Event Center - Mechanical
Event Center - Mechanical
GENERAL NOTES
LEGEND
OU-001
90,000 BTU/H AC Condensate to Grave Pit. HVAC NOTES
AC Condensate to Grave Pit. Power Input = 9500 W OU-002
see detail Height= 50FFL 90,000 BTU/H
see detail
1. APPLICABLE CODES INCLUDE, BUT ARE NOT LIMITED TO, THE LATEST
Power Input = 9500 W OU-004
Height= 50FFL OU-003 90,000 BTU/H
ADOPTED VERSION OF:
AC Condensate to Grave Pit. 90,000 BTU/H Power Input = 9500 W
Power Input = 9500 W Height= 50FFL • 2006 IBC INTERNATIONAL BUILDING CODE
see detail TERRACE 03
01.027 Height= 50FFL • 2006 IMC INTERNATIONAL MECHANICAL CODE
Condensate Pipe sleeve in
foundation slab
Condensate Pipe sleeve in
foundation slab EF-001 • 2002 NFPA 90A AIR CONDITIONING AND VENTILATION CODE
80m3/h EF-002 • 2006 NFPA 90B AIR CONDITIONING AND VENTILATION CODE
Power Input = 22 W 1000 m3/h 100Pa • 1995 SMACNA HVAC DUCT CONSTRUCTION MATERIALS
Height= 3000FFL Power Input = 180 W
Condensate Pipe sleeve in Height= 3200FFL 2. HVAC SYSTEM SHALL BE INSTALLED COMPLETE WITH ALL WORK,
foundation slab Condensate Pipe sleeve in
foundation slab
MATERIALS, AND EQUIPMENT CUSTOMARILY CONSIDERED PART OF SUCH WORK FOR
1 FULLY OPERATIONAL, COMPLETE AND CODE COMPLIANT SYSTEMS. PROVIDE AND INSTALL
ALL EQUIPMENT, DUCTING, DIFFUSERS, LOUVERS, GRILLES, ETC. AS REQUIRED.
150
IU-004
90,000 BTU/H FWC 03
12. ALL DUCT WORK DIMENSIONS SHOWN ARE INSIDE CLEAR. FABRICATE DUCT SO TO
MAINTAIN CLEARANCE SPECIFIED. INTERNALLY LINED DUCTS SHALL BE OVERSIZED SO TO
ACCOMMODATE THICKNESS OF INSULATION.
STORE 02
13. SUPPLY, RETURN, AND OUTSIDE AIR DUCTWORK SHALL BE GALVANIZED SHEET METAL
01.024
WITH INSULATION AS NOTED ON THE PLANS AND MATERIALS SCHEDULES.
- - 14. LOCATE ALL CEILING MOUNTED REGISTERS, GRILLES, DIFFUSERS, FANS, ETC. PER
REFLECTED CEILING PLAN. COORDINATE WITH ELECTRICAL AND FINISH CEILING
INSTALLATION.
MAIN HALL - 776 SEATS
4
01.022
16. TURNS IN DUCTWORK SHALL HAVE 1.5 MINIMUM RADIUS RATIO WHENEVER POSSIBLE,
OTHERWISE TURNING VANES SHALL BE INSTALLED WITHIN DUCT.
IU-010 17. EVERY SUPPLY DIFFUSER SHALL BE INDIVIDUALLY CONTROLLED BY A DAMPER PLACED
24,000 BTU/H ENTRANCE
Height= 2400FFL
01.021
19. ALL OUTDOOR AIR INTAKE LOUVERS SHALL BE 3.5m MINIMUM DISTANCE AWAY FROM
SEWER OR COMBUSTION EXHAUST VENTS.
