NMI/SUB BILLING METERING
IPD3005C
DIGITAL KWH METER 5A , CT CONNECT 415V RS485 MODBUS COMMUNICATION DIN MTG.
ENERGY MANAGEMENT > NMI/SUB-BILLING METERING > THREE PHASE MULTIFUNCTION METER
OVERVIEW
The IPD3005C series Digital Three-Phase Energy Meter is IPD’s latest offer for the low voltage power/energy metering market featuring DIN rail mount, high accuracy, multifunc-
tion true RMS measurements and a large, easy to read LCD display. The IPD3005C series complies with IEC 62053-22 Class 0.5S kWh accuracy standards for 5A CT Input. The
IPD3005C series comes standard with a metrological LED as well as a Solid State Pulse Output for energy pulsing. The IPD3005C series provides 2MB memory for Data Recording
and 3 Digital Inputs for status monitoring, Tariff switching or pulse counting for collecting Water, Air, Gas, Electric and Steam information from 3rd party metering devices. The
standard RS-485 port and Modbus protocol support allows the IPD3005C series to become a vital component of an intelligent, multifunction monitoring solution for any Power
and Energy Management Systems.
FEATURES
Ease of use
- Large, easy to read LCD
- Two LED indicators for energy pulsing and communication activities
- Password-protected setup via front panel
- Easy installation with DIN rail mounting, no tools required
- 3-phase power supply, no external control power required
Basic Measurements
- Multifunction True RMS measurements
• Voltage, Current, kW, kvar, kVA, PF, Phase Angle and Frequency
• Per phase and Total kWh and kvarh Imp/Exp/Tot/Net and kVAh
• 4-Quadrant kvarh
• Device Operating Time (Running Hour)
• Voltage and Current THD, TOHD, TEHD, Individual Harmonics up to 31st and
unbalance
DIMENSIONS AND INSTALLATION • Current K-Factor, Crest Factor, TDD, TDD Odd and TDD Even
• I1, I2, I3, kW/kvar/kVA Total Demands and Max. Demands
L1, L2, L3 N from Source - Max/Min Log
- 12 monthly recording of kWh/kvarh Imp/Exp/Tot/Net, kVAh, kvarh Q1-Q4 as
Voltage Input
well as kWh/kvarh Imp/Exp and kVAh per Tariff
(5A CT Input Option)
- Two TOU schedules, each providing
• 12 Seasons
• 20 Daily Profiles, each with 12 Periods in 15-minute interval
• 90 Holidays or Alternate Days
• 4 Tariffs, each providing the following information
Pulse Output o kWh/kvarh Import/Export, kVAh
o kW/kvar/kVA Max. Demands
Energy Pulse & - 2MB Log Memory
Comm. LEDs - Data Recorder Log of 16 measurements @ 10-minute interval for 197 days
- 16 SOE events time-stamped to 1ms resolution
Buttons
- Front Panel & Communication Programming Counters
Digital Inputs
- 3 channels for external status monitoring and pulse counting
RS-485 - Self-excited, internally wetted at 24VDC
Digital Input
Pulse Outputs
- 1 Front Panel LED and 1 Solid State Pulse Output for energy pulsing application
L1, L2, L3 N to Load Communications
- Optically isolated RS485 port, baud rate from 1200 to 19,200 bps
- Modbus RTU protocol
DIMENSIONS AND INSTALLATION
Real-time Clock
- Battery-backed real-time clock @ 6ppm
- Clock error ≤ 0.5s/day
System Integration
- Easy integration into other Automation or SCADA systems via Modbus RTU protocol
TYPICAL APPLICATIONS
