Transformers Book 2
Transformers Book 2
TECHNOLOGY, KUMASI
W
SANE NO B A
P. Y. OKYERE
SENIOR LECTURER
KNUST
SEPTEMBER 2012 (REVISED EDITION)
Contact Address
Phone: 0322063952
0208124340
E-mail: okyerepy@yahoo.com
pyokyere.soe@knust.edu.gh
ii
Course Author
Dr. Philip Yaw Okyere graduated with a B.Sc. (First Class Honours) degree in electrical
engineering in 1979. After one-year national service in the Department of Electrical & Electronic
Engineering as Teaching Assistant, he proceeded to L’Institut National Polytechnique de
Grenoble (INPG), France to pursue postgraduate studies in electrical engineering on a
scholarship from the French Government. He graduated with DEA (“Mention: Bien”) and
Docteur-Ingenieur degrees in 1982 and 1985 respectively. He returned to Ghana to join the
Department of Electrical & Electronic Engineering of KNUST as a Lecturer in 1985 and was
promoted to Senior Lecturer in 1995.
Dr. Philip Yaw Okyere has taught courses in Electrical Machines, Electric Drives, Power
Electronics and Power Systems and has rendered professional services to industry and the
University. He has produced publications in diverse areas, including power system modelling,
lightning protection, earth electrode resistance enhancement, application of artificial neural
networks to power systems, and renewable energies. His current research interest is in
integration of renewable energy sources into power systems.
iii
Course Outline
Transformers:
Construction; Basic theory; Phasor Diagram; Equivalent Circuits; No-load and Short-Circuit
Tests; Voltage Regulation; Efficiency; Cooling methods; Polarity; Polyphase transformer
Connections; Per-Unit Calculation; Parallel Operation of Transformers; Auto transformers;
Tap-Changing transformers; Instrument Transformers.
Recommended Textbooks
2. John Hindmarsh (1977):Electrical Machines and their Applications, Pergamon Press, Oxford
3. Robert Stein, William T. Hunt, Jr. (1979): Electric Power System Components, Transformers
and rotating Machines, Van Nostrand Reinhold Company, New York
iv
Contents
Contact Address............................................................................................................................................ ii
Course Author .............................................................................................................................................. iii
Course Outline.............................................................................................................................................. iv
Recommended Textbooks ............................................................................................................................ iv
CHAPTER ONE ...............................................................................................................................................1
TRANSFORMERS............................................................................................................................................ 1
1 Introduction .......................................................................................................................................... 1
2 Principle of operation of a transformer................................................................................................ 1
3 Polarity and terminal markings of a transformer ................................................................................. 2
4 Ideal transformer .................................................................................................................................. 2
4.1 Properties of an ideal transformer .............................................................................................. 2
4.1.1 Emf equation and voltage ratio (see Fig. 3) .......................................................................... 2
4.1.2 Current ratio and power equation........................................................................................3
4.1.3 Phasor diagram of an ideal transformer (Fig. 4) ................................................................... 4
4.1.4 Impedance ratio (see Fig. 5).................................................................................................. 5
4.1.5 Equivalent circuits of an ideal transformer........................................................................... 5
5 Practical single-phase transformer ....................................................................................................... 7
5.1 Hysteresis loss .............................................................................................................................. 7
5.2 Eddy-current loss.......................................................................................................................... 7
5.3 Phasor diagram on no load .......................................................................................................... 9
5.4 Mutual and leakage fluxes in a transformer (see Fig. 9)........................................................... 10
5.5 Equivalent circuit of a practical transformer.............................................................................11
5.6 Equivalent circuit referred to the primary side (Fig. 12)........................................................... 12
5.7 Equivalent circuit referred to the secondary side (Fig. 13).......................................................13
5.8 Approximate equivalent circuits................................................................................................13
5.9 The complete phasor diagrams for loaded conditions .............................................................14
5.10 Rating of transformers ............................................................................................................... 15
5.11 The turns ratio............................................................................................................................ 15
5.12 Definition of per-unit impedances.............................................................................................17
v
5.13 Voltage regulation......................................................................................................................17
5.14 Transformer output....................................................................................................................21
5.15 Efficiency..................................................................................................................................... 21
5.16 All-day efficiency ........................................................................................................................23
5.17 Open-circuit and short-circuit tests on a transformer ..............................................................24
5.17.1 Short-circuit test ................................................................................................................. 24
5.17.2 Open-circuit test or no load test......................................................................................... 25
5.18 Construction of transformers .................................................................................................... 28
5.19 Polarity tests...............................................................................................................................28
5.19.1 Using a low-voltage ac source.............................................................................................29
5.19.2 Using dc source ...................................................................................................................29
5.20 Parallel Operation of single-phase transformers ...................................................................... 30
5.21 Load sharing of parallel-connected transformers..................................................................... 31
6 Three-phase transformers .................................................................................................................. 33
6.1 A three-phase transformer bank ...............................................................................................33
6.2 A three-phase transformer unit.................................................................................................34
6.3 Winding arrangement ................................................................................................................ 35
6.3.1 Star connection ...................................................................................................................35
6.3.2 Delta connection................................................................................................................. 35
6.3.3 Zigzag (or interconnected star) connection........................................................................35
6.4 Vector groups ............................................................................................................................. 35
6.5 Three-phase transformer connections ......................................................................................37
6.5.1 Delta-Delta connection (Fig 29.a) .......................................................................................37
6.5.2 Delta-Star connection (Fig. 29.b) ........................................................................................37
6.5.3 Star-Delta connection .........................................................................................................38
6.5.4 Star-Star connection ...........................................................................................................38
6.5.5 Star-Zigzag connection........................................................................................................38
6.6 Parallel operation of three-phase transformers (Fig. 30) ......................................................... 42
7 Cooling methods .................................................................................................................................43
7.1 Air Cooling (Dry type transformers) .......................................................................................... 44
7.1.1 AN........................................................................................................................................ 44
7.1.2 AF ........................................................................................................................................ 44
vi
7.2 Oil-immersed, Oil cooling...........................................................................................................44
7.2.1 ONAN ..................................................................................................................................44
7.2.2 ONAF ...................................................................................................................................44
7.2.3 OFAF....................................................................................................................................44
7.3 Oil-immersed, Water cooling..................................................................................................... 45
7.3.1 ONWF..................................................................................................................................45
7.3.2 OFWF...................................................................................................................................45
8 Tap-changing Transformers ................................................................................................................ 45
8.1 Changing the taps of transformers ............................................................................................ 45
8.1.1 Off-load tap changing..........................................................................................................46
8.1.2 On-load tap changing..........................................................................................................46
9 Autotransformers................................................................................................................................48
9.1 Autotransformer equations ....................................................................................................... 49
9.2 Advantages and disadvantages of autotransformer over two-winding transformer.............. 49
9.3 Two-winding transformer connected as an autotransformer..................................................50
9.4 Applications of autotransformers..............................................................................................52
10 Instrument transformers ................................................................................................................ 52
10.1 The voltage or potential transformers (VTs or PTs)..................................................................53
10.2 Current transformers (CTs) ........................................................................................................53
11 Further exercises.............................................................................................................................57
CHAPTER TWO ............................................................................................................................................59
ELECTROMECHANICAL ENERGY CONVERSION ........................................................................................... 59
1 Introduction ........................................................................................................................................ 59
2 Forces and Torques Developed by Electromechanical Devices.......................................................... 59
3 Energy balance....................................................................................................................................59
4 Force in Singly Excited Electric Field System....................................................................................... 60
5 Force in Singly Excited Magnetic Systems .......................................................................................... 63
6 Useful relations for calculating forces and torques............................................................................64
7 Magnetic Field Energy and Coenergy .................................................................................................66
8 Torque in Singly-Excited Systems........................................................................................................70
9 Torques and Forces in Doubly Excited Magnetic Field Systems ......................................................... 72
10 Alignment and Interaction Forces...................................................................................................74
vii
10.1 Alignment Forces........................................................................................................................74
10.2 Interaction forces .......................................................................................................................74
11 Motional emf ..................................................................................................................................75
12 Examples of Electromechanical Devices ......................................................................................... 76
12.1 Solenoid Relay (Fig. 10) ..............................................................................................................76
12.2 Plunger relay (Fig. 11)................................................................................................................. 77
12.3 Horse shoe electromagnet.........................................................................................................78
12.4 Electrostatic voltmeter............................................................................................................... 79
12.5 Electrostatic loudspeaker...........................................................................................................81
13 Further exercises.............................................................................................................................83
viii
CHAPTER ONE
TRANSFORMERS
1 Introduction
The transformer transfers electrical energy from one circuit to another via the medium of a
pulsating magnetic field that links both circuits. The widespread development of ac power
systems is principally due to the transformer. It enables us to produce and transmit power at
economical voltages and to distribute it safely in factories and homes. In low-power low-current
electronic and control circuits, it is used to provide impedance matching between a source and its
load for maximum power transfer, to isolate one circuit from another, to isolate direct current
while maintaining ac continuity between two circuits and to provide reduced ac voltages and
currents for protection, metering, instrumentation and control.
1
3 Polarity and terminal markings of a transformer
Voltage E1 is induced in coil 1 and voltage E2 in coil 2. These voltages are in phase. Referring to
Fig.2, suppose at any given instant when the primary terminal 1 is positive with respect to
primary terminal 2, the secondary terminal 3 is also positive with respect to secondary terminal
4. Then terminals 1 and 3 are said to have the same polarity. To indicate that their polarities are
the same, a dot is placed beside primary terminal 1 and secondary terminal 3. Alternatively,
letters of the same suffix, A1 (for the high-voltage winding) and a1 (for the low-voltage winding)
say can be used. We note that current I1 entering coil 1 through the dotted terminal 1 and current
I2 entering coil 2 through the dotted terminal 3 create fluxes in the same direction.
4 Ideal transformer
An ideal transformer has no losses, no leakage flux and its core is infinitely permeable. An ideal
transformer is shown in Fig. 3. The mutual flux Φm is confined to the iron. The primary current I1
is zero on no load.
With the primary connected to an ac source V1, an alternating flux Φm is produced in the core.
Let the flux be expressed as
m max sin t webers (1)
2
The induced emf e1 as indicated in Fig. 1 is given by
d d
e1 N1 m N1 max sin t N1 max cos t
dt dt
Hence
N1 max 2fN1
E1 max
2 2
Similarly
N 2 max 2fN 2 max
E2 4.44 fN 2 max (4)
2 2
The ratio a = N1/N2 is called the turns ratio. A step-up transformer has a < 1 and a step-down
transformer has a > 1. In an ideal transformer, the applied voltage V1 and the induced voltage E1
must be identical. Hence we may write
V1 E1 (6.a)
and
V1 4.44 fN 1 max (6.b)
Equation (6.b) indicates that for a given frequency, number of turns and voltage, the peak flux
max must remain constant.
On no load I1 = 0. Now if a load is connected across the secondary terminals (i.e. switch S is
closed) current I2 flows through the load. This current produces mmf N2I2 which if it acted alone
would by Lenz’s law, cause the mutual flux to reduce. Since when V1 is fixed the flux Φmax is
also fixed, the primary develops mmf N1I1 which is such that
N1 I1 N 2 I 2 (7.a)
I1 I 2 a (7.b)
In ideal transformer the secondary voltage
V 2 E 2 (8)
3
The voltage V2 remains constant since E2 is fixed when the Φmax is fixed. It can be deduced from
equations (5), (6.a), (7.a) and (8) that for an ideal transformer
V1 I 1 V2 I 2 (9)
Example 1
An ideal transformer having 90 turns on the primary and 2250 turns on the secondary is
connected to a 200-V, 50-Hz source. The load across the secondary draws a current of 2 A at a
power factor of 0.80 lagging. Calculate (a) the rms value of the primary current (b) the flux
linked by the secondary winding (c) Draw the phasor diagram.
