EasyLogic
  PM1125H series
  Technical Datasheet
  The EasyLogic™ PM1125H basic power and energy meters
  Offering all the measurement capabilities required to monitor the electrical installation in a single 96 x 96 mm unit, with 8
  segment alpha-numeric bright, large 14.2 mm high LED display.
PB120503
                                                              PM1125H
                                                                                                                              1
                 EASYLOGIC PM1125H BASIC POWER AND ENERGY METERS                                             FUNCTIONS AND CHARACTERISTICS
             PM1125H
                                                             EasyLogic™ PM1125H meters are ideal replacements for multiple analogue meters
                                                             for stand-alone metering in custom panels, switch boards, switch-gear, genset
            PB120503
                                                             panels, motor control centres, power factor improvement panels and OEM panel
                                                             board.
                                                             •        Application
                                                                 ––     Cost management applications
                                                                        ––   Measurement of basic electrical parameters in control panels,
                                                                             motor control panels, power distribution boards, OEM’s, Building
                                                                             management systems, panel instrumentation
                                                                        ––   Aggregation of energy consumption and cost allocation per area, per
                                                                             usage, per shift and per time within the same facility
                                                                 ––     Network management applications
                                                                        ––   Power quality analysis (THD %)
                                                                        ––   Demand measurement
            EasyLogic™ PM1125H power meter front ISO view
                                                                        ––   Measurement of Power factor
                                                                        ––   Phase angle between the voltage and current
                                                                        ––   % unbalance among voltage and current
      PB120504
                                                                        ––   Modbus RTU protocol RS-485 communication port for integration with
                                                                             energy management systemMain characteristics
                                                             •        Main characteristics
                                                                 ––     Easy to install: Mounts using two retainer clips, no tools required. Compact
                                                                        meter with 49 mm meter depth behind the panel, connectable up to 480 V
                                                                        +10% AC volts L-L without voltage transformers for installation complaint
                                                                        with measurement category III, and double insulated
                                                                 ––     Easy to operate: Intuitive navigation with self-guided menus and Heart
                                                                        beat LED indicates normal functioning of meters while it conveys the
                                                                        communication status when connected to RS-485 network
                                                                 ––     LED display: Intuitive navigation with self-guided, four buttons, 8 segment
                                                                        alphanumeric LEDs of height ~14.2 mm (0.55 in), and three lines of
                                                                        concurrent values with Kilo & Mega value indicator.
                                                                 ––     Power and energy: measurement, display and recording of three power
             EasyLogic™ PM1125H front view                              and corresponding energy parameters simultaneously - W/Wh, VA/ VAh
                                                                        and VAR/ VARh.
                                                                 ––     Demand: measurement of Peak, present and last demand values of either
                                                                        W, VA or VAR parameters with selectable demand parameter, demand
                                                                        interval and demand technique
PB120505
                                                                 ––     Accuracy:
                                                                        ––   Class 1.0 for active energy as per the test limits given in IEC 62053-21
                                                                        ––   Class 0.5 for active energy as per the test limits given in IEC 62053-22
                                                                        ––   Class 2.0 for reactive energy as per the test limits given in IEC 62053-23
                                                                        ––   Tested in accordance with IEC 62052-11 for energy test requirements
                                                                        ––   EMI/ EMC tests: As per IEC 61326-1
                                                                 ––     CT nominal: 5 A or 1 A I-nominal (field settable). CT reversal auto
                                                                        correction for energy consumption.
                                                                 ––     Password: Field configurable password for securing set up information and
                                                                        prevents tampering of integrated values.
                                                                 ––     Cyber security: Option for disabling RS-485 port through front panel keys
                                                                        against unauthorized access. This feature can also be used for maintenance
                                                                        and troubleshooting of complex communication network.
                                                                 ––     Display: Auto scaling, 4 digits for Instantaneous parameters and 5+3 digits
             EasyLogic™ PM1125H power meter rear view
                                                                        for energy parameter with auto scale and auto range capability.
                                                                 ––     Analogue load bar: The colour-coded analogue load bar at the front side
                                                                        indicates the percentage of load through 12 LED’s with the option to select
                                                                        full scale based on connected load.
