TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
DESIGN ANALYSES/ METHOD OF COMPUTATION
I.BRANCH CIRCUIT COMPUTATION SECOND FLOOR PANEL(BUILDING 1)
PANELBOARD-SECOND FLOOR (BUILDING 1)
A. BRANCH CIRCUIT No. 1
Capacity = 48.10 kVA
Voltage = 230 V
Phase = 3Ph, 2W
P. F. = 1.00
Capacity (KVA) = 48.10 kVA
FULL LOAD CURRENT:
= 48.10 kVA X 1000
$ 1.732 X 230 V
FLC = 120.75 A
CB RATING: = 120.75 X 1.25 = 150.93 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 175 AT 3P
100 AF MCCB
CABLE SIZE AMPACITY:
120.75 X 1.25 = 150.9 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 3 60.0 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 1%
VD = 30.8 X 120.75 X 100 LM
= 4.89 Volts
1000 X 38.0 X 2 SET/S
%VD = 4.89 Volts
230 Volts
%VD = 2.13 ≤ 1 %
USE: 2 SET/S 3 38.0 mm² THHN
FOR BRANCH CIRCUIT NO 1 :
USE: 2 SET/S 3 38.0 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 2 14.0 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 53.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
DESIGN ANALYSES/ METHOD OF COMPUTATION
I.BRANCH CIRCUIT COMPUTATION THIRD FLOOR PANEL(BUILDING 1)
PANELBOARD-THIRD FLOOR (BUILDING 1)
A. BRANCH CIRCUIT No. 2
Capacity = 48.10 kVA
Voltage = 230 V
Phase = 3Ph, 2W
P. F. = 1.00
Capacity (KVA) = 48.10 kVA
FULL LOAD CURRENT:
= 48.10 kVA X 1000
$ 1.732 X 230 V
FLC = 120.75 A
CB RATING: = 120.75 X 1.25 = 150.93 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 175 AT 3P
100 AF MCCB
CABLE SIZE AMPACITY:
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 3 60.0 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 1%
VD = 30.8 X 120.75 X 100 LM
= 4.89 Volts
1000 X 38.0 X 2 SET/S
%VD = 4.89 Volts
230 Volts
%VD = 2.13 ≤ 1 %
USE: 2 SET/S 3 38.0 mm² THHN
FOR BRANCH CIRCUIT NO 2 :
USE: 2 SET/S 3 38.0 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 2 14.0 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 53.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
DESIGN ANALYSES/ METHOD OF COMPUTATION
I.BRANCH CIRCUIT COMPUTATION GROUND FLOOR PANEL(BUILDING 2)
PANELBOARD-GROUND FLOOR (BUILDING 2)
A. BRANCH CIRCUIT No. 1
Capacity = 19.24 kVA
Voltage = 230 V
Phase = 3Ph, 2W
P. F. = 1.00
Capacity (KVA) = 19.24 kVA
FULL LOAD CURRENT:
= 19.24 kVA X 1000
$ 1.732 X 230 V
FLC = 48.30 A
CB RATING: = 48.30 X 1.25 = 60.37 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 85 AT 3P
100 AF MCCB
CABLE SIZE AMPACITY:
48.30 X 1.25 = 60.4 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 3 22.0 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 1%
VD = 30.8 X 48.30 X 100 LM
= 1.96 Volts
1000 X 38.0 X 2 SET/S
%VD = 1.96 Volts
230 Volts
%VD = 0.85 ≤ 1 %
USE: 2 SET/S 3 38.0 mm² THHN
FOR BRANCH CIRCUIT NO 1 :
USE: 2 SET/S 3 38.0 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 2 8.0 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 53.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
DESIGN ANALYSES/ METHOD OF COMPUTATION
I.BRANCH CIRCUIT COMPUTATION SECOND FLOOR PANEL(BUILDING 2)
PANELBOARD-SECOND FLOOR (BUILDING 2)
A. BRANCH CIRCUIT No. 2
Capacity = 20.68 kVA
Voltage = 230 V
Phase = 3Ph, 2W
P. F. = 1.00
Capacity (KVA) = 20.68 kVA