Solution
(a) N 1 I 1 N 2 I 2 90 I 1 2250 2 I 1 50 A
V1 200
(b) max 0.01 Wb
4.44 fN 1 4.44 50 90
N
(c) E 2 2 E1 5000 V
N1
The phase angle between V2 and I 2 is cos -1 (0.8) 36.9
4
Example 2
A 200-kVA, 6600-V / 400-V, 50-Hz 1-ph transformer has 80 turns on the secondary. Calculate
(a) the approximate values of the primary and secondary full-load currents (b) the approximate
number of primary turns and (c) the maximum value of the flux.
Solution
(a) Full - load primary current (200 1000) 6600 30.3 A
and full - load secondary current (200 1000) 400 500 A
(b) N 1 (80 6600) 400 1320
V2 400
(c) max 0.0225 Wb
4.44 fN 2 4.44 50 80
Hence
Ze a2Z (10)
From equation (10), we can represent the transformer in Fig. 5 by equivalent circuit shown in
Fig. 6.a. We may also write
I 2 Z E 2 E1 a V1 a
V1
I2Z (11)
a
and then represent the transformer by an equivalent circuit shown in Fig. 6.b
5
(a) Circuit referred to the primary side (b) Circuit referred to the secondary side
Example 3
Calculate the voltage V and current I in the circuit of Fig. 7, knowing that the ideal transformer
has a primary to secondary turns of 1:100 (i.e. a = 1/100).
Solution
We shall shift all impedances to the primary side to obtain the equivalent circuit:
V aV
Total impedance Z e R 2 X L X C 4 2 32 5
2
V1 10
Total current I 2A
Ze 5
Voltage across the 4-ohm resistance V IR 2 4 8 V.
V
The actual voltage V 100 8 800 V
a
6
5 Practical single-phase transformer
The windings of a practical transformer have both resistance and leakage inductance. The core is
also imperfect: it has a core loss and finite permeability. The core loss has two components:
hysteresis loss and eddy current loss.
The index x is named after Steinmetz and is about 1.6 though it may be higher. In practice the
2
hysteresis loss, for simplicity, is often taken as proportional to Bmax
where
t = thickness of the laminations
ρ = resistivity of the material
k = a constant which depends on the waveform of the alternating flux
At high frequencies where it is not practicable to make very thin laminations, core losses may be
reduced by using ferrite cores or dust cores. Ferrite is a ceramic material having magnetic
properties similar to silicon steel, and dust cores consist of fine particles of carbonyl iron or
7
permalloy (i.e. nickel and iron), each particle of which is insulated from its neighbour by a
binding material. Such materials have a very high value of resistivity.
Example 4
The core of a transformer operating at 50 Hz has an eddy current loss of 100 W/m3 and the core
laminations have a thickness of 0.50 mm. The core is redesigned so as to operate with the same
eddy current loss but at a different voltage and at a frequency of 250 Hz. Assuming that at the
new voltage the maximum flux density is one-third of its original value and the resistivity of the
core remains unaltered, determine the necessary new thickness of the laminations.
Solution
From equation (13.a), we can write
2 2 2
Pe 2 f 2 t2 Bmax 2 1
Pe1 f1 t1 Bmax 1 2
B 1
Since eddy current loss and resistivity remain the same, and max 2 , we have
Bmax 1 3
2 2 2
250 t 2 1
1
50 0.50 3
50 3
Therefore the new thickness t 2 0.50 0.30 mm
250 1
We note that if the new voltage had been given rather than Bmax2, then we would have used
equation (6.b) to find Bmax2. From equation (6.b), we can write
V1, 2 f 2 N 1, 2 max 2 f 2 N 1, 2 Bmax 2 A2
V1,1 f 1 N 1,1 max 1 f 1 N 1,1 Bmax 1 A1
If the number of turns and the cross section remain the same, then the equation reduces to
V1, 2 f 2 Bmax 2
V1,1 f 1 Bmax 1
We can use the above equation to find the new voltage (V1,2) in example 4 if it is required.
Example 5
In a transformer core of volume 0.16 m3 the total iron loss was found to be 2170 W at 50 Hz.
The hysteresis loop of the core material, taken to the same maximum flux density, had an area of
9.0 cm2 when drawn to scales of 1 cm = 0.1 Wb/m2 and 1 cm = 250 AT/m. Calculate the total
iron loss in the transformer core if it is energized to the same maximum flux density, but at a
frequency of 60 Hz.
8
Solution
Hysteresis loss WH = area x scale factors = 9 x 0.1 x 250 = 225 J/m3
At 50 Hz, hysteresis loss Ph fWH volume of core = 225 x 50 x 0.16 = 1800 W
Therefore eddy-current loss = 2170 – 1800 = 370 W
From equation (12), at 60 Hz, hysteresis loss = 1800 x (60/50) = 2160 W
and from equation (13.b), eddy-current loss = 370 x (60/50)2 = 533 W
Therefore total iron loss = 2160 + 533 = 2693 W
Example 6
For the same maximum flux density, the total core loss in a core is 500 W at 25 Hz and 1400 W
at 50 Hz. Find the hysteresis and eddy-current losses for both frequencies.
Solution
Since Bmax is constant, the losses can have the following forms:
Ph Af , Pe Bf 2 and Pc Ph Pe Af Bf 2
For a frequency of 25 Hz, the core loss = 500 = A(25) + B(25)2
For a frequency of 50 Hz, the core loss = 1400 = A(50) + B(50)2
Solving the two equations, we obtain A = 12, B = 0.32 and the individual losses
Ph = 300 W, Pe = 200 W at 25 Hz and Ph = 600 W, Pe = 800 W at 50 Hz
We note that
(i) the no-load current Io taken by the primary is the phasor sum of Ip and Im
(ii) the difference between the value of the applied voltage V1 and that of the induced emf E1 is
only about 0.05% when the transformer is on no load so the two can be considered to be
equal
(iii) Ip is very small compared with Im. Therefore the no-load power factor is very low.
9
Example 7
A 1-ph transformer has 480 turns on the primary and 90 turns on the secondary. The mean length
of the flux path in the iron core lc is 1.8 m and the joints are equivalent to an air gap lg of 0.1 mm.
If the peak value of the flux density is to be 1.1 T when a voltage of 2200 V at 50 Hz is applied
to the primary, find (a) the cross-sectional area of the core (b) the secondary voltage on no load
(c) the primary current and power factor on no load.
Assume the value of the magnetic field strength Hc for 1.1 T in iron to be 400 A/m, the
corresponding iron loss to be 1.7 W/kg at 50 Hz and the density of the iron to be 7800 kg/m3.
Solution
The magnetic circuit of the transformer consists of iron core in series with the air gap.
V1 2200
(a) max 0.0206 Wb
4.44 fN 1 4.44 50 480
0.0206
Cross - sectional area of core Ac max 0.0187m 2
Bmax 1.1
N 90
(b) Secondary voltage on no load V2 V1 2 2200 412.5 V
N1 480
(c) Peak value of mmf required for the iron core Fg max H c l c 400 1.8 720 A
Bg 1.1
Peak value of mmf for the air gap Fg max H g l g lg 0.0001 87.5 A
o 4 10 7
Peak value of total mmf required to produce max Fc max Fg max 720 87.5 807.5 A
Peak value of total mmf 807.5
Peak value of magnetizing current 1.682 A
N1 480
1.682
Its rms value assuming it to be sinusoidal I m 1.19 A
2
Volume of iron l c Ac 1.8 0.0187 0.0337 m 3
Mass of iron volume density 0.0337 7800 263 kg
And iron loss 263 1.7 447 W
I p Iron loss V1 447 2200 0.203 A
No load current I o 1.19 2 0.203 2 1.21 A
No load power factor I p I o 0.203 1.21 0.168 lagging
10
Fig. 9 Transformer possessing two leakage fluxes and a mutual flux
We can separate the four voltages E1, E2, El1 and El2 by rearranging the transformer circuit as
shown in Fig. 10. The rearrangement of the transformer circuit makes it clear that El1 and El2 are
voltage drops across reactances. These reactances called leakage reactances are given
by X 1 El1 I 1 and X 2 El 2 I 2
Let a N 1 N 2 (14.a)
Then
X 2 ( N 1 N 2 ) 2 X 2 a 2 X 2 , R2 ( N 1 N 2 ) 2 R2 a 2 R2 , Z ( N 1 N 2 ) 2 Z a 2 Z (14.b)
V2 ( N 1 N 2 ) V2 aV2 , I 2 I 2 a (14.c)
It is worth noting that for a practical transformer, R2 R1 and X 2 X1
12
5.7 Equivalent circuit referred to the secondary side (Fig. 13)
R1 ( N 2 N 1 ) 2 R1 R1 a 2 , etc (15.a)
N 2 I p N1 I p or I p aI p etc (15.b)
(a)
(b)
13
(c)
The exciting or no load current Io causes voltage drop in the primary leakage impedance. In Fig.
14.a, this voltage drop is neglected.
In Fig. 14.b, the exciting current is neglected entirely. Using this circuit may not cause serious
errors in some applications such as voltage regulation calculations.
In Fig. 14.c, Re is ignored. For transformers above 500 kVA where Xe is at least 5 times greater
than Re, this circuit can be used to calculate say, voltage regulation.
Fig. 15 Complete phasor diagrams for loaded conditions (drawn in two parts)
14
5.10 Rating of transformers
To keep the transformer temperature at an acceptable level, limits are set to both the applied
voltage (this determines the iron loss at a given frequency) and the current drawn by the load
(this determines copper loss in the windings). The limits determine the rated voltage and rated
current of transformers.
The power rating of transformer Srated = rated voltage x rated current can be expressed in VA,
kVA or MVA depending on the size of the transformer. The rated kVA (i.e. the rated power),
frequency and voltage are always shown on the name plate. In large transformers, the
corresponding currents are also shown.
We note that
Rated kVA = V1r x I1fl x10-3 = V2r x I2fl x 10-3 = V2n x I2fl x10-3 = E2n x I2fl x10-3
where
V1r = rated primary voltage
I1fl = rated primary current = primary full load current
V2r = rated secondary voltage = V2n (no load secondary voltage corresponding to the rated
primary voltage) = E2n (no load induced secondary voltage corresponding to primary rated
voltage)
I2fl = rated secondary current = secondary full load current
E1 V1r on no load because I o Z1 is very small. Since the induced voltage in the secondary is
equal to the secondary terminal voltage on no load
a V1r V 2 r (16.a)
and
I 1 fl I 2 fl a (16.b)
Example 8
A transformer is rated 10 kVA, 2400 / 240 V, 60 Hz. The parameters for the approximate
equivalent circuit of Fig. 14.a are Rm = 80 kΩ, Xm = 35 kΩ, Re1 = 8.4 Ω and Xe1 = 13.7 Ω.
Determine the voltage to be applied to the primary to obtain the rated current in the secondary
when the secondary terminal voltage is 240 V. What is the input power factor? The load power
factor is 0.8 lagging.
