100% found this document useful (1 vote)
549 views6 pages

A. Bitzer 4FES-3Y-40S

This document provides information on selecting a semi-hermetic reciprocating compressor for refrigeration and air conditioning applications. It analyzes a 4FES-3Y compressor for a system with an evaporating temperature of -10°C and a condensing temperature of 45°C. The analysis finds that the 4FES- 3Y-40S compressor with a cooling capacity of 9.1 kW would be suitable. It also provides general information on semi-hermetic reciprocating compressors, operating modes, sound data measurement procedures, and connection positions. The document concludes by providing specifications for a horizontal receiver.

Uploaded by

Điện Ice
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
549 views6 pages

A. Bitzer 4FES-3Y-40S

This document provides information on selecting a semi-hermetic reciprocating compressor for refrigeration and air conditioning applications. It analyzes a 4FES-3Y compressor for a system with an evaporating temperature of -10°C and a condensing temperature of 45°C. The analysis finds that the 4FES- 3Y-40S compressor with a cooling capacity of 9.1 kW would be suitable. It also provides general information on semi-hermetic reciprocating compressors, operating modes, sound data measurement procedures, and connection positions. The document concludes by providing specifications for a horizontal receiver.

Uploaded by

Điện Ice
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

BITZER Software v6.4.3 rev1360 30.10.2015 / All data subject to change.

4/9

Compressor Selection: Semi-hermetic Reciprocating Compressors

Input Values
Compressor model 4FES-3Y
Mode Refrigeration and Air
conditioning
Refrigerant R404A
Reference temperature Dew point temp.
Evaporating SST -10,00 °C
Condensing SDT 45,0 °C
Liq. subc. (in condenser) 0K
Suction gas temperature 20,00 °C
Operating mode Auto
Power supply 400V-3-50Hz
Capacity Control 100%
Useful superheat 100%
Result
Compressor 4FES- 3Y-40S
Capacity steps 100%
Cooling capacity 9,10 kW
Cooling capacity * 9,10 kW
Evaporator capacity 9,10 kW
Power input 4,17 kW
Current (400V) 7,41 A
Voltage range 380-420V
Condenser Capacity 13,28 kW
COP/EER 2,18
COP/EER * 2,18
Mass flow 273 kg/h
Operating mode Standard
Discharge gas temp. w/o cooling 93,6 °C

Tentative Data.
*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)

Application Limits 100%

Legend
additional cooling or suction gas
superheat ≤20K
additional cooling or max. toh
<0°C
M1: motor 1

M2: motor 2
BITZER Software v6.4.3 rev1360 30.10.2015 / All data subject to change. 5/9

Technical Data: 4FES- 3Y


Dimensions and Connections

Technical Data
Technical Data
Displacement (1450 RPM 50Hz) 18,05 m3/h
Displacement (1750 RPM 60Hz) 21,78 m3/h
No. of cylinder x bore x stroke 4 x 41 mm x 39,3 mm
Weight 82 kg
Max. pressure (LP/HP) 19 / 32bar
Connection suction line 22 mm - 7/8''
Connection discharge line 16 mm - 5/8''
Oil type R134a/R407C/R404A/R507A/R407A/R407F BSE32(Standard) / R134a tc>70°C: BSE55 (Option)
Oil type R22 (R12/R502) B5.2 (Option)
Motor data
Motor version 2
Motor voltage (more on request) 380-420V Y-3-50Hz
Max operating current 9.5 A
Starting current (Rotor locked) 44.2 A
Max. Power input 5.3 kW
Extent of delivery (Standard)
Motor protection SE-B1
Enclosure class IP65
Vibration dampers Standard
Oil charge 2,00 dm³
Available Options
Discharge gas temperature sensor Option
Capacity control 100-50% (Option)
Capacity Control - infinite 100-10% (Option)
Additional fan Option
Crankcase heater 0..120 W PTC (Option)
Oil level monitoring OLC-K1 (Option)
Sound measurement
Sound power level (-10°C / 45°C) 68,6 dB(A) @ 50Hz
Sound power level (-35°C / 40°C) 70,5 dB(A) @ 50Hz
Sound pressure level @ 1m (-10°C / 45°C) 60,6 dB(A) @ 50Hz
Sound pressure level @ 1m (-35°C / 40°C) 62,5 dB(A) @ 50Hz
BITZER Software v6.4.3 rev1360 30.10.2015 / All data subject to change. 6/9

Semi-hermetic Reciprocating Compressors


Motor 1 = e.g. 4TES-12 (4TCS-12.2) with 12"HP", primary for air-conditioning (e.g. R22,R407C) and air-conditioning with
R134a at high ambient temperatures
Motor 2 = e.g. 4TES-9 (4TCS-8.2) with 8"HP", universal Motor for medium and low temperature application (e.g. R404A,
R507A, R407A, R407F) and air-conditioning with R134a.
Motor 3 = e.g. 4TES-8, for medium temperature applications and R134a
For more information concerning the application range use the "Limits" button.