OU-010
24,000 BTU/H 20. WALL MOUNTED EXHAUST FANS SHALL BE FITTED WITH TIME DELAY SWITCH AND
Power Input = 2300 W CONNECTED TO THE LIGHT SWITCH
Height= 2000FFL
20. WALL MOUNTED THERMOSTATS SHALL BE USED FOR ALL TOWER TYPE INDOOR UNITS.
WALL MOUNTED REMOTE CONTROLLERS SHALL BE INSTALLED FOR USE BY WALL
5 MOUNTED AC UNITS.
STORE 01
21. ALL AC UNITS SHALL BE INVERTER CONTROLS. LG UNITS WAS USED FOR THE DESIGN,
01.023
CONTRACTOR CAN SELECT AN EQUAL BRAND WHICH SHALL BE APPROVED BY ENGINEER
BEFORE PROCUREMENT AND INSTALLATION
Refrigerant Pipes in ceiling
22. EQUIPMENT SIZES ARE AS SHOWN IN THE LAYOUT. AC EQUIPMENTS ARE SIZED @ 24OC
DB/50% RH INDOOR CONDITION; 35OC/26OC OUTDOOR DB/WB
23. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE STATED. ALL ELEVATIONS ARE TO
FINISHED FLOOR LEVELS
EF-003
1000 m3/h 100Pa
150ø Power Input = 180 W
3355 FFL 250ø
IU-005 IU-006 Height= 3200FFL
IU-007 IU-008 3355 FFL
90,000 BTU/H 90,000 BTU/H Exhaust Duct
Power Input = 9500 W Power Input = 9500 W 90,000 BTU/H 90,000 BTU/H
Height= 50FFL Height= 50FFL Power Input = 9500 W Power Input = 9500 W
Height= 50FFL Height= 50FFL Store Store Store Store
Store 01.016 01.017 01.019 01.020
01.015
Pipes to be covered
with trunking Color as
specified by architect
Pipes to be covered
with trunking Color as
specified by architect
150
TERRACE + STAIRS
01.025
8
Client :
CATHOLIC DIOCESE OF OSOGBO
AC Condensate to Grave Pit. AC Condensate to Grave Pit. AC Condensate to Grave Pit. AC Condensate to Grave Pit. AC Condensate to Grave Pit.
see detail see detail see detail see detail see detail
Drawn by AN
M-001
Designed by AF
GENERAL NOTES
OU-103 OU-105 OU-115 OU-117
24,000 BTU/H 24,000 BTU/H 24,000 BTU/H 24,000 BTU/H
Power Input = 2300 W Power Input = 2300 W Power Input = 2300 W Power Input = 2300 W
Height= 600FFL Height= 600FFL Height= 600FFL Height= 600FFL
LEGEND
150
1 1. APPLICABLE CODES INCLUDE, BUT ARE NOT LIMITED TO, THE LATEST
Condensate Pipe Condensate Pipe Condensate Pipe Condensate Pipe Condensate Pipe
below floor slab below floor slab below floor slab below floor slab below floor slab Store ADOPTED VERSION OF:
EF-004 01.112
A' 4. PLAN SCALES NOTED, IF ANY, ARE ONLY APPLICABLE TO PLANS PLOTTED AT FULL SIZE.
CONTRACTOR IS CAUTIONED WHEN USING PLANS PLOTTED AT REDUCED SIZES.
100ø
Refrigerant Pipe in ceiling
3388 FFL
REGARDLESS, CONTRACTOR SHALL NOT SCALE PLANS, BUT SHALL REFER TO NOTED
LOBBY
01.106
DIMENSIONS. FOR DIMENSIONS NOT NOTED, CONTRACTOR SHALL REFER TO ACTUAL
FIELD CONDITIONS AND/OR DIMENSIONED ARCHITECTURAL, STRUCTURAL, OR CIVIL
PLANS.
CONFERENCE HALL
01.119
12. ALL DUCT WORK DIMENSIONS SHOWN ARE INSIDE CLEAR. FABRICATE DUCT SO TO
MAINTAIN CLEARANCE SPECIFIED. INTERNALLY LINED DUCTS SHALL BE OVERSIZED SO TO
ACCOMMODATE THICKNESS OF INSULATION.
IU-123
24,000 BTU/H 13. SUPPLY, RETURN, AND OUTSIDE AIR DUCTWORK SHALL BE GALVANIZED SHEET METAL
Power Input = 2300 W OU-123
IU-107 IU-109 IU-111 Condensate Pipe WITH INSULATION AS NOTED ON THE PLANS AND MATERIALS SCHEDULES.