15
Solution
The secondary current when referred to the primary I 2 I 2 fl a I 1 fl 10000 2400 4.17 A
The load power factor angle cos 1 0.8 36.9
If we choose the load current I2 as the reference phasor, then V 2 24036.9
The load voltage referred to the primary V aV 240036.9 1920 j1440 volts
2 2
Example 9
A 1-ph transformer operates from a 230-V supply. It has an equivalent resistance of 0.1 Ω and an
equivalent leakage reactance of 0.5 Ω referred to the primary. The secondary is connected to a
coil having a resistance of 200 Ω and a reactance of 100 Ω. Calculate the secondary terminal
voltage. The secondary winding has four times as many turns as the primary.
Solution
Refer to approximate equivalent circuit of Fig. 14.b
N 1
a 1 , Z 200 j100 , Z a 2 200 j100 12.5 j 6.25
N2 4
Total impedance referred to the primary Z e1 Z 0.1 j 0.5 12.5 j 6.25 12.6 j 6.75
2300 2300
I2 and V 2 12.5 j 6.25
12.6 j 6.75 12.6 j 6.75
230 12.5 j 6.25 230 13.9754
The magnitude of the voltage V 2 224.8719 volts
12.6 j 6.75 14.2941
V
The actual secondary load voltage V2 2 4 224.8719 899 volts
a
16
5.12 Definition of per-unit impedances
The leakage impedances Z1 and Z2 on the primary and secondary side are expressed in per unit as
follows:
Z1
Zˆ1 (17.a)
Z 1base
Z2
Zˆ 2 (17.b)
Z 2 base
where
V1r V2 V2 r V2
Z 1base 1r and Z 2 base 2r (17.c)
I 1 fl S rated I 2 fl S rated
The impedances are said to be expressed in per unit with reference to a base voltage and a base
power which have been chosen in the case of transformers to be V1r, Srated for the primary circuit
and V2r, Srated for the secondary circuit. The total impedance of the transformer in per unit
Zˆ1 Zˆ 2 .
Example 10
A single-phase transformer that is rated 3000 kVA, 69 kV / 4.16 kV, 60 Hz has an impedance of
8 per cent. Calculate the total impedance of the transformer referred to (a) the primary side (b)
the secondary side
Solution
Vr2 69 2 10 6
(a ) Z1base 1587
S rated 3000 10 3
Z e1 Zˆ e1 Z1base 0.08 1587 127
V22r 4.16 2 10 6
(b) Z 2base 5.7685
S rated 3000 10 3
Z e 2 Zˆ e 2 Z 2 base 0.08 5.7685 0.46
2 2
N 4.16
Alternatively Z e 2 2 Z e1 127 0.46
N1 69
17
usually expressed as a percentage (called percentage regulation), or a fraction of the rated or no-
load terminal voltage (in per unit).
The equivalent circuit given in Fig. 14.b is used to calculate voltage regulation. The circuit may
be either referred to the primary or the secondary side. Therefore the circuit is represented in
general form as shown in Fig. 16.
Re Xe
E Load V
E V V1 V2
Voltage regulation pu (18.a)
E V1
V2 n V 2
Voltage regulation pu (18.b)
V2 n
The voltage regulation given by equations (18.a) and (18.b) are equal as shown below:
V V2 V a V2 a V2 n V 2
1 1 (19)
V1 V1 a V2 n
When voltage regulation is known the terminal voltage can be calculated as follows:
V2 1 V2 n (20)
In general, let the load current be I lagging behind the load voltage V by . Then taking the load
voltage as the reference phasor, we can write
E V 1 j 0 Re jX e I cos jI sin
V IRe cos IX e sin j IX e cos IRe sin
18
and hence
E E V IRe cos IX e sin 2 IX e cos IRe sin 2
The second term under the root is usually negligible except at low leading power factors.
Considering the first term only gives
E V IRe cos IX e sin
E V IRe cos IX e sin and (21.a)
E V IRe IX
cos e sin (21.b)
E E E
The angle is negative when current is leading and positive when current is lagging.
The voltage regulation is maximum for a given current or power when = where
X R X
tan e or cos e or sin e (22.a)
Re Ze Ze
Proof:
d X
From E V IRe sin IX e cos 0 , we have tan e tan
d Re
where
2 2
Z e Re X e (22.c)
E rated V I I fl R I I fl X
cos sin
E rated I E I E
fl rated fl rated
E rated V
I p.u . R p.u. cos I p.u . X p.u. sin (23)
E rated
where
I p.u. I I fl current in per unit R p.u. I fl R E rated resistance in per unit , etc
19
We note the following:
(i) Usually the quantities will be referred to the secondary side.
(ii) Where E is the rated voltage and transformers parameters are given in per unit, equation (23)
may be used. We should remember that with impedances in per unit, primary and secondary
impedances can be added directly.
(iii)The voltage regulation equations (21.a), (21.b), (22.b) and (23) are correct at any current or
kVA.
(iv)At rated current or kVA, Ip.u.=1.
Example 11
A 100-kVA 1-ph transformer has 400 turns on the primary and 80 turns on the secondary. The
primary and secondary resistances are 0.3 Ω and 0.01 Ω respectively, and the corresponding
leakage reactances are 1.1 Ω and 0.035 Ω respectively. The supply voltage is 2200 V. Calculate
(a) the equivalent impedance referred to the primary circuit and (b) the voltage regulation and the
secondary terminal voltage for full load having a power factor of (i) 0.8 lagging and (ii) 0.8
leading (c) the maximum voltage regulation
Solution
(a) Re1 R1 ( N1 N 2 ) 2 R2 0.3 0.01 (400 80) 2 0.55
X e1 1.1 0.035 (400 80) 2 1.975
1
Z e1 0.552 1.9752 2 2.05
(b) (i ) cos 0.8 sin 0.6
I 1 fl 100 10 3 2200 45.45 A
R cos X e1 sin 0.55 0.8 1.975 0.6
I 1 fl e1 45.45 0.0336 pu
V1 2200
N 80
The secondary no load voltage V2 n V1 2 2200 440 V
N1 400
The secondary terminal voltage V2 V2 n 1 4401 0.0336 425.2 V
R cos X e1 sin 0.55 0.8 1.975 0.6
(ii ) I 1 fl e1 45.45 0.0154 pu
V1 2200
The secondary terminal voltage V2 4401 0.0154 446.8 V
I 1 fl Z e1 45.45 2.05
(c) Maximum voltage regulation max 0.0424 pu.
V1 2200
Example 12
The primary and secondary windings of a 30-kVA, 6000-V / 230-V transformer have resistances
of 10 Ω and 0.016 Ω respectively. The total reactance of the transformer referred to the primary
is 23 Ω. Calculate the percentage regulation of the transformer when supplying full load current
at a power factor of 0.8 lagging.
20
Solution
Re1 R1 ( N1 N 2 ) 2 R2 10 0.016 (6000 230) 2 20.89
X e1 23
I1 fl 30 10 3 6000 5 A
R cos X e1 sin 20.89 0.8 23 0.6
I 1 fl e1 5 0.0254 pu
V1 6000
Percent regulation 2.54%
where
V2 = actual load voltage and
I2 = actual load current.
When S is given, V2 is unknown and the load current is required, it can be estimated using the
approximate equation
S V2 n I 2 10 3 kVA (25)
5.15 Efficiency
The losses which occur in a transformer on load are composed of
2 2
(a) Copper losses in primary and secondary windings, namely I12 R1 I 22 R2 I 1 Re1 I 2 Re 2
(b) Iron losses in the core due to hysteresis and eddy currents. The iron losses depend on the
peak value of the mutual flux Φm and frequency. It is therefore independent of load current if
voltage and frequency are constant.
Let
Pi = the iron losses (fixed loss) in kW and
Pc = the copper loss with full-load Srated kVA in kW
Then the total loss at any load S = xSrated kVA at power factor cos is Pi + x2 Pc and the
efficiency is
output xS rated cos S rated cos
input xS rated cos Pi x Pc
2
P
S rated cos i xPc
x
21
For a given power factor, the efficiency is maximum when the expression in brackets is a
minimum. Hence for a maximum efficiency, we have
Pi
x (26)
Pc
Proof:
d Pi Pi
xPc 0 , we obtain 2 Pc 0 or Pi x Pc
2
From
dx x x
According to equation (26), efficiency is maximum when the copper loss, x 2 Pc is equal to the
fixed loss or iron losses Pc, or efficiency is maximum when the load is such that the resulting
copper loss is equal to the fixed loss or iron losses.
Example 13
The primary and secondary windings of a 500-kVA transformer have resistances of 0.42 Ω and
0.0011 Ω respectively. The primary and secondary voltages are 6600 V and 400 V respectively
and the iron loss is 2.9 kW. Calculate the efficiency on full load at a power factor of 0.8.
Solution
500 1000
Full - load secondary current I 2 fl 1250 A
400
1000
Full - load primary current I 1 fl 500 75.8 A
6600
Secondary copper loss on full load 1250 2 0.0011 1720 W
Primary copper loss on full load 75.8 2 0.42 2415 W
Total copper loss on full load , Pc 1720 2415 4135 W 4.135 kW
Total loss on full load Pc Pi 4.135 2.9 7.035 kW
Output power on full load at 0.8 pf S rated cos 500 0.8 400 kW
Pi Pc 7.035
Efficiency on full load 1 1 0.9827 98.27 %
S rated cos Pi Pc 400 7.035
Example 14
Find the output, at which the efficiency of the transformer of example 11 is maximum and
calculate its value assuming the power factor of the load to be 0.8.
22
Solution
Let the load S be a fraction x of the rated power, i.e. S = xSrated. Then
Pi 2.9
x 0.837
Pc 4.135
Example 15
A 400-kVA transformer has an iron loss of 2 kW and the maximum efficiency at 0.8 pf occurs
when the load is 240 kW. Calculate (a) the maximum efficiency at unity power factor and (b) the
efficiency on full load at 0.71 power factor
Solution
(a) Total loss at maximum efficiency 2 Pi 2 2 4 kW
240
Output kVA at maximum efficiency 300 kVA
0 .8
Output power at maximum efficiency at unity pf 300 1 300 kW
4
Maximum efficiency at unity pf max 1 0.9868 98.68 %
4 300
300
(b) The fraction x of full load kVA at which efficiency is maximum 0.75
400
P 2
Hence full load copper loss Pc 2i 3.56 kW
x 0.75 2
Pi Pc 2 3.56
Full load efficiency at 0.71 pf 1 1 98.08 %
S rated cos Pi Pc 2 3.56 400 0.71
Distribution transformers used in distribution networks on the other hand supplies load which
varies widely over a 24-h period. They are always connected in circuit and operate less than full
load for most of the time. Hence they are designed with minimal core losses. Their maximum
efficiency occurs at 60 to 70 % of full load. The efficiency of these transformers is better
23
assessed on energy basis. The output and losses are calculated in kW hours over a 24-hour day.
The all-day efficiency is defined as
losses in kWh
η allday 1 (28)
losses in kWh output in kWh
Example 16
A 200-kVA 1-ph transformer has full load copper loss of 3.02 kW and iron loss of 1.6 kW. The
transformer is in circuit continuously. For a total of 8 hours, it delivers a load of 160 kW at 0.8
pf. For a total of 6 hours, it delivers a load of 80 kW at unity power factor. For the remainder of
the 24-h cycle, it is on no load. What is the all-day efficiency?
Solution
At 160 kW, 0.8 pf, kVA 200 kVA (full load), copper loss 3.02 kW
iron loss 1.60 kW
total loss 4.62 kW
2
80
At 80 kW, upf, kVA 80 kVA , copper loss 3.02 0.48 kW
200
iron loss 1.60 kW
total loss 2.08 kW
On no load (there is no copper loss on no load), Total loss 1.6 kW
This test is used to determine the leakage impedance. During this test, one winding is short-
circuited and a reduced voltage Vsc applied to the other to cause rated current to flow. The test
circuit and the equivalent circuit are shown in Fig. 18.a and Fig. 18.b respectively. The
magnetizing branch is neglected because its current under this condition is less than 1 % of the
total.
