Ups Train3
Ups Train3
Supplier Document
IS BASE DE VIE
Document Title
Operating & Maintenance Manual
IFA
Purchaser review and comments shall not be assumed to indicate either responsibility or liability for accuracy
and completeness of this document or to alter any contractual terms and conditions.
Document Number
Rev
(Purchase Order Number - SDRL Code - Sequential No)
SF0004-N01-8203 01
Page 1 / 3 4A-1110148002/20GB: Rev.01
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
Here only revisions of descriptions in this «Operating & Maintenance Instructions» are
updated (Schematic diagrams, Parts lists, Battery documentation and Customer specific
documentation are excluded).
It is the responsibility of the client to exchange documentation in this «Operating &
Maintenance Instructions».
.
.
.
. Page 1 / 7 7RA9017GB: Rev.05
GENERAL INFORMATION
UNINTERRUPTIBLE POWER SUPPLY (UPS),
Type: PEW / PDW
TABLE OF CONTENTS:
1. Preface
2. General
3. Designation of the Products
4. Standards applied, Conformity
4.1 EU Conformity
4.2 Use according to Destination
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
1. PREFACE
This operation manual provides information about the erection, installation, commissioning and
operation of the system.
In the case of unsureties or special problems, it is not permitted to take unauthorized remedial
action. In such cases the responsible GUTOR technical service department must be contacted and
the required information obtained.
All agreements, assurances and legal relationships, as well as all obligations of GUTOR, also with
respect to the warranty provisions, shall be governed by the respective valid sales contract which is
not influenced by the content of the operation manual.
In the operation of an electrical device certain parts of the device are necessarily
under a hazardous voltage. The failure to observe warnings and incorrect or
inappropriate use can pose a risk and cause damage to persons and property.
Prerequisite to proper and safe operation of this device are correct transport and
storage, erection, installation and commissioning, as well as careful operation,
maintenance and repair.
Work on and manipulation of this device may therefore only be carried out by
qualified personnel.
Qualified personnel
are persons who, amongst other prerequisites
♦ are familiar with the erection, installation, commissioning and operation of the device and of
the system, which is being installed or in which the device is being installed;
♦ are capable of performing switching operations according to safety standards and are entitled
and authorized to switch the equipment on and off and to isolate it from the supply;
♦ are instructed according to the standards of safety in the care and use of the equipment;
Please read this operation manual thoroughly before you perform any
manipulations on the installation.
2. GENERAL
UPS systems are used to feed loads, which
♦ cannot tolerate any interruption in the supply;
♦ impose very strict demands regarding the voltage constancy;
♦ are sensitive to mains transients.
Decisive Features:
Characteristic Features Benefits
Modular and clearly arranged design ♦ Accessible from front and top for repair and
maintenance work
♦ Easy access to power modules, exchange
possible by one person only
High flexibility with respect to specific customer needs
Microprocessor controlled logic, intelligent real time fault ♦ Increased MTBF (Mean Time Between Failures)
analysis by means of built-in recording and monitoring unit — easy maintenance
Multifunctional digital indication, by which all adjustments and ♦ Transparent system operation
settings can be made via the password-protected foil ♦ Better control over the system functions
keyboard. Fault and status indications are also shown on the
same display.
Active mimic diagram on the front panel, adaptable to ♦ Become clear and peace of mind when the system
customer’s specification is in operation
Distinction between flashing new alarm and steady indication ♦ Precise fault diagnosis
of reset faults. Storage of the last 250 events in the memory.
As an option : System integrated communication interface ♦ Remote and easy system supervision
RS232
Independent microprocessor electronics for control and ♦ High integrated control logic, which contributes to
monitoring an increased UPS availability by the drastic
reduction of components and the omission of
internal interconnections.
Redundant PSU’s (power supply units), supplied from the AC ♦ Increased system reliability (reliability of operation)
input side and the DC intermediate circuit (where also the
battery is connected to).
Can be switched in parallel for redundancy or to increase the ♦ Each paralleled unit is autonomous, supplies its
power, with regulated load sharing. relevant current-share and has its own bypass
system. Except from the output busbar, no
To achieve redundancy or for increasing the system power, up common components or central units are required.
to 9 UPS modules can be paralleled. The extension can be ♦ An affected unit would immediately be isolated
made in different power graduations. from the output bus-bar.
♦ Active load sharing between the individual system
units.
Redundant components for parallel redundant operation (no ♦ Guaranteed power supply at all times
common failure points)
Fan monitoring ♦ Each individual longlife fan is monitored by means
of a Hall generator (insensitive to dust) and can be
exchanged in normal operation without danger to
personnel and load.
♦ N+1 fans
♦ Dual speed concept for noise reduction and
lifetime increase.
Temperature-compensated battery charging ♦ Maximising of the battery life
Battery testing programme & monitoring unit to show the ♦ Security and clarity about the function of batteries
remaining capacity and the actual back-up time on the display
Use of the latest semiconductor technology (MOSFET/ IGBT, ♦ optimal regulation of the output voltage
sine optimized pulse width modulation) ♦ short-circuit proof
Galvanic isolation of the consumers from the battery ♦ optimal protection for the consumers
Each additional segregated module (transport separation) includes a partly completed rating plate
without electrical specifications. The module numbering shall be consecutive from left to right.
Additional rating plates may be affixed within the same transport module in order to identify
different functional entities (e.g. different distributions)
EU Declaration of conformity:
Electric shock:
This warning sticker is affixed as close as possible to the terminals:
Behind this cover are storage capacitors with a discharge time of ≤ 5 min.
The following labeL is provided:
Connection diagram
A connection diagram is put into a schema pocket , mounted on the inside of the front door.
International Standards:
SN EN ISO 9001:2008 Quality Management System
SN EN ISO 14001:2004 Environmental Management System
OHSAS 18001: 2007 Occupational Health and Safety Management
4.1 EU Conformity
The product mentioned in this manual conforms to the relevant requirements to the appropriate EU
Directive, i.e. that this product meets all relevant EU directives and that it can be sold inside the
European Union without national commercial hindrances.
The EU conformity, which is indicated by means of the CE label on the name plate shall cease to
be valid if modifications are made to the equipment without the approval of GUTOR.
Relevant EU Directives for GUTOR are the so-called EMC- and Low Voltage Directives:
• EU Directive on Electromagnetic Compatibility 2004/108/EC
• EU Directive on Electrical Equipment designed for use within certain Voltage Limits
(Low Voltage Directive) 2006/95/EC
EN 62040-1 / EN 62040-2 are the EU harmonised product Standard applicable for UPS systems.
Unit with open electric connections are determined for building-in only.
This device fulfills the basic requirements of EN 62040-2. In a domestic environment, this product
may cause radio interference, in which case, the user may be required to take additional measures.
.
.
.
. Page 1 / 8 7RA9018GB: Rev.04
dou
TABLE OF CONTENTS:
1. General UPS Principle diagram
2. Explanation of the Components in the UPS Principle diagram
2.1 Connection Field
2.2 System Part
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
Q050
CONNECTION FIELD
Q004 BYPASS
X002 TEST
AUTO
B+/B-
X090 T090
BYPASS Q090 A035
F028
MAINS
PEW = L, N, PE X004
PDW = L1, L2, L3, EN LOAD
N, PE
PEW = L, N, PE
A030 L005 A032 PDW = L1, L2, L3,
N, PE
T001 L001 L002 T002
X001 Q001 F026 F021 A036
MAINS
L1, L2, L3, PE
EA
+
CB02
I U IDC IBatt U I I U E001...
CB03
A071 INTERFACE
A701
MASTER LOGIC P.C. Board
A070 CONTROLLER
= Option A024 (only connection), A025, A076, A077 & A078 are mounted in the low voltage section
The principle diagram on page 2 is a «MAXIMUM VERSION» and is divided into the following
two main parts:
• Connection field
• System part
These two parts are physically isolated from each other to make service and maintenance work
possible on a safer level.
Depending upon the system configuration, the breakers represented in the principle diagram can
be switch-disconnectors (fuse switch-disconnectors) or circuit breakers and the designation can be
made according to customer's request see «Single line diagram».
.
.
.
. Page 1 / 4 7RA9020GB: Rev.03
SAFETY REGULATIONS
UNINTERRUPTIBLE POWER SUPPLY (UPS),
Type: PEW / PDW
TABLE OF CONTENTS:
1. Technical Safety Information for the User
1.1 Safety Instructions / Precautions
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
Qualified personnel are technically instructed persons who, because of their training, experience
and position as well as their knowledge of appropriate standards, regulations, health and safety
requirements and working conditions, are authorised to be responsible for the safety of the
equipment, at all times whilst carrying out their normal duties and are therefore aware of, and can
report, possible hazards. [The definition of qualified employees is according to «International
Electrotechnical Vocubulary» (IEV) = IEC 60050].
Hazardous voltage
Failure to observe can kill, cause serious injury or material damage.
♦ Isolate from all AC mains and battery supplies before installation or dismantling work, as well
as for fuse changes or post installation modifications. IEC 62040-1-2, 4.9.3
prescribes: ISOLATE UNINTERRUPTIBLE POWER SYSTEM (UPS) BEFORE WORKING
ON THIS CIRCUIT
♦ Observe the prescribed accident prevention and safety rules for the specific application.
♦ Before putting into operation check if the rated voltage for the unit conforms with the local
supply voltage.
♦ Emergency stop devices must be provided for all applications. Operation of the emergency
stop must inhibit any further uncontrolled operation.
♦ The electric connections must be covered !
♦ Earth connection must be checked for safe function after assembly !
Danger:
Used for: Immediate threatening danger
Possible consequences: Can kill or cause grievous bodily harm
Warning:
Used for: Possible dangerous situation
Possible consequences: Can kill or cause grievous bodily harm
Caution:
Used for: Possible dangerous situation
Possible consequences: Insignificant physical injury. Also possible as warning
against material damage
Notice:
Used for: Possible dangerous situation
Possible consequences: Possible damage of the product or something in its
environment
Important:
Used for: Tips for use and helpful informations
Possible consequences: Not an information which warns against dangerous or
harmful situations !
When working inside the device or when isolating parts in the UPS system the
general safety recommendation and the local electrical regulations have to be
observed !
For compliance with the various safety regulations the following points which constitute a hazard
are mentioned:
As soon as the front door is opened the hazard of contact with parts at hazardous
voltages persists. Any operations inside the system must be carried out by
competent/authorized electrical personnel only. Extreme caution should be
exercised at all times.
Certain parts of the current circuit are live, even if the system is shut dwon. Before any part is
touched the circuit diagram must be studied and verification must be conducted with measuring
instruments.
If a fire should break out inside the system, fire extinguishers with CO2 must be
used. Do not inhale vapors.
ASSIGNMENT OF PERSONNEL:
When working under hazardous voltage do not allow personnel to work alone. A second person
should assist so that in the case of emergency help can be called for.
When working on the battery (measuring, topping up electrolyte) goggles, protective (rubber)
gloves, rubber apron and rubber boots shall be worn. Tools for working on the battery shall be
insulated. Refer to chapter on «Battery servicing».
If safety covers are provided, they are the provision for direct contact protection.
They shall prevent unintentional contact with parts at hazardous voltages. Special
caution is required at all times.
