1SFL677001R7011 Af1650 30 11 70

The document provides product details for the AF1650-30-11-70 contactor. It is a 3 pole 1000V contactor with auxiliary contacts that can control motors up to 560kW at 400V AC or 900hp at 480V UL. It has a wide control voltage range of 100-250V 50/60Hz or DC. Key specifications include a rated operational current of 1650A, rated operational power of 630kW at 415V, and rated insulation voltage of 1000V.

Uploaded by

ederson
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views5 pages

1SFL677001R7011 Af1650 30 11 70

The document provides product details for the AF1650-30-11-70 contactor. It is a 3 pole 1000V contactor with auxiliary contacts that can control motors up to 560kW at 400V AC or 900hp at 480V UL. It has a wide control voltage range of 100-250V 50/60Hz or DC. Key specifications include a rated operational current of 1650A, rated operational power of 630kW at 415V, and rated insulation voltage of 1000V.

Uploaded by

ederson
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

PRODUCT-DETAILS

AF1650-30-11-70
AF1650-30-11 100-250V 50/60Hz / 100-250V
DC Contactor

Informações gerais
Extended Product Type AF1650-30-11-70

Product ID 1SFL677001R7011

EAN 7320500249703

Catalog Description AF1650-30-11 100-250V 50/60Hz / 100-250V DC Contactor

The AF1650-30-11-70 is a 3 pole - 1000 V IEC or 1000 V UL contactor pre-mounted


auxiliary contacts and and Main Circuit Bars, controlling motors up to 560 kW / 400 V AC
(AC-3) or 900 hp / 480 V UL and switching power circuits up to 1650 A (AC-1) or 1650 A UL
general use. Thanks to the AF technology, the contactor has a wide control voltage range
Long Description (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel
energy consumptions and ensuring distinct operations in unstable networks. Furthermore,
surge protection is built-in, offering a compact solution. AF contactors have a block type
design, can be easily extended with add-on auxiliary contact blocks and an additional wide
range of accessories.

Ordering
Minimum Order Quantity 1 piece

Customs Tariff Number 85364900

Popular Downloads
Data Sheet, Technical 1SBC100192C0206
Information
AF1650-30-11-70 2

Instructions and Manuals 1SFC101002M5501

Dimension Diagram 53540930-7

Dimensions
Product Net Width 438 mm

Product Net Depth / 244 mm


Length

Product Net Height 392 mm

Product Net Weight 33 kg

Technical
Number of Main Contacts 3
NO

Number of Main Contacts 0


NC

Number of Auxiliary 1
Contacts NO

Number of Auxiliary 1
Contacts NC

Rated Operational Voltage Main Circuit 1000 V

Rated Frequency (f) Main Circuit 50 / 60 Hz

Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 1650 A


Thermal Current (I th )

Rated Operational Current (1000 V) 40 °C 1650 A


AC-1 (I e ) (1000 V) 55 °C 1450 A
(1000 V) 70 °C 1270 A
(690 V) 40 °C 1650 A
(690 V) 55 °C 1450 A
(690 V) 70 °C 1270 A

Rated Operational Current (415 V) 55 °C 1060 A


AC-3 (I e ) (440 V) 55 °C 1060 A
(500 V) 55 °C 970 A
(690 V) 55 °C 970 A
(1000 V) 55 °C 400 A
(380 / 400 V) 55 °C 1060 A
(220 / 230 / 240 V) 55 °C 1060

Rated Operational Power (415 V) 630 kW


AC-3 (P e ) (440 V) 710 kW
(500 V) 710 kW
(690 V) 1000 kW
(1000 V) 600 kW
(380 / 400 V) 560 kW
(220 / 230 / 240 V) 315 kW

Rated Making Capacity 10 x Ie AC-3


AC-3

Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 10000 A
Withstand Current Low at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 2200 A
Voltage (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 5500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 12000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 7500 A

Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 12000 A
Capacity

Maximum Electrical (AC-1) 60 cycles per hour


Switching Frequency (AC-2 / AC-4) 60 cycles per hour
(AC-3) 60 cycles per hour

Rated Operational Current (110 V) 1-Pole, 40 °C 1650 A


AF1650-30-11-70 3

DC-1 (I e ) (110 V) 2 Poles in Series, 40 °C 1650 A


(220 V) 3 Poles in Series, 40 °C 1650 A
(600 V) 3 Poles in Series, 40 °C 1650 A
(850 V) 3 Poles in Series, 40 °C 1650 A

