PRODUCT-DETAILS
AF1650-30-11-70
AF1650-30-11 100-250V 50/60Hz / 100-250V
DC Contactor
Informações gerais
Extended Product Type AF1650-30-11-70
Product ID 1SFL677001R7011
EAN 7320500249703
Catalog Description AF1650-30-11 100-250V 50/60Hz / 100-250V DC Contactor
The AF1650-30-11-70 is a 3 pole - 1000 V IEC or 1000 V UL contactor pre-mounted
auxiliary contacts and and Main Circuit Bars, controlling motors up to 560 kW / 400 V AC
(AC-3) or 900 hp / 480 V UL and switching power circuits up to 1650 A (AC-1) or 1650 A UL
general use. Thanks to the AF technology, the contactor has a wide control voltage range
Long Description (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel
energy consumptions and ensuring distinct operations in unstable networks. Furthermore,
surge protection is built-in, offering a compact solution. AF contactors have a block type
design, can be easily extended with add-on auxiliary contact blocks and an additional wide
range of accessories.
Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900
Popular Downloads
Data Sheet, Technical 1SBC100192C0206
Information
AF1650-30-11-70 2
Instructions and Manuals 1SFC101002M5501
Dimension Diagram 53540930-7
Dimensions
Product Net Width 438 mm
Product Net Depth / 244 mm
Length
Product Net Height 392 mm
Product Net Weight 33 kg
Technical
Number of Main Contacts 3
NO
Number of Main Contacts 0
NC
Number of Auxiliary 1
Contacts NO
Number of Auxiliary 1
Contacts NC
Rated Operational Voltage Main Circuit 1000 V
Rated Frequency (f) Main Circuit 50 / 60 Hz
Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 1650 A
Thermal Current (I th )
Rated Operational Current (1000 V) 40 °C 1650 A
AC-1 (I e ) (1000 V) 55 °C 1450 A
(1000 V) 70 °C 1270 A
(690 V) 40 °C 1650 A
(690 V) 55 °C 1450 A
(690 V) 70 °C 1270 A
Rated Operational Current (415 V) 55 °C 1060 A
AC-3 (I e ) (440 V) 55 °C 1060 A
(500 V) 55 °C 970 A
(690 V) 55 °C 970 A
(1000 V) 55 °C 400 A
(380 / 400 V) 55 °C 1060 A
(220 / 230 / 240 V) 55 °C 1060
Rated Operational Power (415 V) 630 kW
AC-3 (P e ) (440 V) 710 kW
(500 V) 710 kW
(690 V) 1000 kW
(1000 V) 600 kW
(380 / 400 V) 560 kW
(220 / 230 / 240 V) 315 kW
Rated Making Capacity 10 x Ie AC-3
AC-3
Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 10000 A
Withstand Current Low at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 2200 A
Voltage (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 5500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 12000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 7500 A
Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 12000 A
Capacity
Maximum Electrical (AC-1) 60 cycles per hour
Switching Frequency (AC-2 / AC-4) 60 cycles per hour
(AC-3) 60 cycles per hour
Rated Operational Current (110 V) 1-Pole, 40 °C 1650 A
AF1650-30-11-70 3
DC-1 (I e ) (110 V) 2 Poles in Series, 40 °C 1650 A
(220 V) 3 Poles in Series, 40 °C 1650 A
(600 V) 3 Poles in Series, 40 °C 1650 A
(850 V) 3 Poles in Series, 40 °C 1650 A
Rated Operational Current (220 V) 3 Poles in Series, 40 °C 1650 A
DC-3 (I e ) (600 V) 3 Poles in Series, 40 °C 1650 A
(850 V) 3 Poles in Series, 40 °C 1650 A
Rated Operational Current (220 V) 3 Poles in Series, 40 °C 1650 A
DC-5 (I e ) (600 V) 3 Poles in Series, 40 °C 1650 A
(850 V) 3 Poles in Series, 40 °C 1650 A
Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
(U i ) acc. to UL/CSA 1000 V
Rated Impulse Withstand Main Circuit 8 kV
Voltage (U imp )
Mechanical Durability 0.5 million
Maximum Mechanical 300 cycles per hour
Switching Frequency
Coil Operating Limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit 50 Hz 100 ... 250 V
Voltage (U c ) 60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Coil Consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 48 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 48 V·A
Holding at Max. Rated Control Circuit Voltage DC 20.5 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 2450 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 2450 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 2290 V·A
Operate Time Between Coil De-energization and NC Contact Closing 35 ... 55 ms
Between Coil De-energization and NO Contact Opening 35 ... 55 ms
Between Coil Energization and NC Contact Opening 50 ... 80 ms
Between Coil Energization and NO Contact Closing 50 ... 80 ms
Connecting Capacity Main Bar 100 mm²
Circuit
Connecting Capacity Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Auxiliary Circuit Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type Main Circuit: Bars
Technical UL/CSA
NEMA Size 8
Horsepower Rating NEMA (230 V AC) Three Phase 450 Hp
(460 V AC) Three Phase 900 Hp
(575 V AC) Three Phase 900 Hp
Maximum Operating Main Circuit 1000 V
Voltage UL/CSA
General Use Rating (1000 V AC) 1650 A
UL/CSA (600 V AC) 1650 A
Horsepower Rating (220 ... 240 V AC) Three Phase 450 hp
UL/CSA (440 ... 480 V AC) Three Phase 900 hp
(550 ... 600 V AC) Three Phase 1150 hp
Environmental
AF1650-30-11-70 4
Ambient Air Temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Maximum Operating Without Derating 3000 m
Altitude Permissible
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Certificates and Declarations (Document Number)
ABS Certificate 15-LD1408622-PDA
BV Certificate BV_13409-C0BV
CB Certificate SEMKO_SE-74013
CCS Certificate GB14T00030
CQC Certificate CQC2003010304101933
CQC2015010304752548
cUL Certificate UL_20130904-E73397
Declaration of Conformity 2020980304001303
- CCC 2020980304001043
Declaration of Conformity 2CMT2019-005796
- CE
DNV GL Certificate TAE00001W1
EAC Certificate 9AKK107046A8618
Environmental Information 1SFC101014D0201
1SAC200046H0008
GL Certificate GL_20263-04HH
Instructions and Manuals 1SFC101002M5501
LOVAG Certificate SE-201993
LR Certificate 16-20064
PRS Certificate TE_2092_880423_16
RINA Certificate ELE060313XG_002
RMRS Certificate 9AKK107045A6978
RoHS Information 2CMT2019-005796
UL Listing Card UL_E73397
Container Information
Package Level 1 Units box 1 piece
Package Level 1 Width 555 mm
Package Level 1 Depth / 365 mm
Length
Package Level 1 Height 500 mm
Package Level 1 Gross 35 kg
Weight
Package Level 1 EAN 7320500249703
Package Level 2 Units 1 piece
Classifications
Object Classification Code Q
ETIM 4 EC000066 - Magnet contactor, AC-switching
AF1650-30-11-70 5
ETIM 5 EC000066 - Magnet contactor, AC-switching
ETIM 6 EC000066 - Power contactor, AC switching
ETIM 7 EC000066 - Power contactor, AC switching
ETIM 8 EC000066 - Power contactor, AC switching
eClass V11.0 : 27371003
UNSPSC 39121529
IDEA Granular Category 4755 >> Contactors
Code (IGCC)
E-Number (Finland) 3709258
E-Number (Norway) 4115390
E-Number (Sweden) 4115390
Categorias
Produtos e Sistemas de Baixa Tensão → Produtos para controle → Contatores → Contatores