- DIN rail mount energy metering
- Industrial and commercial metering
- Substation, building and factory automation
- Sub-metering
- Power quality monitoring
- NMI Pattern Approval Metering
1
NMI/SUB BILLING METERING
IPD3005C
SPECIFICATIONS
Part No. IPD3005C
Inputs (L1, L2, L3, N)
Voltage (Un) 240VLN
Range 0.7 to 1.1 Un
Burden <10VA/phase
CT Input
Current (In/Imax) 5A/6A
Range (0.1%-120%) In
Starting Current 0.1% In
Burden <0.5VA/phase
Frequency 45Hz-65Hz
Solid State Energy Pulse Output (Selectable - kWh/kvarh)
Pulse Constant 1/10/100/1000/3200 imp/kWh (imp/kvarh)
Isolation Optical
Max. Load Voltage 80V
Max. Forward Current 50mA
Pulse Width 60-150ms
Communications
RS-485 Modbus RTU
Baudrate 1200/2400/4800/9600/19200 bps
Maximum Wire Size 1.5mm2 (16AWG)
Maximum Torque 0.45 N.m
Environmental Conditions
Operating temp. -25°C to +70°C
Storage temp. -40°C to +85°C
Humidity 5% to 95% non-condensing
Atmospheric pressure 70 kPa to 106 kPa
Pollution Degree 2
Mechanical Characteristics
Mounting DIN Rail
Unit Dimensions 126x90x65mm
Shipping Dimensions 165x140x110mm
Shipping Weight TBD
IP Rating 51 (Front), 30 (Body)
ACCURACY
Parameters Accuracy Resolution
Voltage ±0.5% 0.01V
Current ±0.5% 0.001A
kW, kvar, kVA ±1% 0.01kW/kvar/kVA
kWh, kVAh IEC 62053-22 Class 0.5S for 5A CT Input 0.01kXh
kvarh IEC 62053-23 Class 2 0.01kvarh
P.F. ±1% 0.001
Frequency ±0.02Hz 0.001Hz
Harmonics IEC 61000-4-7 Class B 0.1%
2
NMI/SUB BILLING METERING
IPD3005C
STANDARDS OF COMPLIANCE
Safety Requirements
CE LVD 2014 / 35 / EU EN 61010-1: 2010 / EN 61010-2-030: 2010
Insulation IEC 62052-11: 2003, NMI M6-1
AC Voltage 4kV @ 1 minute
Impulse voltage 10kV, 1.2/50µs (NMI M6-1)
Electrical safety in low voltage distribution systems
IEC 61557-12: 2008 (PMD)
up to 1000Vac and 1500Vdc
Electromagnetic Compatibility
CE EMC Directive 2014 / 30 / EU (EN 61326: 2013)
Immunity Tests
Electrostatic discharge EN 61000-4-2: 2009
Radiated fields EN 61000-4-3: 2006+A1: 2008+A2: 2010
Fast transients EN 61000-4-4: 2012
Surges EN 61000-4-5: 2006
Conducted disturbances EN 61000-4-6: 2009
Magnetic Fields EN 61000-4-8: 2010
V Dips, Interruptions & Variations EN 61000-4-11:2004
Oscillatory waves EN 61000-4-12: 2006
Radio Disturbances CISPR 22:2006, Level B
Emission Tests
Limits and methods of measurement of electromagnetic disturbance characteristics EN 55011: 2009 + A1: 2010
of industrial, scientific and medical (ISM) radio-frequency equipment (CISPR 11)
Limits and methods of measurement of radio disturbance characteristics of EN 55022: 2010+AC: 2011
information technology equipment (CISPR 22)
Limits for harmonic current emissions for equipment with rated current ≤16 A EN 61000-3-2: 2014
Limitation of voltage fluctuations and flicker in low-voltage supply systems for
EN 61000-3-3: 2013
equipment with rated current ≤16 A
Emission standard for industrial environments EN 61000-6-4: 2007+A1: 2011
Testing and measurement techniques- Ring wave immunity test. EN 61000-4-12: 2006
Mechanical Tests
Spring Hammer Test IEC 62052-11: 2003
Vibration Test IEC 62052-11: 2003
Shock Test IEC 62052-11: 2003
Revenue Metering Approval
NMI M-6 of Australia Approval Mark: NMI 14/2/102