BYPASS A
A A
-X090
L1,L2 -Q090 -T090 -Q091
1~ 1~
PE
BYPASS MAINS A
-Q050
1x400V, 50Hz
BYPASS
V A
2PH, 2W
B TEST B
-P092 -P091 AUTO
EN
TO BYPASS A
SEE PAGE 4
-X001 -T001 -A030 -L011 -A015 -A032.. -L002 -T002 -A036
-F021
L1,L2 EA
L3 -Q001 3~ 1~ 1~
-Q060
3~ -F026
C PE 3~ C
-CB02 -CB03
-S031 VS AS -A031 -L012
MAINS INPUT A
3x400V, 50Hz
A A A V V/A/F
3PH, 3W
V/A -F027
V A
-P032 -P031
A
D D
-P026
-L005
-S001 -R001
-Q004
E B+,B- E
-X002 220V DC
SHT
F H-EB-085005A H-SWE-1003 F
BYPASS B
A A
-X090
L1,L2 -Q090 -T090 -Q091
1~ 1~
PE
BYPASS MAINS B
-Q050
1x400V, 50Hz
BYPASS
V A
2PH, 2W
B TEST B
-P092 -P091 AUTO
EN
TO BYPASS B
SEE PAGE 4
-X001 -T001 -A030 -L011 -A015 -A032.. -L002 -T002 -A036
-F021
L1,L2 EA
L3 -Q001 3~ 1~ 1~
-Q060
3~ -F026
C PE 3~ C
-CB02 -CB03
-S031 VS AS -A031 -L012
MAINS INPUT B
3x400V, 50Hz
A A A V V/A/F
3PH, 3W
V/A -F027
V A
-P032 -P031
A
D D
-P026
-L005
-S001 -R001
-Q004
E B+,B- E
-X002 220V DC
SHT
F H-EB-085005B H-SWE-1003 F
A BYPASS A DISTRIBUTION A A
H-EL-085005A
-Q100 -Q200 -K110
NC NC NC
FROM BYPASS A BUS A BUS B
SEE PAGE 2
INTERLOCK
B -Q300 -P101 -P102 -P103 -Q101 -Q135 -Q136 -Q155 B
NO A V Hz
RESPECT PROTECTIVE NOTE ISO 16016
DISTRIBUTION B
H-EL-085005B
-Q200 -K210
NC NC
D FROM BYPASS B BUS C BUS D D
SEE PAGE 3
-Q100
NC
E E
BYPASS B
F F
DISTRIBUTION A
BUS A BUS B
A A
B B
RESPECT PROTECTIVE NOTE ISO 16016
C C
D D
E E
F F
DISTRIBUTION B
BUS C BUS D
A A
B B
RESPECT PROTECTIVE NOTE ISO 16016
C C
D D
E E
F F
A DIGITAL METER
3~ 3~ STABILIZER A = AMMETER
MINIATURE CIRCUIT BREAKER 51 OVERCURRENT RELAY
V = VOLTMETER
B Hz = FREQUENCY METER B
S SELECTOR SWITCH
V/A/F MEASUREMENTS TO BE READ
FUSE SWITCH ON THE DISPLAY ELR EARTH LEAKAGE RELAY
A = AMMETER
C V = VOLTMETER C
Hz = FREQUENCY METER
CAPACITOR
GROUNDING LINK EF EARTH FAULT RELAY
CONTACTOR
.
.
.
. Page 1 / 12 7RA9026GB: Rev.04
FUNCTIONAL DESCRIPTION
UPS System with 3-position Manual bypass switch and
Static switches EA & EN,
Type: PEW / PDW
TABLE OF CONTENTS:
1. General Explanations
2. Operating Modes
3. Normal Operation
4. Battery Operation
5. Bypass Operation
6. Charger Only
7. Standby
8. Off
9. Manual Bypass
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
1. GENERAL EXPLANATION
Actuation Of «Switches»
Circuit breakers, switch-disconnectors (fuse switch-disconnectors), or changeover
switches, as well as any additionnal «switches» may only be actuated according to
the descriptions «Commissioning» and 7RA9118GB «Starting - Switching over -
Stopping».
Depending upon the system configuration, the switches represented in the sketches can be circuit
breakers, switch-disconnectors (fuse switch-disconnectors) and the designation can be made
according to customer's request see «Single line diagram».
2. OPERATING MODES
The UPS can be operated in different operating modes, depending on the availability of the rectifier
mains, bypass mains, battery voltage and actual load.
In the following the different operational modes and priorities for an UPS with the static switch EA &
EN are explained:
3. NORMAL OPERATION
At normal operation the manual bypass switch is always at position «AUTO».
The AC input (rectifier mains) feeds to the phase angle controlled rectifier via a matching
transformer. The rectifier compensates mains voltage variabilities as well as load deviations, and
maintains the DC voltage constant.
The rectifier supplies the inverter with energy and secures that the connected battery is kept on
standby (float charge and boost charge depend on the charging condition and on the type of the
battery).
The downstream inverter converts the DC voltage by means of optimized sinewave pulse width
control (PWM) into AC voltage and supplies the connected load via the static switch EA.
Fig. 1 The load is supplied from the inverter via the static switch EA
Concerns: Status:
Rectifier mains available & within the tolerance range
Q001 closed
Bypass mains available & within the tolerance range (may be outside the tolerance range)
Q090 closed
Q050 at position «AUTO»
Battery available & within the tolerance range (depending on the charging condition
of the battery — it may be in recharge mode).
Q004(Q005) closed
Rectifier ON
Inverter ON
Static switch EN OFF
Static switch EA ON
Output voltage within the tolerance range
If the supply of the load from the inverter is not secured, due to e.g. overload (> 150% 1 minute,
125% 10 minutes) or a fault in the inverter, the UPS will change over to bypass operation
for further information see section 5: «Bypass operation».
4. BATTERY OPERATION
At battery operation the manual bypass switch is always at position «AUTO».
In the event of power sags or failures the inverter is no longer supplied from the rectifier. The
battery which is connected to the DC intermediate circuit is called up automatically and without
interruption to supply the current.
The discharging of the battery is signalled. The battery voltage drops as a function of the duration
and the magnitude of the discharge current. The voltage drop is controlled by the inverter and thus
the UPS output voltage is kept constant.
If the limit of discharge of the battery is approached an alarm is activated. On mains recovery or on
emergency power generation by means of a diesel generator before the limit of discharge is
reached the system changes automatically back to normal operation, if not, the system will change
automatically to bypass operation, if the bypass mains is available and within the tolerance range.
If the bypass mains is not available or outside the tolerance range the system will shut down
automatically.
On mains recovery or on emergency power generation by means of a diesel generator the rectifier
starts up after 60 seconds and will charge the battery, if the UPS system is programmed for
«AUTOSTART» at mains recovery see «Technical data». If the system is not programmed
for «AUTOSTART» it has to be restarted manually see description 7RA9118GB «Starting
- Switching over - Stopping».
Depending on the depth of discharge of the battery the charge current is limited by means of the
battery current limitation.
Concerns: Status:
Rectifier mains outside the tolerance range
Q001 closed
Bypass mains available & within the tolerance range (may be outside the tolerance range)
Q090 closed
Q050 at position «AUTO»
Battery available & within the tolerance range
Q004(Q005) closed
Rectifier OFF
Inverter ON
Static switch EN OFF
Static switch EA ON
Output voltage within the tolerance range
5. BYPASS OPERATION
At bypass operation the manual bypass switch is always at position «AUTO».
This system part enables the consumers to be changed over without interruption to direct mains
power supply (bypass mains) under adherence to the specified tolerances. The change-over can
be initiated automatically by a control signal, or manually.
Every interrupt-free change-over, whether automatic or manual is normally only possible if voltage,
frequency and phase relation of the UPS system are synchronized to the bypass mains. Deviations
in the mains frequency outside the specified tolerance ranges inhibit normally a change-over. It is
possible to configure the UPS in such a way that the system can change over to bypass even when
it is not synchronized. In this case the change-over is made with a break of 10….20ms.
The manually change-over is only possible if the system is synchronized to the bypass mains.
Automatic change-over of the load to the bypass mains takes place when the power supply within
the specified tolerances is not assured by the inverters.
If a bypass mains fault occurs in this situation the system will automatically change over to normal
operation if the rectifier mains is available, otherwise a change-over to battery operation takes
place if the battery is available and within the tolerance range (occurs only if the system is manually
switched to bypass operation). Thereby, depending on the programming a short loss of the
output voltage can occur.
Fig. 3 Bypass operation due to automatic change-over. The load is supplied direct from
the bypass mains without disturbing the consumers at the safe bus.
Concerns: Status:
Rectifier mains outside the tolerance range (may be within the tolerance range)
♦ The UPS will also change to bypass if the inverter is in current limitation,
due to overload. The power supply of the inverter is not
guaranteed.
Q001 closed
Bypass mains available & within the tolerance range
Q090 closed
Q050 at position «AUTO»
Battery outside the tolerance range (may be within the tolerance range)
♦ The UPS will also change to bypass if the inverter is in current limitation,
due to overload. The power supply of the inverter is not
guaranteed.
Q004(Q005) closed
Rectifier OFF / ON (depending on the cause of the change-over)
Inverter ON / OFF (depending on the cause of the change-over)
Static switch EN ON
Static switch EA OFF
Output voltage within the tolerance range
If the overload any longer does not exist or a possible error is recovered, the UPS switches
automatically back to normal operation or battery operation.
Fig. 4 Bypass operation due to manual change-over. The load is supplied direct from the
bypass mains without disturbing the consumers at the safe bus.
MANUAL BYPASS
Q090 SWITCH Q050
BYPASS
MAINS
STATIC BYPASS
TEST
F028
SWITCHES AUTO
EN
RECTIFIER INVERTER
Q001 F021 LOAD
MAINS
EA
Q004
(Q005)
BATTERY
Concerns: Status:
Rectifier mains available & within the tolerance range
♦ Bypass operation was selected by means of the foil key board
Q001 closed
Bypass mains available & within the tolerance range
Q090 closed
Q050 at position «AUTO»
Battery available & within the tolerance range
♦ Bypass operation was selected by means of the foil key board
Q004(Q005) closed
Rectifier ON
Inverter ON
Static switch EN ON
Static switch EA OFF
Output voltage within the tolerance range
6. CHARGER ONLY
Fig. 5
MANUAL BYPASS
Q090 SWITCH Q050
BYPASS
MAINS
BYPASS
STATIC TEST
AUTO
F028 SWITCHES
EN
RECTIFIER INVERTER
Q001 F021 LOAD
MAINS
EA
Q004
(Q005)
BATTERY
Concerns: Status:
Rectifier mains available & within the tolerance range
Q001 closed
Bypass mains available & within the tolerance range (may be outside the tolerance range)
Q090 closed
Q050 at position «AUTO» — may be at position «TEST» or «BYPASS»
see section 9
Battery available (depending on the charging condition)
Q004(Q005) closed
Rectifier ON
Inverter OFF
Static switch EN OFF
Static switch EA OFF
Output voltage NO voltage (with Q050 at position «AUTO»)
7. STANDBY
Fig. 6 UPS ready for switching on
Concerns: Status:
Rectifier mains Í) available [at least one of the supplies Í) has to be available]
Q001 closed
Bypass mains Í) available [at least one of the supplies Í) has to be available]
Q090 closed
Q050 at position «AUTO» — may be at position «TEST» or «BYPASS»
see section 9
Battery Í) available [at least one of the supplies Í) has to be available]
Q004(Q005) closed
Rectifier OFF
Inverter OFF
Static switch EN OFF
Static switch EA OFF
Output voltage NO voltage (with qQ050 at position «AUTO»)
8. OFF
Circuit breakers, switch-disconnectors (fuse switch-disconnectors), or changeover
switches, as well as any additionnal «switches» may only be actuated according to
the descriptions «Commissioning» and 7RA9118GB «Starting - Switching over -
Stopping».
MANUAL BYPASS
Q090 SWITCH Q050
BYPASS
MAINS
STATIC BYPASS
TEST
F028
SWITCHES AUTO
EN
RECTIFIER INVERTER
Q001 F021 LOAD
MAINS
EA
Q004
(Q005)
BATTERY
Concerns: Status:
Rectifier mains not available
Q001 open
Bypass mains not available
Q090 open
Q050 at position «AUTO» — may be at position «TEST» or «BYPASS»
see section 9
Battery separated
Q004(Q005) open
Rectifier OFF
Inverter OFF
Static switch EN OFF
Static switch EA OFF
Output voltage NO voltage
9. MANUAL BYPASS
The manual bypass switch Q050 may only be actuated according to the
descriptions «Commissioning» and 7RA9118GB «Starting - Switching over -
Stopping».