FULL LOAD CURRENT:
= 20.68 kVA X 1000
$ 1.732 X 230 V
FLC = 51.91 A
CB RATING: = 51.91 X 1.25 = 64.89 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 85 AT 3P
100 AF MCCB
CABLE SIZE AMPACITY:
51.91 X 1.25 = 64.9 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 3 22.0 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 1%
VD = 30.8 X 51.91 X 100 LM
= 2.10 Volts
1000 X 38.0 X 2 SET/S
%VD = 2.10 Volts
230 Volts
%VD = 0.91 ≤ 1 %
USE: 2 SET/S 3 38.0 mm² THHN
FOR BRANCH CIRCUIT NO 2 :
USE: 2 SET/S 3 38.0 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 2 8.0 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 53.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
DESIGN ANALYSES/ METHOD OF COMPUTATION
I.BRANCH CIRCUIT COMPUTATION THIRD FLOOR PANEL(BUILDING 2)
PANELBOARD-THIRD FLOOR (BUILDING 2)
A. BRANCH CIRCUIT No. 3
Capacity = 20.68 kVA
Voltage = 230 V
Phase = 3Ph, 2W
P. F. = 1.00
Capacity (KVA) = 20.68 kVA
FULL LOAD CURRENT:
= 20.68 kVA X 1000
$ 1.732 X 230 V
FLC = 51.91 A
CB RATING: = 51.91 X 1.25 = 64.89 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 85 AT 3P
100 AF MCCB
CABLE SIZE AMPACITY:
51.91 X 1.25 = 64.9 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 3 22.0 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 1%
VD = 30.8 X 51.91 X 100 LM
= 2.10 Volts
1000 X 38.0 X 2 SET/S
%VD = 2.10 Volts
230 Volts
%VD = 0.91 ≤ 1 %
USE: 2 SET/S 3 38.0 mm² THHN
FOR BRANCH CIRCUIT NO 3 :
USE: 2 SET/S 3 38.0 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 2 8.0 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 53.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
I2 BRANCH CIRCUIT COMPUTATION
LIGHTING PANELBOARD-SECOND FLOOR (BUILDING 1)
B. Circuit No. 1 - Lighting
Capacity = 3.39 kVA
Voltage = 230 V
Phase = 1Ph, 2W
P. F. = 1.00
Capacity (KVA) = 3.39 kVA
FULL LOAD CURRENT:
= 3.39 kVA X 1000
$ 1 X 230 V
FLC = 14.74 A
CB RATING: = 14.74 X 1.25 = 18.42 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 20 AT 1P
30 AF MCCB
CABLE SIZE AMPACITY:
14.74 X 1.25 = 18.4 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 2 3.5 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 3%
VD = 35.6 X 14.74 X 61 LM
= 9.14 Volts
1000 X 3.5 X 1 SET/S
%VD = 9.14 Volts
230 Volts
%VD = 3.98 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
FOR BRANCH CIRCUIT NO 2 :
USE: 1 SET/S 2- 3.5 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 1- 3.5 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 16.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
I2 BRANCH CIRCUIT COMPUTATION
LIGHTING PANELBOARD THIRD FLOOR (BUILDING 1)
B. Circuit No. 2 - Lighting
Capacity = 3.30 kVA
Voltage = 230 V
Phase = 1Ph, 2W
P. F. = 1.00
Capacity (KVA) = 3.30 kVA
FULL LOAD CURRENT:
= 3.30 kVA X 1000
$ 1 X 230 V
FLC = 14.35 A
CB RATING: = 14.35 X 1.25 = 17.93 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 20 AT 1P
30 AF MCCB
CABLE SIZE AMPACITY:
14.35 X 1.25 = 17.9 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 2 3.5 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 3%
VD = 35.6 X 14.35 X 61 LM
= 8.90 Volts
1000 X 3.5 X 1 SET/S