24
Voltage Vsc, current Isc and power Psc measured by the instruments are used to make the
following calculations:
V P
(a ) Z e1 sc (b) Re1 sc2 (c) X e1 Z e21 Re21 (29)
I sc I sc
During this test, one winding is open-circuited and rated voltage at rated frequency is applied to
the other. Quite often the low-voltage side is supplied to reduce the test voltage required for
safety reasons. As with the short-circuit test, the equivalent circuit parameters will be referred to
the side to which the test voltage is applied. The test circuit and equivalent circuit are shown in
Fig. 19.a and b.
Psc and Po represent the full load copper loss and the core loss (or iron losses) respectively. They
can be used directly to calculate efficiency.
.
25
Fig. 19 Open-circuit or no-load test
Example 17
The circuit shown below was used in a test on a 3-kVA transformer. A variable voltage supply of
fixed frequency was connected to terminals A and B and two tests were performed:
(a) The voltage was raised to normal rated voltage and the meter reading were then 200 V, 24
W, 1.2 A
(b) The terminals C and D were short-circuited and the voltage was raised until the transformer
full-load current was flowing. The meter readings were then 6.4 V, 28 W, 15 A
C
A A
B D
Circuit diagram for Example 13
Solution
(i) No - load current I o 1.2 A
input power 24
No - load power factor 0.1 lag
input apparent power 200 1.2
(ii) Iron losses Pi Po 24 W
26
(iii) Full load copper loss Pc Psc 28 W
(iv) Open - circuit test calculations :
P 24 2 2
Ip o 0.12 A I m I o I p 1.2 2 0.12 2 1.19 A
V1 200
V 200 V 200
Rm 1 1.67 kΩ Xm 1 168
I p 0.12 I m 1.19
Short - circuit test calculations :
V 6.4 P 28
Z e1 sc 0.43 Re1 sc2
2 0.12
I sc 15 I sc 15
X e1 Z e21 Re21 0.432 0.12 2 0.41
Pi x 2 Pc 24 28
(v) fl 1 1 0.9788 pu 97.88 %
xS rated cos Pi x Pc
2
(3000 0.8) 24 28
Pi x 2 Pc 24 28( 12 ) 2
(vi) 1 fl 1 1 97.48 %
2 xS rated cos Pi x 2 Pc 12 (3000 0.8) 24 28( 12 ) 2
Example 18
A 10-kVA 1-ph transformer has a voltage ratio 1100 / 250 V. On no load and at normal voltage
(1100 V) and frequency the input current is 0.75 A at a pf of 0.2 lagging. With the secondary
short-circuited, full-load currents flow when the primary applied voltage is 77 V, the power input
being 240 W. Calculate
(a) the transformer equivalent resistance and reactance referred to the secondary side
(b) the maximum value of the voltage regulation at full load and the load power factor at this
regulation
(c) the percentage of full-load current at which the transformer has maximum efficiency
Solution
(a) Referring the circuit to the secondary side,
V 250
Vsc 2 sc1 77 17.5 V
a 1100
S 10 000
I sc 2 I 2 fl rated 40 A
V2 n 250
V 17.5 P 240
Z e 2 sc 2 0.438 , Re 2 2sc 2 0.15 and X e 2 0.4382 0.152 0.41
I sc 2 40 I sc 2 40
(b) The maximum voltage drop at full load = I 2 fl Z e 2 17.5 V
The maximum regulation occurs when or when
R 0.15
cos cos e 2 0.342 lag
Z e 2 0.438
27
(c) Maximum efficiency occurs when x 2 Pc Po . Therefore
Po Vo I o cos o 1100 0.75 0.2
x 0.829 or 82.9 %
Pc Pc 240
The transformer windings are carefully insulated from each other and from the core. Winding
resistances R1 and R2 are also minimized to minimize copper losses.
(a) Core - type constructi on with (b) Shell - type constructi on with
concentric windings sandwiched windings
28
(a) additive polarity (b) subtractive polarity
Fig. 21 Two standard ways of mounting transformer terminals
The following conditions must be fulfilled when operating two or more single-phase
transformers in parallel:
(a) The polarity should be the same. The polarity can be either right or wrong. A wrong polarity
results in a severe short circuit. Terminals of the same markings are connected together to
ensure correct polarity. See Fig. 24. If the polarity markings are either incorrect or not
present, the polarity of the incoming transformer can be checked by connecting a voltmeter
across the paralleling switch
(b) The voltage ratio should be the same. This is to avoid no-load circulating current and also
over-loading on one transformer when the paralleled transformers are loaded.
(c) The per-unit impedances should be equal in magnitude and have the same angle. When they
are equal in magnitude, the transformers share kVA loads in proportion to their respective
ratings. If both their magnitudes and angles are the same they will not only share kVA loads
in proportion to their respective ratings but also the combined load kVA will be the algebraic
sum of the kVA carried by each transformer. If the angles are different, the resultant kVA
capacity of the paralleled group will be slightly smaller than the sum of their individual
ratings if none should be overloaded. It is not very necessary that the angles should be the
same
30
5.21 Load sharing of parallel-connected transformers
The equivalent circuit of two transformers in parallel feeding a common load ZL is shown in Fig.
25. The voltage ratios are supposed to be equal and the magnetizing branch is neglected. The
circuit is referred to the secondary side but it may also be referred to the primary side.
I1 Z1
I
I2
Z2
V1
V ZL
a
Z1 is the impedance of transformer 1 referred to the secondary side and Z2 is the impedance of
transformer 2 referred to the secondary side.
where
S1 VI1 apparent power or load carried by transformer 1 (32.a)
S 2 VI 2 apparent power or load carried by transformer 2 (32.b)
S VI combined apparent power or load (32.c)
The apparent powers S1, S2 and S are in complex notation. With the load voltage V as reference
and the load current I lagging behind the voltage V by , the combined load can be expressed as
S VI VI cos 1 (load pf ) and a transformer 1 load power factor say, obtained as cos 1
where 1 is the phase angle of S1. V V magnitude of the load voltage and I I
magnitude of the load current.
31
Equations (31.a) and (31.b) hold for per-unit impedances provided that all are expressed with
reference to a common base power. The following equation can be used to obtain a new per unit
value with reference to a new base power.
S base,new
Ẑ new Ẑ old (33)
S base,old
Example 19
A 500-kVA transformer (Transformer 1) is connected in parallel with a 250-kVA transformer
(Transformer 2). The secondary voltage of each is 400 V on no load. Find how they share a load
of 750 kVA at power factor of 0.8 lagging if
(a ) Z 1 0.01 j 0.05 pu 0.0509978.69 pu and
Z 2 0.015 j 0.04 pu 0.0427269.44 pu
(b) Z 1 0.01 j 0.05 pu 0.0509978.69 pu and
Z 2 0.01 j 0.05 pu 0.0509978.69 pu
(c) Z 1 0.01 j 0.05 pu 0.0509978.69 pu and
Z 2 0.025 j 0.0444 pu 0.0509560.62 pu
Solution
If all the impedances are referred to a base power of 500 kVA, then only the impedances of
transformer 2 will change.
S base,new 500
Ẑ new Ẑ old Ẑ old 2 Ẑ old
S base,old 250
Case (a)
Z 1 0.01 j 0.05 0.05099 pu78.69 and
Z 2 20.015 j 0.04 0.03 j 0.08 0.08544 pu69.44
Further
Z 1 Z 2 0.01 j 0.05 0.03 j 0.08 0.04 j 0.13 0.1360 pu72.90
Total kVA load S 750 cos 1 0.8 750 kVA 36.9
Z2 0.0854469.44
S1 S 750 36.9 471 kVA 40.36
Z1 Z 2 0.13672.9
471 kVA at power factor of cos 40.36 0.762 lagging
Similarly
0.0509978.69
S 2 750 36.9 281 kVA 31.11
0.13672.9
281 kVA at power factor of 0.856 lagging
Remark:
32
Transformer 1 with larger per-unit impedance is under-loaded whereas transformer 2 with lower
per-unit impedance is overloaded.
Case (b)
Z 2 20.01 j 0.05 0.02 j 0.1 0.10198 pu78.69
Z 1 Z 2 0.03 j 0.15 0.15297 pu78.69
0.1019878.69
S 1 750 36.9 500 kVA 36.9
0.1529778.69
500 kVA at power factor of 0.8 lagging
0.0509978.69
S 2 750 36.9 250 kVA 36.9
0.1529778.69
250 kVA at power factor of 0.8 laggging
Remark:
Load shared in proportion to transformer ratings. Arithmetic sum of loadings is equal to the
combined load. A shorter approach can be used on recognizing that Z 1 pu Z 2 pu
Case (c)
Z 2 20.025 j 0.0444 0.05 j 0.0888 0.1019 pu60.62
Z 1 Z 2 0.06 j 0.1388 0.1512 pu66.62
0.101960.62
S 1 750 36.9 505 kVA 42.9
0.151266.62
505 kVA at power factor of 0.732 lagging
0.0509978.69
S 2 750 36.9 253 kVA 24.82
0.151266.62
253 kVA at power factor of 0.91 lagging
Remark:
Transformers are slightly overloaded when the combined load is equal to the sum of individual
kVAs
6 Three-phase transformers
These are required to transform 3-phase power. The three-phase transformer may be either of the
following:
33
6.2 A three-phase transformer unit
This is a single unit of special construction for three-phase working. Modern large transformers
are usually of the three-phase three-legged core type shown in Fig.27. A leg carries the primary
and secondary windings of a phase. The windings are internally connected. For a given total
capacity, 3-phase units are much cheaper in capital cost, lighter, smaller and more efficient.
For this connection, phase voltage = line voltage/√3 which is about 58 % of the line voltage. This
enables the insulation of the winding to be reduced to a minimum for a given supply voltage. For
star connection line current = phase current. It is the most economical connection for a high-
voltage winding.
For this connection, phase voltage = line voltage. Therefore winding must be insulated for the
full Line voltage. More turns are also required. With very high voltages a saving of 10 % may
be achieved by using star-connection rather than delta connection on account of insulation. The
saving is small, however, at voltages below 11 kV. For delta connection, phase current = line
current/√3 so the winding cross-sectional area is 58 % of that required for the star connection. It
it is the most economical for low-voltage winding.
It is a modification of the star connection. Each phase winding is divided into two sections and
placed on two different legs. The two sections are then connected in phase opposition. 15 %
more turns are required for a given phase terminal voltage compared with a normal star.
The three different winding arrangements give rise to several possible connection combinations:
star-star, star-delta, star-zigzag, delta-star, delta-delta, etc
35
Fig. 28 Vector symbols, diagrams and groups, winding connections,
and phase displacement of 3-phase transformers
36
exist and it has to be found geometrically. Two-winding three-phase transformers are classified
into four vector groups depending on the phase displacement as shown in the table below:
Fig. 28 above shows in addition vector diagrams and winding connections. Before connecting
two or more transformers in parallel, their vector groups will have to be determined.
This connection is economical for large low voltage transformer. Because there is no neutral
point, a four-wire supply cannot be given. It is used in a 3-phase transformer bank but rarely in
3-phase transformer unit. It is possible to use this arrangement to provide 3-phase power with
one transformer removed. This connection, known as open-delta or vee connection, can supply
up to 57.7 % of the load capacity of the delta-delta connection.
