Certificate of Examination and Test of Engine Generator: Certificate No.:DG/C1 Job No.: ASC-18N-0262

The document is a certificate of examination for a 400kVA diesel engine generator located at the Grand Excelsior Hotel in Dubai. It provides details of the generator such as the model, serial number, manufacturer, voltage and frequency ratings. The inspector found the generator to be in satisfactory working condition at the time of inspection, but noted some issues with exhaust smoke leakage and missing warning signage that need rectification. The generator is certified for continued use provided ongoing maintenance is performed and the inspector's recommendations are followed.

Uploaded by

Ravij
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views2 pages

Certificate of Examination and Test of Engine Generator: Certificate No.:DG/C1 Job No.: ASC-18N-0262

The document is a certificate of examination for a 400kVA diesel engine generator located at the Grand Excelsior Hotel in Dubai. It provides details of the generator such as the model, serial number, manufacturer, voltage and frequency ratings. The inspector found the generator to be in satisfactory working condition at the time of inspection, but noted some issues with exhaust smoke leakage and missing warning signage that need rectification. The generator is certified for continued use provided ongoing maintenance is performed and the inspector's recommendations are followed.

Uploaded by

Ravij
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

CERTIFICATE OF EXAMINATION AND TEST OF ENGINE GENERATOR

Certificate No.:DG/C1 Job No.: ASC-18N-0262


Name & Address of the Owner of the Equipment: Name & Address of the Manufacturer of the Equipment:
GRAND EXCELSIOR HOTEL, DUBAI, UNITED ARAB PERKINS
EMIRATES
Location: Survey Requested by: Type of Inspection:
AL BARSHA,PO BOX:214343,DUBAI, UNITED ARAB MR.RAJESH INITIAL
EMIRATES.
Model: Serial No: Year of Manufacture / Installation:
JGP400P3 FGDF3020U15367S NA
Manufacturer / Owner Identification No: Drive: Power Rating.:
DG-01 DIESEL ENGINE 400KVA
Voltage Rating: Current Rating: Frequency:
220/380 V 606 A 50 HZ
Dimensions: RPM: ENGINE TYPE
(L×W×H) – (3500 X1100X1500)mm 1500 PERKINS 2306A-E14TAG-3
ASC Test Method No.: ASC Test Equipment No.: Reference Regulation:
ASC/ITP/N/01 ASC/EQ/02/07 NFPA 70 B
Date of Previous Test: Previous Test Done By:
NIL NIL
Date of Test: Date of next Inspection:
16-08-2018 15-08-2019*
Inspector's Name: Authorized name:
JAYAKRISHNAN
Inspector's Signature: Authorized Signature:

*This Certificate becomes invalid, if any Alteration / Repair & Modification are done.

This is to certify that the Undersigned, a competent representative, did, attend to examine this equipment in accordance to the aforementioned standard to ascertain
its safe working load / max. working pressure and that the examination indicated that the said equipment has no indigenous injury or sighted deformation and the
safe working load / max. working pressure of the said equipment as either identified or test proof loaded / hydraulic pressure tested is shown. The equipment is
satisfactoty for its intended use within the limits specified and at the time of inspection was found to be satisfactory for further use, provided there is continuous
maintenance applied, implementation of our remarks & recommendations and qualified operators employed.

This certificate is granted subject to the condition that is understood and agreed that nothing herein contained shall be deemed to relieve any designer,
manufacturer, seller, supplier, repairer or operator of any warranty, express or implied, and Admiral Safety Consultants liability shall be limited to the acts or
omissions of its employees, agents and subcontractors. Under no circumstances whatsoever shall Admiral Safety Consultants be liable for any injury or damage to any
person or occurring by reason of negligent operation or any defect in materials, machinery, equipment or other items other than such defects ascertainable by
normally accepted standards and only those items actually inspected by Admiral Safety Consultants and which are covered by this certificate. This certificate shall not
be reproduced except in the full without the approval of Admiral Safety Consultant and receiving Client.

ADMIRAL SAFETY CONSULTANTS, TRADE LICENCE NO. 741090, AL GARHOUD, P.O.BOX 125218, DUBAI -UAE, TEL: 04-2899389, FAX: 054-2840557

Doc No. ASC/C/EG/52G (Rev.0) (27/04/2016) Page 1 of 2

Certificate No.:DG/C1 Job No.: ASC-18N-0262


COMPONENTS REMARKS
Equipment Manufacturer’s Instruction & Operational
OK
Manual & Last Test Report/Certificate Details Available
Controllers OK
Panel Board OK
Wiring Insulation OK
Proper Grounding OK
Meter OK
Vibrations OK
Emergency Stop Button OK
Safety Switch OK
Engine Lubrication OK
Caution/Warning Sign NOT OK
Name Plate OK
Automatic Sensors OK

General Condition Satisfactory

RECOMMENDATION / REMARKS

SATISFACTORYAT THE TIME OF INSPECTION


REMARKS
1) Exhaust smoke leakage issue needs to be rectified .
2) Electrical Danger/Warning Signages to be pasted.
3) Maintanace checklist/Tracker needs to be pasted at the engine room.

Doc No. ASC/C/EG/52G (Rev.0) (27/04/2016) Page 2 of 2