Operation modes 4VES-7 (4VCS-6.2) to 6FE-44 (6F-40.2) and 44JE-30 (44J-26.2) to 66FE-88 (66F-80.2) with
R407F/R407A/R22:
CIC = liquid injection with low temperature application, suction gas cooled motor

ASERCOM certified performance data:


The Association of European Refrigeration Component Manufacturers has implemented a procedure of certifying
performance data. The high standard of these certifications is assured by:
-- plausibility tests of the data performed by experts
-- regular measurements at independent institutes
These high efforts result in the fact that only a limited number of compressors can be submitted. Due to this not all
BITZER compresors are certified until now.
Performance data of compressors which fulfil the strict requirements may carry the label "ASERCOM certified". In this
software you will find the label at the respective compressors on the right side below the field "result" or in the print out of
the performance data. All certified compressors and further information are listed on the homepage of ASERCOM
(www.ASERCOM.org).

Condensing capacity:
The condensing capacity can be calculated with or without heat rejection. This option can be set in the menu PROGRAM/
OPTIONS. The heat rejection is constantly 5% of the power consumption. The condensing capacity is to be found in the
line Condensing cap. (with HR) resp. Condensing capacity.

Data for sound emission:


Data based on 50 HZ apllication (IP-units 60Hz) and R404A if not declared.
Sound pressure level: values based on free field area conditions with hemisperhical sound emission in 1 meter distance.

General remarks regarding sound data:


Listed sound data were measured under testing conditions in our laboratory. For this purpose the free-standing test
sample is mounted on a solid foundation plate and the pipework is connected vibration-free to the largest extend
possible. Suction and discharge lines are fixed in a flexible configuration, such that a transmission of vibrations to the
environment can be largely excluded. In real installations considerable differences might be observed, compared to the
measurements in the laboratory. The airborne sound emitted by the compressor can be reflected from surfaces of the
system and this may increase the airborne sound level measured close to the compressor. Vibrations caused by the
compressor are also transferred to the system by the compressor feet and piping depending on the damping ratio of the
fixings. Thus, the vibrations can induce other components to such an extent that these components contribute to an
increase in airborne sound emission. If required, the transfer of vibrations to the system can be minimized by suitable
fixing and damping elements.

Legend of connection positions according to "Dimensions":

1 High pressure connection (HP)


2 Discharge gas temperature sensor (HP)
3 Low pressure connection (LP)
4 CIC system: spray nozzle (LP)
4b CIC sensor
5 Oil fill plug
6 Oil drain (magnetic screw)
7 Oil filter
8 Oil return (oil separator)
9 Oil and gas equalization (parallel operation)
9a Gas equalization (parallel operation)
9b Oil equalization (parallel operation)
10 Crankcase heater
11 Oil pressure connection +
12 Oil pressure connection -
13 Cooling water connection
16 Connection for differential oil pressure switch "Delta-P"
BITZER Software v6.4.3 rev1360 30.10.2015 / All data subject to change. 7/9

Horizontal receivers
Input Values
Common Yes
Auto
Operating point Auto

Operating Points
A
to [°C] -10
tc [°C] 45

Result
Compressor:
Recommendation: F202H
Selection F202H
Recommended operating point: A
Selected operating point: A
Receiver volume 20,00 dm³
max refrigerant charge 19,20 kg
receiver load 92,2 %
Receiver unit mounted compl.
lower fixing rails 327301-04
upper fixing rails 327301-22
upper fixing plate 320366-02
#1: Receiver selection for compact systems without condensing pressure control. Precise calculation only via refrigerant charge (see notes).
BITZER Software v6.4.3 rev1360 30.10.2015 / All data subject to change. 8/9

Technical Data: F202H


Dimensions and Connections

Technical Data
Technical Data
Weight 20,5 kg
Total width 664 mm
Total depth 276 mm
Total height 287mm
Receiver volume refrigerant 20,0 l
Max. refrigerant charge 90% at 20°C 20°C
R22 21,8 kg
R134a 22,1 kg
R407C 20,9 kg
R404A/R507A 19,2 kg
Max. pressure 33 bar
Max. Operating Temperature 120°C
Connection inlet KL 22mm - 7/8''
Connection thread/ -flange 1 1/4'' - 12 UNF
Connection outlet FL 22mm - 7/8''
Connection thread/ -flange 1 1/4'' - 12 UNF
Gauge 7/16'' 20UNF
Connection for pressure relief valve 1 1/4''-12UNF
Adapter for pressure relief valve Option
Minimum level control Option
Maximum level control Option
*According PED 97/23/EC Standard
Special Approvals (on request) Option
BITZER Software v6.4.3 rev1360 30.10.2015 / All data subject to change. 9/9

Liquid receiver
Selection of the receivers:

1) "Approx. according to cooling capacity":

The receiver volume is determined by the design of the unit, the operating mode and the function of the receiver
(receiving the complete refrigerant charge in the receiver or only compensating capacity variations). When selected via
cooling capacity, an approximate selection of the receiver is obtained.
Receivers in systems with long pipelines, winter control or in very compact systems should be selected according to
method 2).

2) "According to refrigerant charge in the receiver":

The calculation is made on the basis of the specified refrigerant charge. The receiver volume is determined at 20°C and
at a maximum filling charge of 95% of the possible receiver content.

Compressor units equipped with receiver

The BITZER range of products comprises compressor units with horizontal receivers. In the output window of the
accessories these units, which are included in the standard delivery, are marked with “mounted” in the compressor unit
line. Units that can be mounted, but are not included in the Bitzer delivery program, are marked with “single parts”.
Units in which the compressor does not fit onto the receiver are marked with "--".

Legend of connection positions according to "Dimensions":

You might also like