Check therefore the fuse size of the main fuse at the UPS input (bypass mains) !
EN
RECTIFIER INVERTER
Q001 F021 LOAD
MAINS
EA
Q004
(Q005)
BATTERY
Concerns: Status:
Rectifier mains available
Q001 closed
Bypass mains available & within the tolerance range
Q090 closed
Q050 at position «TEST»
Battery available
Q004(Q005) closed
Rectifier ON
Inverter ON
Static switch EN ON / OFF
Static switch EA OFF / ON
Output voltage supplied direct from the bypass mains
Concerns: Status:
Rectifier mains not available
Q001 open
Bypass mains available & within the tolerance range
Q090 closed
Q050 at position «BYPASS»
Battery separated
Q004(Q005) open
Rectifier OFF
Inverter OFF
Static switch EN OFF
Static switch EA OFF
Output voltage supplied direct from the bypass mains
.
.
.
. Page 1 / 1 4A-1110148002/20GB: Rev.01
By using the key switch S102 / S202 the distribution load drop after 60 minutes battery operation
can be disabled.
The indication lamp H103 is showing that the timer is inactive and also an external potential free
signal is given at terminals X200 / X300 (NO).
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
.
.
.
. Page 1 / 1 4A-1110148002/20GB: Rev.01
Since the two UPS systems do not have to run (mandatory) synchronously, the parallel
connection of the outputs is not permitted. The tie breaker Q300 is foreseen to couple both
distributions in the case of a failure in one system or for maintenance works. This means
that the Distribution input switch Q100 of the faulty system must be opened before closing
the tie breaker Q300. As consequence of this, the actual distribution must can be volt-free
for a while, before closing the tie breaker (break before make).
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
.
.
.
. Page 1 / 11 7RA9072GB: Rev.06
TABLE OF CONTENTS:
1. Preparations before Packing
2. Packing: Air / Oversea Transport = Solid Wooden Cases or OSB (Oriented
Strand Board) Cases
3. Transport to the Installation Place
4. Unpacking from the Case
5. Storage
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 2 / 11 7RA9072GB: Rev.06
Usually one side of the system is open (due to 1. All doors are opened to equip the system
transport separation) with VCI-chip U
(VCI = Volatile Corrosion Inhibitor)
2. Every field is equipped with one or more chips
(chip-size = 49x100 cm).
3
3. One chip protects a volume of 1m . The number
of chips is calculated as follows:
Example:
3
Gross volume is 3m
3
Equipment / Material 1m
4. The chip is fixed with a cable binder Therefore, two chips are used.
5. Doors are closed
Now the system is prepared to be packed in the case. The lifting into the case is conducted
according to the instructions «Transport of the System without Packing» and the instructions given
in this description.
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 3 / 11 7RA9072GB: Rev.06
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 4 / 11 7RA9072GB: Rev.06
2. Protection against corrosion due to the effects of relative humidity and climatic factors
3. Protection against environmental factors (industrial exhausts, salt in the air, rain, snow, etc.)
4. Suitable for lifting and forwarding equipment (Unit Load Concept)
5. Possible frequent reloading and retransferring
6. Shipment over poor roads
7. Economy of volume
8. Protection of environment when handling hazardous material
9. Capability of recycling
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 5 / 11 7RA9072GB: Rev.06
The following representations correspond to a solid wooden case (the OSB cases
comprise instead of individual boards whole or max. 3 plates per side).
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 6 / 11 7RA9072GB: Rev.06
THE CONSTRUCTION AND DESIGN OF THE CASES ARE PRESENTED IN THE FOLLOWING
DESIGNS:
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 7 / 11 7RA9072GB: Rev.06
c Polyethylene edges:
for the protection and fixing of the system.
d Cross laths (cross-heads)
are determined by the length of the case
and the size of the system to be packed.
(Only equipped in cases containing small
systems or in case of projecting cables,
etc.).
e Compound foam material
for the protection of the system.
f Floor cross laths
for the distribution of the load outward
(lifting of the case with belts) under each
socket of the system one floor cross lath
is laid (not fixed).
GUTOR
XXXXX
1 2 3 4 5 6 7
This side up:
1 The case must always be stored, transferred, and transported in such a way that the
arrow always point up.
Fragile, handle with care:
2 Goods marked in this way must be handled with care and not dropped or tied under
any conditions.
Keep dry:
3 Goods marked in this way also have to be protected from high humidity, they must be
kept under covers when in storage (no unprotected outdoor storage).
Sling here:
4 The symbol indicates only where the sling should be applied, and not the method to
be used for applying it.
Center of gravity:
5 This symbol clearly identifies the center of gravity.
0 Kg stacking load:
6 The plywood and OSB cases are not stackable
GUTOR XXXXXX:
7 This stamp is on each case delivered from GUTOR whereby XXXXXX = the GUTOR
reference number of the system packed therein.
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 8 / 11 7RA9072GB: Rev.06
If required, additional markings are made according to the internal instructions Q470.002 or
according to the instructions of the client or of the case manufacturer.
The following representations correspond to a solid wooden case (the OSB cases
comprise instead of individual boards whole or max. 3 plates per side)
Sling here:
The symbols indicate only where the sling should be
applied, and not the method to be used for applying it.
Whenever the symbols are at an equal distance from
the middle of the center of gravity, the package will
hang straight if the suspensions are of the same length.
If not, the suspension on one side must be shortened.
Never follow this symbol for packages that have
obviously been incorrectly identified and/or designed.
Doing so could cause the packages to be dropped.
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 9 / 11 7RA9072GB: Rev.06
Center of gravity:
This symbol clearly identifies the center of gravity.
Reasonably the symbol should only be used when the
center of gravity is off-center in the package.
Application for the symbol on two surfaces
perpendicular to one another would be sufficient for
clear identification.
If any damage has penetrated the case, or if it is not received in upright position (look for indication
of this on the case), the shipper and the manufacturer should be notified immediately.
All boxes, cases, pallets, and other packages must be examined after unloading for visible and
apparent mechanical damage. Severely damaged packing or equipment should be left untouched
until the shipper and the insurance company have inspected it. Records must be kept on all
findings.
Any non-mechanical damage found, such as: boxes, cases, or other packages that are wet
through or very dirty must be recorded for a later inspection of their contents.
♦ In both cases, an authorized inspector, in consultation with the insurance company,
must make a determination of the actual situation.
♦ Photographs of the damaged containers should be taken as evidence.
In case of any defects the manufacturer should be notified immediately in order to avoid a delay in
the installation of the system.
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 10 / 11 7RA9072GB: Rev.06
♦ By means of a crowbar remove the cover (4). It is not necessary first to remove the cover skids
(9) — since these are fixed to the cover ( see above picture).
♦ By means of a crowbar remove the front wall (2) of the case. It is not necessary first to remove
the front skids (7) with which the side wall of the case is fixed to the pallet ( see above
picture).
♦ Now the system can be removed by means of a fork-lift. When lifting the prepacked system this
has to be made according to the instructions «Transport of the System without Packing» and
the instructions given in this description.
♦ Remove the VCI foil.
♦ Remove eventually delivered parts see first picture of this description.
♦ Open the front door and examine the interior of the system for any potential damage due to
mishandling of the system during transport. Notify the shipper and the manufacturer of any
such damage immediately. Proceed as mentioned under section 4.1.
♦ If the system is not going to be taken into use right away, put the VCI foil over the system
again to protect it against dust and moisture. If the system is going to be installed immediately
without storage, remove the VCI chip inside the system.
♦ Move the system to its installation place. (Remember, before the final placing mount the
ventilation grids see description «Erection — Installation» section 2.1).
PACKING & UNPACKING & STORAGE = AIR/SEA TRANSPORT Page 11 / 11 7RA9072GB: Rev.06
5. STORAGE
SYSTEM
If the system is not to be installed immediately, the cubicles included in the delivery should remain
in dry storage in their crates and protected against dust. Storage temperatures advantageously
should be between -10°C and +55°C (allowable max. -25°C and +70°C). This also applies
generally to all replacement material for the system.
If the humidity is very intense it can be necessary to operate heating facilities (optional) internal the
system until the system will be turned on.
The system is to be installed within 12 months after delivery and put into operation. After these 12
months the manufacturer must be consulted, who will explain the necessary additional precautions
(possibly commissioning by the manufacturer).
.
.
.
. Page 1 / 3 7RA9074GB: Rev.01
TABLE OF CONTENTS:
1. Transport: C-Rail mounted
2. Transport: Lifting Lugs mounted
Please note:
No part of this document may be reproduced or transmitted in any form or by any means —electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
CAUTION:
The lifting lugs have to be strained
perpendicularly.
70
40
125 C-Rail
5
25
Device socket
Device socket
When lifting systems with a rain roof (IPX1 / IPX2), the roof has first to be dismounted.
.
.
.
. Page 1 / 8 7RA9075GB: Rev.05
ERECTION / INSTALLATION
UNINTERRUPTIBLE POWER SUPPLY (UPS),
Type: PEW / PDW
TABLE OF CONTENTS:
1. General
2. Installation / Erection
2.1 IP Protection / Ventilation Grids
2.2 Placing
2.3 Cable Inlet
2.4 Parallel Operation Cables for 2 Redundant Systems
2.5 Parallel Operation Cables for 3 to 9 Redundant Systems
3. Ventilation
4. Connection / Protection
4.1 Earthing of the Cubicle
4.2 Mains Connection
4.3 Backfeed Protection
4.4 Battery Connection
4.5 Earthing of the Battery (for Systems with Battery)
4.6 Connection of the Load
4.7 External Protection
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
1. GENERAL
The following has to be considered in connection with the installation of the UPS system:
♦ System room
♦ Cable connection / cable interconnection
♦ Losses, ambient temperature, ventilation
♦ Connection / Protection
♦ Earthing of the cubicle
♦ Mains connection
♦ Connection of load / distribution
♦ 3-phase systems with SMPS load (increased neutral current)
In the following sections the general requirements for the installation of UPS systems is explained.
2. INSTALLATION / ERECTION
2.1 IP Protection / Ventilation Grids
Fit the ventilation grids on the front and the back ) of the device socket to the snap clip on both
sides by means of sheet metal screws M5,5 and the corresponding washers see Fig. 1.
If additional air filters and gland plates are to be mounted it is absolutely necessary
to displace the system to its definite place of erection before attaching the
) ventilation grids to the front, since a transport of the system with mounted air
filters and gland plates by means of a fork-lift or a pallet-truck is than no longer
possible.
When mounting the rain roof special attention must be paid to the fact that
no parts fall into the system. Besides, the rain roofs are not appropriate for a
load from top and the system may also not be lifted at the rain roof.
FIG. 1 Mounting of air filters and gland plates, as well as fixing of ventilation grids
(front and back)
2.2 Placing
The ventilation grids have in any case to be fixed on the back of the system
before it will be placed to the wall or back to back. see section 2.1.
The UPS system is built in a cubicle with a stable frame. On this frame heavy components such as
transformers, chokes, etc. are mounted. The frame can be placed direct on a levelled concrete
floor.
The UPS system can be placed with the backside to the wall or back to back (but a space of at
least 100mm must be ensured). If possible, preferably a distance of 500mm from the backside of
the system to the wall or between the systems (if these are placed back to back) should be
provided.
Above the top of the system a clearance of 500mm has to be provided to ensure sufficent space for
the air outlet in fig. 2 typical installations are shown.
3. VENTILATION
Attention must be paid to the heat that is to be removed which is generated by the power losses of
the system. The inlet and outlet of air must be ensured, otherwise the system can produce an
alarm due to overheating, or even shut down. Therefore the ambient temperature stated in the
«Technical Data» is to be observed. Alarm indication is given if the temperature of the power
components exceeds the permitted level.
Objects which obstruct ventilation or which are easily combustible should under no circumstances
be placed on, under or very near the system.
