°F
=S um of gauge plus atmospheric
pressure
Vacuum testing
Ensure power is removed from the input Figure 5 and start the pump. See Vacuum dehy-
side of the VSD at all times when the dration in this section.
chiller is under vacuum (less than atmo-
2. Open wide all system valves. Be sure all valves to
spheric pressure). The VSD maintains
the atmosphere are closed.
voltage to ground on the motor when the
chiller is off while voltage is available to 3. Operate the vacuum pump in accordance with
the VSD. Insulating properties in the mo- Vacuum dehydration in this section until a wet
tor are reduced in vacuum and may not bulb temperature of 32°F (0°C) or a pressure of 5
insulate this voltage sufficiently. mm Hg is reached. See Table 1 for corresponding
pressure values.
After the pressure test has been completed, the vacuum
test should be conducted as follows: 4. To improve evacuation circulate hot water, not
to exceed 125°F (51.7ºC) through the evapora-
1. Connect a high capacity vacuum pump, with in- tor and condenser tubes to thoroughly dehydrate
dicator, to the system charging valve as shown in
18 JOHNSON CONTROLS
Form 160.78-O1
Section 3 - Maintenance
Issue date: 05/19/2021
Vacuum dehydration
To obtain a sufficiently dry system, use the following
procedure to evacuate and dehydrate a system in the
field. Although there are several methods of dehydrat-
ing a system, this method produces some of the best
results and provides accurate readings as to the extent
of dehydration.
The equipment required to follow this method of de-
hydration consists of a wet bulb indicator or vacuum
gauge, a chart showing the relation between dew point
temperature and pressure in inches of mercury in a
vacuum (see Table 1), and a vacuum pump capable of LD00474
JOHNSON CONTROLS 19
Form 160.78-O1
Section 3 - Maintenance
Issue date: 05/19/2021
When this point is reached, practically all of the air system pressure is raised above the point correspond-
has been evacuated from the system, but there is still ing to the freezing point of the evaporator liquid. For
a small amount of moisture left. In order to provide water, the pressure corresponding to the freezing point
a medium for carrying this residual moisture to the is 29 psig (200 kPa) for R-134a (at sea level).
vacuum pump, nitrogen must be introduced into the
system to bring it to atmospheric pressure and the indi- While charging, every precaution must be taken to pre-
cator temperature will return to approximately ambient vent moisture laden air from entering the system. Make
temperature. Close off the system again, and start the up a suitable charging connection from new copper
second evacuation. tubing to fit between the system charging valve and the
fitting on the charging drum. This connection should
The relatively small amount of moisture left will be be as short as possible but long enough to permit suf-
carried out through the vacuum pump and the tem- ficient flexibility for changing drums. The charging
perature or pressure shown by the indicator should connection should be purged each time a full container
drop uniformly until it reaches a temperature of 35°F of refrigerant is connected and changing containers
(1.6°C) or a pressure of 5 mm Hg. should be done as quickly as possible to minimize the
loss of refrigerant.
When the vacuum indicator registers this tempera-
ture or pressure, it is a positive sign that the system Refrigerant is furnished in cylinders that contain ei-
is evacuated and dehydrated to the required limit. If ther 30 lb, 50 lb, 125 lb, 1,025 lb, or 1750 lb. (13.6 kg,
this level cannot be reached, it is evident that there is a 22.6 kg, 56.6 kg, 464 kg, or 794 kg) of refrigerant.
leak somewhere in the system. Any leaks must be cor-
rected before the indicator can be pulled down to 35°F Checking the refrigerant charge during
(1.6°C) or 5 mm Hg in the primary evacuation. unit shutdown
During the primary pulldown, makes sure that the wet The refrigerant charge is specified for each chiller
bulb indicator temperature does not fall below 35°F model in Table 2. Charge the correct amount of refrig-
(1.6°C). If the temperature is allowed to fall to 32°F erant and record the level in the evaporator sight glass.
(0°C), the water in the test tube will freeze, and the
The refrigerant charge should always be checked and
result will be a faulty temperature reading.
trimmed when the system is shut down.
Refrigerant charging Charge the refrigerant in accordance with the method
To avoid the possibility of freezing liquid within the shown in Refrigerant charging in this section. The
evaporator tubes when charging an evacuated system, weight of the refrigerant charged should be recorded
only refrigerant vapor from the top of the drum or cyl- after initial charging.
inder must be admitted to the system pressure until the
Estimated refrigerant
Compressor Evaporator Condenser
charge, lb (kg) 1
1 Refrigerant charge quantity and weights will vary based on tube count.
Refer to product drawings for detailed weight information.
20 JOHNSON CONTROLS
Form 160.78-O1
Section 3 - Maintenance
Issue date: 05/19/2021
JOHNSON CONTROLS 21
Form 160.78-O1
Section 3 - Maintenance
Issue date: 05/19/2021
22 JOHNSON CONTROLS
Form 160.78-O1
Section 3 - Maintenance
Issue date: 05/19/2021
of leakage, the corks may blow from the end of a 6. If any of the tube sheet joints are leaking, the leak
tube, indicating the location of the leakage. If not, should be indicated by the detector. If a tube sheet
if will be necessary to make a very thorough test leak is suspected, its exact location may be found
with the leak detector. by using a soap solution. A continuous buildup of
bubbles around a tube indicates a tube sheet leak.