IL
L1
L3
A1 I ph A2 a1 a2
L3 L1
C2 B1 c2 b1
VL V ph
C1 B2 c1 b2
L2 L2
VL V ph
I L 3I ph
Fig. 29.a Delta-delta connection
It is commonly used to step up alternator voltage to transmission line voltage. Another common
application is in distribution service where as a step-down transformer, the windings are not the
most economical. The secondary star point can be earthed and a four-wire supply given.
37
6.5.3 Star-Delta connection
There is no secondary neutral and four-wire supplies cannot be given. The main use is as a step-
down transformer at the load end of transmission line.
This is economical for high-voltage transformer. However, if the secondary load is unbalanced,
the neutral point will be displaced and the line-to-neutral voltages will become unequal, a
situation referred to as floating neutral. If the neutral of the primary and the neutral of the source
are connected together usually by way of ground, the floating neutral problem can be eliminated.
Again if there is no primary ground, the primary and secondary phase voltages will contain
pronounced third harmonic voltages, which will cause the neutral point to oscillate above and
below the earth at a voltage equal in magnitude to the third harmonic voltage. To eliminate the
oscillation problem, a third delta-connected winding called tertiary winding is provided.
Although it can be used to supply additional power, the tertiary winding generally has no
external connection.
The star-zigzag arrangement reduces third harmonic voltages and its neutral point is not affected
by unbalanced loading. The zigzag is restricted to comparatively low-voltage windings.
Example 20
Three single-phase step-up transformers rated 40 MVA, 13.2 kV/80 kV are connected in delta-
star on a 13.2 kV transmission line. If they feed a 90 MVA load, calculate the following:
(a) the secondary line voltage
(b) the currents in the transformer windings
(c) the incoming and outgoing transmission line currents.
Assume transformers are ideal.
38
Solution
(a) Let the voltage applied to the primary of a transformer be Vph1 and the secondary terminal
V ph 2 N 2 80
voltage be Vph2. Then considering the transformer to be ideal
V ph1 N 1 13.2
Since the primary connection is delta, the voltage applied to the primary of each single-phase
transformer is equal to the transmission line voltage. Therefore
N 80
V ph 2 2 V ph1 13.2 80 kV .
N1 13.2
Since the secondary side is connected in star, the line voltage on the secondary side
80 3 138 kV
V ph 2
V ph 1
13.2 kV
I ph 1
I ph 2
90
(b) The load carried by each transformer 30 MVA
3
30 MVA
From S V ph1 I ph1 , current in the primary winding I ph1 2272 A
13.2 kV
30 MVA
From S V ph 2 I ph 2 , current in the secondary winding I ph2 375 A
80 kV
(c) Current in incoming line 3I ph1 2272 3 3932 A
Current in outgoing line I ph 2 I L 375 A
Alternatively, we can first calculate the line currents and use them to calculate the phase currents
or currents in the windings. To calculate a line current we use the formula, S 3V L I L .
Example 21
Three single-phase transformers have their primaries joined in delta to a 6600 V, three-phase,
three-wire supply. Their secondaries are connected to give a three-phase, four-wire output at 415
V across lines. The total load on the transformers is a balanced load of 150 kW at 0.8 pf lag. If
the voltage per turn on the primaries is 4, find
(a) the number of turns on the primary winding and the secondary winding
(b) the currents and voltages in all windings and lines, including the neutral wire on the
secondary side
39
(c) kVA load on each transformer
Solution
V ph1 V ph 2
(a) Voltage per turn 4
N1 N2
For delta connection V ph1 V L1 6600 V
V ph16600
Therefore N 1 1650 turns
4 4
V 415
For star connection V ph 2 L 2
3 3
V ph 2 415
Therefore N 2 60 turns
4 4 3
I L2
I L1
I ph1
415V 150 kW
V ph 2 Load 0.8 pf lagging
6.6 kV V ph1
Power 150 10 3
(b) Secondary I L 2 I ph 2 261 A
3VL cos 3 415 0.8
IN 0 A because load is balanced
N 2 I ph 2 60 261
Primary phase current I ph1 9.5 A
N1 1650
Primary line current I L1 9.5 3 16.4 A .
Example 22
A three-phase 415 V load takes a line current of 800 A from a 3300 / 415 V delta/star
transformer. The 3300 V system is supplied from an 11000/3300 star/star transformer. Draw the
circuit diagram and assuming no losses, find both line and phase values of voltages and currents
in each part of the circuit. What will be the turns ratios of both transformers?
40
Solution
Transforme r B Transformer A
I1 I 2 I3 I 4 800 A
V ph1 I ph 1 V ph 2 I ph 4
I ph2 I ph 3 V ph 4 V 4
V1 11000 V2 V3 V ph 3 415 V
Voltages:
V4 415
V4 415 V; V ph 4 240 V
3 3
V3 3300 V; V ph 3 V3 3300 V
V2 3300
V2 V3 3300 V; V ph 2
1905 V
3 3
V 11000
V1 11000 V ; V ph1 1 6350 V
3 3
Turn ratios:
V ph3 3300
Transformer A 13.75
V ph 4 240
V ph1 6350
Transformer B 3.33
V ph 2 1905
Currents:
I 4 800 A; I ph 4 I 4 800 A
I ph 4 800
I ph 3 58.2 A
turns ratio A 13.75
I 2 I 3 3 I ph 3 3 58.2 100.8 A
I ph 2 I 2 100.8 A
I ph 2 100.8
I ph1 30.2 A
turns ratio B 3.33
I 1 I ph1 30.2 A
Check:
Input kVA 3 V1 I 1 3 11000 30.2 575000 VA 575 kVA
Output kVA 3 V4 I 4 3 415 800 575000 VA 575 kVA
41
6.6 Parallel operation of three-phase transformers (Fig. 30)
Three-phase transformers operating in parallel should have
(a) the same line voltage ratios
(b) the same per-unit impedances, i.e., they are equal in magnitude and in phase
(c) the same phase displacement between primary and secondary line voltages
(d) the same phase sequence
The last two conditions which are absolutely essential ensure that the secondary line voltages of
the transformers are in phase. When these conditions are not fulfilled a potential difference
appears across the paralleling switches S1 and S2.
From the view point of phase sequence and phase displacement, three-phase transformers which
can operate in parallel are:
(a) transformers of the same vector group. In this case the terminals with the same letter must be
connected to the same line as shown in Fig. 30.
(b) transformers having -30o phase displacement (vector group 3 transformers) and those having
+30o phase displacement (vector group 4 transformers). In this case two of the high voltage
connections and the corresponding low voltage connections are interchanged as shown in
Fig. 31.
Faulty internal connections in the transformer tank can cause the phase sequence of a transformer
to be reversed. Voltage across paralleling switches should therefore be monitored before the
switches are closed.
C B A a b c
Transformer 1
A2 a2
B2 b2
C2 c2
Transformer 2
A2 a2
S1
B2 b2
S2
C2 c2
42
a b c
C B A
Transformer 1
A2 a2
B2 b2
C2 c2
Transformer 2
A2 a2
S1
B2 b2
S2
C2 c2
7 Cooling methods
Cooling of transformer windings and core is provided to prevent rapid deterioration of the
insulating materials. There are several methods of transformer cooling. Each method is described
by a standard designation (or nomenclature) consisting of letter symbols. They are
(a) Letters for medium: air A, gas G, synthetic oil L, mineral oil O, solid insulation S, water W
(b) Letters for circulation: natural N, forced F
Up to four letter symbols are used for each method for which the transformer is assigned a
rating: some big transformers are designed to have a variable rating, depending on the method of
cooling used. The order of the symbols is
(i) the medium and
(ii) the circulation of the coolant in contact with the windings; and
(iii)the medium and
(iv)the circulation of the coolant in an external heat exchanger system.
43
Common methods of cooling transformers are:
They use the ambient air as coolant and natural circulation by convection. The metallic housing
is fitted with ventilating louvers. They have ratings up to 50 kVA for low-power transformers.
Using high-temperature insulating materials, glass and silicone resins, make ratings up to 1.5
MVA possible. The low-power transformers are used inside buildings where the air is clean and
high-power ones are for special conditions such as those in mines.
7.1.2 AF
7.2.1 ONAN
Natural oil circulation and natural air flow over the tank are used. It is very common for
transformers rated up to 5 MVA. With radiators, it is possible to build units up to 40 MVA. We
note that limit of output is determined by tank size and cost.
7.2.2 ONAF
Cooling fans blow air over the radiators to enable a much bigger output from a transformer of a
given size. With this method of cooling ratings up to about 75 MVA can be built.
7.2.3 OFAF
Pumps are used to circulate the oil and cooling fans to blow air over radiators. This is the usual
method for transformers of 30 MVA and upward. Both OFAF and ONAN may be used on a unit
with ONAN up to 0.5 per unit rating. Change over is initiated automatically by temperature-
sensing elements. Three-phase type OFAF step-up transformer rated 1300 MVA installed at a
nuclear power generating station is one of the largest units ever built.
44
7.3 Oil-immersed, Water cooling
7.3.1 ONWF
Copper cooling coils are mounted in the tank above the level of the transformer core, but below
the oil surface.
7.3.2 OFWF
Oil is circulated by pump from the top of the transformer tank to an external oil/water heat
exchanger. Oil returns when cold to the bottom of the tank. Its advantages over ONWF include
(a) The transformer is smaller and the tank does not have to contain the cooling coils.
(b) Leakage of water into oil is improbable if oil pressure is greater than that of water
This method is used for large installations. It is commonly used in generating stations,
particularly hydro stations where ample supply of water is available.
8 Tap-changing Transformers
Most power transformers have tappings on coils brought out to terminals so that the number of
turns on one winding can be changed. The turns-ratios are changed in order
(a) to maintain the secondary voltage at their rated value under the varying conditions of load
and power factor. The secondary terminal voltage may vary with changes in load over an
undesirably large range, because of changes in the impedance drop in the transmission lines
and transformers
(b) to control the flow of reactive power between two interconnected power systems or between
component parts of the same system, at the same time permitting the voltages at specified
points to be maintained at desired values.
Tappings on power transformers permit voltage adjustment within 5% . Low- and medium-
power transformers usually have three taps per phase: +5%, 0, and -5% variations in the turns
ratio. Higher power ratings usually have five: +5%, +2.5%, 0, -2.5% and -5% variations in the
turns-ratio. The principal tapping “0” is that to which the rating of the winding is related. A
positive tapping includes more, and a negative less turns than those of the principal tapping.
Tappings are usually fitted on the higher voltage winding to obtain tappings within fine limits.
Consider say, 11kV / 433 V, 600 kVA delta-star distribution transformer having volts / turn = 10.
On the low-voltage side, N 433 10 3 25 . Adjustment can then be in steps of 4%. If 5 %
and 10 % are required, we shall use 4 % and 8 % or 12 %.
On the high-voltage side N 11000 10 1100 and it is possible to make adjustment in steps of
0.09 %.
45
8.1.1 Off-load tap changing
The changes are made when the transformer is disconnected from the primary circuit. The most
common off-load tap changing transformer has tappings inside the tank and connected to an
internal switch which is operated by an external switch handle (usually by rotary movement of a
hand wheel). Fig. 32 shows a three-phase star connected winding with taps made at the neutral.
Off-load tap changing is simple and inexpensive and it is commonly used with distribution
transformers where occasional adjustments are required.
Fig. 32 Three-phase star connected winding with taps at the neutral point
Daily and short-time adjustment is generally by means of on-load tap-changing gear. Tap
changing is done without breaking the circuit. Momentary connection must be made
simultaneously to two adjacent taps during the transition, and the short-circuit current between
them must be limited by some form of impedance known as transition impedance. Centre-tapped
iron-core inductors (the reactor method) or resistors (the resistor method) are used for this
purpose.