If the system is placed with the backside to the wall or back to back, a space of at least 100mm has
to be guaranteed.
The necessary quantity of air cooling per hour depends on the one side on the total developed
power dissipation, i.e. from the size and number of installed UPS systems, and on the other side on
the possible resp. permitted warming of the cooling air. The permitted warming of the cooling air is
the difference between the admissible ambient temperature (e.g. 30° C) and the incoming
temperature of the cooling air into the room (e.g. 25° C).
4. CONNECTION / PROTECTION
4.1 Earthing of the Cubicle
The system cubicle must be earthed, for which purpose earth bars/terminals are provided inside
the system.
The person carrying out the work must be an authorised installation electrician.
The fuse protection and the wire cross section of the mains connection can be seen in the
«Technical Data», however, only if these meet also to the local electrical regulations.
The rectifier mains input and the bypass mains input must be protected by external fuses or
MCCB’s.
All AC mains supply connections are provided with suitable isolators of the contactor type
according to IEC 60947, to prevent the occurrence of any hazardous voltages at these terminals in
the case of AC mains failure due to backfeed from the inverter operating in the stored energy
mode.
All required backfeed contactors in AC mains AND AC bypass path are provided
All AC mains supply connections have to be provided with suitable isolators of the type MCCB,
switch according to IEC 60947, to prevent the occurrence of any hazardous voltages at these
terminals in the case of AC mains failure due to backfeed from the inverter operating in the stored
energy mode.
When the backfeed protection isolator is external to the UPS, the type and rating of this suitable
isolating device is specified in the «Technical Data».
For permanently connected UPS where automatic backfeed isolation is provided external to the
equipment, the instructions shall require the fitting by the user of a warning label on all primary
power isolators installed remote from the UPS area to warn electrical maintenance personnel that
the circuit feeds an UPS.
One or more required backfeed isolators are not provided internally and must
be provided externally.
In addition, the conditions for the rectifier incoming feeder fuse (mains) can be seen in the
«Technical data».
CIRCUIT BREAKER
We recommend when inserting circuit breakers between the busbar and the consumer, to choose
such a type that its rated current not exceeds 15% of the nominal current of the system (voltage
drop over the line between UPS system and consumer max. 3%).
.
.
.
. Page 1 / 3 7RA9195GB: Rev.01
ASSEMBLY OF
PARTICULAR CUBICLE UNITS
TABLE OF CONTENTS:
1. Provided Material per Cubicle Separation
2. Procedure
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
fig. 1:
2. PROCEDURE
1. Place Cubicle unit A) and install the 6 hexagon bolts by means of the screws and the
tooth lock washers (total 6 pieces of connections per cubicle separation = 3 pieces in
front and 3 pieces in the back, i.e. for each 1 piece in the upper, middle and lower
cubicle unit). see fig. 2.
3. Couple Cubicle unit A) with unit B) by means of the remaining 6 screws through the
hexagon bolts and tighten all screws in accordance with the recommended torque.
see fig. 3.
fig. 2:
Always two cubicle units are screwed together in the cubicle inside in accordance with following
figure.
fig. 3:
Hexagon head-fit screws
M8 x 20
.
.
.
. Page 1 / 10 7RA9076GB: Rev.05
TABLE OF CONTENTS:
1. Display unit
2. Change of Operational Parameters
3. Measurements on the Display
4. Alarms on the Display
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
1. DISPLAY UNIT
On the front of the UPS there is a display unit. It
consists of a LC display, an alarm LED, an acoustic
alarm and a Foil keypad (as shown on the left).
If however, a change in the operational mode occurs the display immediately switches over to
show the new operational mode.
In this case the entries have to be repeated by means of the Foil keypad for the system
programming or reading of information.
The following is a description of information which can be shown on the display, as well as
instructions to the programming/setting up, which can be performed by the user.
To enter the «operational parameter» stack push and step inside the stack with the cursor
key or .
Second Language
It is possible to choose between 2 languages: GB + CZ / DE / DK / ES / FI / FR / HU / IT / NL / NO
/ PL / PT / RU / SE / SK, or DE + RU. One of the languages will always be English (exception:
German + Russian), the other one can be chosen by the customer when ordering the system. The
optional language is chosen by pushing and step inside the stack with the cursor key
return to English language on the display push for «Second language OFF».
Autostart
To program the system for autostart, push and step inside the stack with the cursor key
If Autostart is chosen the system will restart automatically at mains return, e.g. if the system has
switched off due to low battery voltage after battery operation during a mains failure.
Bypass Operation
To switch the system to bypass operation push and step inside the stack with the cursor
Bypass operation is chosen by pushing for «ON», the system then switches to bypass if
the bypass mains is within the tolerance range. The display then shows: .
The load is now supplied from the bypass mains via the static switch EN. The bypass mains
voltage and the output voltage are still shown.
The system can be switched back to normal operation by pushing to set bypass operation
«OFF».
The load transfer from normal to bypass operation and vice versa takes place without any
interruption.
Boost Charge
To program the system for boost charge, push and step inside the stack with the cursor
Boost charge is chosen by pushing for «ON», and rejected by pushing for «OFF».
When boost charge is selected the system will only stay in the boost charge operational mode for
the time which has been preprogrammed by the factory. Boost charge is programmable between 0
and 24 hours for any change contact our works.
To program the system for auto boost charge, push and step inside the stack with the
charge is chosen by pushing for «ON», and rejected by pushing for «OFF».
When Autoboost is selected the system will automatically switch over to boost charge operation if
the battery has been discharged. The systems stays in boost charge operation for the time which
has been preprogrammed by the factory. This time is the time while the charger is outside the
battery current limitation. Boost charge is programmable between 0 and 24 hours for any
change contact our works.
For testing the battery capacity from the Foil keypad proceed as follows: push and step
the display, where «xxx» is the back-up time of the last test — if not performed before or if the test
has been aborted, «???» is shown. Push to abort or to continue. The display
shows: , where «time > …min.» is only shown if option «Advanced battery
and a short alarm has been activated. Push and until the display
Please note that after a battery capacity test it will take about 8...24 hours (depending on the
battery type) before the battery is recharged and the full back-up time is available again.
To perform the battery monitor test push and step inside the stack with the cursor key
This function checks the battery condition by switching off the rectifier and let running the inverter in
battery operation until 25% of the battery capacity are used up.
The rectifier will automatically switch on again after the test is finalized or if a fault in the battery has
been detected no loss of the output voltage.
If the battery condition is within the tolerance range no alarm is shown on the display.
If the battery capacity is reduced, one of the following two alarms is shown on the display:
To reset the battery monitor push and step inside the stack with the cursor key or
push .
Adaptive Slewrate
To program the system for adaptive slewrate, push and step inside the stack with the
cursor
If adaptive slewrate mode is chosen the system will automatically select its lowest slewrate with
which it can synchronize to the mains. In the case of many mains variations the system
automatically select the maximum allowable slewrate to ensure that the system remains
synchronous to the mains.
To set the current date in the system, push and step inside the stack with the cursor key
To set the current time in the system, push and step inside the stack with the cursor key
Remember when entering the seconds, the clock is only activated when the confirmation
In the case of single phase UPS systems only the value on the right-hand side
of the window is indicated.
To return to normal status indication wait 30secs or push: . The display shows the current
operational mode.
The acoustic alarm is also activated, but only for 30 seconds. If the alarm disappears in less than
30 seconds the acoustic alarm will stop. If two or more alarms overlap each other, the acoustic
alarm will be activated for further 30 seconds with effect from the arise of the last alarm.
The alarm LED indicates that there is an alarm in the «alarm» stack. The stack contains those
alarms, which at the time in question exist. The alarms are placed in the stack in the same
succession as they arose, indicating the last alarm at first.
To read alarms in the «alarm» stack push and move inside the stack with the cursor key
The alarms are only present in the alarm stack as long as the red «Common Alarm LED» is on.
To enter the «log alarm» stack push and simultaneously and move inside the
stack by means of the cursor key or until the desired event is shown. The last text
The system will log the alarms shown in the alarm stack and at the same time the following
changes in the operational modes:
To check the time for the events go to the actual event by means of the cursor key as mentioned
before. At the actual event push and the time where the actual event happened will be
shown on the display with «year, month, day / hours, minutes, seconds».
The log alarm stack can be cleared by keying in the password: 920701. Push simultaneously
Key in the password 920701 and the alarm log will be cleared and the display will show:
.
.
.
. Page 1 / 11 4A-1110148002/20GB: Rev.01
TABLE OF CONTENTS:
1. Front panel
2. Operation
3. Operating Status Indications
4. Alarm Indications
4.1 Alarm Indication Concept
4.2 Description of the Individual Alarms
4.3 Common Alarm
4.4 Potential-free Relay contacts
5. Analogous Instruments / Switches
6. External Connection P.C.Board
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
OPERATING & INDICATING ELEMENTS (FRONTPANEL — Control- and Monitoring Board) Page 2 / 11 4A-1110148002/20GB: Rev.01
by Schneider
ALARM INDICATION
OPERATING & INDICATING ELEMENTS (FRONTPANEL — Control- and Monitoring Board) Page 3 / 11 4A-1110148002/20GB: Rev.01
The Front panel (Control and Monitoring board) is divided up in the following functional sections:
2. OPERATION
Pos. Designation Explanation
S1 SYSTEM ON Push-button for turning on the entire system.
by Schneider
S2 OFF Push-button for turning off the entire system. For this
function the push-button «OFF» (S2) must be pressed
at the same time as push-button «SYSTEM ON» (S1).
4. ALARM INDICATIONS
4.1 Alarm Indication Concept
The alarm indication concept enables a more precise fault diagnosis because of the distinction
between first alarm, further alarm, permanent fault and transient fault.
INDICATION CRITERIA:
a) 1st value indicator: The first arriving alarm is indicated as a «rapidly flashing» 1st
(rapidly flashing) value and will be memorized.
b) Further alarm: If further alarms follow, they will illuminate «slowly flashing».
(slowly flashing)
c) Permanent alarms: These are alarms already reset (1st value or further alarms)
(Steady indication) which are still present.
ALARM RESET:
Designation Explanation
RECTIFIER MAINS FAULT The indication illuminates if one or more phases of the mains voltage as
(30 s) well as the frequency are out of tolerance.
For tolerances see «Technical Data».
RECTIFIER FAILURE The indication illuminates only, if all the following events occur
(5 s) simultaneously:
the rectifier mains is ok,
the rectifier is not operating in current limitation,
and the rectifier voltage drops below the level «DC low - alarm». For
tolerances see «Technical Data»;
or in case of overtemperature on the rectifier power units.
DC OUT OF TOLERANCE The inverter is shut-down, since the DC voltage is out of the tolerance
(5 s) range of «DC low - shut-down» or «DC high - shut-down».
For tolerances see «Technical Data».
RECTIFIER FUSE BLOWN The rectifier fuse F026(F027) has blown.
(5 s)
Designation Explanation
BATTERY OPERATION The energy for the inverter is supplied from the battery.
(30 s)
BATTERY DISCHARGED The battery voltage is dropped below «DC low - alarm»
(5 s) For tolerances see «Technical Data».
BATT. DISCONNECTED The battery is disconnected from the system, i.e. the battery fuse or switch
(5 s) has released. If a battery MCCB is inserted, this indicates whether the
MCCB has tripped or manually been disconnected.
EARTH FAULT DC The DC earth fault current for the battery positive (+) or negative (-) has
(5 s) exceeded the alarm level.
For tolerances see «Technical Data».
INVERTER FAULT The indication illuminates only, if all the following events occur
(5 s) simultaneously:
inverter switched on
inverter not overloaded
inverter output voltage out of the tolerance range. For tolerances
see «Technical Data»;
or inverter switched off;
or in the case of overtemperature on the inverter power units.
OVERLOAD INV/BYPASS Overload at the inverter or bypass. (Overload = > 100% load).
(30 s)
INVERTER FUSE BLOWN One or more of the inverter fuses have blown or the inverter input switch
(5 s) (option) is open.