4. After the tubes have been corked for 12 to 24
hours, have two people carefully test each tube at Compressor 3
both ends of the evaporator. One person can re-
move corks at one end of the evaporator and the Maintenance for the compressor assembly consists of
second person can remove corks at the opposite observing the operation of the compressor.
end and handle the leak detector. Start with the top If the control panel warns of excessive landings of the
row of tubes in the section being investigated. Re- magnetic bearing motor, notify the nearest Johnson
move the corks at the ends of one tube simultane- Controls office to request the presence of a Johnson
ously and insert the exploring tube for 5 seconds. controls Service Technician. The technician can assess
This should be long enough to draw into the de- the condition of the touchdown bearings using elec-
tector any refrigerant gas that might have leaked tronic tools.
through the tube walls. Place a fan at the end of
the evaporator opposite the detector. This ensures Electrical controls
that any leakage wi travel through the tube to the
detector. For information covering the OptiView™ Control
Center operation, refer to the YMC2 OptiViewTM Con-
5. Mark any leaking tubes for later identification. trol Center Operations Manual (Form 160.78-O2).
JOHNSON CONTROLS 23
Form 160.78-O1
Section 3 - Maintenance
Issue date: 05/19/2021
Maintenance inspections for YORK YMC2 Monthly (or more often as required)
chillers • Log and compare the VSD input voltage current
To avoid serious operating difficulty, follow a regular for balanced values in the readings.
inspection procedure. Use the following list of inspec- • Verify that the unit setpoints have not been
tions and procedures as a guide. changed. Check the setpoints in the Security Log
screen.
Daily
• Check the OptiView™ Control Center display. • Verify that the evaporator and condenser water
Log the date, time, run hours, and number of flows are within rated limits.
starts. • Check the operation of the motor starter. Monitor
• Use the daily log in the YMC centrifugal liquid
2 at unit start-up for any abnormalities.
chiller log sheet, Form 160.78-MR1, to log all of Annually (more often if necessary)
the unit operating data that is outlined in the log.
Use this data for the following comparisons: • For the evaporator and condenser, complete the
following inspections:
• Compare the entering and leaving condenser
water temperatures with the job design con- • Inspect and clean the water strainers.
ditions. Check the condenser water tempera- • Inspect and clean the tubes as required.
tures on the System screen.
• Inspect the end sheet.
• Compare the entering and leaving chilled
liquid temperatures and evaporator pressure • For the compressor drive motor, measure the mo-
with the job design conditions. Check the tor winding insulation resistance (megohm test-
chilled liquid temperatures on the System ing).
screen. • Check and tighten all of the electrical components
• Check the condenser saturation temperature as necessary
on the System screen. The condenser satu- • Clean and backflush the VSD heat exchanger.
ration temperature is based on the condens-
er pressure that is sensed by the condenser • Replace the VSD coolant.
transducer. • Perform refrigerant analysis.
• Check the compressor discharge temperature • For all HYP model VSDs, conduct a Smart Sensor
on the System screen. During normal opera- annual test.
tion, the discharge temperature does not ex-
ceed 220°F (104°C). • Review the operating data for trends that indicate
increasing vibration or power consumption.
• Check the compressor motor current on the
Compressor screen.
Weekly
• Check the refrigerant charge. See Checking the
refrigerant charge during unit shutdown.
• Check for any signs of dirty or fouled condenser
tubes. The temperature difference between the
water leaving the condenser and the saturated
condensing temperature must not exceed the dif-
ference recorded for a new unit by more than 4°F
(2.2°C).
24 JOHNSON CONTROLS
Form 160.78-O1
Issue date: 05/19/2021
Section 4 - Troubleshooting
Insufficient charge of
Temperature difference between leaving Check for leaks and charge refrigerant into system.
refrigerant.
chilled water and refrigerant in the
evaporator greater than normal with normal
Variable orifice
discharge temperature. Remove obstruction.
problem.
Temperature of chilled water too low with Insufficient load for Check capacity control operation and setting of low
low motor amperes. system capacity. water temperature shutdown setpoint.
Capacity control failed Check the PRV (if applicable), VGD, and hot gas
to load. bypass (if applicable) positioning circuits.
JOHNSON CONTROLS 25
Form 160.78-O1
Issue date: 05/19/2021
26 JOHNSON CONTROLS
Form 160.78-O1
Issue date: 05/19/2021
Temperature
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 27.2°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range
JOHNSON CONTROLS 27
5000 Renaissance Drive, New Freedom, Pennsylvania USA 17349 1-800-524-1330 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2021 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 160.78-O1 (521)
Issue Date: May 19, 2021
Supersedes: 160.78-O1 (820)