24,000 BTU/H 24,000 BTU/H 24,000 BTU/H below floor slab RECEPTION 02
01.104 Height= 2750FFL 24,000 BTU/H
Power Input = 2300 W Power Input = 2300 W Power Input = 2300 W Power Input = 2300 W
Height= 2750FFL Height= 2750FFL Height= 2750FFL Height= 1200FFL 14. LOCATE ALL CEILING MOUNTED REGISTERS, GRILLES, DIFFUSERS, FANS, ETC. PER
IU-116 REFLECTED CEILING PLAN. COORDINATE WITH ELECTRICAL AND FINISH CEILING
24,000 BTU/H
STORE
01.121 Power Input = 2300 W INSTALLATION.
Refrigerant Pipe in ceiling Refrigerant Pipe in ceiling
Height= 2750FFL
Refrigerant Pipe in ceiling
Condensate Pipe below floor slab
15. ALL TRANSVERSE JOINTS TO BE SEALED WITH APPROVED DUCTSEALER.
16. TURNS IN DUCTWORK SHALL HAVE 1.5 MINIMUM RADIUS RATIO WHENEVER POSSIBLE,
OTHERWISE TURNING VANES SHALL BE INSTALLED WITHIN DUCT.
20. WALL MOUNTED EXHAUST FANS SHALL BE FITTED WITH TIME DELAY SWITCH AND
Refrigerant Pipe in ceiling CONNECTED TO THE LIGHT SWITCH
Refrigerant Pipe in ceiling Refrigerant Pipe in ceiling
20. WALL MOUNTED THERMOSTATS SHALL BE USED FOR ALL TOWER TYPE INDOOR UNITS.
WALL MOUNTED REMOTE CONTROLLERS SHALL BE INSTALLED FOR USE BY WALL
Condensate Pipe below floor slab
MOUNTED AC UNITS.
6 21. ALL AC UNITS SHALL BE INVERTER CONTROLS. LG UNITS WAS USED FOR THE DESIGN,
OFFICE 02 OFFICE 01 CONTRACTOR CAN SELECT AN EQUAL BRAND WHICH SHALL BE APPROVED BY ENGINEER
BEFORE PROCUREMENT AND INSTALLATION
01.118 01.117
22. EQUIPMENT SIZES ARE AS SHOWN IN THE LAYOUT. AC EQUIPMENTS ARE SIZED @ 24OC
DB/50% RH INDOOR CONDITION; 35OC/26OC OUTDOOR DB/WB
DN32
DN32
23. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE STATED. ALL ELEVATIONS ARE TO
IU-108 IU-110 IU-119 IU-120 IU-121 IU-121 TECHNICAL ROOM
FINISHED FLOOR LEVELS
24,000 BTU/H 24,000 BTU/H 24,000 BTU/H 24,000 BTU/H 24,000 BTU/H 24,000 BTU/H 01.105
Condensate Pipe below floor slab Condensate Pipe below floor slab Condensate Pipe below floor slab Condensate Pipe below floor slab
IU-122
DN32 24,000 BTU/H
STAIRS
Power Input = 2300 W
7
01.122
Height= 2750FFL
TERRACE 03
01.103
OU-108
24,000 BTU/H
Power Input = 2300 W OU-121
Height= 600FFL OU-109 24,000 BTU/H
24,000 BTU/H OU-111 OU-112 OU-119 OU-120 Power Input = 2300 W OU-122
Power Input = 2300 W 24,000 BTU/H 24,000 BTU/H 24,000 BTU/H 24,000 BTU/H Height= 600FFL 24,000 BTU/H
Height= 600FFL Power Input = 2300 W Power Input = 2300 W OU-116 Power Input = 2300 W Power Input = 2300 W Power Input = 2300 W
Height= 600FFL Height= 600FFL 24,000 BTU/H Height= 600FFL Height= 600FFL Height= 600FFL
Power Input = 2300 W
Height= 600FFL
8
OU-107
24,000 BTU/H OU-118
OU-110 24,000 BTU/H
Power Input = 2300 W
24,000 BTU/H Power Input = 2300 W
Height= 600FFL
Power Input = 2300 W Height= 600FFL
Height= 600FFL
Client :
CATHOLIC DIOCESE OF OSOGBO