ASYNCHRONOUS The inverter is asynchronous to the bypass mains.
(30 s)
BYPASS MAINS FAULT The bypass mains voltage or the frequency, measured at the input of the
(30 s) static switch EN, is out of tolerance
For tolerances see «Technical Data».
MANUAL BYPASS ON The manual bypass switch is in position «BYPASS». If a switch with 3
(5 s) switching positions is equipped, in position «TEST» or «BYPASS».
EN INHIBITED The mains-side static switch EN is inhibited if:
(30 s) the bypass mains voltage is out of tolerance,
the bypass mains frequency is out of tolerance, or
overtemperature at the static switch EN
For tolerances see «Technical Data».
EA INHIBITED The inverter-side static switch EA is inhibited, if:
(5 s) the inverter voltage is out of tolerance, or
overtemperature at the static switch EA
For tolerances see «Technical Data».
OVERTEMPERATURE The following elements have a thermal monitoring:
(5 s) Rectifier bridge
Rectifier transformer
DC choke
Power module
Inverter transformer
AC choke
Static switch EN
Static switch EA
FAN FAILURE One or more fans in the system have failed.
(30 s)
Designation Explanation
POWER SUPPLY FAULT One of the electronic supplies (+5V/±12V/+20V) is out of tolerance, or the
(5 s) feeding of one of the power supplies is not available (Rectifier / Bypass
mains or DC).
DISTRIBUTION A MCB ♦ One or more of the MCCB’s in the AC distribution A are open
OPEN ♦ Overload on one of the feeders or short-circuit
(5 s)
DISTRIBUTION B MCB ♦ One or more of the MCCB’s in the AC distribution B are open
OPEN Overload on one of the feeders or short-circuit
(5 s)
DISTR. TIE BREAKER ♦ The Tie breaker Q300 is manually closed due to a failure in one of the
CLOSED UPS or for maintenance works.
(5 s) ♦ For further explanation see chapter 3: «Explanation of the Tie
Breaker Q300».
DISTRIBUTION BUS B Bus B (MCB's Q136...Q155) is disconnected from Distribution A
DISCONNECTED Contactor K110
(5 s)
DISTRIBUTION BUS D Bus D (MCB's Q236...Q255) is disconnected from Distribution B
DISCONNECTED Contactor K110
(5 s)
L1 L3
L2 L0
PH1 OFF
014 2 2
Not used
1 1
X002
021
Common fault
022 Alarm: 021-022 closed
4 blue
024 Battery temperature sensor
3 brown
X003 X007
031 Battery operation 2
(30secs delay) Battery «MCCB»
032 Alarm: 031-032 closed 1
034
X004
041 3 Remote Start/Stop
Static switch EN
042 041-042 closed, when system in bypass operation 2 1 «ON»
2 «OFF»
044 X005 1 3 «common» (closing contacts)
SW01
4 Emergency shut down, if closed – internal
3 supply (for this function insert jumper SW01)
2 Emergency shut down, if external supply
X009 X011 12 VDC (8mA) or 24 VDC (15mA) is
1
X006 removed from terminals
(for use this function: remove jumper SW01 and
remove wire jumper on X006:3-4)
1 2 3 4 1 2 3 4
Not used
Not used
ATTENTION:
Not used Jumper SW01 is normally
Not used inserted as per default
.
.
.
. Page 1 / 2 7RA9078GB: Rev.02
COMMUNICATION INTERFACE
UNINTERRUPTIBLE POWER SUPPLY (UPS),
Type: PEW / PDW
TABLE OF CONTENTS:
1. General
2. Connections / Facilities
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
1. GENERAL
The communication interface - having 3 ports - is used when an interaction between UPS and e.g.
a computer system has to be established. The main purpose is to ensure a controlled shut-down of
the computer in case of failures in the mains power supply.
RS232: J1 & J2
These interfaces consist of a galvanic isolation, which is typical for a communication over longer
distances.
Informations about the system condition and typical measured values are available on these serial
interfaces for further informations a protocol can be provided on request.
2. CONNECTIONS / FACILITIES
.
.
.
. Page 1 / 10 7RA9199GB: Rev.07
TABLE OF CONTENTS:
1. INTRODUCTION
2. CONFIGURING MODBUS CONVERTER
2.1 Switch Block 1 — Baud Rate, Parity settings, MODBUS mode, 2/4 wire configuration, etc.
2.2 Switch Block 2 — ID Address configuration and protocol version
2.3 Switch Block 3 — Serial RS485 output termination
2.4 J6 — RS232 Port Pinout
3. MODBUS ADDRESSING INFORMATION
3.1 Function call 01: Read Coils Registers Status Table
3.2 Function call 03: Read Holding Registers Table
4. PHYSICAL INTERFACES
4.1 Dimensions of PCB board
4.2 J1 — RS485
4.3 J2 — Digital Inputs
4.4 J3 — Analogue Inputs
4.5 J4 — Power
4.6 J5 — RS232 (UPS)
4.7 LED indications
4.8 SW4 — Reset Switch
5. PCB LAYOUT
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
1. INTRODUCTION
MOD-LINK is a device used to convert the GUTOR Communication Protocol on RS232 to the
MODBUS Protocol on RS485, with the addition of a number of other inputs outlined below.
The exact configurations based on the various dip switch settings are shown below. The dip
switch positions ON and OFF are marked on the switch blocks on the MOD-LINK unit.
a) Dip switches 1, 2 and 3 are used to configure the baud rate of the unit in the following
combinations:
Switch combination Baud rate Dip Switch 1 Dip Switch 2 Dip Switch 3
0 300 OFF OFF OFF
1 600 ON OFF OFF
2 1200 OFF ON OFF
3 2400 ON ON OFF
4 4800 OFF OFF ON
5 9600 ON OFF ON
6 19200 OFF ON ON
7 38400 ON ON ON
The default baud rate is 9600 bps, means dip switches 1 and 3 are ON, and dip switch 2 is OFF.
b) Dip Switch 4: Used to set the Parity mode (ON = Enable, OFF = Disable). Default setting
is OFF.
c) Dip Switch 5: Used to set the Parity state (ON = Odd, OFF = Even). Default setting is
OFF.
d) Dip Switch 6: Used to set the MODBUS Serial Transmission Mode (ON = ASCII, OFF =
RTU). Default setting is OFF.
e) Dip Switch 7: Used to set the Physical RS485 connection type (ON = Four wire, OFF =
Two wire). Default setting is ON.
f) Dip Switch 8: Used to set the UPS Type, (ON = SDC, OFF = XXW). Note: The UPS type
XXW includes all AC UPS types PEW, PDW, WEW and WDW. Default
setting is OFF.
a) The ID address will be configured with the dip switches 1-7 as follows:
The ID address range is 1-127. Address 0 is for factory purposes and shall not be used. The
default address is 1, means dip switch 1 is set to ON, and dip switches 2-7 are set to OFF.
b) The GUTOR Communication Protocol version being monitored on the primary input side is
set with dip switch 8. The default GUTOR Communication Protocol version setting is V.08,
means dip switch 8 is set to ON. For GUTOR Communication Protocol version setting V.05,
means setting OFF, please first consult GUTOR.
The default setting for termination is 4 Wire, means all 4 dip switches are set to ON.
3 = RX 2 = RX
2 = TX 3 = TX
The default setting is 2 = RX and 3 = TX. This setting must not be changed.
Coil
Register Format Parameter Notes
UPS will transfer to bypass if mains/bypass is within limits. If
00001 B Output voltage out of range mains/bypass voltage is out of range UPS will shut down after
timeout of undervoltage timer.
00002 B Battery operation UPS is running on battery until Battery voltage low is reached
UPS is operating on bypass, either chosen by user (where
00003 B Bypass operation
applicable) or because of an alarm condition.
Battery voltage low (Low
00004 B Indicates battery depleted and UPS will shut down.
DC shutdown)
Battery voltage high (High UPS will at first transfer to battery and if battery voltage high
00005 B
DC shutdown) condition persist, UPS will transfer to bypass operation.
Common alarm bit for all alarms in UPS. If cleared consider as "UPS
00006 B Common fault
OK" condition.
UPS is overloaded. If condition persists for longer period of time UPS
00007 B Output current > 100%
will either transfer to bypass or shut down.
Static Switch temp. > Either mains or bypass static switch has temperature alarm. UPS will
00008 B
100°C switch operating mode accordingly.
The UPS is turned on by user. Status information bit set for all
00009 B System pushed on
operating modes and cleared only when UPS is turned off again.
Status information bit set when inverter is off or operating in bypass
00010 B Inverter off
and cleared when in normal or battery operation.
00011 B System not synchronized UPS inverter output is not synchronized to bypass input supply.
Battery charge current limit Status bit that the battery charge current is being limited by the UPS.
00012 B
(no common alarm) This alarm will not trigger a common alarm.
00013 B Turn beeper on pulse Flag set for one second every time a new error is set.
00014 B Reserved
00015 B Reserved
00016 B Battery test active "Battery monitor test" or "Battery capacity test" is active running.
00017 B Reserved
Mains transformer UPS switches operating mode according to actual system to protect
00018 B
overheated transformer from overheating. Can be either battery operation,
Coil
Register Format Parameter Notes
bypass operation or shut down. Shut down actions is delayed 10
minutes from arising alarm.
00019 B Reserved
UPS will turn off inverter with overheat alarm and switch operating
00020 B Inverter overheated
mode accordingly, battery or bypass operation.
Battery voltage low warning Warning signal that shut down is imminent when running in battery
00021 B
(Low DC warning) operation.
00022 B Reserved
Inverter current > 100%,
00023 B Inverter is being overloaded. UPS will current limit.
Current limiter active
UPS is excessively overloaded. UPS will transfer to bypass or shut
00024 B Output current > 150%
down.
In normal or battery operation no change in operating mode on this
00025 B Bypass voltage out of range
alarm. In bypass operation however UPS will shut down.
00026 B Mains voltage out of range UPS will transfer to battery operation
00027 B Digital input 1 Open = 1
00028 B Digital input 2 Open = 1
00029 B Digital input 3 Open = 1
00030 B Digital input 4 Open = 1
00031 B Digital input 5 Open = 1
00032 B Digital input 6 Open = 1
00033 B Digital input 7 Open = 1
00034 B Digital input 8 Open = 1
00035 B Inverter fuse blown The inverter fuse has blown.
00036 B Reserved
Aux 1 Error alarm, based on alarms coming from Signalling controller
00037 B Aux 1 Error
A072.
00038 B Fan Fault One of the internal system fans has a fault.
Battery voltage high
00039 B Indicates battery voltage is too high.
warning (High DC warning)
00040 B Inverter Voltage Error The inverter voltage is out of range.
00041 B Reserved
00042 B MPU is reset The internal MPU on controller A070 is reset.
00043 B Fault in int. power supply One of the two internal power supplies has a fault.
00044 B Reserved
00045 B Normal Operation The system is operating in Normal Operation.
00046 B Charger Only The system is operating in Charger Only mode.
00047 B Economy Operation The system is operating in Economy Operation.
High temp charger
00048 B The temperature on the charger magnetics is too high.
magnetic
00049 B High battery temperature The temperature on the battery is too high.
00050 B Battery monitor warning Conclusion of battery monitor test.
00051 B Battery monitor alarm Conclusion of battery monitor test.
System locked in operation The system is locked in any operation mode. Result of too often
00052 B
mode changing operation mode within a certain time period.
00053 B Fatal error RAM1 data The internal RAM1 memory has a fatal data error.
Calibration stack entered The password protected calibration stack was entered. This alarm
00054 B
(no common alarm) will not trigger a common alarm.
TSM 1/2/3 temperature One of the system inverter power modules has a temperature
00055 B
shutdown shutdown signal pending.
Charger 0°/30° temperature One of the system Charger modules has a temperature warning
00056 B
warning signal pending.
Charger 0°/30° temperature One of the system Charger modules has a temperature shutdown
00057 B
shutdown signal pending.