Reactor method
This method has now almost entirely been superseded by the resistor method. It is manufactured
and used only in the USA.
Resistor method
In modern designs the transition impedance is almost invariably obtained by means of a pair of
resistors. An arrangement of such a tap changer for one phase is shown in Fig. 33. In this figure,
46
the diverter switch and the even tap selector are shown in the position when the tap T2 is brought
in circuit.
To move to the next tap, T3, the odd tap selector should first be moved to that tap (see the dashed
lines in Fig. 33.a), and the diverter switch may then be rotated clockwise. The ensuing sequence
of events is as follows:
T8
T7
T6
T5
T4 even tap selector
odd tap selector T3
T2
TS 2
T1
TS1
R1 R2
I
2 3
1
4
I
R1 R2
2 3 1
1
I-i
1
i Ii
2 2
4
I
Fig 33.b
47
- contacts 1 and 4 break, and contacts 1 and 2 make, Fig. 33.c
Fig 33.c
The tap selectors may be moved from tap to tap only when their circuits are de-energized. The
resistors are short-time rated so their time of duty must be kept low. For the same reason, means
must be adopted to ensure that it cannot be inadvertently left in the bridging position.
On-load tap changer control gear can vary from simple push-button initiation to a complex
automatic control of as many as four transformers in parallel.
9 Autotransformers
An autotransformer has a single tapped winding which serves both primary and secondary
functions as shown in Fig. 34. The circuit diagrams are shown in Fig. 35.
I1 A
I2 C
C I1 A
I2
N1
V1 N2
N2 V1 N1 V2 Load
B
V2 Load
B
B B
Fig. 34.a Step - down autotransf ormer Fig. 34.b Step - up autotransformer
48
9.1 Autotransformer equations
If we neglect losses, leakage flux and magnetizing current then the turns ratio
N V I
a 1 1 2
N 2 V2 I 1
Or
saving of copper effected by VL
Volume of copper in the two winding transformer
using an autotransformer VH
where
VL voltage on the low voltage side
VH voltage on high voltage side
In practice, voltage ratios VL V H less than about 1 3 show little economic benefit over two-
winding transformer because of other factors such as cost of insulation.
The main disadvantage is that the primary and secondary circuits are not isolated from each
other.
49
Example 23
An autotransformer is required to step up a voltage from 220 to 250 V. The total number of turns
is 2000. Determine (a) the position of the tapping point (b) the approximate value of the current
in each part of the winding when the output is 10 kVA and (c) the economy in copper over the
two winding transformer having the same peak flux and the same mean length per turn.
Solution
I2
I1
N2 V2
V1 N1
10 10 3
(b) V2 I 2 10 10 3 I 2 40 A
250
10 10 3
V1 I 1 10 10 3 I 1 45.45 A
220
50
(f) the voltages add when terminals of opposite polarity (A1 and a2 or A2 and a1) are connected
together by a jumper. The voltages subtract when terminals of the same polarity (A1 and a1 or
A2 and a2) are connected together.
Example 24
A two-winding single-phase transformer rated 15 kVA, 600 V / 120 V, 60 Hz. We wish to
reconnect it as an autotransformer in three different ways to obtain three different voltage ratios:
Calculate the maximum load the transformer can carry in each case.
Solution
Let the voltage on the high voltage side of the two-winding transformer be VH and voltage on the
low voltage side be VL. Then one of the rated voltages of the autotransformer is always given by
VR = VH or VR = VL. The other must be derived from the two windings in series as VD = VH +VL
by connecting terminals of opposite polarity (A1 and a2 or A2 and a1) together by a jumper or as
VD = VH – VL by connecting terminals of the same polarity (A1 and a1 or A2 and a2) together by a
jumper.
(a) Here VR = 600 V and VD = VH – VL = 600 – 120 = 480 V. Therefore any two terminals of the
same polarity can be connected in series to derive the 480 V. The 480 V, being the secondary
voltage of the autotransformer, goes to load.
To obtain the maximum load the autotransformer can carry, we note that the current in the
120-V winding, connected in series with the load in the autotransformer connection, is not
supposed to exceed its current rating given by I 2 fl S rated 120 15 10 3 120 125 A . This
then limit the load current to 125 A. And at a load voltage of 480 V, the maximum power
becomes 125 480 60 kVA .
51
(b) The secondary voltage 120 V must be added to the 600 V to obtain 720 V
(c) The 120 V becomes the primary of the autotransformer and the 120 V is subtracted from the
600 V to obtain its secondary
10 Instrument transformers
52
The load on the secondary of an instrument transformer is called its burden and is expressed in
volt-amperes (VA). There are two types of instrument transformers: the voltage (or potential)
transformer and the current transformer
Fig. 36 shows the circuit for a potential transformer. One terminal of the secondary winding is
always earthed. The windings though insulated from each other, are connected invisibly together
by distributed capacitance between them. By earthing one of the secondary terminals, the
highest voltage between the secondary lines and earth can never rise above that of the secondary
voltage.
H.V. ac circuit
PT
110 V
V
0 150 V
Fig. 36 Potential transformer installed on H.V. circuit
53
secondary current approximately constant. The nominal or rated secondary currents are usually
5 A or 1 A, irrespective of the primary current rating. The transformer ratio is usually stated to
include the secondary current rating. Current transformers also introduce two errors in
measurement: the ratio error (the ratio between primary and secondary currents is not constant)
and phase angle error (the phase angle between the primary and secondary currents is not zero).
The basic cause of ratio and phase angle errors is the exciting current. To keep the exciting
current small, a high quality iron operating at very low flux densities is used as in PTs. In CTs
the secondary leakage impedance and impedances of the secondary leads and instruments should
also be very low; for any increase in these impedances increases the core flux and therefore the
exciting current. The transformer is connected in the power circuit as shown in Fig. 37. As in the
case of PT (and for the same reasons) one of the secondary terminals is always earthed
Current transformer secondary circuit must not be opened while current is flowing in the
primary. Without opposing ampere-turns the line current, which may be 100 to 200 times the
normal exciting current, becomes the exciting current. The iron core becomes saturated and very
high voltage spikes (several thousand volts) are induced across the open-circuited secondary.
These voltages are dangerous to life and to the transformer insulation. The core when it becomes
saturated can also cause excessive heating of the core and windings. Therefore when it is desired
to remove a load from the secondary circuit, the secondary winding must first be short circuited.
When the line current exceeds 100 A we can sometimes use a toroidal or bar-primary (N1=1)
transformer shown in Fig. 38. It consists of a laminated ring-shaped core which carries the
secondary winding. The primary is composed of a single conductor that simply passes through
the centre of the ring as shown in the figure. Toroidal CTs are simple and inexpensive and are
widely used in HV and MV indoor installations.
Load current
ac supply Load
CT
1 A or 5 A
A
1 A or 5 A
ammeter
54
I 1 600 A
Bar primary
N1 1
I2 3 A
A
Current transformers are also commonly used for the measurements of large currents even when
the circuit voltage is not dangerously high. This avoids bringing heavy leads to the instrument
panels. Whereas instrument CTs have to remain accurate up to 120 % rated current, protection
CTs must retain proportionality up to 20 times normal full load
Example 25
A potential transformer rated 14400 V / 115 V and a current transformer rated 75 A / 5 A are
used to measure the voltage and current in a transmission line. If the voltmeter indicates 111 V
and the ammeter reads 3 A, calculate the voltage and current in the line.
Solution
V1 14400
Treating the PT as an ideal transformer, we have .
V2 115
14400 14400
Therefore the transmission line voltage V1 V2 111 13900 V
115 115
I 75
Treating the CT also as ideal transformer, we have 1
I2 5
75 75
Therefore the transmission line current I 1 I2 3 45 A
5 5
Example 26
The toroidal current transformer of Fig. 38 has a ratio of 1000 A / 5 A. The line conductor carries
a current of 600 A.
(1) Find the voltage across the secondary winding if the ammeter has an impedance of 0.15 Ω
(2) Find the voltage drop the transformer produces on the line conductor
(3) If the primary conductor is looped four times through the toroidal opening, find the new
current ratio
55
Solution
5
(a) Current in the secondary I 2 600 3 A
1000
Voltage drop across the burden 3 0.15 0.45 V
(b) Voltage drop on line conductor = primary voltage V1
I 3
V1 I 1 V2 I 2 . Therefore V1 2 V2 0.45 2.25 mV
I1 600
(c) For a bar primary transformer I 1rated x1 I 2 rated N 2 .
If the primary conductor is looped 4 times, the number of turns on the primary side becomes
4 and we should have I 1rated , new x 4 I 2 rated N 2 .
I 1rated 1000
From the two equations, we obtain I 1rated , new 250 A
4 4
Therefore the new current ratio =250 A/5 A
56
11 Further exercises
(1) A single-phase transformer has a primary winding with 1,500 turns a nd a secondary winding
with 80 turns. If the primary winding is connected to a 2300-V, 50-Hz supply, calculate (a)
the secondary voltage (b) the maximum value of the core flux. Neglect the primary
impedance
(2) A single-phase 2,300/230-V, 500-kVA, 50-Hz transformer is tested with the secondary open-
circuited. The following test results were obtained: V1 = 2,300 V, Io = 10.5 A, and Po = 2,300
W. Calculate (a) the power factor (b) the core-loss current Ip (c) the magnetizing current Im.
(3) A 150-kVA, 2,400/240-V, 50-Hz single-phase transformer has the following resistances and
reactances: R1 =0.225 Ω, Xl1 = 0.525 Ω, R2 = 0.00220 Ω and Xl2 = 0.0445 Ω. Calculate the
transformer equivalent values (a) referred to the primary (b) referred to the secondary.
(4) A 150-kVA, 2,400/240-V, 50-Hz single-phase transformer has the following resistances and
reactances: R1 =0.225 Ω Xl1 = 0.525 Ω, R2 = 0.00220 Ω, Xl2 = 0.00445 Ω, Rm = 10 k Ω and
Xm = 1.5 k Ω. The transformer is supplying full-rated load at 0.85 lagging power factor and
rated secondary terminal voltage. Calculate (a) I2 (b) Ip (c) Im (d) Io (e) I1 (f) V1. Use the
exact equivalent circuit referred to the primary side.
(5) The results of open- and short-circuit tests carried out on a 230/115-V, 60-Hz single –phase
transformer are
(6) The results of open- and short-circuit tests on a 100 kVA, 11,000/2,200-V, and 50-Hz single–
phase transformer are
Determine (a) Re1 and Xe1 (b) Re2 and Xe2 (c) the percentage regulation at 0.75 power factor
leading, unity power factor and 0.85 power factor lagging
(7) From the data of Exercise 6 calculate the transformer efficiency at 0.8 power factor lagging
for (a) 50 % (b) 100 % of rated full load.
57
(8) A 100-kVA, 11,000/220-V, 50-Hz transformer has a core loss Po of 800 W and Re2 of 0.48
Ω. Calculate the secondary current for maximum efficiency.
(9) A 10-kVa, 2,400/240-V, 60-Hz single-phase distribution transformer has a full-load copper
loss of 125 W and a core loss of 63 W. It supplies the following loads over a 24-h period:
Calculate (a) the total energy loss over the 24-h period (b) the total energy output over the
24-h period (c) the all-day efficiency.
(11) A 75-kVA 230-V three-phase load is supplied from a 6,600-V three-phase supply using a
star-star-connected transformer bank. What are the voltage, current and kVA ratings of the
single-phase transformers?
