Product datasheet
Specifications
Harmony, Harmony Hub, wireless
to modbus/TCP, ethernet gateway,
24...240 V AC/DC
Local distributor code: 409067055 ZBRN1
EAN Code : 3606480528484
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Harmony
Product or component type Harmony Hub Wireless/Ethernet gateway
Device short name ZBRN1
Product specific application Wireless Schneider Electric devices ecosystem
Function of module Zigbee green power gateway
Communication port protocol Modbus/TCP client application, with ZBRCETH module
Antenna type Integrated
Transmission frequency 2405…2480 MHz
Complementary
Maximum radio communication 100 m in free field
distance 250 m if a relay antenna is located between the transmitter and Harmony Hub
60 m if an external antenna is connected to Harmony Hub
25 m with Harmony Hub installed in a metal housing or in a closed metal enclosure
Radio response time < 30 ms
Radio channels utilisation <= 60 devices
[Us] rated supply voltage 24...240 V AC/DC 50/60 Hz - 10...10 %
Immunity to microbreaks 10 ms
Maximum power consumption in 4 W AC/DC
W
Control circuit frequency 50...60 Hz +/- 10 %
Short-circuit protection 16 A GB2 circuit breaker
Operating position Any position
Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Mounting plate
Electrical connection 1 conductor cable 0.2…4 mm² - AWG 24...AWG 12 - solid - without cable end conforming to IEC
60947-1
2 conductors cable 0.2…1.5 mm² - AWG 24...AWG 16 - solid - without cable end conforming to IEC
60947-1
1 conductor cable 0.2…0.75 mm² - AWG 24...AWG 14 - flexible - with cable end conforming to IEC
60947-1
2 conductors cable 0.2…2.5 mm² - AWG 24...AWG 18 - flexible - with cable end conforming to IEC
60947-1
Tightening torque 0.35…0.4 N.m conforming to EN/IEC 60947-1
0.35…0.40 N.m conforming to EN/IEC 60947-1
Housing material Self-extinguishing plastic
Jul 28, 2023 1
Status LED 1 LED green for power ON
1 LED yellow for communication network
5 LEDs red for function mode
1 LED green and yellow for reception signal
Rated short-duration power 1.5 kV 50 Hz conforming to EN/IEC 60947-5-1
frequency withstand voltage
[Uimp] rated impulse withstand 4 kV
voltage
Surge withstand 1 kV differential mode conforming to IEC 61000-4-5
2 kV common mode conforming to IEC 61000-4-5
Width 122 mm
Height 90 mm
Depth 60 mm
Product weight 0.26 kg
Antenna gain 0 dBi
Integrated connection type Ethernet Modbus TCP/IP RJ45 Modbus TCP network, 10/100 Mbit/s, 2 twisted pairs
Data storage equipment SD card
Topology Devices linked by daisy-chaining or tap junctions
Port Ethernet 10BASE-T/100BASE-T
Maximum cable distance 1000 m
between devices
Environment
Radio agreement ANATEL, type III conforming to ETSI EN 301 489-3
FCC, category 2 conforming to ETSI EN 300 440-1
ICASA
RSS, category 1 conforming to ETSI EN 300 440-1
SRRC
Product certifications C-Tick
CCC
CSA
GOST
UL
CE
Directives 2004/108/EC - electromagnetic compatibility
1999/5/EC - R&TTE directive
2006/95/EC - low voltage directive
Standards ETSI EN 300 328
EN/IEC 61131-2
CSA C22.2 No 14
ETSI EN 300 440-2
UL 508
EN/IEC 60950-1
EN 62311
Ambient air temperature for -40…70 °C
storage
Relative humidity 90 % at -25…55 °C, without condensation conforming to ETSI EN 300 440-1
Operating altitude 0...2000 m
Storage altitude 0…3000 m
Vibration resistance +/- 3.5 mm (f = 5…14 Hz) conforming to IEC 60068-2-6
1 gn (f = 5…150 Hz) on panel mounting conforming to IEC 60068-2-6
2 gn (f = 8…150 Hz) on DIN rail conforming to IEC 60068-2-6
Shock resistance 10 gn (duration = 16 ms) for 6000 shocks conforming to IEC 60068-2-27
IP degree of protection IP20 (casing) conforming to IEC 60529
IP20 (terminals)
Pollution degree 2 conforming to IEC 60664-1
Electromagnetic compatibility 1.2/50 µs shock waves immunity test - test level: 1 kV (differential mode) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 2 kV (common mode) conforming to IEC 61000-4-5
Immunity to microbreaks and voltage drops - test level: 10 ms conforming to IEC 61000-4-11
2
Jul 28, 2023
Dielectric strength 3000 V between input and output AC
4250 V between input and output DC
1500 V between input and ground AC
2150 V between input and ground DC
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.300 cm
Package 1 Width 9.600 cm
Package 1 Length 13.000 cm
Package 1 Weight 310.000 g
Unit Type of Package 2 S02
Number of Units in Package 2 10
Package 2 Height 15.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 3.524 kg
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
China RoHS Regulation China RoHS declaration
RoHS exemption information Yes
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
Contractual warranty
Warranty 18 months
Jul 28, 2023 3
Product datasheet ZBRN1
Dimensions Drawings
Dimensions
For your information existing access point product is now named “Harmony Hub”
4
Jul 28, 2023
Product datasheet ZBRN1
Mounting and Clearance
Harmony Hub on a Mounting Panel
Harmony Hub is installed according to its vertical axis
Jul 28, 2023 5
Product datasheet ZBRN1
Mounting and Clearance
Harmony Hub on DIN Rail Mounting
6
Jul 28, 2023
Product datasheet ZBRN1
Mounting and Clearance
Clearances
Maximum Distance between Transmitter and Harmony Hub in Free Field Unobstructed
(1) Transmitter
(2) Harmony Hub
Maximum Distance between Transmitter and Harmony Hub in a Metal Enclosure with a Relay Antenna
(1) Transmitter
(3) Harmony Hub in a metal enclosure
(4) Relay antenna
Maximum Distance between Transmitter and Harmony Hub in a Metal Enclosure with a Passive Antenna
(1) Transmitter
(2) External antenna
(3) Harmony Hub in a metal enclosure
The range is reduced if the transmitter is placed in a metal enclosure (reduction factor : approx 10%)
Glass window 10...20 %
Plaster wall 30...45 %
Brick wall 60 %
Concrete wall 70...80 %
Metal structure 50...100 %
Jul 28, 2023 7
Product datasheet ZBRN1
Mounting and Clearance
Harmony Hub Clearances
(1) PLC or other devices
(2) Power supply or other devices
8
Jul 28, 2023
Product datasheet ZBRN1
Connections and Schema
Harmony Hub Wiring Diagram
(1) Wire sizes for Power Supply terminals (L/+, N/-)
Jul 28, 2023 9
Product datasheet ZBRN1
Technical Illustration
Dimensions
10
Jul 28, 2023
Product datasheet ZBRN1
Technical Illustration
Wiring Diagram
Recommended replacement(s)
Jul 28, 2023 11