00058 B High output voltage The system output voltage is too high
Coil
Register Format Parameter Notes
Static switch temperature > One of the system static switch modules (EA or EN) has a
00059 B
90°C (EA, EN warning) temperature warning signal pending.
00060 B Total DC current limit The system charger is operating in total DC current limit mode.
Low current failure in the
00061 B The current in the AC capacitors is below the low warning limit value.
AC capacitors
00062 B Hot Standby The system is operating in Hot Standby mode.
00063 B No redundancy operation The system is not operating in redundant operation.
An internal serial error within the systems control electronic has
00064 B Internal serial error
occurred.
Low current shutdown in the The current in the AC capacitors is below the low shutdown limit
00065 B
AC capacitors value.
00066 B Mains out of tolerance The rectifier mains is out of tolerance.
00067 B Charger on The system charger is running.
00068 B Total DC current limit The system charger is operating in total DC current limit mode.
Charger temperature too One of the system Charger modules has a temperature warning
00069 B
high signal pending.
Charger magnetics
00070 B The temperature on the charger magnetics is too high.
temperature too high
00071 B UPS Comms fail RS232 not connected.
General explanation:
Coil Register: Number of the Read Coil Register on function call 01. Note that a value of 1 in the
Read Coil Registers means that the individual status or alarm mentioned in the
column Parameter is active.
Format: Data type format B means Boolean.
Parameter: Boolean name/source. Records marked "Reserved" are always filled with 0.
Notes: Some additional information about the individual parameter.
General explanation:
Holding Register: Number of the Read Holding Register on function call 03.
Format: Data type format is unsigned integer. FFFF means hexadecimal data format
value of 4 digits. This corresponds to an absolute range of decimal 0 – 65535.
Parameter: Measurement name/source. Records marked "Reserved" are always filled with
value 0000 hex (0 decimal).
Unit of measure: The unit of measure in which the respective analog value is measured.
Note: For some holding registers, no unit of measure is given, since the values
in these holding registers are given in the column Notes (e.g. holding register
40022, Operation mode).
Notes: Some additional information about the individual parameter.
4. PHYSICAL INTERFACES
This section gives some more detailed information about the physical connections to the MOD-
LINK unit, along with information about LED displays on the unit.
4.2 J1 — RS485
Pin 1 ............. 2 & 4 B = RX-
Pin 2.............. 2 & 4 A = RX+
Pin 3.............. 4 B TX = TX-
Pin 4.............. 4 A TX = TX+
Pin 5 ............. GND = GND
4.5 J4 — Power
Pin 1.............. 0V (GND)
Pin 2 ............. +5V (+/-5% tolerance)
Note: ............. The current consumption of the MOD-LINK is 500mA.
5. PCB LAYOUT
BYPASS A
A A
-X090
L1,L2 -Q090 -T090 -Q091
1~ 1~
PE
BYPASS MAINS A
-Q050
1x400V, 50Hz
BYPASS
V A
2PH, 2W
B TEST B
-P092 -P091 AUTO
EN
TO BYPASS A
SEE PAGE 4
-X001 -T001 -A030 -L011 -A015 -A032.. -L002 -T002 -A036
-F021
L1,L2 EA
L3 -Q001 3~ 1~ 1~
-Q060
3~ -F026
C PE 3~ C
-CB02 -CB03
-S031 VS AS -A031 -L012
MAINS INPUT A
3x400V, 50Hz
A A A V V/A/F
3PH, 3W
V/A -F027
V A
-P032 -P031
A
D D
-P026
-L005
-S001 -R001
-Q004
E B+,B- E
-X002 220V DC
SHT
F H-EB-085005A H-SWE-1003 F
BYPASS B
A A
-X090
L1,L2 -Q090 -T090 -Q091
1~ 1~
PE
BYPASS MAINS B
-Q050
1x400V, 50Hz
BYPASS
V A
2PH, 2W
B TEST B
-P092 -P091 AUTO
EN
TO BYPASS B
SEE PAGE 4
-X001 -T001 -A030 -L011 -A015 -A032.. -L002 -T002 -A036
-F021
L1,L2 EA
L3 -Q001 3~ 1~ 1~
-Q060
3~ -F026
C PE 3~ C
-CB02 -CB03
-S031 VS AS -A031 -L012
MAINS INPUT B
3x400V, 50Hz
A A A V V/A/F
3PH, 3W
V/A -F027
V A
-P032 -P031
A
D D
-P026
-L005
-S001 -R001
-Q004
E B+,B- E
-X002 220V DC
SHT
F H-EB-085005B H-SWE-1003 F
A BYPASS A DISTRIBUTION A A
H-EL-085005A
-Q100 -Q200 -K110
NC NC NC
FROM BYPASS A BUS A BUS B
SEE PAGE 2
INTERLOCK
B -Q300 -P101 -P102 -P103 -Q101 -Q135 -Q136 -Q155 B
NO A V Hz
RESPECT PROTECTIVE NOTE ISO 16016
DISTRIBUTION B
H-EL-085005B
-Q200 -K210
NC NC
D FROM BYPASS B BUS C BUS D D
SEE PAGE 3
-Q100
NC
E E
BYPASS B
F F
DISTRIBUTION A
BUS A BUS B
A A
B B
RESPECT PROTECTIVE NOTE ISO 16016
C C
D D
E E
F F
DISTRIBUTION B
BUS C BUS D
A A
B B
RESPECT PROTECTIVE NOTE ISO 16016
C C
D D
E E
F F
A DIGITAL METER
3~ 3~ STABILIZER A = AMMETER
MINIATURE CIRCUIT BREAKER 51 OVERCURRENT RELAY
V = VOLTMETER
B Hz = FREQUENCY METER B
S SELECTOR SWITCH
V/A/F MEASUREMENTS TO BE READ
FUSE SWITCH ON THE DISPLAY ELR EARTH LEAKAGE RELAY
A = AMMETER
C V = VOLTMETER C
Hz = FREQUENCY METER
CAPACITOR
GROUNDING LINK EF EARTH FAULT RELAY
CONTACTOR
.
.
.
. Page 1 / 6 7RA9118GB: Rev.03
TABLE OF CONTENTS:
1. Operational buttons for Starting, Switching over, Stopping
2. Starting the UPS system
3. Switching over from Normal operation to Bypass operation
4. Switching over from Bypass operation to Normal operation
5. Switching over to Manual Bypass
6. Switching over from Manual Bypass to Normal operation
7. Stopping the UPS system
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
This chapter contains all the necessary information to operate the UPS
system after installation and commissioning. See also Instruction
7RA9075GB «Erection – Installation» and «Commissioning».
.................... Activation of ON
2. Press the button S1 «SYSTEM ON» on the front panel. If the display shows:
display shows: .
5. Check in the display that the inverter output voltage is within the tolerance range by
7. Wait 10 seconds and then press the button until all red LED’s of «Alarm indications»
are extinguished.
tolerance range the green LED 9 «BYPASS MAINS O.K.» and the yellow LED 6
If during bypass operation a fault in the bypass mains occurs, the system will automatically
switch over to normal operation if the rectifier mains is available, otherwise to battery
operation if the battery is available and within the tolerance range.
Depending on the programming a short loss of the output voltage can occur.
1. Switch over the UPS system to bypass operation by means of the foil keypad by pressing
tolerance range the green LED 9 «BYPASS MAINS O.K.» and the yellow LED 6
Step 2 and 2b) have to be performed for systems with 2-position manual
bypass switch.
Step 2a), 2b) and 2c) have to be performed for systems with 3-position
manual bypass switch.
2. Before switching the manual bypass switch Q050 to position «BYPASS», secure that the
static switch EN is turned on (the green LED 10 «LOAD VIA EN» must illuminate), then turn
the manual bypass switch Q050 to position «BYPASS» the green LED 11
«MANUAL BYPASS» illuminates.
2a) Before switching the manual bypass switch Q050 to position «TEST», secure that the static
switch EN is turned on (the green LED 10 «LOAD VIA EN» must illuminate), then turn the
manual bypass switch Q050 to position «TEST» the green LED 11 «MANUAL
BYPASS» illuminates.
2b) Turn off the UPS by pressing simultaneously the buttons S1 «SYSTEM ON» and S2 «OFF»
on the front panel the UPS changes to standby operation. The display shows:
2c) Then turn the manual bypass switch Q050 to position «BYPASS». The green LED
11 «MANUAL BYPASS» illuminates.
Ensure that the users of all consumers connected to the UPS system are informed
before proceeding with the following steps and before turning off the system.
After the following steps, i.e. after approx. 5 minutes, when the DC capacitor bank
has discharged, the UPS system is volt-free with the exception of components,
which are connected between the terminals and the switch.
NO OUTPUT VOLTAGE !
Check by means of a voltage measuring device that all power sections are de-
energized. Remember, the rectifier mains and the bypass mains, as well
as the battery are still applied !
The connecting terminals are carrying hazardous voltage !
2. Press simultaneously the buttons S1 «SYSTEM ON» and S2 «OFF» on the front panel for
.
.
.
. Page 1 / 3 4A-1110148002/20GB: Rev.01
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
1. Charge the DC capacitors CB02 by turning the charging/discharging switch S001 to position
«2» and keep it in this position until the warning LED goes off and then before releasing the
switch S001 close the battery switch Q004.
to: .
2. Press the button S3 «LAMP TEST» on the front panel and check that all LED’s of the
«Operating status indications» and «Alarm indications» illuminate.
3. Turn on the UPS by pressing S1 «SYSTEM ON» on the front panel. The display shows:
monitor» is installed.
4. Check in the display that the inverter output voltage is within the tolerance range by
pressing the button . The green LED 7 «INV. VOLTAGE O.K.» must illuminate.
8. Thereafter, when the rectifier mains and bypass mains are available again close the rectifier
input switch Q001 and the bypass input switch Q090.
10. Make sure that the UPS system operates correctly and no alarm of the «Alarm indications»
is pending.
.
.
.
. Page 1 / 9 4A-1110148002/20GB: Rev.01
COMMISSIONING
Dual UPS System with 3-position Manual bypass
switch, Static switches EA & EN and
Tie breaker,
Type: PEW / PDW
TABLE OF CONTENTS:
1. Preparations with Power Off
2. Commissioning of the UPS system
3. Switching volt-free of the UPS system
4. Recommissioning of the UPS system
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
When planning the initial checks read first the complete chapter before starting the
check procedure.
PRINCIPLE DIAGRAM
Depending upon the system configuration, the switches mentioned in this
description can be circuit breakers, switch-disconnectors (fuse switch-
disconnectors) and the designation can be made according to customer's request
see «Single line diagram».
FRONT PANEL
by Schneider
1. Check by means of a voltage measuring device that all power sections are de-energized.
2. Check that the earthing of all cubicles is secure and there are no damages.
4. Check that all printed circuit boards are correctly mounted and the plugs are firmly plugged
in.
7. If bags with moisture absorbing material are in the cubicle, remove these.
Check that the interior of the UPS system is dry. If there is any condensed
water, let the UPS system stand with the front doors open in a dry and
warm area for at least 24 hours.
2. Apply the rectifier mains voltage (according to «Connection diagram») and check phase
sequence as well as the voltage.
3. Apply the bypass mains voltage (according to «Connection diagram») and check the voltage.
The safe bus is now energized via the closed bypass input switch Q090 and
the manual bypass switch Q050.
5. Close the rectifier input switch Q001. The display shows: for 10
programmed for «AUTOSTART» see «Technical data» and the rectifier mains is
within the tolerance range the UPS system will start automatically after 60 seconds.
The green LED’s 14, 16, 1 & 11 as well as the red LED 13 & 19 illuminate.
6. Press the button S3 «LAMP TEST» on the front panel and check that all LED’s of the
«Operating status indications» and «Alarm indications» illuminate.