(12) Three single-phase transformers are connected in delta-delta, and are used to step down a
line voltage of 110 kV to 66 kV to supply an industrial plant drawing 50 MW at a 0.80
power factor. Calculate 9a) the high-voltage-side line current (b) the low-voltage-side line
current (c) the primary phase currents (d) the secondary phase currents
58
CHAPTER TWO
1 Introduction
(a) Signal handling devices: They are used to generate output signals which have linear
relationship with input signals. They generally operate with small signals. Examples are
pickups, loudspeakers, microphones and tachometers.
(b) Force-producing devices: They are used to produce bulk and non-controlled forces or
torques. Examples are lifting magnets, iron-core, solenoid-actuators, relays, contactors and
iron-vane instrument.
(c) Continuous energy-conversion devices: These devices deal with large amounts of energy.
Examples are motors and generators.
A transducer is a device which takes energy from one system and supplies it to another. This
term, however, is usually used for the devices for obtaining signals for measurement and control
which operate at very low power levels. Transducers are signal handling devices.
A method which is simple and is applicable to all the conversion devices will be used to develop
expressions for the forces and torques. The method is based on the law of conservation of
energy.
3 Energy balance
Suppose that the energy conversion device is connected at its input to an electrical source and at
its output to a mechanical system. Then calculating from an initial zero-energy condition, the
energy balance is
59
(electrical energy input, welec ) = (stored field energy, w fld ) + (mechanical energy output, wmech ) +
(energy lost, wloss ) (1)
This relation equally applies to energy changes (i.e. changes after an established condition or
state) and to energy rates, i.e. power:
dwelec dw fld dwmech dwloss (Energy balance) (2)
dw fld dwloss
Pe Pm (Power balance) (3)
dt dt
The copper, friction and windage losses do not play basic part in the energy conversion process.
They can therefore be considered as losses in the electrical and mechanical systems on the two
sides of the conversion device. With the losses considered this way, welec in equations (1) and
(2) becomes the electrical energy supplied to the coupling field, wmech becomes the gross
mechanical output from the coupling field and wloss becomes iron or dielectric loss only. The
schematic diagram of such a device is shown in Fig. 1
These devices are built with only one electric circuit. A model of such a system is shown in Fig.
2. The conversion device consists of two parallel plates separated by air. One of the plates is
60
fixed and the other is movable. The movable part is designed to have one degree of freedom. In
the equilibrium
f mech f fld (4)
where
fmech = the gross mechanical force exerted by the mechanical system and
ffld = the force produced by the field called the field force.
We are interested in the expression for the field force. To derive it, we shall apply the principle
of virtual work: we assume that a small displacement takes place, calculate the work that would
be done in such a virtual displacement, and then use the work done to determine the actual force.
Suppose an incremental displacement dx of the movable plate is made in a time dt . During this
displacement
f fld dx dwmech
f fld dx dwelec dw fld dwloss (5)
The energy supplied to the coupling field during the small displacement is
1
dw fld d qe
2
1 1
dw fld qde edq (8)
2 2
61
Substituting equations (6), (7) and (8) into equation (5) gives
1 1 1 1
f fld dx edq qde edq edq qde
2 2 2 2
From which
1 dq 1 de
f fld e q (9)
2 dx 2 dx
Now
q
c (10.a)
e
Therefore
dc 1 dq de
2 e -q (10.b)
dx e dx dx
The expression for the field force derived is general and is applicable to electromechanical
devices of similar method of excitation. To apply the force expression, it will be necessary to
evaluate capacitances of the systems as functions of position.
Example 1
Two parallel plates as shown in Fig. 2 are maintained at a potential difference e of 104 V. Each
plate has an area of 0.02 m2
(a) Find the force between the plates as a function of their spacing x
(b) Find the energy converted to mechanical form as the plate spacing is reduced from 1 cm to
0.5 cm
Solution
o r A
(a) For the two parallel plate the capacitance as a function of the spacing x is C( x)
x
1 2 dc Ae 2
Therefore f fld ( x) e o r 2
2 dx 2x
The negative sign implies that the direction of the force is the reverse of that shown, i.e.
f fld will rather act to reduce the plate spacing.
1 2 dc 1
(b) For a small change dx , the work done dwmech f fld ( x)dx e dx e 2 dc
2 dx 2
1 C2 1 1 1 1
Therefore Wmech e 2 dc e 2 (C 2 C1 ) e 2 o r A
2 C1 2 2 x 2 x1
62
With e 10 4 V, o 8.85 10 12 , r 1, A 0.02 m 2 , x 2 0.005 m and x1 0.01 m
Wmech 8.85 10 4 Joules
These devices are also built with only one electric circuit. They have no permanent magnet yet
they are capable of producing motor and generator action. They are used for instruments,
microphones and relays. Fig. 3 shows a model of the system. The magnetic circuit of the device
has air gap of length x between fixed and movable members.
Movable
Fixed member member
x
ffld
i
+ fmech
+ e
V(t)
- -
Mechanical
system
Electrical
system
The induced voltage e arises only from the rate of change of flux linking the coil. From
Faraday’s law
d
e (14)
dt
The reluctance of the iron part in the magnetic circuit is assumed to be linear. In this case the
induced voltage can be expressed as
d di dL
e ( Li ) L i (15)
dt dt dt
63
Substituting equation (15) into equation (13) yields
dwelec Li di i 2 dL (16)
Substituting equations (16), (17) and (18) into equation (12) gives
1 1
dwmech Li di i 2 dL i 2 dL Li di i 2 dL
2 2
The above expression for the work done can be used in equation (12) to obtain
1 dL
f fld i 2 (19)
2 dx
To apply this force expression, the inductance of the system must be evaluated as function of
position.
64
Example 2
A steel electromagnet is used to support a solid block of steel having a mass of 908 kg as shown
in Fig. 4. A force of 8900 N is required to support this weight. The cross-sectional area of the
magnet (part 1) is 0.01 m2. The coil has 700 turns. Assume both air gaps are 0.0015 m long.
Neglect the reluctance of the steel parts. Neglect fringing in the air gaps. Find the minimum
current that can keep the weight from falling.
i
Part 1
(fixed)
x x
Part 2
(movable)
Fig. 4 See Example 2
Solution
2x
The total reluctance, R( x) , where A is the cross sectional area of the air gaps.
0 A
N 2 o A
Therefore the inductance of the coil L( x)
2x
1 2 dL 1 2 N o A
2
N 2 o AI 2
The force f fld ( x) I I
2 dx 2 2 x 2 4x 2
The cross sectional area of the air gaps is equal to the cross sectional area of magnet (part 1) if
fringing is neglected.
7 2 10 4 4 10 7 0.01i 2 1960 I 2
Therefore when x 0.0015 m , f fld
4 15 2 10 8 9
1960 I 2 8900 9
Now 8900 . Therefore I 2 13 and I 3.6 A
9 1960
Example 3
Show that the force equation (19) can be restated as
1 dR
f fld 2
2 dx
where Φ is the total flux linking the coil and R is the total reluctance of the magnetic circuit.
65
Solution
N 2 dL N 2 dR
From L , 2
R dx R dx
The total energy stored in the magnetic field of the magnetic circuit given in Fig. 3 can be
expressed in magnetic circuit terms as
1
W fld Fd (21)
0
To evaluate the integral, the mmf F of the coil must be expressed as a function of the total flux .
The relation between the two quantities is described by a saturation curve. For a linear magnetic
circuit, the saturation curve is a straight line passing through the origin as shown in Fig. 5.
The total stored energy is given by the area oabo between the saturation curve and the vertical or
flux axis.
given by this area has no physical meaning, but it is a useful function for
The quantity W fld
evaluating the field force. It is called the coenergy. For a given saturation curve, linear or
nonlinear
F
W fld W fld (23)
If the magnetic circuit is linear, energy and coenergy are equal and they are given by
12 F
W fld W fld (24)
66
If motion is made to occur at a constant flux or so fast that the flux remains constant, it can be
shown that the input electrical energy is zero and mechanical work is done solely at the expense
of stored magnetic energy, i.e.
0 dW fld F fld dx (25)
The device in Fig. 2 has several saturation curves, one for every value of the gap length x . Fig. 6
shows two of such curves for x x1 and x x 2 where x1 is larger than x 2 . Referring to this figure,
the magnetic field energy reduces during motion at a constant flux 1 from the area oaco to the
smaller area oabo. The difference in area given by area obco represents the mechanical work
done.
If motion is made to occur at a constant current (or mmf) or so slowly that the current remains
constant, the mechanical work done is equal to increase in coenergy, i.e.
F fld dx
0 dW fld (26)
Referring to Fig. 7, the coenergy increases during motion at a constant flux F1 from the area oabo
to the larger area oaco. The difference in area given by area obco represents the mechanical work
done.
The equations (25) and (26) can be solved for the field force which comes out as partial
derivatives as follows:
67
W fld
f fld (27)
x cons tan t
W fld
f fld (28)
x i cons tan t
To evaluate equations (27) and (28) for the field force, W fld is expressed as function of and x ,
as function of F or i and x .
and W fld
Example 4
Use equations (27) and (28) to derive force expressions (19) and (20).
Solution
For linear magnetic circuit
12 F
W fld W fld
In terms of the current i and the gap length x or in terms of the current i and coil self inductance
L, L being a function of x , the coenergy is given by
1 N2 1 2
F Ni i 2
1 1 Ni
W fld i L
2 2 R 2 R 2
In terms of flux and the gap length x or in terms of flux and the total reluctance R, R being a
function of x , the magnetic field energy is given by
1 1 1
W fld F R 2 R
2 2 2
Example 5
A relay mechanism has a saturation curve which can be approximated by M F x ,
where M 9 10 8 .
(a) Find the stored energy as a function of and x
(b) Find the coenergy as a function of F and x
(c) Find the derivatives of energy and coenergy with respect to the gap length x
(d) Find the mechanical force for x 0.01 m and 0.0006 webers
68
Solution
(a) Since the saturation curve is nonlinear, to find the field energy we use equation (21):
2 2 2
x
3
1 1 x 2 x 1
W fld Fd d d
2
0 0
M M 0
M 3
(d) The given values are substituted into equation (27) to obtain the force:
W fld
f fld 2 x
3
2
2 0.01 6 10 4 3
178 N
8 2
x cons tan t M 3
9
10
3
Example 6
A relay mechanism has reluctance in terms of the gap length x as R 9 10 8 0.003 x AT/Wb .
The relay coil has 1620 turns and 55 Ω resistance. The external voltage source is 110 V dc.
(a) Find the energy stored in the magnetic field when the relay is open ( x 0.006 m )
(b) Find the energy stored in the magnetic field when the relay is closed ( x 0.001 m )
(c) Find the work done if the relay is allowed to close slowly from x 0.006 m to x 0.001 m
(d) Find the work done if the relay is allowed to close fast from x 0.006 m to x 0.001 m
Solution
(a) The current in the coil is I 1 V R 110 55 2 A
The mmf is F1 NI 1 1620 2 3240AT
For x 0.006 m , the reluctance of the magnetic circuit is
R1 9 10 8 0.003 0.006 8.1 10 6 AT/Wb
The flux across the air gap is 1 F1 R 1 3240 8.1 10 6 0.0004 webers
For a fixed value of x , the relation between and F is a straight line. Therefore from equation
(24), the energy stored in the magnetic field is obtained as
W fld 1 12 F11 12 3240 0.0004 0.648 J
69
(b) In the steady state, the current and mmf have the same values as in (a).