Rated Operational Current (220 V) 3 Poles in Series, 40 °C 1650 A


DC-3 (I e ) (600 V) 3 Poles in Series, 40 °C 1650 A
(850 V) 3 Poles in Series, 40 °C 1650 A

Rated Operational Current (220 V) 3 Poles in Series, 40 °C 1650 A


DC-5 (I e ) (600 V) 3 Poles in Series, 40 °C 1650 A
(850 V) 3 Poles in Series, 40 °C 1650 A

Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
(U i ) acc. to UL/CSA 1000 V

Rated Impulse Withstand Main Circuit 8 kV


Voltage (U imp )

Mechanical Durability 0.5 million

Maximum Mechanical 300 cycles per hour


Switching Frequency

Coil Operating Limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)

Rated Control Circuit 50 Hz 100 ... 250 V


Voltage (U c ) 60 Hz 100 ... 250 V
DC Operation 100 ... 250 V

Coil Consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 48 V·A


Holding at Max. Rated Control Circuit Voltage 60 Hz 48 V·A
Holding at Max. Rated Control Circuit Voltage DC 20.5 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 2450 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 2450 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 2290 V·A

Operate Time Between Coil De-energization and NC Contact Closing 35 ... 55 ms


Between Coil De-energization and NO Contact Opening 35 ... 55 ms
Between Coil Energization and NC Contact Opening 50 ... 80 ms
Between Coil Energization and NO Contact Closing 50 ... 80 ms

Connecting Capacity Main Bar 100 mm²


Circuit

Connecting Capacity Flexible with Ferrule 2x 0.75 ... 2.5 mm²


Auxiliary Circuit Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²

Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00

Terminal Type Main Circuit: Bars

Technical UL/CSA
NEMA Size 8

Horsepower Rating NEMA (230 V AC) Three Phase 450 Hp


(460 V AC) Three Phase 900 Hp
(575 V AC) Three Phase 900 Hp

Maximum Operating Main Circuit 1000 V


Voltage UL/CSA

General Use Rating (1000 V AC) 1650 A


UL/CSA (600 V AC) 1650 A

Horsepower Rating (220 ... 240 V AC) Three Phase 450 hp


UL/CSA (440 ... 480 V AC) Three Phase 900 hp
(550 ... 600 V AC) Three Phase 1150 hp

Environmental
AF1650-30-11-70 4

Ambient Air Temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C

Maximum Operating Without Derating 3000 m


Altitude Permissible

RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Certificates and Declarations (Document Number)


ABS Certificate 15-LD1408622-PDA

BV Certificate BV_13409-C0BV

CB Certificate SEMKO_SE-74013

CCS Certificate GB14T00030

CQC Certificate CQC2003010304101933


CQC2015010304752548

cUL Certificate UL_20130904-E73397

Declaration of Conformity 2020980304001303


- CCC 2020980304001043

Declaration of Conformity 2CMT2019-005796


- CE

DNV GL Certificate TAE00001W1

EAC Certificate 9AKK107046A8618

Environmental Information 1SFC101014D0201


1SAC200046H0008

GL Certificate GL_20263-04HH

Instructions and Manuals 1SFC101002M5501

LOVAG Certificate SE-201993

LR Certificate 16-20064

PRS Certificate TE_2092_880423_16

RINA Certificate ELE060313XG_002

RMRS Certificate 9AKK107045A6978

RoHS Information 2CMT2019-005796

UL Listing Card UL_E73397

Container Information
Package Level 1 Units box 1 piece

Package Level 1 Width 555 mm

Package Level 1 Depth / 365 mm


Length

Package Level 1 Height 500 mm

Package Level 1 Gross 35 kg


Weight

Package Level 1 EAN 7320500249703

Package Level 2 Units 1 piece

Classifications
Object Classification Code Q

ETIM 4 EC000066 - Magnet contactor, AC-switching


AF1650-30-11-70 5

ETIM 5 EC000066 - Magnet contactor, AC-switching

ETIM 6 EC000066 - Power contactor, AC switching

ETIM 7 EC000066 - Power contactor, AC switching

ETIM 8 EC000066 - Power contactor, AC switching

eClass V11.0 : 27371003

UNSPSC 39121529

IDEA Granular Category 4755 >> Contactors


Code (IGCC)

E-Number (Finland) 3709258

E-Number (Norway) 4115390

E-Number (Sweden) 4115390

Categorias

Produtos e Sistemas de Baixa Tensão → Produtos para controle → Contatores → Contatores

You might also like