7. Turn on the UPS system (if not already ensued automatically) by pressing S1 «SYSTEM
ON» on the front panel. If the display shows: wait a short time or
The green LED’s 2 & 5 are additionally illuminated (also LED 7 & 8, but only if the inverter
output voltage and static switch EA are o.k.).
8. Check the rectifier output voltage in the display by pressing the button .
9. Close the battery switch Q004. The green LED 12 is additionally illuminated and the
red LED 13 extinguishes.
10. Check the battery current in the display by pressing the button .
11. Check in the display that the inverter output voltage is within the tolerance range by
pressing the button . The green LED 7 «INV. VOLTAGE O.K.» must illuminate.
12. Check that the green LED 8 «LOAD VIA EA» illuminates.
13. Turn off the rectifier mains by opening the rectifier input switch Q001. The UPS
system changes to battery operation.
14. Check that the green LED 4 «BATTERY OPERATION» and the red LED 15 illuminate,
whereby the green LED 12 remains illuminated and the LED’s 14, 1 & 2 extinguish. The red
LED «BATTERY OPERATION» of the «Alarm indications» illuminates after a 30 seconds
delay and the display shows: , where «time > …min.» is only
17. Check that the yellow LED 6 «SYNCHRONOUS» illuminates (bypass mains must be
available and within the tolerance range — this will be indicated by the green LED 9
«BYPASS MAINS O.K.»).
18. Switch over the UPS system to bypass operation using the Foil keypad by pressing
. Thereafter press and if the bypass mains is within the tolerance range the green
LED 9 «BYPASS MAINS O.K.» and the yellow LED 6 «SYNCHRONOUS» are illuminated
and the display shows: . . Check that the green LED 10 «LOAD VIA
EN» as well as the LED’s 5 & 7 illuminate — the green LED 8 «LOAD VIA EA» extinguishes.
19. Switch back the UPS system to normal operation using the Foil keypad by pressing
green LED 8 «LOAD VIA EA» illuminates and that the green LED’s 5, 7 & 9 and the yellow
LED 6 remain illuminated — the green LED 10 «LOAD VIA EN» extinguishes.
20. Switch over the UPS system to bypass operation using the Foil keypad (as explained
before).
21. Check that the green LED 10 «LOAD VIA EN» illuminates and the display shows:
22. Before switching the manual bypass switch Q050 to position «AUTO», secure that the static
switch EN is turned on (the green LED 10 «LOAD VIA EN» must illuminate), then turn the
manual bypass switch Q050 to position «AUTO» the green LED 11 extinguishes.
23. Switch back the UPS system to normal operation using the Foil keypad (as explained
before). The UPS system is now in normal operation with the static switch EN turned off.
24. Check that the green LED’s 5, 7, 8 & 9 as well as the yellow LED 6 illuminate and that LED
26. Make sure that the UPS system operates correctly and no alarm of the «Alarm indications»
is pending. Exception: LED's, which show the open feeders of the distribution.
The safe bus is energized.
The following LED’s are illuminated: the green LED’s 14, 16, 12, 1, 2, 5, 7,
8 & 9 as well as the yellow LED 6.
27. Close the output switch Q100 in both systems. The red LED 19 extinguishes and
28. Close the distribution input switch Q200 in both systems. The red LED 19
extinguishes and the green LED 18 illuminates.
31. Reset eventual alarms by pressing until all red LED’s are extinguished. The horn
32. Clear the log alarm stack by pressing simultaneously and . Then the display
shows: . Key in the password 920701 and the alarm log will be
Both UPS systems can be switched volt-free in the same way, one
after the other.
With these instructions the UPS system can be switched volt-free. The load is then
supplied via the manual bypass switch Q050 from the bypass mains.
The bypass mains must be available and within the tolerance range.
1. Switch over the UPS system to bypass operation using the Foil keypad (as explained
before). If the bypass mains voltage is available and within the tolerance range the green
LED 9 «BYPASS MAINS O.K.» illuminates and the changeover logic changes to EN.
The green LED 10 «LOAD VIA EN» illuminates.
2. After the static switch EN is switched on, turn the manual bypass switch Q050 to position
«TEST». The green LED 11 «MANUAL BYPASS» illuminates.
3. Turn off the UPS system by pressing simultaneously the buttons S1 «SYSTEM ON» and S2
«OFF» on the front panel the UPS system changes to standby operation. The
4. Open the battery switch Q004. The green LED 12 extinguishes and the red LED 13
illuminates.
5. Open the rectifier input switch Q001. The green LED’s 14 & 1 extinguish.
After approx. 5 minutes, when the DC capacitors have discharged, the UPS
system is volt-free with the exception of components, which are connected
between the terminals and the switch.
Check by means of a voltage measuring device that all power sections are
de-energized. Remember, the rectifier mains and the bypass mains,
as well as the battery are still applied !
These instructions describe the recommissioning of the UPS system after it has been
switched volt-free.
1. Turn manual bypass switch Q050 to position «TEST».
3. Turn on the UPS system (if not already ensued automatically) by pressing the button S1
«SYSTEM ON» on the front panel The system starts up to normal operation and if
the display shows: wait a short time or press any button, e.g.
4. Check in the display that the rectifier output voltage is within the tolerance range by
5. Close the battery switch Q004. The green LED 12 is additionally illuminated and the
red LED 13 extinguishes.
6. Switch over the UPS system to bypass operation using the Foil keypad (as explained
before).
7. Check that the green LED 10 «LOAD VIA EN» illuminates and the display shows:
9. Switch back the UPS system to normal operation using the Foil keypad (as explained
before).
11. Make sure that the UPS system operates correctly and no alarm is pending.
.
.
.
. Page 1 / 5 7RA9090GB: Rev.04
MAINTENANCE
UNINTERRUPTIBLE POWER SUPPLY (UPS),
Type: PEW / PDW
TABLE OF CONTENTS:
1. Maintenance of the UPS System
1.1 Monthly Checks
1.2 Semiannual Checks
1.3 Annual Checks
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
Due to the critical intended purpose and to ensure the safe and reliable operation of the
equipment, inspection and preventive maintenance are essential.
For the checks listed below a brief report/checklist shall be issued where all findings are
documented. These records must be available in case of a warranty claim.
reset the alarms by pressing the button and make sure that the UPS operates
5. Press the button S3 «LAMP TEST». All operating status and alarm indications must
illuminate as long as the button is pressed.
2. Read out the event log and analyse it. In case of irregularities which can not be explained,
kindly contact the GUTOR support.
Detailed corresponding data for the maintenance of the battery see the information given
by the battery manufacturer in «Battery documentation».
2. Check all wet battery cells on the liquid level and if necessary refill ( see «Battery
documentation»).
3. Check the voltage of each individual cell (in the case of wet battery cells additionally the
specific gravity) of the «pilot cells» ( see «Battery documentation»).
3. Check the battery with the rectifier switched on. Measure and record the voltage of each cell.
In the case of wet cells additionally the specific gravity must be checked and recorded.
At the end of this check the capacity of the battery is low. If at this time a mains
failure occurs, it will have a direct influence on the emergency current time
(autonomy time). Therefore, this check must be co-ordinated with the personnel
(e.g. operator of the connected load). Nevertheless, the test should not be
foregone because it provides the best information on the condition of the batteries.
1. Start with fully charged batteries, i.e. if the system has been in normal operation for longer
than 8 hours.
2. For testing the battery capacity from the Foil keypad proceed as follows: push and
shown on the display, where «xxx» is the back-up time of the last test — if not performed
before or if the test has been aborted, «???» is shown.
where «time > …min.» is only shown if option «Advanced battery monitor» is installed.
4. Wait until the display shows: and a short alarm has been activated.
If during the test a mains fault occurs, the test will immediately be aborted and no test result will be
obtained. When reading out data of the battery capacity test in the display after a test has been
aborted, «???» is shown, i.e. that no result was obtained
Please note that after a battery capacity test it will take about 8...24 hours before the battery is
recharged and the full back-up time is available again.
.
.
.
. Page 1 / 3 7RA9091GB: Rev.01
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
As a minimum GUTOR specifies that the following components and parts in the UPS systems are
replaced according to the time periods indicated:
These values refer to a maximum ambient temperature of 40° Celsius and a maximum load of
70%. If one of these values is continuously exceeded, the items mentioned must be replaced 1
year earlier.
Note 2: With enabled battery monitor (option) the battery is automatically monitored.
In the case of a faulty battery an alarm is generated.
Note 3: The air filters must be checked at least every 6 months. Dependent on the
contamination they must be replaced immediately.
Options
Normal NPP Replacement
Part Scope Scope Cycle Remarks
Harmonic Filters X X 10 years
Static Transfer Switch X X 10 years
TDS X X 10 years according specific instructions
AC/DC Converter X X 10 years
DC/DC Converter X X 10 years
Replacement cycle intervals may be shorter and the scope may need to be extended if
the system is exposed to harsh environmental conditions (vibration, climate, air-
pollution).
.
.
.
. Page 1 / 7 7RA9092GB: Rev.04
SERVICE — TRAINING —
CONTACT ADDRESSES
UNINTERRUPTIBLE POWER SUPPLY
(UPS & INVERTER),
Type: PEW/PDW & WEW/WDW
TABLE OF CONTENTS:
1. Service/Repairs
1.1 Service Contract
1.2 Call for After Sales Service and Return of Parts
1.3 Installation and Commissioning
1.4 Maintenance
2. Spare Parts
3. Training
3.1 Level 1: Operation
3.2 Level 1-2: Maintenance
3.3 Level 1-3: Service
4. Contact Addresses
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
1. SERVICE/REPAIRS
1.1 Service Contract
What is a service contract?
A service contract is a formal, mutually agreed, binding contract between GUTOR and a client, in
which GUTOR makes a commitment to provide services over a fixed time period, and at fixed rates
/ yearly fee. These services include technical support, preventive maintenance and repair.
Each contract entails a different degree of commitment. For further information, refer to the table
below.
This label contains all necessary information for the return of parts or for contacting our service
department. It is adhered behind the front door near the name plate.
The necessary information to call for service action are mentioned on the name plate.
1.4 Maintenance
Maintenance covers several important aspects which have a deep impact on the availability and
reliability of the entire system and the plant it services. The aspects of maintenance are divided in:
Preventive Maintenance
The concept of preventive maintenance comprises planned maintenance tasks. Their purpose is to
minimize breakdowns, excessive depreciation of the system and to maximize availability and
reliability during the entire life span. The individual preventive maintenance jobs are performed
according to the system maintenance manual and the OEM maintenance checklist. Preventive
maintenance requires adequately-trained and experienced manpower, replacements of those parts
with limited lifetime, tools and instruments to perform the respective work.
Corrective Maintenance
Preventive maintenance cannot prevent a breakdown that is caused by external influences,
operational error or a part failure. If an unexpected breakdown occurs it is important that the
system is repaired, tested and brought back to operation immediately.
Hotline Services
For operational questions, remote advice, or the request of a field service engineer (FSE).
2. SPARE PARTS
GUTOR UPS systems have proven time and again to last as long as 20 years. GUTOR achieves
this performance by offering clients spare parts throughout this period. Spare parts are categorized
into three groups: start-up, critical, and consumables spares as described in this section.
Accordingly, GUTOR highly recommends clients to maintain a stock of the start-up and critical
spare parts, for the benefits listed here.
The selection of the correct spare parts is crucial. We gladly support you in defining the spare parts
needed taking in consideration of your installed GUTOR systems and requirements.
3. TRAINING
Uninterruptible Power Supply (UPS) systems from GUTOR are designed according to individual
customer needs. Technical staff servicing and maintaining these systems therefore receive
customized training based on specific requirements in relation to those particular systems installed
on-site. GUTOR offers three different training levels concerning operation, maintenance, and
service respectively. Each training course, as well as the documentation, are individually tailored
based on the customer's installed fleet.
4. CONTACT ADDRESSES
GLOBAL SERVICE ORGANIZATION
GUTOR recognizes the importance of a global service network to support our globally operating
customers. As a member of the Schneider Electric group, GUTOR provides you with a worldwide
service network, an inventory of readily available spare parts, and trained service partners. For
more details regarding our service programs, please contact the GUTOR Service Centre nearest to
you, as listed below.
