Finglai
Intelligent digital display controller
▇ Features
● Can input 22 type signals
RTD:Pt100, Cu50
Thermocouples: S/R/B/K/N/E/J/T with automatic cold junction temperature compensation。
Standard signals: 0-10mA/4-20mA/0-5V/1-5V
Linear non-standard signal: any signals within 0-100mV/0-400Ω, need set the range corresponding to input signal
● SCM intelligence
Can adjust the zero point and magnification manually, and there is no drift in linearity for long-term use
All parameters can be set freely as required
● Alarm control parameters can be set
Can use max four relay outputs
Can set each relay’s alarm value and hysteresis
Can set each relay’s alarm type (Upper alarm or lower alarm)
● Has various output
                                                                 om
Transmission output type: 0-10mA/4-20mA/0-5V/1-5V/0-20mA
Can adjust light beam individually
MODBUS-RTU standard communication protocol。
▇ Technical parameter
Measuring range: -1999-9999
                                                               .c
                                                            ai
Accuracy: ±0.5% of full scale
Supply voltage: AC0220(±10%); DC24V
                                                  l
Operating temperature:0-50℃
                                               ng
Operating humidity: 85% RH max, non-condensing
Power consumption: ≤5W
▇ Panel description (Take 160*80 panel as an example)
                                      .fi
                                                                                          智能数字显示控制仪
                             w
                                                                                               100
                                                                                        AHH
                                                                                                90
                                                                             1           AH
                                                                                                80
                            w
                                                                                         AL
                                                                                                70
                                                                                        ALL
                            智能单回路测控仪                                                            60
                                                                                                           SET    2
                  w
             AH   AHH                          PV
                                                                                                50
1                                                                   6
             AL   ALL                                                                           40
                                                                                                                  3
                                                                                                30
                                                                                                20
                                                                                                                  4
                                                                                               10                 5
                                     SET
                                                                                                 0
                                                                                        PV
                                                                                                                  6
                        5    4   3    2
1) Indicator light AH light: The upper limit relay output; AHH light: The upper upper limit relay output
                   AL light: The lower limit relay output; ALL light: the lower lower limit relay output
2) Function key
3) Add key
4) Minus key
5) Shift key
6) Measurement and function menu display window
                                                                1
                                                                                                                   Finglai
▇ Model number legend
T                   80           -□               □                     □
  Temperature       Design       Alarms:           Communication           Output type:
  controller        code         1: No alarm       N: None                 N: None
                                 2: 2 alarms       R: RS485                C420: 4-20mA
                                 3: 3 alarms                               C010: 0-10mA
                                                                           V15: 1-5V
                                                                           v05: 0-5V
▇ Input type code (corresponding to parameter Sn)
Code                Input type and       Code                 Code                   Input type and      Code
                    measured range                                                   measured range
00                  S(0-1600℃)           08                   Pt100(-200-850℃)       16                  mV no standard
                                                                                                         signal (0-100mV)
01                  R(0-1600℃)           09                   Cu50(-50-150℃)         17                  Resistance          no
                                                                                                         standard         signal
                                                                 om
                                                                                                         (0-400Ω)
02                  B(200-1800℃)         10                   0-5V(-1999-9999)       18                  Frequency           no
                                                                                                         standard         signal
                                                                                                         (0-3000Hz)
03
04
                    K(0-1300℃)
                    N(0-1300℃)
                                         11
                                         12                    .c
                                                              1-5V(-1999-9999)
                                                              0-10V(-1999-9999)
                                                                                     19
                                                                                     20
                                                                                                         0-5V2(-1999-9999)
                                                                                                         1-5V2(-1999-9999)
                                                            ai
05                  E(0-800℃)            13                   0-10mA(-1999-9999)     21                  0-10mA2(-1999-9999)
06                  J(0-650℃)            14                   0-20mA(-1999-9999)     22                  4-20mA2(-1999-9999)
                                                  l
                                               ng
07                  T(-200-400℃)         15                   4-20mA(-1999-9999)     23                  Multiple input
▇ First-level parameters setting
                                      .fi
Push down the SET key for 3 second, will enter the following menu: can select the next parameter by clicking the minus key,
the parameters is changed cyclically. If you want set the current parameter, can click SET key to enter the detailed parameters,
                         w
you can modify it by clicking shift key, add and minus key, when finished, can click the SET key to confirm. If you want return
the measured interface, can push down SET for 3 second to quite.
                        w
Parameter    Function                              Measured range     Default
                w
AH           Upper alarm value                     -1999-9999         300.0
dH           Upper alarm hysteresis                0-9999             1.0
AL           Lower alarm value                     -1999-9999         200.0
DL           Lower alarm hysteresis                0-9999             1.0
AHH          Upper upper alarm value               -1999-9999         400.0
Dhh          Upper upper alarm value hysteresis    0-9999             1.0
ALL          Lower lower alarm value               -1999-9999         100.0
Dll          Lower lower alarm hysteresis          0-9999             10
PASS         Second-level menu password            PASS               0 (When input 555, enter the second-level menu)
▇ Second-level parameters setting
When appear PASS parameter in the first-level menu, can click SET key, input password 555 in the PV window, then click SET
key to enter the second-level menu, the set parameter, save parameter and quite menu is same as the first-level parameters
setting.