                                                                 ––     Suppression current: To disregard the measurement of induced and panel
                                                                        auxiliary load current in the circuit (settable from 5 to 99 mA)
                                                                 ––     Protective cover: Tamper-proof terminal screws do not detach from housing
           2                                                                                                                              PLSED310164EN
EASYLOGIC PM1125H BASIC POWER AND ENERGY METERS                                                                    FUNCTIONS AND CHARACTERISTICS
PM1125H
PM1125H technical specifications
General
Use on LV & MV systems with Potential transformer (PT or VT)/ Current transformer (CT) ratio programmable at site
Digital panel meters for measurement of basic electrical parameters
Instantaneous rms values
Current                                              Average line current of 3-phase, per-phase, and calculated neutral current
Voltage                                              Average voltage of L-L, L-N parameters, per-phase
Frequency                                            Any available line
Real (active), reactive, and apparent power          Total and per-phase
True power factor                                    Average and per-phase signed
% Unbalance                                          Maximum % unbalance among phases for Volts & Amps
Revolution per minute (RPM)                          RPM of alternator or generator when number of poles set for 2, 4, 6, 8, 12, 14 or 16 (any one pole)
Energy values stored in non-volatile memory
Delivered & Received or Forward & Reverse or Import & Export energy (4 quadrant) - Accumulated or Integrated active (Real - Wh), reactive (VARh), apparent (VAh)
Time counters such as meter ON Hrs, load RUN Hrs and power outage counters
Old registers facilitate retrieval of last cleared energy values and load Run Hrs
 Display
Bright red colour LED display, 8 segment alphanumeric LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row, auto range, auto scale
 Communication
RS-485 serial channel connection Industry standard Modbus RTU protocol
Native Plug and Play support for Schneider Electric energy management system software - EcoStruxure Power Monitoring Expert, EcoStruxure Power SCADA
Operation along with ION Setup programming support
 Diagnostics
Diagnostic page indicates the healthiness of communication system, all LED test, device serial number, device model number OS & RS version,
communication status, error code display
 Page lock
Page lock and unlock features. Once the commonly referred page is enabled for lock feature, then the display returns to locked page in 4 minutes of inactive
time
 Favourite page
Number and type of parameters can be chosen and arranged in Favourite page according to the user’s requirement
 Electrical characteristics
Type of measurement                                  True RMS, 4 quadrant power and energy, 32 samples/ cycle
 Measurement accuracy
Current, per-phase & average                         ± 0.5 % of reading
Voltage, L-N, L-L, per-phase & average               ± 0.5 % of reading
Power (active and apparent)                          ± 1.0 % for Class 1.0, ± 0.5% for Class 0.5
Power (reactive)                                     ± 2.0 % for Class 1.0 & Class 0.5
Power factor, per-phase & average                    ± 0.01 of reading
Frequency                                            ± 0.05 % for F-nominal 50/ 60 Hz ± 2
                                                     ± 0.2 % for Frequency range from 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz
Active or real energy                                Class 1.0 (± 1.0 %) Class 0.5 (± 0.5%)
Apparent energy                                      ± 1.0 % & ± 0.5 %
Reactive energy                                      Class 2.0 (± 2.0 %)
THD %                                                ± 5 % of reading
 Input-voltage
VT (PT) connection                                   Selectable from No VT (direct), 1 VT, 2 VT to 3 VT
VT (PT) primary                                      100 V L-L to 999 kV L-L max
U (V) nominal (secondary)                            Up to 277 V L-N/ 480 V L-L (selectable VT secondary from 100, 110, 115, 120 to 415 V L-L)
Operating voltage range with accuracy                80-480 V L-L ± 10 % Category III
Measured Voltage with full range                     35 to 600 V L-L
Permanent overload (withstand)                       750 V L-L, continuous
Impedance                                            ≥5 MΩ
Frequency range                                      50/ 60 Hz ± 2
VA burden                                            ≤0.2 VA at 240 V L-N at 50 Hz
 Frequency – measurement
Nominal operating range                              50/60 Hz ± 2 (± 0.05 % accuracy)
Extended operating range                             30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz (± 0.2 % accuracy)
Voltage input                                        80 to 480 V L-L ± 10 %
PLSED310164EN                                                                                                                                                      3
    EASYLOGIC PM1125H BASIC POWER AND ENERGY METERS                                                                 FUNCTIONS AND CHARACTERISTICS
PM1125H
    PM1125H technical specifications (continued)
    Input-current