HEADQUARTER SWITZERLAND
GUTOR Electronic LLC
Hardstrasse 72 – 74
5430 Wettingen, Switzerland
P +41 (0)56 437 34 34
F +41 (0)56 437 34 21
gutor-service-ch@schneider-electric.com
ASIA PACIFIC:
GUTOR Electronic Asia Pacific Sdn Bhd
No. 19, Jln Juruukur U1/19, Seksyen U1
Hicom Glenmarie Industrial Park,
40150 Shah Alam, Selangor, Malaysia
P +(6) 03 5569 0331
F +(6) 03 5569 0332
gutor-service-my@schneider-electric.com
MIDDLE EAST:
GUTOR Electronic LLC
Villa No.2, Defence Road,St.11,
Behind Gava Hotel,
P.O.Box 29580, Abu Dhabi, U.A.E.
P +971 (0)2 443 89 93
F +971 (0)2 443 89 92
gutor-service-ae@schneider-electric.com
SAUDI ARABIA:
GUTOR Electronic LLC
Middle East Commercial Complex
AL-Khobar 31952
P.O.Box. 79575, Saudi Arabia
P +966 (0)3 864 9667
F +966 (0)3 864 9062
gutor-service-sa@schneider-electric.com
RUSSIA
The GUTOR by Schneider Hotline number is: 8-800-200-6446
Please dial 0 for technical consultation, then the Customer Care Center specialist will connect you
to GUTOR by Schneider engineer.
The hotline is open Monday to Friday 8am – 6 pm (Outside business hours please call our GUTOR
Hotline in Switzerland: +41 56 437 6263)
.
.
.
. Page 1 / 6 4A-1110148002/20GB: Rev.01
F
TROUBLE SHOOTING
UNINTERRUPTIBLE POWER SUPPLY (UPS),
Type: PXW 1030-220/230-EAN-D
TABLE OF CONTENTS:
1. Elimination of simple Malfunctions
2. Trouble-Shooting at Alarm Indication
Please note:
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for whatever reason, without the explicit written
permission of GUTOR Electronic LLC.
Depending upon the system configuration, the switches mentioned in this description can be circuit breakers, switch-disconnectors (fuse switch-
disconnectors) and the designation can be made according to customer's request see «Single line diagram».
Alarm Indication Alarm #: / Error in the System Source of Error Test Possibilities Location
RECT MAINS FAULT 40: Mains Phase rotation error ♦ Wrong wiring ♦ Check phase order ♦ Interface A071: X003, F001, F002, F003
(30 s)
41: Mains voltage out of tolerance ♦ Input voltage out of tolerance ♦ Check voltages ♦ Input connector X001
♦ Input switch Q001 open ♦ Check input switch Q001
39: Mains frequency fault ♦ Input frequency out of tolerance ♦ Check frequency ♦ Input switch Q001
RECTIFIER FAILURE No “RECT MAINS FAULT” and:
(5 s)
36: Low DC warning or ♦ DC Load too high ♦ Check DC load ♦ DC Bus
37: Low DC shutdown or ♦ System OFF (also due to shutdown) or System in ♦ Check operation mode and evaluate
standby shutdown cause (Log stack)
♦ Rectifier or PSU faulty
♦ Check current ripple (6-pulse: 300/360Hz, ♦ Input switch Q001
12-pulse: 600/720Hz)
♦ Check PSU LED's ♦ Controller A070
(PSU_OK_AC/PSU_OK_DC)
23: Charger 30 temp shutdown or
Charger modul A030/A31
21: Charger 0 temp shutdown
DC OUT OF TOLERANCE 27: High DC shutdown ♦ Rectifier out of operation ♦ Measure the DC voltage ♦ Battery
(5 s) 37: Low DC shutdown ♦ Battery discharged / disconnected ♦ Measure the battery voltage ♦ Interface A071 / X017: F022/F023
♦ DC has exceeded «High DC warning level» ♦ Controller A070
♦ DC dropped below «Low DC warning level»
RECTIFIER FUSE BLOWN ♦ Fuse trip indicator not connected ♦ Check fuse trip indicator ♦ Rectifier output fuse F026 (F027)
(5 s) ♦ Rectifier output fuse F026 (F027) blown
Alarm Indication Alarm #: / Error in the System Source of Error Test Possibilities Location
BATTERY OPERATION ♦ Rectifier failure ♦ Check the mains input ♦ Rectifier input switch Q001
(30 s) ♦ Inverter supplied from the battery ♦ Interface A071/ X007: F001/F002/F003
BATTERY 11: Battery monitor warning ♦ Rectifier out of operation ♦ Measure DC voltage ♦ Rectifier
DISCHARGED 36: Low DC warning ♦ Battery disconnected ♦ Check Battery MCB ♦ Battery MCB
(5 s) ♦ DC voltage dropped to the lower alarm level. ♦ Inverter input switch Q020
♦ Interface A071/ X017: F022/F023
BATT DISCONNECTED 15: Battery MCB Off ♦ Breaker open or auxiliary contact not connected ♦ Check breaker and auxiliary contacts ♦ Battery
(5 s) ♦ Q004 (Q005), X002
♦ External Connection Board A025:
X004:1 and X004:2
DC EARTH FAULT ♦ One of the battery poles is connected to earth ♦ Isolate the battery ♦ Battery
(5secs) ♦ Check earth fault resistors ♦ Earth fault resistor board A014
INVERTER FAULT 6: Power Module 1 shutdown ♦ Over temperature on inverter power units ♦ Check temperature of power modules and ♦ Fuse F021 (F022... F023)
8: Power Module 2 shutdown ♦ Inverter fuse blown output magnetics ♦ Interface A071
(5 s)
10: Power Module 3 shutdown ♦ Controller A070
♦ Fans
OVERLOAD 25: Overload: load is >100% ♦ Load current higher than the nominal current of ♦ Measure the load current ♦ Current transformer P013 (P014...P015)
INV/BYPASS the system ♦ Interface A071 / X014
(30 s)
INV. FUSE BLOWN 35: Inverter fuse blown ♦ Power fuse F021 (F022... F023) ♦ Check the fuse F021 (F022... F023) ♦ Fuse F021 (F022... F023)
(5 s) ♦ Inverter input switch Q020 open ♦ Check if the inverter input switch Q020 is ♦ Interface A071 / X003
open ♦ Inverter input switch Q020
ASYNCHRONOUS 51: Synchronisation error ♦ Bypass frequency out of tolerance ♦ Measure the voltage between bypass and ♦ Controller A070
♦ Inverter asynchronous to the bypass mains system output ♦ Interface A071
(30 s)
BYP. MAINS FAULT 16: Bypass frequency out of tolerance ♦ Bypass mains voltage or frequency out of ♦ Measure the bypass mains voltage and ♦ Interface A071/ X010: F006/F007/F008
18: Bypass is out of tolerance tolerance frequency at the input of the static switch
(30 s)
EN
MANUAL BYPASS ON 4: System set in manual BYPASS ♦ Manual bypass switch Q050 not at position ♦ Check the position of manual bypass ♦ Manual bypass switch Q050
«AUTO» switch Q050 ♦ Adapter board A068
(5 s)
EN INHIBITED 16: Bypass frequency out of tolerance ♦ Bypass mains voltage or -frequency out of ♦ Measure the bypass mains voltage ♦ Static switch EN — A035
18: Bypass is out of tolerance tolerance ♦ Measure the bypass voltage after F028 ♦ Controller A070
(30 s)
47: Static Switch EN temp shutdown ♦ Over temperature on the static switch EN (F029...F030) ♦ Interface A071/ X010: F006/F007/F008
Alarm Indication Alarm #: / Error in the System Source of Error Test Possibilities Location
EA INHIBITED 42: Output frequency out of tolerance ♦ Inverter voltage out of tolerance ♦ Measure the inverter output voltage after ♦ Static switch EA — A036
43: Output instantaneous out of tolerance ♦ Over temperature on the static switch EA F021 (F022... F023) ♦ Power fuses F021 (F022... F023)
(5 s)
44: Output is out of tolerance ♦ Interface A071/ X012: F010/F011/F012
49: Static Switch EA temp shutdown
OVERTEMPERATURE 5: Power Module 1 temp warning ♦ Heat-sink of the power components too hot ♦ Measure the temperature ♦ Thermostats on power components and
7: Power Module 2 temp warning ♦ Winding material too hot ♦ Check the air flow through the system wiring material
(5 s)
9: Power Module 3 temp warning ♦ Too high ambient temperature ♦ Interface A071
32: High temperature inverter magnetics ♦ Air inlet obstructed
48: Static Switch EN temp warning
50: Static Switch EA temp warning
FAN FAILURE 54: Fan fault ♦ Fans ♦ Check the air flow ♦ Fan monitoring A055 / A056 : Interface
♦ Fan monitoring board (A055 / A056) ♦ Check the power supply A071 / X004
(30 s)
♦ Fan transformer (T051 / T052) ♦ Fan disconnection ♦ Fan transformers (T051 / T052)
♦ Power supply for the fans ♦ Interface A071 / X025...X030:
F016...F021
POWER SUPPLY FAULT 55: Fault in internal power supply ♦ Power supply units : PSU A201 / A202 ♦ Measure the output voltage of the PSU’s ♦ PSU-Transformer T005 : Interface A071
♦ AC or DC power supply sources ♦ Measure the DC supply voltage to PSU 2 / X021 : F004/F005
(5 s)
♦ Interface A071 A202 at X003 ♦ PSU-Transformer T004 : Interface A071
♦ Measure the AC supply voltage to PSU 1 / X022 : F006/F007
A201 at T005 : X001 and T004 : X002 ♦ PSU 2 A202 : Interface A071 / X032 :
F026/F027
DISTRIBUTION A MCB Option 3: ♦ One or more of the MCCB’s in the AC distribution ♦ Check if one or more load breakers are ♦ Load
OPEN A are open open ♦ MCB's Q101...Q135
♦ Overload on one of the feeders or short-circuit ♦ Check if one or more fuses has blown ♦ K101
(5 s)
♦ Check load ♦ Fuses F101 & F102
♦ Relay K101
♦ Adapter board A068
DISTRIBUTION B MCB Option 4: ♦ One or more of the MCCB’s in the AC distribution ♦ Check if one or more load breakers are ♦ Load
OPEN B are open open ♦ MCB's Q201...Q235
♦ Overload on one of the feeders or short-circuit ♦ Check if one or more fuses has blown ♦ K101
(5 s)
♦ Check load ♦ Fuses F201 & F202
♦ Relay K201
♦ Adapter board A068
Alarm Indication Alarm #: / Error in the System Source of Error Test Possibilities Location
DISTR. TIE BREAKER Option 5: ♦ The Tie breaker Q300 is manually closed due to ♦ Check if the tie breaker Q300 is closed ♦ Tie breaker Q300
CLOSED a failure in one of the UPS or for maintenance ♦ Output switch-disconnector Q100
(5 s) works. ♦ Output switch-disconnector Q200
♦ For further explanation see chapter 3: ♦ Fuses F103...F106
«Explanation of the Tie Breaker Q300». ♦ K151
♦ Adapter board A068
DISTRIBUTION BUS B Option 6: ♦ Bus B is disconnected from Distribution A ♦ Check if Bus B is disconnected ♦ Load
DISCONNECTED ♦ Check whether the contactor K110 is open ♦ MCB's Q136...Q155
(5 s) ♦ Measure AC output voltage ♦ Adapter board A068
DISTRIBUTION BUS D Option 6: ♦ Bus D is disconnected from Distribution B ♦ Check if Bus D is disconnected ♦ Load
DISCONNECTED ♦ Check whether the contactor K110 is open ♦ MCB's Q236...Q255
(5 s) ♦ Measure AC output voltage ♦ Adapter board A068