                                                                2
                                                                                                   Finglai
Parameter   Name                                Set range                       Description
Sn          Input type                          0-22                            See input type table
dOt         Decimal point                       dot=0                           Without decimal point
                                                dot=1                           Ten decimals (show XXX.X)
                                                dot=2                           Hundred decimals (show
                                                dot=3                           XX.XX)
                                                                                Thousand decimals (show
                                                                                X.XXX)
PUL         Lower limit of measured             -999-9900                       Set the input signal’s lower
            range                                                               limit measured value
PUH         Upper limit of measured             -900-9999                       Set the input signal’s upper
            range                                                               limit measured value
PbIR        Zero shift                          Full scale range                Set zero point’s shift value
FILt        Filter coefficient                  0.100-0.900                     Can’t exceet0.900,otherwise
                                                                                 will be an error
K1          Input range’s magnification         0-1.999 magnification           Set       input         range’s
                                             om
                                                                                magnification
OU-R        First transmission output           OU-R=0 No transmission          Linear output corresponding
                                                output                          to the measured value
                                                OU-R=1 0-10mA
                                           .c   OU-R=2 4-20mA
                                                OU-R=3 0-20mA
                                        ai
PH          Upper limit alarm type              Thousands place : 0 alarm       Default is 0001
                                                  without flashing 1 alarm
                             l
                                                  with flashing
                          ng
                                                Hundreds place:0 Monitor
                                                PV
                                                Tens place: 0 The relay is NC
                 .fi
                                                   stats 1 The relay is NO
                                                   stats
             w
                                                Ones place: 0 Forbid alarm 1
                                                 upper alarm 2 lower alarm
            w
PL          Lower limit alarm type              Definition is the same as       Default is 0002
                                                PH
            w
PHH         Upper upper limit alarm type        Definition is the same as       Default is 0001
                                                PH
PLL         Lower lower limit alarm type        Definition is the same as       Default is 0002
                                                PH
InPH        Non-standard signal input           10-100mV; 10-400Ω; 2-300Hz      Default is 100.0
            Maximum
InPL        Non-standard signal input           0-90mV; 0-390Ω; 0-2998Hz        Default is 0.0
            minimum
bRUd        Communication baud rate             0=1200bps                       Communication speed
                                                1=2400bps
                                                2=4800bps
                                                3=9600bps
Id          Communication address               0-31                            Cannot exceed 31
K2          Bar graph display input range       0.100-9.999                     Only bar graph instrument
            ratio                                                               has this parameter
                                            3
                                                                                                                  Finglai
▇ Application description
The range selection of instrument and sensor: All sensor’s range must be same as instrument’s range, otherwise, the display
will display wrong value. For example: Liquid level transmitter range is 0-5m(According to the sensor label), output 4-20mA,
can set the instrument as the following: 1). enter the second-level parameters menu. 2). Set the parameters as follow:
Parameter                      Name                              Set value                    Description
Sn                             Input type                        15                           Must be same as the output
                                                                                               signal
Dot                            Decimal point                     2                            According to the accuracy
                                                                                              requirement
PuL                            Lower limit of measured           0.00                         The lowest range of the
                               range                                                          sensor
PuH                            Upper limit of measured           5.00                         The highest range of the
                               range                                                          sensor
Can see the following three examples, the transmitter is 0-5m
                                                              om
Example 1: Require instrument alarm when higher than 4m or lower than 1m. Push down the SET key for 3 second, enter the
first-level parameters menu,the parameters are as follow:
Parameter                      Name                              Set value                    Description
AH                             Upper alarm value
                                                            .c   4.00                         The relay output is upper
                                                                                              alarm
                                                         ai
dH                             Upper alarm hysteresis            0.05                         Can be set freely
AL                             Lower alarm value                 1.00                         The relay output is lower
                                               l
                                                                                              alarm
                                            ng
dL                             Lower alarm hysteresis            0.05                         Can be set freely
Example 2: Require start pump when lower than 1m, stop pump when higher than 4m. Push down the SET key for 3 second,
                                    .fi
enter the first-level parameters menu,the parameters are as follow:
Parameter                      Name                              Set value                    Description
                       w
AL                             Lower alarm value                 1.00                         The relay output is lower
                                                                                              alarm
                      w
dL                             Lower alarm hysteresis            3.00
               w
Example 3: Require start pump when higher than 4m, stop pump when lower than 1m. Push down the SET key for 3 second,
enter the first-level parameters menu,the parameters are as follow:
Parameter                      Name                              Set value                    Description
AH                             Upper alarm value                 4.00                         The relay output is upper
                                                                                              alarm
dH                             Upper alarm hysteresis            3.00
The upper upper limit and upper limit, lower lower limit and lower limit, their function are same in default. According the
 actual requirement Buyer can select It themselves (Can change it by the actual requirement)
Example 4: Adjustable the light beam,when buyer use the light beam instrument, if transformer range is 0-8m,the actual
measured liquid level is 0-5m,need the light beam’s percent display changed as 0-5m,display actual measured value. Can set
the parameters as follow: set Sn=15,dot=2, PUL=0.00, PUH=8.00, K2=8.00/5.00=1.600