For x 0.001 m , the reluctance of the magnetic circuit is
R2 9 10 8 0.003 0.001 3.6 10 6
The flux across the air gap is 2 F1 R 2 3240 3.6 10 6 0.0009 webers
W fld 2 12 F1 2 12 3240 0.0009 1.458 J
(c) For slow closure or closure at constant current,
x2 x2 L2 2
1 dL 1 1 2
Wmech f fld dx i 2 dx 2i
2
dL i L2 L1
x1 x1
2 dx L11
2
1 2N2 N2 1 NI 1 NI 1 1
i NI 1 F1 2 1 0.810 J
2 R2 R1 2 R2 R1 2
Alternatively, we can plot the saturated curves for the two gap lengths as shown in Fig. 7 and
use the shaded area to find the work done.
Electromechanical devices can be designed in such a way that the permitted motion is rotational
rather than translational. Examples are shown in Fig. 8. In this case, the mechanical work is
expressed in terms of torque Tfld and the angle θ of rotation. The torque is given by
dwmech
T fld Nm (29)
d
By analogy with equations (11) and (19), the torque may be expressed as
1 dC
T fld e 2 for electric coupling and (30)
2 d
1 dL
T fld i 2 for magnetic field coupling (31)
2 d
The angular position θ is measured from arbitrarily chosen reference position for which θ is zero.
70
Fig. 8.a Simple rotating electrostatic machine
71
9 Torques and Forces in Doubly Excited Magnetic Field Systems
Multiple excited magnetic field devices are used to obtain forces and torques proportional to
electrical signals and electrical signals proportional to forces and velocities. Permanent magnets
are frequently used as one of the excitation paths. Models of doubly excited magnetic field
systems are shown in Fig. 9
Let us consider the system in Fig. 9.a which has a permanent magnet as one of the excitation
paths. The force developed by the device is given by the well known expression
f fld Bli (32)
where B is the flux density in the air gap and l is the total active length of the coil. This
expression for the force can also be derived using the foregoing method. Let the coil be displaced
through dx in a time dt . Then the electrical energy input
dx
dwelec eidt B l i dt Bl i dx
dt
ffld
fmech
N
x
Mechanical
system
S
i
Permanent + -
magnet V(t)
Fig. 9.a Doubly-excited magnetic system with permanent magnet as one of excitation paths
72
θ
i1
Tfld
-
e1 V2(t)
+ +
V1(t) e2
-
i2
Fig. 9.b Doubly-excited magnetic field system with two sets of electrical terminals
In this device the field energy remains constant during the conversion process so that
dw fld 0
Equating therefore the mechanical and electrical expressions, the force is found to be
f fld dwmech dx Bl i
Let us now consider the system in Fig. 9.b. The electrical energy input
dwelec e1i1 dt e2 i2 dt
Similarly
di dL di dM
e2 L2 2 i 2 2 M 1 i1 (34)
dt dt dt dt
73
From the relation
dw dwelec dw fld
T fld mech
d d
Example 7
For the doubly excited system in Fig. 9.b, the inductances are approximated as follows: L1 = 11
+ 3cos2θ, L2 = 7 + 2cos2θ, M = 11cosθ. The coils are energized with dc currents. I1 = 0.7 A, I2
= 0.8 A. Find the torque for θ = +50°. What is its direction?
Solution
dL1 dL2 dM
6 sin 2θ ; 4 sin 2θ ; 11sin θ
d d d
1 dL 1 dL dM
T fld i12 1 i 22 2 i1i2
2 d 2 d d
1 1
0.7 6 sin 2θ 0.8 4 sin 2θ 0.7 0.8 11sin θ
2 2
2 2
2.75 sin 2θ 6.16 sin θ Nm
For 50, T fld 7.43 Nm . The torque acts anticlockwise on the rotor.
74
mutual inductance is also due to interaction force. Forces of interaction between two current-
carrying coils are directed in a way that tends to increase the magnitude of the flux linkage of
each of the coil or in a way that tends to align the mmf axes of the coils.
The forces of interaction can be made proportional to electrical signals by supplying the
particular signals at one of the electrical inputs and their direction can be controlled.
11 Motional emf
The terms in the induced voltage equations (15), (33) and (34) for which inductances or mutual
inductances are constant with current i differentiated, are the transformer emfs. They give rise to
electrical/electrical power conversion. The other terms arise if the inductances or mutual
inductances vary as the movable members move. These voltages called motional or rotational
emfs give rise to mechanical/electrical power conversion. Expressions for torque or force in
electromagnetic devices can be derived by considering only these terms.
Let us consider the singly excited electromagnetic system. Electrical energy flow due to this emf
component caused by movement is
dL
d welec i i dt i 2 dL
dt
Example 8
Considering only the motional emfs, derive an expression for torque developed in a doubly
excited electromagnetic device.
Solution
d w elec e1i1dt e 2 i2 dt i1 i1dL1 i2 dM i2 i2 dL2 i1dM i12 dL1 2i1i2 dM i22 dL2
1 1
d w fld i12 dL1 i22 dL2 i1i 2 dM
2 2
1 1
dwmech d w elec d w fld i12 dL1 i22 dL2 i1i2 dM
2 2
Hence
1 dL 1 dL dM
T fld i12 1 i 22 2 i1i2
2 d 2 d d
75
12 Examples of Electromechanical Devices
A solenoid relay is operated from a 110-V, dc supply and the 5000-turn coil resistance is 5.5 kΩ.
The core diameter of the relay is 20 mm and the gap length is 1.5 mm, the armature being
stationary. The gap faces may be taken as parallel and the permeability of the ferromagnetic parts
as very high. Estimate (a) the gap flux density (b) the coil inductance (c) the pull on the armature
Solution
V 100
(a) I 20 10 3 A
R 5.5 10 3
F NI 20 10 3 5000 100AT
F 100
H 3
0.67 10 5 AT/m
l g 1.5 10
B o H 4 10 7 0.67 10 5 84 10 3 Wb/m 2
(b) BA 84 10 3 10 2 10 6 26.3 10 6 Wb
L
N
26.3 10 6 5000 6.56 H
I 20 10 3
1 dL
(c) F fld i 2
2 dx
1.5 10 3 9.82 10 3
L( x) 6.56
x x
where x is in meters
76
dL 9.82 10 3
dx x2
1 9.82 10 3
Therefore F fld 20 2 10 6 2 0.88 N
2 1.5 10 6
When the plunger relay is energized, the current remains constant at 2.0 A and the plunger
moves such that the air gap is reduced in length from 20 mm to 10 mm. If losses may be
neglected, calculate the average force experienced by the plunger and the energy taken from the
source. The diameter of the plunger is 50 mm. Neglect the air gap at the hole through which the
armature moves.
Solution
For x 2 l g 10 mm, F NI 1500 2 3000 AT
F 3000
H 300 10 3 AT/m
lg
10 10 3
B o H 4 10 300 10 3 0.377 T
7
BA 0.377 25 2 10 6 0.74 10 3 Wb
N 1500 0.74 10 3
L2 0.56 H
I 2
N 2 N 2 o A 1500 2 4 10 7 25 2 10 6
Alternatively, L1 0.56 H
R1 x1 10 10 3
10 mm
For x1 l g 20 mm , L1 0.56 0.28 H
20 mm
77
1 2 x2 dL 1 1 1
dx I 2 dL I 2 L2 L1 2 2 0.28 0.56 J
L2
Total work done I
2 x1 dx 2 L1 2 2
Solution
1 dR
f fld 2
2 dx
With the fixed and movable members separated by a distance x m, the total air gap would be 2 x .
Hence the total reluctance would be in the form
2x dR 2
R( x) C and
o A dx o A
78
where B is the flux density in the iron. We note that the cross-sectional area of the iron part of
the magnetic circuit is equal to the cross-sectional area of the air gaps.
Now
B2 A
20 N .
o
Therefore
1
20 4 10 7 2
B 6 0.222 T and
500 10
B 0.222
H 250 AT/m
μ o μ r 4 10 7 700
The total mmf required to create the above flux density in both the core and the block
F Hl 250 600 200 10 3 200 AT
200
Hence I 2.0 A
100
79
Solution
(a) The equivalent circuits can be indicated as shown below:
where d = the air spacing and A is the effective area of the plate
1
A( ) r 2
2
80
o r 2
C ( ) where r = radius of the plates
d
1 dC o r 2 e 2
(b) T fld e 2 k e 2
2 d 2d
r E 2 2
8.85 10 12 4 2 10 4 10 6
(c) T fld o 3
7.08 10 6 Nm
2d 2 10
Tmech 3 k T fld .
70.8 10 7
Therefore k 2.36 10 6 Nm/rad
3
(d) T fld k e . Therefore T fld (ave) k ave(e 2 ) k E rms
2 2
81
Fig. 14 Electrostatic loudspeaker
Solution
1 2 dC
(a) f fld
et
2 dx
A
C o r
x
Hence
1 o r Aet2 1 o r A
f fld 2
2
E e2 1 o 2r A E 2 2 Ee e 2
2 x 2 x 2 x
1 o r A 2
f fld
2 x2
E 2 Ee if e 2 0
Now
1 o r A 2 1 8.85 10 12 1 0.12 106
E 0.139 and
2 x2 2 0.52 4
1 o r A
2
2 E 2 0.139 2.78 10 4
2 x E
Hence f fld 0.139 2.78 10 4 e Nm
(b) 300 x pp 2 2.78 10 4 100 x pp 0.185 mm
82
13 Further exercises
1. A machine with two coils has inductances as follows: (on rotor) L1 = 0.1 H, (on stator) L2 =
0.5 H, M = 0.2cosθ H, where θ is the angle of the rotor coil axis displaced anti-clockwise
with respect to the stator coil axis. Coil 1 (on rotor) is short circuited. Coil 2 (on stator) is
energized from a 60-Hz sinusoidal voltage source of 110 V. Resistances of the coils may be
neglected. Assume the circuit operates in sinusoidal steady state. θ is set to 30°.
(a) Find an expression for the instantaneous torque on the rotor.
(b) Find the value of the average torque on the rotor
(c) Determine the direction of this torque.
2. Fig. E.1 shows the essential components of a loudspeaker. The permanent magnet produces a
uniform radial magnet flux density of 0.8 Wb/m2 across a cylindrical air gap. The coil of 30
turns is wound on a fiber cylinder of diameter d = 2 cm. When assembled, the coil is inserted
into the air gap of the magnet.
(a) Determine the force of the cone as a function of the current i.
(b) Determine the induced voltage in the coil per unit of coil velocity
(c) Neglecting coil resistance, show that the electrical power input to the coil is equal to the
mechanical power delivered to the cone.
(d) Over most of the audio frequency range, the force is absorbed by the damping action of
the air being driven by motion of cone. Suppose the damping coefficient of the cone is
0.3 N per m/s of velocity. If the current in the coil is imsinωt, determine the velocity of
the coil and the voltage induced in the coil. Show that the impedance looking into the coil
terminals is resistive and has a value of 7.6 Ω
3. A rotating machine of the form shown in Fig. E.2 has a reluctance which can be expressed
approximately by
R = 5.06 x 104(2.5 + 1.5 cos2θ) AT/Wb
where θ is the angle between the axis of the rotor and of the stator.
(a) Suppose a voltage of 110 V rms at 60 Hz is applied to the 15-turn winding. If the winding
resistance is negligible, determine the magnetic flux in the machine.
(b) At what angular velocity must the rotor rotate to produce an average torque?
83
(c) What is the maximum value of the average torque this machine can produce when
connected to a 110-V, 60-Hz supply? What is the maximum mechanical power?
84