    CT connect                              Solo or multi-phase current measurement by installing CT (s) in either of A1, A2, A3, A12, A23, A13, A123 phase(s)
    CT primary                              1 A to 32767 Amps, programmable
    CT secondary                            1 A or 5 Amps I-nominal (field settable)
    Operating current range with accuracy   10 mA to 6 A+1
    Measured Amps with full range           5 mA to 10 A
    Suppression current                     5 to 99 mA (to disregard negligible load)
    Permanent overload (withstand)          Continuous 10 A, 10 s/hr 50 A, 1s/hr 500 A
    Impedance                               0.3 mΩ
    Frequency range                         50/60 Hz ± 2
    VA burden                               ≤0.1 VA at 5 A, 50 Hz
    AC - control power
    Operating range                         48 to 277 V L-N AC ± 10 %
    Burden                                  ≤4 VA at 240 V L-N, 50 Hz
    Frequency                               50/60 Hz nominal (45 to 65 Hz operating range)
    Ride-through time                       200 ms at 240 V L-N, 50Hz
    DC - control power
    Operating range                         48 to 277 V DC ± 10 %
    Burden                                  ≤2 W at 240 V DC
    Ride-through time                       120 ms at 240 V DC
    Display update
    Instantaneous/ RMS parameters           1s
    Demand parameters                       5s
    THD % (voltage and current)             5s
    Power system
    Phase labelling                         Configurable to 123, ABC, rst, pqr or ryb
    Wiring configuration                    13 wiring schemes (5 on front screen)
                                            1ph, 2 w, L-N
                                            1ph, 2 w, L-L
                                            1ph, 3 w, L-L with N (2phase)
                                            3ph, 3 w, Delta, Ungrounded
                                            3ph, 3 w, Delta, Corner Grounded+2
                                            3ph, 3 w, Wye, Ungrounded+2
                                            3ph, 3 w, Wye Grounded+2
                                            3ph, 3 w, Wye, Resistance Grounded+2
                                            3ph, 4 w, Open Delta, Center-Tapped+2
                                            3ph, 4 w, Delta, Center-Tapped+2
                                            3ph, 4 w, Wye, Ungrounded+2
                                            3ph, 4 w, Wye Grounded
                                            3ph, 4 w, Wye, Resistance Grounded+2
    Mechanical characteristics
    Weight                                  ~ 300 g (10.6 oz)
    IP degree of protection                 IP 51 front side, IP 54 with gasket (optional accessory), IP 30-meter body, tested as per IEC 60529
    Material                                Polycarbonate meets UL 94V-0 flammability rating
    Dimensions W x H x D                    96 x 96 x 49 mm (3.78 x 3.78 x 1.93 in) (D = depth of the meter from housing mounting flange)
                                            13 mm (0.51 in) protrusion of meter from housing flange
    Mounting position                       vertical
    Panel thickness                         5 mm (0.196 in) maximum
    Environmental characteristics
    Operating temperature                   - 10 to +60º C (14 to140º F)
    Storage temperature                     - 20 to +70º C (-4 to 158º F)
    Humidity rating                         5 % to 95 % RH non-condensing
    Pollution degree                        2
    Attitude                                ≤2000 metres (6562 ft), Category III
    Product life                            >7 years
    Insulation category                     Double insulation for user accessible parts
+1
      Additional error of ± 2 % between 10 mA to 50 mA, ± 1% between 50 mA to 100 mA)
+2
     Through communication
4                                                                                                                                                 PLSED310164EN
EASYLOGIC PM1125H BASIC POWER AND ENERGY METERS                                                                   FUNCTIONS AND CHARACTERISTICS
PM1125H
PM1125H technical specifications (continued)
 Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge                       IEC 61000-4-2
Immunity to radiated field                    IEC 61000-4-3
Immunity to fast transients                   IEC 61000-4-4
Immunity to impulse waves                     IEC 61000-4-5
Conducted immunity                            IEC 61000-4-6
Immunity to magnetic fields                   IEC 61000-4-8
Immunity to voltage dips                      IEC 61000-4-11
Emissions                                     Emissions FCC Part 15 Class A/CE
 Safety
Europe                                        CE, as per IEC 61010-1 edition-3
US and Canada                                 cULus as per UL61010-1 and CAN/CSA-C22.2 IEC 61010-1 edition-3, for 480 V AC L-L
Measurement Category (Voltage inputs)         CAT III up to 480 V L-L
Overvoltage Category (Control power)          CAT III up to 300 V L-N
Dielectric                                    As per IEC/UL 61010-1 edition-3
Protective Class                              II, Double insulated for user accessible parts
Green premium                                 EOL, REACH , PEP, RoHS complied
 Communication
RS-485 port                                   Modbus RTU: 2-Wires, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity is Odd or
                                              Even, 2 stop bits if none.