%VD = 8.90 Volts
230 Volts
%VD = 3.87 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
FOR BRANCH CIRCUIT NO 2 :
USE: 1 SET/S 2- 3.5 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 1- 3.5 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 16.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
I2 BRANCH CIRCUIT COMPUTATION
LIGHTING PANELBOARD GROUND FLOOR (BUILDING 2)
B. Circuit No. 1 - Lighting
Capacity = 1.62 kVA
Voltage = 230 V
Phase = 1Ph, 2W
P. F. = 1.00
Capacity (KVA) = 1.62 kVA
FULL LOAD CURRENT:
= 1.62 kVA X 1000
$ 1 X 230 V
FLC = 7.04 A
CB RATING: = 7.04 X 1.25 = 8.80 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 15 AT 1P
30 AF MCCB
CABLE SIZE AMPACITY:
7.04 X 1.25 = 8.8 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 2 3.5 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 3%
VD = 35.6 X 7.04 X 61 LM
= 4.37 Volts
1000 X 3.5 X 1 SET/S
%VD = 4.37 Volts
230 Volts
%VD = 1.90 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
FOR BRANCH CIRCUIT NO. 1 :
USE: 1 SET/S 2- 3.5 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 1- 2.0 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 16.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
I2 BRANCH CIRCUIT COMPUTATION
LIGHTING PANELBOARD SECOND FLOOR (BUILDING 2)
B. Circuit No. 2 - Lighting
Capacity = 1.68 kVA
Voltage = 230 V
Phase = 1Ph, 2W
P. F. = 1.00
Capacity (KVA) = 1.68 kVA
FULL LOAD CURRENT:
= 1.68 kVA X 1000
$ 1 X 230 V
FLC = 7.30 A
CB RATING: = 7.30 X 1.25 = 9.13 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 15 AT 1P
30 AF MCCB
CABLE SIZE AMPACITY:
7.30 X 1.25 = 9.1 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 2 3.5 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 3%
VD = 35.6 X 7.30 X 61 LM
= 4.53 Volts
1000 X 3.5 X 1 SET/S
%VD = 4.53 Volts
230 Volts
%VD = 1.97 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
FOR BRANCH CIRCUIT NO 2 :
USE: 1 SET/S 2- 3.5 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 1- 2.0 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 16.0 mmØ IMC
TAGANITO HPAL PROJECT
TAGANITO, SURIGAO DEL NORTE
I2 BRANCH CIRCUIT COMPUTATION
LIGHTING PANELBOARD THIRD FLOOR (BUILDING 2)
B. Circuit No. 3 - Lighting
Capacity = 1.44 kVA
Voltage = 230 V
Phase = 1Ph, 2W
P. F. = 1.00
Capacity (KVA) = 1.44 kVA
FULL LOAD CURRENT:
= 1.44 kVA X 1000
$ 1 X 230 V
FLC = 6.26 A
CB RATING: = 6.26 X 1.25 = 7.83 A
Article 2.10 .2.3 (A) Overcurrent Protection PEC 1 2017 page 44
USE: 15 AT 1P
30 AF MCCB
CABLE SIZE AMPACITY:
6.26 X 1.25 = 7.8 A
Article 2.10 .2.2 (A)(1)(a) Conductor setting PEC 1 2017 page 43
1 SET/S 2 3.5 mm² THHN
VOLTAGE DROP CALCULATION:
* Allowable Voltage Drop for Branch Circuit say 3%
VD = 35.6 X 6.26 X 61 LM
= 3.88 Volts
1000 X 3.5 X 1 SET/S
%VD = 3.88 Volts
230 Volts
%VD = 1.69 ≤ 3 %
USE: 1 SET/S 2 3.5 mm² THHN
FOR BRANCH CIRCUIT NO 3 :
USE: 1 SET/S 2- 3.5 mm² THHN
FOR GROUND WIRE:
Article 2.50. Table 2.50.6.13 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
PEC 1 2017 page 124
USE: 1- 2.0 mm² Copper Wire
FOR CONDUIT SIZING:
Article 3.0 Table 3.0.1.1© Metric Designator and Trade Size
USE: 1- 16.0 mmØ IMC