                                              DLF3000: Firmware update through communication port
Isolation                                     2.5 kV RMS, double insulated
Protection features                           User configurable password (selectable from 0000 to 9999) protected for set-up and clearing of energy, and
                                              other integrated data
Display language                              English
Technical publication                         Printed installation guide (QSG) supplied with meter in multi-language (EN, ES, FR, DE, PT, RU, TR, ZH) and user
                                              guide in soft format
 Human machine interface
Display type                                  8 segment Alpha-numeric LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row, 1 column of 12 LEDs to
                                              indicate percentage of load connected in system. 4 digits for V AF PF parameters with auto scaling and auto range
Keypad                                        4 buttons for navigation at the front, combination of 2 buttons for performing set-up, lock/unlock pages and
                                              viewing diagnostic pages
CAL LED (pulse LED)                           Red colour, meter constant is configurable from 1 to 9999000 pulses/ k_h (kWh, kVAh, or kVARh)
Comm. activity                                Green LED (for indicating RS-485 interface or heart beat pulse)
Feature set summary
 Parameter/ Meter reference                                                                PM1125H, CL 1.0, RS-485              PM1125H CL 0.5, RS-485
Class of accuracy (Wh)                                                                                 1.0                                  0.5
Sampling rate per cycle                                                                                32                                    32
Amps: average and per-phase, calculated neutral current                                                 b                                     b
Voltage: V L-N, V L-L, average, per-phase                                                               b                                     b
Power factor: average and per-phase                                                                     b                                     b
Frequency: any available phase                                                                          b                                     b
Power (W, VA, VAR) - Total and per-phase                                                                b                                     b
Energy (Wh, VARh, VAh) - Delivered & Received or Forward & Reverse or Import &                          b                                     b
Demand parameters – selectable for W, VA, VAR (one at a time)                                           b                                     b
Old registers – retrieval of last cleared values of energy and Run Hrs                                  b                                     b
Revolutions per minute (RPM)                                                                            b                                     b
Phase angle : Amp Deg (V to Amps, per-phase)                                                            b                                     b
% Unbalance: Max unbalance Volts & Amps among 3 phase (s)                                               b                                     b
Life time counter - meter ON Hrs, Load Run Hrs and number of power interruptions                        b                                     b
Communication: 2 wire, RS-485, Modbus RTU protocol                                                      b                                     b
Commercial reference number                                                                    METSEPM1125HCL10RS               METSEPM1125HCL05RS
PLSED310164EN                                                                                                                                                  5
               EASYLOGIC PM1125H BASIC POWER AND ENERGY METERS                                                                         FUNCTIONS AND CHARACTERISTICS
      PM1125H
                       PM1125H meter mounting
            PB119373
                                                        PB119374
                                                                                                     PB119375
                      See the appropriate Installation Guide for correct installation instructions.
                       PM1125H meter mechanical dimensions
PB119372
                  PM1125H meter display overview
                                                                                    A    Menu selection buttons
            PB120506
                                                                                        < Left key: To navigate left
                                                                                            Down key: To navigate down
                                                                                        <
                                                                                            Up key: To navigate up
                                                                                        <
                                                                                        <   Right/OK key: To navigate right/Enter key
                                                                                    B    LED indicators
                                                                                    C    Alpha numeric LED display
                                                                                    D       Analogue load bar
                                                                                    E    Current inputs
           PB120507
                                                                                    F       RS-485
                                                                                    G       Retainer clip
                                                                                    H Control power
                                                                                    I    Voltage inputs
                                                                                 See the appropriate Installation Guide for correct installation instructions.
       6                                                                                                                                                   PLSED310164EN
Schneider Electric Industries SAS   As standards, specifications and designs develop from time to time, please ask
35, Rue Joseph Monier,              for confirmation of the information given in this document.
CS 30323
F - 92506 Rueil Malmaison Cedex
                                    Design: Schneider Electric
RCS Nanterre 954 503 439            Photos: Schneider Electric
Capital social 896 313 776
www.schneider-electric.com          Over 75 % of Schneider Electric products
                                    have been awarded the Green Premium ecolabel.
EasyLogic PM1125H
PLSED310164EN                       © 2018 - Schneider Electric - All rights reserved                  07-2018